SPLN S5.002:2008
SPLN S5.002:2008
PT PLN (PERSERO)
PT PLN (PERSERO)
JALAN TRUNOJOYO BLOK M-I/135 KEBAYORAN BARU JAKARTA SELATAN 12160
Disusun oleh: Kelompok Bidang SCADA dengan Surat Keputusan Direksi PT PLN (PERSERO) No.094.K/DIR/2006
Kelompok Kerja Teleinformasi Data Untuk Pemeliharaan Instalasi Sistem Tenaga Listrik dengan Surat Keputusan General Manager PT PLN (Persero) Penelitian dan Pengembangan Ketenagalistrikan No. 006.K/LITBANG/2007
Diterbitkan oleh: PT PLN (PERSERO) Jalan Trunojoyo Blok M-I /135, Kebayoran Baru Jakarta Selatan
10. Ir. Yarid Pabisa 11. Ir. Ruly Chaerul 12. Ir. Herry Santoso 13. Ir. Yanuar I. Prakoso 14. Ir. Hesti Sayoga 15. Ir. Deany EA Rumengan
Susunan Kelompok Kerja Teleinformasi Data Untuk Pemeliharaan Instalasi Sistem Tenaga Listrik
Surat Keputusan General Manager PT PLN (Persero) Litbang Ketenagalistrikan No: 004.K/LITBANG/2007
1. 2. 3. 4. 5. 6. 7. 8. Ir. Solida Novrizal Erdiansyah, ST Ir. A. Sugeng Sugarjito Ir. Ruly Chaerul Tri Hardimasyar, ST Ir. Yarid Pabisa Ir. Joko Pramono Ir. Denden Ruhdani : Sebagai Ketua merangkap Anggota : Sebagai Sekretaris merangkap Anggota : Sebagai Anggota : Sebagai Anggota : Sebagai Anggota : Sebagai Anggota : Sebagai Anggota : Sebagai Anggota
DAFTAR ISI
Daftar Isi .............................................................................................................................................. i Daftar Tabel ...................................................................................................................................... iii Daftar Gambar ................................................................................................................................. iv Daftar Gambar ................................................................................................................................. iv Daftar Lampiran ................................................................................................................................ v Prakata ............................................................................................................................................. vii 1. 2. 3. 4. 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 4.9 4.10 4.11 4.12 4.13 4.14 4.15 4.16 4.17 4.18 4.19 5. 5.1 Ruang Lingkup........................................................................................................ 1 Tujuan ..................................................................................................................... 1 Acuan Normatif ....................................................................................................... 1 Istilah dan Definisi................................................................................................... 1 Alarm ....................................................................................................................... 1 Control center.......................................................................................................... 2 Distribution control center (DCC) ............................................................................ 2 Feeder colouring ..................................................................................................... 2 Gardu hubung ......................................................................................................... 2 Gardu induk............................................................................................................. 2 Gardu tengah .......................................................................................................... 2 Inter distribution control center (IDCC).................................................................... 2 Inter regional control center (IRCC) ........................................................................ 2 Keypoint .................................................................................................................. 2 Maintenance center................................................................................................. 2 National control center (NCC) ................................................................................. 3 Operator .................................................................................................................. 3 Regional control center (RCC) ................................................................................ 3 Regu pemeliharaan ................................................................................................. 3 Supervisory control and data acquisition (SCADA)................................................. 3 Telecontrol .............................................................................................................. 3 Telesignal ................................................................................................................ 3 Telemetering ........................................................................................................... 3 Umum ..................................................................................................................... 3 Fasilitas SCADA...................................................................................................... 3
