Perhitungan Struktur Baja Dengan Microsoft Excel

PERHITUNGAN BALOK DENGAN PENGAKU BADAN

[C]2011 : M. Noer Ilham

A. DATA BAHAN

Tegangan leleh baja (yield stress), fy = 240 MPa


Tegangan sisa (residual stress), fr = 70 MPa
Modulus elastik baja (modulus of elasticity), E= 200000 MPa
Angka Poisson (Poisson's ratio), u= 0.3

B. DATA PROFIL BAJA


Profil : WF 400.200.8.13
ht = 400 mm
bf = 200 mm
tf tw = 8 mm
tf = 13 mm
r=
tw 16 mm

h h2 ht A= 8410 mm2
Ix = 237000000 mm4
Iy = 17400000 mm4
rx = 168 mm
r
h1 ry = 45.4 mm
Sx = 1190000 mm3
bf Sy = 174000 mm3
Berat : w= 647 N/m

BALOK DENGAN PENGAKU BADAN

[C]2011 : MNI Balok Dengan Pengaku Badan 1


Perhitungan Struktur Baja Dengan Microsoft Excel

C. DATA BALOK

Panjang elemen thd.sb. x, Lx = 12000 mm


Panjang elemen thd.sb. y ( jarak dukungan lateral ), Ly = 4000 mm
Jarak antara pengaku vertikal pada badan, a= 1000 mm
Tebal plat pengaku vertikal pada badan, ts = 13 mm
Momen maksimum akibat beban terfaktor, Mu = 146000000 Nmm
Momen pada 1/4 bentang, MA = 122000000 Nmm
Momen di tengah bentang, MB = 146000000 Nmm
Momen pada 3/4 bentang, MC = 115000000 Nmm
Gaya geser akibat beban terfaktor, Vu = 328000 N
Faktor reduksi kekuatan untuk lentur, fb = 0.90
Faktor reduksi kekuatan untuk geser, ff = 0.75

D. SECTION PROPERTIES
G=E/[2*(1+u)]= 76923 MPa
h1 = t f + r = 29.00 mm
h2 = h t - 2 * h 1 = 342.00 mm
h = ht - tf = 387.00 mm
J = S [ b * t3/3 ] = 2 * 1/3 * bf * tf3 + 1/3 * (ht - 2 * tf) * tw3 = 356762.7 mm4
I w = I y * h2 / 4 = 6.515E+11 mm6
X1 = p / Sx * √ [ E * G * J * A / 2 ] = 12682.9 MPa
X2 = 4 * [ Sx / (G * J) ]2 * Iw / Iy = 0.0002816 mm2/N2
Z x = t w * ht 2 / 4 + ( b f - t w ) * ( h t - t f ) * t f = 1285952.0 mm3
Z y = t f * bf 2 / 2 + ( h t - 2 * t f ) * t w 2 / 4 = 265984.0 mm3

G = modulus geser, Zx = modulus penampang plastis thd. sb. x,


J = Konstanta puntir torsi, Zy = modulus penampang plastis thd. sb. y,
Iw = konstanta putir lengkung, X1 = koefisien momen tekuk torsi lateral - 1,

[C]2011 : MNI Balok Dengan Pengaku Badan 2


Perhitungan Struktur Baja Dengan Microsoft Excel

h = tinggi bersih badan, X2 = koefisien momen tekuk torsi lateral - 2,

E. PERHITUNGAN KEKUATAN

Syarat yg harus dipenuhi untuk balok dengan pengaku, maka nilai : a / h ≤ 3.0
a/h= 2.584 < 3.00
® berlaku rumus balok dengan pengaku (OK)
Ketebalan plat badan dengan pengaku vertikal tanpa pengaku memanjang harus meme-
nuhi : h / tw £ 7.07 * √ ( E / fy )
48.375 < 204.09 ® tebal plat badan memenuhi (OK)

1. MOMEN NOMINAL PENGARUH LOCAL BUCKLING

1.1. Pengaruh tekuk lokal (local buckling) pada sayap

Kelangsingan penampang sayap, l = bf / tf = 15.385


Batas kelangsingan maksimum untuk penampang compact,
lp = 500 / √ fy = 32.275
Batas kelangsingan maksimum untuk penampang non-compact,
lr = 625 / √ fy = 40.344
Momen plastis, Mp = fy * Zx = 308628480 Nmm
Momen batas tekuk, Mr = Sx * ( fy - fr ) = 202300000 Nmm
Momen nominal penampang untuk :
a. Penampang compact, l £ lp
→ Mn = Mp
b. Penampang non-compact, lp < l £ lr
→ Mn = Mp - (Mp - Mr) * ( l - lp) / ( lr - lp)
c. Penampang langsing, l > lr
→ M n = M r * ( lr / l ) 2

l < lp dan l < lr


Berdasarkan nilai kelangsingan sayap, maka termasuk penampang compact
Momen nominal penampang dihitung sebagai berikut :
compact : Mn = Mp = 308628480 Nmm

[C]2011 : MNI Balok Dengan Pengaku Badan 3


Perhitungan Struktur Baja Dengan Microsoft Excel

non-compact : Mn = Mp - (Mp - Mr) * ( l - lp) / ( lr - lp) = - Nmm


langsing : M n = M r * ( lr / l ) =
2
- Nmm
Momen nominal untuk penampang : compact Mn = 308628480 Nmm
1.2. Pengaruh tekuk lokal (local buckling) pada badan

Kelangsingan penampang badan, l = h / tw = 48.375


Batas kelangsingan maksimum untuk penampang compact,
lp = 1680 / √ fy = 108.444
Batas kelangsingan maksimum untuk penampang non-compact,
lr = 2550 / √ fy = 164.602
l < lp dan l < lr
Berdasarkan nilai kelangsingan badan, maka termasuk penampang compact
Momen nominal penampang dihitung sebagai berikut :
compact : Mn = Mp = 308628480 Nmm
non-compact : Mn = Mp - (Mp - Mr) * ( l - lp) / ( lr - lp) = - Nmm
langsing : M n = M r * ( lr / l ) =
2
- Nmm
Momen nominal untuk penampang : compact Mn = 308628480 Nmm

2. MOMEN NOMINAL BALOK PLAT BERDINDING PENUH

Kelangsingan penampang badan, l = h / tw = 48.375


Untuk penampang yang mempunyai ukuran : h / tw > lr
48.375 > 40.344
maka momen nominal komponen struktur, harus dihitung dengan rumus :
Mn = Kg * S * fcr
dengan, Kg = 1 - [ ar / (1200 + 300 * ar) ] * [ h / tw - 2550 / Ö fcr ]
a. Untuk kelangsingan : lG ≤ lp → fcr = fy
b. Untuk kelangsingan : l p < l G ≤ lr
→ fcr = Cb * fy * [ 1 - ( lG - lp ) / ( 2 * ( lr - lp ) ) ] ≤ fy
c. Untuk kelangsingan : lG > lr → fcr = fc * ( lr / lG )
2
≤ fy
Untuk tekuk torsi lateral : → fc = Cb * f y / 2 ≤ fy
Untuk tekuk lokal : → fc = f y / 2
Koefisien momen tekuk torsi lateral,
Cb = 12.5 * Mu / ( 2.5*Mu + 3*MA + 4*MB + 3*MC ) = 1.10 < 2.3

[C]2011 : MNI Balok Dengan Pengaku Badan 4


Perhitungan Struktur Baja Dengan Microsoft Excel

® diambil, Cb = 1.10
Perbandingan luas plat badan terhadap luas plat sayap,
ar = h * t w / ( b f * t f ) = 1.191
Momen inersia, I1 = Iy / 2 - 1/12 * tw * 1/3 * h2 = 8695136 mm4
3

Luas penampang, A1 = A / 2 - 1/3 * tw * h2 = 3293 mm2


Jari-jari girasi daerah plat sayap ditambah sepertiga bagian plat badan yang mengalami
tekan, r1 = Ö ( I1 / A1 ) = 51 mm

