STANDAR OPERASIONAL PROCEDURE

NOVEC-1230 FIRE SUPPRESSION SYSTEM

(1). BILA TERDENGAR BUNYI MULTITONE. (6). LAKUKAN PEMERIKSAAN KE LOKASI YANG (9). BILA BELL BERBUNYI, MENANDAKAN
DIMAKSUD TERHADAP TERJADINYA INDIKASI BAHWA GAS NOVEC-1230 DISCHARGE KE
KEBAKARAN. DALAM RUANGAN YANG DIPROTEKSI.

(7). JIKA KONDISI DAPAT DIATASI TANPA


HARUS MENGELUARKAN GAS NOVEC-1230,
TEKAN TOMBOL “RESET”.

(2). KONDISI TELAH TERJADI ALARM, SEGERA


MENUJU PANEL KONTROL NOVEC-1230
UNTUK MELIHAT LOKASI TERJADINYA ALARM
PADA LCD.

DISAAT YANG SAMA LAMPU GAS DISCHARGE


JUGA MENYALA.

(8). SAAT TERJADI KONDISI “ALARM-2”


(CROSS ZONE) MAKA AKAN TERDENGAR BUNYI
PUTUS-PUTUS PANJANG DARI MULTITONE.

PASTIKAN SEMUA PINTU TERTUTUP SELAMA


KURANG LEBIH 30 MENIT SEBELUM PERSONIL
YANG BERKEPENTINGAN MASUK KEDALAM
LOKASI KEBAKARAN UNTUK MELAKUKAN
PEMERIKSAAN.
(3). TEKAN TOMBOL “ACKNOWLEDGE” PADA PANEL KONTROL TERBACA TELAH
(BEBERAPA KALI JIKA PERLU) UNTUK TERJADI 2 ATAU LEBIH ALARM PADA
MEMATIKAN SUARA BUZZER PADA PANEL RUANGAN YANG SAMA, PADAHAL PADA
KONTROL NOVEC-1230. RUANGAN TERSEBUT TIDAK TERLIHAT
TANDA-TANDA TERJADINYA KEBAKARAN
(FALSE ALARM), SEGERA TEKAN TOMBOL (10). JIKA TERJADI KEBAKARAN DI SALAH
“ABORT” DAN TAHAN SEBELUM HITUNGAN SATU RUANGAN YANG DIPROTEKSI GAS
DELAY COUNTER (30 DETIK MENCAPAI 0), NOVEC-1230, NAMUN SMOKE DETECTOR
PENGAKTIFAN TOMBOL INI HARUS SESUAI TIDAK MENDETEKSI ADANYA ASAP, MAKA GAS
DENGAN TEMPAT TERJADINYA ALARM. NOVEC-1230 DAPAT DIKELUARKAN SECARA
MANUAL ELEKTRONIK DENGAN
MENGAKTIFKAN TUAS “MANUAL PULL
STATION”.

(4). (SETELAH BUNYI BUZZER PADA KONTROL


PANEL PADAM) UNTUK MEMATIKAN SUARA
MULTITONE, TEKAN TOMBOL “SILENCE”.

TEKAN TOMBOL UNTUK “RESET” UNTUK


MENORMALKAN KONDISI ALARM (TOMBOL
ABORT TETAP DITEKAN) HINGGA LED
INDIKATOR ALARM PADA PANEL KONTROL
PADAM.

(5). IDENTIFIKASI DETEKTOR/ DEVICE YANG


MENAMPILKAN “ALARM” DENGAN MELIHAT
PADA LCD PANEL KONTROL DAN LIHAT
LOKASI DETECTOR PADA GAMBAR.