Anda di halaman 1dari 176

PT PLN (Persero)

PUSAT MANAJEMEN PROYEK


UNIT PELAKSANA MANAJEMEN KONSTRUKSI IV

KAJIAN TEKNIS
KEUNTUNGAN PEMASANGAN SSVT DI GITET 500 KV PERANAP

Kontrak No : 0740.PJ/DAN.02.02/DIR/2017

Surat Penugasan No. : 0004.STg/KON.02.03/UIPSBT/2019


Tanggal : 01 Februari 2019

PT PLN (PERSERO) PUSAT MANAJEMEN PROYEK


UNIT PELAKSANA MANAJEMEN KONSTRUKSI IV
Jl. Sei Batu Gingging No.11 Medan - 20154
Telp. : (061) 80513132, 80513284 Facsimile : (061) 80513142

PR.SMT.PUSMANPRO.37
GITET 500 KV PERANAP PT PLN (PERSERO) PUSMANPRO UPMK IV

DAFTAR ISI

DAFTAR ISI .................................................................................................................... i


BAGIAN I PENDAHULUAN ............................................................................................. 1
1.1 INFORMASI PROYEK ........................................................................................... 1
1.2 SSVT (STATION SERVICE VOLTAGE TRANSFORMER)
BAGIAN II PERMASALAHAN .......................................................................................... 5
2.1. KRONOLOGIS ...................................................................................................... 5
2.1. PENGAJUAN KONTRAKTOR ............................................................................... 7
BAGIAN III HASIL EVALUASI/KAJIAN ............................................................................ 8
3.1. ASPEK LEGAL .................................................................................................... 10
3.2. ASPEK TEKNIS .................................................................................................... 9
3.2. ASPEK KEUNTUNGAN PEMASANGAN SSVT DI GARDU INDUK .................... 11
BAGIAN IV KESIMPULAN ............................................................................................. 13
DAFTAR LAMPIRAN ...................................................................................................... 14
LAMPIRAN 1. AMANDEMEN KONTRAK I dan II
LAMPIRAN 2. APROVAL DRAWING
LAMPIRAN 3. MINUTES OF MEETING
LAMPIRAN 4. BERITA ACARA NEGOISASI DAN VERIFIKASI
LAMPIRAN 5. SURAT KONFIRMASI DARI PLN UIP SBT

KEUNTUNGAN PEMASANGAN SSVT DI GITET 500 KV PERANAP i


PR.SMT.PUSMANPRO.37
GITET 500 KV PERANAP PT PLN (PERSERO) PUSMANPRO UPMK IV

BAGIAN 1
PENDAHULUAN

1.1 INFORMASI PROYEK


Dalam upaya memenuhi kebutuhan pasokan listrik di berbagai pusat beban seperti
kota, kawasan industri, permukiman dan lainnya sangat diperlukan adanya sarana yang
mampu menyalurkan tenaga listrik. Salah satu bentuk sarana yang digunakan adalah
Gardu Induk (GI). Gardu Induk ini diharapkan dapat mensuplai energy listrik, baik
masyarakat dan industri, serta meningkatkan keandalan system kelistrikan. Peranap
merupakan salah satu daerah yang memiliki tingkat kebutuhan tenaga listrik yang besar,
sehingga menjaga pasokan listrik yang stabil mutlak diperlukan. Dengan adanya
pekerjaan Pengadaan dan Pemasangan Gardu Induk Tegangan Ekstra Tinggi 500 kV
Peranap. Peranap akan meningkatkan kapasitas penyaluran tenaga listrik sehingga
kebutuhan pasokan tenaga listrik dapat terpenuhi serta meningkatkan keandalan system
tenaga listrik di Peranap, Riau. Berdasarkan latar belakang tersebut, maka PT PLN
(Persero) Unit Induk Pembangunan Sumatera Bagian Tengah akan melaksanakan
pekerjaan : “Pekerjaan Pembangunan GI Tegangan Ekstra Tinggi 500 kV Peranap”.
Data proyek adalah sebagai berikut :
1. Nomor kontrak : 0740.PJ/DAN.02.02/DIR/2017
2. Pelaksana proyek : KSO PT ABB SAKTI INDUSTRI – PT WASKITA
KARYA (PERSERO) TBK
3. Waktu Pelaksanaan : 912 (sembilan ratus dua belas) hari kalender
4. Tanggal Efektif : 31 Desember 2018 sampai dengan tanggal 29 Juni
2021
5. Harga Kontrak : Rp. 325.046.316.100
6. Amandemen :
a) Amandemen I No.0740.PJ/DAN.02.02/DIR/2017 tanggal 16
November 2020, Tentang Perubahan Komparisi &
Korespondensi dan Perubahan Masa Pelaksanaan.
b) Amandemen II No.0740.PJ/DAN.02.02/DIR/2017 tanggal 25
November 2021, Tentang Perubahan Masa
Pelaksanaan.

7. Progres Pekerjaan : Hingga bulan Juni 2022, progres tercapai 93,4498%


KEUNTUNGAN PEMASANGAN SSVT DI GITET 500 KV PERANAP
PR.SMT.PUSMANPRO.37
1
GITET 500 KV PERANAP PT PLN (PERSERO) PUSMANPRO UPMK IV

Progress
BOBOT
NO ITEM PEKERJAAN s/d saat Deviasi
(%)
ini

A GARDU INDUK
A.1 GI Tegangan Ekstra Tinggi 500 kV Peranap
Pengadaan Material Termasuk Transportasi,
1. 75,0023 71,2767
Pemasangan Commisioning Dan Asuransi
2. Installation Services For Civil Works 24,9977 22,1731
TOTAL SEMUA 100,000 93,4498
Gambar 1. Tabel pencapaian progres hingga bulan Juni 2022.

1.2 STATION SERVICE VOLTAGE TRANSFORMER (SSVT)


Station Service Voltage Transformers (SSVT) banyak digunakan di Amerika
Utara sebagai catu daya untuk layanan tambahan gardu induk. Mereka adalah solusi
hibrid, menggabungkan dalam selungkup yang sama sifat insulasi transformator
tegangan induktif (IVT) dengan transformator distribusi.
SSVT adalah Transformator Tegangan Induktif (Magnetik) yang mampu
memasok daya Tegangan Rendah langsung dari Saluran Tegangan Tinggi dalam
satu langkah transformasi. Ini adalah perbedaan utama dari transformator daya karena
SSVT dapat menawarkan daya secara langsung pada 220-240 volt, sedangkan
transformator daya biasanya memerlukan transformator distribusi tambahan.

Station Service Voltage Transformers (SSVT) digunakan untuk memasok daya


Tegangan Rendah langsung dari saluran Tegangan Tinggi hingga 550 kV. Terletak di
dalam gardu induk sendiri, mereka dapat menyediakan daya hingga 333 kVA per
fase dengan cara yang andal dan hemat biaya. Mereka menawarkan berbagai
aplikasi, tetapi mereka unggul ketika catu daya layanan tambahan gardu diperlukan
di daerah terpencil, menjadikannya solusi ideal untuk memenuhi kebutuhan energi di
gardu induk tersebut.
Sesuai dengan draft IEEE C.57.13-8, SSVT adalah transformator fase tunggal
dengan nilai di atas 46kV, mulai dari 25kVA hingga 500 kVA, namun, saat ini peringkat
output daya yang lebih tinggi yang tersedia di pasar adalah 333 kVA per fase. Mereka
menawarkan koneksi langsung dan andal dengan HV saluran transmisi, dengan cara
yang praktis dan mudah dipasang di transformator tipe alas (Gambar 2). Saluran

KEUNTUNGAN PEMASANGAN SSVT DI GITET 500 KV PERANAP


PR.SMT.PUSMANPRO.37
2
GITET 500 KV PERANAP PT PLN (PERSERO) PUSMANPRO UPMK IV
terhubung ke tanah, sistem tiga fase dapat dibentuk dengan output sekunder dari 3 IVT
dalam konfigurasi bintang.

SSVT memiliki koneksi fase langsung ke ground dengan insulasi galvanik antara
belitan primer dan sekunder, yang digulung di atas inti magnet yang sama dengan insulasi
independen. Mereka menyajikan kerugian rendah dengan perlindungan impedansi untuk
membatasi arus gangguan trafo tegangan ini dapat berupa kertas minyak atau isolasi
SF6.

SSVT dengan insulasi kertas minyak (Gambar 3 kiri) dibuat dengan inti magnetik
di dalam tangki logam dengan gulungan primer dan sekunder di sekitarnya. Konduktor
utama tertutup oleh bushing kapasitif yang terdiri dari pelindung dan lapisan kertas isolasi
yang diisi dengan minyak. Untuk mengontrol perubahan level oli, mereka dilengkapi
dengan bellow metalik.

SSVT dengan insulasi gas (Gambar 3 kanan) dibuat dengan inti magnetik di
dalam tangki logam dengan gulungan primer dan sekunder di sekitarnya. Gulungan ini
terbuat dari kabel listrik tahan panas yang dilapisi resin sintetis dan lapisan plastik dengan
ketahanan dielektrik yang tinggi dan kinerja termal dan mekanik yang sangat baik. SF6
dan lapisan plastik ini membentuk isolasi listrik. Katup input untuk gas SF6 disediakan di
sisi tangki bersama dengan manometer untuk memantau tekanan gas.

Gambar 2. Aplikasi SSVT

KEUNTUNGAN PEMASANGAN SSVT DI GITET 500 KV PERANAP


PR.SMT.PUSMANPRO.37
3
GITET 500 KV PERANAP PT PLN (PERSERO) PUSMANPRO UPMK IV

Gambar 3. (kiri) SSVT Arteche UTP-245 yang diisolasi minyak


(kanan) SF6 SSVT Arteche UGP-245 yang terisolasi

Gambar 4. Pemasangan SSVT di GITET 500 kV Peranap

KEUNTUNGAN PEMASANGAN SSVT DI GITET 500 KV PERANAP


PR.SMT.PUSMANPRO.37
4
GITET 500 KV PERANAP PT PLN (PERSERO) PUSMANPRO UPMK IV

BAGIAN II
PERMASALAHAN

2.1. KRONOLOGIS
Kronologis singkat Pekerjaan Pembangunan GI Tegangan Ekstra Tinggi 500 kV
Peranap secara umum dijabarkan berikut :

No Tanggal Deskripsi

1 31 Desember 2018 Berdasarkan surat penyampaian pembahasan kick off


meeting GITET 500 kV Peranap tanggal 9 Januari 2019
dijelaskan bahwa waktu pelaksaan 600 hari kalender
terhitung efektif sejak tanggal 31 Desember 2018 dan
berakhir tanggal 22 Agustus 2020.
2 16 Januari 2019 Penandatangan surat penugasan dengan PLN
PUSMANPRO dengan SLA
0004.STg/KON.02.03/UIPSBT/2019
3 18 Februari 2019 Pertama kali dimulai kegiatan lapangan untuk pekerjaan
pembuatan direksi keet
4 01 November 2019 Material EM onsite untuk kebutuhan GITET 500 kV
Peranap
5 13 Maret 2020 Pembahasan ATK & EOT GITET 500 kV Peranap poin
6C tetntang usulan penambahan SSVT.
6 07 Agustus 2020 Rapat pembahasan progres pekerjaan dan rencana
amandemen GITET 500 kV Peranap poin 2.8 tentang
PLN UIP Sumbagteng menyetujui pemanfaatan SSVT
di GITET 500 kV Peranap
7 16 September 2020 Usulan Amandemen Kerja Tambah Kurang Pekerjaan
Pembangunan Gardu Induk Tegangan Ekstra Tinggi 500
kV Peranap berdasarkan surat KSO PT ABB SAKTI
INDUSTRI - PT WASKITA KARYA (Persero) Tbk. No.
098/ABB-WSKT/LX/2020 tanggal 16 September 2020
8 16 Oktober 2020 Berita acara negoisasi dan verifikasi perihal variation
order pembangunan GITET 500 KV PERANAP tanggal
16 Oktober 2020

KEUNTUNGAN PEMASANGAN SSVT DI GITET 500 KV PERANAP


PR.SMT.PUSMANPRO.37
5
GITET 500 KV PERANAP PT PLN (PERSERO) PUSMANPRO UPMK IV
9 16 November 2020 Amandemen I Perubahan Komparisi & Korespondensi
dan Perubahan Masa Pelaksanaan.
Semula waktu pelaksanaan 600 hari kalender terhitung
efektif sejak tanggal 31 Desember 2018 dan berakhir
tanggal 22 Agustus 2020 menjadi912 hari kalender,
efektif sejak tanggal 31 Desember 2018 dan berakhir 29
Juni 2021
10 19 Desember 2020 UIP SBT mengirim surat
No. 2827/TRS.01.04/B42000000/2020 tanggal 19
Desember kepada KSO PT. ABB Power Grids Indonesia
– PT Waskita Karya perihal konfirmasi persetujuan
pekerjaan tambah SSVT pada pekerjaan Gardu Induk
500 KV peranap
11 31 Agustus 2021 - 20 Rentang waktu pemasangan SSVT di GITET 500 kV
September 2021 Peranap
12 06 Oktober 2021 Teguran pekerjaan melalui surat PT PLN (Persero)
UPP SUMBAGTENG 3
No.0749/TRS.01.04/C38030000/2021 tangggal 6
Oktober 2021 perihal teguran pelaksanaan pekerjaan
GITET 500 kV Peranap
13 03 Januari 2022 KSO ABB-Waskita mengirim surat
No. 001/ABB-WSKT/I/2022 tanggal 03 Januari 2022
kepada PLN UPP Sumbagteng 3 perihal Pengajuan
permintaan revisi surat rekomendasi kerja tambah dan
kurang untuk pekerjaan sipil, EM, dan SSVT
berdasarkan hasil review BPKP

KEUNTUNGAN PEMASANGAN SSVT DI GITET 500 KV PERANAP


PR.SMT.PUSMANPRO.37
6
GITET 500 KV PERANAP PT PLN (PERSERO) PUSMANPRO UPMK IV

2.2. PENGAJUAN KONTRAKTOR


Sehubungan dengan surat KSO PT ABB SAKTI INDUSTRI - PT WASKITA KARYA
(Persero) Tbk. Surat nomor 098/ABB-WSKT/LX/2020 tanggal 16 September 2020
perihal Usulan Amandemen Kerja Tambah Kurang Pekerjaan Pembangunan
Gardu Induk Tegangan Ekstra Tinggi 500 kV Peranap dan diperbaharui dengan
surat KSO PT ABB SAKTI INDUSTRI - PT WASKITA KARYA (Persero) Tbk. Surat
nomor 001/ABB-WSKT/I/2022 tanggal 03 Januari 2022 perihal pengajuan
permintaan revisi surat rekomendasi kerja tambah dan kurang untuk pekerjaan
sipil, EM, dan SSVT berdasarkan hasil review BPKP, kontraktor mengajukan
penambahan item pekerjaan sebagai berikut :
1. Electrical & Mechanical Material
a. Substansion Service Voltage Transformer
b. Connector for SSVT
c. Spacer for downlead SSVT
d. Conductor TAL 2x850 mm2
e. LV Power cable (1x300sqmm), control cable and accessories
f. Free standing cubicle
2. Civil Material
a. Foundation of SSVT
b. Foundation of Marshaling Kiosk
c. Cable trench (K225, BJTD 40 incld cover, Galvanized Cable Tray L 50.50.5
and PVC Pipe)
- Cable duct type 2 (Medium, Width > 60 cm, < 80 cm)
- Cable duct type 3 (Small, Width < 60 cm)

KEUNTUNGAN PEMASANGAN SSVT DI GITET 500 KV PERANAP


PR.SMT.PUSMANPRO.37
7
GITET 500 KV PERANAP PT PLN (PERSERO) PUSMANPRO UPMK IV

BAGIAN III
HASIL EVALUASI / KAJIAN

3.1. ASPEK LEGAL


Daftar klausul kontrak yang dijadikan referensi untuk melakukan kajian ini adalah
sebagai berikut :
A. Dokumen kontrak BAB VI syarat syarat umum kontrak
1. Pekerjaan tambah kurang
1.1 Apabila terdapat perbedaan antara kondisl lapangan pada sat
pelaksanaan pekerjaan dengan spesifikasi teknis dan gambar yang
ditetapkan dalam dokumen Perjanjian/Kontrak, maka Penyedia
barang/Jasa dan Pengguna Barang/Jasa dapat melakukan perubahan
(Addendum/Amandemen) Perjanjian/Kontrak yang meliputi antara lain:
a. Menambah atau mengurangi volume pekerjaan yang tercantum
dalam Dokumen Perjanjian/Kontrak
b. Menambah atau mengurangi jenis pekerjaan
c. Mengubah spesifikasi teknis dan gambar pekerjaan sesuai dengan
kebutuhan lapangan
1.2 Pekerjaan Tambah yang tidak dapat dielakkan dalam rangka
penyelesaian pekerjaan, dengan ketentuan nilainya tidak lebih dari 10%
(sepuluh persen) dari harga yang tercantum dalam Perjanjian/Kontrak
awal maka pekerjaan tambah tersebut harus didasarkan pada justifikasi
yang dapat dipertanggungjawabkan secara profesional ole Direksi
Pekerjaan.
1.3 Dalam hal pekerjaan tambah melebihi 10% (sepuluh persen) dari harga
yang tercantum dalam Perjanjian/Kontrak awal maka pekerjaan tambah
tersebut harus didasarkan pada justifikasi yang dapat dipertanggung
jawabkan secara profesional oleh Direksi Pekerjaan dan wajib
mendapatkan persetujuan terlebih dahulu dari Pengguna Barang/Jasa
sebelum pelaksanaannya.
1.4 Perintah perubahan pekerjaan harus dibuat secara tertulis oleh
Pengguna Barang/Jasa kepada Penyedia Barang/Jasa atau dicatumkan
Dalam notulen rapat (MOM) bersama, ditindak lanjuti dengan negosiasi

KEUNTUNGAN PEMASANGAN SSVT DI GITET 500 KV PERANAP


PR.SMT.PUSMANPRO.37
8
GITET 500 KV PERANAP PT PLN (PERSERO) PUSMANPRO UPMK IV
teknis dan harga dengan tetap mengacu pada ketentuan yang
tercantum dalam dokumen Perjanjian/Kontrak. Perubahan tersebut
dituangkan dalam Addendum/ Amandemen Perjanjian/Kontrak
B. Approval drawing
No Judul Gambar No. Gambar
1. SSVT Plan & Section View 1HID1-1-8055-B704
2. TPG & Outline Drawing Of Marshalling Kiosk 1HID1-2-8055-B737-4
For SSVT

C. Minutes of meeting
- MOM tanggal 13 Maret 2020 pembahasan Atk & Eot Gitet 500 Kv Peranap

D. Berita Acara negoisasi dan verifikasi

- Variation order pembangunan GITET 500 KV PERANAP tanggal 16


Oktober 2020
E. Surat Pendukung
- Usulan Amandemen Kerja Tambah Kurang Pekerjaan Pembangunan
Gardu Induk Tegangan Ekstra Tinggi 500 kV Peranap berdasarkan surat
KSO PT ABB SAKTI INDUSTRI - PT WASKITA KARYA (Persero) Tbk. No.
098/ABB-WSKT/LX/2020 tanggal 16 September 2020
- UIP SBT mengirim surat No. 2827/TRS.01.04/B42000000/2020 tanggal 19
Desember kepada KSO PT. ABB Power Grids Indonesia – PT Waskita
Karya perihal konfirmasi persetujuan pekerjaan tambah SSVT pada
pekerjaan Gardu Induk 500 KV peranap
- KSO ABB-Waskita mengirim surat No. 001/ABB-WSKT/I/2022 tanggal 03
Januari 2022 kepada PLN UPP Sumbagteng 3 perihal Pengajuan
permintaan revisi surat rekomendasi kerja tambah dan kurang untuk
pekerjaan sipil, EM, dan SSVT berdasarkan hasil review BPKP

KEUNTUNGAN PEMASANGAN SSVT DI GITET 500 KV PERANAP


PR.SMT.PUSMANPRO.37
9
GITET 500 KV PERANAP PT PLN (PERSERO) PUSMANPRO UPMK IV

3.2. ASPEK TEKNIS

Gardu Induk Peranap merupakan salah satu Gardu Tegangan Ekstra Tinggi yang
terkoneksi melalui Jaringan Tegangan Tinggi 500kV di Sumatera. Detail status
saat ini dapat diketahui dari gambar di bawah ini, sesuai rilis oleh PLN.

Berdasarkan dokumen kontrak yang diberikan kepada KSO ABB-WSKT no.


0740.PJ/DAN.02.02/DIR/2017 tanggal 28 Desember 2017, tidak ada Inter Bus
Transformer (IBT) dari 500kV ke tegangan terendah. Tingkat tegangan sumber
adalah 500kV yang dipasok dari Jaringan Transmisi 500kV dari Gardu Induk Aur
Duri Baru. Untuk skema ini, sumber konsumsi daya gardu induk sendiri perlu
mendapat perhatian khusus karena terdapat 2 Auxiliary Transformer (20/0.4kV)
yang akan dipasang di gardu induk.

Untuk keandalan, setiap gardu induk membutuhkan dua catu/sumber daya


kontrol, Biasanya, transformator utama di gardu induk adalah sumber utama daya
kontrol. Namun, catu daya kedua diperlukan – karena beberapa alasan. Misalnya,
di gardu generator, di mana pasokan utama sering disadap/gangguan dari

KEUNTUNGAN PEMASANGAN SSVT DI GITET 500 KV PERANAP


PR.SMT.PUSMANPRO.37
10
GITET 500 KV PERANAP PT PLN (PERSERO) PUSMANPRO UPMK IV
generator itu sendiri, generator dapat berhenti untuk pemeliharaan atau mungkin
untuk waktu yang lama.
Ketika tidak ada pembangkit listrik, daya kontrol harus diambil dari jaringan. Ada
beberapa cara untuk melakukan ini, transformator daya besar dapat tetap diberi
energi untuk memasok daya kontrol sekunder – tetapi ini sangat tidak efisien.
Dalam beberapa kasus, Transformator HV utama dilengkapi dengan belitan ketiga
untuk menyediakan catu daya kontrol. Namun, hal ini tidak berlaku karena tidak
ada trafo utama yang dibangun di Area Proyek Peranap. Menarik daya dari
generator siaga, atau jaringan distribusi LV (low voltage) lokal, atau dari Substation
Service Voltage Transformer (SSVT) dapat menjadi pilihan. Berdasarkan
pertimbangan, maka dipilih untuk pemasangan SSVT di GITET 500 Peranap
sebagai salah satu sumber daya untuk operasional gardu induk, disamping juga
dibangun generator diesel untuk sumber daya sekunder.

3.3. ASPEK KEUNTUNGAN PEMASANGAN SSVT DI GARDU INDUK


Berikut beberapa keuntungan yang didapatkan dari pemasangan SSVT di gardu induk :
1. Reliability (Keandalan)

Catu/sumber daya yang sangat andal, karena daya diambil langsung dari saluran
HV/transmisi, yang memiliki tingkat keandalan yang jauh lebih tinggi dari pada
saluran distribusi.

2. Hemat biaya.
Biaya pemasangan umumnya lebih rendah, dan biaya hidup pasti lebih rendah,
karena tidak perlu membayar energi ke pihak ke-3.
3. Desain bebas perawatan dan umur panjang
SSVT hanya membutuhkan lebih sedikit perawatan. Ini adalah salah satu
keuntungan menggunakan SSVT untuk daya bantu. .
4. Pasokan layanan bantu independen.
Pengguna tidak harus bergantung pada pihak ketiga, seperti utilitas
distribusi,pemasok bahan bakar, dll. Mengambil daya langsung dari saluran HV di
switchyard dapat menyebabkan ketergantungan yang lebih sedikit. Selama garis
HV diberi energi, daya tersedia. Tidak perlu koordinasi antar pihak karena kekuatan
tambahan dimiliki oleh P3BS atau unit distribusi. Pemilik dapat dengan mudah
melakukan penutupan dan pembukaan saklar tanpa campur tangan dari pihak lain.

KEUNTUNGAN PEMASANGAN SSVT DI GITET 500 KV PERANAP


PR.SMT.PUSMANPRO.37
11
GITET 500 KV PERANAP PT PLN (PERSERO) PUSMANPRO UPMK IV
5. Instalasi yang fleksibel, cepat dan mudah
Waktu cepat untuk instalasi saat menggunakan SSVT karena dapat diinstal
bersama dengan peralatan HV lainnya yang terletak di switchyard. Tidak perlu lahan
tambahan.
6. Desain yang kuat.
Diuji menurut standar yang sama untuk menjamin keandalan tinggi yang sama
seperti transformator instrumen tegangan induktif.
7. Resiko operasional yang lebih kecil dibandingkan dengan suplai daya dari jaringan
distribusi.
8. Keuntungan sosial.
Elektrifikasi daerah terpencil atau pedesaan, dan bisa digunakan sebagai pasokan
darurat setelah bencana alam.
9. Fleksibilitas desain.
Tegangan sekunder yang berbeda tersedia. Sehingga dapat memilih tegangan
sekunder yang diinginkan sesuai kebutuhan.

