Anda di halaman 1dari 6

Respon PLTU Pacitan

Jumat, 05 Agustus 2022 Jam 20:00 WIB

The information contained in this document is strictly confidential. It is strictly forbidden to use, disclose, copy, modify, or distribute this document
without permission of PEMBANGKITAN JAWA-BALI, PT 1
Respon Terhadap - PLTU BATANG Load Rejection Test 950 MW

(INFO JCC)

The information contained in this document is strictly confidential. It is strictly forbidden to use, disclose, copy, modify, 2
or distribute this document without permission of PEMBANGKITAN JAWA-BALI, PT
Respon Pembangkit – PLTU Pacitan #1
Waktu 5 mnt sebelum Waktu 5 mnt setelah
Waktu saat kejadian :
kejadian : kejadian :
Jam : 20:01:00 WIB
Jam : 19:55:00 WIB Jam : 20:05:00 WIB
Load Gross : 285,9 MW
Load Gross : 283,2 MW Load Gross : 288,08 MW
Freq : 50,22 Hz
Freq : 50,28 Hz Freq : 50,03Hz GOVERNOR FREE ON

• Beban :
281,3 MW → 285,9 MW

• Frekuensi :
49,86 Hz → 50,22 Hz

• Respon kenaikan beban : 4,6 MW

Freq Tinggi : Freq Terendah :


Jam : 20:00:59 WIB Jam : 20:01:15 WIB
Load Gross : 285,9 MW Load Gross : 281,3MW
Freq : 50,22 Hz Freq : 49,86 Hz

The information contained in this document is strictly confidential. It is strictly forbidden to use, disclose, copy, modify, 3
or distribute this document without permission of PEMBANGKITAN JAWA-BALI, PT
Respon Pembangkit – PLTU Pacitan #2
Waktu saat kejadian : Waktu 5 mnt setelah
Waktu 5 mnt sebelum
Jam : 20:01:00 WIB kejadian :
kejadian :
Load Gross : 132,17 MW Jam : 20:05:00 WIB
Jam : 19:55:00 WIB
Freq : 50,25Hz Load Gross : 127,61 MW GOVERNOR FREE OFF
Load Gross : 130,14 MW
Freq : 50,03Hz
Freq : 50,26Hz

• Beban :
132,17 MW → 128,66 MW

• Frekuensi :
49,84 Hz → 50,29 Hz

• Respon kenaikan beban : 3,51 MW

Freq Tinggi : Freq Terendah :


Jam : 20:00:59 WIB Jam : 20:01:15 WIB
Load Gross : 130,14MW Load Gross : 128,66MW
Freq : 50,29 Hz Freq : 49,84 Hz

The information contained in this document is strictly confidential. It is strictly forbidden to use, disclose, copy, modify, 4
or distribute this document without permission of PEMBANGKITAN JAWA-BALI, PT
Respon Kenaikan Beban PLTU PACITAN 1 & 2

UNIT Δ BEBAN (MW)

PLTU PACITAN #1 4,5


PLTU PACITAN #2 3,51

TOTAL RESPON KENAIKAN BEBAN PLTU PACITAN 8,01

The information contained in this document is strictly confidential. It is strictly forbidden to use, disclose, copy, modify, 5
or distribute this document without permission of PEMBANGKITAN JAWA-BALI, PT
The information contained in this document is strictly confidential. It is strictly forbidden to use, disclose, copy, modify, or distribute this document
without permission of PEMBANGKITAN JAWA-BALI, PT

Anda mungkin juga menyukai