PERHITUNGAN
Tipe heat exchanger yang digunakan adalah tipe shell and tube dengan 2
passes dengan beberapa keterangan yang diketahui :
panjang tube keseluruhan : 264 cm = 103,43 inch
diameter tube : 1,27 cm = 0,5 inch
panjang shell : 70 cm = 27,56 inch
diameter shell : 16 cm = 6,299 inch
tebal shell : 2 cm = 0,787 inch
Jarak antarbafel : 20 cm = 7,87 inch
Jarak antar tube : 60,55 mm = 2,38 inch
Diameter tube dianggap sebagai OD sehingga pada Tabel 11, OD nominal
pipe 0,5 inch didapat ID = 0,622 lalu dicek ke Tabel 10 didapat spesifikasi
OD = 0,5 In = 0,042 ft
ID = 0,370 In = 0,031 ft
Flowrate = 0,302 In2
BWG = 16
Pitch Tube = 0,75 inch (Tabel 10)
1. Suhu 40°C
T1 = 38,2°C = 100,76°F
T2 = 36°C = 96,8°F
t1 = 25,2°C = 77,36°F
t2 = 28,8°C = 83,84°F
a. Heat Balance (Q)
Pada Fluida Panas
( T1 + T2 ) 10 0,76 + 96,8
= = 98,78°F
2 2
Dari Appendix Fig.2 (Kern, 1965) diperoleh:
Cp = 1,0 Btu/lb °F
Q = 8,26 L/menit
ρ = 62,1061 lbm/ft3 (Range Suhu 80°C - 100°C)
(A-2.11, Geankoplis, 1915)
Maka,
W = ρ × Laju Alir
= 62,1061 lbm/ft3 × (8,26 L/menit × 1 ft3/28,32 L × 60 menit/hr)
= 1.086,85 lbm/hr
Q = W × Cp (T1 T2)
= 1.086,85 lbm/hr × 1 Btu/lbm°F × (100,76 – 96,8)°F
= 4.303,92 Btu/hr
Pada Fluida Dingin
( t 2 + t 1 ) 83,84 + 77,36
= = 8 0,6 °F
2 2
Dari Appendix Fig.2 (Kern, 1965) diperoleh:
Cp = 1,0 Btu/lb °F
Q = 7,18 L/menit
ρ = 62,197 lbm/ft3
(A-2.11, Geankoplis, 1915)
Maka,
W = ρ × Laju Alir
= 62,197 lbm/ft3 × (7,18 L/menit × 1 ft3/28,32 L × 60 menit/hr)
= 946,1323 lbm/hr
Q = W × Cp (t2 t1)
= 946,1323 lbm/hr × 1 Btu/lbm°F × (83,84 – 77,36)°F
= 6.130,9373 Btu/hr
b. LMTD
Fluida Panas
Temperatur Fluida Dingin (°F) Selisih (°F)
(°F)
100,76 Temperatur Tinggi 83,84 16,92
96,8 Temperatur Rendah 77,36 19,44
3,96 Beda Temperatur 6,48 - 2,52
( T 1 - t 2) - ( T2 - t 1 )
LMTD =
ln
[ ] T 1 - t2
T 2 - t1
Ret =D (Gtμ )
D Gt
Ret =
μ
0,0 026 ( 1.430.065,78 )
= 1,91
= 3.718,17
L 8,66
= = 206,19
D 0,042
Dari Appendix Fig. 24 Buku Kern diperoleh
jH = 3,8
Pada Tc = 98,78°F,
Dari lampiran Fig. 2 Kern, halaman 804 dan tabel Kern, halaman 800
diperoleh :
Btu
Cp = 1,0
lb °F
Btu
k = 0,364 °F
hr ft2
ft
( ) ( )
1 1
cp μ 3 1,0 × 1,91 3
=
k 0,364
= 1,76
( )
1
k cμ
hi/∅ t = jH 3
×1
D k
( ) x1
1
0,364 1 ,0 × 1,91
= 3,8 × 3
0,0026 0,36
= 936,32
h i ID
hio / ∅ t = ×
∅ t OD
0,031
= 936,32 ×
0,042
= 691,093 BTU/hr ft2 ° F
Tube Wall Correction
ho
∅s
tw = tc +
hi o ho
( Tc - t c )
+
∅t ∅s
872/1
= 8 0,6 ℉ + ( 98,78 - 80,6 ℉ )
