Anda di halaman 1dari 9

ANALISA LISTRIK

Nama - Projek (Kode - Projek)


Analisa Stop Kontak AC
Nama - Projek (Kode Projek)

Ukuran
W

Daya
AC

Jumlah AC per ruangan


1 HP

Total Arus
per AC

MCB
per AC

(m)

(m)

(BTU/h/m )
7000

(HP)

(buah)

(A)

(A)

Laboratorium

3,5

4,24

NYM

3x2,5mm2

General Check Room

500

14000

4,24

NYM

3x2,5mm2

Dentist Room

3,5

500

7000

4,24

NYM

3x2,5mm2

Radio Operator Room

500

8000

4,24

NYM

3x2,5mm2

Immunization Room

3,5

500

7000

4,24

NYM

3x2,5mm2

Nutrition Room

3,5

500

7000

4,24

NYM

3x2,5mm2

Mother & Child Room

3,5

500

7000

4,24

NYM

3x2,5mm2

Pharmacy Storage

3,5

500

7000

4,24

NYM

3x2,5mm2

Pharmacy

3,5

500

7000

4,24

NYM

3x2,5mm2

10

Card Room

500

8000

4,24

NYM

3x2,5mm2

Administration Office

3,5

500

7000

4,24

NYM

3x2,5mm2

12

Director

3,5

500

7000

4,24

NYM

3x2,5mm2

13

Integrated Management

3,5

500

7000

4,24

NYM

3x2,5mm2

14

Hygen Sanitation Room

500

8000

4,24

NYM

3x2,5mm2

School Health Program

3,5

500

7000

4,24

NYM

3x2,5mm2

Mental & Health Room

500

8000

4,24

NYM

3x2,5mm2

20

Storage

3,5

500

7000

4,24

NYM

3x2,5mm2

22

Prayer Room

500

6000

4,24

NYM

3x2,5mm2

Delivery Room

500

14000

4,24

NYM

3x2,5mm2

UGD

500

14000

4,24

NYM

3x2,5mm2

Meeting Room

500

16000

4,24

NYM

3x2,5mm2

Inpatient Room

7,5

500

15000

4,24

NYM

3x2,5mm2

No

Group

1
2

6
7

11

15
16

17

SDP1

SDP2

SDP3

SDP4

SDP5

18
19
21

SDP6

Nama Ruang

Hari
BTU

(m) (BTU/h/m3)
3
500

Total BTU
3

Jenis
Kabel

Ukuran
Kabel
per AC

Analisa Beban Penerangan


1

Nama - Projek (Kode Projek)

LAMPU
No Group

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
36
37

Laboratorium
SDP2

SDP1

MDP

SDP3

SDP4

SDP5

TL
1x40
(W)

Tipe Beban

Stop

Motor

TL
TL P-SL P-SL Spot Mercury Kontak Pump
2x40 1x20
18
9
100
250
150
250
(W) (W) (W)
(W)
(W)
(W)
(W)
(W)

Spare
per
phase
704
(W)
690

Daya
Arus
MCB Nama
Ukuran
beban
beban
Rating kabel
kabel
(W)
(A)
(A)
3,92

NYA

3x2,5mm2

General Check Room

10

950

5,40

NYA

3x2,5mm2

Dentist Room
Radio Operator Room
Immunization Room
Nutrition Room
Mother & Child Room

6
6

3
3

570
570

3,24
3,24

6
4

NYA
NYA

3x2,5mm2
3x2,5mm2

2
2

380
380

2,16
2,16

NYA

2
2

27
420
420

0,15
2,39
2,39

NYA

500

2,84

530
380
380
54
90
54
72
588
54
120
300
18
40
54

3,01
2,16
2,16
0,31
0,51
0,31
0,41
3,34
0,31
0,68
1,70
0,10
0,23
0,31

NYA

3x2,5mm2

NYA

2x2,5mm2

NYA

2x2,5mm2

474

2,69

2,16
2,39
0,51
0,31
0,41
1,08

NYA

3x2,5mm2

NYA

2x2,5mm2

380
420
90
54
72
190

5
5

1008
1039

5,73
5,90

6
6

2
4
4

Toilet A
Pharmacy Storage
Pharmacy

420

2,39

3
6
6

Mercury Lamp
Card Room
Administration Office
Director
Integrated Management
Coridoor d
Coridoor E
Coridoor i
Verandah (h)
Front Side Verandah (A, B)
Verandah (e)
Lobby
Spot Light (E2,f)
Gazebo
Name Plate Light
Front Side Car Port

