Anda di halaman 1dari 24

TECHNICAL PARTICULAR AND GUARANTEE

TPG : KWH METER

NO URAIAN PEKERJAAN UNIT REQUIRED

Merek - (to be mentioned)


1 Tipe - (to be mentioned)
Model/Part Number - (to be mentioned)
2 Jenis Meter - Meter Elektronik
3 Standard - ANSI C12.20 dan atau IEC 62053-22 (kWh) atau yang lebih baru
IEC 1268 (VARh) atau IE 62053-22 (kWh) atau yang lebih baru
4 Jenis Konstruksi - Switchboard (draw out)
5 Metode Komunikasi - Multi-tasking, multi user & web based
6 Terminal Komunikasi (Built in) - Optical Port
- RS232 atau RS485
- Port Ethernet (TCP/IP, tidak menggunakan konverter)
7 Protokol Komunikasi (tersedia) - DLMS atau (DNP3 dan MODBUS)
8 Sinkronisasi dengan GPS - Dapat tersinkronisasi
9 Tipe Pengawatan - 3 Fasa - 4 Kawat
10 Arus Nominal A Disesuaikan dengan arus sekunder CT Terpasang
11 Ketahanan Arus Gangguan A 1.5 x In Kontinyu, 10 x In selama 0,5 detik
12 Tegangan Nominal VAC 57.7 - 240 V AC (auto range) Minimum pick-up voltage :
57.7V Fasa - Netral
13 Aux. Power Supply VAC / VDC 57.7 - 240 V AC (Auto Range) dan 110 - 220 V DC (Auto Range)

page 1 of 24
TECHNICAL PARTICULAR AND GUARANTEE

TPG : KWH METER

NO URAIAN PEKERJAAN UNIT REQUIRED

14 Frekuensi Hz 50
15 Kelas Ketelitian - kWh : 0.2 (Mengacu pada Standard IEC62053-22)

- kVARh : 2 (Mengacu pada Standard IEC62053-23)


16 Temperatur Operasi -40oC sampai +75oC
17 Jumlah Kanal Penyimpanan Load Profile min 14 Channel load profile (Dapat dibagi menjadi 2 Grup)
18 Kapasitas Penyimpanan Memori Load Profile Minimum 14 channel 30 menit selama 120 hari
19 Interval Perekaman Daya (Dapat Diprogram) 1 Sampai 60 Menit

page 2 of 24
TECHNICAL PARTICULAR AND GUARANTEE

TPG : KWH METER

NO URAIAN PEKERJAAN UNIT REQUIRED

20 Besaran Energi yang diukur / direkam Wh Kirim


Wh Terima
VARh Kirim
VARh Terima
VAh Kirim
VAh Terima
21 Besaran Daya yang diukur / direkam W Kirim
W Terima
VAR Kirim
VAR Terima
VA Kirim
VA Terima
22 Interval Perekaman Energi (Dapat Diprogram) menit 1, 5, 10, 15, 20, 30, dan 60
23 Besaran Sesaat yang diukur dan dapat direkam W Kirim
W Terima
VAR Kirim
VAR Terima
VA Kirim
VA Terima

page 3 of 24
TECHNICAL PARTICULAR AND GUARANTEE

TPG : KWH METER

NO URAIAN PEKERJAAN UNIT REQUIRED

kV Tegangan Tiap Fasa (Antar Fasa dan Fasa - Netral)


A Arus Tiap Fasa
Faktor Daya
Hz Frekuensi
24 Koinsiden Demand W Kirim
W Terima
VAR Kirim
VAR Terima

page 4 of 24
TECHNICAL PARTICULAR AND GUARANTEE

TPG : KWH METER

NO URAIAN PEKERJAAN UNIT REQUIRED

VA Kirim
VA Terima
kV Tegangan Tiap Fasa (Antar Fasa dan Fasa - Netral)
A Arus Tiap Fasa
Faktor Daya
Hz Frekuensi
25 Pembagian Tarif - 8 Tarif (minimal)
26 End of billing / register freeze Tanggal 1 jam 10:00 setiap bulan untuk semua tarif
27 Aplikasi Baca / Seting Meter - - Disertakan
- Berbasis Windows XP, Vista dan 7 (seven)