KEUNTUNGAN PEMASANGAN SSVT DI GITET 500 KV PERANAP


PR.SMT.PUSMANPRO.37
12
GITET 500 KV PERANAP PT PLN (PERSERO) PUSMANPRO UPMK IV

BAGIAN IV
KESIMPULAN

Station Service Voltage Transformers (SSVT) juga dikenal sebagai Power Voltage
Transformers (PVT) digunakan untuk memasok daya Tegangan Rendah langsung dari
saluran Tegangan Tinggi hingga 550kV. Terletak di dalam gardu induk sendiri,
mereka dapat menyediakan daya hingga 333kVA per fase dengan cara yang andal
dan hemat biaya. Dengan semua pertimbangan yang disebutkan, solusi untuk memasok
layanan tambahan dengan SSVT adalah solusi terbaik sebagai sumber utama layanan
tambahan gardu induk, dengan generator diesel sebagai cadangan. Dan memiliki
beberapa keunggulan mendasar dibadingkan penggunaan sumber daya dari saluran
distribusi atau LV line, yaitu :

SSVT LV Line/Jaringan distribusi


Catu daya yang andal. Kurang dapat diandalkan.
Daya langsung diambil dari HV Line Daya diambil dari jalur distribusi.
Konstruksi rendah Konstruksi Tinggi
Pasokan layanan tambahan independen. Tergantung pasokan layanan tambahan.
Pengguna tidak harus bergantung pada Pengguna bergantung pada utilitas
pihak ketiga,
Bebas seperti utilitas distribusi.
perawatan distribusi.
Butuh perawatan
Dampak lingkungan yang rendah Dampak Visual
Biaya efektif Tidak hemat biaya

Selanjutnya proses persiapan dan administrasi amandemen dapat dilakukan setelah ada
pembahasan dan kesepakatan para pihak sebagai tindak lanjut penyelesaian progress
pekerjaan Pembangunan GITET 500 KV Peranap bersama Direksi Pekerjaan dan/atau
pihak terkait lainnya yang mewakili. Selanjutnya pelaksana juga harus memastikan dan
melakukan perubahan terkait waktu jaminan pelaksanaan sesuai dengan kesepakatan
perubahan waktu dari para pihak.

KEUNTUNGAN PEMASANGAN SSVT DI GITET 500 KV PERANAP


PR.SMT.PUSMANPRO.37
13
GITET 500 KV PERANAP PT PLN (PERSERO) PUSMANPRO UPMK IV

DAFTAR
LAMPIRAN

LAMPIRAN 1. Amandemen Kontrak I-II


LAMPIRAN 2. Approval Drawing
LAMPIRAN 3. Minutes of Meeting
LAMPIRAN 4. Berita Acara negoisasi dan verifikasi
LAMPIRAN 5. Surat pendukung

KAJIAN DAN EVALUASI KEMAJUAN PEKERJAAN TERHADAP PERPANJANGAN WAKTU


PR.SMT.PUSMANPRO.37 14
Reference Document
Drawing Number Designation Status

C As commented 05.06.2021 RY UA UA
B Re-Issued For Approval 14.12.2020 RY UA UA
A For Approval 17.07.2020 RY UA UA
Rev. Description Date Designed Checked Approved
Owner :

PT. PLN (Persero)


UNIT INDUK PEMBANGUNAN SUMATERA BAGIAN TENGAH
Consultant :

PT PLN ENJINIRING

Project :

PEMBANGUNAN GARDU INDUK TEGANGAN EKSTRA TINGGI


500KV PERANAP
Contract No : 0740.PJ/DAN.02.02/DIR/2017, Date : 28 December 2017

Title :

TPG & OUTLINE DRAWING OF


SUBSTATION SERVICE VOLTAGE TRANSFORMER
Contractor :
KSO PT ABB SAKTI INDUSTRI - PT. WASKITA KARYA (PERSERO) TBK.


PLN Dwg. No. :
Responsible Dept. : Created by : Checked by : Approved by : Format :
RY UA UA
PGGI 17th-Jul, 2020 17th-Jul, 2020 17th-Jul, 2020 A4 size
Doc. Type : ☑ For Approval □ For Information □ Other
Doc. Status: □ Approved □ Approved on Condition □ Not Approved
PT ABB Sakti Industri Contractor
Dwg/Doc. No. 1HID1-1-8055-B755-1 Rev. C
Total __ Pages (including this cover Sheet)
TECHNICAL PARTICULAR AND GUARANTEE

TPG SUBSTATION SERVICE VOLTAGE TRANSFORMER

NO. DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEED

Manufacturer to be mentioned Arteche - Spain


Type of Designation to be mentioned UG-550
Applicable Standards IEC 61869-3; IEC 60076-15 IEC 61869-3; IEC 60076-15

System Voltage
1. Rated frequency (Fr) Hz 50 50
2. Highest Voltage for equipment (Um) kVrms 550 550
3. Insulation Class :
- Power frequency withstand voltage kVrms 680 680 (primary); 3 (secondary)
- Lightning impulse withstand voltage kVp 1550 1550
- Switching impulse withstand voltage kVp 1175 1175

Operating Conditions
4. Rated primary voltage (Upr) kV 500/√3 500/√3
5. Rated secondary voltage (Usr) kV 0.4/√3 0.4/√3
6. Rated overvoltage factor to be mentioned 1.2Un for cont.; 1.5Un for 30s
7. Windings power kVA 100 100
8. Rated secondary current A to be mentioned 433
9. Rated short circuit current (1s) kA to be mentioned N/A
10. Rated dynamic current kA to be mentioned N/A

Environmental Conditions
11. Min. operating temperature ᵒC to be mentioned -10
12. Max operating temperature (shade conditions) ᵒC to be mentioned +45
13. Relative humidity % to be mentioned As per IEC
14. Altitude above sea level m to be mentioned ≤1000

2 of 4
TECHNICAL PARTICULAR AND GUARANTEE

TPG SUBSTATION SERVICE VOLTAGE TRANSFORMER

NO. DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEED


15. Site pollution severity (SPS) class (IEC 60815) to be mentioned As per IEC
16. Corrosive environment (ISO 12944-2) to be mentioned As per IEC
17. Solar radiation W/m2 to be mentioned As per IEC
18. Ice Load mm to be mentioned As per IEC
19. Seismic Level g 0.3 0.3
20. Secondary terminal box degree of protection to be mentioned IP55

Insulator
21. Material - Color to be mentioned Polimeric
22. Creepage distance mm/kV 25 25
23. Min. flashover distance mm to be mentioned 5050
24. Static withstand loads N to be mentioned 2100
25. Insulation fluid to be mentioned 100% SF6

Others
26. Impedance % to be mentioned <9
27. Type of tapping to be mentioned N/A
28. Number of taps to be mentioned 0
29 Maximum losses for:
No load losses (at rated voltage) W to be mentioned 642
Load losses at rated load W to be mentioned 703
30. Gas pressure indicator to be provided Yes, provided (2 alarm)
31. Leakage rate of gas per Annum % to be mentioned <0.5%
32. Total height mm to be mentioned 7400
33. Type Test Report to be provided Yes, provided

3 of 4
PT PLN (Persero) Unit Induk Pembangunan KSO PT ABB Sakti Industri - PT Waskita Karya (Persero) Tbk. PT PLN Enjiniring
Sumatera Bagian Tengah
CONTRACTOR'S REPLY

PEMBANGUNAN GARDU INDUK TEGANGAN EKSTRA TINGGI 500KV PERANAP


CONTRACT NO : 0740.PJ/DAN.02.02/DIR/2017
DATE : 28 DECEMBER 2017

No. No. Gambar Title Rev. Status Tanggapan PLN Jawaban Kontraktor

1. Pada TPG untuk Type of Designation yang dicantumkan


TPG and Outline Drawing 1. Type of Designation SSVT adalah UG 550. UGP 550
1 1HID1-1-8055-B755-1 B EN adalah UGP 550, namun pada type test type designation yang
of SSVT dipakai untuk keperluan internal.
dicantumkan adalah UG 550. Mohon dijelaskan

2. Pada TPG impedance < 8 % namun pada type test 2. Nilai aktual adalah < 9 %. Nilai < 8 % merupakan teori
impedance < 9 %. Mohon dikoreksi perhitungan.

3. Gambar MK SSVT dicantumkan pada dokumen 1HID1-2-


3. Tidak ada gambar klem dan wiring pada MK SSVT bagian
8055-B737-3 TPG & Outline Drawing of Marshalling Kiosk
dalam. Tolong dilampirkan.
(dilampirkan)

1
SSVT
OUTLINE DRAWING
DESCRIPCION
DESCRIPTION

Indicador presión gas


1.-
Gas pressure indicator

Terminal primario
2.-
Primary terminal

Toma de tierra
3.-
Earthing terminal

5360
Caja bornes
4.-
Terminal box
7400

Cáncamo elevación
5.-
Lifting eyebolt

Valvula de llenado
GC 6.-
Filling valve

Dispositivo liberador presión


7.-
Pressure relief device
1895

Anillo Deflector
8.-
1075

Deflector ring

Detalle "X"
Ver Detalle "X" Detail "X"
See detail "X"
5

4-Ø38
7
R

45
Ø
909

50
790

25

14

Detalle Toma de Tierra


790 En los 4 vertices de la base.
Bornes tipo Phoenix UT4
UT4 Phoenix type

Ho

1 2 34 1 3

6 0 8
© Copyright by ARTECHE G.I.T. S.L.U. Vitoria-Gasteiz. En "Fecha creación". Todos los derechos reservados, estando prohibida la reproducción total o parcial del plano, sin autorización del titular.

X1 X3 X2 X4

Terminal M16 1x(35-300mm²)


Puentes DIN912 M6 M16 Stud1x(1AWG-1000Kcmil)
Jumper DIN912 0.236 in

VISTA DEL BLOQUE DE BORNES SECUNDARIOS


MARCA
CANT.

DESCRIPCION MATERIAL TRATAMIENTO


Rev Modificaciones Fecha Tolerancia para
medidas sin
indicación
según:
ISO 2768-mk
Sustituye a:
MICR.

VISTA DEL BLOQUE DE BORNES SECUNDARIOS


Sustituido por:

TyT Cacei Calc. Delin.

ESCALA DIBUJADO FECHA COMPROB.

SZ 11/12/2020 JRG
PLANO Nº
20026423_4216631
CHARACTERISTICS SHEET SERIAL N 20026423

Client PT. ABB POWER GRIDS INDONESIA


Customer Ref LOA Temp. Min. -10 ºC
Order 0010019876 Temp. Max. 45 ºC

Model UG-550 Frequency 50 Hz Standard


Quantity 6 Creep. dist 48 mm/kV IEC 61869
Draw. Nº/Mark 4288910 Insulator POLIMERIC

System maximum voltage (Um) 550 kV


Rated power frequency withstand voltage (60s) 680 kV
Rated lightning impulse withstand voltage (complete wave) 1550 kV
Rated switching impulse withstand voltage 1175 kV
Rated power freq. withstand volt. for sec. windings insulation. and between sections 3 kV
Rated power freq. withstand volt. for the primary low voltage terminal 3 kV

Upr (V) Usr (V) Sr (VA) Vcc (%) Ir (A) Errors


500000:V3 400:V3 100000 433

Permanent overvoltage 1.2Un Rated Voltage Factor 1.5Un/30s

Primary Connector Aluminum Diam 30x80mm


Sec. Connector For cables up to 300 mm2
Acces.

Earthing Terminal See drawing


Cable glands Without
Manometer 2 alarms
Valve DN20
Particulari
dades

Mechanic features 1500 (N) Seismics 0.5 (g) / (g) Wind speed (km/h)
Painted: RAL 9002

Filling pressure: 0,50 MPaG


Filling Gas

Minimum working pressure: 0,43 MPaG


Maximum acceptable working pressure: 0,70 MPaG
Mixture type: 100% SF6
SF6 mass: 110 kg
Leakage rate: max 0,5% anual

Language: Reports ENGLISH Documents ENGLISH Plates ENGLISH


Reference Document
Drawing Number Designation Status

C As Commented on 10 Nov 2020 10.01.2021 RY UA UA


B As Commented on 28 Aug 2020 15.09.2020 RY UA UA
A For Approval 17.07.2020 RY UA UA
Rev. Description Date Designed Checked Approved
Owner :

PT. PLN (Persero)


UNIT INDUK PEMBANGUNAN SUMATERA BAGIAN TENGAH
Consultant :

PT PLN ENJINIRING

Project :

PEMBANGUNAN GARDU INDUK TEGANGAN EKSTRA TINGGI


500KV PERANAP
Contract No : 0740.PJ/DAN.02.02/DIR/2017, Date : 28 December 2017

Title :

TPG & OUTLINE DRAWING OF


MARSHALLING KIOSK FOR SSVT
Contractor :
KSO PT ABB SAKTI INDUSTRI - PT. WASKITA KARYA (PERSERO) TBK.


PLN Dwg. No. :
Responsible Dept. : Created by : Checked by : Approved by : Format :
RY UA UA
PGGI 17th-Jul, 2020 17th-Jul, 2020 17th-Jul, 2020 A4 size
Doc. Type : ☑ For Approval □ For Information □ Other
Doc. Status: □ Approved □ Approved on Condition □ Not Approved
PT ABB Sakti Industri Contractor
Dwg/Doc. No. 1HID1-2-8055-B737-4 Rev. C
Total __ Pages (including this cover Sheet)
TECHNICAL PARTICULAR AND GUARANTEE

TPG MARSHALLING KIOSK FOR SSVT


NO. DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE

1 Manufacturer - ABB

2 Type - Outdoor

3 Protection class - IP54

4 Mounting position - On frame

5 Material of cubicle - Hot dip galvanised sheet steel

6 Minimum thickness of sheet steel mm 2

7 Front cover : door with glass window - No, front cover with lamp indication

8 Provided with swingable cover for mimic and control - No

9 Dimension :
- depth mm 700
- width mm 800
- height mm 1950

10 Roof : shallow pitched - Yes

11 Heating resistor : manual control - Yes

12 Mimic diagram provided - Yes


TPG MARSHALLING KIOSK FOR SSVT
NO. DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE

13 Position indicators provided for :


- busbar isolators - No
- circuit breaker - No
- line isolator - Yes (3P MCCB 800A)
- earthing switch - No

14 Control push-buttons for all motor


operated isolators - No

15 Built-in sockets :
- 2 pole AC 220 V 16 A - Yes
- 3 pole AC 380 V 25 A - Yes
protected by MCBs

16 Built-in lighting - Yes

17 Built-in terminal blocks - Yes

18 Built-in switches - No

19 Built-in fuses - No

20 Total weight kg Approx. 300


SSVT MARSHALLING KIOSK
OUTLINE DRAWING
SYMBOL DESCRIPTION SYMBOL DESCRIPTION

TERMINAL IN GENERAL COIL RELAY

CIRCUIT BREAKER NO CONTACT


NORMALLY OPEN

DOOR SWITCH NC CONTACT


NORMALLY CLOSE

LAMP CHANGE OVER CONTACT

THERMOSTAT DIODE

OUTLET

HEATING RESISTOR

SYMBOL LEGENDS
EARTH TITLE: Schematic SSVT Peranap r1

Document Number: REV:


01
Date: 1/13/2021 11:26 AM Sheet: 1/7
MAIN CIRCUIT BREAKER

INCOMING

L1 L2 L3 L1 L2 L3
NEUTRAL NEUTRAL NEUTRAL

-L3:X2
-F92:1
-F92:3
-F92:5
MCCB
F90 1 3 5

I>
800A 2 4 6

-XAC1:5
-XAC1:3
-XAC1:1
-XAC1:7

NEUTRAL L1 L2 L3

OUTGOING

MCCB CIRCUIT DIAGRAM

TITLE: Schematic SSVT Peranap r1

Document Number: REV:


01
Date: 1/13/2021 11:26 AM Sheet: 2/7
HEATING / LIGHTING 3P SOCKET INDICATION

-F90:2

-F90:4

-F90:6

-F90:1

-F90:3

-F90:5
-BB:N

-BB:N
1 2 3 4 5 6 7 8 9

XAC1
Red 4.0mm

Yellow 4.0mm

Black 4.0mm

F91 1 3 5 Blue 4.0mm 7 F92 1 3 5

I> I>
25A 2 4 6 8 6A 2 4 6
4.0mm

4.0mm

4.0mm

4.0mm

1.5mm

1.5mm

1.5mm

1.5mm
Yellow

Yellow
Black

Black
Blue

Blue
Red

Red
1 2 3 4 5 6 7 8 9 10 11 12
X1 X1 X1
XAC2
1.5mm

1.5mm

4.0mm

4.0mm

4.0mm
4.0mm

L1 L2 L3
Yellow

Black

Blue
Red

Red

Red

X2 X2 X2

XG91
B91
21 21 11 4
<φ PH N

22 22
3
S91 S92 12 PH T
2
XG1 PH S
L X1 X1 L 1
Gn/Ye
4.0mm PE
E91 E92 E93 PE Gn/Ye
PH R
5
4.0mm

4.0mm
Gn/Ye

N X2 X2 PE
PE1 N PE2 PE3 AC SUPPLY DIAGRAM
1.5mm

1.5mm

1.5mm
Blue

Blue

Blue

10 11 12
TITLE: Schematic SSVT Peranap r1
XAC1 Document Number: REV:
01
Date: 1/13/2021 11:26 AM Sheet: 3/7
MCCB / MCB TRIP INDICATION CB OPEN CB CLOSE
110V DC Distribution Board

+DC -DC

MK SSVT

1 2 3 4

XDC

12 14 12 14 12 14 22 24 12 14 22 24

F91 F92 F90 F90 KCO KCO

11 11 11 21 11 21

X1 X1
A1 A1
KACTR KCO LOP LCL
A2 A2 X2 Green X2 Red

Grey Grey Grey Grey


1.5mm 1.5mm 1.5mm 1.5mm

12 14 22 24 32 34 42 44

KACTR KACTR KCO KCO

11 21 31 41

1 2 3 4 5 6 7 8 9 10 11 12

XACTR

SAS PANEL
1 2 3 4 5 6 7 8 9 10 11 12
TRIP STATUS
CLOSE OPEN CB
TRIP SIGNAL TRIP SIGNAL MCCB MCCB MCCB MCCB TITLE: Schematic SSVT Peranap r1
MCCB / MCB MCCB / MCB OPEN CLOSE OPEN CLOSE Document Number: REV:
01
Date: 1/13/2021 11:26 AM Sheet: 4/7
1 2 3 4 5 6

XSSVT

7 8 9 10 11 12

13 14 15 16 17 18

TERMINAL SPARE

TITLE: Schematic SSVT Peranap r1

Document Number: REV:


01
Date: 1/13/2021 11:26 AM Sheet: 5/7
DEVICE DEVICE DEVICE DEVICE REMARK
MANUFACTURE DESIGNATION DESCRIPTION TYPE

ABB F90 MCCB T6N 800 MCCB 3P 36kA


3P PR222DS/P-LSI 320-800A
800A

ABB F91 MCB S203-C25


3P S2C-H6R
25A

ABB F92 MCB S203-C6


3P S2C-H6R
6A

FORT S91 DOOR SWITCH D4MC-5000


SPDT

FORT S92 DOOR SWITCH D4MC-5000


SPDT

PHILIPS E91 LED LAMP


220VAC / 4W

PHILIPS E92 LED LAMP


220VAC / 4W

LEIPOLE E93 HEATER JRQ100


220VAC / 100W

ABB L1 PILOT LAMP CL2 - 523R


220VAC
RED

ABB L2 PILOT LAMP CL2 - 523Y


220VAC
YELLOW

ABB L3 PILOT LAMP CL2 - 523G


MATERIAL LIST
220VAC
GREEN TITLE: Schematic SSVT Peranap r1

Document Number: REV:


01
Date: 1/13/2021 11:26 AM Sheet: 6/7
DEVICE DEVICE DEVICE DEVICE REMARK
MANUFACTURE DESIGNATION DESCRIPTION TYPE

LEIPOLE B91 THERMOSTAT JWT6011R

HAGER XG1 RECEPTACLE SN016


1P+N+PE
16A

MENNEKES XG91 RECEPTACLE 1551


3P+N+PE
32A

ABB KACTR RELAY CR-M110DC4


4CO CR-M4SS
110VDC CR/PM-22
CR-MH
ABB KCO RELAY CR-M110DC4
4CO CR-M4SS
110VDC CR/PM-22
CR-MH
PHOENIX XAC1 UT6
FEED THROUGH
TERMINAL

PHOENIX XAC2 UT6


FEED THROUGH
TERMINAL

PHOENIX XDC UT6


FEED THROUGH
TERMINAL

ENTRELEC XSSVT M4/6.SNB


DISCONNECT
TERMINAL

PHOENIX XACTR UT4


FEED THROUGH
TERMINAL

MATERIAL LIST

TITLE: Schematic SSVT Peranap r1

Document Number: REV:


01
Date: 1/13/2021 11:26 AM Sheet: 7/7
PT PLN (Persero) Unit Induk Pembangunan KSO PT ABB Sakti Industri - PT Waskita Karya (Persero) Tbk. PT PLN Enjiniring
Sumatera Bagian Tengah
CONTRACTOR'S REPLY

PEMBANGUNAN GARDU INDUK TEGANGAN EKSTRA TINGGI 500KV PERANAP


CONTRACT NO : 0740.PJ/DAN.02.02/DIR/2017
DATE : 28 DECEMBER 2017

No. No. Gambar Title Rev. Status Tanggapan PLN Jawaban Kontraktor

1. TPG sudah mengikuti


1. TPG (harus mengikuti) - Heating Resistor (Yes)
- Heating Resistor (Yes) - Mimic Diagram (Yes)
- Mimic Diagram (Yes) - Line Insulator (Yes)
- Line Insulator (Yes)
2. Sudah ditambahkan pada revisi selanjutnya untuk
2. MK keterangan berikut,
TPG & OUTLINE
- Ada gambar klem-klem terminal - Ada gambar klem-klem terminal
1 1HID1-2-8055-B737-4 DRAWING OF MK FOR B RFC
- Ada rel grounding - Ada rel grounding
SSVT
3. SSVT 3. Mimic diagram sudah ditambahkan. Titik neutral akan
- Jika terminasi Y Y maka harus ada grounding (titik neutral ditanahkan langsung.
ditanahkan langsung dan mimic diagram perlu ditambah)
4. Gambar wiring MK sudah dimasukkan ke dalam dokumen
4. Gambar wiring dalam MK akan masuk ke gambar mana? 1HID1-2-8055-B737-4

1
SSVT
TYPE TEST
T E S T S
Nº: 3/LE130 ‘

LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA

LCOE
FUNDACIÓN PARA EL FOMENTO DE LA INNOVACIÓN INDUSTRIAL
Centro Tecnológico UPM – Tecnogetafe
C/ Eric Kandel, 1 – 28906 Getafe (Madrid)
Teléfono: +34 91 491 81 68
www.f2i2.net

TYPE TEST REPORT 2017 03 3D 0097


OBJECT Voltage Transformer

MANUFACTURER Arteche

TYPE UG-550

APPLICANT Arteche Gas Insulated Transformers


Gerezpea, 15 – 01015 Vitoria (Álava)

TEST DATES From 2nd to 27th March 2017

DATE OF ISSUE 18th April 2017

RESULTS Tests performed passed according to IEC 61869-3 Std.

This report consists of 22 pages and 7 Annexes

Authorized signatory/s

Mr. Tomás García Aguado


Technical Responsible of Testing in HV Lab

CONDITIONS OF VALIDITY OF THIS DOCUMENT:

• The results of the tests refer exclusively to the sample which was tested.
• The above-mentioned sample is the one described in the Report and is the sample which was originally received, with any
modifications which may have been produced during the tests, in order that these could be correctly performed. These
modifications are documented in the LCOE files, and are available for inspection by any person or organization authorized to do so.
• Partial reproduction of this document is prohibited.
LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA

INDEX

Page Number
1 IDENTIFICATION OF THE TEST OBJECT ............................................................................................ 3
1.1 DESCRIPTION OF THE TEST OBJECT ........................................................................................................... 3
1.2 NOMINAL CHARACTERISTICS ASSIGNED BY THE MANUFACTURER ................................................................... 3
1.3 RATING PLATE OF VOLTAGE TRANSFORMER ............................................................................................... 4
1.4 PICTURES OF TEST OBJECT ...................................................................................................................... 5
2 GENERAL INFORMATION ............................................................................................................... 7
2.1 TESTS CARRIED OUT BY .......................................................................................................................... 7
2.2 MEASUREMENT UNCERTAINTY ................................................................................................................ 7
2.3 STANDARDS APPLIED ............................................................................................................................. 7
2.4 ADDITIONAL INFORMATION .................................................................................................................... 7
3 PERFORMED TESTS ........................................................................................................................ 8
3.1 VERIFICATION OF NAMEPLATE AND TERMINAL MARKINGS ............................................................................ 8
3.2 TEST FOR ACCURACY OF VOLTAGE TRANSFORMER ....................................................................................... 9
3.3 LIGHTNING IMPULSE TEST ON PRIMARY TERMINALS................................................................................... 10
3.4 WET TEST FOR OUTDOOR TYPE TRANSFORMERS. SWITCHING IMPULSE TEST. ................................................ 12
3.5 RADIO INTERFERENCE VOLTAGE MEASUREMENT ....................................................................................... 14
3.6 POWER FREQUENCY WITHSTAND TEST ON SECONDARY TERMINALS .............................................................. 15
3.7 TEMPERATURE-RISE TEST WITH THERMAL LIMITING OUTPUT ...................................................................... 16
3.8 SHORT-CIRCUIT WITHSTAND CAPABILITY TEST .......................................................................................... 18
3.9 TRANSMITTED OVERVOLTAGE TEST........................................................................................................ 19
3.10 MEASUREMENT OF NO-LOAD LOSSES AND EXCITATION CURRENT ................................................................ 20
3.11 MEASUREMENT OF LOAD LOSSES AND IMPEDANCE VOLTAGE ...................................................................... 21
4 SUMMARY AND CONCLUSIONS ................................................................................................... 22

ANNEX 1: Drawing of voltage transformer.


