FASA
dengan Fluksi Bocor
Persamaan Dasar:
Jika diketahui
a.
|Z1|
RIIL
Imajiner
Z1
Z1 R12 X 12
Z0
1
Tan
X1
R
1
Z1 Z0
c. Pembagian Sudut
1
Z1
Z 1 1 2
2
d. Perkalian Sudut
Z 1 1 * 2 Z 1 1 2
Persamaan Dasar:
a. Arus (I1) pd sisi Primer;
P1 V1 I1 Cos atau P1 V1 I1 pf
P1
P1
I1
atau I1
V1 Cos
V1 pf
pf Cos 1( )
E2
Z 2L
I 2 E2 Z 2 L
Contoh Soal
Sebuah Trafo satu fasa mensuplly beban dg
rincian; tegangan beban (V 2) = 380 Volt dg
faktor daya (pf)= 0,75. R1 =1,2 Ohm, X1 =
0,6 Ohm.
Trafo tsb memp. data sbb:
* Pada sisi Primer: R1 = 0,06 Ohm, X1 =
0,004 Ohm dan N1= 500 lilitan
* Pada sisi skunder: R2 =0,04 Ohm, X2 =
0,003 Ohm dan N2= 6 lilitan.
* Rugi Flusi bocor: PCU = 2 Watt; PXL = 0,5
Watt
Hitung :
1. Daya beban (P2)
2. Arus skunder (I2)
3. Tegangan GGm Skunder (E2)
4. Tegangan GGm Primer (E1)
5. Daya Trafo (P1)
6. Efisiensi trafo ( )
Langkah 1
Arus (IL) pada ZL
V2 = Cos-1(pf) = Cos-1(0,75) =
41,410
Z L 1,2 2 0 ,6 2 1,3416 Ohm
0 ,6
0
Z L Tan 1
26,57
1,2
IZL
Z L
V2
380
283,2353 Amp
Z L 1,3416
41,41 - 26,57 0 14,850
Langkah 2
Tegangan GGM (E2) pada sisi skunder
Z 2 0,04 2 0 ,0032 0,0401 Ohm
1 0 ,003
0
Z 2 Tan
4 ,29
0 ,02
Langkah 3
Tranformasi Teg. E2 ke Teg. E1 dan Arus I2 ke I2'
melalui lilitan
|E1| = (N1/N2) * |E2|
|E1| = (500/6) * 390,5379 = 32.544,8248 Volt
qE1 =40,760
E1 = 32.544,8248Cos(40,760) + j32.544,8248Sin(40,760)
E1 = 24.659,8475 + j 21.238,1153 Volt
I2' = (N2/N1)*I2
|I2'| = (6/500) * 283,2353 = 3,40 Amp
qI2' = 14,850
I2' = 3,4 * Cos(14,85) + j3,4 * Sin(14,85)
= 3,2855 + j0,8703 Amp
Langkah 4
Fluksi Bocor
ICU = Pcu / |E1| = (2) / 32.544,8248
|ICU| = 61 10-6 Amp
qCU = 0 - 40,760 = - 40,760
ICU = 61 10-6 Cos(-40,76) + 61 10-6 Sin(-40,76)
ICU = 0,000047 - j0,00004
IM = PM / |E1|
|IM| = (0,5) / 32.544,8248 = 15 10-6 Amp
qXM = 90 - 40,760 = 49,240
IM=15 10-6 * Cos(49,24) + 15 10-6 * Sin(49,24)
IM = 0,00001 + j0,000012 Ohm
I0 = ICU + IM
I0 = 0,000047 - j0,00004 + 0,00001 + j0,000012
I0 = 0,000057 - j2,8 10-5 Amp
Langkah 5
Arus pada sisi Primer (I1)
I1 = I2' + I0
I1 = 3,2855 + j0,8703 + 0,000057 - j2,8 10-5
I1 = 3,2855 + j0,8703 + 0,000057 - j2,8 10-5
|I1| = 3,2856 + j0,8703 Amp
I1 3 ,2856 2 0 ,8703 2
I1 3 ,3989 Volt
1 0 ,8703
0
I1 tan
14
,
84
3 ,2856
Langkah 6
Tegangan Sumber (V1)
|V1| = |I1|* |Z1| + |E1|
Z1 0 ,06 2 0 ,004 2 0 ,0601
0 ,004
0
Z 1 tan 1
3 ,82
0 ,06
V1 24.660,0412 2+ 21.238,1806 2
V1 32.545,0142 Volt
1 21.238,1806
0
V1 tan
40 ,74
24.660,0412
Perhitungan
Daya Trafo
P1 = I 1 * V 1
P1 = 110.615,9892 VA
P1 = 55,570
P1 = I1 * V1 Cos(P1)
P1 =110.615,9892 Cos(55,570)
P1 = 62.583,8355 Watt
Efisiensi
Trafo ( )
PZ L
x100%
P1
59.833,8276
x100%
62.583,8355
95 ,61%