691,093/1 + 872/1
=90,74 ℉
Pada tw 90,74˚F, maka diperoleh μw = 0,8 centipoise
μw = 0,8 × 2,42
lb
= 1,93
ft.hr
( )
0,14
μ
∅t =
μw
1,91 0,14
=( )
1,93
= 0,99
hi = jH ( )[ k
(
D k
Cp μ 13
]
) ∅t
= 3,8 (
0,0026 )
0,364
[1,76] 0,99
0,031
= 926,95 × 0,042
0,00716
=9
= 0,000796 ft2
4 × P T ² - πd0/4
De =
π d0
4 × (0,75)² - 3,14 × 0,5/4
=
3,14 × 0,5
2,25 - 0,3925
= 1,57
1,8575
=
1,57
= 1,18 In
= 0,098 ft
Mass Velocity
W
Gs =
as
946,1323 lb m /hr
= 2
0,000796 ft
lb
= 1.188.608,41 2
ft × hr
Velocity Through Shell
Gs
V =
3600 × ρ
1.188.608,41
= (A-2.11
3600 × 62,197
Geankoplis)
= 5,30 ft/s
Pada tc = 80,6°F
Dari Appendix Fig. 14 (Kern, 1965) diperoleh:
Diperoleh μ = 0,9 centipoises
Maka,
μ = 0,9 × 2,42
lb
= 2,17
ft.hr
De Gs
Res =
μ
0,0 98 ft (1.188.608,41 lb)
=
2,1 7 lb ft hr
= 53.679,08
L 2,30
= = 23,47
D 0,0 98
Dari Appendix Fig.24 (Kern, 1965) diperoleh:
JH = 120
Pada tc = 80,6°F,
Btu
Cp = 1,0 ,
lb °F
Btu
k = 0,355 2 °F
hr ft
ft
( ) (
1
)
1
cp μ 3 1,0 × 2,1 7 3
=
k 0,3 55
= 2,03
( ) ×1
1
k cμ
ho / ∅ s = jH 3
D k
0,0 98 ( 0,36 )
1
0,3 5 1,01 × 2,1 7 3
= 120 ×
Btu
= 870
hr ft2 ℉
( )
0,14
μ
∅s =
μw
( )
0,14
2,17
=
1,93
= 1,01
ho = jH ( )[
k
(
D k
Cp μ 13
]
) ∅s
= 140 (
0,098 )
0,363
[2,03] 1,01
Btu
= 33,7
hr ft2 ℉
h. Dirt Factor Rd
Fluida Panas di Tube
U C - Ud 416,29 - 23,7
Rd = = = 0,039 Btu/hr.ft2.°F
U C . Ud ( 416,29 ) ( 23,7 )
Fluida Dingin di Shell
U C - Ud 416,29 - 33,7
Rd = = = 0,27 Btu/hr.ft2.°F
U C . Ud ( 416,29 ) ( 33,7 )
i. Koefisien Overall Perpindahan Panas (U)
Stainless Steels AISI 302,
k = 15,1 W/m. K = 9,02 BTU/hr.ft2.°F (Cengel, Appx.1 Tabel A-3 Hal 844)
Wall Thickness (x)
x = 0,065 In = 0,00542 ft
1
U= 1
hi
+
x
k
+
1
()
ho
1
U= 1
926,95
+
9,02 (
0,00542
+
1
)
1. 063,227
1
U= = 381,64 Btu/hr.ft2.°F
0,002566
Koefisien Perpindahan Panas Pada Fluida Panas di Tube
ID = 0,370 In = 0,031 ft
ID 0,031
ri = = = 0,0155 ft
2 2
OD = 0,5 In = 0,042 ft
OD 0,042
ro = = = 0,021 ft
2 2
1
Ui = 1 ri ro ri 1
+ ln ( )+ ( )( )
hi k ri ro ho
1
Ui = 1 0,0155 0,021 0,0155 1
+ ln ( )+( )( )
926,95 9,02 0,0155 0,021 1.063,227
Ui = 435,75 Btu/hr.ft2.°F
Koefisien Perpindahan Panas Pada Fluida Dingin di Shell
ID = 0,620 In = 0,052 ft
ID 0,052
ri = = = 0,26ft
2 2
OD = 7,09 In = 0,59 ft
OD 0,59
ro = = = 0,295 ft
2 2
1
Uo = 1 ro ro ro 1
+ ln ( )+ ( )( )
ho k ri ri ho
1
Uo = 1 0,295 0,295 0,295 1
+ ln ( )+( )( )
1.063,227 9,02 0,26 0,26 1.063,227
Uo = 162,91 Btu/hr.ft2.°F