Teleinformasi data .................................................................................................. 4 Struktur informasi.................................................................................................... 4 Simbol dan warna ................................................................................................... 4 Perbatasan Kebutuhan Teleinformasi Data ........................................................... 4 Perbatasan kebutuhan teleinformasi data antara IRCC dan RCC ......................... 5 Perbatasan kebutuhan teleinformasi data antara RCC dan DCC .......................... 6
Lampiran A Daftar Teleinformasi (Transmisi) .......................................................................... 7 Lampiran B Bidang Transmisi (Teleinformasi pada Berbagai Konfigurasi Gardu Induk) 17 Lampiran C Daftar Teleinformasi (Distribusi)....................................................................... 133 Lampiran D - Bidang Distribusi (Teleinformasi pada Berbagai Konfigurasi Jaringan Distribusi) ....................................................................................................................................... 141 Lampiran E Struktur Informasi ............................................................................................... 174 Lampiran F Simbol dan Warna .............................................................................................. 182
ii
DAFTAR TABEL
Tabel 1. Struktur informasi............................................................................................... 175 Tabel 2. Level tegangan .................................................................................................. 177 Tabel 3. Nama bay atau feeder ....................................................................................... 178 Tabel 4. Kode tegangan dari primer dan sekunder trafo ................................................. 178 Tabel 5. Kode nama peralatan/alarm/elemen.................................................................. 179 Tabel 6. Warna tampilan.................................................................................................. 185
iii
DAFTAR GAMBAR
Gambar 1. Batas wewenang antara IRCC dengan RCC (Tipe-a) ....................................... 5 Gambar 2. Batas wewenang antara IRCC dengan RCC (Tipe-b) ....................................... 5 Gambar 3. Batas wewenang antara RCC dengan DCC ..................................................... 6 Gambar 4. Struktur informasi khusus (bay diameter) ...................................................... 180 Gambar 5. Struktur informasi khusus (gardu induk 1 breaker) .................................... 181 Gambar 6. Simbol gambar .............................................................................................. 183 Gambar 7. Tampilan status ............................................................................................. 184
iv
DAFTAR LAMPIRAN
Lampiran A Daftar Teleinformasi (Transmisi) .................................................................. 7 A-1: Telesignal ..................................................................................................................... 8 A-2: Telemeasurement ...................................................................................................... 14 A-3: Tap Changer Position................................................................................................. 15 A-4: Remote Control Digital ............................................................................................... 16 Lampiran B Bidang Transmisi (Teleinformasi pada Berbagai Konfigurasi Gardu Induk)17 TA-01: Konfigurasi Umum Pada 1 Breaker..................................................................... 18 TA-02: Konfigurasi Umum Pada Double Busbar ............................................................... 28 TA-03: Konfigurasi Umum Pada Single Busbar ................................................................. 39 TB-01: Generator Combined Cycle Pada Konfigurasi 1 Breaker .................................... 50 TB-02: 2 Generator Terhubung ke MTR 3-Belitan Pada Konfigurasi 1 Breaker ............. 52 TB-03: 2 Generator Terhubung ke MTR 3-Belitan Pada Konfigurasi Double Busbar........ 54 TB-04: 2 Generator Terhubung ke MTR 3-Belitan Pada Konfigurasi Single Busbar ......... 56 TB-05: 1 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi 1 Breaker ............. 58 TB-06: 1 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Double Busbar........ 60 TB-07: 1 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Single Busbar ......... 62 TB-08: 2 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi 1 Breaker ............. 64 TB-09: 2 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Double Busbar........ 