Panduan Dry contact untuk ZXDU68 W201 Smartfren LTE Project

Dry Contact for Power Monitoring


Solution without EISU at
ZXDU68 W201
Panduan Dry contact untuk ZXDU68 W201 Smartfren LTE Project

Table of Contents
1. POWER MONITORING DENGAN DRY CONTACT..............................................3
1.1 Landasan informasi...................................................................3
1.2 Tabel alarm dan koneksi.............................................................3
1.3 Material list...........................................................................4
2. HARDWARE INSTALLATION.................................................................6
2.1 DB25 Converter ke SA................................................................6
2.2 Alarm PLN failure.....................................................................6
2.3 Alarm Rectifier Module/Arrester Rectifier..........................................7
2.4 Alarm DC low voltage alarm.........................................................7
2.5 Alarm Input SPD PLN Failure.........................................................7
2.6 Alarm Battery stolen.................................................................8
2.7 Alarm High temperature.............................................................8
2.8 Alarm Diesel Generator Set On......................................................8
2.9 Alarm Door Open.....................................................................8
3. SETTING ALARM CSU VIA LAPTOP.........................................................9

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] | 2 / 12
Panduan Dry contact untuk ZXDU68 W201 Smartfren LTE Project

1. Power monitoring dengan Dry contact


1.1 Landasan informasi
Untuk memonitor DC power system ZTE ZXDU68 W201 tanpa menggunakan EISU, maka akan digunakan signal alarm
melalui dry contact.

Pembagian alarm dry contact sbb :

1. Beberapa alarm akan menghubungkan koneksi dari SA cable (cable B3) ke dry contact di SIB pada ZXDU68 W201

2. Beberapa alarm akan menghubungkan konesi dari SA cable (cable B3) ke ke dry contact di ACPDB

3. Tabel dibawah untuk pembagian koneksi dan alarm dry contactnya pada ZXDU68 W201

1.2 Tabel alarm dan koneksi


SA cable B3
NO Alarm Source SIB koneksi Jalur Koneksi Alarm Code di Nodeb
koneksi

Option 1 : Jika ACPDB support terminal contactor


1.Koneksi dari DB25 ke terminal di ACPDB AC power-cut alarm (198092207)
X14 (Pin 2 & 3) 2. Dari terminal ACPDB ke SIB
Dry contat di ACPDB +
1 PLN Failure DB 25 Pin 1 -14 3. Dari SIB ke DB25 Dry contact number : 0
Dry contact di SIB NC-1
Option 2 : Jika ACPDB tidak support terminal contactor Alarm Status : Alarm when open (1)
1. Koneksi dari DB25 ke SIB saja

Rectifier Module Alarm (198092208)


Rectifier Module & X14 (Pin 5 & 6)
2 Dry contact di SIB DB 25 Pin 2 -15 Koneksi SIB ke SA Dry contact number : 1
Arrester Rectifier NC-2
Alarm Status : Alarm when open (1)

Battery Low Voltage Alarm (198092259)


X16 (Pin 5 & 6)
3 DC Low Voltage Dry contact di SIB DB 25 Pin 3 -16 Koneksi SIB ke SA Dry contact number : 2
NC-6
Alarm Status : Alarm when open (1)

Arrester failure (198092560)

4 Input SPD PLN Failure Dry contat di ACPDB / DB 25 Pin 4 -17 Koneksi ke terminal di ACPDB Dry contact number : 3

Alarm Status : Alarm when open (1)

Battery Stolen (198092555)


Dry contact di SIB + X15 (Pin 2 & 3)
5 Battery Stolen DB 25 Pin 5 -18 Koneksi SIB ke SA+lilitan batere Dry contact number : 4
lilitan batere NC-3
Alarm Status : Alarm when open (1)

High Temp Alarm (198092595)


X15 (Pin 5 & 6)
6 High Temp Dry contact di SIB DB 25 Pin 6 -19 Koneksi SIB ke SA Dry contact number : 5
NC-4
Alarm Status : Alarm when open (1)

