Anda di halaman 1dari 38

pemilihan penghantar dan pen

arus pengaman
no sdp keterangan r s t r s
1 sdp 1 lamp np 3.7465149856 3.491736 3.047521 4.308492 4.015496
2 sdp 1 lamp pr 7.7859108273 9.750354 7.785911 8.953797 11.21291
3 sdp 1 beban np 105.00022727 103.9548 103.9548 120.7503 119.548
4 sdp 1 beban pr 89.183639277 91.51631 89.65889 102.5612 105.2438
5 sdp 2 beban pr 564.92424242 564.9242 564.9242 649.6629 649.6629
6 sdp 2 beban np 564.92424242 564.9242 564.9242 649.6629 649.6629
7 sdp 3 beban pr 650.57359307 650.5736 650.5736 748.1596 748.1596
8 sdp 3 beban np 650.57359307 650.5736 650.5736 748.1596 748.1596
9 sdp 4 beban pr 205.79383117 205.7938 205.7938 236.6629 236.6629
10 sdp 4 beban np 254.21590909 254.2159 254.2159 292.3483 292.3483
11 sdp 5 beban pr 485.15151515 485.1515 485.1515 557.9242 557.9242
12 sdp 5 beban np 452.68398268 452.684 452.684 520.5866 520.5866

pemilihan penghantar MDP-SDP


faktor koreksi
no sdp arus total KHA A(suhu) B(penempaC
1 sdp 1 208.71317196 260.8915 0.73 0.94 0.74
2 sdp 2 1129.8484848 1412.311 0.73 0.94 0.74
3 sdp 3 1325.3195673 1656.649 0.73 0.94 0.74
4 sdp 4 460.00974026 575.0122 0.73 0.94 0.74
5 sdp 5 937.83549784 1172.294 0.73 0.94 0.74
6 spare 812.34529244 1015.432 0.73 0.94 0.74

pengaman MDP -SDP


arus nominal pengaman
no sdp r s t r s t
1 sdp 1 205.716292363 208.71317196 204.4471 236.5737 240.0201 235.1142
2 sdp 2 1129.848484848 1129.8484848 1129.848 1299.326 1299.326 1299.326
3 sdp 3 1301.147186147 1325.3195673 1129.848 1496.319 1524.118 1299.326
4 sdp 4 460.0097402597 460.00974026 460.0097 529.0112 529.0112 529.0112
5 sdp 5 937.8354978355 937.83549784 937.8355 1078.511 1078.511 1078.511
6 spare 806.9114402908 812.34529244 772.3979 927.9482 934.1971 888.2575
4034.557201454 4061.7264622 3861.989
TOTAL 2630.820051456

Berdasarkan ketentuan tersebet di atas, besar arus nominal


proteksi penghantar harus lebih besar dari arus desain dan lebih
kecil dari KHA penghantar.
Bila diambil faktor 115% dari arus nominal, maka arus pengenal
proteksi penghantar sebesar :

TRAFO YANG DIGUNAKAN RATING DIATAS 2630.82


pemilihan penghantar dan pengaman untuk sdp percabang
penghantar
t r s t pengaman yang digunakan arus pengenal(A)
3.504649 4.683144 4.3646694215 3.809401 mcb shneider 6&4
8.953797 9.732389 12.1879424572 9.732389 mcb shneider 16 & 10 A
119.548 131.2503 129.943465909 129.9435 mccb hitachi fxk125-5 125
103.1077 111.4795 114.395387165 112.0736 mccb hitachi fxk125-5 125
649.6629 706.1553 706.15530303 706.1553 mccb hitachi fx800(adjustable) 700
649.6629 706.1553 706.15530303 706.1553 mccb hitachi fx800(adjustable) 700
748.1596 813.217 813.216991342 813.217 mccb hitachi fx800(adjustable) 800
748.1596 813.217 813.216991342 813.217 mccb hitachi fx800(adjustable) 800
236.6629 257.2423 257.242288961 257.2423 mccb hitachi fx400(adjustable) 250
292.3483 317.7699 317.769886364 317.7699 mccb hitachi fx800(adjustable) 300
557.9242 606.4394 606.439393939 606.4394 mccb hitachi fx800(adjustable) 600
520.5866 565.855 565.854978355 565.855 mccb hitachi fx800(adjustable) 600

ar MDP-SDP

Arus kabel yang dipilih kha kabel jumlah kabel pembulatan


513.7803 NYY 1x25 mm 140 3.669859201 4
2781.3 NYY 1x150mm 445 6.2501116588 6
3262.482 NYY 1x150mm 445 7.3314213281 7
1132.386 NYY 1x150mm 445 2.5446883182 3
2308.63 NYY 1x150mm 445 5.1879315304 5
1999.716 NYY 1x150mm 445 4.4937430562 4

pengaman yang dipilih rating(A)


mccb hitachi fx400(adjustable) 250
ACB AKH 13D 1250
ACB F-1000C 1600
AKH-06D 630
ACB AKH-10D 1000
ACB AKH-10D 1000
KHA KABEL JUMLAH
kabel yang digunakan
1 X NYA 1X2.5MM
1X NYA 1X2.5MM
1X NYM 2X10MM
1X NYM 2X10MM nyy 1x120mm
445 2 2 x NYY 1x150mm nyy 1x150mm
445 2 2 x NYY 1x150mm NYY 1x35mm
445 2 2 x NYY 1x150mm NYY 1x95mm
445 2 2 x NYY 1x150mm
175 1 1 xNYY 1x35mm
175 2 2 x NYY 1x35mm
335 2 2 x NYY 1x95mm
335 2 2x NYY 1x95mm
UNTUK BEBAN LAMPU DAN BEBAN AC DLL KECUALI MOTOR M
mccb hitachi fX800 UNTUK MOTOR 250%
mccb hitachi fx400
mccb hitachi f-1005
EBAN AC DLL KECUALI MOTOR MENGGUNAKAN KHA 125%
mcb
dipilih fx1200 pada catalog tersebut karena untuk pengaman sendir
pada catalog tersebut lebih mudah untuk pengaturan a
t karena untuk pengaman sendiri dibutuhkan pengaman yang ratingnya diatas arus pengaman
lebih mudah untuk pengaturan arusnya karena dapat disesuaikan dengan beban
dipilih fx400 pada catalog tersebut karena untuk pengaman sendiri dibutuhkan pengaman yang ratingnya
pada catalog tersebut lebih mudah untuk pengaturan arusnya karena dapat disesuaikan deng
uhkan pengaman yang ratingnya diatas arus pengaman
a karena dapat disesuaikan dengan beban
dipilih f-1005 pada catalog tersebut karena untuk pengaman sendiri dibutuhkan pengaman yang ratingnya
pada catalog tersebut tersedia beberapa rating arus yang sesuai dengan beban
uhkan pengaman yang ratingnya diatas arus pengaman
rus yang sesuai dengan beban
0.74
penempatan penataan
0.94 0.74

Anda mungkin juga menyukai