STANDARDISASI TELE INFORMASI DATA SOGI

GARDU INDUK 500 KV

OPS

OHL FEEDER

IBT 500(275)/150 SIS

IBT 500(275)/150 SIS

REACTOR

DIAMETER

GEN TRANSF

GENERATOR

BLOK

10

11

12

13

BLOK

BUS SECTION

GENERATOR

BUS COUPLER

GEN TRANSF

13

DIAMETER

12

REACTOR

11

IBT 500(275)/150 SIS

10

IBT 500(275)/150 SIS

OHL FEEDER

BUS SECTION

BUS COUPLER

BUSBAR

GARDU INDUK

REMOTE STATION (S

BUSBAR

PEMELIHARAAN

GARDU INDUK

OPERASI
1

REMOTE STATION

COMMON

PER PHASA

JUMLAH
PER PEMBANGKIT

PER GI

PER BAY

BAGIAN
PER PERALATAN

LN IEC61850

SUMBER
SIGNAL

HARDWIRING

IED PROTEKSI

IED AVR

IED BCU

DESIGNATION

LOCAL HMI

MNEMO

NO

TIPE INFORMASI

TIPE

TAMPILAN

KETERANGAN PEMBAHASAN

KETERANGAN

HAR
PROTOKOL KOMUNIKASI
101
104
61850
DNP

1
2
3
4

IEC 870-5-101
IEC 870-5-104
IEC 61850
DNP3

1
1
1
1
4

TOTAL

TAP CHANGER ( TC )
5

TPI

TPI

TC

TAP POSITION INDICATION

TC

1
1

TOTAL

TELE MEASUREMENT ( TM )
F

FREKUENSI

TM

TEGANGAN

TM

ARUS

TM

DAYA AKTIF

TM

10 Q

DAYA REAKTIF

TM

11 PF

PF

POWER FACTOR

TM

MAX POWER VARIATION SETTING

TM

14

VAC

TEGANGAN AC DB

TM

15

VDC

TEGANGAN DC RECTIFIER

TM

16

PRES

PRESSURE SF6

TM

17

CCB

COUNTER OF CIRCUIT BREAKER

TM

18

CNTA

COUNTER LIGHTNING ARRESTER

TM

19

COLTC

COUNTER OLTC OPERATION

TM

20

KWH

KILOWATT HOUR (EXPORT & IMPORT)

TM

21

KVARH

KILOVAR HOUR (EXPORT & IMPORT)

TM

22

WTHV

HV WINDING TEMPERATURE

TM

23

WTLV

LV WINDING TEMPERATURE

TM

24

WTTV

TV WINDING TEMPERATURE

TM

25

OT

OIL TEMPERATURE

TM

26

RT

ROOM TEMPERATURE

TM

27

RH

RELATIVE HUMIDITY

TM

28

AMF

AMPERES FAULT ( PER PHASE )

TM

29

DTF

DISTANCE TO FAULT

TM

TOTAL

TM

REAL POWER SETTING

13 PRAQ

3
3

3
3

SPLN Spek SOGI, diperbaiki AVR agar menggunakan 4-20 mA

TM

12 POAQ

1
1

2
1

Setiap line ada frekuensi untuk keperluan sinkro setelah island


3
3

Fasa RST

Daya 3 fasa / (untuk Gen Trafo = ekspor dan impor)

Daya 3 fasa / (untuk Gen Trafo = ekspor dan impor)

1
1
4

TAMBAHAN

GITET Konvensional (non GIS)

OHL 3/set, Trafo 1/set

TAMBAHAN (untuk GIS akan dihitung jumlahnya)

TAMBAHAN

Dari satu buah IED Energy Meter dgn 2 address Export & Import

TAMBAHAN

Dari satu buah IED Energy Meter dgn 2 address Export & Import

TAMBAHAN

from AVR

3
3
3
1
1

1
14

1
23

1
19

1
5

27

17

Dari BPU dan tampilan akan muncul apabila diminta (soft button)

di verifikasi untuk pengambilan datanya

Dari MPU dan tampilan akan muncul apabila diminta (soft button)

