(1). BILA TERDENGAR BUNYI (6). LAKUKAN PEMERIKSAAN KE (9). BILA BELL BERBUNYI, MULTITONE LOKASI YANG DIMAKSUD TERHADAP MENANDAKAN BAHWA GAS FM200 TERJADINYA INDIKASI KEBAKARAN. DISCHARGE KE DALAM RUANGAN YANG DIPROTEKSI.
(7). JIKA KONDISI DAPAT DIATASI
TANPA HARUS MENGELUARKAN GAS FM-200, TEKAN TOMBOL “RESET”
(2). KONDISI TELAH TERJADI ALARM,
SEGERA MENUJU PANEL KONTROL FM200 UNTUK MELIHAT LOKASI TERJADINYA ALARM PADA LCD
DISAAT YANG SAMA LAMPU GAS
DISCHARGE JUGA MENYALA
(8). SAAT TERJADI KONDISI “ALARM-
2” (CROSS ZONE) MAKA AKAN TERDENGAR BUNYI PUTUS-PUTUS PANJANG DARI MULTITONE.
PASTIKAN SEMUA PINTU TERTUTUP
SELAMA KURANG LEBIH 30 MENIT SEBELUM PERSONIL YANG BERKEPENTINGAN MASUK KEDALAM LOKASI KEBAKARAN UNTUK (3). TEKAN TOMBOL PADA PANEL KONTROL TERBACA MELAKUKAN PEMERIKSAAN “ACKNOWLEDGE” (BEBERAPA KALI TELAH TERJADI 2 ATAU LEBIH ALARM JIKA PERLU) UNTUK MEMATIKAN PADA RUANGAN YANG SAMA, SUARA BUZZER PADA PANEL PADAHAL PADA RUANGAN TERSEBUT KONTROL FM200 TIDAK TERLIHAT TANDA-TANDA TERJADINYA KEBAKARAN (FALSE ALARM), SEGERA TEKAN TOMBOL (10). JIKA TERJADI KEBAKARAN DI “ABORT” DAN TAHAN SEBELUM SALAH SATU RUANGAN YANG HITUNGAN DELAY COUNTER (30 DIPROTEKSI GAS FM200, NAMUN DETIK MENCAPAI 0), PENGAKTIFAN SMOKE DETECTOR TIDAK TOMBOL INI HARUS SESUAI DENGAN MENDETEKSI ADANYA ASAP, MAKA TEMPAT TERJADINYA ALARM. GAS FM200 DAPAT DIKELUARKAN SECARA MANUAL ELEKTRONIK DENGAN MENGAKTIFKAN TUAS “MANUAL PULL STATION”
(4). (SETELAH BUNYI BUZZER PADA
KONTROL PANEL PADAM) UNTUK MEMATIKAN SUARA MULTITONE, TEKAN TOMBOL “SILENCE”
TEKAN TOMBOL UNTUK “RESET”
UNTUK MENORMALKAN KONDISI ALARM (TOMBOL ABORT TETAP DITEKAN) HINGGA LED INDIKATOR ALARM PADA PANEL KONTROL PADAM
(5). IDENTIFIKASI DETEKTOR/ DEVICE
YANG MENAMPILKAN “ALARM” DENGAN MELIHAT PADA LCD PANEL KONTROL DAN LIHAT LOKASI DETECTOR PADA GAMBAR