Anda di halaman 1dari 14

PANDUAN CARA BACA ARUS GANGGUAN

BERBAGAI MACAM MERK RELAY PROTEKSI

Disusun Oleh :

TIM PROTEKSI

PT PLN (PERSERO) DISTRIBUSI JAKARTA RAYA


AREA PENGATUR DISTRIBUSI
2017
CARA BACA ARUS GANGGUAN RELAY MICOM P123
x.xxA x.xxA

x.xxA x.xxA

RECORDS OP PARAMETER CONFIGURATION

CB MONITORING FAULT RECORDS

RECORDS NUMBER

25

FAULT TIME

FAULT DATE

KETERANGAN

1. xxx = NILAI ARUS


FAULT
PHASEEARTH/PHA 2.Threshold = INDIKASI GGN

3. I> = OC

THRESHOLD 4. I>> = MOMENT OC

I>/I>>/Ie>/Ie>> 5. Ie = GF

6. Ie>> = MOMENT GF

7. Magnitude = ARUS GGN


IA/IB/IC/IN
MAGNITUDE X.XXX A

1
CARA BACA ARUS GANGGUAN RELAY GE MULTILIN 350

Klik
MENU

ACTUAL VALUES ……….. EVENT RECORD ……..


……….. ……….. …………. ……...
……….. …………. ……
RECORD sampai ketemu
………..
………
Phase TOC / IOC1 TRIP OP
GroundTOC/ IOC1 TRIP OP

Arus gangguan

Phase A Current …
Phase B Current …
Phasa C Current …
Ground Current …

KETERANGAN:

Phase TOC : OC

Phase IOC1 : MOC

Ground TOC : GF

Ground IOC1 : MGF

CARA BACA ARUS GANGGUAN RELAY SIEMENS 7SR11

2
na NAMA
FEEDER

SETTING MODE Test/


INSTRUMENT FAULT DATA
Reset MODE MODE

FAULT 1 DATE
TIME
( cek indikasi LED)

Tekan terus kebawah sampai


ketemu Arus gangguan

IA = …
IB = …
IC = …
In = ….

Indikasi LED settingan Relay Siemens

CARA BACA ARUS GANGGUAN RELAY VAMP 40

3
NAMA PENYULANG

IL1, IL2, IL3, IFIt

MEAS

EVNT COUNT 200 ………….

“pilih tanggal & jam


DR
yang sesuai di last trip”

TIMR Sampai Trip On


….. x pu

DI

CBWE CBWE/ CBWE/


CBWEAR CBWEAR LAST TRIP
STATUS IL1 : ………….. A
IL2 : …………. A
IL3 : ………….. A
Tanggal Trip……
Waktu Trip……..
UNTUK RESET TEKAN :

NB: untuk melihat Io ada di Event, cari tanggal & jam yang sesuai Last trip di CBWE sampai Trip On,
kemudian kalikan nilai …pu dengan Nominal CT

Contoh : 2.1 x pu, (CT 400) maka nilai Io = 2.1 x 400 = 840

4
CARA BACA ARUS GANGGUAN RELAY MICOM P142/141

Description
MICOM P142

SYSTEM DATA VIEW RECORD

SELECT EVENT

SELECT FAULT

SELECT FAULT
0

TRIP
Earth Fault IN1>2

Tanggal …
Jam …

Ia
Ib
Ic

In
“INDIKASI GANGGUAN”
Enter 2x (memilih biar select Faultnya 0)

Tekan ke bawah Sampai ketemu Trip

5
Tekan ke bawah Sampai ketemu besar arus gangguan

I >1 : OC I >2 : MOC I >3 : MOC

IN1 > 1 : GF IN1>2 : MGF

CARA BACA ARUS GANGGUAN RELAY THYTRONIC

THYTRONIC
OKJOOCJF
Date : 6/3/2017

Time : 14:00

6
MODULE

Tekan ke bawah 3x

READ Serial
Number

Tekan ke bawah 15x

Indikasi Gangguan
Fault Record Fault 0
I>, I>>, Ie>, Ie>>

Date

Time

IL1 : …. A

IL2 : …. A

IL3 : …. A

ILE : …. A

CARA BACA ARUS GANGGUAN RELAY ABB REF615

(Layar Kecil-Type B)