di verifikasi untuk pengambilan datanya

1 of 5

STANDARDISASI TELE INFORMASI DATA SOGI


GARDU INDUK 500 KV

OPS

OHL FEEDER

IBT 500(275)/150 SIS

IBT 500(275)/150 SIS

REACTOR

DIAMETER

GEN TRANSF

GENERATOR

BLOK

10

11

12

13

BLOK

BUS SECTION

GENERATOR

BUS COUPLER

GEN TRANSF

13

DIAMETER

12

REACTOR

11

IBT 500(275)/150 SIS

10

IBT 500(275)/150 SIS

OHL FEEDER

BUS SECTION

BUS COUPLER

BUSBAR

GARDU INDUK

REMOTE STATION (S

BUSBAR

PEMELIHARAAN

GARDU INDUK

OPERASI
1

REMOTE STATION

COMMON

PER PHASA

JUMLAH
PER PEMBANGKIT

PER GI

PER BAY

BAGIAN
PER PERALATAN

LN IEC61850

SUMBER
SIGNAL

HARDWIRING

IED PROTEKSI

IED AVR

IED BCU

DESIGNATION

LOCAL HMI

MNEMO

NO

TIPE INFORMASI

TIPE

TAMPILAN

KETERANGAN

KETERANGAN PEMBAHASAN

HAR
REMOTE CONTROL DIGITAL ( RCD )

30

DCB

DUMMY CIRCUIT BREAKER CLOSED/OPENED

31 CB

CB

CIRCUIT BREAKER CLOSED/OPENED

32

ARO

AUTO RECLOSE ON/OFF

33

BI

BUS ISOLATOR SWITCH CLOSED/OPENED

34

DI

DIAMETER ISOLATOR SWITCH CLOSED/OPENED

35

LI

LINE ISOLATOR SWITCH CLOSED/OPENED

36 AVRAM

AVRAM

AVR AUTO/MANUAL

37 TC

TC

TAP CHANGER RAISE/LOWER

38 CSO

CSO

CHECK SYNCHRONIZING OVERRIDE

39

RPB

RESET PER BAY

40 LFR

LOAD FREQ REQUEST ON/OFF

41 CAM

CAPACITOR AUTO/MANUAL
TOTAL

RCD

RCD

RCD
RCD
RCD

RCD

DCB

DUMMY CIRCUIT BREAKER CLOSED/OPENED

CB

CIRCUIT BREAKER CLOSED/OPENED

47 ARO

ARO

AUTO RECLOSE ON/OFF

48 LBS

LBS

LOAD BREAK SWITCH CLOSED/OPENED

49 BI

BI

BUS ISOLATOR SWITCH CLOSED/OPENED

50 DI

DI

DIAMETER ISOLATOR SWITCH CLOSED/OPENED

51 LI

LI

LINE ISOLATOR SWITCH CLOSED/OPENED

52 ES

ES

EARTH SWITCH CLOSED/OPENED

53 RACK

RACK

CIRCUIT BREAKER RACKIN/RACKOUT

54

TFAM

TRANSFORMER FAN AUTO/MANUAL

55 AVRAM

AVRAM

AVR AUTO/MANUAL

56 CSO

CSO

CHECK SYNCHRONIZING OVERRIDE

57 LFR

LFR

LOAD FREQ REQUEST ON/OFF

58 LFC

LFC

LOAD FREQ CONTROL ON/OFF SWITCH

59 LFA

LFA
PSO

POWER STATION OPERATED

61 GUC

GUC

GENERATOR UNIT RUN/STOP

62 CAM

CAM

CAPASITOR AUTO/MANUAL

63 LRHMI

LRHMI

LOCAL/REMOTE FOR LOCAL HMI

64 LRBCU

LRBCU

LOCAL/REMOTE FOR BCU

65

LRCB

LOCAL/REMOTE FOR CIRCUIT BREAKER

66

LRBI

LOCAL/REMOTE FOR BUS ISOLATOR

67

LRDI

LOCAL/REMOTE FOR DIAMETER ISOLATOR

68

LRLI

LOCAL/REMOTE FOR LINE ISOLATOR

69

LRA

LOCAL/REMOTE SWITCH FOR AVR

70

LRO

LOCAL/REMOTE SWITCH FOR OLTC

71 SIB

SIB

SOFTWARE INTERLOCKING BY PASSED

72 GRM

GRM

GENSET READY/MAINTENANCE
TOTAL

1
1

ON/OFF saja. Untuk IED Proteksi dilakukan melalui keypad menu

1
6
1

1
1
1
3

1
1
1
3

12

1 Tidak ada command di HMI lokal

RCA
RCA
RCA
RCA

LOAD FREQ AVAILABLE/NOT AVAILABLE

60 PSO

RCD

TELESIGNAL DOUBLE ( TSD )


