TABEL BEBAN ELEKTRIKAL

BEBAN TERPASANG DALAM (Watt) DEMAND BEBAN MAXIMUM DALAM (Watt)


LANTAI NO NAMA PANEL KETERANGAN GENSET ON GENSET ON
PLN ON GENSET ON FIRE FAKTOR PLN ON NORMAL FIRE

P.LIFT

LANTAI ATAP
P.OU.VRF

PC.BOOSTER

P.HEAT PUMP

PP.A

JUMLAH 60.446 60.446 14.800 51.817 51.817 14.800

PP.7

LANTAI 7
FB.7.1 s/d FB.7.8
(8 UNIT)

PP.FASAD

JUMLAH 13.488 13.488 10.591 10.591

PP.6

LANTAI 6
FB.6.1 s/d FB.6.8
(8 UNIT)

JUMLAH 11.637 11.637 9.150 9.150

PP.5

LANTAI 5
FB.5.1 s/d FB.5.8
(8 UNIT)

JUMLAH 11.637 11.637 9.150 9.150

PP.4

LANTAI 4
FB.4.1 s/d FB.4.8
(8 UNIT)

JUMLAH 11.637 11.637 9.150 9.150

PP.3

LANTAI 3
FB.3.1 s/d FB.3.8
(8 UNIT)

JUMLAH 11.637 11.637 9.150 9.150

LANTAI 2
PP.2

FB.2.1 s/d FB.2.8


(8 UNIT)

JUMLAH 11.676 11.676 9.181 9.181

PP.1

LANTAI 1
P.AL

P.KITCHEN

P.LAUNDRY

JUMLAH 37.812 37.812 8.000 31.850 31.850 8.000

P.ABR

LANTAI BASEMENT
PC.IPAL

P.HYDRANT

JUMLAH 5.400 5.400 50.000 5.400 5.400 50.000

TOTAL kWatt 175,370 175,370 72,800 145,439 145,439 72,800


TOTAL kVA 219 219 91 182 182 91

BEBAN PLN MAXIMUM DIBAGI DEVERSITY FACTOR 1,2 151 kVA


SAMBUNGAN PLN 164 kVA
BEBAN TRAFO GANTUNG 160 kVA
BEBAN GENSET SILENT 100kVA