LAPORAN

SONDIR TEST
PERENCANAAN GEDUNG DINAS KERASIPAN
DAN PERPUSTAKAAN KOTA BANJAR
Jl. Ciamis -Banjar No.120, Purwaharja,
KOTA BANJAR

2020
Laporan Sondir Test

I DAFTAR ISI
DAFTAR ISI ......................................................................................................................................... I
KATA PENGANTAR .......................................................................................................................... II
BAB I .................................................................................................................................................... 1
PENDAHULUAN ................................................................................................................................. 1
1.1. MAKSUD DAN TUJUAN PENYELIDIKAN ............................................................................... 1
1.2. LINGKUP PEKERJAAN ............................................................................................................... 1
1.2.1 Pekerjaan Sondir .................................................................................................................. 1
1.2.2 Tata Cara Pekerjaan Sondir .................................................................................................. 2

1.3. METODA PENYELIDIKAN ......................................................................................................... 2


1.3.1 Perlatan ................................................................................................................................ 2
1.3.2 Cara kerja ............................................................................................................................. 3

BAB II ................................................................................................................................................... 4
DESKRIPSI LOKASI PROYEK .......................................................................................................... 4
2.1. LOKASI DAN PENCAPAIAN SITE ............................................................................................ 4
2.2. GEOMORFOLOGI ........................................................................................................................ 4
2.3. GEOLOGI REGIONAL ............................................................................................................... 4
2.4. PERCEPATAN GEMPA .............................................................................................................. 5
BAB III ................................................................................................................................................. 7
HASIL UJI SONDIR............................................................................................................................. 7
3.1. HASIL PENGUJIAN ..................................................................................................................... 7
BAB IV ............................................................................................................................................... 17
KESIMPULAN DAN SARAN ........................................................................................................... 17
4.1. KESIMPULAN ............................................................................................................................ 17
4.2. SARAN....................................................................................................................................... 17
DAFTAR PUSTAKA.......................................................................................................................... 18
DOKUMENTASI................................................................................................................................ 19

i
CV. AULIA SURVEY KONSULTINDO
Laporan Sondir Test

KATA PENGANTAR

Dalam rangka menunjang pekerjaan Perencanaan Pembangunan Gedung Dinas


Kerasipan dan Perpustakaan Kota Banjar maka perlu dilakukan pengujian sondir, Sehubungan
dengan pekerjaan tersebut telah dilaksanakan penyelidikan sondir untuk Perencanaan
Pembangunan Gedung Dinas Kerasipan dan Perpustakaan Kota Banjar yang berlokasi di Jl.
Ciamis-Banjar No.120, Purwaharja Kota Banjar.
Pekerjaan Soil Test ini meliputi pekerjaan lapangan yang terdiri dari uji sondir sebanyak
3 titik, serta pelaporan.
Hasil pekerjaan tersebut diatas ditambah dengan data studi terdahulu dan analisa serta
perhitungan-perhitungan, disusun dan dituangkan dalam bentuk laporan akhir ini.
Kami mengharapkan agar laporan ini berguna untuk bahan penunjang perencanaan
teknik dan kepada semua pihak yang telah membantu pekerjaan ini, kami ucapkan terima kasih.

Tasikmalaya, 28 Oktober 2020

Dibuat oleh,

Syara Hanjaya, ST

ii
CV. AULIA SURVEY KONSULTINDO
Laporan Sondir Test

BAB I
PENDAHULUAN

1.1. Maksud dan Tujuan Penyelidikan


Maksud dari penyelidikan uji sondir ini adalah untuk mengetahui kekuatan tanah
tiap kedalaman dan stratifikasi tanah secara pendekatan.
Tujuan penyelidikan ialah untuk mengetahui perlawanan penetrasi konus dan
perlawanan geser tanah. Serta untuk mengetahui kedalaman lapisan tanah keras dan
sifat daya dukung maupun daya lekat setiap kedalaman.
Perlawanan penetrasi konus adalah perlawanan tanah terhadap ujung konus
(perlawanan dari bawah) dengan satuan gaya persatuan luas. Perlawanan geser tanah
adalah perlawanan geser tanah terhadap selubung bikonus (perlawanan dari samping)
dengan satuan gaya persatuan panjang.
1.2. Lingkup Pekerjaan
Menurut spesifikasi yang telah ditentukan oleh Pemberi Tugas, penyelidikan
geoteknik / mekanika tanah yang telah dilakukan di lokasi penyelidikan adalah sebagai
berikut:

