OUTGOING FEEDER
PER PEMBANGKIT
NO MNEMO DESIGNATION
PER PERALATAN
INCOMING 20 KV
INCOMING 20 KV
TIPE INFORMASI
BUS COUPLER
BUS COUPLER
GARDU INDUK
GARDU INDUK
IED PROTEKSI
BUS SECTION
BUS SECTION
HARDWIRING
GEN TRANSF
GEN TRANSF
GENERATOR
GENERATOR
LN IEC61850
CAPACITOR
CAPACITOR
PER PHASA
LOCAL HMI
REACTOR
REACTOR
COMMON
PER BAY
BUSBAR
BUSBAR
IED BCU
IED AVR
PER GI
OPS HAR
PROTOKOL KOMUNIKASI
1 101 IEC 870-5-101 √ 1 1
2 104 IEC 870-5-104 √ 1 1
3 61850 IEC 61850 √ 1 1
4 DNP3 DNP3 √ 1 1
TOTAL 4 4
TAP CHANGER ( TC ) TC
5 TPI TPI TAP POSITION INDICATION TC √ √ √ 1 1 SPLN Spek SOGI, diperbaiki AVR agar menggunaka
TOTAL 1 1
TELE MEASUREMENT ( TM ) TM
6 F F FREKUENSI √ √ TM √ √ √ 1 1 1 1
7 V V TEGANGAN √ √ TM √ √ √ 1 1 1 1
8 I I ARUS √ √ TM √ √ √ 1 1 1 3 3 1 Untuk pemeliharaan, 3 titik berarti tiap phasa. Untuk operasi, 1 phFasa RST
9 P P DAYA AKTIF √ √ TM √ √ √ 1 1 1 1 1 1 Daya 3 fasa / (untuk Gen Trafo = ekspor dan impor)
10 Q Q DAYA REAKTIF √ √ TM √ √ √ 1 1 1 1 1 1 Daya 3 fasa / (untuk Gen Trafo = ekspor dan impor)
11 PF PF POWER FACTOR √ √ TM √ √ √ 1 1 1 1
12 REAL POWER SETTING TM √ √ √ √
13 MAX POWER VARIATION SETTING TM √ √ √ √
14 VAC TEGANGAN AC DB √ √ TM √ √ √ 3
15 VDC TEGANGAN DC RECTIFIER √ √ TM √ √ √ 4 Rectifier ada 2 tegangan dan redundant sehingga total 4 TAMBAHAN
16 PRES PRESSURE SF6 √ TM √ √ √ 1 1 1 1 1 1 TAMBAHAN (untuk GIS akan dihitung jumlahnya)
17 CCB COUNTER OF CIRCUIT BREAKER √ TM √ √ √ 1 1 1 1 1 1
18 COUNTER LIGHTNING ARRESTER TM √ √ √ TAMBAHAN
19 COLTC COUNTER OLTC OPERATION TM √ √ √ from AVR
20 KWH KILOWATT HOUR (EXPORT & IMPORT) √ TM √ √ √ 1 1 Dari satu buah IED Energy Meter dgn 2 address Export & ImpTAMBAHAN
21 KVARH KILOVAR HOUR (EXPORT & IMPORT) √ TM √ √ √ 1 1 Dari satu buah IED Energy Meter dgn 2 address Export & ImpTAMBAHAN
22 WTHV HV WINDING TEMPERATURE TM √ √ √ phase segregated
23 WTLV LV WINDING TEMPERATURE TM √ √ √ phase segregated
24 WTTV TV WINDING TEMPERATURE TM √ √ √
25 OT OIL TEMPERATURE TM √ √ √ phase segregated
26 RT ROOM TEMPERATURE √ TM √ √ √ 1 phase segregated
27 RH RELATIVE HUMIDITY √ TM √ √ √ 1
28 AMF AMF AMPERES FAULT ( PER PHASE ) √ √ TM √ √ √ 4 4 4 4 4 4 4 4 4 nilai (R S T N) di verifikasi untuk pengambilan datanya
29 DTF DISTANCE TO FAULT TM √ √ √ di verifikasi untuk pengambilan datanya
TOTAL 1 1 8 8 10 1 6 6 14 14 2 2 5
1 of 7
STANDARDISASI TELE INFORMASI DATA SOGI
GARDU INDUK SISI 20 KV
SUMBER OPERASI PEMELIHARAAN