ANNEX 2: Lightning impulse test.
ANNEX 3: Switching impulse test.
ANNEX 4: Temperature-rise test.
ANNEX 5: Short-circuit withstand capability test.
ANNEX 6: Transmitted overvoltage test.
ANNEX 7: Routine tests performed at manufacturer’s factory.

Test Report Nº 2017 03 3D 0097 Page 2 of 22


LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA

1 IDENTIFICATION OF THE TEST OBJECT

Inductive Voltage Transformer

1.1 Description of the test object

Manufacturer: Arteche
Type: UG-550
Serial number: 1600018/1
According to Standard: IEC 61869-3
Year of manufacture: 2017

1.2 Nominal characteristics assigned by the manufacturer

Highest Voltage for equipment, Um: 550 kV


Rated power-frequency withstand test voltage: 680 kV
Rated lightning impulse withstand test voltage: 1550 kV
Rated switching impulse withstand test voltage: 1175 kV
Rated frequency: 50 Hz

Rated primary voltage, Un: 525 000/√3 V


Rated secondary current, Ir: 433 A
Rated ratio and terminal markings:

a-n Us 400/√3 V 100 VA Class 1

Thermal limiting output: 100 kVA


Rated voltage factor: 1.2 Un Continuous Operation
Thermal Insulation class A
Ambient temperature category: -10 ºC / +40 ºC

Total weight: 4470 Kg


SF6 weight: 132 Kg
Rated SF6 pressure: 0.50 MPaG
Alarm SF6 pressure: 0.45 MPaG
Minimum SF6 pressure: 0.43 MPaG
Maximum SF6 pressure: 0.70 MPaG

NO TEXT BELOW THE LINE

Test Report Nº 2017 03 3D 0097 Page 3 of 22


LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA

1.3 Rating plate of voltage transformer

Picture 1.1 – Voltage transformer UG-550. Rating plate.

NO TEXT BELOW THE LINE

Test Report Nº 2017 03 3D 0097 Page 4 of 22


LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA

1.4 Pictures of test object

Picture 1.2 – Voltage transformer UG-550 during accuracy test.

NO TEXT BELOW THE LINE

Test Report Nº 2017 03 3D 0097 Page 5 of 22


LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA

Picture 1.3 – Voltage transformer UG-550 during lightning impulse test.

NO TEXT BELOW THE LINE

Test Report Nº 2017 03 3D 0097 Page 6 of 22


LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA

2 GENERAL INFORMATION

2.1 Tests carried out by

Tests have been performed in L.C.O.E. High Voltage laboratory place at Tecnogetafe, Eric
Kandel Street, number 1 – 28906 Getafe (Madrid) except short-circuit withstand capability test
was performed at High Power Laboratory, located at Parque Empresarial Boroa, parcel 24 –
48340 Amorebieta (Vizcaya).

Name Company

Mr. José Antonio Bregel Serna L.C.O.E. (High Voltage Department)


Mr. Pablo Cerezo Gallego L.C.O.E. (High Voltage Department)
Mr. Miguel Corriols Delgado L.C.O.E. (High Voltage Department)
Mr. Tomás García Aguado L.C.O.E. (High Voltage Department)
Mr. Juan de Dios López Serrano L.C.O.E. (High Voltage Department)

Tests performed on voltage transformer have been witnessed by:

Name Company

Mr. Daniel Seoane SGS Tecnos, S.A.


Mrs. Susana Simal Dettmar Grupo SGS España (short-circuit test)

2.2 Measurement uncertainty

The uncertainty of the test is calculated and at the disposal of the applicant.

2.3 Standards applied

Tests have been performed according to following Standards:

- UNE-EN 61869-1:2010, “Transformadores de medida. Parte 1: Requisitos generales”,


Spanish official version of the European Standard EN 61869-1:2009, which adopts the
modified International Standard IEC 61869-1:2007.

- UNE-EN 61869-3:2012, “Transformadores de medida. Parte 3: Requisitos adicionales


para los transformadores de tension inductivos”, Spanish official version of the European
Standard EN 61869-3:2011, which adopts the International Standard IEC 61869-3:2011.

- UNE-EN 60060-1:2012, “Técnicas de ensayo de alta tension. Parte 1: Definiciones


generales y requisitos de ensayo” Spanish official version of the European Standard EN
60060-1:2010, which adopts the modified International Standard IEC 60060-1:2010.

2.4 Additional information

In this report, voltage values corresponding to power frequency withstand tests are expressed in
peak value divided by root of two and voltage values corresponding to lightning impulse tests are
expressed in peak value.

Test Report Nº 2017 03 3D 0097 Page 7 of 22


LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA

3 PERFORMED TESTS

3.1 Verification of nameplate and terminal markings

• Test date: 2nd March 2017

• Procedure: UNE-EN 61869-3 section 6.13

Information of nameplate was verified on voltage transformer according to section


6.13.302 of UNE-EN 61869-3 Standard and terminal markings were verified according to
section 6.13.301 of UNE-EN 61869-3 Standard.

• Results:

Nameplate of voltage transformer includes the minimum information required and satisfies
section 6.13.302 of UNE-EN 61869-3 Standard.

Terminal markings of voltage transformer satisfy section 6.13.301 of UNE-EN 61869-3


Standard.

• Conclusion: Test passed

NO TEXT BELOW THE LINE

Test Report Nº 2017 03 3D 0097 Page 8 of 22


LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA

3.2 Test for accuracy of voltage transformer

• Test date: 2nd March 2017

• Procedure: UNE-EN 61869-3 section 7.2.6

Ratio and phase displacement errors of voltage transformer were measured according to
section 7.2.6 of UNE-EN 61869-3 Standard.

• Results of accuracy test. Primary A-N and secondary winding a-n.

Errors
Voltage
Ratio Burden
(% Un)
Ratio (%) Phase (min)

80 -0.061 +0.1
0 VA
100 -0.059 +0.2
Cos phi 0.8
120 -0.055 +0.1
80 -0.063 +0.2
525000/√3 V 25 VA
100 -0.061 +0.2
/ 400/√3 V Cos phi 0.8
120 -0.056 +0.2
80 -0.066 +0.0
100 VA
100 -0.064 +0.0
Cos phi 0.8
120 -0.060 -0.0

Voltage ratio and phase displacement errors are between the limits specified for
the accuracy class for metering 1.

• Results of accuracy test with thermal limiting output.

Errors
Voltage
Ratio Burden
(% Un)
Ratio (%) Phase (min)

80 50 kVA -0.55 -129

525000/√3 V 100 Cos phi 1 -0.52 -125


/ 400/√3 V 80 100 kVA -1.12 -245
100 Cos phi 1 -1.08 -242

• Conclusion: Test passed

NO TEXT BELOW THE LINE

Test Report Nº 2017 03 3D 0097 Page 9 of 22


LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA

3.3 Lightning impulse test on primary terminals

• Test date: 8th March 2017

• Procedure: UNE-EN 61869-3 section 7.2.3

Lightning impulse test on primary terminals of voltage transformer was performed


according to section 7.2.3 of UNE-EN 61869-3 Standard.

Peak value of full impulses was equal to 1550 kV without correction due to local
atmospheric conditions and test wave polarity of the impulses was both positive and
negative.

Terminal N, one terminal of each secondary winding and tank were connected to ground
during the impulse test.

Sequence of the impulse test:

1 Reduced positive impulse (less than 80 % of test voltage)


3 Full positive impulses (100 % of test voltage)

1 Reduced negative impulse (less than 80 % of test voltage)


3 Full negative impulses (100 % of test voltage)

• Lightning impulse test with positive polarity. Test results:

Lightning Impulse Test – Positive polarity


Peak Value of impulses 1550 kV
Positive full impulses 3
Front Time t1 1.47 µs
Time to half value t2 58.7 µs
Ambient Conditions
Ambient temperature 15.5 ºC
Relative Humidity 47.4 %
Atmospheric Pressure 957.8 hPa
Filling pressure during the test 0.44 MPaG

NO TEXT BELOW THE LINE

Test Report Nº 2017 03 3D 0097 Page 10 of 22


LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA

• Lightning impulse test with negative polarity. Test results:

Lightning Impulse Test - Negative polarity


Peak Value of full impulses 1550 kV
Negative full impulses 3
Front Time t1 1.48 µs
Time to half value t2 58.3 µs
Ambient Conditions
Ambient temperature 15.5 ºC
Relative Humidity 47.4 %
Atmospheric Pressure 957.8 hPa
Filling pressure during the test 0.44 MPaG

• Test result:

No external flashover or insulation damage was detected during the impulse test.

• Conclusion: Test passed

NO TEXT BELOW THE LINE

Test Report Nº 2017 03 3D 0097 Page 11 of 22


LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA

3.4 Wet test for outdoor type transformers. Switching Impulse Test.

• Test date: 9th March 2017

• Procedure: UNE-EN 61869-3 section 7.2.4

Wet test for outdoor type transformers was performed on voltage transformer according to
sections 7.2.3.3 and 7.2.4 of UNE-EN 61869-1 Standard.

Fifteen switching impulses of peak voltage equal to 1175 kV, corrected due to local
atmospheric conditions, were applied on HV terminal of voltage transformer and ground
under wet condition according to UNE-EN 60060-1 Standard.

Terminal N, one terminal of each secondary winding and tank were connected to ground
during the impulse test.

Sequence of the impulse test:

1 Reduced positive impulse (less than 80 % of test voltage)


15 Full positive impulses (100 % of test voltage)

• Switching impulse test with positive polarity. Test results:

Switching Impulse Test - Positive polarity


Peak Value of impulses (normal conditions) 1175 kV
Peak value of impulses (local conditions) 1164 kV
Positive full impulses 15
Front Time t1 288.6 µs
Time to half value t2 1557 µs
Rain parameters
Horizontal flow rate 1.35 mm / min
Vertical flow rate 1.70 mm / min
Water conductivity 106.5 µS / cm
Water temperature 12.1 ºC
Ambient Conditions
Ambient temperature 15.2 ºC
Atmospheric Pressure 958.2 hPa
Filling pressure during the test 0.44 MPaG

NO TEXT BELOW THE LINE

Test Report Nº 2017 03 3D 0097 Page 12 of 22


LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA

Number Impulse Peak Value (kV) T1 (µs) T2 (µs) Result


1 Reduced 616 286.8 2151 OK
2 Full 1173 292.4 1556 OK
3 Full 1152 290.6 1526 OK
4 Full 1160 288.0 1531 OK
5 Full 1159 283.6 1578 OK
6 Full 1159 283.0 1567 OK
7 Full 1164 287.0 1553 OK
8 Full 1165 288.4 1560 OK
9 Full 1163 290.6 1558 OK
10 Full 1165 292.6 1559 OK
11 Full 1161 284.9 1586 OK
12 Full 1162 287.1 1566 OK
13 Full 1165 290.4 1557 OK
14 Full 1165 290.7 1558 OK
15 Full 1162 287.9 1557 OK
16 Full 1163 292.2 1550 OK

• Test result:

No external flashover or insulation damage was detected during switching impulse test.

• Conclusion: Test passed

NO TEXT BELOW THE LINE

Test Report Nº 2017 03 3D 0097 Page 13 of 22


LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA

3.5 Radio interference voltage measurement

• Test date: 9th March 2017

• Procedure: UNE-EN 61869-1 section 7.2.5

Radio interference voltage measurement was performed on voltage transformer according


to section 7.2.5 of UNE-EN 61869-1 Standard.

Test voltage of 476.3 kV (1.5 Um/√3), 50 Hz was applied for 30 seconds between high
voltage primary terminal of voltage transformer and ground. Terminal N, one terminal of
each secondary winding and tank were connected to ground during the test.

Then test voltage was reduced to 349.3 kV (1.1 Um/√3) and radio interference voltage was
measured during 30 seconds with measuring frequency equal to 1.26 MHz.

• Test results:

RIV Measurement
Test voltage Level 1 476.3 kV
Test voltage Level 2 349.3 kV
Test frequency 50 Hz
Test duration 30 s (each level)
RIV measuring frequency 1.26 MHz
Ambient Conditions
Ambient temperature 21.4 ºC
Relative Humidity 39.7 %
Atmospheric Pressure 955.7 hPa

Test Voltage (kV) RIV (µV) RIV Limits (µV) Result

476.3 kV 645.7 µV - -
349.3 kV 70.0 µV 2500 µV (IEC) OK

• Conclusion: Test passed

NO TEXT BELOW THE LINE

Test Report Nº 2017 03 3D 0097 Page 14 of 22


LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA

3.6 Power frequency withstand test on secondary terminals

• Test date: 10th March 2017

• Procedure: UNE-EN 61869-3 section 7.3.4

Power frequency withstand test on secondary terminals was performed on voltage


transformer according to section 7.3.4 of UNE-EN 61869-3 Standard.

Test voltage equal to 3 kV, 50 Hz was applied during 60 seconds between short-circuited
terminals of each secondary winding and earth with the primary terminals of the
transformer, other secondary terminals and tank connected to ground.

Power frequency withstand tests was performed on N terminal of voltage transformer


according to section 7.3.1 of UNE-EN 61869-3 Standard.

Test voltage of 3 kV, 60 Hz was applied during 60 seconds between terminal N of primary
winding and earth with secondary terminals short-circuited and tank of the transformer
connected to ground.

• Test results:

Voltage applied to secondary terminals a-n (winding 1)


Test voltage 3 kV
Test frequency 50 Hz
Test duration 60 s
Voltage applied to secondary terminals a-n (winding 2)
Test voltage 3 kV
Test frequency 50 Hz
Test duration 60 s
Applied Voltage test on terminal N
Test voltage 3 kV
Test frequency 50 Hz
Test duration 60 s
Ambient Conditions
Ambient temperature 16.9 ºC
Relative Humidity 46.8 %
Atmospheric Pressure 955.2 hPa

No flashover or insulation damage was detected during the tests.

• Conclusion: Test passed

Test Report Nº 2017 03 3D 0097 Page 15 of 22


LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA

3.7 Temperature-rise test with thermal limiting output

• Test date: 14th, 15th and 16th March 2017

• Procedure: UNE-EN 61869-3 section 7.2.2

Temperature-rise test was performed on voltage transformer according to section 7.2.2 of


UNE-EN 61869-3 Standard.

Temperature rise of primary winding A-N and secondary winding a-n were measured by
the increase-in-resistance method and several thermocouples were placed over the
surface of the transformer tank to control external temperatures.

Three thermocouples were placed around the test object to control the ambient
temperature.

A resistive burden was connected to secondary winding of voltage transformer, test


voltage around rated was applied on HV terminal of voltage transformer and the rated
secondary current (Ir equal to 433 A) was controlled during the test.

Rated secondary current was applied on voltage transformer for several hours to reach
stable thermal condition and winding resistances were measured again.

• Temperature-rise of windings. Results:

Resistance measurement of windings


Test secondary current 433 A
A-N a-n (winding 1) a-n (winding 2)
Ro (Ohm) 621.6 Ω 1.378 mΩ 2.105 mΩ
θo (ºC) 18.0 ºC
Rt (Ohm) 695 Ω 1.562 mΩ 2.358 mΩ
θf (ºC) 20.1 ºC
∆θ (K) 27.8 K ± 3 K 31.7 K ± 3 K 28.3 K ± 3 K

Temperature rises of primary winding A-N and secondary winding a-n (two sections) were
lower than limit specified of 60 K (thermal insulation class A) specified by UNE-EN 61869-
1 and UNE-EN 61869-3 Standards.

NO TEXT BELOW THE LINE

Test Report Nº 2017 03 3D 0097 Page 16 of 22


LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA

• Temperature-rise measurement of external parts. Results:

Ambient Temperature before the test 15.9 ºC


Ambient Temperature after the test 20.1 ºC
Secondary test voltage (U2) during the test 220 V
Secondary current (Ir) during the test 433 A
Resistive load during the test 97 kW
Test frequency (f) 50 Hz
SF6 pressure before the test 0.45 MPaG
SF6 pressure after the test 0.50 MPaG
Atmospheric Pressure after the test 953.4 hPa
Temperature rise – Terminal Box 11.1 K
Temperature rise – External 1 Middle Part 11.0 K
Temperature rise – External 2 Upper Part 12.1 K
Temperature rise – External 3 Middle Part 11.4 K
Temperature rise – External 4 Lower Part 8.6 K
Temperature rise – External 5 Middle Part 11.5 K
Temperature rise – External 6 Upper Part 12.5 K
Temperature rise – External 7 Middle Part 11.8 K
Temperature rise – External 8 Lower Part 10.2 K
Temperature rise – External 9 Middle Part 10.9 K

Temperature rise of external and metallic parts of voltage transformer was lower than limit
specified of 60 K (thermal insulation class A) specified by UNE-EN 61869-1 Standard.

• Conclusion: Test passed

NO TEXT BELOW THE LINE

Test Report Nº 2017 03 3D 0097 Page 17 of 22


LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA

3.8 Short-circuit withstand capability test

• Test date: 27th March 2017

• Procedure: UNE-EN 61869-3 section 7.2.301

Short-circuit withstand capability test was performed on voltage transformer according to


section 7.2.301 of UNE-EN 61869-3 Standard.

The voltage transformer was energized from the secondary winding with the primary
winding short-circuited. Test voltage equal to rated secondary voltage was applied to
voltage transformer for one second with test frequency equal to 50 Hz.

• Test results. Primary winding A-N short-circuited.

Short-circuit test terminals A-N


Test voltage 235.7 V
Test frequency 50 Hz
Test duration 1.05 s
Secondary test current 6.14 kA
Ambient temperature 15 ºC

Visual inspection of test object

• Test date: 27h March 2017

• Results of test:

After short-circuit test voltage transformer is not visibly damaged and the insulation next to
the surface of both the primary and the secondary windings does not show significant
deterioration.

Accuracy test and routine dielectric tests were performed on voltage transformer after
short-circuit test at manufacturer Lab and witnessed by LCOE technician. All tests
performed passed successfully.

• Conclusion: Test passed

NO TEXT BELOW THE LINE

Test Report Nº 2017 03 3D 0097 Page 18 of 22


LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA

3.9 Transmitted Overvoltage Test

• Test date: 6th March 2017

• Procedure: UNE-EN 61869-1 section 7.4.4

• Procedure:

Transmitted overvoltage test was performed on voltage transformer in accordance with


section 7.4.4 of UNE-EN 61869-1 Standard.

Ten reduced impulse with a peak value (Up) of around 5.56 kV were applied to terminal A
of primary winding. Test wave polarity was positive, front time around 500 ns and time to
half value above 50 µs.

The transmitted voltage at the open secondary terminals (Us) was measured by using an
oscilloscope having a bandwidth of 500 MHz and input impedance equal to 50 Ω.

Terminal N, one terminal of each secondary winding and tank were connected to ground
during the impulse test.

• Transmitted overvoltage test.

Transmitted overvoltage test


Peak Value of primary impulses,U1 5.56 kV
Front Time t1 540 ns
Time to half value t2 > 50 µs
Limit of peak value on secondary winding 1.6 kV
Applied peak value, U1 5.56 kV
Secondary a-n Transmitted peak voltage, U2 4.50 V
Calculated peak value on secondary 0.58 kV
Ambient Conditions
Ambient temperature 17.5 ºC
Relative Humidity 64 %
Atmospheric Pressure 955 hPa

Transmitted peak voltage measured on secondary winding was lower than limit value
specified by UNE-EN 61869-1 Standard.

• Conclusion: Test passed

NO TEXT BELOW THE LINE

Test Report Nº 2017 03 3D 0097 Page 19 of 22


LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA

3.10 Measurement of no-load losses and excitation current

• Test date: 3rd March 2017

• Procedure:

Measurement of no-load losses and excitation current was performed on voltage


transformer according to specification of the manufacturer.

The rated voltage of 230 V, 50 Hz was applied to secondary winding of voltage


transformer with high voltage terminal open-circuited. No-load losses and excitation
current were measured during the test.

• Test results:

No-load losses and excitation current


Test voltage Ur 230.2 V
Test frequency 50 Hz
Secondary Excitation current (A) 48.6 A
Secondary Excitation current (%) 11.2 %
No-load losses 642 W
Total Power 11.2 kVA
Power factor 0.057
Ambient temperature 15.9 ºC

Then test voltage was applied on primary winding of voltage transformer up to 1.2 Ur and
test current from N terminal to ground was measured.

Excitation primary current up to 1.2 Ur

Excitation Current Excitation current


Primary Voltage (kV)
(mA) RMS Value (mA) Peak Value
20.1 0.39 0.85
50.5 1.14 1.70
75.8 1.82 2.67
100.6 2.46 3.81
150.6 3.79 5.69
200.0 5.16 7.84
242.4 6.35 9.58
304.1 8.07 12.11
364.2 9.69 14.59
Ambient temperature 16.7 ºC
Test Frequency 50 Hz

• Conclusion: Test passed

The tests performed is out of the scope of ENAC Accreditation

Test Report Nº 2017 03 3D 0097 Page 20 of 22


LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA

3.11 Measurement of load losses and impedance voltage

• Test date: 3rd March 2017

• Procedure:

Measurement of load losses and short-circuit voltage was performed on voltage


transformer according to specification of the manufacturer.

Test voltage was applied to secondary winding of voltage transformer with high voltage
winding short-circuited, up to secondary current was equal to rated current Ir 433 A. Load
losses and impedance voltage were measured during the test.

• Test results:

Load losses and impedance voltage


Test current Ir 433.1 A
Test frequency 50 Hz
Impedance voltage (V) 16.85 V
Impedance voltage (%) 7.33 %
Load losses 703 W
Total Power 7298 VA
Power factor 0.096
Ambient temperature 16.3 ºC

• Conclusion: Test passed

The test performed is out of the scope of ENAC Accreditation

NO TEXT BELOW THE LINE

Test Report Nº 2017 03 3D 0097 Page 21 of 22


LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA

4 SUMMARY AND CONCLUSIONS

The following tests according to IEC 61869-1 and IEC 61869-3 Standards have been performed
on voltage transformer manufactured by Arteche Nissin, type UG-550 and identification
1600018/1.

- Verification of nameplate and terminal markings.


- Accuracy test of voltage transformer.
- Lightning impulse test on primary terminals.
- Wet test for outdoor type transformer.
- Radio interference voltage measurement.
- Power frequency withstand test on secondary terminals.
- Temperature-rise test with thermal limiting output.
- Short-circuit withstand capability test.
- Transmitted overvoltage test.

Measurement of no-load losses, excitation current, load-losses and impedance voltage of voltage
transformer have been performed according to specification of the manufacturer.

All test performed on voltage transformer have been successful.

NO TEXT BELOW THE LINE

Test Report Nº 2017 03 3D 0097 Page 22 of 22


LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA Annex 1 to Test Report 2017 03 3D 0097
Page 1 of 2

Annex 1
Drawing of voltage transformer
LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA Annex 1 to Test Report 2017 03 3D 0097
Page 2 of 2

 Drawing of voltage transformer type UG-550.


LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA Annex 2 to Test Report 2017 03 3D 0097
Page 1 of 3

Annex 2
Lightning impulse test
LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA Annex 2 to Test Report 2017 03 3D 0097
Page 2 of 3

 Lightning impulse test. Positive polarity.


LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA Annex 2 to Test Report 2017 03 3D 0097
Page 3 of 3

 Lightning impulse test. Negative polarity.


LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA Annex 3 to Test Report 2017 03 3D 0097
Page 1 of 2

Annex 3
Switching Impulse Test
LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA Annex 3 to Test Report 2017 03 3D 0097
Page 2 of 2

 Switching Impulse test. Impulse nº 1.

 Switching Impulse test. Impulse nº 15.


LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA Annex 4 to Test Report 2017 03 3D 0097
Page 1 of 3

Annex 4
Temperature-rise test
LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA Annex 4 to Test Report 2017 03 3D 0097
Page 2 of 3

 Figure 1 – Temperature-Rise Test with thermal limiting output

Secondary Test Voltage ⇒ 220 V


Secondary Test Current ⇒ 433 A
LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA Annex 4 to Test Report 2017 03 3D 0097
Page 3 of 3

 Figure 2 – Thermo-graphic Camera Images.


LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA Annex 5 to Test Report 2017 03 3D 0097
Page 1 of 2

Annex 5
Short-circuit withstand capability test
LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA Annex 5 to Test Report 2017 03 3D 0097
Page 2 of 2

 Short-circuit test on primary winding A-N.

Test voltage ⇒ 235.7 V


Test duration ⇒ 1.05 s
Secondary test current ⇒ 6.14 kA
LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA Annex 6 to Test Report 2017 03 3D 0097
Page 1 of 2

Annex 6
Transmitted overvoltage test
LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA Annex 6 to Test Report 2017 03 3D 0097
Page 2 of 2

 Figure 1 – Transmitted overvoltage test. Secondary winding a-n. Impulse 1.

 Figure 2 – Transmitted overvoltage test. Secondary winding a-n. Impulse 10.


LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA Annex 7 to Test Report 2017 03 3D 0097
Page 1 of 9

Annex 7
Routine tests performed at Arteche factory
LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA Annex 7 to Test Report 2017 03 3D 0097
Page 2 of 9

A GENERAL INFORMATION

A.1 Tests witnessed by

Tests were performed at Arteche factory located at Derio Bidea, number 28 - 48100 Munguía
(Vizcaya) by Arteche technicians and by using manufacturer equipment. Tests have been
witnessed by:

Name Company

Mr. Tomás García Aguado L.C.O.E. (High Voltage Department)


Mrs. Susana Simal Dettmar Grupo SGS España

A.2 Standards applied

Tests have been performed according to following Standards:

- UNE-EN 61869-1:2010, “Transformadores de medida. Parte 1: Requisitos generales”,


Spanish official version of the European Standard EN 61869-1:2009, which adopts the
modified International Standard IEC 61869-1:2007.