1.2.1 Pekerjaan Sondir


Uji sondir saat ini merupakan salah satu uji lapangan yang telah diterima oleh
para praktisi dan pakar geoteknik. Uji sondir ini telah menunjukkan manfaat untuk
pendugaan profil atau pelapisan (stratifikasi) tanah terhadap kedalaman karena jenis
perilaku tanah telah dapat diindentifikasi dari kombinasi hasil pembacaan tahanan
ujung dan gesekan selimutnya.
Besaran penting yg diukur pada uji sondir adalah perlawanan ujung yg
diambil sebagai gaya penetrasi per satuan luas penampang ujung sondir (qc).
Besarnya gaya ini seringkali menunjukkan identifikasi dari jenis tanah dan
konsistensinya. Pada tanah pasiran, tahanan ujung jauh lebih besar daripada tanah
butiran halus.
Apa hubungan kuat dukung tanah dengan data sondir (qc). Anda dapat
melihat hubungan nilai tahanan konus (qc) terhadap konsistensi tanah, sebagai
berikut ini. Untuk tanah yang sangat lunak nilai qc < 5 kg/cm2, lunak 5-10 kg/cm2,

1
CV. AULIA SURVEY KONSULTINDO
Laporan Sondir Test

teguh 10-20 kg/cm2, kenyal 20-40 kg/cm2, sangat kenyal 40-80 kg/cm2, keras 80-
150 kg/cm2, dan sangat keras > 150 kg/cm2.

1.2.2 Tata Cara Pekerjaan Sondir


Dilakukan untuk mengetahui nilai index properties dan engineering
properties yang akan dipakai untuk kalkulasi dalam perencanaan detail. Prosedur
pekerjaan laboratorium disesuaikan dengan Standar Pekerjaan Umum dengan
menggunakan 1 set perlengkapan ASTM.
1.3. Metoda Penyelidikan

1.3.1 Perlatan
a. Mesin sondir dengan kapasitas 2,5 ton

Gambar 1.1 Peralatan Sondir Test

b. Seperangkat pipa sondir lengkap dengan batang dalam sesuai dengan kebutuhan,
denagan panjang masing-masing 1m.
c. Manometer 2 buah dengan masing-masing : 0-60 kg/cm2 dan 0-250 kg/cm2.
d. Bikonis (beugemen priction jacket gone ).
e. 4 buah jangkar berbentuk spiral dan alat pemutar .
f. kunci-kunci pipa, alat pembersih, Castrol oil, unting- unting, kepala babi.
g. 2 buah baja kanal ukuran 3m, 2 buah baja kanal ukuran 1m serta alat pengunci.

2
CV. AULIA SURVEY KONSULTINDO
Laporan Sondir Test

Gambar 1.2 Gambar Biconus

1.3.2 Cara kerja


a. Jangkar ditanam kedalam tanah dengan menggunakan alat pemutarnya.
b. Mesin sondir dipasang dan diatur secara vertical ditempat yng akan diperiksa
dengan menggunakan baja kanal, ditahan pada tanah dengan jangkar tersebut
diatas.
c. Bikonus dipasang pada ujung bawah pipa yang pertama dan manometer
dipasang pada mesin sondir.
d. Mesin diisi dengan minyak hidrolik dan pengisiannya harus bebas gelembung
udara sebelum manometer dipasang.
e. Setelah semua siap, pipa ditekan beserta batang didalamhya untuk
memasukkan bikonis sedalam 20 cm ke dalam tanah .
f. Pada saat siap membaca, tungkai yang berada dekat dengan manometer,
didekat ujung atas pipa paling atas diubah posisinya . sehingga penekanan
hanya akan menekan batang didalam pipa sondir, yang hanya akan
menggerakkan ujung konus dan selimut gesernya. pembacaaan dilakukan 2kali
setelah pembacaan pertama yaitu pambacaan kedua setelah kita-kira 4cm pipa
tersebut masuk lagi kedalam tanah setelah pembacaan pertama.
g. Pada pembacaan pertama hanya ujung konus yang tertekan dalam tanah,
sehingga bacaan pertama adalah = tekanan konus. pada pembacaan kedua ujung
konus dan selimut geser yang tertekan, sehingga bacaan ke-2 adalah tahanan
konus ditambah tahanan geser.

3
CV. AULIA SURVEY KONSULTINDO
Laporan Sondir Test

BAB II
DESKRIPSI LOKASI PROYEK

2.1. Lokasi dan Pencapaian Site


Secara administratif lokasi proyek berada di Gedung Dinas Kerasipan dan Perpustakaan
Kota Banjar yang berlokasi di Jl. Ciamis-Banjar No.120, Purwaharja Kota Banjar.