2.1. Momen nominal berdasarkan tekuk torsi lateral

Jarak antara pengekang lateral, L = Ly = 4000 mm


Angka kelangsingan, lG = L / r 1 = 77.843
Batas kelangsingan maksimum untuk penampang compact,
lp = 1.76 * √ ( E / fy ) = 50.807
Batas kelangsingan maksimum untuk penampang non-compact,
lr = 4.40 * √ ( E / fy ) = 127.017
Tegangan acuan untuk momen kritis tekuk torsi lateral,
fc = C b * f y / 2 = 131.93 MPa
fc < fy maka diambil, fc = 131.93 MPa
lG > lp dan lG < lr
Tegangan kritis penampang dihitung sebagai berikut :
lG ≤ lp fcr = fy = - MPa
lp ≤ lG ≤ lr fcr = Cb* fy* [ 1 - ( lG - lp) / ( 2*( lr - lp) ) ] = 217.05 MPa
lG > lr fcr = fc * ( lr / lG )2 = - MPa
fcr = 217.05 MPa
fcr < fy maka diambil, fcr = 217.05 MPa
Modulus penampang elastis, S = Sx = 1190000 mm3
Koefisien balok plat berdinding penuh,
Kg = 1 - [ ar / (1200 + 300 * ar) ] * [ h / tw - 2550 / Ö fcr ] = 1.095
Momen nominal penampang, Mn = Kg * S * fcr = 282925041 Nmm

2.2. Momen nominal berdasarkan local buckling pada sayap

Kelangsingan penampang sayap, lG = b f / ( 2 * t f ) = 7.69

[C]2011 : MNI Balok Dengan Pengaku Badan 5


Perhitungan Struktur Baja Dengan Microsoft Excel

Faktor kelangsingan plat badan, ke = 4 / Ö ( h / tw ) = 0.575 < 0.763


diambil, ke = 0.575
Batas kelangsingan maksimum untuk penampang compact,
lp = 0.38 * √ ( E / fy ) = 10.97

Batas kelangsingan maksimum untuk penampang non-compact,


lr = 1.35 * √ ( ke * E / fy ) = 29.55
Tegangan acuan untuk momen kritis tekuk lokal, f c = fy / 2 = 120.00 MPa
lG < lp dan lG < lr
Tegangan kritis penampang dihitung sebagai berikut :
lG ≤ lp fcr = fy = 240.00 MPa
lp ≤ lG ≤ lr fcr = Cb* fy* [ 1 - ( lG - lp) / ( 2*( lr - lp) ) ] = - MPa
lG > lr fcr = fc * ( lr / lG )2 = - MPa
Tegangan kritis penampang, fcr = 240.00 MPa
fcr < fy maka diambil, fcr = 240.00 MPa
Modulus penampang elastis, S = Sx = 1190000 mm3
Koefisien balok plat berdinding penuh,
Kg = 1 - [ ar / (1200 + 300 * ar) ] * [ h / tw - 2550 / Ö fcr ] = 1.089
Momen nominal penampang, Mn = Kg * S * fcr = 310982774 Nmm

3. MOMEN NOMINAL PENGARUH LATERAL BUCKLING

Momen nominal komponen struktur dengan pengaruh tekuk lateral, untuk :


a. Bentang pendek : L £ Lp
→ Mn = M p = fy * Z x
b. Bentang sedang : Lp < L £ Lr
→ M n = Cb * [ M r + ( M p - M r ) * ( L r - L ) / ( L r - L p ) ] £ Mp
c. Bentang panjang : L > Lr
→ Mn = Cb * p / L*√ [ E * Iy * G * J + ( p * E / L )2 * Iy * Iw ] £ Mp
Panjang bentang maksimum balok yang mampu menahan momen plastis,
Lp = 1.76 * ry * √ ( E / fy ) = 2307 mm
Tegangan leleh dikurangi tegangan sisa, f L = f y - fr = 170 MPa
Panjang bentang minimum balok yang tahanannya ditentukan oleh momen kritis tekuk
torsi lateral, Lr = ry * X1 / fL * √ [ 1 + √ ( 1 + X2 * fL2 ) ] = 6794 mm

[C]2011 : MNI Balok Dengan Pengaku Badan 6


Perhitungan Struktur Baja Dengan Microsoft Excel

Koefisien momen tekuk torsi lateral,


Cb = 12.5 * Mu / ( 2.5*Mu + 3*MA + 4*MB + 3*MC ) = 1.10
Momen plastis, Mp = fy * Zx = 308628480 Nmm
Momen batas tekuk, Mr = Sx * ( fy - fr ) = 202300000 Nmm
Panjang bentang thd.sb. y (jarak dukungan lateral), L = Ly = 4000 mm

L > Lp dan L < Lr


® Termasuk kategori : bentang sedang
Momen nominal dihitung sebagai berikut :
Mn = M p = f y * Z x = - Nmm
Mn = Cb * [ Mr + ( Mp - Mr ) * ( Lr - L ) / ( Lr - Lp ) ] = 295188726 Nmm
Mn = Cb * p / L*√ [ E * Iy * G * J + ( p * E / L )2 * Iy * Iw ] = - Nmm
Momen nominal balok untuk kategori : bentang sedang Mn = 295188726 Nmm
Mn < Mp
Momen nominal yang digunakan, Mn = 295188726 Nmm

4. TAHANAN MOMEN LENTUR

a. Momen nominal pengaruh local buckling :


Momen nominal pengaruh local buckling pada sayap, Mn = 308628480 Nmm
Momen nominal pengaruh local buckling pada badan, Mn = 308628480 Nmm
b. Momen nominal balok plat berdinding penuh :
Momen nominal berdasarkan tekuk torsi lateral, Mn = 282925041 Nmm
Momen nominal berdasarkan local buckling pd. sayap, Mn = 310982774 Nmm
c. Momen nominal berdasarkan pengaruh lateral buckling, Mn = 295188726 Nmm
Momen nominal (terkecil) yang menentukan, ® Mn = 282925041 Nmm
Tahanan momen lentur, fb * M n = 254632537 Nmm
Momen akibat beban terfaktor, Mu = 146000000 Nmm
Syarat yg harus dipenuhi : M u £ fb * M n
146000000 < 254632537 ® AMAN (OK)

Mu / ( fb * Mn ) = 0.5734 < 1.0 (OK)

[C]2011 : MNI Balok Dengan Pengaku Badan 7


Perhitungan Struktur Baja Dengan Microsoft Excel

5. TAHANAN GESER

Tahanan geser nominal plat badan dengan pengaku dihitung sebagai berikut :
Untuk nilai, h / tw ≤ 1.10 * Ö ( kn * E / fy )
Tahanan geser plastis :
→ Vn = 0.60 * fy * Aw
Untuk nilai, 1.10 * Ö ( kn * E / fy ) ≤ h / tw ≤ 1.37 * Ö ( kn * E / fy )
Tahanan geser elasto plastis :
→ Vn = 0.60 * fy * Aw * [ 1.10*Ö ( kn * E / fy ) ] / ( h / tw )
Untuk nilai, h / tw > 1.37 * Ö ( kn * E / fy )
Tahanan geser elastis :
→ Vn = 0.90 * Aw * kn * E / ( h / tw )2

Luas penampang badan, Aw = tw * ht = 3200 mm2


kn = 5 + 5 / ( a / h )2 = 5.7488
Perbandingan tinggi terhadap tebal badan, h / tw = 48.375
1.10 * Ö ( kn * E / fy ) = 76.136
1.37 * Ö ( kn * E / fy ) = 94.824
h / tw < 1.10*Ö ( kn*E / fy ) dan h / tw < 1.37*Ö ( kn*E / fy )
® Tahanan geser plastis
Tahanan geser nominal dihitung sebagai berikut :
Vn = 0.60 * fy * Aw = 460800 N
Vn = 0.60 * fy * Aw * [ 1.10*Ö ( kn * E / fy ) ] / ( h / tw ) = - N
Vn = 0.90 * Aw * kn * E / ( h / tw )2 = - N
Tahana geser nominal untuk geser : plastis Vn = 460800 N
Tahanan gaya geser, ff * Vn = 345600 N
Gaya geser akibat beban terfaktor, Vu = 328000 N

[C]2011 : MNI Balok Dengan Pengaku Badan 8


Perhitungan Struktur Baja Dengan Microsoft Excel

Syarat yg harus dipenuhi : Vu £ ff * Vn


328000 < 345600 ® AMAN (OK)

6. INTERAKSI GESER DAN LENTUR

Elemen yang memikul kombinasi geser dan lentur harus dilakukan kontrol sbb. :
Syarat yang harus dipenuhi untuk interakasi geser dan lentur :
Mu / ( fb * Mn ) + 0.625 * Vu / ( ff * Vn ) £ 1.375
Mu / ( fb * Mn ) = 0.5734
Vu / ( ff * Vn ) = 0.9491
Mu / ( fb * Mn ) + 0.625 * Vu / ( ff * Vn ) = 1.1665
1.1665 < 1.375 AMAN (OK)