- Dapat diinstall ke semua laptop/pc milik PLN P3B berikut


lisensinya
- Dapat Mengambil data berdasarkan waktu yang dapat
dikonfigurasi (mampu mengambil loadprofile dengan range tanggal
yang ditentukan)

- Mampu mengexport data load profile dalam format teks dan atau
spreadsheet
28 Tampilan Layar - Minimum 8 digit
28 Pengaman - Pada Hardware (lock) & Software (password level)

page 5 of 24
TECHNICAL PARTICULAR AND GUARANTEE

TPG : KWH METER

NO URAIAN PEKERJAAN UNIT REQUIRED

29 Integrasi Sistem - Dapat terintegrasi dengan Sistem AMR P3B JB

page 6 of 24
NICAL PARTICULAR AND GUARANTEE

PROPOSED AND GUARANTEE

page 7 of 24
NICAL PARTICULAR AND GUARANTEE

PROPOSED AND GUARANTEE

page 8 of 24
NICAL PARTICULAR AND GUARANTEE

PROPOSED AND GUARANTEE

page 9 of 24
NICAL PARTICULAR AND GUARANTEE

PROPOSED AND GUARANTEE

page 10 of 24
NICAL PARTICULAR AND GUARANTEE

PROPOSED AND GUARANTEE

page 11 of 24
NICAL PARTICULAR AND GUARANTEE

PROPOSED AND GUARANTEE

page 12 of 24
PT PLN (Persero)
TECHNICAL PARTICULAR AND GUARANTEE
AUTOMATIC VOLTAGE REGULATOR ( AVR )

NO DESCRIPTION UNIT REQUIRED PROPO

1 Name Automatic Voltage Regulator


2 Merk/Type/Order Code (Manufacture) ……../……../………( ……..... ) ……..
3 Nominal Current ( In ) A 1 and 5
4 Auxillary Supply Voltage V 110 VDC (-15% s.d +10%)
5 Rating
Nominal Current (In) A 1A and 5 A
Voltage Input ( Vn ) V 100 or 110
Frequency HZ 50 ± 5%
Auxiliary DC Voltage ( Vx ) VDC 110 Volt DC (-15%;+10%), tolerable DC ripple up
to 12%
Digital input
Capacity 8
Rated voltage range VDC 110 V DC (-15 % - + 10%) tolerable DC ripple up to
12%

6 Burden
Current circuits ( In ) VA ≤ 0,2 (1 A)
VA ≤ 1,0 (5 A)
Reference voltage ( Vn ) V 100 or 110
Auxiliary voltage VA ≤ 50
7 Control function setting ranges
Setting Setting Range Step size
Regulated Voltage Vs % 90 - 120 of Vn 0,1

13 of 24
PT PLN (Persero)
TECHNICAL PARTICULAR AND GUARANTEE
AUTOMATIC VOLTAGE REGULATOR ( AVR )

NO DESCRIPTION UNIT REQUIRED PROPO

Deadband dVs % ±0.5 to ± 5.0 of Vn 0,1


Resistive line drop compensation Vr V 0 - 50 1,0
Resistive line drop compensation Vxl V 0 - 50 1,0
Circulating current compensation Vc V 0 - 50 1,0
Load shedding/boosting % 0 - ±10 of Vs 1
Total taps available TapsAvail - 1 - 40 or 1 - 30 1
Maximum total tap position TP> - 1 - 40 or 1 - 30 1
Minimum total tap position TP< - - 30 or 1 - 30 1

14 of 24
PT PLN (Persero)
TECHNICAL PARTICULAR AND GUARANTEE
AUTOMATIC VOLTAGE REGULATOR ( AVR )