Gambar 2.1. Peta Lokasi Penyelidikan sondir

2.2. Geomorfologi
Lokasi proyek dan sekitarnya pada umumnya merupakan morfologi tanah datar.
Penggunaan lahan berupa komplek perkantoran.

2.3. Geologi Regional


Berdasarkan Peta Formasi Geologi lokasi Penyelidikan di daerah Kerasipan dan
Perpustakaan Kota Banjar (Gambar 2.2), termasuk kedalam formasi Hasil Gunung Api
Tua (QTv). Formasi ini terdiri dari breksi gunung api, breksi aliran, tufa dan lava bersusun
andesit sampai basal dari Gunung Sawal (QTvs).

4
CV. AULIA SURVEY KONSULTINDO
Laporan Sondir Test

Gambar 2.2. Peta Geologi Regional Kota Banjar

2.4. Percepatan Gempa


Berdasarkan peta zona kegempaan untuk desain bangunan yang diterbitkan oleh
Puskim PU, Kementrian Pekerjaan Umum dan Perumahan Rakyat, maka rencana lokasi
proyek terletak pada zona kegempaan dengan koefisien zona = 1,00.
Jika pondasi bangunan diletakan pada batuan dengan anggapan periode ulang 50
tahun, maka percepatan gempa perencanaan harus di hitung dari data di bawah ini.

Tabel 2.1 Spektrum Gempa untuk tanah sedang


PGA = 0.425553 g
PGAm = 0.499789 g
CRs = 0.000000
CR1 = 0.000000
Ss = 0.923444 g
S1 = 0.422161 g
TL = 20.000000 detik
Fa = 1.130622
Fv = 1.877839
Sms = 1.044066 g

5
CV. AULIA SURVEY KONSULTINDO
Laporan Sondir Test

Sm1 = 0.792750 g
Sds = 0.696044 g
Sd1 = 0.528500 g
T0 = 0.151858 detik
Ts = 0.759291 detik

Sumber: Peta Gempa dan Respons Spektra 2019, © ERSC-PUSGEN-PUSKIM


PUPR,2019-2020

Gambar 2.3. Nilai Spektral Percepatan Di Permukaan Dari Gempa Risk-Targeted Maximum
Consider Earthquake Dengan Probabilitas Keruntuhan Bangunan 1% dalam 50 Tahun.

Gambar 2.4. Peta Zona Gempa Indonesia


6
CV. AULIA SURVEY KONSULTINDO
Laporan Sondir Test

BAB III
HASIL UJI SONDIR

3.1. Hasil Pengujian


Penyelidikan lapangan yang dilakukan adalah penyelidikan sondir yang
dilaksanakan pada lokasi pekerjaan dengan pengujian 3 titik pengujian.
Evaluasi kondisi lapisan tanah di lokasi yang dilakukan berdasarkan data hasil uji
sondir dengan mempelajari kurva gabungan nilai qc dan kedalamannya didapatkan adanya
beberapa kondisi dan jenis lapisan-lapisan tanah. Dalam análisis ini lapisan tanah dibagi
menjadi beberapa lapisan dimana masing-masing lapisan memiliki batasan nilai qc yang
tertentu.
Berdasarkan data hasil uji sondir selanjutnya dapat diperkirakan karakteristik lapisan
tanah yang ada di lokasi pengujian. Lapisan tanah tersebut dapat dikelompokkan
berdasarkan nilai rata-rata qc-nya yaitu :
5 – 10 kg/cm2 merupakan representasi dari tanah lunak (soft)
10 – 20 kg/cm2 merupakan representasi dari tanah Teguh
20 – 40 kg/cm2 merupakan representasi dari tanah kenyal
40 – 80 kg/cm2 merupakan representasi dari tanah sangat kenyal
80 – 150 kg/cm2 merupakan representasi dari tanah keras
> 150 kg/cm2 merupakan representasi dari tanah sangat keras

Gambar 3.1. Lokasi Titik Pengujian

7
CV. AULIA SURVEY KONSULTINDO
Laporan Sondir Test

SONDIR TEST

Project : Perencanaan Gedung Perpustakaan dan Data : 25 Oktober 2020 Project


Kearsipan Kota Banjar
Location : Jl. Ciamis -Banjar No.120, Purwaharja, Tested By : Indra Faisal, ST Location
Kota Banjar, Jawa Barat 46331
Koordinat : E: 228298.580 Checked By : Syara Hanjaya, ST Koordinat
: N: 9185717.122
Depth 13.4 m Depth
Sondir No. :S-1 Sondir No.

