SECARA TERUS – MENERUS DENGAN ALIRAN KECIL UNTUK EVAPORATOR DAN CONDENSER YANG OFF. DICATAT SETIAP PAGI (PUKUL 07:00 WIB) UNTUK KUBIKASINYA. COOLING TOWER LAKUKAN BLOWDOWN PADA SAAT LIQUID TEMPERATURE MENCAPAI SUHU 31C. BLOWDOWN DIHENTIKAN APABILA LIQUID TEMPERATURE 29C DAN PANTAU NILAI TDS. SAAT PENGECEKAN TDS DI ATAS 80 PPM, LAKUKAN BLOWDOWN. RENTANG pH COOLING TOWER ADALAH 7-8. SISTEM RO SISTEM RO MATI PADA 3 POSISI LEVEL 150 M DAN 3 PADA POSISI LEVEL 120 M SISTEM RO JALAN LAGI. GROUNDTANK POSISI LEVEL 120 M3 PDAM HARUS DIBUKA SAMPAI POSISI LEVEL 150 M3 HARUS DIMATIKAN.
CATATAN : USAHAKAN PEMBUKAAN PDAM 1 X
SEHARI. APABILA GROUNDTANK DAN MAKE UP RO TIDAK MENGCOVER, HARUS DIBACKUP DENGAN AIR PDAM. TIDAK DIIJINKAN MENGGUNAKAN FILTER SOFTENER / AIR SUMUR LANGSUNG. LAKUKAN LOG SHEET SESUAI JAM YANG SUDAH TERCANTUM PADA BUKU LOG SHEET. LAKUKAN PENGISIAN KUBIKASI DENGAN BENAR.