7. DIMENSI PENGAKU VERTIKAL PADA BADAN

Luas penampang plat pengaku vertikal harus memenuhi,


As ≥ 0.5 * D * Aw * (1 + Cv) * [ a / h - (a / h)2 / Ö (1 + (a / h)2 ) ]
Tebal plat pengaku vertikal pada badan (stiffner), ts = 13 mm
Tinggi plat pengaku, hs = h t - 2 * t f = 374 mm
Luas penampang plat pengaku, As = hs * ts = 4862 mm2
Untuk sepasang pengaku, D= 1
Cv = 1.5 * kn * E / fy * 1 / ( h /tw )2 = 3.0708
0.5 * D * Aw * (1 + Cv) * [ a / h - (a / h)2 / Ö (1 + (a / h)2 ) ] = 1134 mm2
Syarat yang harus dipenuhi :
As ≥ 0.5 * D * Aw * (1 + Cv) * [ a / h - (a / h)2 / Ö (1 + (a / h)2 ) ]
4862 > 1134 ® AMAN (OK)

Pengaku vertikal pada plat badan harus mempunyai momen inersia :


Is ≥ 0.75 * h * tw3 untuk a / h ≤ Ö2
Is ≥ 1.5 * h3 * tw3 / a2 untuk a / h > Ö2

Momen inersia plat pengaku, Is = 2/3 * hs * ts3 = 547785 mm4


untuk, a/h= 2.584 > Ö2
Batasan momen inersia pengaku vertikal dihitung sebagai berikut :

[C]2011 : MNI Balok Dengan Pengaku Badan 9


Perhitungan Struktur Baja Dengan Microsoft Excel

0.75 * h * tw3 = - mm4


1.5 * h3 * tw3 / a2 = 44514 mm4
Momen inersia minimum = 44514 mm4
Kontrol momen inersia plat pengaku,
Is = 547785 > 44514 ® AMAN (OK)

[C]2011 : MNI Balok Dengan Pengaku Badan 10


Pehitungan Struktur Baja Dengan Microsoft Excel

PERHITUNGAN BALOK TANPA PENGAKU BADAN

[C]2011 : M. Noer Ilham

A. DATA BAHAN

Tegangan leleh baja (yield stress), fy = 240 MPa


Tegangan sisa (residual stress), fr = 70 MPa
Modulus elastik baja (modulus of elasticity), E= 200000 MPa
Angka Poisson (Poisson's ratio), u= 0.3

B. DATA PROFIL BAJA


Profil : WF 400.200.8.13
ht = 400 mm
tf bf = 200 mm
tw = 8 mm
tf = 13 mm
tw r=
h h2 ht A=
16
8410
mm
mm2
Ix = 237000000 mm4
Iy = 17400000 mm4

r rx = 168 mm
h1 ry = 45.4 mm
bf Sx = 1190000 mm3
Sy = 174000 mm3
Berat : w= 647 N/m

BALOK TANPA PENGAKU BADAN

[C]2011 : MNI Balok Tanpa Pengaku Badan 11


Pehitungan Struktur Baja Dengan Microsoft Excel

C. DATA BALOK

Panjang elemen thd.sb. x, Lx = 12000 mm


Panjang elemen thd.sb. y ( jarak dukungan lateral ), Ly = 4000 mm
Momen maksimum akibat beban terfaktor, Mu = 146000000 Nmm
Momen pada 1/4 bentang, MA = 122000000 Nmm
Momen di tengah bentang, MB = 146000000 Nmm
Momen pada 3/4 bentang, MC = 115000000 Nmm
Gaya geser akibat beban terfaktor, Vu = 328000 N
Faktor reduksi kekuatan untuk lentur, fb = 0.90
Faktor reduksi kekuatan untuk geser, ff = 0.75

D. SECTION PROPERTIES
G = E / [ 2 *( 1 + u ) ] = 76923 MPa
h1 = t f + r = 29.00 mm
h2 = h t - 2 * h 1 = 342.00 mm
h = ht - tf = 387.00 mm
J = S [ b * t3/3 ] = 2 * 1/3 * bf * tf3 + 1/3 * (ht - 2 * tf) * tw3 = 356762.7 mm4
Iw = I y * h2 / 4 = 6.515E+11 mm6
X1 = p / Sx * √ [ E * G * J * A / 2 ] = 12682.9 MPa
X2 = 4 * [ Sx / (G * J) ]2 * Iw / Iy = 0.0002816 mm2/N2
Zx = tw * ht2 / 4 + ( bf - tw ) * ( ht - tf ) * tf = 1285952.0 mm3
Zy = tf * bf2 / 2 + ( ht - 2 * tf ) * tw2 / 4 = 265984.0 mm3

G = modulus geser, tf
J = Konstanta puntir torsi,
Iw = konstanta putir lengkung, tw
h h2 ht
X1 = koefisien momen tekuk torsi lateral - 1,
X2 = koefisien momen tekuk torsi lateral - 2, r
h1
bf
[C]2011 : MNI Balok Tanpa Pengaku Badan 12
tw
h h2 ht
Pehitungan Struktur Baja Dengan Microsoft Excel

r
Zx = modulus penampang plastis thd. sb. x, h1
bf
Zy = modulus penampang plastis thd. sb. y,
E. PERHITUNGAN KEKUATAN

1. MOMEN NOMINAL PENGARUH LOCAL BUCKLING

Kelangsingan penampang sayap, l = b f / tf = 15.385


Batas kelangsingan maksimum untuk penampang compact,
lp = 170 / √ fy = 10.973
Batas kelangsingan maksimum untuk penampang non-compact,
lr = 370 / √ ( fy - fr ) = 28.378
Momen plastis, Mp = fy * Zx = 308628480 Nmm
Momen batas tekuk, Mr = Sx * ( fy - fr ) = 202300000 Nmm
Momen nominal penampang untuk :
a. Penampang compact : l £ lp
→ Mn = Mp
b. Penampang non-compact : lp < l £ lr
→ Mn = Mp - (Mp - Mr) * ( l - lp) / ( lr - lp)
c. Penampang langsing : l > lr
→ M n = M r * ( lr / l ) 2

l > lp dan l < lr


Berdasarkan nilai kelangsingan sayap, maka termasuk penampang non-compact
Momen nominal penampang dihitung sebagai berikut :
compact : Mn = M p = - Nmm
non-compact : Mn = Mp - (Mp - Mr) * ( l - lp) / ( lr - lp) = 281679191 Nmm
langsing : M n = M r * ( lr / l ) 2 = - Nmm
Momen nominal untuk penampang : non-compact Mn = 281679191 Nmm

[C]2011 : MNI Balok Tanpa Pengaku Badan 13


Pehitungan Struktur Baja Dengan Microsoft Excel

2. MOMEN NOMINAL BALOK PLAT BERDINDING PENUH

Kelangsingan penampang badan, l = h / tw = 48.375


Untuk penampang yang mempunyai ukuran : h / tw > lr
maka momen nominal komponen struktur, harus dihitung dengan rumus :
Mn = Kg * S * fcr
dengan, Kg = 1 - [ ar / (1200 + 300 * ar) ] * [ h / tw - 2550 / Ö fcr ]
a. Untuk kelangsingan : lG ≤ lp → fcr = fy
b. Untuk kelangsingan : l p < l G ≤ lr
→ fcr = Cb * fy * [ 1 - ( lG - lp ) / ( 2 * ( lr - lp ) ) ] ≤ fy
c. Untuk kelangsingan : lG > lr → fcr = fc * ( lr / lG )
2
≤ fy
Untuk tekuk torsi lateral : → f c = C b * fy / 2 ≤ fy
Untuk tekuk lokal : → fc = fy / 2
Koefisien momen tekuk torsi lateral,
Cb = 12.5 * Mu / ( 2.5 * Mu + 3 * MA + 4 * MB + 3 * MC ) = 1.10 < 2.3
® diambil, Cb = 1.10
Perbandingan luas plat badan terhadap luas plat sayap,
ar = h * t w / ( b f * t f ) = 1.191
Momen inersia, I1 = Iy / 2 - 1/12 * tw3 * 1/3 * h2 = 8695136 mm4
Luas penampang, A1 = A / 2 - 1/3 * tw * h2 = 3293 mm2
Jari-jari girasi daerah plat sayap ditambah sepertiga bagian plat badan yang mengalami
tekan, r1 = Ö ( I1 / A1 ) = 51 mm

2.1. Momen nominal berdasarkan tekuk torsi lateral

Jarak antara pengekang lateral, L = Ly = 4000 mm


Angka kelangsingan, lG = L / r 1 = 77.843
Batas kelangsingan maksimum untuk penampang compact,
lp = 1.76 * √ ( E / fy ) = 50.807
Batas kelangsingan maksimum untuk penampang non-compact,
lr = 4.40 * √ ( E / fy ) = 127.017