Depth Cw Tw Kw qc LF 20 cm. LF TF Ratio


( m) (kg/cm2 ) (kg/cm2 ) (kg/cm2 ) (kg/cm2 ) (kg/cm) (kg/cm) (kg/cm) 100 x LF/qc
0.0 0 0 0 0 0.00 0.0 0.0 0.00
0.2 5 8 3 5 0.20 4.0 4.0 4.02
0.4 5 10 5 5 0.33 6.7 10.7 6.69
0.6 10 20 10 10 0.67 13.4 24.1 6.69
0.8 40 60 20 40 1.34 26.8 50.9 3.35
1.0 30 90 60 30 4.02 80.3 131.2 13.38
1.2 18 27 9 18 0.60 12.0 143.2 3.35
1.4 16 24 8 16 0.54 10.7 153.9 3.35
1.6 30 32 2 30 0.13 2.7 156.6 0.45
1.8 34 38 4 34 0.27 5.4 161.9 0.79
2.0 34 40 6 34 0.40 8.0 170.0 1.18
2.2 36 42 6 36 0.40 8.0 178.0 1.12
2.4 32 42 10 32 0.67 13.4 191.4 2.09
2.6 28 40 12 28 0.80 16.1 207.4 2.87
2.8 30 38 8 30 0.54 10.7 218.2 1.78
3.0 100 110 10 100 0.67 13.4 231.5 0.67
3.2 30 50 20 30 1.34 26.8 258.3 4.46
3.4 10 20 10 10 0.67 13.4 271.7 6.69
3.6 20 30 10 20 0.67 13.4 285.1 3.35
3.8 10 20 10 10 0.67 13.4 298.5 6.69
4.0 10 20 10 10 0.67 13.4 311.8 6.69
4.2 50 70 20 50 1.34 26.8 338.6 2.68
4.4 50 70 20 50 1.34 26.8 365.4 2.68
4.6 20 30 10 20 0.67 13.4 378.8 3.35
4.8 40 50 10 40 0.67 13.4 392.1 1.67
5.0 60 80 20 60 1.34 26.8 418.9 2.23
5.2 40 50 10 40 0.67 13.4 432.3 1.67
5.4 40 50 10 40 0.67 13.4 445.7 1.67
5.6 40 50 10 40 0.67 13.4 459.1 1.67
5.8 20 40 20 20 1.34 26.8 485.8 6.69
6.0 20 50 30 20 2.01 40.2 526.0 10.04
6.2 15 25 10 15 0.67 13.4 539.4 4.46
6.4 60 80 20 60 1.34 26.8 566.1 2.23
6.6 40 60 20 40 1.34 26.8 592.9 3.35
6.8 10 30 20 10 1.34 26.8 619.7 13.38
7.0 30 40 10 30 0.67 13.4 633.0 2.23
7.2 30 50 20 30 1.34 26.8 659.8 4.46
7.4 30 40 10 30 0.67 13.4 673.2 2.23
7.6 10 20 10 10 0.67 13.4 686.6 6.69
7.8 40 50 10 40 0.67 13.4 700.0 1.67
8.0 15 25 10 15 0.67 13.4 713.3 4.46
8.2 15 20 5 15 0.33 6.7 720.0 2.23
8.4 10 20 10 10 0.67 13.4 733.4 6.69 8
CV. AULIA SURVEY KONSULTINDO
Laporan Sondir Test

8.6 15 25 10 15 0.67 13.4 746.8 4.46


8.8 40 50 10 40 0.67 13.4 760.2 1.67
9.0 20 50 30 20 2.01 40.2 800.3 10.04
9.2 20 40 20 20 1.34 26.8 827.1 6.69
9.4 20 40 20 20 1.34 26.8 853.9 6.69
9.6 20 40 20 20 1.34 26.8 880.6 6.69
9.8 20 40 20 20 1.34 26.8 907.4 6.69
10.0 20 40 20 20 1.34 26.8 934.2 6.69
10.2 10 30 20 10 1.34 26.8 960.9 13.38
10.4 10 30 20 10 1.34 26.8 987.7 13.38
10.6 50 90 40 50 2.68 53.5 1041.2 5.35
10.8 40 60 20 40 1.34 26.8 1068.0 3.35
11.0 30 70 40 30 2.68 53.5 1121.5 8.92
11.2 40 100 60 40 4.02 80.3 1201.8 10.04
11.4 40 70 30 40 2.01 40.2 1242.0 5.02
11.6 40 60 20 40 1.34 26.8 1268.8 3.35
11.8 40 60 20 40 1.34 26.8 1295.5 3.35
12.0 40 60 20 40 1.34 26.8 1322.3 3.35
12.2 10 50 40 10 2.68 53.5 1375.8 26.77
12.4 40 60 20 40 1.34 26.8 1402.6 3.35
12.6 60 90 30 60 2.01 40.2 1442.7 3.35
12.8 100 180 80 100 5.35 107.1 1549.8 5.35
13.0 50 100 50 50 3.35 66.9 1616.7 6.69
13.2 100 160 60 100 4.02 80.3 1697.0 4.02
13.4 250 300 50 250 3.35 66.9 1763.9 1.34