66 TB-10: 2 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Single Busbar ......... 68 TB-11: Interbus Transformer (Secondary Side Connected to 1 Breaker) ..................................................................... 70 TB-12: Interbus Transformer73 (Secondary Side Connected to Double Busbar) ................................................................ 73 TB-13: Interbus Transformer (Secondary Side Connected to Single Busbar) ................................................................. 76 TB-14: Interbus Transformer (Secondary Side Connected to 1 Breaker Dilengkapi Shunt Reaktor Pada Kumparan Tersier) .................................................................................................. 79 TB-15: Interbus Transformer (Secondary Side Connected to Double Busbar Dilengkapi Shunt Reaktor Pada Kumparan Tersier) .................................................................................................. 82 TB-16: Interbus Transformer (Secondary Side Connected to Single Busbar Dilengkapi Shunt Reaktor Pada Kumparan Tersier) .................................................................................................. 85 TB-17: Bay Trafo Tenaga Pada Konfigurasi 1 Breaker .................................................. 88 TB-18: Bay Trafo Tenaga Pada Konfigurasi Double Busbar ............................................. 91 TB-19: Bay Trafo Tenaga Pada Konfigurasi Single Busbar............................................... 94 TB-20: Bay Reaktor Pada Konfigurasi 1 Breaker .......................................................... 97 TB-21: Bay Reaktor Pada Konfigurasi Double Busbar ...................................................... 99 TB-22: Bay Reaktor Pada Konfigurasi Single Busbar...................................................... 101 TB-23: Bay Capasitor Pada Konfigurasi Double Busbar ................................................. 103 TB-24: Bay Capasitor Pada Konfigurasi Single Busbar ................................................... 105 TB-25: Bay Penghantar Pada Konfigurasi 1 Breaker .................................................. 107 TB-26: Bay Penghantar Pada Konfigurasi Double Busbar .............................................. 110 TB-27: Bay Penghantar Pada Konfigurasi Single Busbar................................................ 113 TB-28: Bay Penghantar Paralel Dengan Reaktor Pada Konfigurasi Double Busbar ....... 116 TB-29: Bay Penghantar Paralel Dengan 1 Reaktor Pada Konfigurasi 1 Breaker ......... 120 TB-30: Bay Penghantar Paralel Dengan 2 Reaktor Seri Pada Konfigurasi 1 Breaker .. 123 TB-31: Bay Kopel Pada Konfigurasi Double Busbar........................................................ 126
TB-32: Bus Section.......................................................................................................... 128 TB-33: Bay Diameter Pada Konfigurasi 1 Breaker ....................................................... 130 TB-34: Bus Bar ................................................................................................................ 132 Lampiran C Daftar Teleinformasi (Distribusi) ............................................................... 133 C-1: Telesignal ................................................................................................................ 134 C-2: Telemeasurement .................................................................................................... 138 C-3: Tap Changer Position .............................................................................................. 139 C-4: Remote Control Digital............................................................................................. 140 Lampiran D - Bidang Distribusi (Teleinformasi pada Berbagai Konfigurasi Jaringan Distribusi) ......................................................................................................................... 141 DA-01: Konfigurasi Umum Pada Double Busbar............................................................. 142 DA-02: Konfigurasi Umum Pada Single Busbar .............................................................. 145 DB-01: Trafo 150/20 kV dan 70/20 kV Tipe 1 .................................................................. 148 DB-02: Trafo 150/20 kV dan 70/20 kV Tipe 2 .................................................................. 150 DB-03: Trafo 150/20 kV dan 70/20 kV Tipe 3 .................................................................. 152 DB-04: Generator Pada Konfigurasi Double Busbar ....................................................... 154 DB-05: Generator Pada Konfigurasi Single Busbar ........................................................ 156 DB-06: Feeder 20 kV Tipe 1 ............................................................................................ 158 DB-07: Feeder 20 kV Tipe 2 ............................................................................................ 160 DB-08: Feeder 20 kV Tipe 3 ............................................................................................ 