2
3

6
4
4
4

570
3
2
2

6
3
1
2
3

Cafe
Hygen Sanitation Room
School Health Program
Mental & Health Room
Coridoor j
Coridoor K
Verandah (K)
Storage

Delivery Room
UGD

6
7

2
4
6

380
2
2

5
3
4
2
1

2x2,5mm2
3x2,5mm2

NYY

2x4mm2

3,24

3
5
3
4
6
3

3x2,5mm2

NYA

3x2,5mm2

2,16

NYA
NYA

3x2,5mm2
3x2,5mm2
2

38
39
40

Spot Light (j2)


Spot Light Right Side (j3,g)
Verandah (N)

41

Meeting Room

42
43
44
45
46
47
48

Inpatient Room
Spotlight (M1)
Verandah (P)
Prayer Verandah(Q)
Coridoor L
Coridoor M
Toilet B

SDP6

49

Prayer Room (Light)+Wudhu

50

Motor Pump

51
52

MDP

Mercury Lamp

2
4

200
400
126

1,14
2,27
0,72

770

4,38

NYA

3x2,5mm2

910
100
90
90
54
72
27

5,17
0,57
0,51
0,51
0,31
0,41
0,15

NYA

3x2,5mm2

400

2,27

250

1,42

500

2,84

704

4,00

7
8
8
1
5
5
3
4
3
2

2
1
2

spare per phase

NYA
2x2,5mm2

NYA

2x2,5mm2

3x2,5mm2
NYY

3x2,5mm2

NYY

2x4mm2

NYA

3x2,5mm2

Analisa Kebutuhan Lampu Penerangan


Nama - Projek (Kode Projek)
3

No

Tipe Ruangan

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25

Laboratorium
General Check Room
Dentist Room
Radio Operator Room
Immunization Room
Nutrition Room
Mother & Child Room
Pharmacy Storage
Pharmacy
Card Room
Administration Office
Director
Integrated Management
Hygen Sanitation Room
School Health Program
Mental & Health Room
Delivery Room
UGD
Meeting Room
Storage
Inpatient Room
Prayer Room
Per Toilet
Corridor
Verandah

Ukuran
L
(m)
4
7
4
4
4
4
4
4
4
4
4
4
4
4
4
4
7
7
8
4
7,5
4
1,8
32,4
44,52

W
(m)
3,5
4
3,5
4
3,5
3,5
3,5
3,5
3,5
4
3,5
3,5
3,5
4
3,5
4
4
4
4
3,5
4
3
1,1
1,98
1,98

H
(m)
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3

Iluminasi

Faktor rugi

koefesien

(lux)

cahaya
(LLF)
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8

Utilitas
(CU)
0,6
0,6
0,6
0,6
0,6
0,6
0,6
0,6
0,6
0,6
0,6
0,6
0,6
0,6
0,6
0,6
0,6
0,6
0,6
0,6
0,6
0,6
0,6
0,6
0,6

500
250
300
250
300
250
300
300
300
250
250
350
250
250
250
250
250
300
300
150
200
200
150
60
50

Kuat
penerangan
lampu
(lumen)
3000
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
3000
3000
3000
3000
1500
3000
400
850
850

Banyak Lampu
Perhitungan
4,86
9,72
5,83
5,56
5,83
4,86
5,83
5,83
5,83
5,56
4,86
6,81
4,86
5,56
4,86
5,56
4,86
5,83
6,67
1,46
8,33
1,67
1,55
9,43
10,80

N
40 W
6

N
20 W

N
9W

N
18W

10
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
7
8
1
8
2
1
9
10

Analisa Rating MCB Utama dan Kapasitas Genset


Nama - Projek (Kode Projek)
4

AC

No

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42

Group

SDP2

SDP1

MDP

SDP3

SDP4

SDP5

SDP6

Tipe Beban

Laboratorium
General Check Room
Dentist Room
Radio Operator Room
Immunization Room
Nutrition Room
Mother & Child Room
Toilet A
Pharmacy Storage
Pharmacy
Mercury Lamp
Card Room
Administration Office
Director
Integrated Management
Coridoor d
Coridoor E
Coridoor i
Verandah (h)
Front Side Verandah (A, B)
Verandah (e)
Lobby
Spot Light (E2,f)
Gazebo
Name Plate Light
Front Side Car Port
Cafe
Hygen Sanitation Room
School Health Program
Mental & Health Room
Coridoor j
Coridoor K
Verandah (K)
Storage
Prayer Room (AC)
Delivery Room
UGD
Spot Light (j2)
Spot Light Right Side (j3,g)
Verandah (N)
Meeting Room
Inpatient Room