9
CV. AULIA SURVEY KONSULTINDO
Laporan Sondir Test

SONDIR TEST

Project : Perencanaan Gedung Perpustakaan Data : 25 Oktober 2020


dan Kearsipan Kota Banjar
Location : Jl. Ciamis -Banjar No.120, Purwaharja, Tested By : Indra Faisal, ST
Kota Banjar, Jawa Barat 46331
Koordinat : E: 228298.580 Checked By : Syara Hanjaya, ST
: N: 9185717.122
Depth 13.4 m
Sondir No. :S-1

Cone Penetration (km/cm2) RATIO


0 50 100 150 200 0 4 8 12 16 20 24 28
0 0

1 1

2 2

3 3

4
4

5
5

6
6

7
Kadalaman (m)

8 ```
8

9
9

10
10
11

11
12

12
13

13
14

14
15

15
0.0 1.0 2.0 3.0 4.0
Local Friction (kg/cm)

10
CV. AULIA SURVEY KONSULTINDO
Laporan Sondir Test

SONDIR TEST

Project : Perencanaan Gedung Perpustakaan dan Data : 25 Oktober 2020 Project


Kearsipan Kota Banjar
Location : Jl. Ciamis -Banjar No.120, Purwaharja, Tested By : Indra Faisal, ST Location
Kota Banjar, Jawa Barat 46331
Koordinat : E: 228312.000 Checked By : Syara Hanjaya, ST Koordinat
: N: 9185730.000
Depth 16.0 m Depth
Sondir No. :S-2 Sondir No.

Depth Cw Tw Kw qc LF 20 cm. LF TF Ratio


( m) (kg/cm2 ) (kg/cm2 ) (kg/cm2 ) (kg/cm2 ) (kg/cm) (kg/cm) (kg/cm) 100 x LF/qc
0.0 0 0 0 0 0.00 0.0 0.0 0.00
0.2 5 8 3 5 0.20 4.0 4.0 4.02
0.4 5 10 5 5 0.33 6.7 10.7 6.69
0.6 12 22 10 12 0.67 13.4 24.1 5.58
0.8 18 26 8 18 0.54 10.7 34.8 2.97
1.0 18 26 8 18 0.54 10.7 45.5 2.97
1.2 19 23 4 19 0.27 5.4 50.9 1.41
1.4 24 40 16 24 1.07 21.4 72.3 4.46
1.6 28 30 2 28 0.13 2.7 74.9 0.48
1.8 22 30 8 22 0.54 10.7 85.7 2.43
2.0 70 90 20 70 1.34 26.8 112.4 1.91
2.2 20 40 20 20 1.34 26.8 139.2 6.69
2.4 20 40 20 20 1.34 26.8 166.0 6.69
2.6 15 25 10 15 0.67 13.4 179.3 4.46
2.8 20 30 10 20 0.67 13.4 192.7 3.35
3.0 15 25 10 15 0.67 13.4 206.1 4.46
3.2 15 20 5 15 0.33 6.7 212.8 2.23
3.4 15 20 5 15 0.33 6.7 219.5 2.23
3.6 10 20 10 10 0.67 13.4 232.9 6.69
3.8 15 25 10 15 0.67 13.4 246.3 4.46
4.0 20 60 40 20 2.68 53.5 299.8 13.38
4.2 30 50 20 30 1.34 26.8 326.6 4.46
4.4 10 50 40 10 2.68 53.5 380.1 26.77
4.6 15 20 5 15 0.33 6.7 386.8 2.23
4.8 10 20 10 10 0.67 13.4 400.2 6.69
5.0 5 10 5 5 0.33 6.7 406.9 6.69
5.2 5 15 10 5 0.67 13.4 420.2 13.38
5.4 10 20 10 10 0.67 13.4 433.6 6.69
5.6 20 50 30 20 2.01 40.2 473.8 10.04
5.8 10 40 30 10 2.01 40.2 513.9 20.08
6.0 10 20 10 10 0.67 13.4 527.3 6.69
6.2 5 20 15 5 1.00 20.1 547.4 20.08
6.4 5 15 10 5 0.67 13.4 560.8 13.38
6.6 10 40 30 10 2.01 40.2 600.9 20.08
6.8 30 50 20 30 1.34 26.8 627.7 4.46
7.0 40 60 20 40 1.34 26.8 654.5 3.35
7.2 25 30 5 25 0.33 6.7 661.1 1.34
7.4 15 40 25 15 1.67 33.5 694.6 11.15
7.6 10 40 30 10 2.01 40.2 734.8 20.08
7.8 15 60 45 15 3.01 60.2 795.0 20.08
8.0 25 60 35 25 2.34 46.8 841.8 9.37
8.2 40 70 30 40 2.01 40.2 882.0 5.02
8.4 35 100 65 35 4.35 87.0 969.0 12.43 11
CV. AULIA SURVEY KONSULTINDO
Laporan Sondir Test