TAMPILAN TIPE
SIGNAL
BAGIAN JUMLAH KETERANGAN KETERANGAN PEMBAHASAN
1 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10
OUTGOING FEEDER
PER PEMBANGKIT
NO MNEMO DESIGNATION
PER PERALATAN
INCOMING 20 KV
INCOMING 20 KV
TIPE INFORMASI
BUS COUPLER
BUS COUPLER
GARDU INDUK
GARDU INDUK
IED PROTEKSI
BUS SECTION
BUS SECTION
HARDWIRING
GEN TRANSF
GEN TRANSF
GENERATOR
GENERATOR
LN IEC61850
CAPACITOR
CAPACITOR
PER PHASA
LOCAL HMI
REACTOR
REACTOR
COMMON
PER BAY
BUSBAR
BUSBAR
IED BCU
IED AVR
PER GI
OPS HAR
REMOTE CONTROL DIGITAL ( RCD )
30 DCB DUMMY CIRCUIT BREAKER CLOSED/OPENED √ RCD √ √ √ 1
31 CB CB CIRCUIT BREAKER CLOSED/OPENED √ RCD √ √ √ 1 1 1 1 1 1 1 1 1 1 1 1 1 1
32 ARO ARO AUTO RECLOSE ON/OFF √ √ RCD √ √ √ 1 1 ON/OFF saja
33 BI BUS ISOLATOR SWITCH CLOSED/OPENED RCD √ √ √
34 DI DIAMETER ISOLATOR SWITCH CLOSED/OPENED RCD √ √ √
35 LI LINE ISOLATOR SWITCH CLOSED/OPENED RCD √ √ √
36 AVRAM AVRAM AVR AUTO/MANUAL RCD √ √ √ 1 1
37 TC TC TAP CHANGER RAISE/LOWER RCD √ √ √ 1 1
38 CHECK SYNCHRONIZING OVERRIDE RCD √ √ √
39 RPB RPB RESET PER BAY √ RCD √ √ √ 1 1 1 1 1 1 1 1 1 1 1 1 1 1
40 LOAD FREQ REQUEST ON/OFF RCD √ √ √
41 CAPACITOR AUTO/MANUAL √ RCD √ √ √ 1 1
TOTAL 2 2 3 2 2 3 1 2 1 2 2 3 2 2 3 1 2 1
OUTGOING FEEDER
PER PEMBANGKIT
NO MNEMO DESIGNATION
PER PERALATAN
INCOMING 20 KV
INCOMING 20 KV
TIPE INFORMASI
BUS COUPLER
BUS COUPLER
GARDU INDUK
GARDU INDUK
IED PROTEKSI
BUS SECTION
BUS SECTION
HARDWIRING
GEN TRANSF
GEN TRANSF
GENERATOR
GENERATOR
LN IEC61850
CAPACITOR
CAPACITOR
PER PHASA
LOCAL HMI
REACTOR
REACTOR
COMMON
PER BAY
BUSBAR
BUSBAR
IED BCU
IED AVR
PER GI
OPS HAR
87 COM COMMUNICATION FAULTY √ TSS 1
88 CF CARRIER FAULTY TSS √ √ √ 1
89 FOTF FO TERMINAL (PDH/SDH) FAULTY TSS √ √ √ 1
90 PLCF PLC TERMINAL FAULTY TSS √ √ √ 1
91 RADF RADIO LINK FAULTY TSS √ √ √ 1
92 PBXF PABX FAULTY TSS √ √ √ 1
3 of 7
STANDARDISASI TELE INFORMASI DATA SOGI
GARDU INDUK SISI 20 KV
SUMBER OPERASI PEMELIHARAAN
TAMPILAN TIPE
SIGNAL
BAGIAN JUMLAH KETERANGAN KETERANGAN PEMBAHASAN
1 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10
OUTGOING FEEDER
PER PEMBANGKIT
NO MNEMO DESIGNATION
PER PERALATAN
INCOMING 20 KV
INCOMING 20 KV
TIPE INFORMASI
BUS COUPLER
BUS COUPLER
GARDU INDUK
GARDU INDUK
IED PROTEKSI
BUS SECTION
BUS SECTION
HARDWIRING
GEN TRANSF
GEN TRANSF
GENERATOR
GENERATOR
LN IEC61850
CAPACITOR
CAPACITOR
PER PHASA
LOCAL HMI
REACTOR
REACTOR
COMMON
PER BAY
BUSBAR
BUSBAR
IED BCU
IED AVR