- UNE-EN 61869-3:2012, “Transformadores de medida. Parte 3: Requisitos adicionales para


los transformadores de tension inductivos”, Spanish official version of the European
Standard EN 61869-3:2011, which adopts the International Standard IEC 61869-3:2011.

- UNE-EN 60060-1:2012, “Técnicas de ensayo de alta tension. Parte 1: Definiciones


generales y requisitos de ensayo” Spanish official version of the European Standard EN
60060-1:2010, which adopts the modified International Standard IEC 60060-1:2010.

A.3 Additional information

In this report, voltage values corresponding to power frequency withstand tests are expressed in
peak value divided by root of two and voltage values corresponding to lightning impulse tests are
expressed in peak value.

NO TEXT BELOW THE LINE


LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA Annex 7 to Test Report 2017 03 3D 0097
Page 3 of 9

B PERFORMED TESTS

B.1 Power frequency withstand test on primary terminals

• Test date: 12th April 2017

• Procedure: UNE-EN 61869-3 section 7.3.1

Power frequency withstand tests was performed on primary terminals of voltage transformer
after short-circuit withstand capability test according to section 7.3.1 of UNE-EN 61869-3
Standard.

Test voltage of 680 kV, 120 Hz was applied during 50 seconds between high voltage
terminal of primary winding and earth with terminal N, one terminal of each secondary
winding and tank of the transformer connected to ground.

Test voltage of 3 kV, 50 Hz was applied during 60 seconds between terminal N of primary
winding and earth with secondary terminals short-circuited and tank of the transformer
connected to ground.

• Test Parameters:

Induced voltage test on winding A-N


Test voltage 680 kV
Test frequency 120 Hz
Test duration 50 s
Applied voltage test on terminal N
Test voltage 3 kV
Test frequency 50 Hz
Test duration 60 s
Ambient Conditions
Ambient temperature 13.7 ºC
Relative Humidity 60.3 %
Atmospheric Pressure 1016.7 hPa
Filling pressure during the test 0.43 MPaG

• Results:

No flashover or insulation damage was detected during the tests.

• Conclusion: Test passed

NO TEXT BELOW THE LINE


LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA Annex 7 to Test Report 2017 03 3D 0097
Page 4 of 9

B.2 Partial discharges measurement

• Test date: 12th April 2017

• Procedure: UNE-EN 61869-3 section 7.3.2

Partial discharges measurement was performed on voltage transformer after short-circuit


withstand capability test according to method B of section 7.3.2 of UNE-EN 61869-3
Standard.

Test voltage of 550 kV (higher than 80 % of rated power-frequency test voltage) , 120 Hz
was applied during 60 seconds between high voltage terminal of primary winding and earth
with terminal N, one terminal of the secondary winding and tank of the transformer
connected to ground.

Partial discharges were measured while test voltage applied on primary terminal was equal
to 550 kV (Um) and 381 kV (1.2 Um/√3).

• Test results:

Partial Discharges Measurement


Excitation Voltage 550 kV
Test Frequency 120 Hz
Test Duration 60 s
Test Voltage 550 kV
Level 1 Partial Discharges Level < 6 pC
Partial Discharges Limit 10 pC
Test Voltage 381 kV
Level 2 Partial Discharges Level < 3 pC
Partial Discharges Limit 5 pC

Partial discharges measured at test voltage equal to Um and 1.2 Um/√3 were lower than limit
specified by UNE-EN 61869-3 Standard.

• Conclusion: Test passed

NO TEXT BELOW THE LINE


LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA Annex 7 to Test Report 2017 03 3D 0097
Page 5 of 9

B.3 Test for accuracy of voltage transformer

• Test date: 12th April 2017

• Procedure: UNE-EN 61869-3 section 7.2.6

Ratio and phase displacement errors of voltage transformer were measured after short-
circuit withstand capability test according to section 7.2.6 of UNE-EN 61869-3 Standard.

• Results of accuracy test. Primary A-N and secondary winding a-n.

Errors
Voltage
Ratio Burden
(% Un)
Ratio (%) Phase (min)

80 -0.019 -1.2
100 0 VA -0.020 -1.2
120 -0.018 -1.2
80 -0.021 -1.2
525000/√3 V 25 VA
100 -0.022 -1.2
/ 400/√3 V Cos phi 0.8
120 -0.020 -1.2
80 -0.026 -1.3
100 VA
100 -0.027 -1.3
Cos phi 0.8
120 -0.025 -1.3

Voltage ratio and phase displacement errors are between the limits specified for the
accuracy class for metering 1.

• Conclusion: Test passed

NO TEXT BELOW THE LINE


LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA Annex 7 to Test Report 2017 03 3D 0097
Page 6 of 9

B.4 Power frequency withstand test on secondary terminals

• Test date: 12th April 2017

• Procedure: UNE-EN 61869-3 section 7.3.4

Power frequency withstand test on secondary terminals was performed on voltage


transformer after short-circuit withstand capability test according to section 7.3.4 of UNE-EN
61869-3 Standard.

Test voltage equal to 3 kV, 50 Hz was applied during 60 seconds between short-circuited
terminals of secondary winding and earth with the primary terminals of the transformer and
tank connected to ground.

• Test results:

Voltage applied to secondary terminals a-n


Test voltage 3 kV
Test frequency 50 Hz
Test duration 60 s
Ambient Conditions
Ambient temperature 14.2 ºC
Relative Humidity 60.3 %
Atmospheric Pressure 1016.7 hPa

No flashover or insulation damage was detected during the test.

• Conclusion: Test passed

NO TEXT BELOW THE LINE


LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA Annex 7 to Test Report 2017 03 3D 0097
Page 7 of 9

C EQUIPMENT USED TO PERFORM THE TESTS

All equipment used during the performed tests was calibrated and satisfied technical requirements
according to UNE-EN 61869-3 and UNE-EN 60060-1 Standard.

High Voltage AC Measuring System.

Manufacturer: HIMALAYAL / MAKANG


Internal Code: 501
Last calibration date: February 2016
Calibration interval: 2 years
Certificate of Calibration: ENAC / ILAC 2016023C0047
Calibration Laboratory: LCOE

Partial Discharge Meter.

Manufacturer: YANGZHOU
Internal Code: 424
Last calibration date: June 2015
Calibration interval: 2 years
Certificate of Calibration: ENAC / ILAC 201506600855
Calibration Laboratory: LCOE

Partial Discharge Calibrator.

Manufacturer: OMICRON
Internal Code: 534
Last calibration date: October 2016
Calibration interval: 2 years
Certificate of Calibration: ENAC / ILAC 2016103B0448
Calibration Laboratory: LCOE

Voltage Transformer Ratio Measuring System.

Manufacturer: HAEFELY / ZERA


Internal Code: 512 / 502 / 511
Last calibration date: February 2016
Calibration interval: 2 years
Certificate of Calibration: ENAC / ILAC 2016023C0046
Calibration Laboratory: LCOE

Electronic Standard Voltage Burden.

Manufacturer: ZERA
Internal Code: 514
Last calibration date: January 2017
Calibration interval: 2 years
Certificate of Calibration: ENAC / ILAC 201701600040
Calibration Laboratory: LCOE
LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA Annex 7 to Test Report 2017 03 3D 0097
Page 8 of 9

High Voltage AC Generator.

Manufacturer: SEFELEC
Internal Code: 523
Last calibration date: October 2016
Calibration interval: 2 years
Certificate of Calibration: ENAC / ILAC 2016103C0467
Calibration Laboratory: LCOE

D PICTURE OF VOLTAGE TRANSFORMER


LABORATORIO CENTRAL OFICIAL DE ELECTROTECNIA Annex 7 to Test Report 2017 03 3D 0097
Page 9 of 9

E SUMMARY AND CONCLUSIONS

The following tests according to IEC 61869-1 and IEC 61869-3 Standards have been performed
after type tests on voltage transformer manufactured by Arteche, type UG-550 and identification
1600018/1.

- Power frequency withstand test on primary terminals.


- Partial discharges measurement.
- Test for accuracy of voltage transformer.
- Power frequency withstand test on secondary terminals.

All routine tests performed on voltage transformer have been successful.

NO TEXT BELOW THE LINE


SSVT
REFERENCE LIST
SALES REFERENCE - 2014 to 2020
MODEL UG-550 & UG-420

Iten Name Customer Destination Qty EXW date


UP-420 RED ELECTRICA DE ESPAÑA S.A.U. SPAIN 3,0 05/12/2014
UP-420 RED ELECTRICA DE ESPAÑA S.A.U. SPAIN 3,0 29/05/2015
UP-420 RED ELECTRICA DE ESPAÑA S.A.U. SPAIN 3,0 29/05/2015
UP-420 EMPOWER AS USA 6,0 20/11/2015
UG-550 GRID SOLUTIONS CHILE, S.A CHILE 6,0 14/10/2016
UP-420 EMPOWER AS USA 1,0 18/07/2017
UP-420 EMPOWER AS USA 1,0 18/07/2017
UP-420 EMPOWER AS USA 1,0 30/08/2017
UP-420 EMPOWER AS USA 1,0 30/08/2017
UP-420 EMPOWER AS USA 1,0 30/08/2017
UP-420 EMPOWER AS USA 1,0 30/08/2017
UG-550 GRID SOLUTIONS CHILE, S.A CHILE 1,0 22/03/2018
UG-550 GRID SOLUTIONS CHILE, S.A CHILE 1,0 04/06/2018
UG-420 INGEMAS MEXICO, S.A. DE C.V MEXICO 3,0 08/06/2018
UG-550 GRID SOLUTIONS CHILE, S.A CHILE 1,0 11/06/2018
UG-550 GRID SOLUTIONS CHILE, S.A CHILE 1,0 11/06/2018
UP-420 INGEMAS MEXICO, S.A. DE C.V MEXICO 1,0 21/01/2019
UP-420 INGEMAS MEXICO, S.A. DE C.V MEXICO 1,0 21/01/2019
UP-420 INGEMAS MEXICO, S.A. DE C.V MEXICO 1,0 01/02/2019
UP-420 INGEMAS MEXICO, S.A. DE C.V MEXICO 1,0 01/02/2019
UP-420 INGEMAS MEXICO, S.A. DE C.V MEXICO 1,0 23/04/2019
UP-420 INGEMAS MEXICO, S.A. DE C.V MEXICO 1,0 23/04/2019
UP-420 INGEMAS MEXICO, S.A. DE C.V MEXICO 1,0 13/05/2019
UP-420 INGEMAS MEXICO, S.A. DE C.V MEXICO 1,0 13/05/2019
UP-420 ACTOM TRANSMISSION & DISTRIBUTION L SOUTH AFRICA 7,0 29/05/2019
UP-420 ACTOM TRANSMISSION & DISTRIBUTION L SOUTH AFRICA 7,0 21/06/2019
UP-420 ACTOM TRANSMISSION & DISTRIBUTION L SOUTH AFRICA 7,0 28/06/2019
UP-420 ACTOM TRANSMISSION & DISTRIBUTION L SOUTH AFRICA 7,0 28/06/2019
UP-420 PROYECTO NUÑEZ DE BALBOA, S.L. SPAIN 3,0 10/12/2019
UG-550 TRANSENER S.A. ARGENTINA 4,0 30/04/2020
SSVT
BROCHURE/CATALOGUE
5. POWER VOLTAGE
TRANSFORMERS
Oil-paper insulation
Gas insulation

› 245 kV Transformer
for substation auxiliary
services, model UTP.
Coyote Switch (USA).

42 Instrument transformers | High voltage


5. POWER VOLTAGE TRANSFORMERS > Oil-paper and gas insulation

INTRODUCTION
This type of voltage transformer can supply
several kVA low voltage power directly from a
high voltage transmission line.

It offers all the benefits of a potential


transformer with the applications of a Oil-paper insulation:
distribution transformer.
model UT up to 245 kV and
10 kVA;
model UTP up to 362 kV
and 333 kVA.

Gas insulation:
model UG up to 550 kV and
100 kVA.

› Model UTP › Model UT › Model UG

Instrument transformers | High voltage 43


5. POWER VOLTAGE TRANSFORMERS > Oil-paper and gas insulation

APPLICATIONS
1. Substations auxiliary services power 3. Rural electrification of isolated popula-
supply: tions:
Power supply in conventional substations As a power source for supplying reliable
where low voltage power is needed as a power to rural populations in isolated
primary or back-up supply; or in remote areas where there are no distribution lines
areas where building distribution lines nearby, but there are transmission lines.
is unsafe and with unreliable supply that This particular application supplies low
requires frequent maintenance and high voltage power directly from HV line in an
costs. economical and practical way.

It can also be used as a primary power 4. Temporary power supply when building
source in switching substations without substations, wind farms, etc., and emer-
power transformers to supply the gency supply during natural disasters.
substation and SCADA control systems.

2. Power supply for telecommunication 5. Voltage elevator for High Voltage electrical
and monitoring systems: test laboratories, wind and solar farms.
High quality electrical supply for booster
antennas in remote locations using a
voltage transformer connected to a nearby
transmission line.

› UTP-245 Voltage
transformer for
rural electrification.
Chihuahua State
(Mexico).

44 Instrument transformers | High voltage


5. POWER VOLTAGE TRANSFORMERS > Oil-paper and gas insulation

DESIGN AND MANUFACTURE


Power voltage transformers have a direct The SF6 and the plastic layer form the
phase to ground connection with galvanic electrical insulation. An input valve for SF6 gas
insulation between primary and secondary is provided on a side of tank together with a
windings, which are coiled over the same manometer for monitoring leakages and gas
magnetic core with independent insulation. pressure.

Voltage transformers for auxiliary services


with oil-paper insulation are made with a
magnetic core inside a metallic tank with
its primary and secondary windings around
it. The primary conductor is enclosed by a
capacitive bushing consisting of shields and
layers of insulating paper impregnated in oil.
In order to control oil level changes, they are
fitted with metallic bellows.

Voltage transformers for auxiliary services


with gas insulation are made with a magnetic
core inside a metallic tank with its primary and
secondary windings around it. These windings
are made of heat-resisting electric wires
coated in synthetic resin and a layer of plastic
with a high dielectric resistance and excellent
thermal and mechanical performance.

› Oil-paper insulated
power voltage
transformers.

› 72.5 kV Gas Power


voltage transformer.
R.E.E. (Spain).

Instrument transformers | High voltage 45


5. POWER VOLTAGE TRANSFORMERS > Oil-paper and gas insulation

ADVANTAGES

The conventional solutions used for OIL-PAPER:


applications mentioned on page 44 usually › Oil compensating system that effectively
are a dedicated medium voltage line, regulates changes in oil volume mainly
diesel generators or the power transformer caused by temperature.
tertiary winding. ARTECHE’S power voltage
transformer has the following advantages: › Oil sampling valve for periodic analysis.
› Highly reliable power source within the OPTIONS:
substation. › Porcelain or silicone rubber insulator.
› Independent power supply, more flexible › Over-pressure relief valve with connection
as the user does not have to depend on capability to SCADA system.
third parties. › Terminal for main insulation monitoring
› Cost effective. (tangent δ measurement).
› Maintenance-free throughout their lifespan.
› Taps for voltage regulation.
› Winding for secondary current measuring
› Quick and flexible solution and protection.
› Release of the power transformer tertiary › Single-phase/three-phase voltages in the
winding. secondary from a single HV phase.
› Social benefits. Electrification of isolated
rural areas, emergency power after natural GAS:
disasters…
› The silicone rubber insulator guarantees
safety during transportation and service.
In addition to the several advantages of this
solution, there are also the common ones to
› Online monitoring of the insulation status
with a manometer alarm.
ARTECHE instrument transformers range:
› Pressure relief device (rupture disc) in the
› Wide range of designs meeting customer top part of the transformer.
needs.
› Hermetically sealed to guarantee complete
water tightness with the minimum volume
of oil or gas (Each unit is tested individu-
ally).
› Excellent response under extreme weather
conditions, high altitudes, seismic hazard
areas, violent winds, etc.
› Officially homologated in-house testing
facilities.
› Each transformer is routine tested for partial
ARTECHE has developed
discharges, tangent delta (DDF), insulation a pioneeriingg pilot projject
and accuracy and designed to withstand all
the type tests included in the standards. in the State of Chihuahua
› Environmental-friendly design. The materi- (Mexico) in collaboration
als used are recyclable and resistant to the
elements. with the local government
› May be transported and stored horizontally and C.FF.E
E. to extend
or vertically.
electrical service to the
OPTIONS: region’s rural population,
› Additional secondaries for measuring and/
using power voltage
or protection.
› Inner temperature monitoring sensor. transformers, helping to
reduce their isolation. This
project has been awarded
with the “Tomorrow’s Energy
Prize” in the 2013 World
Energy Congress (WEC).

46 Instrument transformers | High voltage


Instrument transformers | High voltage 47
5. POWER VOLTAGE TRANSFORMERS > Oil-paper and gas insulation

RANGE
Auxiliary service inductive voltage trans-
formers are named using different letters
(UT followed by a third letter to indicate the
model for oil-paper insulation and UG for gas
insulation) followed by 2 or 3 numbers to
indicate their service voltages.

The table on the next page shows the range


of transformers currently built by ARTECHE.
These characteristics are merely indicative.

ARTECHE can also manufacture these trans-


formers to comply with any domestic or
international standards.

B
B
B

A A A

› Model UTE › Model UG › Model UTP

› 145 kV UTE Power


voltage transformers.
Transener (Argentina).

› 420 kV UG Power
voltage transformer.
Routine tested in
ARTECHE’s laboratory.

48 Instrument transformers | High voltage


5. POWER VOLTAGE TRANSFORMERS > Oil-paper and gas insulation

Oil-paper insulation > Model UT

Rated insulation level Dimensions


Standard
Highest
Lightning Burden creepage Weight
Model Voltage Power Switching
impulse (kVA) distance AxB H (kg)
(kV) frequency impulse
(BIL) (mm) (mm) (mm)
(kV) (kVp)
(kVp)

UTE-72 72.5 140 325 - up to 10 1825 400x430 1645 285

UTE-145 145 275 650 - up to 10 3625 400x400 2105 400

UTG-245 245 460 1050 - up to 10 6125 500x640 3260 800

Approximate dimensions and weights. For special requirements, please consult.

Oil-paper insulation > Model UTP

Rated insulation level Dimensions


Standard
Highest
Lightning Burden creepage Weight
Model Voltage Power Switching
impulse (kVA) distance AxB H (kg)
(kV) frequency impulse
(BIL) (mm) (mm) (mm)
(kV) (kVp)
(kVp)

UTP-123 123 230 550 - 50/100 4525 1100x776 3100 2950

UTP-145 145 275 650 - 50/100 4525 1101x776 3100 2950

UTP-170 170 325 750 - 50/100 5285 1102x776 3400 3200

395 900 1450x1220


UTP-245 245 - 50/100/167/333 6125 4590 4500
460 1050 1451x1220
510 1175 1452x1220
UTP-362 362 950 50/100/167/333 9050 5270 5135
575 1300 1453x1220

Approximate dimensions and weights For special requirements, please consult

Gas insulation > Model UG

Rated insulation level Dimensions


Standard
Highest
Lightning Burden creepage Weight
Model voltage Power Switching
impulse (kVA) distance Base Height (kg)
(kV) frequency Impulse
(BIL) (mm) (mm) (mm)
(kV) (kVp)
(kVp)

UG-72 72.5 140 325 - 50 2248 600x600/1200x1200 2250 < 3500


123 230 550 - 100 3813 600x600/1200x1200 3100 < 3500
UG-145
145 275 650 - 100 4495 600x600/1200x1200 3100 < 3500
170 325 750 - 100 5270 600x600/1200x1200 3300 < 3500
UG-245 245 460 1050 - 100 7595 600x600/1200x1200 3800 < 3500
300 460 1050 850 100 9300 600x600/1200x1200 4200 < 3500
362 510 1175 950 100 11222 900x900/1200x1200 4600 < 3500
UG-420
420 630 1425 1050 100 13020 900x900/1200x1200 5300 < 3500
UG-550 550 680 1550 1175 100 17050 900x900/1200x1200 5800 < 3500

Approximate dimensions and weights For special requirements, please consult

Instrument transformers | High voltage 49


Nomor : 098/ABB-WSKT/IX/2020 Jakarta, 16 September 2020
Lampiran: 1 set
Sifat : Penting
Kepada Yth.
Manager UPP Jaringan Jambi
PT. PLN (Persero)
Di
Jalan. Dr. Setia Budhi RT. 09, Kelurahan Rajawali, Kecamatan Jambi Timur, Jambi 36143
Up. Bapak Didien Hendrarianto

Perihal : Usulan Amandemen Kerja Tambah Kurang Pekerjaan Pembangunan


Gardu Induk Tegangan Ekstra Tinggi 500 KV Peranap

Dengan hormat,
Menunjuk :
a. Surat Perjanjian Pembangunan Gardu Induk Tegangan Ekstra Tinggi 500 KV Peranap,
No. 0740.PJ/DAN.02.02/DIR/2017, tanggal 28 Desember 2017.
b. Kesepakatan Diskusi Kontrak Pekerjaan Pembangunan Gardu Induk Tegangan Ekstra
Tinggi 500 KV Peranap, tanggal 15 Desember 2017
c. Surat KSO ABB Waskita No. 045/ABB-WSKT/V/2020 tanggal 6 Mei 2020, perihal :
Surat Penyampaian Amandemen Kerja Tambah Kurang dalam Proyek Pembangunan
GITET 500 kV Peranap
d. Surat KSO ABB Waskita No. 078/ABB-WSKT/IX/2020 tanggal 21 Juli 2020, Perihal : Permohonan
Pembahasan Amandemen Kerja Tambah Kurang Pekerjaan Pembangunan Gardu Induk Tegangan
Ekstra Tinggi 500 KV Peranap
e. Risalah Rapat (MOM) tanggal 7 Agustus 2020, agenda Rapat Pembahasan Progress Pekerjaan dan
Rencana Amandemen GITET 500 KV Peranap
f. Surat KSO ABB Waskita No. 096/ABB-WSKT/IX/2020 tanggal 11 September 2020, perihal Permohonan
Pembahasan Amandemen Kerja Tambah Kurang Pekerjaan Pembangunan
Gardu Induk Tegangan Ekstra Tinggi 500 kV Peranap
Bersama ini kami sampaikan beberapa hal sebagai berikut :
1. Berdasarkan Laporan Kemajuan Pekerjaan (LKP) bulan Agustus 2020, progress pada Proyek
Pembangunan GITET 500 KV Peranap adalah 79,995% dengan rincian:
- Pekerjaan Sipil : 87.292 %
- Pekerjaan Elektrikal Mekanikal : 77,563 %
2. Kami telah melaksanakan dan menyelesaikan beberapa pekerjaan tambah (daftar terlampir)
berdasarkan Berita Acara Lapangan dan Risalah Rapat (Minute of Meeting) yang
ditandatangani oleh Pusmanpro dan UPPJ Jambi, akan tetapi kami tidak dapat memasukkan
item pekerjaan tersebut dalam Laporan Kemajuan Proyek karena belum masuk dalam
Amandemen Kontrak.
3. Berdasarkan poin 2 di atas kami sampaikan Usulan Amandemen Tambah Kurang Pekerjaan
Pembangunan Gardu Induk Tegangan Ekstra Tinggi 500 KV Peranap sebagai berikut :

Rincian Amandemen Tambah Kurang (terlampir)


4. Item-item pekerjaan yang yang kami sampaikan dalam Amandemen Tambah Kurang pada poin 3 di
atas sudah melalui kajian dan telah disetujui dalam Konsinyering antara PT PLN UIP SBT, PT PLN UPPJ
Jambi dan PLN Enjiniring.
5. Selain itu terdapat item kerja tambah SSVT yang memerlukan waktu 9 bulan untuk proses engineering,
pengadaan material, pengiriman dan pemasangan material di site, yang baru dapat kami mulai
prosesnya setelah Usulan Amandemen Tambah Kurang pada poin 3 di atas disetujui.
Kami mohon arahan dari Bapak terkait tindak lanjut Usulan Amandemen Kerja Tambah Kurang ini.
Demikian kami sampaikan, atas perhatian dan kerjasanya kami ucapkan terima kasih.