7
REF
IL1 ; IL2 ; IL3 ; Io

Klik
Buku
u
Event
………. 5x
Monitoring IED Status
…………… 6x
Record Data Fault Record 1 Time
………..………… IL1 = …. x In
IL2 = …. x In
IL3 = …. x In
Io = …. x In

NO LED SIMBOL INDIKASI


1 3I> OC
2 3I>> MOC
3 Io>-> GF
4 Io>> MGF

CARA RESET:

KLIK CLEAR

Indications & Leds : Tekan enter ( ), ke atas ( ), Enter ( ),

Alarm & Leds : Tekan enter ( ), ke atas ( ), Enter ( ),

KLIK BUKU 2x

CARA BACA ARUS GANGGUAN RELAY ABB REF615

(Layar Lebar-Type D)

8
REF

CARA RESET:

KLIK CLEAR

Indications & Leds : Tekan enter ( ), ke atas ( ), Enter ( ),

Alarm & Leds : Tekan enter ( ), ke atas ( ), Enter ( ),

KLIK BUKU 2x

CARA BACA ARUS GANGGUAN RELAY MC 30

9
MEAS .IB
*0 A

ENTE
R

MAIN MENU
MEAS

MAIN MENU
COUNTER

MAIN MENU ENTER LAST TRIP # 0 FUNC


ENTER
LAST TRIP REC # 0 I0 >

# 0 Date
02/01/01

# 0 hh : mm
00 : 20

# 0 SS : dd
35 : 57

KETERANGAN :

1. xxx = NILAI ARUS GGN PRIMER #0 IA


300 A
2. IA, IB, IC = PHASA R, S, T
3. I> = OC
4. I>> = MOMENT OC #0 IB
5. Io = GF 148 A
6. Io>> = MOMENT GF

10
Dst

CARA BACA ARUS GANGGUAN RELE SEPAM 1000+

Langkah – langkah yang harus dilakukan adalah sebagai berikut :

Tekan tombol yang berlambang

Maka akan muncul di display sebagai berikut :

Trip L1 = xxxx A
Trip L2 = xxxx A
Trip L3 = xxxx A
Trip Lo = xxxx A

Keterangan :

1. xxxx = angka arus gangguan

2. L1,L2,L3, = arus gangguan Phasa 3. Lo = arus gangguan

Ground Fault 4. Arus gangguan terbaca Primer.

11
CARA BACA ARUS GANGGUAN RELE MIF II

Ia : 0.0 , IB : 0.0 ENTER 1.08 10 : 28 : 45


IC : 0.0 , Ig : 0.0 ENTER
1 51P C 1.50
Trip 1

ENTER

23.07 00 : 24 : 23 Trip 2
2 51P B 2.40

ENTER

22.07 20 : 12 : 11
3 51P C 1.65 Trip 3

KETERANGAN :

1. xxx = NILAI ARUS GGN


2. Ia, Ib, Ic = PHASA R, S, T
3. 51P = OC
4. 50P1 = MOMENT OC 1
5. 50 P2 = MOMENT OC 2
6. 51 N = GF
7. 50 G1 = MOMENT GF 1
8. 50 G 2 = MOMENT GF 2
9. Reset = ESC / Reset ( tekan ± 10 detik )

CARA BACA ARUS GANGGUAN RELAY MICOM P543

(RELAY LINE CURRENT DIFFERENTIAL – ZDT)

12
50 A 50 A Enter 2x (memilih biar select Faultnya 0)
50 A 0A

SYSTEM DATA VIEW RECORD

SELECT EVENT

Tekan 25x ke bawah Sampai ketemu besar


SELECT FAULT
arus gangguan

CURRENT DIFF Tekan 2x ke bawah

TRIP INTERTRIP
Tekan 2x ke bawah

Tanggal …
Jam …
Tekan 2x ke bawah

IA fault
…. A Tekan 20x ke bawah

IB fault
…. A

IC fault
…. A

Selesai., untuk ke menu awal tekan tombol C terus.


IN fault
…. A

Untuk mereset Gangguan, tekan tombol


IA Diff no 10, di pojok
…. A

IB Diff
…. A

IC Diff
…. A
kanan bawah (Reset LED)
CP : RESTU
0857 4344 7451