Genset ON (198092567)
Diesel Generator Set
7 ATS FGS / DB 25 Pin 7 -20 DB 25 Pin 7 -20 di loop Dry contact number : 6
On
Alarm Status : Alarm when open (1)

Door Control Alarm (198092044)


X16 (Pin 2 & 3)
8 Door Open Dry contact di SIB DB 25 Pin 8 -21 Koneksi SIB ke SA Dry contact number : 7
NC-5
Alarm Status : Alarm when open (1)

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] | 3 / 12
Panduan Dry contact untuk ZXDU68 W201 Smartfren LTE Project

1.3 Material list


No Materials/Cable Name QTY Remark

1 0.3mm2 black single core heat resistant Flexible power cable 10 M Lilitan batere

2 Black dual core heat resistant Flexible power cable 30 M Untuk alarm koneksi dari SIB ke SA

3 Temperature Transducer Cable & sensor 1 KIT Di pasang di X10 SIB

5 SA cable 1 KIT BBU

6 Converter RS232 DB25 1 KIT Dipasang di SA B3 cable

SA cable

Converter RS232 Db25 Cable black dual core

Temperature sensor di X10 Lilitan batere

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] | 4 / 12
Panduan Dry contact untuk ZXDU68 W201 Smartfren LTE Project

1.1 X14 : Output Relay


1,2
1.2 Pin 2,3 --> NC-1 di
CSU A1
1.3 Pin 5,6 --> NC-2 di

1.4 X15 : Output Relay


3,4
1.5 Pin 2,3 --> NC-3 di
CSU A3
1.6 Pin 5,6 --> NC-4 di

1.7 X16 : Output Relay


5,6
1.8 Pin 2,3 --> NC-5 di
CSU A5
1.9 Pin 5,6 --> NC-6 di

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] | 5 / 12
Panduan Dry contact untuk ZXDU68 W201 Smartfren LTE Project

2. Hardware installation
2.1 DB25 Converter ke SA
Install DB25 converter ke SA cable, koneksi kabel SA nya di konektor dengan inisial B3.

2.2 Alarm PLN failure


Option 1 : Jika ACPDB panel tersedia terminal dry contact alarm untuk phase failure

Step :

a. Install kabel signal dari DB25 pin 1 ke terminal dry contact di ACPDB

b. Install kabel signal dari terminal dry contact untuk terminal lainnya di ACPDB ke SIB X14 pin 2

c. Install kabel signal dari SIB X14 pin 3 ke DB25 pin 14

Warna merah pake kabel isi 2

Warna hitam pake kabel isi 1

Option 2 : Jika ACPDB panel tidak tersedia terminal dry contact alarm untuk phase failure

Step :

a. Install kabel signal dari DB25 pin 1 ke SIB X14 pin 2

b. Install kabel signal dari DB25 pin 14 ke SIB X14 pin 3

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] | 6 / 12
Panduan Dry contact untuk ZXDU68 W201 Smartfren LTE Project

2.3 Alarm Rectifier Module/Arrester Rectifier


Kabel signal yang dipakai isi 2 pcs

Step :

a. install kabel signal dari DB25 pin 2 ke SIB X14 pin 5

b. Install kabel signal dari DB25 pin 15 ke SIB X14 pin 6

2.4 Alarm DC low voltage alarm


Kabel signal yang dipakai isi 2 pcs

Step :

a. install kabel signal dari DB25 pin 3 ke SIB X16 Pin 5

b. Install kabel signal dari DB25 pin 16 ke SIB X16 Pin 6

2.5 Alarm Input SPD PLN Failure

Jika ACPDB panel tersedia terminal dry contact alarm untuk arrester failure

Kabel signal yang dipakai isi 2 pcs

Step :

a. Install kabel signal dari DB25 pin 4 ke dry contact di ACPDB

b. Install kabel signal dari terminal dry contact untuk terminal lainnya di ACPDB ke DB25 pin 17

