Anda di halaman 1dari 53

FILOSOPHI PROTEKSI

TRANSMISI

- Simple - Inspiring - Performing - Phenomenal -


DIAGRAM SEDERHANA SISTEM PROTEKSI

Perintah buka PMT


Transmisi

Relai Proteksi Sinyal kirim Relai Proteksi


Masukan besaran Sinyal terima
arus dan tegangan

Catu Daya
(battere)

Disturbance Recorder
Data Scada
Evaluasi Gangguan
Indikasi relai
Simulasi S/W & H/W

Simple, Inspiring, Performing, Phenomenal 2


Distance Relay

 Relai penghantar yang prinsip kerjanya berdasarkan


pengukuran impedansi penghantar.
 Relai ini mempunyai beberapa karakteristik seperti
mho, quadralateral, reaktans, adaptive mho dll.
 Dapat digunakan sebagai cadangan jauh (remote
back up)
 Sebagai pengaman utama Zone 1 disetting 80 % dari
impedansi SUTET
 Relai ini mempunyai ketergantungan terhadap
besarnya SIR dan keterbatasan sensitivitas untuk
gangguan satu fasa ke tanah.
 Sebagai unit proteksi relai ini dilengkapi dengan pola
teleproteksi seperti putt, pott dan blocking.
 Jika tidak terdapat teleproteksi maka relai ini berupa
step distance saja (basic).

Simple, Inspiring, Performing, Phenomenal 3


PRINSIP KERJA

Zs ZL

Ir
Vs Vr Zbeba ZR = VR / IR
n
= ZL + Z
beban
Zs ZL

Ir
Vs Vr Zbeba ZR = VR / IR
n
= ZF

Jika setting rele sama dengan ZSet maka rele akan bekerja
jika ZF < ZSet
Simple, Inspiring, Performing, Phenomenal 4
5
Karakteristik Distance Relay

Gambar : Characteristics for the phase-to-phase measuring loops.

Simple, Inspiring, Performing, Phenomenal 6


Simple, Inspiring, Performing, Phenomenal 7
8
FIGURE : PHASE/PHASE FAULT QUADRILATERAL CHARACTERISTICS ( /PHASE SCHEME)

9
Karakteristik Distance Relay

Gambar : Characteristics for the phase-to-earth measuring loops,ohm/loop domain


Simple, Inspiring, Performing, Phenomenal 10
Simple, Inspiring, Performing, Phenomenal 11
Simple, Inspiring, Performing, Phenomenal 12
13
FIGURE : PHASE/GROUND FAULT QUADRILATERAL CHARACTERISTICS ( /PHASE SCHEME)

14
Local bus Near and bus far and bus

Zone-3(A) Zone-3(B)
Zone-2(A) Zone-2(B)
Zone-1(A) Zone-1(B)

A B C

Gambar : Jangkauan Setting Distance Relay 3 Zone

Simple, Inspiring, Performing, Phenomenal 15


Karakteristik Distance Relay

Gambar : Phase Fault Quadrilateral Characteristics

Simple, Inspiring, Performing, Phenomenal 16


Karakteristik Distance Relay

Gambar : Earth Fault Quadrilateral Characteristics

Simple, Inspiring, Performing, Phenomenal 17


Karakteristik Distance Relay

Gambar : Power Swing Detection Characteristics

Power swing adalah variasi aliran daya dimana relai jarak mendeteksi ada lokus
impedan yang bergerak dari daerah beban memasuki daerah kerja relai jarak.

Simple, Inspiring, Performing, Phenomenal 18


Cara Kerja Distance Relai (1)

Simple, Inspiring, Performing, Phenomenal 19


Cara Kerja Distance Relai (2)

Simple, Inspiring, Performing, Phenomenal 20


Setting Distance Relai
 Zone-1 80 % dari impedansi saluran, trip
instant
 Untuk gangguan Phase to phase
menggunakan kharakteristik Mho
 Untuk gangguan Phase to Ground
menggunakan karakteristik Quadrilateral
 Zone-2, trip dengan delay 0.4 detik
 Zone-3, trip dengan delay 1.6 detik

Simple, Inspiring, Performing, Phenomenal 21


Distance Relai di sistem 500 KV Jawa Bali

 Main (a) : PUTT (Permissive Underreach Transfer


Trip), Zone-1 kirim sinyal
 Main (b) : POTT (Permissive Overreach Transfer
Trip), Zone-2 start kirim sinyal
 DEF + REC signal/ Aided Signal : 100 ms (main)
 DEF : 2000 ms (back up)
 Reverse DEFDeaktif