[C]2011 : MNI Balok Tanpa Pengaku Badan 14


Pehitungan Struktur Baja Dengan Microsoft Excel

Tegangan acuan untuk momen kritis tekuk torsi lateral,


fc = Cb * f y / 2 = 131.93 MPa
fc < fy maka diambil, fc = 131.93 MPa

lG > lp dan lG < lr


Tegangan kritis penampang dihitung sebagai berikut :
lG ≤ lp fcr = fy = - MPa
lp ≤ lG ≤ lr fcr = Cb* fy* [ 1 - ( lG - lp) / ( 2*( lr - lp) ) ] = 217.05 MPa
lG > lr fcr = fc * ( lr / lG )2 = - MPa
fcr = 217.05 MPa
fcr < fy maka diambil, fcr = 217.05 MPa
Modulus penampang elastis, S = Sx = 1190000 mm3
Koefisien balok plat berdinding penuh,
Kg = 1 - [ ar / (1200 + 300 * ar) ] * [ h / tw - 2550 / Ö fcr ] = 1.095
Momen nominal penampang, Mn = Kg * S * fcr = 282925041 Nmm

2.2. Momen nominal berdasarkan local buckling pada sayap

Faktor kelangsingan plat badan, ke = 4 / Ö ( h / tw ) = 0.575 < 0.763


diambil, ke = 0.575
Kelangsingan penampang sayap, lG = b f / ( 2 * t f ) = 7.69
Batas kelangsingan maksimum untuk penampang compact,
lp = 0.38 * √ ( E / fy ) = 10.97
Batas kelangsingan maksimum untuk penampang non-compact,
lr = 1.35 * √ ( ke * E / fy ) = 29.55
Tegangan acuan untuk momen kritis tekuk lokal, fc = f y / 2 = 120.00 MPa
lG < lp dan lG < lr
Berdasarkan nilai kelangsingan sayap, maka termasuk penampang compact
Tegangan kritis penampang dihitung sebagai berikut :
lG ≤ lp fcr = fy = 240.00 MPa
lp ≤ lG ≤ lr fcr = Cb* fy* [ 1 - ( lG - lp) / ( 2*( lr - lp) ) ] = - MPa
lG > lr fcr = fc * ( lr / lG )2 = - MPa
Tegangan kritis penampang, fcr = 240.00 MPa
fcr < fy maka diambil, fcr = 240.00 MPa

[C]2011 : MNI Balok Tanpa Pengaku Badan 15


Pehitungan Struktur Baja Dengan Microsoft Excel

Modulus penampang elastis, S = Sx = 1190000 mm3


Koefisien balok plat berdinding penuh,
Kg = 1 - [ ar / (1200 + 300 * ar) ] * [ h / tw - 2550 / Ö fcr ] = 1.089
Momen nominal penampang, Mn = Kg * S * fcr = 310982774 Nmm

3. MOMEN NOMINAL PENGARUH LATERAL BUCKLING

Momen nominal komponen struktur dengan pengaruh tekuk lateral, untuk :


a. Bentang pendek : L £ Lp
→ Mn = M p = fy * Z x
b. Bentang sedang : Lp < L £ Lr
→ M n = Cb * [ M r + ( M p - M r ) * ( L r - L ) / ( L r - L p ) ] £ Mp
c. Bentang panjang : L > Lr
→ Mn = Cb * p / L*√ [ E * Iy * G * J + ( p * E / L )2 * Iy * Iw ] £ Mp

Panjang bentang maksimum balok yang mampu menahan momen plastis,


Lp = 1.76 * ry * √ ( E / fy ) = 2307 mm
fL = f y - f r = 170 MPa
Panjang bentang minimum balok yang tahanannya ditentukan oleh momen kritis tekuk
torsi lateral, Lr = ry * X1 / fL * √ [ 1 + √ ( 1 + X2 * fL2 ) ] = 6794 mm
Koefisien momen tekuk torsi lateral,
Cb = 12.5 * Mu / ( 2.5*Mu + 3*MA + 4*MB + 3*MC ) = 1.10
Momen plastis, Mp = fy * Zx = 308628480 Nmm
Momen batas tekuk, Mr = Sx * ( fy - fr ) = 202300000 Nmm
Panjang bentang thd.sb. y (jarak dukungan lateral), L = Ly = 4000 mm
L > Lp dan L < Lr
® Termasuk kategori : bentang sedang
Momen nominal dihitung sebagai berikut :
Mn = M p = fy * Z x = - Nmm
Mn = Cb * [ Mr + ( Mp - Mr ) * ( Lr - L ) / ( Lr - Lp ) ] = 295188726 Nmm
Mn = Cb * p / L*√ [ E * Iy * G * J + ( p * E / L )2 * Iy * Iw ] = - Nmm
Momen nominal untuk kategori : bentang sedang Mn = 295188726 Nmm
Mn < Mp
Momen nominal yang digunakan, ® Mn = 295188726 Nmm

[C]2011 : MNI Balok Tanpa Pengaku Badan 16


Pehitungan Struktur Baja Dengan Microsoft Excel

4. TAHANAN MOMEN LENTUR

a. Momen nominal berdasarkan pengaruh local buckling, Mn = 308628480 Nmm


b. Momen nominal balok plat berdinding penuh :
Momen nominal berdasarkan tekuk torsi lateral, Mn = 282925041 Nmm
Momen nominal berdasarkan local buckling pd. sayap, Mn = 310982774 Nmm
c. Momen nominal berdasarkan pengaruh lateral buckling, Mn = 295188726 Nmm
Momen nominal (terkecil) yang menentukan, ® Mn = 282925041 Nmm
Tahanan momen lentur, fb * Mn = 254632537 Nmm
Momen akibat beban terfaktor, Mu = 146000000 Nmm
Syarat yg harus dipenuhi : M u £ fb * M n
146000000 < 254632537 ® AMAN (OK)

M u / ( fb * M n ) = 0.5734 < 1.0 (OK)

5. TAHANAN GESER

Kontrol tahanan geser nominal plat badan tanpa pengaku :


Ketebalan plat badan tanpa pengaku harus memenuhi syarat,
h2 / t w £ 6.36 * Ö ( E / fy )
42.75 < 183.60 ® Plat badan memenuhi syarat (OK)

Gaya geser akibat beban terfaktor, Vu = 328000 N


Luas penampang badan, Aw = tw * ht = 3200 mm2
Tahanan gaya geser nominal, Vn = 0.60 * fy * Aw = 460800 N
Tahanan gaya geser, ff * Vn = 345600 N
Syarat yg harus dipenuhi : Vu £ ff * Vn
328000 < 345600 ® AMAN (OK)

[C]2011 : MNI Balok Tanpa Pengaku Badan 17


Pehitungan Struktur Baja Dengan Microsoft Excel

Vu / ( ff * Vn ) = 0.7500 < 1.0 (OK)

6. INTERAKSI GESER DAN LENTUR

Elemen yang memikul kombinasi geser dan lentur harus dilakukan kontrol sbb. :
Syarat yang harus dipenuhi untuk interaksi geser dan lentur :
Mu / ( fb * Mn ) + 0.625 * Vu / ( ff * Vn ) £ 1.375

Mu / ( fb * Mn ) = 0.5734
Vu / ( ff * Vn ) = 0.9491
Mu / ( fb * Mn ) + 0.625 * Vu / ( ff * Vn ) = 1.1665
< 1.375 AMAN (OK)

[C]2011 : MNI Balok Tanpa Pengaku Badan 18


PERHITUNGAN BALOK DENGAN PENGAKU BADAN

A. DATA BAHAN

Tegangan leleh baja (yield stress), fy = 240 MPa


Tegangan sisa (residual stress), fr = 70 MPa
Modulus elastik baja (modulus of elasticity), E= 200000 MPa
Angka Poisson (Poisson's ratio), u= 0.3

B. DATA PROFIL BAJA

WF 350.175.7.11
ht = 350 mm
bf = 175 mm
tw = 7 mm
tf = 11 mm
r= 14 mm
A= 6314 mm2
Ix = 136000000 mm4
Iy = 9840000 mm4
rx = 147 mm
ry = 39.5 mm
Sx = 775000 mm3
Sy = 112000 mm3
w= 486.08 N/m

Balok dengan pengaku badan


C. DATA BALOK

Panjang elemen thd.sb. x, Lx = 6000 mm


Panjang elemen thd.sb. y ( jarak dukungan lateral ), Ly = 2000 mm
Jarak antara pengaku vertikal pada badan, a= 1000 mm
Tebal plat pengaku vertikal pada badan, ts = 8 mm
Momen maksimum akibat beban terfaktor, Mu = 112233695 Nmm

