Jawa 9&10 Coal Fired Steam Power Plant_Design Review Comment Sheet
From : EPC Consortium
To : PLN Comment Resolution Sheet Document No : J910‐YU02‐P0AB‐145639_CS
Cc : IRT
Dwg Title : 500kV Switchyard ‐ 400/230 VAC Single Line Diagram
Dwg No : J910‐YU02‐P0AB‐145639
DRM (date) or
No. Rev. Comments Resolution/Reply Status
page
(PLN Comment 29‐04‐2021):
Meeting Resolution on 30‐04‐2021 DRM ke‐5 :
1. pasitikan pembebanan redundant (50:50)
'1. EPC telah menjelaskan interlock breaker dengan tabel yang ada di
2. Beri penjelasan terkait normal operation Couple MCB
drawing untuk 4 cases.
3. Apakah ada interlock operation MCB Couple dengan MCB Incoming serta Incoming generator 2. Diberikan indikasi interlocking otomatis.
DRM ke‐5 4. capasitas MCB agar di sesuaikan dengan kapasitas generator maupun trafo distribusi
1 A 3. Voltage limiter pada incoming agar diindikasikan. closed
(30‐04‐2021) 5. beban common dan essensial agar dipisahkan panel 4. Common dan Essential Load akan dipisahkan panel.
5. MCCB incoming akan disesuaikan dengan kapasitas generator
maupun trafo distribusi.
6. Bus couple breaker rating agar disesuaikan dengan busbar rating.
‐ Terkait metering di panel untuk direvisi menjadi 0.2 dan spesifikasi metering akan disesuaikan dengan surat
DRM ke‐6
2 A edaran PLN No. 0330/DIS.00.03/010703/2019 (Rekomendasi Spesifikasi Teknis Metering Transaksi Jawa‐Bali). Telah di akomodir dalam revisi. closed
(06‐05‐2021)
‐ Ditambahkan logic & tripping logic pengoperasian Open/Close incoming breaker dan starting genset.
3 0 page 1 Sesuai CRS breaker couple sama dengan kapasitas busbar Telah di akomodir dalam revisi. open
Sesuaikan kapasitas busbar dengan approval sebelumnya (800A). Kapasitas busbar menggunakan 800A namun MCCB cukup
4 1 page 1 open
Sesuaikan MCCB section dengan kapasitas busbar. dengan 400A sesuai dengan beban dari Panel dan sistem.
Jawa 9&10 Coal Fired Steam Power Plant_Design Review
From : HK Document Controller
To : IRT Mr. Salam Syah Comment Sheet Document No : J910‐YU02‐P0AB‐145639_CS
cc : TEPSCO Mr. Kubota Hiroshi
Dwg Title : 500kV Switchyard ‐ 400V AC Single Line Diagram
Dwg No : J910‐YU02‐P0AB‐145639
Purpose : FC
Review Category
A = Approved
B = Approved with comments, forward final document B
C = Not Approved
I = Accepted for reference (For information only)
,!
,!
)25&216758&7,21
,!
Ϯϭ Ϯϭ Ϯϭ Ϯϭ Ϯϭ Ϯϭ Ϯϭ Ϯϭ Ϯϭ Ϯϭ Ϯϭ Ϯϭ Ϯϭ Ϯϭ
ϮϮ ϮϮ ϮϮ ϮϮ ϮϮ ϮϮ ϮϮ ϮϮ ϮϮ ϮϮ ϮϮ ϮϮ ϮϮ ϮϮ ϮϮ ϮϮ ϮϮ
-$:$ &2$/),5('67($032:(53/$17
$[PP
,!
)25&216758&7,21
-$:$ &2$/),5('67($032:(53/$17
$[PP
Jawa 9&10 Coal Fired Steam Power Plant_Design Review Comment Sheet
From : EPC Consortium
To : PLN Comment Resolution Sheet Document No : J910‐YU02‐P0AB‐145639_CS
Cc : IRT
Dwg Title : 500kV Switchyard ‐ 400/230 VAC Single Line Diagram
Dwg No : J910‐YU02‐P0AB‐145639
DRM (date) or
No. Rev. Comments Resolution/Reply Status
page
(PLN Comment 29‐04‐2021):
Meeting Resolution on 30‐04‐2021 DRM ke‐5 :
1. pasitikan pembebanan redundant (50:50)
'1. EPC telah menjelaskan interlock breaker dengan tabel yang ada di
2. Beri penjelasan terkait normal operation Couple MCB
drawing untuk 4 cases.
3. Apakah ada interlock operation MCB Couple dengan MCB Incoming serta Incoming generator 2. Diberikan indikasi interlocking otomatis.
DRM ke‐5 4. capasitas MCB agar di sesuaikan dengan kapasitas generator maupun trafo distribusi
1 A 3. Voltage limiter pada incoming agar diindikasikan. closed
(30‐04‐2021) 5. beban common dan essensial agar dipisahkan panel 4. Common dan Essential Load akan dipisahkan panel.
5. MCCB incoming akan disesuaikan dengan kapasitas generator
maupun trafo distribusi.
6. Bus couple breaker rating agar disesuaikan dengan busbar rating.
‐ Terkait metering di panel untuk direvisi menjadi 0.2 dan spesifikasi metering akan disesuaikan dengan surat
DRM ke‐6
2 A edaran PLN No. 0330/DIS.00.03/010703/2019 (Rekomendasi Spesifikasi Teknis Metering Transaksi Jawa‐Bali). Telah di akomodir dalam revisi. closed
(06‐05‐2021)
‐ Ditambahkan logic & tripping logic pengoperasian Open/Close incoming breaker dan starting genset.
3 0 page 1 Sesuai CRS breaker couple sama dengan kapasitas busbar Telah di akomodir dalam revisi (400A). open
Sesuaikan kapasitas busbar dengan approval sebelumnya (800A). Kapasitas busbar menggunakan 800A namun MCCB cukup
4 1 page 1
Sesuaikan MCCB section dengan kapasitas busbar. dengan 400A sesuai dengan beban dari Panel dan sistem. Jika
kapasitas breaker menjadi 800A maka akan menjadi ACB open
sehingga tidak sesuai dengan total load yang hanya kurang dari
250A. 800A busbar ini juga mengacu type test Panel dari
manufacture.
Jawa 9&10 Coal Fired Steam Power Plant_Design Review Comment
1 of 1
Jawa 9&10 Coal Fired Steam Power Plant_Design Review
From : HK Document Controller
To : IRT Mr. Salam Syah Comment Sheet Document No : J910‐YU02‐P0AB‐145639_CS
cc : TEPSCO Mr. Kubota Hiroshi
Dwg Title : 500kV Switchyard ‐ 400V AC Single Line Diagram
Dwg No : J910‐YU02‐P0AB‐145639
Purpose : FC
Review Category
A = Approved
B = Approved with comments, forward final document B
C = Not Approved
I = Accepted for reference (For information only)