Simple, Inspiring, Performing, Phenomenal 22


Teleproteksi
 Peralatan untuk kirim terima sinyal trip dari
Distance Relai/DEF ke GI diseberangnya
 Untuk Lp(a) menggunakan FO dan Lp(b)
menggunakan PLC
 Biasanya Terdiri dari 3 channel
 Distance
 DEF
 DTT (direct transfer trip)

Simple, Inspiring, Performing, Phenomenal 23


Pola/ Scheme Teleproteksi

Gambar : Logic Diagram for the Basic Scheme


Simple, Inspiring, Performing, Phenomenal 24
Pola/ Scheme Teleproteksi

Gambar : The PUP Z2 Permissive Underreach Scheme


Simple, Inspiring, Performing, Phenomenal 25
Pola/ Scheme Teleproteksi

Gambar : Logic Diagram for the POP Z2 Scheme


Simple, Inspiring, Performing, Phenomenal 26
Pola/ Scheme Teleproteksi

Gambar : Logic Diagram for the BOP Z2 Scheme


Simple, Inspiring, Performing, Phenomenal 27
Faktor-Faktor Yang Mempengaruhi
Pengukuran Distance Relay

1. Pengaruh Infeed Faktor dan Outfeed Faktor,


2. Pengaruh Tahanan Gangguan,
3. Mutual Impedansi,
4. SIR (Source to Line Impedance Ratio)

Simple, Inspiring, Performing, Phenomenal 28


1. Pengaruh Infeed Faktor dan Outfeed Faktor,

Infeed Faktor : Adanya pembangkit pada rel ujung saluran yang diamankan
A B
I1 I1 + I2

 Z1 f
ZBf

VAf I1.ZAB  ( I1  I 2).ZBf I2


ZAf  
I1 I1
( I1  I 2).ZBf 
ZAf  ZAB   ZAB  K .ZBf
I1

(I1  I 2)
Jadi faktor infeed K
I1

Simple, Inspiring, Performing, Phenomenal 29


Infeed Faktor : Saluran transmisi ganda ke tunggal

A B
I
2I

f
I

( I . ZAB  2 IZBf )
ZRA   ZAB  2 ZBf
I

Jadi faktor infeed K = 2

Simple, Inspiring, Performing, Phenomenal 30


Infeed Faktor : Saluran transmisi ganda ke ganda
A B C
I I1
f
 xx
f
l-x
I I

Jika terjadi gangguan pada titik f impedansi yang terlihat oleh relai A, adalah :
IZAB  I 1ZBf I1
ZRA   ZAB  ZBf
I I
(2l  x ) Jadi faktor infeed
I1  2I
2l
(2l  x )
(2l  x )
ZRA  ZAB  ZBf K
l l
• Untuk gangguan f dekat rel B (x  0) faktor infeed K = 2
• Untuk gangguan f dekat rel C (x  l) faktor infeed K = 1 dan
• Untuk gangguan diantar rel B dan rel C nilai infeed berfariasi antara 1 dan 2.

Simple, Inspiring, Performing, Phenomenal 31


Outfeed Faktor : Saluran transmisi tunggal ke ganda
A B C
I1


I f
xx f l
I

Impedansi saluran yang terlihat oleh relai A jika terjadi gangguan di f adalah :
IZAB  I 1ZBf I1
ZRA   ZAB  ZBf
I I Jadi faktor infeed
(2l  x )
I1  I
2l ( 2l  x )
(2l  x ) K
ZRA  ZAB  ZBf 2l
2l

• Untuk gangguan f dekat rel B (x  0) faktor infeed K = 1


• Untuk gangguan f dekat rel C (x  1) faktor infeed K = 0.5 dan
• Untuk gangguan diantar rel B dan rel C nilai infeed berfariasi antara 0.5 dan 1.
Simple, Inspiring, Performing, Phenomenal 32
2. Pengaruh Tahanan Gangguan,

Gambar : Resistive Reaches for Load Avoidance

Simple, Inspiring, Performing, Phenomenal 33


Blinder :

