= 22939,6043 m3
Volume bak penampung air sungai :
Volume balok = P x L x H
1
Volume prisma = 2 x P x L x Hp
Asumsi :
Panjang (P) =2L
Kedalaman (H) =L
1
Kedalaman Prisma (Hp) =2L
1
Volume bak penampung air sungai = P x L x H + 2 x P x L x Hp
1 1
22939,6043 m3 =2LxLxL+2x2LxLx2L
1
22939,6043 m3 = 2 2 L3
L = 20,9354 m
P = 41,8708 m
H = 20,9354 m
Hp = 10,4677 m
Spesifikasi Bak Penampung Air Sungai
Panjang (P) = 41,8708 m
Lebar (L) = 20,9354 m
Kedalaman (H) = 20,9354 m
Kedalaman Prisma (Hp) = 10,4677 m
2. Tangki Koagulasi
Asumsi padatan yang mengendap 10% dari total air yang dibutuhkan
Rate Volumetrik Padatan = 10% x Total air yang dibutuhkan
= 10% x 18351,6834 m3/hari
= 1835,1683 m3/hari
Q1 = Debit air yang akan masuk ke tangki koagulasi
Q1 = Total air yang dibutuhkan - Rate Volumetrik Padatan
= 18351,6834 m3/hari – 1835,1683 m3/hari
= 16516,5151 m3/hari = 16516515,1 L/hari
Waktu tinggal (t) = 5 menit = 0,003472 hari
Jenis koagulan : Al2 (SO4)3
𝑚𝑔
Dosis Al2 (SO4)3 = 20 𝐿
𝑔𝑟 𝑔𝑟
Kelarutan Al2 (SO4)3 = 0,404 = 404 (Perry 8th ed, Table 2-122, Page 2-
𝑐𝑚3 𝐿
126)
𝑔𝑟
Densitas Al2 (SO4)3 (ρ) = 1,62 𝑐𝑚3
𝑐𝑚3 𝑚3
= 203907,5938 ℎ𝑎𝑟𝑖 = 0,2039ℎ𝑎𝑟𝑖
𝑔𝑟
330330,302
ℎ𝑎𝑟𝑖
Kebutuhan air untuk melarutkan Al2 (SO4)3 = 𝑔𝑟
404
𝐿
𝐿 𝑚3
= 817,6493 ℎ𝑎𝑟𝑖 = 0,8176 ℎ𝑎𝑟𝑖
= 57,3526 m3
Asumsi : Liquida mengisi 80% dari volume tangki
𝑉𝑜𝑙𝑢𝑚𝑒 𝑙𝑖𝑞𝑢𝑖𝑑𝑎
Volume tangki = 80%
57,3526 𝑚3
= 80%
= 71,6908 m3
Asumsi : H = 2,5 D
1
Volume tangki = 4 x π x D2 x H
1
71,6908 m3 = 4 x π x D2 x 2,5 D
71,6908 m3 = 1,9635 D3
D = 3,3175 m
H = 8,2938 m
Sistem Pengaduk :
1
Diameter Impeller (Da) = 3 x Diameter tangki
1
= 3 x 3,3175 m
= 1,1058 m
Kecepatan Pengadukan (N) = 100 rpm = 1,6667 rps
𝑘𝑔
ρ air = 1000 𝑚3
𝑘𝑔
µ air = 0,8 cp = 0,0008 𝑚.𝑠
𝜌 𝑥 𝐷𝑎2 𝑥 𝑁
NRe = µ
= 80,7813 Hp
Tangki Koagulasi
Volume tangki : 71,6908 m3
Diameter tangki (D) : 3,3175 m
Tinggi tangki (H) : 8,2938 m
Tipe pengaduk : Turbin, 6 flat blades
Kecepatan pengadukan (N) : 100 rpm
Diameter Impeller (Da) : 1,1058 m
Effisieansi motor : 80%
Daya (P) : 80,7813 Hp
3. Tangki Flokulasi
𝑚3 𝐿
Rate volumetrik (Q2) : 16517,5366 = 16517536,6 ℎ𝑎𝑟𝑖
ℎ𝑎𝑟𝑖
𝑐𝑚3 𝑚3
= 68823,0692 ℎ𝑎𝑟𝑖 = 0,0688 ℎ𝑎𝑟𝑖
𝑔𝑟
82587,683
ℎ𝑎𝑟𝑖
Kebutuhan air untuk melarutkan PAC = 𝑔𝑟
300
𝐿
𝐿 𝑚3
= 275,2923 ℎ𝑎𝑟𝑖 = 0,2752 ℎ𝑎𝑟𝑖
Q total (Q3) = Q2 + Volume PAC + Pelarut flokulan
𝑚3 𝑚3 𝑚3