8.6 40 75 35 40 2.34 46.8 1015.8 5.86


8.8 40 90 50 40 3.35 66.9 1082.7 8.36
9.0 20 95 75 20 5.02 100.4 1183.1 25.09
9.2 80 110 30 80 2.01 40.2 1223.2 2.51
9.4 40 90 50 40 3.35 66.9 1290.2 8.36
9.6 50 90 40 50 2.68 53.5 1343.7 5.35
9.8 40 70 30 40 2.01 40.2 1383.8 5.02
10.0 40 70 30 40 2.01 40.2 1424.0 5.02
10.2 40 90 50 40 3.35 66.9 1490.9 8.36
10.4 40 95 55 40 3.68 73.6 1564.5 9.20
10.6 35 75 40 35 2.68 53.5 1618.1 7.65
10.8 40 85 45 40 3.01 60.2 1678.3 7.53
11.0 90 95 5 90 0.33 6.7 1685.0 0.37
11.2 50 100 50 50 3.35 66.9 1751.9 6.69
11.4 40 90 50 40 3.35 66.9 1818.8 8.36
11.6 10 80 70 10 4.68 93.7 1912.5 46.84
11.8 15 80 65 15 4.35 87.0 1999.5 29.00
12.0 35 90 55 35 3.68 73.6 2073.1 10.52
12.2 60 160 100 60 6.69 133.8 2206.9 11.15
12.4 100 200 100 100 6.69 133.8 2340.8 6.69
12.6 100 200 100 100 6.69 133.8 2474.6 6.69
12.8 60 150 90 60 6.02 120.5 2595.1 10.04
13.0 50 150 100 50 6.69 133.8 2728.9 13.38
13.2 55 140 85 55 5.69 113.8 2842.6 10.34
13.4 70 120 50 70 3.35 66.9 2909.6 4.78
13.6 20 100 80 20 5.35 107.1 3016.6 26.77
13.8 15 100 85 15 5.69 113.8 3130.4 37.92
14.0 40 110 70 40 4.68 93.7 3224.1 11.71
14.2 40 150 110 40 7.36 147.2 3371.3 18.40
14.4 100 210 110 100 7.36 147.2 3518.5 7.36
14.6 50 140 90 50 6.02 120.5 3639.0 12.05
14.8 60 145 85 60 5.69 113.8 3752.7 9.48
15.0 80 150 70 80 4.68 93.7 3846.4 5.86
15.2 70 150 80 70 5.35 107.1 3953.5 7.65
15.4 60 150 90 60 6.02 120.5 4073.9 10.04
15.6 70 160 90 70 6.02 120.5 4194.4 8.60
15.8 70 130 60 70 4.02 80.3 4274.7 5.74
16.0 250 300 50 250 3.35 66.9 4341.6 1.34

12
CV. AULIA SURVEY KONSULTINDO
Laporan Sondir Test

SONDIR TEST

Project : Perencanaan Gedung Perpustakaan Data : 25 Oktober 2020


dan Kearsipan Kota Banjar
Location : Jl. Ciamis -Banjar No.120, Purwaharja, Tested By : Indra Faisal, ST
Kota Banjar, Jawa Barat 46331
Koordinat : E: 228312.000 Checked By : Syara Hanjaya, ST
: N: 9185730.000
Depth 16 m
Sondir No. :S-2

Cone Penetration (km/cm2) RATIO


0 50 100 150 200 250 300 0 10 20 30 40 50
0 0

1 1

2 2

3 3

4
4

5
5

6
6

7
7

8
Kadalaman (m)

9 ```
9
10
10
11
11
12

12
13

13
14

14
15

15
16

16
17

17
0.0 1.0 2.0 3.0 4.0
Local Friction (kg/cm)

13
CV. AULIA SURVEY KONSULTINDO
Laporan Sondir Test

SONDIR TEST

Project : Perencanaan Gedung Perpustakaan dan Data : 25 Oktober 2020 Project


Kearsipan Kota Banjar
Location : Jl. Ciamis -Banjar No.120, Purwaharja, Tested By : Indra Faisal, ST Location
Kota Banjar, Jawa Barat 46331
Koordinat : E: 228307.000 Checked By : Syara Hanjaya, ST Koordinat
: N: 9185745.000
Depth 15.4 m Depth
Sondir No. :S-3 Sondir No.

