JOINT OPERATION
LOKASI PEKERJAAN : PS 3
Hasil Ukur (M
R-G
1,200,000
S-G
1,200,000
mm
T-G
1,200,000
meter
R-S
1,190,000
R-T
1,200,000
S-T
316,000
R-G
1,200,000
S-G
1,200,000
mm
T-G
1,200,000
meter
R-S
1,200,000
R-T
1,200,000
S-T
1,200,000
KABEL METAL
NA2XSEBY
KABEL METAL
NA2XSEBY
SKTM 20 kV
R-G
S-G
mm
T-G
meter
R-S
Merk
R-T
S-T
SKTM 20 kV
R-G
S-G
mm
T-G
meter
R-S
Merk
R-T
S-T
NO
Hasil Uji
Arus Bocor (M
R - (S+T+G)
0.02
S - (R+T+G)
0.02
T - (R+S+G)
0.02
Hasil Uji
R - (S+T+G)
0.078
S - (R+T+G)
0.078
T - (R+S+G)
0.078
Diketahui,
PMU - BSH
PT. ANGKASA PURA II
...............................
...............................
Arus Bocor (M
Kriteria
1,200,000
1,200,000
1,200,000
1,190,000
1,200,000
316,000
1,200,000
1,200,000
1,200,000
1,200,000
1,200,000
1,200,000
* Untuk sistem Tegangan
20 kV > 200 M
Keterangan
0.02
0.02
0.02
Keterangan
0.078
0.078
0.078
Diajukan,
Kontraktor
NINDYA - ARIA, JO
...............................
NINDYA - ARIA
JOINT OPERATION
LOKASI PEKERJAAN
: PS 3
CENTRADO
Type / Jenis
OUTDOOR
Impedansi
Daya Pengenal
3150
kVA
Tegangan Pengenal
20
kV
400 V
Arus Pengenal
90,9
4546,76 A
Phase / Frekuensi
50
Type of Cooling
No. Seri
Hz
Tahun
Primer (M)
Nilai DAR
Phase 1 - Body
5060
1.73
Phase 2 - Body
5500
1.73
Phase 3 - Body
5630
1.73
Phase 1 - Phase 2
Phase 1 - Phase 3
Phase 2 - Phase 3
Netral - Body
8060
1.73
Primer - Sekunder (M) dan Nilai DAR
U1 - U2
6630
1.22
V1 - U2
6920
1.22
U1 - V2
7490
1.21
V1 - V2
7760
1.21
U1 - W2
7970
1.22
V1 - W2
8370
1.22
CENTRADO
Type / Jenis
OUTDOOR
Impedansi
Daya Pengenal
Tegangan Pengenal
Arus Pengenal
Phase / Frekuensi
3150
20
kVA
kV
400 V
90,9 A
3
Type of Cooling
4546,76
No. Seri
50
Hz
Tahun
Primer (M)
Nilai DAR
Phase 1 - Body
2570
1.32
Phase 2 - Body
2760
1.32
Phase 3 - Body
2990
1.32
Phase 1 - Phase 2
Phase 1 - Phase 3
Phase 2 - Phase 3
Netral - Body
3110
1.32
Primer - Sekunder (M) dan Nilai DAR
U1 - U2
5270
1.25
V1 - U2
5420
1.25
U1 - V2
6330
1.21
V1 - V2
6120
1.21
U1 - W2
6600
1.19
V1 - W2
6770
1.19
Diketahui,
PMU - BSH
PT. ANGKASA PURA II
...............................
...............................
Ynd5
Impedansi
5.70%
125
kV
Type of Cooling
ONAN
No. Seri
1609009
Tahun
2016
Sekunder (M)
Nilai DAR
506
1.06
481
1.06
581
1.06
7340
1.22
W1 - V2
7960
1.21
W1 - W2
8200
1.22
Ynd5
Impedansi
5.50%
125
kV
Type of Cooling
ONAN
No. Seri
1609010
Tahun
2016
Sekunder (M)
Nilai DAR
> 100.000
1.19
> 100.000
1.19
> 100.000
1.19
5610
1.25
W1 - V2
6340
1.21
W1 - W2
6760
1.19
Diajukan,
Kontraktor
NINDYA - ARIA, JO
...............................