Momen pada 1/4 bentang, MA = 26965643.45 Nmm

Momen di tengah bentang, MB = 52557735.98 Nmm

Momen pada 3/4 bentang, MC = 32404928 Nmm


Gaya geser akibat beban terfaktor, Vu = 91836.98 N
Faktor reduksi kekuatan untuk lentur, fb = 0.90
Faktor reduksi kekuatan untuk geser, ff = 0.75

D. SECTION PROPERTIES
G=E/[2*(1+u)]= 76923 MPa
h1 = tf + r = 25.00 mm
h2 = ht - 2 * h1 = 300.00 mm
h = ht - tf = 339.00 mm
J = S [ b * t /3 ] = 2 * 1/3 * bf * tf + 1/3 * (ht - 2 * tf) * t
3 3
w
3
= 192784.7 mm4
Iw = Iy * h2 / 4 = 2.827E+11 mm6
X 1 = p / Sx * √ [ E * G * J * A / 2 ] = 12404.1 MPa
X2 = 4 * [ Sx / (G * J) ] * Iw / Iy = 0.0003139
2
mm2/N2
Zx = tw * ht2 / 4 + ( bf - tw ) * ( ht - tf ) * tf = 840847.0 mm3
Zy = tf * bf2 / 2 + ( ht - 2 * tf ) * tw2 / 4 = 172455.5 mm3

G = modulus geser, Zx = modulus penampang plastis thd. sb. x,

J = Konstanta puntir torsi, Zy = modulus penampang plastis thd. sb. y,


Iw = konstanta putir lengkung, X1 = koefisien momen tekuk torsi lateral - 1,

h = tinggi bersih badan, X2 = koefisien momen tekuk torsi lateral - 2,

E. PERHITUNGAN KEKUATAN

Syarat yg harus dipenuhi untuk balok dengan pengaku, maka nilai : a / h ≤ 3.0
a/h= 2.950 < 3.00
® berlaku rumus balok dengan pengaku (OK)
Ketebalan plat badan dengan pengaku vertikal tanpa pengaku memanjang harus meme-
nuhi : h / tw £ 7.07 * √ ( E / fy )

48.429 < 204.09 ® tebal plat badan memenuhi (OK)

1. MOMEN NOMINAL PENGARUH LOCAL BUCKLING

1.1. Pengaruh tekuk lokal (local buckling) pada sayap

Kelangsingan penampang sayap, l = bf / t f = 15.909


Batas kelangsingan maksimum untuk penampang compact,
lp = 500 / √ fy = 32.275
Batas kelangsingan maksimum untuk penampang non-compact,
lr = 625 / √ fy = 40.344
Momen plastis, Mp = fy * Zx = 201803280 Nmm

Momen batas tekuk, Mr = Sx * ( fy - fr ) = 131750000 Nmm

Momen nominal penampang untuk :


a. Penampang compact, l £ lp
→ Mn = Mp

b. Penampang non-compact, lp < l £ lr


→ Mn = Mp - (Mp - Mr) * ( l - lp) / ( lr - lp)

c. Penampang langsing, l > lr


→ Mn = Mr * ( lr / l )2

l < lp dan l < lr


Berdasarkan nilai kelangsingan sayap, maka termasuk penampang compact
Momen nominal penampang dihitung sebagai berikut :
compact : Mn = Mp = 201803280 Nmm
non-compact : Mn = Mp - (Mp - Mr) * ( l - lp) / ( lr - lp) = - Nmm
langsing : Mn = Mr * ( lr / l )2 = - Nmm
Momen nominal untuk penampang : compact Mn = 201803280 Nmm
1.2. Pengaruh tekuk lokal (local buckling) pada badan

Kelangsingan penampang badan, l = h / tw = 48.429


Batas kelangsingan maksimum untuk penampang compact,
lp = 1680 / √ fy = 108.444
Batas kelangsingan maksimum untuk penampang non-compact,
lr = 2550 / √ fy = 164.602
l < lp dan l < lr

Berdasarkan nilai kelangsingan badan, maka termasuk penampang compact


Momen nominal penampang dihitung sebagai berikut :
compact : Mn = Mp = 201803280 Nmm

non-compact : Mn = Mp - (Mp - Mr) * ( l - lp) / ( lr - lp) = - Nmm


langsing : Mn = Mr * ( lr / l ) = 2
- Nmm
Momen nominal untuk penampang : compact Mn = 201803280 Nmm

2. MOMEN NOMINAL BALOK PLAT BERDINDING PENUH

Kelangsingan penampang badan, l = h / tw = 48.429


Untuk penampang yang mempunyai ukuran : h / tw > lr

48.429 > 40.344


maka momen nominal komponen struktur, harus dihitung dengan rumus :
Mn = Kg * S * fcr

dengan, Kg = 1 - [ ar / (1200 + 300 * ar) ] * [ h / tw - 2550 / Ö fcr ]

a. Untuk kelangsingan : lG ≤ lp → fcr = fy

b. Untuk kelangsingan : lp < lG ≤ lr


→ fcr = Cb * fy * [ 1 - ( lG - lp ) / ( 2 * ( lr - lp ) ) ] ≤ fy

c. Untuk kelangsingan : lG > lr → fcr = fc * ( lr / lG )2 ≤ fy

Untuk tekuk torsi lateral : → fc = Cb * fy / 2 ≤ fy

Untuk tekuk lokal : → fc = f y / 2

Koefisien momen tekuk torsi lateral,


Cb = 12.5 * Mu / ( 2.5*Mu + 3*MA + 4*MB + 3*MC ) = 2.10 < 2.3
® diambil, Cb = 2.10
Perbandingan luas plat badan terhadap luas plat sayap,
ar = h * tw / ( bf * tf ) = 1.233
Momen inersia, I1 = Iy / 2 - 1/12 * tw3 * 1/3 * h2 = 4917142 mm4
Luas penampang, A1 = A / 2 - 1/3 * tw * h2 = 2457 mm2
Jari-jari girasi daerah plat sayap ditambah sepertiga bagian plat badan yang mengalami
tekan, r1 = Ö ( I1 / A1 ) = 45 mm

2.1. Momen nominal berdasarkan tekuk torsi lateral

Jarak antara pengekang lateral, L = Ly = 2000 mm


Angka kelangsingan, lG = L / r1 = 44.707
Batas kelangsingan maksimum untuk penampang compact,
lp = 1.76 * √ ( E / fy ) = 50.807
Batas kelangsingan maksimum untuk penampang non-compact,
lr = 4.40 * √ ( E / fy ) = 127.017
Tegangan acuan untuk momen kritis tekuk torsi lateral,
fc = Cb * fy / 2 = 251.67 MPa
fc > fy maka diambil, fc = 240.00 MPa
lG < lp dan lG < lr

Tegangan kritis penampang dihitung sebagai berikut :


lG ≤ lp fcr = fy = 240.00 MPa
lp ≤ lG ≤ lr fcr = Cb* fy* [ 1 - ( lG - lp) / ( 2*( lr - lp) ) ] = - MPa
lG > lr fcr = fc * ( lr / lG ) =
2
- MPa
fcr = 240.00 MPa
fcr < fy maka diambil, fcr = 240.00 MPa
Modulus penampang elastis, S = Sx = 775000 mm3
Koefisien balok plat berdinding penuh,
Kg = 1 - [ ar / (1200 + 300 * ar) ] * [ h / tw - 2550 / Ö fcr ] = 1.091
Momen nominal penampang, Mn = Kg * S * fcr = 202968233 Nmm

2.2. Momen nominal berdasarkan local buckling pada sayap

Kelangsingan penampang sayap, lG = bf / ( 2 * tf ) = 7.95


Faktor kelangsingan plat badan, ke = 4 / Ö ( h / tw ) = 0.575 < 0.763
diambil, ke = 0.575
Batas kelangsingan maksimum untuk penampang compact,
lp = 0.38 * √ ( E / fy ) = 10.97
Batas kelangsingan maksimum untuk penampang non-compact,
lr = 1.35 * √ ( ke * E / fy ) = 29.55
Tegangan acuan untuk momen kritis tekuk lokal, fc = f y / 2 = 120.00 MPa
lG < lp dan lG < lr
Tegangan kritis penampang dihitung sebagai berikut :
lG ≤ lp fcr = fy = 240.00 MPa
lp ≤ lG ≤ lr fcr = Cb* fy* [ 1 - ( lG - lp) / ( 2*( lr - lp) ) ] = - MPa
lG > lr fcr = fc * ( lr / lG )2 = - MPa
Tegangan kritis penampang, fcr = 240.00 MPa
fcr < fy maka diambil, fcr = 240.00 MPa
Modulus penampang elastis, S = Sx = 775000 mm3
Koefisien balok plat berdinding penuh,
Kg = 1 - [ ar / (1200 + 300 * ar) ] * [ h / tw - 2550 / Ö fcr ] = 1.091
Momen nominal penampang, Mn = Kg * S * fcr = 202968233 Nmm