Jika tidak tersedia, cukup di loop koneksi di DB25 converter pin 4 ke pin 17

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] | 7 / 12
Panduan Dry contact untuk ZXDU68 W201 Smartfren LTE Project

2.6 Alarm Battery stolen


Kabel signal yang dipakai isi 1 pcs

Step

a. install kabel signal dari DB25 pin 5 ke SIB X15 Pin 2

b. Install kabel signal dari DB25 pin 18 ke SIB X15 Pin 3 setelah

Melakukan lilitan pada semua bank batere

2.7 Alarm High temperature


Kabel signal yang dipakai isi 2 pcs

Step

a. Install temperature sensor di SIB di X10

b. install kabel signal dari DB25 pin 6 ke SIB SIB X15 Pin 5

c. Install kabel signal dari DB25 pin 19 ke SIB X15 Pin 6

2.8 Alarm Diesel Generator Set On


Loop koneksi dari DB25 pin 7 ke DB25 pin 20

Smartfren nantinya yang akan instal sendiri ke Genset

2.9 Alarm Door Open


Kabel signal yang dipakai isi 2 pcs

Step :

a. install kabel signal dari DB25 pin 8 ke SIB X16 Pin 2

b. Install kabel signal dari DB25 pin 21 ke SIB X16 Pin 3

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] | 8 / 12
Panduan Dry contact untuk ZXDU68 W201 Smartfren LTE Project

3. Setting Alarm CSU via laptop


Karena menggunakan relay output, untuk alarm yang tidak dipakai dari penjelasan diatas harus di set NULL alarm alokasi
relaynya dan alokasi yang dipakai juga harus di set sesuai pengaturan koneksi diatas.

Dikarenakan default CSU sudah di set alokasi relaynya, untuk memudahkan perubahan harus menggunakan laptop yang di
hubungkan ke CSU

Step

1. Dari CSU pilih menu local set, akan tampil beberapa sub menu
2. Local menuNetworkWire NetworkLokal IPGanti ke StaticEnter kemudian “ESC” dan pilih “YES”

3. Konek kabel LAN dari laptop ke CSU di coba beberapa kemungkinan user dan password dibawah

user : Power; password:ZTECorporation@0063

user : power; password : 0063

user : ZTECorporation; Password : 0063

user : admin; Password : 0063

user : admin; Password : power123

4. Set IP laptop

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] | 9 / 12
Panduan Dry contact untuk ZXDU68 W201 Smartfren LTE Project

5. Via browser, masukin IP CSU, masukin user : Power dan Password : 0063

6. Masuk ke menu di kotak merah dibawah untuk mengatur output relay

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] | 10 / 12
Panduan Dry contact untuk ZXDU68 W201 Smartfren LTE Project

7. Set Alarm level dibawah ini dan untuk alarm lainya harus di set di set NULL

Parameter Name Parameter Value Remark


AC Power OFF A1 di sub menu AC alarm attr
AC Voltage Low A1 di sub menu AC alarm attr
AC Phase Lack A1 di sub menu AC alarm attr
AC SPD Abnormal A2 di sub menu AC alarm attr
SMR Fan Fault A2 di sub menu SMR alarm attr
SMR Communication Fail A2 di sub menu SMR alarm attr
DC Voltage Low A6 di sub menu DC alarm attr
DC SPD Abnormal A2 di sub menu DC alarm attr
Battery Voltage Low A6 di sub menu DC alarm attr
Battery Loop Broken A3 di sub menu DC alarm attr
Environment Temp High A4 di sub menu ENV alarm attr
Door Alarm A5 di sub menu ENV alarm attr

SET SEMUA ALARM Selain dari tabel diatas untuk output relaynya : NULL

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] | 11 / 12
Panduan Dry contact untuk ZXDU68 W201 Smartfren LTE Project