LAMPU
Stop
Motor
Spare
Total
TL
TL
TL P-SL P-SL Spot Mercury Kontak Pompa per phase Beban
Beban
Semua
1 1x40 2x40 1x20 18
9 100
250
150
250
704
AC penerangan beban
R
S
( HP) (W) (W) (W) (W) (W) (W)
(W)
(W)
(W)
(W)
(W)
(W)
(W)
(W)
(W)
1
6
3
746
690
1436
3
10
5
2238
950
3188
1
6
3
746
570
1316
2
6
3
1492
570
2062
1
6
2
746
420
1166 14279
1
4
2
746
380
1126
1
4
2
746
380
1126
3
0
27
27
1
6
2
746
420
1166
1
6
2
746
420
1166
2
0
500
500
2
6
3
1492
570
2062
1
4
3
746
530
1276
1
4
2
746
380
1126
1
4
2
746
380
1126
3
0
54
54
5
0
90
90
3
0
54
54
4
0
72
72
6
6
0
588
588
3
0
54
54
6

0
0
0
0
0
0

3
1
2
3
3

6
2

4
1
2

2
4
6

1492
2
2

5
3
4
1
1
3

6
3

2238
5

2
4
7
3
3

8
8

3
5

380

120
300
18
40
54
474

120
300
18
40
54
474

380
420
90
54
72
190
0

1126
1912
90
54
72
936
746

1039
200
400
126
770
910

3277
200
400
126
3008
3148

Beban @ Phase
T
(W)

14316

1872

746
1492
0
0
0
746
746
1008
3246
2238
0
0
0
2238
2238

43
44
45
46
47
48
49
50
51
52

MDP

Spotlight (M1)
Verandah (P)
Prayer Verandah(Q)
Coridoor L
Coridoor M
Toilet B
Prayer Room (Light)+Wudhu
Motor Pump
Mercury Lamp
spare per phase

1
5
5
3
4
3
2

2
1
2
1
Daya (W)
DAya (VA)
Arus (A)

0
0
0
0
0
0
0
0
0
0
26856
33570
152,59

100
90
90
54
72
27
400
250
500
704
16727
20908,75
95,04

100
90
90
54
72
27
400
250
500
704
43583
54479
247,63

14988

14279
17849
81,13

14316
17895
81,34

14988
18735
85,16

Total kapasitas MCB 3- yang diusulkan pada PLN: [(81,13+81,34+85,16)/3] x 0,8 = 66,03 A , dipilih : 60 A atau 39,5 kVA
Total Arus AC = 152,59 A, @ per phase = 50, 86 A
Total Arus Penerangan = 95,04 A, @ per phase = 31, 68 A
Kapasitas Genset 3- dipilih = 26 kVA atau 39,5 A, Dengan rating MCB 3- = 30 A

1. Kotak Kontak merupakan kelompok beban yang tidak tetap sehingga dalam perencanaan dapat ditentukan kapasitas MCB untuk kelompok beban yang memiliki kotak kontak menjadi lebih kecil atua besar dari

nilai perhitungan arus yang sebenarnya.

2. Kabel Penghantar NYA


-

Kabel NYA berinti tunggal :

Merah untuk kabel fasa, tersambung ke fasa MCB

Hitam/biru untuk kabel netral, tersambung ke netral


Hijau/kuning untuk kabel pentanahan, tersambung ke grounding peralatan
-

Kabel NYA 3 x 2,5 mm2 :

terdiri dari 3 inti kabel, masing masing: merah, hitam/biru, hijau/kuning dengan luas
penampang nominal 2,5 mm2.

Berdasarkan Tabel 7.3-1 Peraturan Umum Intalasi Listrik (PUIL) 2000 Indonesia: Kemampuan Hantar Arus (KHA) Kabel NYA dengan luas penampang nominal 2,5 mm2 dalam pipa PVC adalah 20 A.

3. Kabel NYM
-

Merah untuk kabel fasa, tersambung ke fasa MCB

Kabel NYM berinti banyak :

Hitam/biru untuk kabel netral, tersambung ke netral


Hijau/kuning untuk kabel pentanahan, tersambung ke grounding peralatan

Kabel NYM 3 x 2,5 mm2 :

terdiri dari 3 inti kabel, masing masing: merah, hitam/biru, hijau/kuning dengan luas penampang
nominal 2,5 mm.