3. MOMEN NOMINAL PENGARUH LATERAL BUCKLING


Momen nominal komponen struktur dengan pengaruh tekuk lateral, untuk :
a. Bentang pendek : L £ Lp

→ M n = M p = f y * Zx

b. Bentang sedang : Lp < L £ Lr

→ Mn = Cb * [ Mr + ( Mp - Mr ) * ( Lr - L ) / ( Lr - Lp ) ] £ Mp

c. Bentang panjang : L > Lr

→ Mn = Cb * p / L*√ [ E * Iy * G * J + ( p * E / L )2 * Iy * Iw ] £ Mp
Panjang bentang maksimum balok yang mampu menahan momen plastis,
Lp = 1.76 * ry * √ ( E / fy ) = 2007 mm
Tegangan leleh dikurangi tegangan sisa, fL = f y - f r = 170 MPa
Panjang bentang minimum balok yang tahanannya ditentukan oleh momen kritis tekuk
torsi lateral, Lr = ry * X1 / fL * √ [ 1 + √ ( 1 + X2 * fL2 ) ] = 5888 mm
Koefisien momen tekuk torsi lateral,
Cb = 12.5 * Mu / ( 2.5*Mu + 3*MA + 4*MB + 3*MC ) = 2.10
Momen plastis, Mp = fy * Zx = 201803280 Nmm

Momen batas tekuk, Mr = Sx * ( fy - fr ) = 131750000 Nmm

Panjang bentang thd.sb. y (jarak dukungan lateral), L = Ly = 2000 mm


L < Lp dan L < Lr

® Termasuk kategori : bentang pendek


Momen nominal dihitung sebagai berikut :
Mn = Mp = fy * Zx = 201803280 Nmm
Mn = Cb * [ Mr + ( Mp - Mr ) * ( Lr - L ) / ( Lr - Lp ) ] = - Nmm
Mn = Cb * p / L*√ [ E * Iy * G * J + ( p * E / L )2 * Iy * Iw ] = - Nmm
Momen nominal balok untuk kategori : bentang pendek Mn = 201803280 Nmm
Mn > Mp

Momen nominal yang digunakan, Mn = 201803280 Nmm

4. TAHANAN MOMEN LENTUR


a. Momen nominal pengaruh local buckling :
Momen nominal pengaruh local buckling pada sayap, Mn = 201803280 Nmm
Momen nominal pengaruh local buckling pada badan, Mn = 201803280 Nmm
b. Momen nominal balok plat berdinding penuh :
Momen nominal berdasarkan tekuk torsi lateral, Mn = 202968233 Nmm
Momen nominal berdasarkan local buckling pd. sayap, Mn = 202968233 Nmm
c. Momen nominal berdasarkan pengaruh lateral buckling, Mn = 201803280 Nmm
Momen nominal (terkecil) yang menentukan, ® Mn = 201803280 Nmm
Tahanan momen lentur, fb * Mn = 181622952 Nmm
Momen akibat beban terfaktor, Mu = 112233695 Nmm

Syarat yg harus dipenuhi : Mu £ fb * Mn

112233695 < 181622952 ® (OK)

Mu / ( fb * Mn ) = 0.6179 < 1.0 (OK)

5. TAHANAN GESER
Tahanan geser nominal plat badan dengan pengaku dihitung sebagai berikut :
Untuk nilai, h / tw ≤ 1.10 * Ö ( kn * E / fy )

Tahanan geser plastis :


→ Vn = 0.60 * fy * Aw
Untuk nilai, 1.10 * Ö ( kn * E / fy ) ≤ h / tw ≤ 1.37 * Ö ( kn * E / fy )

Tahanan geser elasto plastis :


→ Vn = 0.60 * fy * Aw * [ 1.10*Ö ( kn * E / fy ) ] / ( h / tw )

Untuk nilai, h / tw > 1.37 * Ö ( kn * E / fy )

Tahanan geser elastis :


→ Vn = 0.90 * Aw * kn * E / ( h / tw )2

Luas penampang badan, Aw = tw * ht = 2450 mm2


kn = 5 + 5 / ( a / h )2 = 5.5746
Perbandingan tinggi terhadap tebal badan, h / tw = 48.429
1.10 * Ö ( kn * E / fy ) = 74.974
1.37 * Ö ( kn * E / fy ) = 93.376
h / tw < 1.10*Ö ( kn*E / fy ) dan h / tw < 1.37*Ö ( kn*E / fy )

® Tahanan geser plastis


Tahanan geser nominal dihitung sebagai berikut :
Vn = 0.60 * fy * Aw = 352800 N
Vn = 0.60 * fy * Aw * [ 1.10*Ö ( kn * E / fy ) ] / ( h / tw ) = - N
Vn = 0.90 * Aw * kn * E / ( h / tw ) = 2
- N
Tahana geser nominal untuk geser : plastis Vn = 352800 N
Tahanan gaya geser, ff * Vn = 264600 N
Gaya geser akibat beban terfaktor, Vu = 91836.98 N
Syarat yg harus dipenuhi : Vu £ ff * Vn

91836.98 < 264600 ® (OK)

6. INTERAKSI GESER DAN LENTUR

Elemen yang memikul kombinasi geser dan lentur harus dilakukan kontrol sbb. :
Syarat yang harus dipenuhi untuk interakasi geser dan lentur :
Mu / ( fb * Mn ) + 0.625 * Vu / ( ff * Vn ) £ 1.375
Mu / ( fb * Mn ) = 0.6179
Vu / ( ff * Vn ) = 0.3471
Mu / ( fb * Mn ) + 0.625 * Vu / ( ff * Vn ) = 0.8349
0.8349 < 1.375 (OK)

7. DIMENSI PENGAKU VERTIKAL PADA BADAN


Luas penampang plat pengaku vertikal harus memenuhi,
As ≥ 0.5 * D * Aw * (1 + Cv) * [ a / h - (a / h)2 / Ö (1 + (a / h)2 ) ]

Tebal plat pengaku vertikal pada badan (stiffner), ts = 8 mm


Tinggi plat pengaku, hs = ht - 2 * tf = 328 mm
Luas penampang plat pengaku, As = hs * ts = 2624 mm2
Untuk sepasang pengaku, D= 1
Cv = 1.5 * kn * E / fy * 1 / ( h /tw )2 = 2.9711
0.5 * D * Aw * (1 + Cv) * [ a / h - (a / h)2 / Ö (1 + (a / h)2 ) ] = 760 mm2
Syarat yang harus dipenuhi :
As ≥ 0.5 * D * Aw * (1 + Cv) * [ a / h - (a / h)2 / Ö (1 + (a / h)2 ) ]

2624 > 760 ® (OK)

Pengaku vertikal pada plat badan harus mempunyai momen inersia :


Is ≥ 0.75 * h * tw3 untuk a / h ≤ Ö2
Is ≥ 1.5 * h3 * tw3 / a2 untuk a / h > Ö2

Momen inersia plat pengaku, Is = 2/3 * hs * ts3 = 111957 mm4


untuk, a/h= 2.950 > Ö2
Batasan momen inersia pengaku vertikal dihitung sebagai berikut :
0.75 * h * tw3 = - mm4
1.5 * h3 * tw3 / a2 = 20044 mm4
Momen inersia minimum = 20044 mm4
Kontrol momen inersia plat pengaku,
Is = 111957 > 20044 ® (OK)
tf

tw
h h2 ht

r
h1
bf

10000 13600
10000 984
10 14.7
10 3.95
1000 775
1000 112
9.8 49.6
berlaku rumus balok dengan pengaku (OK)
tebal plat badan memenuhi (OK)
compact
compact
compact
compact
bentang pendek
(OK)
< 1.0 (OK)
(OK)
1.375 (OK)
(OK)
(OK)
PERHITUNGAN BALOK DENGAN PENGAKU BADAN

A. DATA BAHAN

Tegangan leleh baja (yield stress), fy = 240 MPa


Tegangan sisa (residual stress), fr = 70 MPa
Modulus elastik baja (modulus of elasticity), E= 200000 MPa
Angka Poisson (Poisson's ratio), u= 0.3

B. DATA PROFIL BAJA

WF 250.125.6.9
ht = 250 mm
bf = 125 mm
tw = 6 mm
tf = 9 mm
r= 12 mm
A= 3766 mm2
Ix = 40500000 mm4
Iy = 2940000 mm4
rx = 104 mm
ry = 27.9 mm
Sx = 324000 mm3
Sy = 47000 mm3
w= 290.08 N/m