= 16517,5366 ℎ𝑎𝑟𝑖 + 0,0688 + 0,2752 ℎ𝑎𝑟𝑖
ℎ𝑎𝑟𝑖
𝑚3
= 16517,8806 ℎ𝑎𝑟𝑖
= 172,0668 m3
Asumsi : Liquida mengisi 80% dari volume tangki
𝑉𝑜𝑙𝑢𝑚𝑒 𝑙𝑖𝑞𝑢𝑖𝑑𝑎
Volume tangki = 80%
172,0668 𝑚3
= 80%
= 215,0835 m3
Asumsi : H = 2,5 D
1
Volume tangki = x π x D2 x H
4
1
215,0835 m3 = 4 x π x D2 x 2,5 D
215,0835 m3 = 1,9635 D3
D = 4,7847 m
H = 11,9618 m
Sistem Pengaduk :
1
Diameter Impeller (Da) = 3 x Diameter tangki
1
= 3 x 4,7847 m
= 1,5949 m
Kecepatan Pengadukan (N) = 30 rpm = 0,5 rps
𝑘𝑔
ρ air = 1000 𝑚3
𝑘𝑔
µ air = 0,8 cp = 0,0008 𝑚.𝑠
𝜌 𝑥 𝐷𝑎2 𝑥 𝑁
NRe = µ
= 13,6123 Hp
Tangki Flokulasi
Volume tangki : 215,0835 m3
Diameter tangki (D) : 4,7847 m
Tinggi tangki (H) : 11,9618 m
Tipe pengaduk : Turbin, 6 flat blades
Kecepatan pengadukan (N) : 30 rpm
Diameter Impeller (Da) : 1,5949 m
Effisieansi motor : 80%
Daya (P) : 13,6123 Hp
4. Clarifier
𝑚3 𝑚3
Rate volumetrik (Q3) : 16517,8806 ℎ𝑎𝑟𝑖 = 688,245 𝑗𝑎𝑚
= 412,947 m2
𝐴
Diameter clarifer (D) = √4 𝑥 𝜋
412,947
= √4 𝑥 𝜋
= 22,9299 m
r = 11,465 m
= 2,8662 m
Asumsi : s = 3,5 m
s/s’ = 4
3,5
s’ = = 0,875 m
4
= 1,7197 jam
= 1,8 , memenuhi standart yaitu 1,5 - 2,5jam
Volume air = Q3 x t
𝑚3
= 688,245 𝑗𝑎𝑚 x 1,8 jam
= 1238,841 m3
Volume clarifier = Volume air, agar terjadi overflow
Volume clarifier = 1238,841 m3
Spesifikasi Clarifier
𝑚3
Rate volumetrik (Q3) = 16517,8806 ℎ𝑎𝑟𝑖
= 68,8796 m3
Asumsi : Volume air mengisi 80% volume bak penampung flok
𝑉𝑜𝑙𝑢𝑚𝑒 𝑙𝑖𝑞𝑢𝑖𝑑𝑎
Volume bak penampung flok = 80%
68,8796
= 80%
= 86,0995 m3
Asumsi :
Panjang (P) =2L
Kedalaman (H) =L
Volume bak penampung flok = P x L x H
86,0995 m3 =2LxLxL
86,0995 m3 = 2 L3
L = 3,5047 m
P = 7,0094 m
H = 3,5047 m
= 700,193 m3
Asumsi : Volume air mengisi 80% volume bak penampung air bersih
𝑉𝑜𝑙𝑢𝑚𝑒 𝑙𝑖𝑞𝑢𝑖𝑑𝑎
Volume bak penampung air bersih = 80%
700,193
= 80%
= 875,2412 m3
Asumsi :
Panjang (P) =2L
Kedalaman (H) =L
Volume bak penampung flok = P x L x H
875,2412 m3 =2LxLxL
875,2412 m3 = 2 L3
L = 7,5922 m
P = 15,1844 m
H = 7,5922 m
7. Sand Filte
𝑚3
Rate volumetrik (Q5) : 14866,0925 ℎ𝑎𝑟𝑖
Laju alir (v) untuk rapid sand filter = 100 m3/m2 hari
𝑄5
Luas penampang (A) = 𝑣
14866,0925
= 100
= 148,6609 m2
𝐴
Diameter sand filter (D) = √4 𝑥 𝜋
148,6609
= √4 𝑥 𝜋
= 13,7579 m
r = 6,879 m
Total tinggi sand filter = Tinggi lapisan + Tinggi ruang kosong bagian atas
+ Tinggi ruang kosong bagian bawah