KSO ABB –Waskita Proyek GITET 500kV Peranap


Project Manager

Muhamad Sidik

Tembusan:
1. General Manager UIP SUMBAGTENG – PT. PLN (Persero), Up. Bpk. Henvry Setijabudi
2. Senior Manager Bidang Operasi dan Konstruksi UIP SUMBAGTENG - PT. PLN (Persero), Up. Bpk. Teddy Finzar
3. Manager PLN PUSMANPRO UPMK III dan IV
4. LBU Manager PGGI – PT. ABB Power Grids Indonesia
5. SVP EPC Division PT. Waskita Karya (Perero) Tbk
6. PLN Engineering
7. Arsip.
LAMPIRAN
REKAPITULASI BIAYA ADDENDUM PEKERJAAN TAMBAH - KURANG
PEMBANGUNAN GARDU INDUK TEGANGAN EKSTRA TINGGI 500 KV PERANAP
GRAND REKAPITULASI BIAYA
ADDENDUM PEKERJAAN TAMBAH - KURANG
PEMBANGUNAN GARDU INDUK TEGANGAN EKSTRA TINGGI 500 KV PERANAP

NO URAIAN PEKERJAAN HARGA KONTRAK USULAN AMANDEMEN TAMBAH KURANG

( Rp ) ( Rp ) ( Rp ) ( Rp )
1 2 3 4 5 6

1,1 PENGADAAN MATERIAL TERMASUK TRANSPORTASI, PEMASANGAN 221.629.371.371 222.460.223.179 21.154.899.102 20.324.047.294,58
COMMISSIONING DAN ASURANSI ( FOR SUBSTATION ) 500 kV SUBSTATION
1
1 1,2 INSTALATION SERVICE FOR CIVIL WORKS 73.867.280.344 88.048.373.510 21.244.450.483 7.063.357.317
1
1,3 SUBSTATION SERVICE VOLTAGE TRANSFORMER (SSVT) 0 14.161.534.108 14.161.534.108 -

1 GRAND TOTAL (TANPA PEMBULATAN ) 295.496.651.715 324.670.130.797 56.560.883.693 27.387.404.612


2 GRAND TOTAL (DENGAN PEMBULATAN ) 295.496.651.715 324.670.130.797 56.560.883.693 27.387.404.612
2 PPN 10 % 29.549.665.172 32.467.013.080 5.656.088.369 2.738.740.461
2 GRAND TOTAL (TERMASUK PPN ) 325.046.316.887 357.137.143.877 62.216.972.062 30.126.145.073
REKAPITULASI BIAYA
ADDENDUM PEKERJAAN TAMBAH - KURANG
PEMBANGUNAN GARDU INDUK TEGANGAN EKSTRA TINGGI 500 KV PERANAP

NO URAIAN PEKERJAAN HARGA KONTRAK USULAN AMANDEMEN TAMBAH KURANG

( Rp ) ( Rp ) ( Rp ) ( Rp )
1 2 3 4 5 6

1,1 PENGADAAN MATERIAL, TRANSPORTASI, PEMASANGAN COMMISIONING


DAN ASURANSI ( FOR SUBSTATION ) 500 kV SUBSTATION.

500 KV OUTDOOR EQUIPMENT FOR NEW AUR DURI OHL FEEDER No. 1 & FUTURE OHL
1 1 20.468.843.060 20.198.498.191 0 270.344.870
FEEDER
500 KV OUTDOOR EQUIPMENT FOR NEW AUR DURI OHL FEEDER No. 2 & FUTURE OHL
1 2 20.587.546.820 20.317.201.951 0 270.344.870
FEEDER
500 KV OUTDOOR EQUIPMENT FOR PERAWANG OHL FEEDER No. 3 WITH SHUNT
1 3 24.654.966.822 24.047.810.544 114.373.504 721.529.782
REACTOR & FUTURE OHL FEEDER
500 KV OUTDOOR EQUIPMENT FOR PERAWANG OHL FEEDER No. 4 WITH SHUNT
1 4 24.490.302.770 23.883.146.492 114.373.504 721.529.782
REACTOR & FUTURE OHL FEEDER
2 5 500 KV BUSBARS AND CONNECTIONS 4.756.444.169 4.756.444.169 0 0
2 6 500 KV SUBSTATION EARTING SYSTEM 4.523.022.851 4.523.022.851 0 0
2 7 500 KV SUBSTATIONS MULTICORE AND AUXILIARY CABLES 3.076.798.371 3.076.798.371 0 0
2 8 500 KV SUBSTATION STRUCTURES 18.866.676.598 16.922.763.794 62.196.400 2.006.109.204
2 9 500 kV SUBSTATION CONTROL PANELS 6.518.213.204 7.062.604.913 2.698.823.150 2.154.431.440
1.10 10 500 KV SUBSTATION PROTECTION PANELS 25.276.747.268 30.565.546.833 18.165.132.544 12.876.332.979
1 11 INVERTER FOR SUBSTATION AUTOMATION 628.265.838 628.265.838 0 0
1 12 DFR 6.542.286.523 6.542.286.523 0 0
1 13 110 VOLT DC EQUIPMENT 3.260.988.299 3.260.988.299 0 0
1 14 48 VOLT DC EQUIPMENT 1.574.817.338 1.574.817.338 0 0
1 15 LVAC EQUIPMENT 3.043.598.296 1.740.173.928 0 1.303.424.368
1 16 500 KV SHUNT REACTOR 40.940.319.372 40.940.319.372 0 0
1 17 SUBSTATION AUTOMATION HARDWARE 6.633.615.519 6.633.615.519 0 0
1 18 SUBSTATION AUTOMATION SOFTWARE 0 0 0 0
1 19 POWER LINE CARRIER SYSTEM 0 0 0 0
1.20 20 MISCELLANEOUS 1.770.708.406 1.770.708.406 0 0
1 21 TRAINING 892.467.807 892.467.807 0 0
1 22 TEST AND COMISSIONING 2.928.314.432 2.928.314.432 0 0
1 23 JASA SERTIFIKASI 0 0 0 0
1 24 AS BUILT DRAWING 194.427.608 194.427.608 0 0

SUB TOTAL I PENGADAAN MATERIAl, TRANSPORTASI DAN PEMASANGAN 221.629.371.371 222.460.223.179 21.154.899.102 20.324.047.295
NO URAIAN PEKERJAAN HARGA KONTRAK USULAN AMANDEMEN TAMBAH KURANG

( Rp ) ( Rp ) ( Rp ) ( Rp )
1 2 3 4 5 6

1..2 INSTALATION SERVICE FOR CIVIL WORKS

CONTROL BUILDING
3 1 CONTROL BUILDING SAS 11.680.052.564 11.048.689.154 2.593.944.326 3.225.307.736

SUB TOTAL CONTROL BUILDING 11.680.052.564 11.048.689.154 2.593.944.326 3.225.307.736

SWITCHYARD
4 1 PREPARATION WORK FOR CONTROL BUILDING 4.279.109.011 6.605.455.336 2.326.346.325 0
4 2 SITE WORKS 38.775.493.082 51.578.242.148 16.200.283.745 3.397.534.679
4 3 FOUNDATION 500 KV 19.132.625.687 18.815.986.872 123.876.087 440.514.902

SUB TOTAL SWITCH YARD 62.187.227.780 76.999.684.356 18.650.506.157 3.838.049.581


SUB TOTAL INSTALATION SERVICE FOR CIVIL WORKS 73.867.280.344 88.048.373.510 21.244.450.483 7.063.357.317

1,3 SUBSTATION SERVICE VOLTAGE TRANFORMER ( SSVT )


1 ELECTRICAL & MECHANICAL MATERIAL 0 13.954.438.370 13.954.438.370 0
2 CIVIL MATERIAL 0 207.095.738 207.095.738 0

SUB TOTAL IV 0 14.161.534.108 14.161.534.108 0


GRAND TOTAL 295.496.651.715 324.670.130.797 56.560.883.693 27.387.404.612
BILL OF QUANTITY
RESUME ADD.01.PEMBANGUNAN GARDU INDUK TEGANGAN EKSTRA TINGGI 500 KV, PERANAP

VOLUME HARGA SATUAN USULAN TOTAL


VOLUME VOLUME PERUBAHAN SETELAH HARGA PENGADAAN HARGA JASA
NO. URAIAN PEKERJAAN SATUAN PENGURANGAN PENAMBAHAN
BOQ Pengurangan / PERUBAHAN SATUAN TOTAL SATUAN TOTAL
KONTRAK Penambahan (Rp.) (Rp.) (Rp.) (Rp.) (Rp.) (Rp.)
(1) (2) (3) (4) (4') (4'') (5) (6) = (4'') x (5) (7) (8) = (4'') x (7) (9) = -[(6) + (8)] (10) = (6) + (8)

A PENGADAAN MATERIAL & PEMASANGAN


1. 500 KV OUTDOOR EQUIPMENT FOR PERAWANG OHL
Circuit Breaker, 3 Pole Complete With Operating Mechanism
Suitable For Single Phase High Speed Auto-Reclosure And
Delayed 3 Pole Auto-Reclosure, Complete With Control Cubicle
1.1
And All Local Control Apparatus, Including Anti-Condensation
Heaters, Auxiliary Switches, Terminals, Labels And All Necessary
Equipment Of :
1.1.1 - Circuit breaker with closing resistance sets 2,0 - 2,0 2.961.996.426 5.923.992.851 136.629.211 273.258.421 - -
1.1.2 - Circuit breaker without closing resistance set - - - - - 125.698.874 - - -
Busbar Selector Disconnector, Three single phase Motor
Operated With Operating Mechanism And Local Control
1.2 Apparatus Complete With Anti-Condensation Heaters, Auxiliary sets 2,0 - 2,0 803.925.712 1.607.851.425 16.395.505 32.791.011 - -
Switches, Terminals, Labels, Interlocks And All Necessary
Equipment.
Disconnector, 3 Pole Motor Operated With Operating Mechanism
And Local Control Apparatus Complete With Anti-Condensation
1.3 sets 3,0 - 3,0 416.075.270 1.248.225.811 122.966.290 368.898.869 - -
Heaters, Auxiliary Switches, Terminals, Labels, Interlocks And All
Necessary Equipment.
Disconnector, 3 Pole Motor Operated And Associated Manually
Operated Earth Switch With Operating Mechanism And Local
1.4 Control Apparatus Complete With Anti-Condensation Heaters, set 1,0 - 1,0 506.394.720 506.394.720 109.303.369 109.303.369 - -
Auxiliary Switches, Terminals, Labels, Interlocks And All
Necessary Equipment.
1.5 Voltage Transformer For Instrumentation. unit 1,0 - 1,0 236.040.184 236.040.184 9.715.855 9.715.855 - -
Voltage Transformer For Line Protection And To Act Also As
1.6 units 3,0 - 3,0 239.232.998 717.698.993 9.715.855 29.147.565 - -
Power Line Carrier Coupling Capacitor.
Post Type Current Transformer Complete With Secondary
1.7 Windings Of Required Ratio And Accuracy (See Appropriate units 3,0 - 3,0 353.490.130 1.060.470.390 32.791.011 98.373.032 - -
Clauses And Plate Drawings) For Line.
Post Type Current Transformer Complete With Secondary
1.8 Windings Of Required Ratio And Accuracy (See Appropriate unit - - - - - - - - -
Clauses And Plate Drawings) For IBT.
Post Type Current Transformer Complete With Secondary
1.9 Windings Of Required Ratio And Accuracy (See Appropriate unit - - - - - 32.791.011 - - -
Clauses And Plate Drawings) For Reactor.
Post Type Current Transformer Complete With Secondary
1.10 Windings Of Required Ratio And Accuracy (See Appropriate units 6,0 - 6,0 317.000.826 1.902.004.958 32.791.011 196.746.063 - -
Clauses And Plate Drawings) For Diameter.
Line Trap Complete With Supporting Post Insulators And All
1.11 unit 1,0 - 1,0 682.901.198 682.901.198 32.791.011 32.791.011 - -
Necessary Fixings And Ancilliary Items Of Equipment 0.5 mh
500 kV Post Insulator, complete with fittings, supporting steel
1.12 sets 8,0 - 8,0 34.208.722 273.669.778 40.988.763 327.910.106 - -
structure, clamps and all necessary items equipment
Outdoor Switchbay Marshalling Cubicle Complete With Terminal
Boards, Weatherproof Switched Socket Outlet, Anti-Condensation
1.13 Heater, Telephone Jack, Wiring, Glands, Labels, And sets 2,0 - 2,0 89.780.246 179.560.492 24.593.258 49.186.516 - -
Accommodation For All Necessary Multicore And Auxiliary
Cables.And Auxiliary Cables.
Surge Diverter Mounted On Insulating Base, Complete With
1.14 units 3,0 - 3,0 177.885.356 533.656.067 27.325.842 81.977.526 - -
Surge Counter And Leakage Current Meter.
VOLUME HARGA SATUAN USULAN TOTAL
VOLUME VOLUME PERUBAHAN SETELAH HARGA PENGADAAN HARGA JASA
NO. URAIAN PEKERJAAN SATUAN PENGURANGAN PENAMBAHAN
BOQ Pengurangan / PERUBAHAN SATUAN TOTAL SATUAN TOTAL
KONTRAK Penambahan (Rp.) (Rp.) (Rp.) (Rp.) (Rp.) (Rp.)
(1) (2) (3) (4) (4') (4'') (5) (6) = (4'') x (5) (7) (8) = (4'') x (7) (9) = -[(6) + (8)] (10) = (6) + (8)

Bare aluminium conductor of 2 x AAC with capacity 4000 A for 3-


1.15 diameter 1,0 - 1,0 534.580.314 534.580.314 16.395.505 16.395.505 - -
phase fly bus, bay line and reactor
1.16 500 kV double tension string insulator set complete with fittings sets 24,0 (6,0) 18,0 25.382.872 456.891.695 19.674.606 354.142.914 270.344.870 -
1.17 500 kV Single suspension string insulator set complete with sets 12,0 - 12,0 13.683.489 164.201.867 16.395.505 196.746.063 - -
1.18 Set of clamps, connectors and accessories for installation diameter 1,0 - 1,0 303.066.473 303.066.473 3.036.205 3.036.205 - -
1.19 LV power cable, control cable and accessories and necessary diameter 1,0 - 1,0 1.677.762.331 1.677.762.331 9.108.614 9.108.614 - -

SUB TOTAL A.1 18.008.969.547 2.189.528.644 270.344.870 -

2. 500 KV OUTDOOR EQUIPMENT FOR PERAWANG OHL


Circuit Breaker, 3 Pole Complete With Operating Mechanism
Suitable For Single Phase High Speed Auto-Reclosure And
Delayed 3 Pole Auto-Reclosure, Complete With Control Cubicle
2.1
And All Local Control Apparatus, Including Anti-Condensation
Heaters, Auxiliary Switches, Terminals, Labels And All Necessary
Equipment Of :
2.1.1 - Circuit breaker with closing resistance sets 2,0 - 2,0 2.961.996.426 5.923.992.851 136.629.211 273.258.421 - -
2.1.2 - Circuit breaker without closing resistance set - - - - - 125.698.874 - - -
Busbar Selector Disconnector, Three single phase Motor
Operated With Operating Mechanism And Local Control
2.2 Apparatus Complete With Anti-Condensation Heaters, Auxiliary sets 2,0 - 2,0 803.925.712 1.607.851.425 16.395.505 32.791.011 - -
Switches, Terminals, Labels, Interlocks And All Necessary
Equipment.
Disconnector, 3 Pole Motor Operated With Operating Mechanism
And Local Control Apparatus Complete With Anti-Condensation
2.3 sets 3,0 - 3,0 416.075.270 1.248.225.811 122.966.290 368.898.869 - -
Heaters, Auxiliary Switches, Terminals, Labels, Interlocks And All
Necessary Equipment.
Disconnector, 3 Pole Motor Operated And Associated Manually
Operated Earth Switch With Operating Mechanism And Local
2.4 Control Apparatus Complete With Anti-Condensation Heaters, set 1,0 - 1,0 506.394.720 506.394.720 109.303.369 109.303.369 - -
Auxiliary Switches, Terminals, Labels, Interlocks And All
Necessary Equipment.
2.5 Voltage Transformer For Instrumentation. unit 1,0 - 1,0 236.040.184 236.040.184 9.715.855 9.715.855 - -
Voltage Transformer For Line Protection And To Act Also As
2.6 units 3,0 - 3,0 239.232.998 717.698.993 9.715.855 29.147.565 - -
Power Line Carrier Coupling Capacitor.

Post Type Current Transformer Complete With Secondary


2.7 Windings Of Required Ratio And Accuracy (See Appropriate units 3,0 - 3,0 353.490.130 1.060.470.390 32.791.011 98.373.032 - -
Clauses And Plate Drawings) For Line.

Post Type Current Transformer Complete With Secondary


2.8 Windings Of Required Ratio And Accuracy (See Appropriate unit - - - - - - - - -
Clauses And Plate Drawings) For IBT.

Post Type Current Transformer Complete With Secondary


2.9 Windings Of Required Ratio And Accuracy (See Appropriate unit - - - - - 32.791.011 - - -
Clauses And Plate Drawings) For Reactor.

Post Type Current Transformer Complete With Secondary


2.10 Windings Of Required Ratio And Accuracy (See Appropriate units 6,0 - 6,0 317.000.826 1.902.004.958 32.791.011 196.746.063 - -
Clauses And Plate Drawings) For Diameter.

Line Trap Complete With Supporting Post Insulators And All


2.11 unit 1,0 - 1,0 682.901.198 682.901.198 32.791.011 32.791.011 - -
Necessary Fixings And Ancilliary Items Of Equipment 0.5 mh
VOLUME HARGA SATUAN USULAN TOTAL
VOLUME VOLUME PERUBAHAN SETELAH HARGA PENGADAAN HARGA JASA
NO. URAIAN PEKERJAAN SATUAN PENGURANGAN PENAMBAHAN
BOQ Pengurangan / PERUBAHAN SATUAN TOTAL SATUAN TOTAL
KONTRAK Penambahan (Rp.) (Rp.) (Rp.) (Rp.) (Rp.) (Rp.)
(1) (2) (3) (4) (4') (4'') (5) (6) = (4'') x (5) (7) (8) = (4'') x (7) (9) = -[(6) + (8)] (10) = (6) + (8)

500 kV Post Insulator, complete with fittings, supporting steel


2.12 sets 8,0 - 8,0 34.208.722 273.669.778 40.988.763 327.910.106 - -
structure, clamps and all necessary items equipment
Outdoor Switchbay Marshalling Cubicle Complete With Terminal
Boards, Weatherproof Switched Socket Outlet, Anti-Condensation
2.13 Heater, Telephone Jack, Wiring, Glands, Labels, And sets 2,0 - 2,0 89.780.246 179.560.492 24.593.258 49.186.516 - -
Accommodation For All Necessary Multicore And Auxiliary
Cables.And Auxiliary Cables.
Surge Diverter Mounted On Insulating Base, Complete With
2.14 units 3,0 - 3,0 177.885.356 533.656.067 27.325.842 81.977.526 - -
Surge Counter And Leakage Current Meter.
Bare aluminium conductor of 2 x AAC with capacity 4000 A for 3-
2.15 diameter 1,0 - 1,0 534.580.314 534.580.314 16.395.505 16.395.505 - -
phase fly bus, bay line and reactor
500 kV double tension string insulator set complete with fittings
2.16 sets 24,0 (6,0) 18,0 25.382.872 456.891.695 19.674.606 354.142.914 270.344.870 -
for installation of the main busbar as specified.
500 kV Single suspension string insulator set complete with
2.17 sets 12,0 - 12,0 13.683.489 164.201.867 16.395.505 196.746.063 - -
fittings for installation of the main busbar as specified.
2.18 Set of clamps, connectors and accessories for installation diameter 1,0 - 1,0 303.066.473 303.066.473 3.036.205 3.036.205 - -
2.19 LV power cable, control cable and accessories and necessary diameter 1,0 - 1,0 1.796.466.091 1.796.466.091 9.108.614 9.108.614 - -

SUB TOTAL A.2 18.127.673.307 2.189.528.644 270.344.870 -

3. 500 KV OUTDOOR EQUIPMENT FOR NEW AUR DURI OHL


Circuit Breaker, 3 Pole Complete With Operating Mechanism
Suitable For Single Phase High Speed Auto-Reclosure And
Delayed 3 Pole Auto-Reclosure, Complete With Control Cubicle
3.1
And All Local Control Apparatus, Including Anti-Condensation
Heaters, Auxiliary Switches, Terminals, Labels And All Necessary
Equipment Of :
3.1.1 - Circuit breaker with closing resistance sets 2,0 - 2,0 2.961.996.426 5.923.992.851 136.629.211 273.258.421 - -
3.1.2 - Circuit breaker without closing resistance set 1,0 - 1,0 2.194.079.028 2.194.079.028 - - - -
Busbar Selector Disconnector, Three single phase Motor
Operated With Operating Mechanism And Local Control
3.2 Apparatus Complete With Anti-Condensation Heaters, Auxiliary sets 2,0 - 2,0 803.925.712 1.607.851.425 16.395.505 32.791.011 - -
Switches, Terminals, Labels, Interlocks And All Necessary
Equipment.
Disconnector, 3 Pole Motor Operated With Operating Mechanism
And Local Control Apparatus Complete With Anti-Condensation
3.3 sets 3,0 - 3,0 416.075.270 1.248.225.811 122.966.290 368.898.869 - -
Heaters, Auxiliary Switches, Terminals, Labels, Interlocks And All
Necessary Equipment.
Disconnector, 3 Pole Motor Operated And Associated Manually
Operated Earth Switch With Operating Mechanism And Local
3.4 Control Apparatus Complete With Anti-Condensation Heaters, set 1,0 - 1,0 506.394.720 506.394.720 109.303.369 109.303.369 - -
Auxiliary Switches, Terminals, Labels, Interlocks And All
Necessary Equipment.
3.5 Voltage Transformer For Instrumentation. unit 1,0 - 1,0 236.040.184 236.040.184 9.715.855 9.715.855 - -
Voltage Transformer For Line Protection And To Act Also As
3.6 units 3,0 - 3,0 239.232.998 717.698.993 9.715.855 29.147.565 - -
Power Line Carrier Coupling Capacitor.
Post Type Current Transformer Complete With Secondary
3.7 Windings Of Required Ratio And Accuracy (See Appropriate units 3,0 - 3,0 353.490.130 1.060.470.390 32.791.011 98.373.032 - -
Clauses And Plate Drawings) For Line.
Post Type Current Transformer Complete With Secondary
3.8 Windings Of Required Ratio And Accuracy (See Appropriate unit - - - - - - - - -
Clauses And Plate Drawings) For IBT.
VOLUME HARGA SATUAN USULAN TOTAL
VOLUME VOLUME PERUBAHAN SETELAH HARGA PENGADAAN HARGA JASA
NO. URAIAN PEKERJAAN SATUAN PENGURANGAN PENAMBAHAN
BOQ Pengurangan / PERUBAHAN SATUAN TOTAL SATUAN TOTAL
KONTRAK Penambahan (Rp.) (Rp.) (Rp.) (Rp.) (Rp.) (Rp.)
(1) (2) (3) (4) (4') (4'') (5) (6) = (4'') x (5) (7) (8) = (4'') x (7) (9) = -[(6) + (8)] (10) = (6) + (8)

Post Type Current Transformer Complete With Secondary


3.9 Windings Of Required Ratio And Accuracy (See Appropriate units 3,0 - 3,0 445.853.680 1.337.561.040 - - - -
Clauses And Plate Drawings) For Reactor.
Post Type Current Transformer Complete With Secondary
3.10 Windings Of Required Ratio And Accuracy (See Appropriate units 6,0 - 6,0 317.000.826 1.902.004.958 32.791.011 196.746.063 - -
Clauses And Plate Drawings) For Diameter.
Line Trap Complete With Supporting Post Insulators And All
3.11 unit 1,0 - 1,0 682.901.198 682.901.198 32.791.011 32.791.011 - -
Necessary Fixings And Ancilliary Items Of Equipment 0.5 mh
500 kV Post Insulator, complete with fittings, supporting steel
3.12 sets 8,0 (6,0) 2,0 34.208.722 68.417.445 40.988.763 81.977.526 451.184.913 -
structure, clamps and all necessary items equipment
Outdoor Switchbay Marshalling Cubicle Complete With Terminal
Boards, Weatherproof Switched Socket Outlet, Anti-Condensation
3.13 Heater, Telephone Jack, Wiring, Glands, Labels, And sets 2,0 1,0 3,0 89.780.246 269.340.738 24.593.258 73.779.774 - 114.373.504
Accommodation For All Necessary Multicore And Auxiliary
Cables.And Auxiliary Cables.
Surge Diverter Mounted On Insulating Base, Complete With
3.14 units 3,0 - 3,0 177.885.356 533.656.067 27.325.842 81.977.526 - -
Surge Counter And Leakage Current Meter.
Bare aluminium conductor of 2 x AAC with capacity 4000 A for 3-
3.15 diameter 1,0 - 1,0 528.482.440 528.482.440 16.395.505 16.395.505 - -
phase fly bus, bay line and reactor
500 kV double tension string insulator set complete with fittings
3.16 sets 24,0 (6,0) 18,0 25.382.872 456.891.695 19.674.606 354.142.914 270.344.870 -
for installation of the main busbar as specified.
500 kV Single suspension string insulator set complete with
3.17 sets 12,0 - 12,0 13.683.489 164.201.867 16.395.505 196.746.063 - -
fittings for installation of the main busbar as specified.
3.18 Set of clamps, connectors and accessories for installation diameter 1,0 - 1,0 212.413.359 212.413.359 3.036.205 3.036.205 - -
3.19 LV power cable, control cable and accessories and necessary diameter 1,0 - 1,0 2.428.997.013 2.428.997.013 9.108.614 9.108.614 - -