45

RCD
RCD

REAL POWER SET POINT


MAX POWER VARIATION SET POINT
LOAD FREQ CONTROL N_LEVEL
TOTAL

46 CB

RCD

RCD

REMOTE CONTROL ANALOG ( RCA )


42 POOP
43 PROP
44 N

RCD

TSD
TSD
TSD
TSD
TSD
TSD
TSD
TSD
TSD
TSD
TSD
TSD
TSD
TSD
TSD
TSD
TSD
TSD
TSD
TSD
TSD
TSD
TSD
TSD
TSD
TSD
TSD
TSD
TSD

1
1

2
6

1
2

3
1

1
8

8 ES untuk aplikasi diameter GIS

3
1

Pembangkit running

1
1

1
1

Bagaimana informasi data ke control center

2
6
1

36

LINE=bay line/bay trafo/bay reaktor/bay capasitor

Tidak ada command dilocal HMI


Tidak ada command dilocal HMI
Tidak ada command dilocal HMI

1
1
4

1
2

12

1
1

11

3
3

TELESIGNAL SINGLE (TSS)


73 SLF

STATION LEVEL FAULTY

SRVF

SERVER FAILURE

TSS

WSF

WORKSTATION FAILURE

TSS

76

GATF

GATEWAY FAILURE

77

ESF

ETHERNET SWITCH FAILURE

TSS

78

GPSF

GPS FAILURE

TSS

79 IEDF
80

IED BAY LEVEL FAULTY


BCUF

TSS

IED BCU FAULTY

TSS

81

MPUF

IED MPU FAULTY

TSS

BPUF

IED BPU FAULTY

TSS

AVRF

IED AVR FAULTY

TSS

84

IEDCF

IED COMMON IO FAULTY

TSS

85

IEMF

IED ENERGY METER FAULTY

TSS

86

DFRF

DISTURBANCE FAULT RECORDER FAULTY

TSS

87 COM

COMMUNICATION FAULTY

TSS

88

CF

CARRIER FAULTY

TSS

89

FOTF

FO TERMINAL (PDH/SDH) FAULTY

TSS

90

PLCF

PLC TERMINAL FAULTY

TSS

91

RADF

RADIO LINK FAULTY

TSS

92

PBXF

PABX FAULTY

TSS

93 BUAL

BUILDING ALARM

94

DOOR

DOOR ACTIVATED

TSS

SIA

STATION INTRUDER ALARM

TSS

96

BFADF

BUILDING FIRE ALARM DEVICE FAILURE

TSS

97

BFAA

BUILDING FIRE ALARM ACTIVATED

TSS

98

GRUN

GENSET RUNNING

TSS

99

RTH

ROOM TEMPERATURE HIGH

TSS

100

OVP

OVER VOLTAGE PROTECTION

TSS

TSS

95

TSS

82
83

TSS

74
75

Bagaimana informasi data ke control center


1

Bagaimana informasi data ke control center

Bagaimana informasi data ke control center

1
1
1

3
2

2
1

1
1
1

1
1
1
1
1

1
1
1
1
1
1
1

2 of 5

STANDARDISASI TELE INFORMASI DATA SOGI


GARDU INDUK 500 KV

OPS

OHL FEEDER

IBT 500(275)/150 SIS

IBT 500(275)/150 SIS

REACTOR

DIAMETER

GEN TRANSF

GENERATOR

BLOK

10

11

12

13

BLOK

BUS SECTION

GENERATOR

BUS COUPLER

GEN TRANSF

13

DIAMETER

12

REACTOR

11

IBT 500(275)/150 SIS

10

IBT 500(275)/150 SIS

OHL FEEDER

BUS SECTION

BUS COUPLER

BUSBAR

GARDU INDUK

REMOTE STATION (S

BUSBAR

PEMELIHARAAN

GARDU INDUK

OPERASI
1

REMOTE STATION

COMMON

PER PHASA

JUMLAH
PER PEMBANGKIT

PER GI

PER BAY

BAGIAN
PER PERALATAN

LN IEC61850

SUMBER
SIGNAL

HARDWIRING

IED PROTEKSI

IED AVR

IED BCU

DESIGNATION

LOCAL HMI

MNEMO

NO

TIPE INFORMASI

TIPE

TAMPILAN

KETERANGAN PEMBAHASAN

KETERANGAN

HAR

101 VACF

VAC FAILURE

220F

220 VAC FAILURE

TSS

380F

380 VAC FAILURE

TSS

104 VDCF

VDC FAILURE

105

110RF

110VDC RECTIFIER FAILURE

110DF

110VDC DB FAILURE

TSS

107

24RF

24VDC RECTIFIER FAILURE

TSS

108

24DF

24VDC DB FAILURE

TSS

109

48RF

48VDC RECTIFIER FAILURE

TSS

110

48DF

48VDC DB FAILURE

TSS

111

INVF

INVERTER FAILURE (110VDC/220VAC)