NO DESCRIPTION UNIT REQUIRED PROPO

Total number of tap changes TotalOps> - 1 - 10000 1


Tap Changers Operations Ops/tP> - 1 - 100 1
Time Period tP Hrs 1 - 24 1 - 24
Intertap Delay (tINTER) secs 0 - 120 0,1
Tap Change indication time (tPULSE) 0,5 - 5 0,5
Tap Change indication time (tTapChange) 1–3 0,1
8 Time delay setting ranges
Inverse time delay t= k+[(initial time delay setting ) x ( 1/N)] *) or
Time curve : Short time inverse
Definite time delay Setting Range Step size
Initial time (definite) secs 0 - 20 0 - 20
secs 20 - 300 10
9 Supervision function settings
Setting Setting Range Step size
Under voltage blocking (V<<) V 60-130 1,0
Under voltage detection (V<) V 80-130 1,0
Over voltage detection (V>) V 105 - 160 1,0
Circulating current (Ic) A 0.02-0.5 ( In = 1A) 0.01
A 0.1-2.5 (In = 5A) 0,05
Load current (IL>) A 0.05-2.0 ( In = 1A)
A 2.5-10 ( In = 5A) 0,05
Load current (IL<) A 0 - 1 ( In = 1A)
A 0 - 5 ( In = 5A) 0 - 5 ( In = 5A)

15 of 24
PT PLN (Persero)
TECHNICAL PARTICULAR AND GUARANTEE
AUTOMATIC VOLTAGE REGULATOR ( AVR )

NO DESCRIPTION UNIT REQUIRED PROPO

Excessive circulating
current time delay (tIC) secs 0 - 180 10
Power factor angle degrees 0 - 90 1
10 Transformers Ratios
CT ratios - 9999 : 1 Default = 1:1
VT ratios - 9999 : 1 Default = 1:1
11 Measurement - Enable

16 of 24
PT PLN (Persero)
TECHNICAL PARTICULAR AND GUARANTEE
AUTOMATIC VOLTAGE REGULATOR ( AVR )

NO DESCRIPTION UNIT REQUIRED PROPO

12 Maintenace - Free : no need to have components which require


maintenace or replacement during life of the
device

13 Safety and reliability - Die noise imunity against electromagnetic fields


acc.
to IEC 6100-4-3 needs to be (HF) 20V/m 80-
3000Mhz
Noise imunity against fast transients/burst (IEC
61000-4-4)
needs to be 6.5 kV. The power frequency for
magnetic field

Immunity (IEC 61000-4-8) needs to be 1000A/m


14 Bandwidht setting - Automatic setting of bandwidht by IED
15 Software - Must be possible of the limit the regulating range of
IED in the menu setting of the controller

16 Local Configuration

Terminal Interface - RJ45/RS 485/RS 232


Database configuration - Upload dan download
17 Performance Test

17 of 24
PT PLN (Persero)
TECHNICAL PARTICULAR AND GUARANTEE
AUTOMATIC VOLTAGE REGULATOR ( AVR )

NO DESCRIPTION UNIT REQUIRED PROPO

Type Test - Submitted


Routine Test - Submitted
Licensed Software for setting & analysis - Included
18 Connection between relay to computer - Included
19 Default Setting & Programmable Logic Controller - Enable
20 Guarantee - Min 5 (five) years after operation (from
manufacture)
21 Manual book (original hard and soft copy) and - Submitted
enclosed with original certificate of routine test
22 Protocol Communication - IEC 61850
23 Requirment - Completed with interface or converter that could
accommodate indication and control of transformer
OLTC tap position

18 of 24
PT PLN (Persero)
ARTICULAR AND GUARANTEE
VOLTAGE REGULATOR ( AVR )

PROPOSED AND GUARANTEE

……../……../………( ……..... )
.

19 of 24
PT PLN (Persero)
ARTICULAR AND GUARANTEE
VOLTAGE REGULATOR ( AVR )

PROPOSED AND GUARANTEE

20 of 24
PT PLN (Persero)
ARTICULAR AND GUARANTEE
VOLTAGE REGULATOR ( AVR )

PROPOSED AND GUARANTEE

21 of 24
PT PLN (Persero)
ARTICULAR AND GUARANTEE
VOLTAGE REGULATOR ( AVR )

PROPOSED AND GUARANTEE

22 of 24
PT PLN (Persero)
ARTICULAR AND GUARANTEE
VOLTAGE REGULATOR ( AVR )

PROPOSED AND GUARANTEE

23 of 24
PT PLN (Persero)
ARTICULAR AND GUARANTEE
VOLTAGE REGULATOR ( AVR )

PROPOSED AND GUARANTEE

24 of 24