SUB TOTAL A.3 22.079.621.221 1.968.189.323 721.529.782 114.373.504

4. 500 KV OUTDOOR EQUIPMENT FOR NEW AUR DURI OHL


Circuit Breaker, 3 Pole Complete With Operating Mechanism
Suitable For Single Phase High Speed Auto-Reclosure And
Delayed 3 Pole Auto-Reclosure, Complete With Control Cubicle
4.1
And All Local Control Apparatus, Including Anti-Condensation
Heaters, Auxiliary Switches, Terminals, Labels And All Necessary
Equipment Of :
4.1.1 - Circuit breaker with closing resistance sets 2,0 - 2,0 2.961.996.426 5.923.992.851 136.629.211 273.258.421 - -
4.1.2 - Circuit breaker without closing resistance set 1,0 - 1,0 2.194.079.028 2.194.079.028 - - - -
Busbar Selector Disconnector, Three single phase Motor
Operated With Operating Mechanism And Local Control
4.2 Apparatus Complete With Anti-Condensation Heaters, Auxiliary sets 2,0 - 2,0 803.925.712 1.607.851.425 16.395.505 32.791.011 - -
Switches, Terminals, Labels, Interlocks And All Necessary
Equipment.
Disconnector, 3 Pole Motor Operated With Operating Mechanism
And Local Control Apparatus Complete With Anti-Condensation
4.3 sets 3,0 - 3,0 416.075.270 1.248.225.811 122.966.290 368.898.869 - -
Heaters, Auxiliary Switches, Terminals, Labels, Interlocks And All
Necessary Equipment.
Disconnector, 3 Pole Motor Operated And Associated Manually
Operated Earth Switch With Operating Mechanism And Local
4.4 Control Apparatus Complete With Anti-Condensation Heaters, set 1,0 - 1,0 506.394.720 506.394.720 109.303.369 109.303.369 - -
Auxiliary Switches, Terminals, Labels, Interlocks And All
Necessary Equipment.
4.5 Voltage Transformer For Instrumentation. unit 1,0 - 1,0 236.040.184 236.040.184 9.715.855 9.715.855 - -
Voltage Transformer For Line Protection And To Act Also As
4.6 units 3,0 - 3,0 239.232.998 717.698.993 9.715.855 29.147.565 - -
Power Line Carrier Coupling Capacitor.
VOLUME HARGA SATUAN USULAN TOTAL
VOLUME VOLUME PERUBAHAN SETELAH HARGA PENGADAAN HARGA JASA
NO. URAIAN PEKERJAAN SATUAN PENGURANGAN PENAMBAHAN
BOQ Pengurangan / PERUBAHAN SATUAN TOTAL SATUAN TOTAL
KONTRAK Penambahan (Rp.) (Rp.) (Rp.) (Rp.) (Rp.) (Rp.)
(1) (2) (3) (4) (4') (4'') (5) (6) = (4'') x (5) (7) (8) = (4'') x (7) (9) = -[(6) + (8)] (10) = (6) + (8)

Post Type Current Transformer Complete With Secondary


4.7 Windings Of Required Ratio And Accuracy (See Appropriate units 3,0 - 3,0 353.490.130 1.060.470.390 32.791.011 98.373.032 - -
Clauses And Plate Drawings) For Line.
Post Type Current Transformer Complete With Secondary
4.8 Windings Of Required Ratio And Accuracy (See Appropriate unit - - - - - - - - -
Clauses And Plate Drawings) For IBT.
Post Type Current Transformer Complete With Secondary
4.9 Windings Of Required Ratio And Accuracy (See Appropriate units 3,0 - 3,0 445.853.680 1.337.561.040 - - - -
Clauses And Plate Drawings) For Reactor.
Post Type Current Transformer Complete With Secondary
4.10 Windings Of Required Ratio And Accuracy (See Appropriate units 6,0 - 6,0 317.000.826 1.902.004.958 32.791.011 196.746.063 - -
Clauses And Plate Drawings) For Diameter.
Line Trap Complete With Supporting Post Insulators And All
4.11 unit 1,0 - 1,0 682.901.198 682.901.198 32.791.011 32.791.011 - -
Necessary Fixings And Ancilliary Items Of Equipment 0.5 mh
500 kV Post Insulator, complete with fittings, supporting steel
4.12 sets 8,0 (6,0) 2,0 34.208.722 68.417.445 40.988.763 81.977.526 451.184.913 -
structure, clamps and all necessary items equipment
Outdoor Switchbay Marshalling Cubicle Complete With Terminal
Boards, Weatherproof Switched Socket Outlet, Anti-Condensation
4.13 Heater, Telephone Jack, Wiring, Glands, Labels, And sets 2,0 1,0 3,0 89.780.246 269.340.738 24.593.258 73.779.774 - 114.373.504
Accommodation For All Necessary Multicore And Auxiliary
Cables.And Auxiliary Cables.
Surge Diverter Mounted On Insulating Base, Complete With
4.14 units 3,0 - 3,0 177.885.356 533.656.067 27.325.842 81.977.526 - -
Surge Counter And Leakage Current Meter.
Bare aluminium conductor of 2 x AAC with capacity 4000 A for 3-
4.15 diameter 1,0 - 1,0 528.482.440 528.482.440 16.395.505 16.395.505 - -
phase fly bus, bay line and reactor
500 kV double tension string insulator set complete with fittings
4.16 sets 24,0 (6,0) 18,0 25.382.872 456.891.695 19.674.606 354.142.914 270.344.870 -
for installation of the main busbar as specified.
500 kV Single suspension string insulator set complete with
4.17 sets 12,0 - 12,0 13.683.489 164.201.867 16.395.505 196.746.063 - -
fittings for installation of the main busbar as specified.
4.18 Set of clamps, connectors and accessories for installation diameter 1,0 - 1,0 212.413.359 212.413.359 3.036.205 3.036.205 - -
4.19 LV power cable, control cable and accessories and necessary diameter 1,0 - 1,0 2.264.332.961 2.264.332.961 9.108.614 9.108.614 - -

SUB TOTAL A.4 21.914.957.169 1.968.189.323 721.529.782 114.373.504

5. 500 KV BUSBARS AND CONNECTIONS


Voltage Transformer For Synchronizing Purposes Complete With
5.1 units 2,0 - 2,0 236.040.184 472.080.367 9.715.855 19.431.710 - -
Connections, Fitting And Clamps.
Bare aluminium conductor of 2 x AAC with capacity 4000 A for
5.2 the installation of 3-phase busbar to complete the specified diameter 4,0 - 4,0 76.315.821 305.263.283 16.395.505 65.582.021 - -
scope of works.
500 kV double tension string insulator set complete with fittings
5.3 sets 24,0 - 24,0 25.382.872 609.188.926 19.674.606 472.190.552 - -
for installation of the main busbar as specified.
500 kV Single suspension string insulator set complete with
5.4 sets 6,0 - 6,0 13.683.489 82.100.933 16.395.505 98.373.032 - -
fittings for installation of the main busbar as specified.
Set of clamps, connectors and accessories for installation of the
5.5 diameter 4,0 - 4,0 49.944.735 199.778.938 3.036.205 12.144.819 - -
main busbar as specified
Set of conductor for shield wire and accessories for installation of
5.6 diameter 4,0 - 4,0 10.712.416 42.849.663 6.072.409 24.289.637 - -
the main busbar as specified
3 Pole Manually Operated Earth Switch With Operating
5.7 Mechanism Complete With Auxiliary Switches, Terminals Labels, sets 2,0 - 2,0 256.474.194 512.948.387 2.186.067 4.372.135 - -
Interlocks And All Necessary Equipment.
Miscellaneous equipment and material required for completion
5.8 lot 1,0 - 1,0 1.808.523.923 1.808.523.923 27.325.842 27.325.842 - -
the scope of work.

SUB TOTAL A.5 4.032.734.421 723.709.748 - -


VOLUME HARGA SATUAN USULAN TOTAL
VOLUME VOLUME PERUBAHAN SETELAH HARGA PENGADAAN HARGA JASA
NO. URAIAN PEKERJAAN SATUAN PENGURANGAN PENAMBAHAN
BOQ Pengurangan / PERUBAHAN SATUAN TOTAL SATUAN TOTAL
KONTRAK Penambahan (Rp.) (Rp.) (Rp.) (Rp.) (Rp.) (Rp.)
(1) (2) (3) (4) (4') (4'') (5) (6) = (4'') x (5) (7) (8) = (4'') x (7) (9) = -[(6) + (8)] (10) = (6) + (8)

6. 500 KV SUBSTATION EARTING SYSTEM


Copper Strip Or Flexible Conductors Of The Cross Section
Specified, Installed So As To Form A Grid System Laid Directly In
6.1 The Ground Enclosing The Complete Substation Together With diameter 4,0 - 4,0 1.097.745.312 4.390.981.247 4.372.135 17.488.539 - -
All Electrodes For Surge Diverter And PLC Signalling Equipment
Direct Earthing.
Copper Strip Of Flexible Conductors To Connect Metalclad Parts
6.2 lot 1,0 - 1,0 - - 27.325.842 27.325.842 - -
Of All Equipment And Structures To Main Earth System.
Copper Strip Or Flexible Conductors To Bond All Overhead Line
6.3 lot 1,0 - 1,0 - - 27.325.842 27.325.842 - -
Towers Direct To The Substation Earth System.
Portable Maintenance Earthing Equipment With Mechanical
Lifting Device, Flexible Conductors And Clamps For Making
6.4 set 1,0 - 1,0 48.971.043 48.971.043 10.930.337 10.930.337 - -
Temporary Earth Connections To The Conductors Of 1 Three
Phase 500 kV Circuit.

SUB TOTAL A.6 4.439.952.290 83.070.560 - -

7. 500 KV SUBSTATIONS MULTICORE AND AUXILIARY


Trunk Multicore Cables Including Terminations, Glands, Supports,
Racks Cleats And All Necessary Items Of Equipment To
7.1 Interconnect All Items Of Control Protective Devices Alarms, AC set 1,0 - 1,0 2.803.539.949 2.803.539.949 136.629.211 136.629.211 - -
And DC Supplies Equipment On The 500 kV Substation Site And
Buildings.
Trunk Multicore Cables Including Terminations, Glands Supports,
7.2 Items Between The 500 kV And 150 kV Substation For Control set 1,0 - 1,0 - - 136.629.211 136.629.211 - -
Alarms And Protection Interconnections.

SUB TOTAL A.7 2.803.539.949 273.258.421 - -

8. 500 KV SUBSTATION STRUCTURES


Galvanised steel structure (gantries) to complete the specified
8.1
scope of work for outdoor switcyard : (see the drawing)
8.1.1 Post steel structure sets 31,0 - 31,0 274.949.637 8.523.438.747 39.466.455 1.223.460.105 - -
8.1.2 Beam steel structure sets 38,0 (12,0) 26,0 132.594.031 3.447.444.806 19.032.636 494.848.536 1.819.520.004 -
8.2 Supporting Structures Suitable For The Termination Of All - - - - - - - - - -
8.3 Supporting Structure For 3 Phase Circuit Breakers. sets 10,0 - 10,0 28.277.900 282.779.000 4.263.000 42.630.000 - -
8.4 Supporting Structure For Busbar 3 Phase Disconnector. sets 8,0 - 8,0 55.998.600 447.988.800 8.442.000 67.536.000 - -
8.5 Supporting Structure For Switchbay 3 Phase Disconnector. sets 12,0 - 12,0 55.998.600 671.983.200 8.442.000 101.304.000 - -
Supporting Structure For Switchbay 3 Phase Disconnector With
8.6 sets 6,0 - 6,0 55.998.600 335.991.600 8.442.000 50.652.000 - -
Integral Earth Switches.
8.7 Supporting Structure For Single Phase Post Type Current units 42,0 - 42,0 10.308.200 432.944.400 1.554.000 65.268.000 - -
8.8 Supporting Structure For Single Phase Voltage Transformer. units 18,0 - 18,0 8.915.200 160.473.600 1.344.000 24.192.000 - -
8.9 Supporting Structure For Single Phase Surge Diverter. units 12,0 - 12,0 8.079.400 96.952.800 1.218.000 14.616.000 - -
Supporting Structure For Single Phase Post Insulator Support
8.10 unit - 4,0 4,0 13.512.100 54.048.400 2.037.000 8.148.000 - 62.196.400
(For Line Trap).
8.11 Supporting Structure For 3 Phase Earth Switch. sets 2,0 - 2,0 28.277.900 56.555.800 4.263.000 8.526.000 - -
8.12 Supporting Structure For Post Insulator. units 32,0 (12,0) 20,0 13.512.100 270.242.000 2.037.000 40.740.000 186.589.200 -

SUB TOTAL A.8 14.780.843.153 2.141.920.641 2.006.109.204 62.196.400


VOLUME HARGA SATUAN USULAN TOTAL
VOLUME VOLUME PERUBAHAN SETELAH HARGA PENGADAAN HARGA JASA
NO. URAIAN PEKERJAAN SATUAN PENGURANGAN PENAMBAHAN
BOQ Pengurangan / PERUBAHAN SATUAN TOTAL SATUAN TOTAL
KONTRAK Penambahan (Rp.) (Rp.) (Rp.) (Rp.) (Rp.) (Rp.)
(1) (2) (3) (4) (4') (4'') (5) (6) = (4'') x (5) (7) (8) = (4'') x (7) (9) = -[(6) + (8)] (10) = (6) + (8)

9. 500 kV SUBSTATION CONTROL PANELS


NEW
Control Cubicle for Diameter comprising: set - 2,0 2,0 1.317.961.329 2.635.922.658 31.450.246 62.900.492 - 2.698.823.150
9.1
Ethernet Switch For Inter-Bay System
IED Bay Control A (BCU A)
IED Bay Control AB (BCU AB)
IED Bay Control B (BCU B)
Bay Control Mimic
Miscellaneous equipment, test block, rack cabinet, optical cables
and cord, control cables, clamps, connectors, connections to
individual item of equipment, terminals, auxiliary relays, interior
lamp, heater,… etc to complete the scope of works
9,2 Control Cubicle for Diameter comprising: sets 4,0 (2,0) 2,0 1.067.499.865 2.134.999.730 9.715.855 19.431.710 2.154.431.440 -
Ethernet switch for inter-bay level system
IED Bay Control A (BCU A)
IED Bay Control AB (BCU AB)
Miscellaneous equipment, test block, rack cabinet, optical cables
and cord, control control cables, clamps, connectors, connection
to individual item of equipment, terminals, auxiliary relay,
interior lamp, heater,.. etc to complete the scope of works.
9,3 Control Cubicle for Diameter comprising:
9,4 Control Cubicle for 500/275 kV Interbus Transformer Comprising:
9,5 Control Cubicle for 500kV Reactor Comprising: sets 2,0 - 2,0 1.094.959.307 2.189.918.613 9.715.855 19.431.710 - -

SUB TOTAL A.9 6.960.841.002 101.763.912 2.154.431.440 2.698.823.150

10. 500 KV SUBSTATION PROTECTION PANELS


10.1 Protection Cubicle 1 for OHL Comprising: sets 4,0 (4,0) - 1.069.704.176 - 9.715.855 - 4.317.680.123 -
Ethernet switch for inter-bay level system
IED Main 1 line protection (MPU 1) - Distance, DEF, Over
IED Main 1 Circulating Current Protection (CCP 1)
Miscellaneous equipment, test block, rack cabinet, optical cables
and cord, control control cables, clamps, connectors, connection
to individual item of equipment, terminals, auxiliary relay,
interior lamp, heater,.. etc to complete the scope of works.
NEW
Protection Cubicle 1 for OHL Comprising: set - 4,0 4,0 - - 1.386.577.229 5.546.308.916 - 5.546.308.916
10.1.1
Ethernet switch for inter-bay level system
IED Main 1 line protection (MPU 1) - Distance, DEF, Over
Current, Autoreclose, etc.
IED Main 1 Circulating Current Protection (CCP 1)
IED External Autoreclose
Miscellaneous equipment, test block, rack cabinet, optical cables
and cord, control control cables, clamps, connectors, connection
to individual item of equipment, terminals, auxiliary relay,
interior lamp, heater,.. etc to complete the scope of works.
10.2 Protection Cubicle 2 for OHL Comprising: sets 4,0 (4,0) - 1.069.704.176 - 9.715.855 - 4.317.680.123 -
Ethernet switch for inter-bay level system
IED Main 2 line protection (MPU 2) - Differential, DEF, Over
Current, Autoreclose, etc.
IED Main 2 Circulating Current Protection (CCP 2)
Miscellaneous equipment, test block, rack cabinet, optical cables
and cord, control control cables, clamps, connectors, connection
to individual item of equipment, terminals, auxiliary relay,
interior lamp, heater,.. etc to complete the scope of works.
Note : If Main 1 and Main 2 are the same algorithm, protection
relay must be different manufacturer
VOLUME HARGA SATUAN USULAN TOTAL
VOLUME VOLUME PERUBAHAN SETELAH HARGA PENGADAAN HARGA JASA
NO. URAIAN PEKERJAAN SATUAN PENGURANGAN PENAMBAHAN
BOQ Pengurangan / PERUBAHAN SATUAN TOTAL SATUAN TOTAL
KONTRAK Penambahan (Rp.) (Rp.) (Rp.) (Rp.) (Rp.) (Rp.)
(1) (2) (3) (4) (4') (4'') (5) (6) = (4'') x (5) (7) (8) = (4'') x (7) (9) = -[(6) + (8)] (10) = (6) + (8)

NEW
Protection Cubicle 2 for OHL Comprising: set - 4,0 4,0 - - 1.619.421.262 6.477.685.048 - 6.477.685.048
10.2.1
Ethernet switch for inter-bay level system
IED Main 2 line protection (MPU 2) - Differential, DEF, Over
Current, Autoreclose, etc.
IED Main 2 Circulating Current Protection (CCP 2)
Miscellaneous equipment, test block, rack cabinet, optical cables
and cord, control control cables, clamps, connectors, connection
to individual item of equipment, terminals, auxiliary relay,
interior lamp, heater,.. etc to complete the scope of works.
Note : - If Main 1 and Main 2 are the same algorithm, protection
relay must be different manufacturer
- IED Main 2 Line Protection changes from ABB to Toshiba
10.3 Protection Cubicle 1 for 500/275 kV Interbus Transformer set - -
10.4 Protection Cubicle 2 for 500/275 kV Interbus Transformer set - -
10.5 Protection Cubicle 1 for 500 kV Reactor comprising: sets 2,0 (2,0) - 1.094.959.307 - 9.715.855 - 2.209.350.323 -
Ethernet switch for inter-bay level system
IED Main 1 Reactor Protection (MPU 1) - Restricted Earth Fault
low impedance type, Over Current, 3-phase under/over voltage,
etc.
IED Main 1 Circulating Current Protection (CCP 1)
Miscellaneous equipment, test block, rack cabinet, optical cables
and cord, control control cables, clamps, connectors, connection
to individual item of equipment, terminals, auxiliary relay,
interior lamp, heater,.. etc to complete the scope of works.
NEW
Protection Cubicle 1 for 500 kV Reactor comprising: set - 2,0 2,0 - - 913.219.331 1.826.438.662 - 1.826.438.662
10.5.1
Ethernet switch for inter-bay level system
IED Main 1 Reactor Protection (MPU 1) - Restricted Earth Fault
low impedance type, Over Current, 3-phase under/over voltage,
etc.
Miscellaneous equipment, test block, rack cabinet, optical cables
and cord, control control cables, clamps, connectors, connection
to individual item of equipment, terminals, auxiliary relay,
interior lamp, heater,.. etc to complete the scope of works.
10.6 Protection Cubicle 2 for 500 kV Reactor comprising: sets 2,0 - 2,0 1.094.959.307 2.189.918.613 9.715.855 19.431.710 - -
Ethernet switch for inter-bay level system
IED Main 1 Reactor Protection (MPU 1) - Restricted Earth Fault
IED Main 2 Circulating Current Protection (CCP 2)
Miscellaneous equipment, test block, rack cabinet, optical cables
and cord, control control cables, clamps, connectors, connection
to individual item of equipment, terminals, auxiliary relay,
interior lamp, heater,.. etc to complete the scope of works.
Note : Main 1 and Main 2 Protection must be different
manufacturer
NEW
Protection Cubicle 2 for 500 kV Reactor comprising: set - 2,0 2,0 - - 913.219.331 1.826.438.662 - 1.826.438.662
10.6.1
Ethernet switch for inter-bay level system
IED Main 1 Reactor Protection (MPU 1) - Restricted Earth Fault
low impedance type, Over Current, 3-phase under/over voltage,
etc.
Miscellaneous equipment, test block, rack cabinet, optical cables
and cord, control control cables, clamps, connectors, connection
to individual item of equipment, terminals, auxiliary relay,
interior lamp, heater,.. etc to complete the scope of works.
Note : Main 1 and Main 2 Protection must be different
manufacturer
10.7 Protection Cubicle 1 for Busbar comprising: set 1,0 - 1,0 3.870.834.299 3.870.834.299 9.715.855 9.715.855 - -
10.8 Protection Cubicle 2 for Busbar comprising: set 1,0 - 1,0 3.870.834.299 3.870.834.299 9.715.855 9.715.855 - -
VOLUME HARGA SATUAN USULAN TOTAL
VOLUME VOLUME PERUBAHAN SETELAH HARGA PENGADAAN HARGA JASA
NO. URAIAN PEKERJAAN SATUAN PENGURANGAN PENAMBAHAN
BOQ Pengurangan / PERUBAHAN SATUAN TOTAL SATUAN TOTAL
KONTRAK Penambahan (Rp.) (Rp.) (Rp.) (Rp.) (Rp.) (Rp.)
(1) (2) (3) (4) (4') (4'') (5) (6) = (4'') x (5) (7) (8) = (4'') x (7) (9) = -[(6) + (8)] (10) = (6) + (8)

10.9 Protection Cubicle for Diameter comprising: set - 2,0 2,0 1.234.414.773 2.468.829.546 9.715.855 19.431.710 - 2.488.261.256
Ethernet switch for inter-bay level system
IED Circuit Breaker Failure & Short Zone Protection for CB A (CBF
& SZP A)
IED Circuit Breaker Failure & Short Zone Protection for CB AB
(CBF & SZP AB)
IED Circuit Breaker Failure & Short Zone Protection for CB B (CBF
& SZP B)
Miscellaneous equipment, test block, rack cabinet, optical cables
and cord, control control cables, clamps, connectors, connection
to individual item of equipment, terminals, auxiliary relay,
interior lamp, heater,.. etc to complete the scope of works.
10.10 Protection Cubicle for Diameter comprising: sets 4,0 (2,0) 2,0 1.006.095.350 2.012.190.700 9.715.855 19.431.710 2.031.622.410 -
Ethernet switch for inter-bay level system
IED Circuit Breaker Failure & Short Zone Protection for CB A (CBF
& SZP A)
IED Circuit Breaker Failure & Short Zone Protection for CB AB
(CBF & SZP AB)
Miscellaneous equipment, test block, rack cabinet, optical cables
and cord, control control cables, clamps, connectors, connection
to individual item of equipment, terminals, auxiliary relay,
interior lamp, heater,.. etc to complete the scope of works.
10.11 Protection Cubicle for Diameter comprising: set - - -
10.12 Energy Meter Panel. lot 1,0 - 1,0 386.196.429 386.196.429 12.144.819 12.144.819 - -

SUB TOTAL A.10 14.798.803.887 15.766.742.947 12.876.332.979 18.165.132.544

11. INVERTER FOR SUBSTATION AUTOMATION


11.1 Inverter including AC Distribution Board sets 2,0 - 2,0 301.988.100 603.976.200 12.144.819 24.289.637 - -

SUB TOTAL A.11 603.976.200 24.289.637 - -

12,0 DFR
12.1 INTERFACE CUBICLE FOR SCADA set - - -
12.2 FAULT RECORDER sets 4,0 - 4,0 643.153.035 2.572.612.139 7.590.512 30.362.047 - -
12.3 EVENT RECORDER set 1,0 - 1,0 917.390.877 917.390.877 7.590.512 7.590.512 - -
12.4 FAULT LOCATION EQUIPMENT (FAULT LOCATOR) (1 Panel) sets 4,0 - 4,0 745.992.225 2.983.968.902 7.590.512 30.362.047 - -

SUB TOTAL A.12 6.473.971.917 68.314.605 - -

13. 110 VOLT DC EQUIPMENT


Battery Complete With Stand, With Required Capacity For Min. 4
Diameters and future 4 Diameters 500 kV All Connections And
13.1 sets 2,0 - 2,0 943.508.767 1.887.017.533 87.442.695 174.885.390 - -
Insulators Including LVAC Connection From Battery Charger To
Battery.
13.2 Battery Fuse Box. sets 2,0 - 2,0 13.875.129 27.750.258 4.372.135 8.744.269 - -
Main Connection Between Battery Fuse Box And Distribution
13.3 sets 2,0 - 2,0 8.161.841 16.323.681 4.372.135 8.744.269 - -
Panel.
Automatic Constant Voltage Battery Charger For Float Operation
13.4 With Required Capacity For Min. 8 Dia. 500 kV And Equipped sets 2,0 - 2,0 285.664.419 571.328.838 16.395.505 32.791.011 - -
With The Following :
110 V DC Distribution Panel Equipped With Sufficient Output
Citcuits Of Required Rating. Each With Fuse And Link To Supply
13.5 sets 2,0 - 2,0 236.693.376 473.386.751 16.395.505 32.791.011 - -
Each Relay Panel Protection Equipment And Also Equipped With
The Following.
13.6 Loose Equipment Comprising : set 1,0 - 1,0 22.853.154 22.853.154 4.372.135 4.372.135 - -

SUB TOTAL A.13 2.998.660.215 262.328.084 - -


VOLUME HARGA SATUAN USULAN TOTAL
VOLUME VOLUME PERUBAHAN SETELAH HARGA PENGADAAN HARGA JASA
NO. URAIAN PEKERJAAN SATUAN PENGURANGAN PENAMBAHAN
BOQ Pengurangan / PERUBAHAN SATUAN TOTAL SATUAN TOTAL
KONTRAK Penambahan (Rp.) (Rp.) (Rp.) (Rp.) (Rp.) (Rp.)
(1) (2) (3) (4) (4') (4'') (5) (6) = (4'') x (5) (7) (8) = (4'') x (7) (9) = -[(6) + (8)] (10) = (6) + (8)

14. 48 VOLT DC EQUIPMENT


14,1 Battery Complete With Stand, With Required Capacity To Supply sets 2,0 - 2,0 253.017.057 506.034.114 32.791.011 65.582.021 - -
14,2 Battery Fuse Box. sets 2,0 - 2,0 13.875.129 27.750.258 4.372.135 8.744.269 - -
14,3 Main Connection Between Battery Fuse Box And Distribution sets 2,0 - 2,0 8.161.841 16.323.681 4.372.135 8.744.269 - -
14,4 Automatic Constant Voltage Battery Charger For Float Operation sets 2,0 - 2,0 220.369.695 440.739.389 16.395.505 32.791.011 - -
Circuit Breaker To Control Charger AC Output-On/Off.
Neon Type Indication Lamp For AC Supply On.
Ammeter To Indicate Charger Output With A Range To Suite
Voltmeter To Indicate Charger Output Scaled 0-80 V With 54.24
Circuit Breaker To Control Charger AC Output. Battery 1 / Off /
Charger Fail Alarm Contacts For Remote Alarm, Timer, High-Rate
14,5 48 V DC Distribution Panel Equipped With Sufficient Output sets 2,0 - 2,0 204.046.014 408.092.027 16.395.505 32.791.011 - -
8 Spare Output Circuits Of Each Rating.
Ammeter To Indicate Battery Output With A Range To Suit
Voltmeter To Indicate Busbar Voltage Scaled 40-60 V With 52 V
Battery Earthed Alarm Relay With Contacts For Remote Alarms
Battery Low Volt Alarm Relay With Contacts For Remote Alarms
Battery High Volt Alarm Relay With Contacts For Remote Alarms
Amber Indicating Lamp For Battery Earthed Fault.
Amber Indicating Lamp For Battery Low Volt.
14,6 Loose Equipment Comprising : set 1,0 - 1,0 22.853.154 22.853.154 4.372.135 4.372.135 - -
1 Syringe Hydrometer Of Suitable Scale.
1 Cell Testing Voltmeter.
1 Cell Bridging Voltmeter.
1 Instruction Card Or Manual.
1 Plastic Filler Bottle For Distilled Water.