TSS

SUPPLY FAILURE

TSS

106

112 SF

TSS

102
103

TSS

TSS

113

MSF

114

PSF

PROTECTION SUPPLY FAILURE

TSS

115

CSF

CONTROL SUPPLY FAILURE

TSS

116

DCG

DC GROUND

TSS

TSS

MOTOR SUPPLY FAILURE

TSS

117 DISZ1

DISZ1

DISTANCE PROTECTION ZONE 1

118 DISZ2

DISZ2

DISTANCE PROTECTION ZONE 2

119 DISZ3

DISZ3

DISTANCE PROTECTION ZONE 3

120 DISZ4

DISZ4

DISTANCE PROTECTION ZONE 4

121

SOTF

SWITCH ON TO FAULT

122 DEF

DEF

DIRECTIONAL EARTH FAULT

123 LCD

LCD

LINE CURRENT DIFFERENTIAL

124

PCF

PROTECTION COMMUNICATION FAILURE

TSS

125

OCPA

OIL CABLE PRESSURE ALARM

TSS

126

OCPT

OIL CABLE PRESSURE TRIP

127 AR

AR

CIRCUIT BREAKER AUTO RECLOSE SUCCESS

TSS

TSS

TSS

TSS

128 ARL

ARL

CIRCUIT BREAKER AUTO RECLOSE LOCK OUT

129 CSP

CSP

CHECK SYNCHRONIZING IN PROGRESS

TSS

TSS
TSS
TSS

TSS

TSS

1
1

Khusus untuk migrasi RTU ke SOGI


Khusus untuk migrasi RTU ke SOGI
Khusus untuk migrasi RTU ke SOGI

Khusus untuk migrasi RTU ke SOGI


TAMBAHAN

Untuk suplai motor PMT

Untuk suplai proteksi

Untuk suplai kontrol

Positif dan Negatif Ground


6
6

1
1

1
1

3 of 5

STANDARDISASI TELE INFORMASI DATA SOGI


GARDU INDUK 500 KV

OPS

OHL FEEDER

IBT 500(275)/150 SIS

IBT 500(275)/150 SIS

REACTOR

DIAMETER

GEN TRANSF

GENERATOR

BLOK

10

11

12

13

BLOK

BUS SECTION

GENERATOR

BUS COUPLER

GEN TRANSF

13

DIAMETER

12

REACTOR

11

IBT 500(275)/150 SIS

10

IBT 500(275)/150 SIS

OHL FEEDER

BUS SECTION

BUS COUPLER

BUSBAR

GARDU INDUK

REMOTE STATION (S

BUSBAR

PEMELIHARAAN

GARDU INDUK

OPERASI
1

REMOTE STATION

COMMON

PER PHASA

JUMLAH
PER PEMBANGKIT

PER GI

PER BAY

BAGIAN
PER PERALATAN

LN IEC61850

SUMBER
SIGNAL

HARDWIRING

IED PROTEKSI

IED AVR

IED BCU

DESIGNATION

LOCAL HMI

MNEMO

NO

TIPE INFORMASI

TIPE

TAMPILAN

KETERANGAN

KETERANGAN PEMBAHASAN

HAR

130 TEA

TEMPERATURE ALARM

131

WTHVA

HV WINDING TEMPERATURE ALARM

132

WTLVA

LV WINDING TEMPERATURE ALARM

133

WTTVA

TV WINDING TEMPERATURE ALARM

134

OTA

OIL TEMPERATURE ALARM

135 TET
WTHVT

HV WINDING TEMPERATURE TRIP

137

WTLVT

LV WINDING TEMPERATURE TRIP

138

WTTVT

TV WINDING TEMPERATURE TRIP

139

OTT

OIL TEMPERATURE TRIP

140 TRA
TBUA

TRANSFORMER BUCHOLZ ALARM

142

TOLA

TRANSFORMER OIL LEVEL ALARM

143

TOOLA

TRANSFORMER OLTC OIL LEVEL ALARM

144

TOOS

TRANSFORMER OUT OF STEP ALARM

145

TFPF

146 TRMPT

TRANSFORMER FIRE PROTECTION FAILURE

TRANSFORMER BUCHOLZ TRIP

TBUT

148

TSPT

TRANSFORMER SUDDEN PRESSURE TRIP

149

TJANT