162 DB-09: Bus Section 20 kV Tipe 1 .................................................................................... 164 DB-10: Bus section 20 kV Tipe 2..................................................................................... 165 DB-11: Kopel ................................................................................................................... 166 DB-12: Capacitor Bay ...................................................................................................... 167 DB-13: SUTM radial dengan keypoint dan PBO ............................................................. 168 DB-14: SUTM radial dengan keypoint tanpa PBO .......................................................... 170 DB-15: SUTM loop dengan beberapa keypoint ............................................................... 171 DB-16: Spindle 20 kV ...................................................................................................... 172 Lampiran E Struktur Informasi...................................................................................... 174 A. Nomor ID ..................................................................................................................... 175 B. Time stamp ................................................................................................................. 177 C. Nama GI/GH/GT ......................................................................................................... 177 D. Level Tegangan .......................................................................................................... 177 E. Nama Bay / Feeder ..................................................................................................... 178 F. Kode Nama Peralatan atau Nama Alarm atau Nama Elemen .................................... 179 G. Status Peralatan atau Status Alarm............................................................................ 179 H. Nama user yang melakukan aksi ................................................................................ 179 I. Prioritas Alarm .............................................................................................................. 180 Struktur Informasi Khusus ............................................................................................... 180 Lampiran F Simbol dan Warna..................................................................................... 182
vi
PRAKATA
Standar SCADA ini merupakan pengganti dari Pola SCADA SPLN No. 109 Tahun 1996, dalam rangka mengikuti perkembangan teknologi SCADA. Standar ini menjelaskan mengenai master station, komunikasi dan remote station yang terdiri dari enam bagian, yaitu: 1. 2. 3. 4. 5. 6. S3.001:2008 S5.001:2008 S5.002:2008 S4.001:2008 S6.001:2008 S7.001:2008 Peralatan SCADA sistem tenaga listrik Teleinformasi data untuk operasi jaringan tenaga listrik Teleinformasi data untuk pemeliharaan instalasi sistem tenaga listrik Pengujian sistem SCADA Perencanaan dan pembangunan sistem SCADA Operasi dan pemeliharaan sistem SCADA
Keenam standar di atas adalah yang telah diselesaikan dalam tahun 2008 dan direncanakan akan ditambah dengan beberapa standar lainnya mengenai SCADA. Standar ini mencakup definisi, perangkat keras, perangkat lunak, kebutuhan teleinformasi data, pengujian, kinerja, kajian kelayakan dalam pembangunan, operasi dan pemeliharaan yang memiliki hubungan dengan sistem SCADA. Standar ini dapat menjadi acuan dalam setiap perencanaan, pembangunan, operasi dan pemeliharaan sistem SCADA di PT PLN (PERSERO) secara nasional.
vii
1.
Ruang Lingkup
Teleinformasi data terdiri dari telecontrol, telesignal dan telemetering. Sesuai dengan penggunaannya, teleinformasi data dibedakan untuk kepentingan operasi dan kebutuhan pemeliharaan. Standar ini dimaksudkan untuk menetapkan standar teleinformasi data yang diaplikasikan untuk kebutuhan pemeliharaan sistem tenaga listrik dan mencakup sistem transmisi dan sistem distribusi. Standar ini, berlaku untuk sistem SCADA: a. National Control Center, disingkat NCC; b. Inter Regional Control Center, disingkat IRCC; c. Regional Control Center, disingkat RCC; d. Inter Distribution Control Center, disingkat IDCC; e. Distribution Control Center, disingkat DCC.
2.
Tujuan
Standar ini ditujukan untuk memberikan pedoman yang terarah dan seragam dalam penerapan teleinformasi data bagi kebutuhan pemeliharaan sistem transmisi dan sistem distribusi tenaga listrik yang mengutamakan mutu, keandalan dan ekonomi. Standar ini merupakan acuan dalam pembangunan sistem SCADA baru dan pengembangan sistem SCADA yang telah ada.
3.
Acuan Normatif
Dokumen normatif berikut berisi persyaratan-persyaratan yang menjadi referensi dalam pembuatan standar SCADA: Teleinformasi Data Untuk Pemeliharaan Instalasi Sistem Tenaga Listrik. a. SNI 04-7021.1.1-2004: 2004, Peralatan dan Sistem Telekontrol Bagian 1: Pertimbangan Umum Seksi 1: Prinsip Umum; b. Keputusan Menteri Energi dan Sumberdaya Mineral Nomor: 150K/30/MEM/2004, Aturan Jaringan Sistem Tenaga Listrik Jawa-Madura-Bali.