SUB TOTAL A.14 1.421.792.622 153.024.716 - -

15. LVAC EQUIPMENT


15,1 3 Phase 4 Wire 230/400 Volt Indoor Metalclad Common Services sets 2,0 - 2,0 232.450.630 464.901.260 19.937.500 39.875.000 - -
Switchboard Comprising :
3 Pole And Neutral Main Busbar Chamber 1200 Amps Rating.
3 Pole Circuit Breaker With Neutral Link 1200 Amps Rating.
3 Pole And Neutral Circuit Breaker 400 Amps Rating.
3 Pole And Neutral Switch-Fuse 200 Amps Rating.
3 Pole And Neutral Switch-Fuse 100 Amps Rating.
3 Pole And Neutral Switch-Fuse 60 Amps Rating.
Ammeter Scaled 0-1200 Amps
Voltmeter Scaled 0-500 Volts
15,2 3 Phase 4 Wire 230/400 Volt Indoor Metalclad Essential Services sets 2,0 - 2,0 161.373.834 322.747.668 15.950.000 31.900.000 - -
Switchboard Comprising :
3 Pole And Neutral Main Busbar Chamber 600 Amps Rating.
3 Pole Circuit Breaker With Neutral Link 600 Amps Rating.
3 Pole Fuse Unit Neutral Link 600 Amps Rating.
3 Pole And Neutral Switch-Fuse 100 Amps Rating.
3 Pole And Neutral Switch-Fuse 60 Amps Rating.
Ammeter Scaled 0-600 Amps
Voltmeter Scaled 0-500 Volts
15,4 20 kV Indoor Metalclad Switchgear Single-Busbar Scheme
Incoming Cubicle
Busbar PT + Earthing Switch Cubicle
15.4.1 Auxiliary Transformer Cubicle set 2,0 (2,0) - 233.921.184 - 15.950.000 - 499.742.368 -
Outgoing Feeder Cubicle
Bus Section
15.4.2 Interface Cubicle set 2,0 (2,0) - 102.187.000 - 15.950.000 - 236.274.000 -
Bus Riser Cubicle
Including single rate tariff metering kwh-meter for incoming and
outgoing feeders.
VOLUME HARGA SATUAN USULAN TOTAL
VOLUME VOLUME PERUBAHAN SETELAH HARGA PENGADAAN HARGA JASA
NO. URAIAN PEKERJAAN SATUAN PENGURANGAN PENAMBAHAN
BOQ Pengurangan / PERUBAHAN SATUAN TOTAL SATUAN TOTAL
KONTRAK Penambahan (Rp.) (Rp.) (Rp.) (Rp.) (Rp.) (Rp.)
(1) (2) (3) (4) (4') (4'') (5) (6) = (4'') x (5) (7) (8) = (4'') x (7) (9) = -[(6) + (8)] (10) = (6) + (8)

15,5 4x20 kV XLPE 630 SQMM AL power cable/phase between bus-


15,6 20/0.4 kV 800 kVA 3-phase station auxiliary transformer sets 2,0 (2,0) - 272.104.000 - 11.600.000 - 567.408.000 -
15,7 Standbay Diesel 300 kW and accessories complete with control set 1,0 - 1,0 876.400.000 876.400.000 4.350.000 4.350.000 - -

SUB TOTAL A.15 1.664.048.928 76.125.000 1.303.424.368 -

16. 500 KV SHUNT REACTOR


Three Single Phase Unit Of 500 kV 100 MVAR Total Shunt
16,1 Reactor With Accessories Including Bushing With Creepage sets 2,0 - 2,0 19.353.578.400 38.707.156.800 559.535.000 1.119.070.000 - -
Distance 31 mm/KV.
Ring Type CT's For Mounting In The 500 KV Primary/Phase Side
16,2 sets N/A
Bushing
Neutral Side CT (Bushing) 3 core With Ratio150/1 A, Class X,
16,3 sets 6,0 - 6,0 - - - - - -
(Bushing Type)
Disconnector, 3 Pole Motor Operated And Associated Manually
Operated Earth Switch With Operating Mechanism And Local
16,4 Control Apparatus Complete With Anti-Condensation Heaters, sets 2,0 - 2,0 286.103.379 572.206.758 109.303.369 218.606.737 - -
Auxiliary Switches, Terminals, Labels, Interlocks And All
Necessary Equipment.
Connections, Post Insulators, Fittings, Clamps And All Necessary
16,5 lot 1,0 - 1,0 26.664.733 26.664.733 27.325.842 27.325.842 - -
Items, To Equip One Complete Switchbay Of Reactor.
16,6 Free Standing Transformer Marshalling Kiosk. sets 2,0 - 2,0 89.780.246 179.560.492 16.395.505 32.791.011 - -
Control Cables And Accessories For Proper Operation Of The
16,7 sets 2,0 - 2,0 16.323.681 32.647.362 12.144.819 24.289.637 - -
Reactor.

SUB TOTAL A.16 39.518.236.145 1.422.083.227 - -

17. SUBSTATION AUTOMATION HARDWARE


17.1 HMI-Operator Work Station (1 set consist 2 HMI for operator and set 1,0 - 1,0 6.600.968.157 6.600.968.157 32.647.362 32.647.362 - -

17.2 Server consist of : - CPU - KEYBOARD - MOUSE, VDU UNIT - 2,0 - 2,0
17.3 Colour Laser Printer. - 1,0 - 1,0
17.4 GPS Time reference clock complete with Antenna. sets 1,0 - 1,0
17.5 Gate Way. Set 1,0 - 1,0
17.6 Modem. Set 2,0 - 2,0
17.7 Router for communication to Sumatera Control Center Set 1,0 - 1,0
17.8 Ethernet Switch for station level (manageable). sets 2,0 - 2,0
17.9 IED Bay Control (BCU) for Common Set 1,0 - 1,0
HMI-Operator Work Station (1 set consist 2 HMI for operator and
17.10 sets
engineer ) consist of :
17.11 Furniture. set 1,0 - 1,0
17.12 Engineering Tools and Test Equipment (Laptop). set 1,0 - 1,0
Integration to the existing SAS Peranap 275 KV Substation,
17.13 set 1,0 - 1,0
Peranap 150 KV substation
Commisioning and point to point test between substation to
17.14 set 1,0 - 1,0
Sumatera control center
Miscelaneous equipment and material including cables, optical
cable, STP cable and cord, clamps, connectors, compression
17.15 lot 1,0 - 1,0
terminal, connection to individual items of equipment ….etc, to
complete the scope of works.

SUB TOTAL A.17 6.600.968.157 32.647.362 - -


VOLUME HARGA SATUAN USULAN TOTAL
VOLUME VOLUME PERUBAHAN SETELAH HARGA PENGADAAN HARGA JASA
NO. URAIAN PEKERJAAN SATUAN PENGURANGAN PENAMBAHAN
BOQ Pengurangan / PERUBAHAN SATUAN TOTAL SATUAN TOTAL
KONTRAK Penambahan (Rp.) (Rp.) (Rp.) (Rp.) (Rp.) (Rp.)
(1) (2) (3) (4) (4') (4'') (5) (6) = (4'') x (5) (7) (8) = (4'') x (7) (9) = -[(6) + (8)] (10) = (6) + (8)

18. SUBSTATION AUTOMATION SOFTWARE


18,1 Operating System set 1,0 - 1,0
18,2 Basic SA Software and Licences set 1,0 - 1,0
18,3 HMI Software set 1,0 - 1,0
Communication Protocol with Control Center Consist of IEC
18,4 set 1,0 - 1,0
60870-5-101, IEC 60870-5-104 and existing proprietary protocol
SAS Software for operation maintenance and IED Software for
18,5 set 1,0 - 1,0
configuration
18,6 Training lot - - -
18,7 FAT lot 1,0 - 1,0

SUB TOTAL A.18 - - - -

19. POWER LINE CARRIER SYSTEM


19,1 PLC TERMINAL 2 CH. set N/A
19,2 AF TELEPROTECTION set N/A
LINE TRAP 0.5 MH/3150 A - 50KA (Phase to Phase intercircuit
19,3 set N/A
connection)
19,4 LINE MATCHING UNIT/COUPLING DEVICES (PHASE TO PHASE) set N/A
19,5 COAXIAL CABLE m N/A
19,6 PAX TELEPHONE set N/A
19,7 SUBSCRIBER TELEPHONE SET set N/A
19,8 MISCELLANEOUS MATERIAL TO COMPLETE THE SYSTEM lot N/A

SUB TOTAL A.19 - - - -

20. MISCELLANEOUS
CCTV SYSTEM COMPLETE AS SPECIFIED IN THE TECHNICAL
20,1 lot 1,0 - 1,0 1.139.967.526 1.139.967.526 212.773.790 212.773.790 - -
SPECIFICATION consist of :
Miscellaneous equipment and material including power cables,
video cable, network cable, patch cord, pig tail, connectors,
20,2 lot 1,0 - 1,0 205.193.300 205.193.300 212.773.790 212.773.790 - -
compression terminal, connection to individual items of
equipment, etc, to complete the scope of works.

SUB TOTAL A.20 1.345.160.826 425.547.580 - -

21. TRAINING
21,1 Substation Automation Engineer ( 3 trainee, 15 duration) MD 45,0 - 45,0 - - 8.499.693 382.486.203 - -
Substation Automation Operation and Maintenance ( 3 trainee,
21,2 MD 30,0 - 30,0 - - 8.499.693 254.990.802 - -
10 duration)
Substation Telecommunication Operation and Maintenance Staff
21,4 MD 30,0 - 30,0 - - 8.499.693 254.990.802 - -
( 3 trainee, 10 duration)

SUB TOTAL A.21 - 892.467.807 - -

22. TEST AND COMISSIONING lot 1,0 - 1,0 - - 2.928.314.432 2.928.314.432 - -


23. JASA SERTIFIKASI lot - - - - - -
24. As Built Drawing in hard and soft copy consist of : sets 3,0 - 3,0 64.809.203 194.427.608 - - - -

SUB TOTAL A.22-A.23-A.24 194.427.608 2.928.314.432 - -


TOTAL ITEM PENGADAAN MATERIAL & PEMASANGAN 188.769.178.565 33.691.044.614 20.324.047.295 21.154.899.102
VOLUME HARGA SATUAN USULAN TOTAL
VOLUME VOLUME PERUBAHAN SETELAH HARGA PENGADAAN HARGA JASA
NO. URAIAN PEKERJAAN SATUAN PENGURANGAN PENAMBAHAN
BOQ Pengurangan / PERUBAHAN SATUAN TOTAL SATUAN TOTAL
KONTRAK Penambahan (Rp.) (Rp.) (Rp.) (Rp.) (Rp.) (Rp.)
(1) (2) (3) (4) (4') (4'') (5) (6) = (4'') x (5) (7) (8) = (4'') x (7) (9) = -[(6) + (8)] (10) = (6) + (8)

B PEKERJAAN SITE SWITCHYARD


1 Preparatory work for Control Building , MV Cell and
1.1 Site Clearing m2 50.589,0 91.408,5 141.997,5 24.050 3.415.039.875 - - - 2.198.374.425
1.2 Plank name Project Unit 1,0 - 1,0 5.600.000 5.600.000 - - - -
1.3 Setting Survey and Installation of Setting plan Ls 1,0 - 1,0 4.800.000 4.800.000 - - - -
1.4 Survey Topography ( Profil memanjang dan melintang serta m2 50.589,0 91.408,5 141.997,5 1.400 198.796.500 - - - 127.971.900
1.5 Site Office(4m x 6m) complete m2 24,0 - 24,0 5.600.000 134.400.000 - - - -
1.6 Site Storage ( 3m x 10 m) m2 30,0 - 30,0 2.400.000 72.000.000 - - - -
1.7 Water Supply for Construction Ls 1,0 - 1,0 120.000.000 120.000.000 - - - -
1.8 Electrical Supply for Construction Ls 1,0 - 1,0 1.066.078.961 1.066.078.961 - - - -
1.9 Soil Investigation for control building :
1.9.1 a. Sondir pcs 5,0 - 5,0 5.670.000 28.350.000 - - - -
1.9.2 b. Boring and Test Lab ( C, Æ and g ) pcs 3,0 - 3,0 60.760.000 182.280.000 - - - -
1.9.3 c. Soil Investigation Report (Sondir & Boring) pcs 3,0 - 3,0 2.100.000 6.300.000 - - - -
1.10 Design (calculation, detail design and drawing must be Ls 1,0 - 1,0 800.000.000 800.000.000 - - - -
1.11 Exit permit to instansion Pemda .......... (IMB) must be real cost Ls 1,0 - 1,0 571.810.000 571.810.000 - - - -

SUB TOTAL B.1 6.605.455.336 - - 2.326.346.325

2 Site Works
2,1 Earth Work
2.1.1 a. Common excavation m3 32.000,0 22.691,9 54.691,9 36.569 2.000.028.091 - - - 829.820.091
2.1.2 b. Back Fill with selected material m3 32.000,0 1.913,6 33.913,6 86.695 2.940.139.552 - - - 165.899.552
2.1.3 c. Import Fill with selected material m3 2.666,7 (2.666,7) - 181.195 - - - 483.187.271 -
2.1.4 d. Soil Disposal m3 - - - 21.651 - - - - -
2.2 Slope Stability
2.2.1 a. Retaining Wall ( Stone Masonry) m3 250,0 413,9 663,9 1.332.168 884.426.335 - - - 551.384.335
2.2.2 b. Gabion m3 320,0 (320,0) - 1.239.970 - - - 396.790.400 -
2.2.3 c. Sodding ( Gebalan Rumput) m3 - - - 28.000 - - - - -
d. Concrete frame ( Concrete K175, Fe: 150kg/m3 ; BJTD-35,
2.2.4 m3 - - - 5.459.235 - - - - -
formwork)
2.3 Road Works ( Rigid Pavement)
2.3.1 a. Prepare Compacted Subgrade (Thickness 15cm) m2 10.092,0 3,0 10.095,0 16.586 167.435.670 - - - 49.758
2.3.2 b. Lean concrete K-100 (Thickness 5cm) m3 504,6 0,1 504,8 2.033.117 1.026.215.806 - - - 304.968
2.3.3 c. Concrete K-225, Fe:150kg/m3, Formwork (thickness 20cm) m3 2.018,4 0,6 2.019,0 5.553.699 11.212.918.281 - - - 3.332.219
2.3.4 d. Joint Sealing & Joint Filler (4mm) m' 800,0 2.141,1 2.941,1 52.540 154.522.767 - - - 112.490.767
2.4 Kerbs (15/30)
2.4.1 a. Precast Concrete Kerbs for Switchyard (15x30x50 cm) m' 694,0 (694,0) - 280.990 - - - 195.007.060 -
2.4.2 b. Precast Concrete Kerbs for Road (20x30x50 cm) m' 804,0 1.478,0 2.282,0 296.490 676.590.180 - - - 438.212.220
2.5 Fence Complete with accessories, and Foundation
2.5.1 a. BRC 1.50 m height For Switchyard m' 560,0 800,0 1.360,0 1.015.079 1.380.507.440 - - - 812.063.200
2.5.2 b. BRC 1.90 m height m' 326,0 (323,0) 3,0 1.197.101 3.591.303 - - 386.663.623 -
c. Brick Wall Fence 2,4 m height (lower part) complete with tie
2.5.3 m' 1.200,0 790,0 1.990,0 2.680.071 5.333.341.290 - - - 2.117.256.090
beam, wall painting and barbed wire 0,60 m height (Upper part)
2.5.4 d. Fabricated Concrete Fence 2.40 m height m' - - - - - - - - -
2.6 Gate Complete with pole, accessories and foundation
2.6.1 a. Sliding gate BRC 1.90 m height, 7 m width ( include Column Unit 1,0 - 1,0 28.175.000 28.175.000 - - - -
2.6.2 b. Single Gate BRC 1.50m hight, 3 m Width Unit 4,0 (1,0) 3,0 9.660.000 28.980.000 - - 9.660.000 -
2.7 Landscaping m2 1.000,0 - 1.000,0 490.000 490.000.000 - - - -
2.8 Gravel (dia 3 - 5 cm); thickness = 20 cm m2 25.500,0 1.885,0 27.385,0 207.713 5.688.220.505 - - - 391.539.005
Cable trench (K225, BJTD 40 incld cover, Galvanized Cable Tray
2.9
L 50.50.5 and PVC Pipe)
2.9.1 a. Cable duct type 1 (Large, Width > 80 cm) m' 137,0 768,5 905,5 4.136.595 3.745.686.773 - - - 3.178.973.258
2.9.2 b. Cable duct type 2 (Medium, Width > 60 cm, < 80 cm) m' 568,0 320,0 888,0 3.282.252 2.914.639.776 - - - 1.050.320.640
2.9.3 c. Cable duct type 3 (Small, Width < 60 cm) m' 760,0 (698,2) 61,8 2.735.075 169.027.635 - - 1.909.629.365 -
2.9.4 d. Cable Duct (Crossing Road) m' 12,0 57,0 69,0 5.136.319 354.406.011 - - - 292.770.183
Open Drainage for Switchyard, Control building and substation
2.10 m' 540,0 190,0 730,0 660.168 481.922.640 - - - 125.431.920
area
2.11 Sub soil Drainage PVC dia 6 inc including gravel & Palm Fibre m' 800,0 - 800,0 709.092 567.273.600 - - - -
2.12 Fire wall reinforced concrete grade 225/20 complete with m3 - - -
VOLUME HARGA SATUAN USULAN TOTAL
VOLUME VOLUME PERUBAHAN SETELAH HARGA PENGADAAN HARGA JASA
NO. URAIAN PEKERJAAN SATUAN PENGURANGAN PENAMBAHAN
BOQ Pengurangan / PERUBAHAN SATUAN TOTAL SATUAN TOTAL
KONTRAK Penambahan (Rp.) (Rp.) (Rp.) (Rp.) (Rp.) (Rp.)
(1) (2) (3) (4) (4') (4'') (5) (6) = (4'') x (5) (7) (8) = (4'') x (7) (9) = -[(6) + (8)] (10) = (6) + (8)

2.13 Post security (4m x 4 m) included toilet 1,5m x 1,5m unit 1,0 - 1,0 12.600.000 12.600.000 - - - -
2.14 Loading test No 1,0 - 1,0 436.679.320 436.679.320 - - - -
2.15 Pilling Foundation
2.15.1 b. Bored Pile dia. 60 cm m' 1.320,0 2.707,5 4.027,5 1.603.966 6.459.892.867 - - - 4.342.657.747
2.15.2 c. Driven Pile dia. 50 cm m' 10,0 (10,0) - 1.659.696 - - - 16.596.960 -
-
Item baru
2.16 Firewall unit - 7,0 7,0 202.611.966 1.418.283.761 - - - 1.418.283.761
2.17 Oil pit unit - 2,0 2,0 109.486.776 218.973.551 - - - 218.973.551
2.18 Ground Reservoir unit - 1,0 1,0 150.520.480 150.520.480 - - - 150.520.480

2.19 Site and Road Lighting


2.19.1 1. Mercury Vapour Flouresent light 1 x 250 W NO 24,0 - 24,0 50.099.022 1.202.376.538 - - - -
complete with lighting column 9 m high, fuse
box, grounding system and installation of cable
conduit and wiring and all accessories and
foundation of column
-
2.20 2. Mercury flood light 2x400 W complete with NO 10,0 - 10,0 88.691.416 886.914.164 - - - -
2.20.1 15 m height, fuse box, grounding system and
installation of cable conduit and wiring and
all accessories and foundation of column
-
2.21 3. Mercury Vapour Flouresent light 1 x 80 W NO 6,0 - 6,0 86.445.918 518.675.511 - - - -
2.21.1 complete with lighting column 2 m high, fuse
box, grounding system and installation of cable
conduit and wiring and all accessories and
foundation of column
-
2.22 4. Lighting panel outdoor complete with folo cell Sets 1,0 - 1,0 25.277.301 25.277.301 - - - -
2.22.1 switch fuse, mcb, grouding system -
indicator wiring and all accessories (foto cell) -
and foundation of panel -

SUB TOTAL B.2 51.578.242.148 - 3.397.534.679 16.200.283.745


-
3 Foundation for 500 kV
3.1 Gantries Units 31,0 - 31,0 404.075.587 12.526.343.197 - - - -
3.2 Intermediate Tower Units - - -
3.3 Circuit Breakers Units 30,0 - 30,0 71.106.472 2.133.194.160 - - - -
3.4 Capacitor Voltage Transformer Units 14,0 - 14,0 29.397.777 411.568.878 - - - -
3.5 Current Transformer Units 42,0 - 42,0 29.397.777 1.234.706.634 - - - -
3.6 Surge Arrester Units 12,0 - 12,0 29.397.777 352.773.324 - - - -
3.7 Post Insulator Units 32,0 (12,0) 20,0 29.397.777 587.955.540 - - 352.773.324 -
3.8 Marshalling Kiosks Units 10,0 2,0 12,0 12.073.099 144.877.188 - - - 24.146.198
3.9 Neutral Grounding Resistors Units - - -
3.10 IBT Transformer (single phase) Units - - -
3.11 Voltage Transformers Units 4,0 - 4,0 29.397.777 117.591.108 - - - -
3.12 Disconnecting /& Earthing Switches (DS/E) Sets 20,0 (2,0) 18,0 29.397.777 529.159.986 - - 58.795.554 -
3.13 Disconnector Pantograph Sets 8,0 - 8,0 29.397.777 235.182.216 - - - -
3.14 Reactor 500 kV Units 2,0 - 2,0 162.656.822 325.313.644 - - - -
3.15 Line Traps Units 4,0 - 4,0 29.397.777 117.591.108 - - - -
3.16 Pantograph Isolator Units - - -
3.17 Service Transformer Units 2,0 (2,0) - 14.473.012 - - - 28.946.024 -
-
Item baru -
3.18 Earthing Switch. Sets - 2,0 2,0 49.864.945 99.729.889 - - - 99.729.889

SUB TOTAL B.3 18.815.986.872 - 440.514.902 123.876.087


TOTAL ITEM PEKERJAAN SITE SWITCHYARD 76.999.684.356 - 3.838.049.581 18.650.506.157
VOLUME HARGA SATUAN USULAN TOTAL
VOLUME VOLUME PERUBAHAN SETELAH HARGA PENGADAAN HARGA JASA
NO. URAIAN PEKERJAAN SATUAN PENGURANGAN PENAMBAHAN
BOQ Pengurangan / PERUBAHAN SATUAN TOTAL SATUAN TOTAL
KONTRAK Penambahan (Rp.) (Rp.) (Rp.) (Rp.) (Rp.) (Rp.)
(1) (2) (3) (4) (4') (4'') (5) (6) = (4'') x (5) (7) (8) = (4'') x (7) (9) = -[(6) + (8)] (10) = (6) + (8)

C CONTROL BUILDING SAS


1 Foundation work - -
1.1 Common Excavation m3 860,0 437,4 1.297,4 36.569 47.446.083 - - - 15.996.743
1.2 Backfill with selected material m3 530,0 536,7 1.066,7 86.695 92.473.222 - - - 46.524.872
1.3 Compacted sand layer t : 10 cm m3 93,0 (45,9) 47,1 536.695 25.283.701 - - 24.628.934 -
1.4 Lean Concrete t ; 10 cm, 1 PC : 3 Sand : 5 Split (t:5cm) m2 567,0 (543,4) 23,6 203.312 4.790.024 - - 110.487.710 -
1.5 Stone Masonry 1 PC : 3 Sand m3 27,0 (27,0) - 1.332.168 - - - 35.968.536 -
1.6 Borepile Dia 60 m m' 342,0 (342,0) - 1.603.966 - - - 548.556.372 -
1.7 Concrete Reinforcement for Foundation K225, Fe :225 kg/m3 m3 104,5 116,9 221,4 6.117.556 1.354.304.547 - - - 715.019.945