PER GI
OPS HAR
130 TEMPERATURE ALARM TSS √ √ √
131 HV WINDING TEMPERATURE ALARM TSS √ √ √ phase segregated
132 LV WINDING TEMPERATURE ALARM TSS √ √ √ phase segregated
133 TV WINDING TEMPERATURE ALARM TSS √ √ √ phase segregated
134 OIL TEMPERATURE ALARM TSS √ √ √ phase segregated
OUTGOING FEEDER
PER PEMBANGKIT
NO MNEMO DESIGNATION
PER PERALATAN
INCOMING 20 KV
INCOMING 20 KV
TIPE INFORMASI
BUS COUPLER
BUS COUPLER
GARDU INDUK
GARDU INDUK
IED PROTEKSI
BUS SECTION
BUS SECTION
HARDWIRING
GEN TRANSF
GEN TRANSF
GENERATOR
GENERATOR
LN IEC61850
CAPACITOR
CAPACITOR
PER PHASA
LOCAL HMI
REACTOR
REACTOR
COMMON
PER BAY
BUSBAR
BUSBAR
IED BCU
IED AVR
PER GI
OPS HAR
5 of 7
STANDARDISASI TELE INFORMASI DATA SOGI
GARDU INDUK SISI 20 KV
SUMBER OPERASI PEMELIHARAAN
TAMPILAN TIPE
SIGNAL
BAGIAN JUMLAH KETERANGAN KETERANGAN PEMBAHASAN
1 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10
OUTGOING FEEDER
PER PEMBANGKIT
NO MNEMO DESIGNATION
PER PERALATAN
INCOMING 20 KV
INCOMING 20 KV
TIPE INFORMASI
BUS COUPLER
BUS COUPLER
GARDU INDUK
GARDU INDUK
IED PROTEKSI
BUS SECTION
BUS SECTION
HARDWIRING
GEN TRANSF
GEN TRANSF
GENERATOR
GENERATOR
LN IEC61850
CAPACITOR
CAPACITOR
PER PHASA
LOCAL HMI
REACTOR
REACTOR
COMMON
PER BAY
BUSBAR
BUSBAR
IED BCU
IED AVR
PER GI
OPS HAR
197 TELEPROTECTION TRIP TRANSMIT TSS
198 DISTANCE RELAY TRANSMIT TSS √ √ √
199 DIRECTIONAL EARTH FAULT RELAY TRANSMIT TSS √ √ √
200 DIRECT TRANSFER TRIP TRANSMIT TSS √ √ √
6 of 7
STANDARDISASI TELE INFORMASI DATA SOGI
GARDU INDUK SISI 20 KV
SUMBER OPERASI PEMELIHARAAN
TAMPILAN TIPE
SIGNAL
BAGIAN JUMLAH KETERANGAN KETERANGAN PEMBAHASAN
1 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10
OUTGOING FEEDER
PER PEMBANGKIT
NO MNEMO DESIGNATION
PER PERALATAN
INCOMING 20 KV
INCOMING 20 KV
TIPE INFORMASI
BUS COUPLER
BUS COUPLER
GARDU INDUK
GARDU INDUK
IED PROTEKSI
BUS SECTION
BUS SECTION
HARDWIRING
GEN TRANSF
GEN TRANSF
GENERATOR
GENERATOR
LN IEC61850
CAPACITOR
CAPACITOR
PER PHASA
LOCAL HMI
REACTOR
REACTOR
COMMON
PER BAY
BUSBAR
BUSBAR
IED BCU
IED AVR
PER GI
OPS HAR
205 UNIT TRIP TSS √ √ √
206 GENERATOR TRANSFORMER TRIP TSS √ √ √
KETERANGAN :
Fungsi PEMELIHARAAN: adalah semua informasi yang dikirimkan oleh SOGI ke Control Center dan ditampilkan di lokal HMI.
Fungsi OPERASI: adalah semua informasi yang ditampilkan di Dispatcher Control Center, merupakan filter atau gruping yang dilakukan oleh Control Center dari fungsi PEMELIHARAAN.