Balok dengan pengaku badan


C. DATA BALOK

Panjang elemen thd.sb. x, Lx = 6000 mm


Panjang elemen thd.sb. y ( jarak dukungan lateral ), Ly = 2000 mm
Jarak antara pengaku vertikal pada badan, a= 1000 mm
Tebal plat pengaku vertikal pada badan, ts = 8 mm
Momen maksimum akibat beban terfaktor, Mu = 36850193.1 Nmm
Momen pada 1/4 bentang, MA = 4386808.1 Nmm
Momen di tengah bentang, MB = 18996991.9 Nmm
Momen pada 3/4 bentang, MC = 4920716.4 Nmm
Gaya geser akibat beban terfaktor, Vu = 32247.6 N
Faktor reduksi kekuatan untuk lentur, fb = 0.90
Faktor reduksi kekuatan untuk geser, ff = 0.75

D. SECTION PROPERTIES
G=E/[2*(1+u)]= 76923 MPa
h1 = tf + r = 21.00 mm
h2 = ht - 2 * h1 = 208.00 mm
h = ht - tf = 241.00 mm
J = S [ b * t /3 ] = 2 * 1/3 * bf * tf + 1/3 * (ht - 2 * tf) * t
3 3
w
3
= 77454.0 mm4
Iw = Iy * h2 / 4 = 4.269E+10 mm6
X 1 = p / Sx * √ [ E * G * J * A / 2 ] = 14524.3 MPa
X2 = 4 * [ Sx / (G * J) ] * Iw / Iy = 0.0001718
2
mm2/N2
Zx = tw * ht2 / 4 + ( bf - tw ) * ( ht - tf ) * tf = 351861.0 mm3
Zy = tf * bf2 / 2 + ( ht - 2 * tf ) * tw2 / 4 = 72400.5 mm3

G = modulus geser, Zx = modulus penampang plastis thd. sb. x,

J = Konstanta puntir torsi, Zy = modulus penampang plastis thd. sb. y,


Iw = konstanta putir lengkung, X1 = koefisien momen tekuk torsi lateral - 1,

h = tinggi bersih badan, X2 = koefisien momen tekuk torsi lateral - 2,

E. PERHITUNGAN KEKUATAN

Syarat yg harus dipenuhi untuk balok dengan pengaku, maka nilai : a / h ≤ 3.0
a/h= 4.149 > 3.00
® tidak berlaku rumus balok dg pengaku
Ketebalan plat badan dengan pengaku vertikal tanpa pengaku memanjang harus meme-
nuhi : h / tw £ 7.07 * √ ( E / fy )

40.167 < 204.09 ® tebal plat badan memenuhi (OK)

1. MOMEN NOMINAL PENGARUH LOCAL BUCKLING


1.1. Pengaruh tekuk lokal (local buckling) pada sayap

Kelangsingan penampang sayap, l = bf / t f = 13.889


Batas kelangsingan maksimum untuk penampang compact,
lp = 500 / √ fy = 32.275
Batas kelangsingan maksimum untuk penampang non-compact,
lr = 625 / √ fy = 40.344
Momen plastis, M p = f y * Zx = 84446640 Nmm
Momen batas tekuk, Mr = Sx * ( fy - fr ) = 55080000 Nmm
Momen nominal penampang untuk :
a. Penampang compact, l £ lp
→ Mn = Mp

b. Penampang non-compact, lp < l £ lr


→ Mn = Mp - (Mp - Mr) * ( l - lp) / ( lr - lp)

c. Penampang langsing, l > lr


→ Mn = Mr * ( lr / l )2

l < lp dan l < lr


Berdasarkan nilai kelangsingan sayap, maka termasuk penampang compact
Momen nominal penampang dihitung sebagai berikut :
compact : Mn = M p = 84446640 Nmm
non-compact : Mn = Mp - (Mp - Mr) * ( l - lp) / ( lr - lp) = - Nmm
langsing : Mn = Mr * ( lr / l )2 = - Nmm
Momen nominal untuk penampang : compact Mn = 84446640 Nmm
1.2. Pengaruh tekuk lokal (local buckling) pada badan

Kelangsingan penampang badan, l = h / tw = 40.167


Batas kelangsingan maksimum untuk penampang compact,
lp = 1680 / √ fy = 108.444
Batas kelangsingan maksimum untuk penampang non-compact,
lr = 2550 / √ fy = 164.602
l < lp dan l < lr

Berdasarkan nilai kelangsingan badan, maka termasuk penampang compact


Momen nominal penampang dihitung sebagai berikut :
compact : Mn = M p = 84446640 Nmm
non-compact : Mn = Mp - (Mp - Mr) * ( l - lp) / ( lr - lp) = - Nmm
langsing : Mn = Mr * ( lr / l ) = 2
- Nmm
Momen nominal untuk penampang : compact Mn = 84446640 Nmm

2. MOMEN NOMINAL BALOK PLAT BERDINDING PENUH

Kelangsingan penampang badan, l = h / tw = 40.167


Untuk penampang yang mempunyai ukuran : h / tw > lr

40.167 < 40.344


maka momen nominal komponen struktur, tidak harus dihitung dengan rumus :
Mn = Kg * S * fcr

dengan, Kg = 1 - [ ar / (1200 + 300 * ar) ] * [ h / tw - 2550 / Ö fcr ]

a. Untuk kelangsingan : lG ≤ lp → fcr = fy

b. Untuk kelangsingan : lp < lG ≤ lr


→ fcr = Cb * fy * [ 1 - ( lG - lp ) / ( 2 * ( lr - lp ) ) ] ≤ fy

c. Untuk kelangsingan : lG > lr → fcr = fc * ( lr / lG )2 ≤ fy

Untuk tekuk torsi lateral : → fc = Cb * fy / 2 ≤ fy

Untuk tekuk lokal : → fc = f y / 2

Koefisien momen tekuk torsi lateral,


Cb = 12.5 * Mu / ( 2.5*Mu + 3*MA + 4*MB + 3*MC ) = 2.35 > 2.3
® diambil, Cb = 2.30
Perbandingan luas plat badan terhadap luas plat sayap,
ar = h * tw / ( bf * tf ) = 1.285
Momen inersia, I1 = Iy / 2 - 1/12 * tw3 * 1/3 * h2 = 1468752 mm4
Luas penampang, A1 = A / 2 - 1/3 * tw * h2 = 1467 mm2
Jari-jari girasi daerah plat sayap ditambah sepertiga bagian plat badan yang mengalami
tekan, r1 = Ö ( I1 / A1 ) = 32 mm

2.1. Momen nominal berdasarkan tekuk torsi lateral

Jarak antara pengekang lateral, L = Ly = 2000 mm


Angka kelangsingan, lG = L / r1 = 63.208
Batas kelangsingan maksimum untuk penampang compact,
lp = 1.76 * √ ( E / fy ) = 50.807
Batas kelangsingan maksimum untuk penampang non-compact,
lr = 4.40 * √ ( E / fy ) = 127.017
Tegangan acuan untuk momen kritis tekuk torsi lateral,
fc = Cb * fy / 2 = 276.00 MPa
fc > fy maka diambil, fc = 240.00 MPa
lG > lp dan lG < lr

Tegangan kritis penampang dihitung sebagai berikut :


lG ≤ lp fcr = fy = - MPa
lp ≤ lG ≤ lr fcr = Cb* fy* [ 1 - ( lG - lp) / ( 2*( lr - lp) ) ] = 507.09 MPa
lG > lr fcr = fc * ( lr / lG ) =
2
- MPa
fcr = 507.09 MPa
fcr > fy maka diambil, fcr = 240.00 MPa
Modulus penampang elastis, S = Sx = 324000 mm3
Koefisien balok plat berdinding penuh,
Kg = 1 - [ ar / (1200 + 300 * ar) ] * [ h / tw - 2550 / Ö fcr ] = 1.101
Momen nominal penampang, Mn = Kg * S * fcr = 85603707 Nmm

