JOBSHEET BAB 12

TES SPESIFIKASI PLC S7-1200


Yang diampu oleh Ibu Mila Fauziyah, ST., MT

Disusun oleh :

SEYRA AMANDA.P

1941170037

3A D4 – Teknik Elektronika

PROGRAM STUDI D-IV TEKNIK ELEKTRONIKA


JURUSAN TEKNIK ELEKTRO
POLITEKNIK NEGERI MALANG
2022
Jobsheet Bab 12.
1. Lengkapi tabel di bawah ini

Tabel 12.1 Tes Spesifikasi PLC S7-1200


No Item Deskripsi
CPU 1214C
1 Tipe CPU CPU 1214C DC/DC/DC
DC/DC/RLY
2 User Memory Work 100 kbyte 50 kbyte
Load 4 Mbyte 2 Mbyte
Retentive 14 kbyte 2048 byte
Local on-board (Input:14), (Input:14), (output:10)
4 Digital
I/O (output:10)
Analog (Input:2), (Input:2), (output:0)
(output:0)
Process image 1 kbyte 1 kbyte
5 Inputs (I)
size
Outputs (Q) 1 kbyte 1 kbyte
6 Bit Memory (M) 8192 bytes 8192 bytes
Communication ➢ PROFIBUS ➢ PROFIBUS
7
Module ➢ PROFINET ➢ PROFINET
8 PROFINET YES. Transmission rate, max. YES. PROFINET IO
100 Controller
Mbit/s
Ethernet port ethernet communicate with Ethernet Port QCPU
9 communication HMI (WinCC Adv V14)
port
Real math 2.3 μs/instruction 2.3 μs/instruction
10
execution speed
Boolean 0.08 μs/instruction 0.08 μs/instruction
11
execution speed
Jumlah 3 CMs max 3 CMs max
maksimum
12
komunikasi
modul yang
terpasang

2. Hasil Eksperimen
(Jabarkan hasil eksperimen yang telah dilakukan)
➢ Aplikasi yang digunakan pada eksperimen kali ini menggunakan TIA
Portal. Dengan menggunakan TIA Portal kita dapat membuat program
yang diinginkan untuk dijalankan pada PLC. Kita dapat membuat program
kemudian didownload ke PLC sesuai tipe nya. Apabila konfigurasi
berhasil maka indikator pada CPU akan menyala warna hijau,dan apabila
terjadi error maka indikator menyala warna orange, indicator led akan
berkedip apabila program sedang diunduh ke dalam cpu.

3. Post-test Praktikum
Jawab pertanyaan di bawah ini dengan lengkap

a. Jelaskan I/O yang disediakan oleh CPU 1214C. Apa yang


dimaksuddengan DC/DC/RLY?
➢ I/O yang disediakan oleh CPU 1214C yaitu 14 Digital input dan 10
digital output. Sedangkan untuk (Input analog:2) dan (output
analog:0) atau
CPU 1214C menyediakan Input digital dan analog, sedangkan
untuk output berupa digital. Pada CPU 1214C DC/DC/DC, terdapat
14 digital inputs dan 2 analog inputs, juga 10 digital outputs.
Sedangkan pada CPU 1214C DC/DC/RLY terdapat 14 konektor 24
VDC digital input, 2 analog inputs, 0 to 10V, dan Removable user
wiring connector (Relay Outputs) 10 konecktor 24 VDC digital
output 4 Pulse output.
➢ DC/DC/RLY maksudnya menggunakan Sumber DC untuk power
supplyPLC, dengan Input DC 24 V dan Keluaran PLC bertipe
Relay.

b. Apakah on-board CPU1214C menyediakan modul komunikasi? Sebutkan.