TRANSFORMER JANSEN TRIP

150

TOSPT

TRANSFORMER OLTC SUDDEN PRESSURE TRIP

151

TFPA

TRANSFORMER FIRE PROTECTION ACTIVATED

152

DIFT

DIFFERENTIAL TRIP

153

REFT

RESTRICTED EARTH FAULT TRIP

154 TRBPT

TSS

TSS

TSS
TSS

TSS

TSS
TSS
TSS
TSS

TSS

TSS
TSS
TSS
TSS
TSS

TRANSFORMER MAIN PROTECTION TRIP

147

TSS

TRANSFORMER ALARM

141

TSS

TEMPERATURE TRIP

136

TSS

TSS

TSS

TSS

TSS
TSS
TSS
TSS
TSS

TSS

TRANSFORMER BACK UP PROTECTION TRIP

155

SBEFT

STAND BY EARTH FAULT TRIP

156

NVD

NEUTRAL VOLTAGE DISPLACEMENT (TERSIER)

157

TGFT

TRANSFORMER GROUND FAULT TRIP

158

TIGFT

TRANSFORMER INSTANTANEOUS GROUND FAULT TRIP

159

TOCT

TRANSFORMER OVER CURRENT TRIP

160

TIOCT

TRANSFORMER INSTANTANEOUS OVER CURRENT TRIP

161 TCH

TCH

TAP CHANGER HIGH LIMIT

162 TCL

TCL

TAP CHANGER LOW LIMIT

163 TCIP

TCIP

TAP CHANGER IN PROGRESS

164

TCFF

TRANSFORMER COOLING FAN FAILURE

165

TCPF

TRANSFORMER COOLING PUMP FAILURE

166 OCGF

GFT

168

IGFT

INSTANTANEOUS GROUND FAULT TRIP

169

OCT

OVER CURRENT TRIP

170

IOCT

INSTANTANEOUS OVER CURRENT TRIP

171 RA

GROUND FAULT TRIP

RBUCA

REAKTOR BUCHOLZ ALARM

173

ROLA

REAKTOR OIL LEVEL ALARM

174

RCFF

REAKTOR COOLING FAN FAILURE

175

RF

REACTOR FAILURE

176 RT

REAKTOR BUCHOLZ TRIP

RBUCT

178

RSPT

REAKTOR SUDDEN PRESSURE TRIP

179

RFDP

REAKTOR FIRE DETECTION & PROTECTION

180 BP

BP

BUSBAR PROTECTION

181 VS

VS

VOLTAGE STATUS

182 LOR

LOR

LOCK OUT RELAY TRIP

183

UNDER FREQUENCY RELAY TRIP

184

UFR SELECTED

185

UNDER VOLTAGE RELAY TRIP

186 OVR

OVR

OVER VOLTAGE RELAY TRIP

187

RTN

RELAY TEGANGAN NOL

188

POT

PROTECTION ON TEST

190

CCP

CIRCULATING CURRENT PROTECTION TRIP

191

CBF

CIRCUIT BREAKER FAILURE TRIP

192

SZP

SHORT ZONE PROTECTION TRIP

189 DTT

DIRECT TRANSFER TRIP

193 TTR

TELEPROTECTION TRIP RECEIVE

TSS
TSS

TSS

TSS
TSS
TSS

TSS
TSS
TSS

TSS
TSS
TSS
TSS

REAKTOR TRIP

177

TSS

TSS

REAKTOR ALARM

172

TSS

TSS

OVER CURRENT GROUND FAULT

167

TSS

TSS

TSS
TSS
TSS

TSS

TSS

TSS
TSS

TSS
TSS
TSS

TSS
TSS
TSS
TSS

TSS
TSS
TSS

194

DISRX

DISTANCE RELAY RECEIVE

TSS

195

DEFRX

DIRECTIONAL EARTH FAULT RELAY RECEIVE

TSS

196

DTTRX

DIRECT TRANSFER TRIP RECEIVE

TSS

phase segregated

phase segregated

phase segregated

phase segregated

phase segregated

phase segregated

phase segregated

phase segregated

phase segregated

phase segregated

3
3
3

phase segregated

phase segregated

gas protection in tap changer

3
3

fire protection di transformer (nitrogen)