4. 4.1
Perubahan kondisi dari peralatan atau sistem yang telah terdeteksi sebelumnya karena fungsi yang tidak dilakukan oleh operator/dispatcher, atau kegagalan peralatan untuk merespon secara benar. Indikasi alarm berupa audible atau visual, atau keduanya.
4.2
Control center
Pusat kendali pengoperasian sistem tenaga listrik dimana master station ditempatkan.
4.3
4.4
Feeder colouring
4.5
Gardu hubung
4.6
Gardu induk
4.7
Gardu tengah
Gardu yang merupakan titik tengah beban atau titik tengah feeder.
4.8
4.9
4.10
Keypoint
Peralatan switching dimana bisa dilakukan manuver antara dua feeder atau lebih.
4.11
Maintenance center
4.12
Pusat kendali yang terhubung dengan beberapa inter regional control center.
4.13
Operator
Petugas yang mengawasi dan mengeksekusi secara lokal peralatan di gardu induk.
4.14
4.15
Regu pemeliharaan
4.16
Sistem yang mengawasi dan mengendalikan peralatan proses yang tersebar secara geografis. [ IEC 870-1-3 ]
4.17
Telecontrol
Kendali peralatan operasional jarak jauh menggunakan transmisi informasi dengan teknik telekomunikasi. [IEV 371-01-01]
CATATAN: Telekontrol dapat berisi kombinasi perintah, alarm, indikasi, metering/pengukuran, proteksi dan fasilitas tripping, tidak menggunakan pesan suara.
4.18
Telesignal
Pengawasan status dari peralatan operasional dalam jarak tertentu dengan menggunakan teknik telekomunikasi seperti kondisi alarm, posisi switch atau posisi katup. [IEV 371-0104]
4.19
Telemetering
Transmisi nilai variabel yang diukur dengan menggunakan teknik telekomunikasi. [IEV 371-01-03]
5. 5.1
Setiap pembangunan pembangkit, gardu induk, gardu hubung, gardu tengah, key point dan fasilitas sistem tenaga listrik yang baru harus dapat dipantau dari control center dan
dilakukan pengujian sebelum diintegrasikan ke sistem transmisi atau sistem distribusi tenaga listrik.
5.2
Teleinformasi data
Standar ini membedakan teleinformasi data untuk transmisi dan distribusi. Teleinformasi data untuk pemeliharaan instalasi sistem tenaga listrik dapat dilihat pada pada Lampiran A Daftar Teleinformasi (Transmisi) sampai dengan Lampiran D - Bidang Distribusi (Teleinformasi pada Berbagai Konfigurasi Jaringan Distribusi). Untuk daerah yang fungsi transmisi dan distribusi masih dalam satu organisasi maka master station dapat digunakan untuk fungsi RCC dan DCC. Dalam hal ini teleinformasi yang digunakan mengacu pada teleinformasi data transmisi dan distribusi. Teleinformasi data untuk pemeliharaan instalasi sistem tenaga listrik ditampilkan pada Maintenance Center dan Local HMI (Human Machine Interface). Konfigurasi workstation di luar control center yang difungsikan untuk Maintenance Center, menampilkan kebutuhan teleinformasi data untuk pemeliharaan instalasi sistem tenaga listrik, dapat dilihat pada SPLN S3.001: 2008 Butir 5.2 dan untuk Local HMI (Human Machine Interface) dapat dilihat pada SPLN S3.001: 2008 Butir 7.2. Setiap pembangunan SCADA untuk fasilitas sistem tenaga listrik, kebutuhan teleinformasi datanya harus mengacu pada SPLN S5.001:2008 Teleinformasi data untuk operasi jaringan tenaga listrik dan SPLN S5.002: 2008 Teleinformasi data untuk pemeliharaan instalasi sistem tenaga listrik.
5.3
Struktur informasi
Event dan alarm pemeliharaan merupakan informasi kepada regu pemeliharaan dan operator tentang kejadian pada peralatan sistem tenaga listrik yang tampil di monitor dan disimpan di data historikal. Struktur informasi event dan alarm SCADA dapat dilihat pada Lampiran E Struktur Informasi.