➢ Ya, on-board CPU1214C menyediakan modul komunikasi yaitu
modulkomunikasi PROFIBUS dan modul komunikasi
PROFINET.atau
mengindikasikan bahwa PLC tersebut memerlukan power supply
sebesar 24VDC, lalu sinyal input berupa DC 24V, dan tipe
output berupa relay.

c. Sebutkan alamat input/output digital dan analog yang disediakan oleh


CPU 1214C.
➢ Input = dimulai dengan I0.00.
➢ Output = dimulai dengan Q100.00.
➢ mengindikasikan bahwa PLC tersebut memerlukan power supply sebesar
24VDC, lalu sinyal input berupa DC 24V, dan tipe output berupa relay.

d. Saat melakukan konfigurasi menggunakan TIA Portal, sebutkan kelebihan


dan kekurangan dari software baik program maupun simulator yang
disediakan.
➢ Kelebihan
• Efisiensi yang tinggi dan penggunaan yang mudah dengan
design yang di khususkan untuk para engineering pemula
maupun profesional tia portal di harapkan dapat
memudahkan pekerjaan para engineer.
• Salah satu kelebihan TIA PORTAL yakni bisa terkoneksi
ke InTouch, dan semuanya tanpa PLC secara fisik sehingga
dengan hanya melakukan konfigurasi secara software maka
kita dapat melakukan simulasi secara langsung akan
program yang sudah kita desain.
➢ Kekurangan
• Softwarenya cukup berat untukdijalankan (karena
memiliki ukuran yang besar).
• Jika ada perbedaan versi software pada PLC dengan di
Laptop maka programnya tidak bisa di upload.

e. Apa tanda atau indicator CPU error? Sebutkan apa saja penyebab
CPUerror.
➢ Tanda CPU Error adalah LED Indicator menyala merah, hal tersebut
dapat disebabkan oleh konfigurasi PLC yang masih salah dan
kesalahan dalam pemograman.atau mengindikasikan bahwa PLC
tersebut memerlukan power supply sebesar 24VDC, lalu sinyal
input berupa DC 24V, dan tipe output berupa relay.

4. Screenshoot hasil pindai augmented reality


(lampirkan screenshoot hasil 3D View pada halaman Assemblr)
6ES7214-1HE30-0XB0 Page 1

Product data sheet 6ES7214-1HE30-0XB0

SIMATIC S7-1200, CPU 1214C,


COMPACT CPU, DC/DC/RELAY,
ONBOARD I/O: 14 DI 24V DC;
10 DO RELAY 2A;
2 AI 0 - 10V DC,
POWER SUPPLY: AC 20.4 - 28.8 V DC,
PROGRAM/DATA MEMORY: 50 KB

General information
Engineering with
Programming package STEP 7 V10.5 or higher
Display
integrated No
Supply voltage
24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Load voltage L+
Rated value (DC) 24 V
permissible range, lower limit (DC) 5 V
permissible range, upper limit (DC) 250 V
Input current
Current consumption (rated value) 500 mA ; Typical

Date: subject to modifications


03/21/2012 © Copyright Siemens AG 2012
6ES7214-1HE30-0XB0 Page 2

Current consumption, max. 1.2 A ; 24 V DC


Inrush current, max. 12 A ; at 28.8 V DC
Encoder supply
24 V encoder supply
24 V Permissible range: 20.4 to 28.8 V
Output current
Current output to backplane bus (DC 5 V), max. 1600 mA ; Max. 5 V DC for SM and CM
Power losses
Power loss, typ. 12 W
Memory
Usable memory for user data 50 kbyte
Work memory
integrated 50 kbyte
expandable No
Load memory
integrated 2 Mbyte
expandable, max. 24 Mbyte ; with SIMATIC memory card
Backup
present Yes ; Entire project maintenance-free in the integral
EEPROM
without battery Yes
CPU processing times
for bit operations, min. 0.1 µs ; / Operation
for word operations, min. 12 µs ; / Operation
for floating point arithmetic, min. 18 µs ; / Operation
CPU-blocks
Number of blocks (total) DBs, FCs, FBs, counters and timers. The maximum
number of addressable blocks ranges from 1 to 65535.
There is no restriction, the entire working memory can
be used
OB
Number, max. Limited only by RAM for code
Data areas and their retentivity
retentive data area in total (incl. times, counters, 2048 byte
flags), max.