Depth Cw Tw Kw qc LF 20 cm. LF TF Ratio


( m) (kg/cm2 ) (kg/cm2 ) (kg/cm2 ) (kg/cm2 ) (kg/cm) (kg/cm) (kg/cm) 100 x LF/qc
0.0 0 0 0 0 0.00 0.0 0.0 0.00
0.2 4 6 2 4 0.13 2.7 2.7 3.35
0.4 5 8 3 5 0.20 4.0 6.7 4.02
0.6 10 20 10 10 0.67 13.4 20.1 6.69
0.8 10 20 10 10 0.67 13.4 33.5 6.69
1.0 15 25 10 15 0.67 13.4 46.8 4.46
1.2 20 23 3 20 0.20 4.0 50.9 1.00
1.4 20 30 10 20 0.67 13.4 64.2 3.35
1.6 25 30 5 25 0.33 6.7 70.9 1.34
1.8 20 30 10 20 0.67 13.4 84.3 3.35
2.0 60 80 20 60 1.34 26.8 111.1 2.23
2.2 20 40 20 20 1.34 26.8 137.8 6.69
2.4 20 40 20 20 1.34 26.8 164.6 6.69
2.6 15 25 10 15 0.67 13.4 178.0 4.46
2.8 20 35 15 20 1.00 20.1 198.1 5.02
3.0 15 20 5 15 0.33 6.7 204.8 2.23
3.2 15 20 5 15 0.33 6.7 211.5 2.23
3.4 10 20 10 10 0.67 13.4 224.8 6.69
3.6 10 15 5 10 0.33 6.7 231.5 3.35
3.8 15 20 5 15 0.33 6.7 238.2 2.23
4.0 20 40 20 20 1.34 26.8 265.0 6.69
4.2 20 40 20 20 1.34 26.8 291.8 6.69
4.4 10 20 10 10 0.67 13.4 305.1 6.69
4.6 15 25 10 15 0.67 13.4 318.5 4.46
4.8 10 20 10 10 0.67 13.4 331.9 6.69
5.0 5 10 5 5 0.33 6.7 338.6 6.69
5.2 5 10 5 5 0.33 6.7 345.3 6.69
5.4 10 20 10 10 0.67 13.4 358.7 6.69
5.6 20 40 20 20 1.34 26.8 385.4 6.69
5.8 10 30 20 10 1.34 26.8 412.2 13.38
6.0 10 20 10 10 0.67 13.4 425.6 6.69
6.2 5 10 5 5 0.33 6.7 432.3 6.69
6.4 5 10 5 5 0.33 6.7 439.0 6.69
6.6 10 20 10 10 0.67 13.4 452.4 6.69
6.8 30 40 10 30 0.67 13.4 465.7 2.23
7.0 40 50 10 40 0.67 13.4 479.1 1.67
7.2 20 30 10 20 0.67 13.4 492.5 3.35
7.4 15 30 15 15 1.00 20.1 512.6 6.69
7.6 10 30 20 10 1.34 26.8 539.4 13.38
7.8 20 40 20 20 1.34 26.8 566.1 6.69
8.0 20 40 20 20 1.34 26.8 592.9 6.69
8.2 40 60 20 40 1.34 26.8 619.7 3.35
8.4 40 80 40 40 2.68 53.5 673.2 6.69 14
CV. AULIA SURVEY KONSULTINDO
Laporan Sondir Test