Ground fault distance comparator InPCT  800 CCC  540

3 Vn
Vn  70 10 ZL   n1 0.5 ZL  9.409 
CCC 3

Power factor sistem Pf  0.8

acos ( Pf )
L  L  36.87 faktor L  36 derajat
deg

AngleLoad  L AngleLoad  36

RLoad  ZL cos ( L  k) RLoad  7.612  ( Sekunder) pilih RLoad  7.6

dipilih : BFRS  7.6  BFRG  BFRS

110
PTS1 
BFLS = Linked with BFRS 3

Simple, Inspiring, Performing, Phenomenal 34


3. Mutual Impedansi

Effects of Mutual Coupling on Distance Settings


Where overhead lines are connected in parallel or run in close proximity for the
whole or part of their length, mutual coupling exists between the two circuits.
The positive and negative sequence coupling is small and can be neglected.
The zerosequence coupling is more significant and will affect relay measurement during
earth faults with parallel line operation.

Zero sequence mutual coupling will cause a distance relay to underreach or


overreach, depending on the direction of zero sequence current flow in the parallel line.
However, it can be shown that this underreach or overreach will not affect relay
discrimination during parallel line operation (ie. it is not be possible to overreach for
faults beyond the protected line and neither will it be possible to underreach to such a
degree that no zone 1 overlap exists).
A channel-aided scheme will therefore still respond to faults within the protected line and remain
secure during external faults. Some applications exist, however, where the effects of mutual
coupling should be addressed.

Simple, Inspiring, Performing, Phenomenal 35


Effect of Mutual Coupling on Zone 1 Setting

For the case shown in Figure 4, where one circuit of a parallel line is out of service
and earthed at both ends, an earth fault at the remote bus may result in incorrect
operation of the zone 1 earth fault elements.
It may be desireable/menguntungkan to reduce the zone 1 earth loop reach for this
application. This can be achieved / mencapai, meraih using an alternative setting group
within the relay, in which the residual compensation factor kZ1 is set at a lower value than
normal (typically ≤ 80% of normal kZ1).
Zapp = Va/Ia + In* KN KN = (Z0-Z1) / 3Z1

Simple, Inspiring, Performing, Phenomenal 36


Effect of Mutual Coupling on Zone 2 Setting

Boost = dorongan, kenaikan


Simple, Inspiring, Performing, Phenomenal 37
Effect of Mutual Coupling on Zone 2 Setting
If the double circuit line to be protected is long and there is a relatively short adjacent
line, it is difficult to set the reach of the zone 2 elements to cover 120% of the
protected line impedance for all faults, but not more than 50% of the adjacent line.
This problem can be exacerbated / memperburuk when a significant additional allowance has
to be made for the zero-sequence mutual impedance in the case of earth faults (see Section
2.4.6).
For parallel circuit operation the relay Zone 2 earth fault elements will tend to
underreach. Therefore, it is desirable to boost the setting of the earth fault elements
such that they will have a comparable reach to the phase fault elements.
Increasing the residual compensation factor kZ2 for zone 2 will ensure/ menjamin adequate/
cukup fault coverage.
Under single circuit operation, no mutual coupling exists, and the zone 2 earth fault
elements may overreach beyond 50% of the adjacent line, necessitating time
discrimination with other Zone 2 elements.
Therefore, it is desirable to reduce the earth fault settings to that of the phase fault elements for
single circuit operation, as shown in Figure 5. Changing between appropriate settings can be
achieved by using the alternative setting groups available in the relay series relays.
Simple, Inspiring, Performing, Phenomenal 38
4. SIR (Source to Line Impedance Ratio)

SIR adalah perbandingan impedansi sumber terhadap impedansi penghantar,


sehingga panjang penghantar menjadi salah satu faktor terhadap besaran SIR.
SIR menunjukan kekuatan sistem yang akan diproteksi, makin kecil SIR makin
kuat sumber yang memasok SUTT tersebut.

SIR menurut IEEE Std C17.113-1999 tentang Guide for Protective Relay
Applications to Transmission Lines, panjang penghantar dikelompokan menjadi :
- Penghantar Pendek dengan SIR > 4
- Penghantar Sedang dengan 0.5 < SIR < 4
- Penghantar Panjang dengan SIR < 0.5

Simple, Inspiring, Performing, Phenomenal 39


SIR (Source to Line Impedance Ratio)