5.4
Simbol dan warna diperlukan untuk penyajian diagram sistem tenaga listrik pada monitor dan layar tayang. Simbol dan warna untuk tiap jenis dan kondisi peralatan bersifat informatif dan dipilih sedemikian rupa sehingga jenis dan kondisi peralatan tersebut mudah dikenali oleh regu pemeliharaan dan operator. Simbol dan warna dapat dilihat pada Lampiran F Simbol dan Warna.
6.
Teleinformasi data yang dikirim ke/dari suatu control center ditentukan oleh kewenangannya dalam operasi sistem, sehingga dibutuhkan adanya batas yang jelas antara kewenangan IRCC dan RCC serta RCC dan DCC. Berikut ini dijelaskan perbatasan kebutuhan teleinformasi data antara IRCC dan RCC serta antara RCC dan DCC.
6.1
Perbatasan kebutuhan teleinformasi data antara IRCC dan RCC adalah di titik pelayanan tegangan ekstra tinggi atau tegangan tinggi yang ditentukan, dan atau seperti Gambar 1 dan Gambar 2. a. Bila sisi sekunder IBT terhubung dengan konfigurasi double busbar
BUSBAR TET/TT
IRCC
RCC BUSBAR TT
BUSBAR TT
IRCC
RCC
BUSBAR TT
6.2
Perbatasan kebutuhan teleinformasi data antara RCC dan DCC di gardu induk ditunjukan pada Gambar 3.
BUSBAR TT
L /R P Q V I RCC
DCC
BUSBAR TM
Untuk daerah yang fungsi transmisi dan distribusi masih dalam satu organisasi (belum dipisahkan antara fungsi RCC dan DCC) maka perbatasan kebutuhan teleinformasi data dapat mengacu pada perbatasan fungsi RCC dan DCC atau disesuaikan dengan SOP yang berlaku di daerah tersebut.
A-1: Telesignal
Single (S) or Double (D) Indication D Alarm (A) or Event/ Indication (I) I
No
Kode
Fungsi
Implementasi Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor Capasitor Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor RTU Gardu induk, Kopel, Feeder, Diameter Gardu induk Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor Generator Generator Generator Generator Feeder, Trafo Gardu induk, Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor Trafo Generator Distribution Transformer Gardu induk Gardu induk, Kopel, Feeder, Trafo, Diameter Trafo Trafo Transformer Gardu Induk Gardu Induk Gardu Induk Gardu Induk Gardu Induk Gardu Induk Gardu Induk Gardu Induk Gardu Induk Gardu Induk Gardu Induk Generator
BI
CAM
Capasitor Auto/Manual
3 4 5 6 7 8 9 10 11 12
Circuit breaker closed/opened Control disable switch Check synchronizing override Dummy breaker closed/opened Earth Switch Closed/Opened Generator unit run/stop Load frequency available/not available Load frequency control on/off switch Load frequency request on/off Line isolator switch closed/opened
D D D D D D D D D D
I I I I I I I I I I
13
LR
Local remote
14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
LRT PSO RACK RMT SAM TC TCC TFAM 110RF 110SF 220F 220RF 220SF 24RF 24SF 380F 48RF 48SF AIRCF AQR
Local remote switch for tapchanger Power station operated Circuit Breaker Rack-In/Rack-Out Reset Master Trip Synchronization Auto/Manual Tap changer raise/lower Tap changer auto/manual Transformer Fan Auto/Manual 110 VDC Rectifier failure 110 VDC Supply failure 220 VAC Failure 220 VDC Rectifier failure 220 VDC Supply failure 24 VDC Rectifier failure 24 VDC Supply failure 380 VAC Failure 48 VDC Rectifier failure 48 VDC Supply failure Air conditioning failure Automatic power factor regulator
D D D D D D D D S S S S S S S S S S S S
I I I I I I I I A A A A A A A A A A A I
No
Kode active
Fungsi
Implementasi
34 35 36 37 38 39 40 41
Circuit breaker auto reclose Auto reclose off Automatic voltage regulator on/off Busbar protection (a) Busbar protection (a) failure Busbar protection (b) Busbar protection (b) failure Circuit breaker drive failure