Date: subject to modifications


03/21/2012 © Copyright Siemens AG 2012
6ES7214-1HE30-0XB0 Page 3

Flag
Number, max. 8 kbyte ; Size of bit memory address area
Address area
I/O address area
I/O address area, overall 1024 bytes for inputs / 1024 bytes for outputs
Inputs 1024 byte
Outputs 1024 byte
Process image
Inputs, adjustable 1 kbyte
Outputs, adjustable 1 kbyte
Hardware configuration
Number of modules per system, max. 3 comm. modules, 1 signal board, 8 signal modules
Time of day
Clock
Hardware clock (real-time clock) Yes
Deviation per day, max. +/- 60 s/month at 25 °C
Backup time 240 h ; Typical
Digital inputs
Number/binary inputs 14 ; integrated
of which, inputs usable for technological functions 6 ; HSC (High Speed Counting)
integrated channels (DI) 14
m/p-reading Yes
Input voltage
Rated value, DC 24 V
for signal "0" 5 V DC at 1 mA
for signal "1" 15 V DC at 2.5 mA
Input current
for signal "1", typ. 1 mA
Input delay (for rated value of input voltage)
for standard inputs
Parameterizable 0.2, 0.4, 0.8, 1.6, 3.2, 6.4, and 12.8 ms, selectable in
groups of four
at "0" to "1", min. 0.2 ms
at "0" to "1", max. 12.8 ms

Date: subject to modifications


03/21/2012 © Copyright Siemens AG 2012
6ES7214-1HE30-0XB0 Page 4

for interrupt inputs


Parameterizable Yes
for counter/technological functions
Parameterizable Single phase : 3 at 100 kHz & 3 at 30 kHz, differential:
3 at 80 kHz & 3 at 30 kHz
Cable length
Cable length, shielded, max. 500 m ; 50 m for technological functions
Cable length unshielded, max. 300 m ; For technological functions: No
Digital outputs
Number/binary outputs 10 ; Relay
integrated channels (DO) 10
Functionality/short-circuit strength No ; to be provided externally
Switching capacity of the outputs
with resistive load, max. 2 A
on lamp load, max. 30 W DC; 200 W AC
Output delay with resistive load
0 to "1", max. 10 ms ; max.
1 to "0", max. 10 ms ; max.
Switching frequency
of the pulse outputs, with resistive load, max. 1 Hz
Relay outputs
Number of relay outputs 10
Number of operating cycles, max. mechanically 10 million, at rated load voltage 100,000
Cable length
Cable length, shielded, max. 500 m
Cable length unshielded, max. 150 m
Analog inputs
Integrated channels (AI) 2 ; 0 to 10 V
Number of analog inputs 2
Input ranges
Voltage Yes
Input ranges (rated values), voltages
0 to +10 V Yes
Input resistance (0 to 10 V) ≥100k ohms

Date: subject to modifications


03/21/2012 © Copyright Siemens AG 2012
6ES7214-1HE30-0XB0 Page 5

Cable length
Cable length, shielded, max. 100 m ; twisted and shielded
Analog outputs
Cable length
Cable length, shielded, max. 100 m ; Shielded, twisted wire pair
Analog value creation
Integrations and conversion time/ resolution per channel
Resolution with overrange (bit including sign), 10 bit
max.
Integration time, parameterizable Yes
Conversion time (per channel) 625 µs
Encoder
Connectable encoders
2-wire sensor Yes
1st interface
Type of interface PROFINET
Physics Ethernet
Isolated Yes
Automatic detection of transmission speed Yes
Autonegotiation Yes
Autocrossing Yes
Functionality
PROFINET IO Controller Yes
Communication functions
S7 communication
supported Yes
as server Yes
Open IE communication
TCP/IP Yes
ISO-on-TCP (RFC1006) Yes
Web server
supported Yes
User-defined websites Yes
Number of connections