B ZL
E
Z = n x ZL
Z = n x ZL
ZS ZL
n = 0- 1
E VB
Z
F
Letak Gangguan = Z/ZL

Zs = Impedansi sumber
ZL = Impedansi saluran yang diamankan
Z = Impedansi dari bus ke titik gangguan
V = Tegangan di bus
F = Letak gangguan
B = Lokasi relay
Tegangan Relay berfariasi tergantung Zs, dalam hal ini
dinyatakan dalam perbandingan Zs/ZL disebut SIR atau
tergantung lokasi gangguan (Zs/Z),

Simple, Inspiring, Performing, Phenomenal 40


Hubungan antara Zs, letak gangguan dan tegangan yang
dirasakan oleh relay adalah sebagai berikut :

Contoh pada hubung singkat 3 fasa,


VB = (Z1xE) / (Zs1 + Z1)
VB = ((Z1 / ZL1) x E) / (Zs1/ZL1) + (Z1 / ZL1)

Karena E dapat dianggap konstan, maka VB saat gangguan


harganya dipengaruhi oleh SIR dan letak gangguan (Z1 / ZL1)

Simple, Inspiring, Performing, Phenomenal 41


Directional Earth Fault (DEF)
 Digunakan untuk mendeteksi gangguan high resistance,
sebagai komplemen untuk Distance relai
 Pada distance yang masih elektrostatik biasanyamasih
berupa hardware yang terpisah, pada distance numerik
biasanya dalam hardware yang sama dengan distance.
 Jika relai sudah Phase segregated, maka reclose untuk
DEF diaktifkan.
 Untuk relai yang elektrostatik masih terpisah dengan
Distance Relai
 Setting 10 % In (main : 100 ms , back up 2000ms)

Simple, Inspiring, Performing, Phenomenal 42


KARAKTERISTIK RELAY DEF PADA SUATU PRODUK RELAY

Simple, Inspiring, Performing, Phenomenal 43


KARAKTERISTIK RELAI DEF
-(VB+VC)

Vreferensi =  0
IA sefase VA (Cos  = 1)
Arcing (R)
sefase VA OPERATING

VA AREA
IA langging 36 VA (Cos  = 0,8)

IA IA RCA (-60)

(-60)
BLOKING

AREA

VC VB

VB+VC

Gambar : Vektor DEF hubungan 0° dan - 60° RCA


Simple, Inspiring, Performing, Phenomenal 44
Distance Relay Terdapat Beberapa Fasilitas Seperti :
- Autoreclose,
- Synchro Check,
- SOTF,
- Power Swing,
- Out Of Step,

Simple, Inspiring, Performing, Phenomenal 45


Synchro Check Relay

 Minimum Voltage : 90 %Vn


 Voltage different : 10 % Vn
 Angle different : 15 degrees
 Slip frequency : 167 mHz
 Time delay : 500 ms

46
Auto Reclose

 Single Pole Auto Recloser  Dead Time : 900 ms


 Initiate from 1ph to ground fault only  Reclaime Time : 40 s
 Single shoot only  No Master and slaves
 Trigger from :
Z1, Z2+Aided and DEF+Aided
47
SOTF (Switch On To Fault)

 Pada saat pemasukan PMT system terjadi


gangguan
 Pada saat energizing Earthing Switch masih masuk
 Menggunakan fungsi non-directional overcurrent
 Elemen Distance belum siap karena tidak adanya
elemen voltage input.

48
Current Differential Relay

EndA End B

Relay A Relay B

Tanpa gangguan atau gangguan eksternal IA +IB = 0


Relai arus differensial Transmisi
Keadaan gangguan internal IA +IB ≠ 0 (= IF)

49
Contoh karakteristik current differensial relay

Gambar : Relay bias characteristic

50
The characteristic is determined by four protection settings:

Is1 is The basic differential current setting which determines


the minimum pick-up level of the relay.

k1 is The lower percentage bias setting used when the


bias current is below Ιs2. This provides stability for small
CT mismatches, whilst ensuring good sensitivity to
resistive faults under heavy load conditions.

51
Is2 is A bias current threshold setting, above which the
higher percentage bias k2 is used.

k2 is The higher percentage bias setting used to improve


relay stability under heavy through fault current conditions.

The tripping criteria can be formulated as:


a. for |Ibias| < Is2, |Idiff| > k1.| Ibias| + Is1
b. for |Ibias| > Is2, |Idiff| > k2.| Ibias| - (k2 - k1). Is2 + Is1

52
THANK FOR YOUR ATTENTION

- Simple - Inspiring - Performing - Phenomenal - 53

Anda mungkin juga menyukai