42
CBFA
43
CBFB
44
CBM
Feeder Feeder Generator Busbar Busbar Busbar Busbar Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor, Generator Diameter Diameter Diameter Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Gardu induk Remote station Kopel, Feeder, Trafo, Capasitor, Reaktor Gardu Induk Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder
45
CBTR
Circuit breaker trip Circulating current protection (a) operate Circulating current protection (b) operate Circulating current protection failure Current differential relay (a) failure Current differential (a) phase R Current differential (a) phase S Current differential (a) phase T Current differential relay (b) failure Current differential (b) phase R Current differential (b) phase S Current differential (b) phase T Carrier faulty Check synchronizing in progress Cabinet temperatur DC supply failure DC ground Directional earth fault (a) relay receive Directional earth fault (a) relay transmit Directional earth fault (b) relay receive Directional earth fault (b) relay transmit Directional earth fault (a) failure Directional earth fault (a) phase r Directional earth fault (a) phase s Directional earth fault (a) phase t
46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69
CCPA CCPB CCPF CDAF CDAR CDAS CDAT CDBF CDBR CDBS CDBT CF CSP CTE DCF DCG DEARX DEATX DEBRX DEBTX DEFAF DEFAR DEFAS DEFAT
S S S S S S S S S S S S S S S S S S S S S S S S
A A A A A A A A A A A A I I A A A A A A A A A A
No 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112
Kode DEFBF DEFBR DEFBS DEFBT DFRF DIFF DOOR DSDF DTARX DTATX DTBRX DTBTX DZ1AR DZ1AS DZ1AT DZ1BR DZ1BS DZ1BT DZ2AR DZ2AS DZ2AT DZ2BR DZ2BS DZ2BT DZ3AR DZ3AS DZ3AT DZ3BR DZ3BS DZ3BT DZAF DZARX DZATX DZBF DZBRX DZBTX ERF FOTF FPO FRA FRSF GFRF GOV
Fungsi Directional earth fault (b) failure Directional earth fault (b) phase r Directional earth fault (b) phase s Directional earth fault (b) phase t Disturbance fault recorder faulty Differential failure Door activated Disconnecting switch driving fault Direct transfer trip (a) receive Direct transfer trip (a) transmit Direct transfer trip (b) receive Direct transfer trip (b) transmit Distance (a) phase R zone 1 Distance (a) phase S zone 1 Distance (a) phase T zone 1 Distance (b) phase R zone 1 Distance (b) phase S zone 1 Distance (b) phase T zone 1 Distance (a) phase R zone 2 Distance (a) phase S zone 2 Distance (a) phase T zone 2 Distance (b) phase R zone 2 Distance (b) phase S zone 2 Distance (b) phase T zone 2 Distance (a) phase R zone 3 Distance (a) phase S zone 3 Distance (a) phase T zone 3 Distance (b) phase R zone 3 Distance (b) phase S zone 3 Distance (b) phase T zone 3 Distance relay (a) failure Distance (a) relay receive Distance (a) relay transmit Distance relay (b) failure Distance (b) relay receive Distance (b) relay transmit Event recorder failure FO terminal faulty Fire protection operated Fire alarm Fire alarm system failure Ground fault relay failure Free acting governor active
Implementasi Feeder Feeder Feeder Feeder Gardu Induk Trafo Gardu Induk Busbar, Kopel, Feeder, Trafo, Capasitor Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Busbar, Kopel, Bus Section, Feeder, Trafo, Reaktor, Diameter Gardu Induk Trafo Gardu Induk Gardu Induk Gardu Induk, Kopel, Bus Section, Feeder, Trafo, Capasitor Generator
10
Fungsi Genset ready Generator transformer trip Internal remote station Load frequency control unit failure Low oil pressure cable trip