1
1

1
1

1
1
1

indikasi umpan balik dari TCC

3
3
1

1
1

1
1
1
1

1
1
1
1

indikasi live bus (tiap bus)


1

indikasi karena reset per bay

1
1

alarm RTN kerja apabila bus A dan bus B padam (AND gate). (Not Applicable
1

4
6
6

2
2
2

4 of 5

STANDARDISASI TELE INFORMASI DATA SOGI


GARDU INDUK 500 KV

OPS

OHL FEEDER

IBT 500(275)/150 SIS

IBT 500(275)/150 SIS

REACTOR

DIAMETER

GEN TRANSF

GENERATOR

BLOK

10

11

12

13

BLOK

BUS SECTION

GENERATOR

BUS COUPLER

GEN TRANSF

13

DIAMETER

12

REACTOR

11

IBT 500(275)/150 SIS

10

IBT 500(275)/150 SIS

OHL FEEDER

BUS SECTION

BUS COUPLER

BUSBAR

GARDU INDUK

REMOTE STATION (S

BUSBAR

PEMELIHARAAN

GARDU INDUK

OPERASI
1

REMOTE STATION

COMMON

PER PHASA

JUMLAH
PER PEMBANGKIT

PER GI

PER BAY

PER PERALATAN

LN IEC61850

BAGIAN

KETERANGAN PEMBAHASAN

KETERANGAN

HAR

197 TTT

TELEPROTECTION TRIP TRANSMIT


DISTX

DISTANCE RELAY TRANSMIT

TSS

199

DEFTX

DIRECTIONAL EARTH FAULT RELAY TRANSMIT

TSS

200

DTTTX

DIRECT TRANSFER TRIP TRANSMIT

TSS

201 GOV

FREE ACTING GOVERNOR ACTIVE

TSS

202 AVR

AUTOMATIC VOLTAGE REGULATOR ON/OFF

203 AQR

AUTOMATIC POWER FACTOR ACTIVE

TSS

204 LFF

LOAD FREQ CONTROL UNIT FAILURE

TSS

TSS

205 UT

UT

UNIT TRIP

TSS

206 GTT

GTT

GENERATOR TRANSFORMER TRIP

TSS

207 BRF

BREAKER FAULT

208

LPA

LOW PRESSURE ALARM

209

LPB

LOW PRESSURE BLOCK

210

LPT

LOW PRESSURE TRIP

211

PD

POLE DISCREPANCY

212

CBDF

CIRCUIT BREAKER DRIVE FAILURE

213

TCS

TRIP CIRCUIT SUPERVISION

214 BF
VTMT

VOLTAGE TRANSFORMER MCB TRIP

DSMT

DISCONNECTING SWITCH MCB TRIP


GROUND FAULT DETECTOR
TOTAL

TSS

BAY FAULT

215
216

TSS

198

217 GFD

SUMBER
SIGNAL

HARDWIRING

IED PROTEKSI

IED AVR

IED BCU

DESIGNATION

LOCAL HMI

MNEMO

NO

TIPE INFORMASI

TIPE

TAMPILAN

TSS
TSS
TSS
TSS
TSS

TSS

TSS

TSS
TSS

1
2
2
2
1
1
1
1

Pembangkit trip
Trafo step trip

3
3
3
3
3
3
18
1

VT MCB fail

66

82

12

27

66

MCB motor fail

TSS

Detector gangguan tanah di TM


5

16

12

13

REVISI : 08 (17 Januari 2013)


KETERANGAN :
Fungsi PEMELIHARAAN: adalah semua informasi yang dikirimkan oleh SOGI ke Control Center dan ditampilkan di lokal HMI.
Fungsi OPERASI: adalah semua informasi yang ditampilkan di Dispatcher Control Center, merupakan filter atau gruping yang dilakukan oleh Control Center dari fungsi PEMELIHARAAN.

5 of 5