Date: subject to modifications


03/21/2012 © Copyright Siemens AG 2012
6ES7214-1HE30-0XB0 Page 6

overall 15 ; dynamically
Test commissioning functions
Status/control
Status/control variable Yes
Variables Inputs/outputs, memory bits, DBs, distributed I/Os,
timers, counters
Forcing
Forcing Yes
Integrated Functions
Number of counters 6
Counter frequency (counter) max. 100 kHz
Frequency meter Yes
controlled positioning Yes
PID controller Yes
Number of alarm inputs 4
Galvanic isolation
Galvanic isolation digital inputs
Galvanic isolation digital inputs No
between the channels, in groups of 1
Galvanic isolation digital outputs
Galvanic isolation digital outputs Relay
between the channels No
between the channels, in groups of 1
Permissible potential difference
between different circuits 500 V DC between 24 V DC and 5 V DC
EMC
Interference immunity against discharge of static electricity
Interference immunity against discharge of static Yes
electricity acc. to IEC 61000-4-2
Test voltage at air discharge 8 kV
Test voltage at contact discharge 6 kV
Interference immunity to cable-borne interference
on the supply lines acc. to IEC 61000-4-4 Yes

Date: subject to modifications


03/21/2012 © Copyright Siemens AG 2012
6ES7214-1HE30-0XB0 Page 7

Interference immunity on signal lines acc. to IEC Yes


61000-4-4
Surge immunity
on the supply lines acc. to IEC 61000-4-5 Yes
Immunity against conducted interference induced by high-frequency fields
Interference immunity against high-frequency Yes
radiation acc. to IEC 61000-4-6
Emission of radio interference acc. to EN 55 011
Emission of radio interferences acc. to EN 55 011 Yes ; Group 1
(limit class A)
Emission of radio interference acc. to EN 55 011 Yes ; When appropriate measures are used to ensure
(limit class B) compliance with the limits for Class B according to EN
55011
Degree and class of protection
IP20 Yes
Standards, approvals, certificates
CE mark Yes
cULus Yes
C-TICK Yes
FM approval Yes
Ambient conditions
Operating temperature
Min. 0 °C
max. 55 °C
vertical installation, min. 0 °C
vertical installation, max. 45 °C
horizontal installation, min. 0 °C
horizontal installation, max. 55 °C
Storage/transport temperature
Min. -40 °C
max. 70 °C
Air pressure
Operation, min. 795 hPa
Operation, max. 1080 hPa
Storage/transport, min. 660 hPa

Date: subject to modifications


03/21/2012 © Copyright Siemens AG 2012
6ES7214-1HE30-0XB0 Page 8

Storage/transport, max. 1080 hPa


Relative humidity
Operation, max. 95 % ; no condensation
Vibrations
Vibrations 2G wall mounting, 1G DIN rail
Operation, checked according to IEC 60068-2-6 Yes
Shock test
checked according to IEC 60068-2-27 Yes ; IEC 68, Part 2-27 half-sine: strength of the shock
15 g (peak value), duration 11 ms
Climatic and mechanical conditions for storage and transport
Climatic conditions for storage and transport
Free fall
Drop height, max. (in packaging) 0.3 m ; five times, in dispatch package
Temperature
Permissible temperature range -40 °C to +70 °C
Mechanical and climatic conditions during operation
Climatic conditions in operation
Temperature
Permissible temperature range 0 °C to 55 °C horizontal installation 0 °C to 45 °C
vertical installation
Permissible temperature change 5°C to 55°C, 3°C / minute
Air pressure acc. to IEC 60068-2-13
Permissible air pressure 1080 to 795 hPa
Permissible operating height -1000 to 2000 m
Pollutant concentrations
SO2 at RH < 60% without condensation S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60%
condensation-free
Configuration
programming
Programming language
LAD Yes
FBD Yes
SCL Yes
Cycle time monitoring

Date: subject to modifications


03/21/2012 © Copyright Siemens AG 2012
6ES7214-1HE30-0XB0 Page 9

adjustable Yes
Dimensions
Width 110 mm
Height 100 mm
Depth 75 mm
Weight
Weight, approx. 435 g
internTechDB
Characteristics will be deleted after 2012-12-31
Product version
STEP 7 STEP 7 V10.5 or higher
Status Mar 12, 2012

Date: subject to modifications


03/21/2012 © Copyright Siemens AG 2012