2.2. Momen nominal berdasarkan local buckling pada sayap

Kelangsingan penampang sayap, lG = bf / ( 2 * tf ) = 6.94


Faktor kelangsingan plat badan, ke = 4 / Ö ( h / tw ) = 0.631 < 0.763
diambil, ke = 0.631
Batas kelangsingan maksimum untuk penampang compact,
lp = 0.38 * √ ( E / fy ) = 10.97
Batas kelangsingan maksimum untuk penampang non-compact,
lr = 1.35 * √ ( ke * E / fy ) = 30.96
Tegangan acuan untuk momen kritis tekuk lokal, fc = f y / 2 = 120.00 MPa
lG < lp dan lG < lr
Tegangan kritis penampang dihitung sebagai berikut :
lG ≤ lp fcr = fy = 240.00 MPa
lp ≤ lG ≤ lr fcr = Cb* fy* [ 1 - ( lG - lp) / ( 2*( lr - lp) ) ] = - MPa
lG > lr fcr = fc * ( lr / lG )2 = - MPa
Tegangan kritis penampang, fcr = 240.00 MPa
fcr < fy maka diambil, fcr = 240.00 MPa
Modulus penampang elastis, S = Sx = 324000 mm3
Koefisien balok plat berdinding penuh,
Kg = 1 - [ ar / (1200 + 300 * ar) ] * [ h / tw - 2550 / Ö fcr ] = 1.101
Momen nominal penampang, Mn = Kg * S * fcr = 85603707 Nmm

3. MOMEN NOMINAL PENGARUH LATERAL BUCKLING


Momen nominal komponen struktur dengan pengaruh tekuk lateral, untuk :
a. Bentang pendek : L £ Lp

→ M n = M p = f y * Zx

b. Bentang sedang : Lp < L £ Lr

→ Mn = Cb * [ Mr + ( Mp - Mr ) * ( Lr - L ) / ( Lr - Lp ) ] £ Mp

c. Bentang panjang : L > Lr

→ Mn = Cb * p / L*√ [ E * Iy * G * J + ( p * E / L )2 * Iy * Iw ] £ Mp
Panjang bentang maksimum balok yang mampu menahan momen plastis,
Lp = 1.76 * ry * √ ( E / fy ) = 1418 mm
Tegangan leleh dikurangi tegangan sisa, fL = f y - f r = 170 MPa
Panjang bentang minimum balok yang tahanannya ditentukan oleh momen kritis tekuk
torsi lateral, Lr = ry * X1 / fL * √ [ 1 + √ ( 1 + X2 * fL2 ) ] = 4422 mm
Koefisien momen tekuk torsi lateral,
Cb = 12.5 * Mu / ( 2.5*Mu + 3*MA + 4*MB + 3*MC ) = 2.30
Momen plastis, M p = f y * Zx = 84446640 Nmm
Momen batas tekuk, Mr = Sx * ( fy - fr ) = 55080000 Nmm
Panjang bentang thd.sb. y (jarak dukungan lateral), L = Ly = 2000 mm
L > Lp dan L < Lr

® Termasuk kategori : bentang sedang


Momen nominal dihitung sebagai berikut :
M n = M p = f y * Zx = - Nmm
Mn = Cb * [ Mr + ( Mp - Mr ) * ( Lr - L ) / ( Lr - Lp ) ] = 181134397 Nmm
Mn = Cb * p / L*√ [ E * Iy * G * J + ( p * E / L )2 * Iy * Iw ] = - Nmm
Momen nominal balok untuk kategori : bentang sedang Mn = 181134397 Nmm
Mn > Mp

Momen nominal yang digunakan, Mn = 84446640 Nmm

4. TAHANAN MOMEN LENTUR


a. Momen nominal pengaruh local buckling :
Momen nominal pengaruh local buckling pada sayap, Mn = 84446640 Nmm
Momen nominal pengaruh local buckling pada badan, Mn = 84446640 Nmm
b. Momen nominal balok plat berdinding penuh :
Momen nominal berdasarkan tekuk torsi lateral, Mn = 85603707 Nmm
Momen nominal berdasarkan local buckling pd. sayap, Mn = 85603707 Nmm
c. Momen nominal berdasarkan pengaruh lateral buckling, Mn = 84446640 Nmm
Momen nominal (terkecil) yang menentukan, ® Mn = 84446640 Nmm
Tahanan momen lentur, fb * Mn = 76001976 Nmm
Momen akibat beban terfaktor, Mu = 36850193.1 Nmm

Syarat yg harus dipenuhi : Mu £ fb * Mn

36850193 < 76001976 ® (OK)

Mu / ( fb * Mn ) = 0.4849 < 1.0 (OK)

5. TAHANAN GESER
Tahanan geser nominal plat badan dengan pengaku dihitung sebagai berikut :
Untuk nilai, h / tw ≤ 1.10 * Ö ( kn * E / fy )

Tahanan geser plastis :


→ Vn = 0.60 * fy * Aw
Untuk nilai, 1.10 * Ö ( kn * E / fy ) ≤ h / tw ≤ 1.37 * Ö ( kn * E / fy )

Tahanan geser elasto plastis :


→ Vn = 0.60 * fy * Aw * [ 1.10*Ö ( kn * E / fy ) ] / ( h / tw )

Untuk nilai, h / tw > 1.37 * Ö ( kn * E / fy )

Tahanan geser elastis :


→ Vn = 0.90 * Aw * kn * E / ( h / tw )2

Luas penampang badan, Aw = tw * ht = 1500 mm2


kn = 5 + 5 / ( a / h )2 = 5.2904
Perbandingan tinggi terhadap tebal badan, h / tw = 40.167
1.10 * Ö ( kn * E / fy ) = 73.038
1.37 * Ö ( kn * E / fy ) = 90.965
h / tw < 1.10*Ö ( kn*E / fy ) dan h / tw < 1.37*Ö ( kn*E / fy )

® Tahanan geser plastis


Tahanan geser nominal dihitung sebagai berikut :
Vn = 0.60 * fy * Aw = 216000 N
Vn = 0.60 * fy * Aw * [ 1.10*Ö ( kn * E / fy ) ] / ( h / tw ) = - N
Vn = 0.90 * Aw * kn * E / ( h / tw ) = 2
- N
Tahana geser nominal untuk geser : plastis Vn = 216000 N
Tahanan gaya geser, ff * Vn = 162000 N
Gaya geser akibat beban terfaktor, Vu = 32247.6 N
Syarat yg harus dipenuhi : Vu £ ff * Vn

32247.6 < 162000 ® (OK)

6. INTERAKSI GESER DAN LENTUR

Elemen yang memikul kombinasi geser dan lentur harus dilakukan kontrol sbb. :
Syarat yang harus dipenuhi untuk interakasi geser dan lentur :
Mu / ( fb * Mn ) + 0.625 * Vu / ( ff * Vn ) £ 1.375
Mu / ( fb * Mn ) = 0.4849
Vu / ( ff * Vn ) = 0.1991
Mu / ( fb * Mn ) + 0.625 * Vu / ( ff * Vn ) = 0.6093
0.6093 < 1.375 (OK)

7. DIMENSI PENGAKU VERTIKAL PADA BADAN


Luas penampang plat pengaku vertikal harus memenuhi,
As ≥ 0.5 * D * Aw * (1 + Cv) * [ a / h - (a / h)2 / Ö (1 + (a / h)2 ) ]

Tebal plat pengaku vertikal pada badan (stiffner), ts = 8 mm


Tinggi plat pengaku, hs = ht - 2 * tf = 232 mm
Luas penampang plat pengaku, As = hs * ts = 1856 mm2
Untuk sepasang pengaku, D= 1
Cv = 1.5 * kn * E / fy * 1 / ( h /tw )2 = 4.0989
0.5 * D * Aw * (1 + Cv) * [ a / h - (a / h)2 / Ö (1 + (a / h)2 ) ] = 442 mm2
Syarat yang harus dipenuhi :
As ≥ 0.5 * D * Aw * (1 + Cv) * [ a / h - (a / h)2 / Ö (1 + (a / h)2 ) ]

1856 > 442 ® (OK)

Pengaku vertikal pada plat badan harus mempunyai momen inersia :


Is ≥ 0.75 * h * tw3 untuk a / h ≤ Ö2
Is ≥ 1.5 * h3 * tw3 / a2 untuk a / h > Ö2

Momen inersia plat pengaku, Is = 2/3 * hs * ts3 = 79189 mm4


untuk, a/h= 4.149 > Ö2
Batasan momen inersia pengaku vertikal dihitung sebagai berikut :
0.75 * h * tw3 = - mm4
1.5 * h3 * tw3 / a2 = 4535 mm4
Momen inersia minimum = 4535 mm4
Kontrol momen inersia plat pengaku,
Is = 79189 > 4535 ® (OK)
tf

tw
h h2 ht

r
h1
bf

100 37.66
10000 4050
10000 294
10 10.4
10 2.79
1000 324
1000 47
9.8 29.6
tidak berlaku rumus balok dg pengaku
tebal plat badan memenuhi (OK)
compact
compact
compact
compact
(OK)
< 1.0 (OK)
(OK)
1.375 (OK)
(OK)
(OK)