8.6 40 80 40 40 2.68 53.5 726.7 6.69


8.8 40 60 20 40 1.34 26.8 753.5 3.35
9.0 20 90 70 20 4.68 93.7 847.2 23.42
9.2 60 80 20 60 1.34 26.8 873.9 2.23
9.4 40 80 40 40 2.68 53.5 927.5 6.69
9.6 50 90 40 50 2.68 53.5 981.0 5.35
9.8 40 90 50 40 3.35 66.9 1047.9 8.36
10.0 40 90 50 40 3.35 66.9 1114.8 8.36
10.2 40 90 50 40 3.35 66.9 1181.8 8.36
10.4 40 85 45 40 3.01 60.2 1242.0 7.53
10.6 30 70 40 30 2.68 53.5 1295.5 8.92
10.8 40 90 50 40 3.35 66.9 1362.4 8.36
11.0 40 90 50 40 3.35 66.9 1429.4 8.36
11.2 50 100 50 50 3.35 66.9 1496.3 6.69
11.4 50 90 40 50 2.68 53.5 1549.8 5.35
11.6 40 80 40 40 2.68 53.5 1603.3 6.69
11.8 30 80 50 30 3.35 66.9 1670.3 11.15
12.0 50 100 50 50 3.35 66.9 1737.2 6.69
12.2 60 220 160 60 10.71 214.1 1951.3 17.84
12.4 100 220 120 100 8.03 160.6 2111.9 8.03
12.6 100 220 120 100 8.03 160.6 2272.5 8.03
12.8 60 120 60 60 4.02 80.3 2352.8 6.69
13.0 60 140 80 60 5.35 107.1 2459.9 8.92
13.2 50 140 90 50 6.02 120.5 2580.3 12.05
13.4 50 120 70 50 4.68 93.7 2674.0 9.37
13.6 40 100 60 40 4.02 80.3 2754.3 10.04
13.8 40 120 80 40 5.35 107.1 2861.4 13.38
14.0 40 110 70 40 4.68 93.7 2955.1 11.71
14.2 100 200 100 100 6.69 133.8 3088.9 6.69
14.4 60 120 60 60 4.02 80.3 3169.2 6.69
14.6 80 140 60 80 4.02 80.3 3249.5 5.02
14.8 80 140 60 80 4.02 80.3 3329.8 5.02
15.0 150 210 60 150 4.02 80.3 3410.1 2.68
15.2 200 250 50 200 3.35 66.9 3477.0 1.67
15.4 250 300 50 250 3.35 66.9 3543.9 1.34

15
CV. AULIA SURVEY KONSULTINDO
Laporan Sondir Test

SONDIR TEST

Project : Perencanaan Gedung Perpustakaan Data : 25 Oktober 2020


dan Kearsipan Kota Banjar
Location : Jl. Ciamis -Banjar No.120, Purwaharja, Tested By : Indra Faisal, ST
Kota Banjar, Jawa Barat 46331
Koordinat : E: 228307.000 Checked By : Syara Hanjaya, ST
: N: 9185745.000
Depth 15.4 m
Sondir No. :S-3

Cone Penetration (km/cm2) RATIO


0 50 100 150 200 250 300 0 4 8 12 16 20 24 28
0 0

1 1

2
2

3
3

4
4
5
5
6

6
7

7
8
Kadalaman (m)

8 9 ```

9 10

11
10

12
11

13
12
14
13
15

14
16

15
17

16
0.0 1.0 2.0 3.0 4.0
Local Friction (kg/cm)

16
CV. AULIA SURVEY KONSULTINDO
Laporan Sondir Test

BAB IV
KESIMPULAN DAN SARAN

4.1. Kesimpulan
Berdasarkan hasil penyelidikan di lapangan dan hasil perhitungan serta hasil
evaluasi sondir test berikut ini disampaikan kesimpulan dan saran antara lain:
Dari data sondir diperoleh lapisan keras Qc > 250 kg/cm2 adalah S –1 = 13,4 meter,
S-2 = 16,0 meter dan S-3 = 15,4 meter.

4.2. Saran
• Dalam pelaksanaan konstruksi disarankan agar memakai pedoman teknik yang sudah
diperoleh dari hasil perhitungan.
• Berdasarkan kalkulasi daya dukung tanah pada lokasi rencana bangunan,
menunjukkan nilai daya dukung yang cukup kuat dan dalam yaitu di kedalaman 16,0
meter dari permukaan tanah setempat, maka disarankan untuk memakai fondasi
mencapai kedalaman yang keras (qc) 200-250 kg/cm2
• Disarankan untuk memakai pondasi Tiang Pancang.
• Dalam pengambilan bahan timbunan/bangunan jika diperlukan disarankan agar ada
pengaturan, supaya tidak menimbulkan bahaya gerakan tanah.
• Disarankan untuk melakukan penelitian menggunakan deep boring supaya lebih
mengetahui karakteristik tanah dan batuan di lokasi pekerjaan.

17
CV. AULIA SURVEY KONSULTINDO
Laporan Sondir Test

DAFTAR PUSTAKA

Departemen Permukiman dan Prasarana Wilayah, Badan Penelitian dan Pengembangan,

2002, PT-02, Persyaratan Teknis Bagian Penyelidikan Geologi Teknik, Jakarta.

Sosrodarsono, S. Ir. Dr., 1980, Mekanika Tanah dan teknik Pondasi, PT. Pradnya

Paramita, Jakarta.

SNI 2827:2008, “Cara uji penetrasi lapangan dengan alat sondir”

ASTM D 3441-86 tentang cara uji penetrasi lapangan dengan sondir