3297
66
2487
2410
3
168
1586
103
109
35°
3
9462
1. Data Konstruksi :
2. Analisa Beban
2.1 Analisa Beban
Beban Mati
Beban Gording = 1,00 Kg/m
Berat Atap = 45,00 x 0,35 = 15,53 Kg/m
Berat Pengaku (Bracing) = 20% x 1,00 = 0,20 Kg/m
Berat Total = 16,725 Kg/m
Berat Antar Joint Rangka Kuda-Kuda = 1 x 16,725 = 67,8696 Kg/m
0,345
Beban Hidup
Beban Hidup = 100,00 Kg
Beban Air Hujan = 20 x 0,35 = 6,90 Kg
Berat Antar Joint Rangka Kuda-Kuda = 1 x 6,90 = 28 Kg/m
0,35
Beban Angin
Beban Angin = 25,00 Kg/m2
3. Analsia Statika
3.1 Analisa Beban
BEBAN MATI
qy = q x Cos x
= 67,869565 x Cos ( 35 )
= 55,6 Kg/m
BEBAN HIDUP
qy = q x Cos x
= 100,00 x Cos ( 35 )
= 81,92 Kg/m
λc = = 550,00 = 1,61 N
212,20
2
- Untuk λc ≤ 1,5 fn = = 185,88 N/mm
- Menghitung luas efektif
Ae = Ag = 106,65 mm2
- Menghitung kapasitas komponen struktur nominal (Nc) dan kapasitas penampang nominal (Ns)
- Ns = Ae x fy
= 106,65 x 550,00
= 58659,7 N
= 5865,97 Kg
- Nc = Ae x fn
= 106,65 x 185,88
= 19824,734 N
= 1982,473 Kg
- Persyaratan :
Dengan gaya aksial tekan ( N* ) = 1525,05 Kg ,
ɸc = 0,85 ( Tabel 1.6 SNI 7971 : 2013 )
N* ≤ ɸc x Nc
Le = 1750 mm
<> dh = 6 mm
N* ft = 12659 N
N* ft ≤ ɸ x Nft
12659 ≤ 0,8 x 88522,82
12659 ≤ 70.818,26 N … OK!!!
- Jumlah baut :
n = N (tarik) / ɸ Nft
= 12659 / 70.818,26
= 0,17875 2,00000 (Catatan : Jumlah minimum baut sebanyak 2 buah)
Nt = 0,85 x Kt x An x fy
= 0,85 x 0,85 x 94,654 x 550
= 37613,13 N
= 3761,31 Kg
<> Persyaratan :
N* ≤ ɸ x t x Nt
1265,9 ≤ 0,9 x 0,75 x 3761,313
1265,9 ≤ 2538,886 Kg … OK!!!