SUB TOTAL C.1 1.524.297.577 - 719.641.552 777.541.560

2 Structure (Steel and Concrete), Stairs works and wall


2.1 Column Work (Concrete K225, Fe : 180 kg/m3) m3 90,0 26,0 116,0 6.923.712 803.289.066 - - - 180.154.986
2.2 Balk Work ( Concrete K225, Fe :180 kg/m3) m3 49,7 11,8 61,5 6.529.067 401.537.621 - - - 77.173.572
2.3 Slab Floor Work ( Concrete K225, Fe:180 kg/m3, Thickness m3 113,4 71,3 184,7 5.518.776 1.019.373.115 - - - 393.543.917
2.4 Stairs Work ( Concrete K225, Fe :150 kg/m3) m3 10,0 (3,1) 6,9 5.553.699 38.542.671 - - 16.994.319 -
Column, Sloof and ring balk practical work ( Concrete K225, Fe
2.5 m3 14,5 (1,9) 12,6 6.874.767 86.415.821 - - 13.268.300 -
:100kg/m3)
Steel Structure for Entrance Stairs, Complete with connection
2.6 kg 9.750,0 (7.644,6) 2.105,4 33.740 71.037.546 - - 257.927.454 -
and Accessories
Hand Rail and Fence for Stairs (Stainless Steel) Complete with
2.7 m' 98,0 (43,8) 54,2 2.851.317 154.541.381 - - 124.887.685 -
Connection & Accessories
2.8 Canopy ( Concrete K225, Fe :150kg/m3) m3 18,0 14,9 32,9 5.553.699 182.550.086 - - - 82.583.504
2.9 A half brick Wall 1 PC : 4 Sand m3 605,0 (605,0) - 224.710 - - - 135.949.550 -
2.10 A half brick Wall 1 PC : 4 Sand m2 - 1.576,7 1.576,7 224.710 354.309.245 - - - 354.309.245
2.11 Partition(gypsum) Framing complete with installation m2 85,5 (85,5) - 388.958 - - - 33.255.909 -

SUB TOTAL C.2 3.111.596.552 - 582.283.217 1.087.765.224

3 Roof Work
3.1 Steel trusses complete with connection kg 33.600,0 (18.510,3) 15.089,7 33.740 509.127.153 - - 624.536.847 -
3.2 Purlin kg 3.360,0 106,9 3.466,9 33.740 116.973.206 - - - 3.606.806
3.3 Wind Bracing and tie rod kg 10.080,0 (9.728,7) 351,35 33.740 11.854.549 - - 328.244.651 -
PVC Pipe vertical dia 3 inch ( Included bends, tees, albows,
3.4 m' 98,0 199,6 297,6 184.158 54.805.421 - - - 36.757.937
reducers, adaptors, roof drain)
Water proofing membrane type Thickness 3 mm and mortar
3.5 m2 25,0 229,6 254,6 329.447 83.890.384 - - - 75.654.209
screed
3.6 Corrugated metal sheet complete with accessories m2 1.055,0 (352,6) 702,4 260.400 182.894.544 - - 91.827.456 -
3.7 Acrylie Roof complete with Accessories m2 - - - - - - - - -
3.8 Foam Foil Insulation m2 567,0 135,4 702,4 105.996 74.447.351 - - - 14.347.619

SUB TOTAL C.3 1.033.992.607 - 1.044.608.954 130.366.570


-
4 Floor Work
4.1 Floor Concrete K125 Thickness 10 cm Around Control Building m2 103,0 412,0 515,0 208.009 107.124.635 - - - 85.699.708
4.2 Plain Concrete 10.0/20 or 10.0/40 , t : 15 cm m2 - - -
4.3 Ceramic Tile 40 cm x 40 cm , 1 PC : 3 Sand m2 729,0 (150,6) 578,4 326.112 188.623.181 - - 49.112.467 -
4.4 Ceramic wall (20 cm x 25 cm) and floor (20 cm x 20 cm) 1PC : 3 m2 24,0 43,3 67,3 326.112 21.953.860 - - - 14.127.172
4.5 Raised floor m2 337,5 67,5 405,0 2.118.084 857.824.020 - - - 142.970.670
4.6 Stepnosing (For Terrace and Stairs) m' 55,0 35,0 90,0 44.647 4.018.230 - - - 1.562.645

Item baru
4.7 Floor hardener m2 - 168,8 168,8 95.000 16.036.000 - - - 16.036.000

SUB TOTAL C.4 1.195.579.926 - 49.112.467 260.396.195


VOLUME HARGA SATUAN USULAN TOTAL
VOLUME VOLUME PERUBAHAN SETELAH HARGA PENGADAAN HARGA JASA
NO. URAIAN PEKERJAAN SATUAN PENGURANGAN PENAMBAHAN
BOQ Pengurangan / PERUBAHAN SATUAN TOTAL SATUAN TOTAL
KONTRAK Penambahan (Rp.) (Rp.) (Rp.) (Rp.) (Rp.) (Rp.)
(1) (2) (3) (4) (4') (4'') (5) (6) = (4'') x (5) (7) (8) = (4'') x (7) (9) = -[(6) + (8)] (10) = (6) + (8)

5 Plasterig & Grouting


5.1 Plastering wall work t : 10 cm, 1PC : 4 Sand m2 5.760,0 (1.479,5) 4.280,5 70.922 303.582.330 - - 104.928.390 -
5.2 Acian m2 5.760,0 (1.479,5) 4.280,5 44.825 191.873.861 - - 66.318.139 -
5.3 Grouting cement work m3 8,0 (7,4) 0,6 24.696.000 14.817.600 - - 182.750.400 -
5.4 Brafen for foundation 1 PC : 2 Sand m2 75,0 (75,0) - 44.825 - - - 3.361.875 -

SUB TOTAL C.5 510.273.791 - 357.358.804 -

6 Doors and windows


Glass door complete with aluminium frame and accessories:
6.1 Type P1 (Double Door, 150 W/ 250 H) unit 8,0 - 8,0 7.728.000 61.824.000 - - - -
6.2 Type P1A ( Double Door, 180 W / 250 H with 2 Glass window ) Unit 1,0 (1,0) - 14.404.320 - - - 14.404.320 -
6.3 Type P2 (Single Door, 110 W/ 250 H) unit 6,0 1,0 7,0 5.456.640 38.196.480 - - - 5.456.640
6.4 Type P3 (Fibre door, 85 W/ 200 H) unit 3,0 - 3,0 5.040.000 15.120.000 - - - -
6.5 Type P4 ( Rolling Door, 250 W / 260 H) unit - - - 5.460.000 - - - - -

Glass window complete with aluminium frame, Sun screen and -


6.6 Type J1 ( 230 W/ 160 H with 1 Window Frame and 2 fixed glass) unit 12,0 (8,0) 4,0 6.913.200 27.652.800 - - 55.305.600 -
6.7 Type J2 ( 325 W / 140 H with Sliding window ) unit 10,0 11,0 21,0 12.666.150 265.989.150 - - - 139.327.650
6.8 Type J3 ( 200 W / 140 H with 1 Window frame and 2 fixed glass) unit 6,0 (3,0) 3,0 5.858.160 17.574.480 - - 17.574.480 -
6.9 Type J4 ( 135 W / 140 H with 2 Window frame ) unit 2,0 1,0 3,0 5.461.680 16.385.040 - - - 5.461.680
6.10 Type J5 ( 50 W / 195 H, one window frame) unit 8,0 (6,0) 2,0 3.578.400 7.156.800 - - 21.470.400 -

Glass ventilations complete with aluminium frame and -


6.11 Type V1 unit - 4,0 4,0 1.864.296 7.457.184 - - - 7.457.184
6.12 Type V1A unit - 16,0 16,0 2.150.442 34.407.072 - - - 34.407.072
6.13 Type V2 unit - - - 853.373 - - - - -
6.14 Type V3 unit - 1,0 1,0 1.077.754 1.077.754 - - - 1.077.754
6.15 Type V3A unit - 4,0 4,0 1.706.746 6.826.984 - - - 6.826.984
6.16 Type V4 unit - 8,0 8,0 726.668 5.813.344 - - - 5.813.344
6.17 Type V4A ( 135 W/50 H, with 2 ventilation) for Toilet unit 3,0 (1,0) 2,0 877.868 1.755.736 - - 877.868 -
6.18 Type V5 unit - - - 375.581 - - - - -
6.19 Type V5A unit - - - 451.181 - - - - -

SUB TOTAL C.6 507.236.824 - 109.632.668 205.828.308

7 Ceiling work - -
7.1 Acoustic ceiling complete with hanger, Aluminium frame and m2 1.134,0 (67,5) 1.066,5 420.000 447.930.000 - - 28.350.000 -
7.2 Aluminium ceiling complete with hanger, frame and painting m2 103,0 (1,1) 101,9 672.000 68.476.800 - - 739.200 -

SUB TOTAL C.7 516.406.800 - 29.089.200 -

8 Water Supply, Pipe Works And Drainage :


Fiber Water tank cap 1.2 m3 and jet pump complete with
8.1 Ls 1,0 - 1,0 48.821.000 48.821.000 - - - -
Instalation
Submersible pump complete with Instalation piping for drainage
8.2 Ls - - - - - - - - -
basement
Installation of Water Supply complete Pipe PVC and fittings (
8.3 Include for all pipes, bends, tees, albows, reducers, adaptors, Ls 1,0 - 1,0 14.500.000 14.500.000 - - - -
taps and connections to fittings, appliances)
Installation of Water waste complete Pipe PVC and fittings (
8.4 Include for all pipes, bends, tees, albows, reducers, adaptors, Ls 1,0 - 1,0 21.750.000 21.750.000 - - - -
metal grill and connections to fittings, appliances)

SUB TOTAL C.8 85.071.000 - - -


VOLUME HARGA SATUAN USULAN TOTAL
VOLUME VOLUME PERUBAHAN SETELAH HARGA PENGADAAN HARGA JASA
NO. URAIAN PEKERJAAN SATUAN PENGURANGAN PENAMBAHAN
BOQ Pengurangan / PERUBAHAN SATUAN TOTAL SATUAN TOTAL
KONTRAK Penambahan (Rp.) (Rp.) (Rp.) (Rp.) (Rp.) (Rp.)
(1) (2) (3) (4) (4') (4'') (5) (6) = (4'') x (5) (7) (8) = (4'') x (7) (9) = -[(6) + (8)] (10) = (6) + (8)

9 Kitchen and Sanitary work


9.1 Bath basin complete accessories unit 2,0 (2,0) - 7.894.800 - - - 15.789.600 -
9.2 Squatting water closed complete accessories unit 2,0 1,0 3,0 4.386.000 13.158.000 - - - 4.386.000
9.3 Urinal complete accessories unit - - - 4.035.120 - - - - -
9.4 Wash basin (Stainless Steel) for pantry complete accessories unit 1,0 - 1,0 6.140.400 6.140.400 - - - -
9.5 Wastafel complete accessories unit 2,0 - 2,0 7.017.600 14.035.200 - - - -
9.6 Wash basin for ritual complete accessories unit 1,0 2,0 3,0 6.140.400 18.421.200 - - - 12.280.800

SUB TOTAL C.9 51.754.800 - 15.789.600 16.666.800

10 Septic tank works (4 m2) complete Installation,


10.1 Septic tank works (4 m2) complete Installation, Infiltrate with Palm-Fibre & sand Stone
unit 1,0 - 1,0 8.435.571 8.435.571 - - - -

11 Cable Tray Works (Metal )


11.1 Galvanized cable tray for Cable Power m' - - -
11.2 Galvanized cable tray for Cable Control m' 185,0 - 185,0 420.000 77.700.000 - - - -
11.3 Water stop for Cable Duct ( Concrete and Sheller) Sets - - -

SUB TOTAL C.10 dan C.11 86.135.571 - - -

12 CABLE DUCT INCD METAL WORKS


Concrete Cable Duct Type I ( K175 ; Fe : 100kg/m3) included
12.1 Galvanized Cable Tray Steel Angle 50.50.5 and Chequered Plate m' - - - 7.845.189 - - - - -
6mm
Concrete Cable Duct Type II ( K175 ; Fe : 100kg/m3) included
12.2 Galvanized Cable Tray Steel Angle 50.50.5 and Chequered Plate m' 70,0 (26,6) 43,4 4.458.967 193.608.347 - - 118.519.343 -
6mm
Concrete Cable Duct Type III ( K175 ; Fe : 100kg/m3) included
12.3 Galvanized Cable Tray Steel Angle 50.50.5 and Chequered Plate m' 75,0 (24,2) 50,8 3.598.959 182.827.117 - - 87.094.808 -
6mm

SUB TOTAL C.12 376.435.464 - 205.614.151 -

13 Painting works
13.1 Wall Painting exterior (Grade Weathershield) m2 1.980,0 1.876,8 3.856,8 53.912 207.927.802 - - - 101.182.042
13.2 Wall Painting Interior m2 4.252,0 (1.447,5) 2.804,5 47.479 133.156.755 - - 68.723.953 -
Aluminium & Steel Painting ( Lead Primer, Undercoat and Gloss
13.3 m2 1.127,0 (158,6) 968,4 4.900 4.745.209 - - 777.091 -
Paint)

SUB TOTAL C.13 345.829.765 - 69.501.044 101.182.042

14 Electrical
Balcon And Lobby Room
14.1 Downlight fitting including installation, wiring, switch and LED 9 Sets 20,0 - 20,0 594.550 11.890.992 - - - -
14.2 Stop Contact including installation and wiring Sets 4,0 - 4,0 567.940 2.271.761 - - - -
14.3 Emergency Lighting including installation, wiring and Lamp 30 Sets 2,0 - 2,0 3.739.832 7.479.665 - - - -

Corridor, AC/DC, Batteray, Hall, Pantry, Toilet, Storage, Meeting,


Staff, and Leader Room at First Floor
Downlight fitting including installation, wiring, switch and LED 9
14.4 Sets 46,0 (1,0) 45,0 594.550 26.754.732 - - 594.550 -
watt
Spotlight fitting including installation, wiring, switch and Lamp 40
14.5 Sets 28,0 (1,0) 27,0 1.236.643 33.389.371 - - 1.236.643 -
watt ( For Corridor AC/DC, Batteray and Storage Room)
14.6 Stop contact including installation wiring Sets 21,0 - 21,0 567.940 11.926.748 - - - -
14.7 Stop contact AC including installation wiring Sets 3,0 - 3,0 667.999 2.003.998 - - - -
14.8 Emergency lighting including installation wiring and lamp 20W. Sets 12,0 - 12,0 3.739.832 44.877.988 - - - -
VOLUME HARGA SATUAN USULAN TOTAL
VOLUME VOLUME PERUBAHAN SETELAH HARGA PENGADAAN HARGA JASA
NO. URAIAN PEKERJAAN SATUAN PENGURANGAN PENAMBAHAN
BOQ Pengurangan / PERUBAHAN SATUAN TOTAL SATUAN TOTAL
KONTRAK Penambahan (Rp.) (Rp.) (Rp.) (Rp.) (Rp.) (Rp.)
(1) (2) (3) (4) (4') (4'') (5) (6) = (4'') x (5) (7) (8) = (4'') x (7) (9) = -[(6) + (8)] (10) = (6) + (8)

MDP including installation fuse, switch, MCB, wiring pipe


14.9 Sets 1,0 - 1,0 36.781.100 36.781.100 - - - -
indicator lamp and grounding system
SP including installation fuse, switch, MCB, wiring pipe indicator
14.10 Sets 2,0 - 2,0 29.711.285 59.422.570 - - - -
lamp and grounding system

Corridor,Control & Protection Panel, Telecommunication,


Mushola, Toilet Room at Second Floor
Downlight fitting including installation, wiring, switch and LED 9
14.11 Sets 10,0 1,0 11,0 594.550 6.540.046 - - - 594.550
watt
Spotlight fitting including installation, wiring, switch and Lamp 40
14.12 Sets 26,0 11,0 37,0 1.236.643 45.755.804 - - - 13.603.077
watt (for Corridor, Control Protection and Telkom Room)
14.13 Stop contact including installation wiring Sets 25,0 - 25,0 567.940 14.198.509 - - - -
14.14 Stop contact AC including installation wiring Sets 23,0 - 23,0 667.999 15.363.985 - - - -
14.15 Stop contact TV including installation wiring Sets 1,0 - 1,0 415.500 415.500 - - - -
14.16 Emergency lighting including installation wiring and lamp 20W. Sets 27,0 - 27,0 3.739.832 100.975.474 - - - -

SUB TOTAL C.14 420.048.243 - 1.831.193 14.197.627

15 Air Conditioner and exhaust fan -


15.1 AC Split 4 PK, R 134 A NO 4,0 - 4,0 36.563.989 146.255.955 - - - -
15.2 AC Split 2 PK, R 134 A NO 17,0 - 17,0 20.474.108 348.059.830 - - - -
15.3 AC Split 1 PK, R 134 A NO 2,0 - 2,0 12.668.038 25.336.077 - - - -
15.4 exhaust Fan 800 CFM, 1200 RPM Industrid type NO 2,0 - 2,0 7.978.062 15.956.123 - - - -

SUB TOTAL C.15 535.607.985 - - -

16 Lighting Protection -
Cable BC 70 mm including all accessories clamps steel plate,
16.1 Lot 1,0 - 1,0 76.984.136 76.984.136 - - - -
material support and spole, grounding system for control building

17 Fire Alarm
17.1 Alarm bell 6" (150 mm) diameter including installation wiring NO 27,0 (3,0) 24,0 3.756.356 90.152.544 - - 11.269.068 -
17.2 Smoke detector including installation wiring NO 25,0 (3,0) 22,0 4.929.303 108.444.666 - - 14.787.909 -
Fixed and rate of rise temperature detector including installation
17.3 NO 25,0 (3,0) 22,0 4.929.303 108.444.666 - - 14.787.909 -
wiring
MCFA (Master Control Fire Almr) Including indication lamp,
17.4 NO 1,0 - 1,0 196.078.235 196.078.235 - - - -
batttery rectifier and all accessories

SUB TOTAL C.16 DAN C.17 580.104.247 - 40.844.886 -

18 Fire Fighting Equipment -


18.1 Portable fire extinghuister (5 kg hallon) NO 20,0 - 20,0 4.468.500 89.370.000 - - - -

19 Crane Manual -
19.1 Crane Manual complete with accessories capacity 1,0 ton NO 1,0 - 1,0 78.948.000 78.948.000 - - - -
SUB TOTAL C.18 DAN C.19 168.318.000 - - -
TOTAL ITEM PEKERJAAN CONTROL BUILDING SAS 11.048.689.154 - 3.225.307.736 2.593.944.326
VOLUME HARGA SATUAN USULAN TOTAL
VOLUME VOLUME PERUBAHAN SETELAH HARGA PENGADAAN HARGA JASA
NO. URAIAN PEKERJAAN SATUAN PENGURANGAN PENAMBAHAN
BOQ Pengurangan / PERUBAHAN SATUAN TOTAL SATUAN TOTAL
KONTRAK Penambahan (Rp.) (Rp.) (Rp.) (Rp.) (Rp.) (Rp.)
(1) (2) (3) (4) (4') (4'') (5) (6) = (4'') x (5) (7) (8) = (4'') x (7) (9) = -[(6) + (8)] (10) = (6) + (8)

D SUBSTATION VOLTAGE TRANFORMER ( SSVT )


1 Electrical & Mechanical Material
1.1 Substation Service Voltage tranformer units - 6,0 6,0 2.033.800.775 12.202.804.650 105.583.333 633.500.000 - 12.836.304.650
1.2 Steel Support for SSVT sets - - - - - - - - -
1.3 Connector for SSVT sets - 6,0 6,0 234.378 1.406.268 - - - 1.406.268
1.4 Conductor TAL 2x850 mm2 meter - 600,0 600,0 243.392 146.035.200 - - - 146.035.200
1.5 LV Power cable ( 1x300 sqmm ), control cable and accesories meter - 2.350,0 2.350,0 280.145 658.340.750 - - - 658.340.750
1.6 Free Standing Cubicle units - 2,0 2,0 156.175.751 312.351.502 - - - 312.351.502
SUB TOTAL D.1 13.320.938.370 633.500.000 - 13.954.438.370

2 Civil Material
2.1 Foundation of SSVT units - 6,0 6,0 30.491.590 182.949.540 - - - 182.949.540
2.2 Foundation of Marshaling Kiosk units - 2,0 2,0 12.073.099 24.146.198 - - - 24.146.198
SUB TOTAL D.2 207.095.738 - - 207.095.738
TOTAL ITEM PEKERJAAN SUBSTATION VOLTAGE
13.528.034.108 633.500.000 - 14.161.534.108
TRANFORMER ( SSVT )
TOTAL ITEM A + B + C + D 290.345.586.183 34.324.544.614 27.387.404.612 56.560.883.693
ANALISA HARGA SATUAN PEKERJAAN
NEW ITEM ( CIVIL WORK )
Harga Satuan Jumlah Harga
No Uraian Pekerjaan Sat Vol
Usulan Usulan
(1) (2) (3) (4) (5) (6 = 4 x 5)

2.1 Foundation SSTV Units 1 32.331.589,97


1 Concrete K 225 m³ 5,92 2.176.117,00 12.882.612,64
2 Lean Concrete K 100 m³ 0,45 2.033.117,00 914.902,65
3 Galian Tanah m³ 20,25 36.569,00 740.522,25
4 Back Fill m³ 14,32 86.695,00 1.241.472,40
5 Bekisting m² 17,38 236.787,00 4.115.358,06
6 Penulangan kg 651,27 15.411,00 10.036.721,97
7 Anchor bolt M 30 bh 4,00 600.000,00 2.400.000,00

3.18 Foundation of Earthing Switch Units 1 49.864.944,56


1 Galian Tanah m3 44,93 36.569,00 1.643.045,17
2 Urugan Pasir m3 2,03 536.695,00 1.089.490,85
3 Lean Concrete m3 1,01 2.033.117,00 2.053.448,17
4 Concrete K.225 m3 9,73 2.176.507,00 21.177.413,11
5 Penulangan Ulir kg 1.309,28 15.411,00 20.177.314,08
6 Bekisting m2 9,14 236.787,00 2.164.233,18
7 Anchor Bolt M24 set 12,00 130.000,00 1.560.000,00

4.7 Floor Hardener m2 1 120.000,00


1 Material :
Floor hardener m2 1,00 120.000,00 120.000,00

2 Alat bantu : include


3 Upah : -
Upah hampar / pasang m2 1,00 include
Harga Satuan Jumlah Harga
No Uraian Pekerjaan Sat Vol
Usulan Usulan
(1) (2) (3) (4) (5) (6 = 4 x 5)

2.18 Ground Reservoir Units 1 150.520.480,22


1 Galian Tanah m3 216,00 36.569,00 7.898.904,00
2 Urugan Pasir t = 10 m m3 3,00 536.695,00 1.610.085,00
3 Lean Concrete t = 5 cm m3 1,50 2.033.117,00 3.049.675,50
4 Concrete K.225 m3 25,16 2.176.507,00 54.760.916,12
5 Besi tulangan kg 3.324,09 15.411,00 51.227.550,99
6 Bekisting m2 135,03 236.787,00 31.973.348,61

2.17 Oil Pit Units 1 109.486.775,72


1 Galian Tanah m3 83,79 36.569,00 3.064.116,51
2 Gravel m2 57,80 207.713,00 12.005.811,40
3 Urugan Pasir m3 2,50 536.695,00 1.341.737,50
4 Lean Concrete m3 1,25 2.033.117,00 2.541.396,25
5 Concrete K.225 m3 13,64 2.176.507,00 29.687.555,48
6 Penulangan Ulir kg 1.866,01 15.411,00 28.757.080,11
7 Bekisting m2 103,81 236.787,00 24.580.858,47
8 Ladder besi beton (U) dia 16" & painted kg 20,00 15.411,00 308.220,00
9 PVC dia 12" m1 24,00 300.000,00 7.200.000,00

2.16 Fire Wall Units 1 202.611.965,87


1 Galian Tanah m3 27,00 36.569,00 987.363,00
2 Urugan Pasir m3 2,75 536.695,00 1.475.911,25
3 Lean Concrete m3 1,38 2.033.117,00 2.805.701,46
4 Concrete K.225 m3 39,27 2.176.507,00 85.471.429,89
5 Penulangan Ulir kg 3.826,09 15.411,00 58.963.872,99
6 Bekisting m2 223,44 236.787,00 52.907.687,28
TABEL HARGA SATUAN
PEMBANGUNAN GARDU INDUK TEGANGAN EKSTRA TINGGI 500 KV PERANAP
SUB STATION SERVICE TRANSFORMER ( SSVT )

HARGA SATUAN
KONTRAK USULAN KONTRAKTOR
NO. URAIAN PEKERJAAN SATUAN
PENGADAAN PENGADAAN
PEMASANGAN JUMLAH PEMASANGAN JUMLAH
MATERIAL MATERIAL
(1) (2) (3) (4) (5) (6) (7) (8) (9)

SUBSTATION VOLTAGE TRANFORMER ( SSVT )


1 Electrical & Mechanical Material

1.1 Substation Service Voltage tranformer units 2.033.800.775 105.583.333 2.139.384.108


1.2 Steel Support for SSVT sets - -
1.3 Connector for SSVT sets 234.378 Include in 1.1 234.378
1.4 Conductor TAL 2x850 mm2 meter 243.392 Include in 1.1 243.392
1.5 LV Power cable ( 1x300 sqmm ), control cable and accesories meter 280.145 Include in 1.1 280.145
1.6 Free Standing Cubicle units 156.175.751 Include in 1.1 156.175.751

SUB TOTAL D.1

2 Civil Material

2.1 Foundation of SSVT units 32.331.590 32.331.590


2.2 Foundation of Marshaling Kiosk units 12.073.099 12.073.099

SUB TOTAL D.2


TOTAL SUBSTATION VOLTAGE TRANFORMER ( SSVT )