= 1,4 m + 0,5 m + 0,5 m
= 2,4 m
= 613,7169 m3
Asumsi : Volume air mengisi 80% volume bak penampung air bersih dari sand
filter
𝑉𝑜𝑙𝑢𝑚𝑒 𝑙𝑖𝑞𝑢𝑖𝑑𝑎
Volume bak penampung air = 80%
613,7169
= 80%
= 767,1461 m3
Asumsi :
Panjang (P) =2L
Kedalaman (H) =L
Volume bak penampung air = P x L x H
767,1461 m3 =2LxLxL
767,1461 m3 = 2 L3
L = 7,2658 m
P = 14,5316 m
H = 7,2658 m
= 2,2143 m3
Asumsi :
Panjang (P) =2L
Kedalaman (H) =L
Volume bak penampung air bersih =PxLxH
2,2143 m3 =2LxLxL
2,2143 m3 = 2 L3
L = 1,0345 m
P = 2,069 m
H = 1,0345 m
Spesifikasi Bak Penampung Air Bersih untuk Sanitasi :
𝑚3
Rate volumetrik (Q) : 42,4800 ℎ𝑎𝑟𝑖
= 62801,3663 ek/hari
Resin yang dipilih adalah jenis Dowex
Kapasitas = 2 ek/L resin (Perry 6ed ; T.16-4)
62801,3663
Resin yang diperlukan = 2
= 3532,5 m3
Asumsi : Resin mengisi 50% Volume tangki
Total kebutuhan resin
Volume tangki = 50%
3532,5
= 50%
= 7065 m3
Asumsi : H = 2 D
1
Volume tangki = 4 x π x D2 x H
1
7065 m3 = 4 x π x D2 x 2 D
7065 m3 = 1,5708 D3
D = 16,5068 m
H = 33,0136 m
= 41867,5775 ek
Resin yang dipilih adalah jenis Dowex
Kapasitas = 2 ek/L resin
41867,5775
Resin yang diperlukan = 2
= 2355,0525 m3
Asumsi : Resin mengisi 50% Volume tangki
Total kebutuhan resin
Volume tangki = 50%
2355,0525
= 50%
= 4710,105 m3
Asumsi : H = 2 D
1
Volume tangki = 4 x π x D2 x H
1
4710,105 m3 = 4 x π x D2 x 2 D
4710,105 m3 = 1,5708 D3
D = 14,4202 m
H = 28,8404 m
Reaksi anion exchange : R – OH- + H2SO4 → R – SO42- + H2O
= 611,9321 m3
Asumsi : Volume air mengisi 80% volume bak penampung air demineralisasi
𝑉𝑜𝑙𝑢𝑚𝑒 𝑙𝑖𝑞𝑢𝑖𝑑𝑎
Volume bak penampung air demineralisasi = 80%
611,9321
= 80%
= 764,9152 m3
Asumsi :
Panjang (P) =2L
Kedalaman (H) =L
Volume bak penampung air = P x L x H
764,9152 m3 =2LxLxL
764,9152 m3 = 2 L3
L = 7,2587 m
P = 14,5174 m
H = 7,2587 m
Spesifikasi Bak Penampung Air Demineralisasi :
𝑚3
Rate volumetrik (Q7) : 14674,6316 ℎ𝑎𝑟𝑖
= 11726,9582 m3/hari
= 2151,3435
2
= 1075,6718 ft2
Asumsi : P = 3L
Luas area pendinginan (A) =PxL
1075,6718 ft2 = 3L x L
L = 18,9356 ft
P = 56,8068 ft
= 78,9474%
Cooling capacity (TR) = Kebutuhan cooling water x cp x (T1 – T2)
𝑘𝑔 𝑘𝐶𝑎𝑙
= 11726958,2 x1 x (45 – 30) C
ℎ𝑎𝑟𝑖 𝑘𝑔.℃
𝑘𝐶𝑎𝑙 𝑘𝐶𝑎𝑙
= 175904373 ℎ𝑎𝑟𝑖 = 7329348,875 𝑗𝑎𝑚
= 3,738 m3/jam
Total air untuk make up water (Wm) = W e + Wb
= 11,2139 + 3,738
= 14,9519 m3/jam