Berdasarkan Tabel 7.3-4 Peraturan Umum Intalasi Listrik (PUIL) 2000 Indonesia: Kemampuan Hantar Arus (KHA) Kabel NYM dengan luas penampang nominal 2,5 mm2 adalah 26 A.

4. Kabel Penghantar NYY


-

Merah untuk kabel fasa, tersambung ke fasa MCB

Kabel NYY berinti tunggal :

Hitam/biru untuk kabel netral, tersambung ke netral


Hijau/kuning untuk kabel pentanahan, tersambung ke grounding peralatan
-

Kabel NYY 2 x 2,5 mm2

Kabel NYY 2 x 4 mm2

:
:

terdiri dari 2 inti kabel, masing masing: merah, hitam/biru dengan luas penampang nominal 2,5 mm2.
terdiri dari 2 inti kabel, masing masing: merah, hitam/biru dengan luas
penampang nominal 4 mm2.

Kabel NYY 3 x 2,5 mm2 :

terdiri dari 3 inti kabel, masing masing: merah, hitam/biru, hijau/kuning dengan luas
7

penampang nominal 2,5 mm2.


-

Berdasarkan Tabel 7.3-5a Peraturan Umum Intalasi Listrik (PUIL) 2000 Indonesia: Kemampuan Hantar Arus (KHA) Kabel NYY berinti 2 dengan luas penampang nominal 2,5 mm2 dalam pipa dan tanah
adalah

41 A.

Berdasarkan Tabel 7.3-5a Peraturan Umum Intalasi Listrik (PUIL) 2000 Indonesia: Kemampuan Hantar Arus (KHA) Kabel NYY berinti 2 dengan luas penampang nominal 4 mm2 dalam pipa dan tanah
adalah 54 A.

Berdasarkan Tabel 7.3-5a Peraturan Umum Intalasi Listrik (PUIL) 2000 Indonesia: Kemampuan Hantar Arus (KHA) Kabel NYY berinti 3 dengan luas penampang nominal 2,5 mm2 dalam pipa dan tanah
adalah

34 A.

Berdasarkan pasal 7.15.1.2 Peraturan Umum Intalasi Listrik (PUIL) 2000 Indonesia: penananaman kabel tanah dilakukan pada: minimum 0,6 m dibawah permukaan tanah yang tidak dilewati kenderaan dan
minimum 0,8 m dibawah permukaan tanah yang dilewati kenderaan.

5. Air Conditioner (AC)


Berdasarkan Standar Nasional Indonesia (SNI) bahwa untuk mencapai suhu kamar (251) oC pada siang hari diperlukan kalor sebanyak 500 BTU/h/m3, sedangkan pada malam hari diperlukan kalor 350
BTU/h/m3, dalam perhitungan jumlah kalor yang diperlukan suatu ruangan mencapai 5000 BTU/h/m3 untuk ketinggian 3 m diasumsikan sama dengan 1 HP.

6. Elektroda pentanahan
-

Elektroda tembaga batang pentanahan peralatan instalasi listrik berdiameter ditanam pada kedalam tanah antara 0.5 m sampai 10 m.

Elektroda dapat ditanam pada jarak kedalaman kurang dari 10 meter bila kondisi resistansi pembumian telah mencapai 5 Ohm.

Berdasarkan pasal 3.19.1.4 Peraturan Umum Intalasi Listrik (PUIL) 2000 Indonesia: Elektroda batang dimasukkan tegak lurus kedalam tanah dan panjangnya disesuaikan dengan resistansi pembumian yang
diperlukan. Jika beberapa elektroda diperlukan untuk memperoleh resistansi pembumian yang rendah maka jarak antara elektroda tersebut minimum harus dua kali panjangnya.

7. Elektroda penangkal petir


-

Standar Panjang batang elektroda yang digunakan 10 inc sampai dengan 24 inc

Elektroda tembaga penangkal petir dipasang tegak lurus pada puncak gedung.

Menurut Standar SNI No: 03- 3990-1995, pemasangan elektroda penangkal petir pada bangunan disesuaikan dengan panjang dan bentuk bangunan serta beda tinggi antara bubungan atap dengan lisplang.

Elektroda dapat ditanam pada jarak kedalaman kurang dari 10 meter bila kondisi resistansi pembumian telah mencapai 2 Ohm.