Implementasi Gardu Induk Trafo Generator Remote Station Generator Cable Feeder Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter, Generator Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter, Generator Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter, Generator Gardu Induk Cable Feeder Kopel, Bus Section, Feeder, Trafo, Capasitor Trafo Trafo Busbar, Feeder, Trafo, Capasitor Busbar, Feeder, Trafo, Capasitor Trafo, Capasitor, Reaktor Trafo Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor Kopel, Feeder, Bus Section, Trafo, Reaktor, Capasitor Gardu Induk Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter Gardu Induk
118
LPA
119
LPB
120
LPT
121 122 123 124 125 126 127 128 129 130
MTO OCPA OCRF OTA OTT OVR OVRF P1DIF P1REF P2GFR
Master trip operate Oil cable pressure alarm Over current relay failure Oil temperature alarm Oil temperatur trip Over voltage relay operate Over voltage relay failure Differential Restricted earth fault Ground fault relay
S S S S S S S S S S
A A A A A A A A A A
P2OCR PBXF PD
S S S
A A A
134
PHR
Trip phase R
135
PHS
Trip phase S
136 137
PHT PLCF
S S
A A
11
No
Kode
Fungsi
Implementasi Busbar, Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter Trafo, Reaktor Gardu induk Feeder Gardu Induk Reaktor Reaktor Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter Reaktor Trafo Reaktor Reaktor Reaktor Reaktor Reaktor Gardu Induk Gardu Induk Gardu Induk Gardu Induk Gardu induk Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter Trafo Trafo Trafo Trafo Trafo Trafo Trafo Trafo Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter
138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158
POT PRDT PTF PWF RADF RBUC2 RBUCA RCBF RCFF REFF RF RFDP ROLA RSPA RSPT RSTA RTN RTUA SIA SYNF SZPA
Protection on test Pressure relay device trip Protection faulty Pilot wire failure Radio link faulty Reaktor bucholz trip Reaktor bucholz alarm Relay circuit breaker fail failure Reaktor cooling fan failure Restrcited earth fault failure Reactor failure Reaktor fire detection & protection Reaktor oil level alarm Reaktor sudden pressure alarm Reaktor sudden pressure trip Reset alarm Relay tegangan nol Remote Station Alarm Station intruder alarm Synchronizing failure Short zone protection (a) operate
S S S S S S S S S S S S S S S S S S S
A A A A A A A A A A A A A I I A A A A
159
SZPB
160 161 162 163 164 165 166 167 168 169
SZPF TAF TBUC2 TBUCA TCA TCFF TCH TCL TCPF TCS1
Short zone protection failure Tranformer AVR failure Transformer Bucholz trip Transformer Bucholz alarm Tap changer alarm Transformer cooling fan failure Tap changer high limit Tap changer low limit Transformer cooling pump failure Trip coil supervisory 1
S S S S S S S S S S
A A A A A A A A A A
170
TCS2
12
No 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190
Kode TFDP TJANT TOLA TOOS TPAF TPBF TPIF TSPA TSPT UFR UT UVR UVRF VS VTF WTHVA WTHVT WTLVA WTLVT SIB
Fungsi Transformer fire detection & protection Transformer jansen trip Transformer oil level alarm Transformer out of step alarm Teleprotection (a) failure Teleprotection (b) failure Tap position indication failure Transformer sudden pressure alarm Transformer sudden pressure trip Under frequency relay operate Unit trip Under voltage relay Under voltage relay failure Voltage status Voltage transformer failure HV winding temperatur alarm HV winding temperatur trip LV winding temperatur alarm LV winding temperatur trip Software interlocking bypass
Implementasi Trafo Trafo Trafo Trafo Feeder Feeder Trafo Trafo Trafo Feeder, Trafo Generator Busbar Busbar, Feeder, Trafo Busbar Busbar, Feeder, Trafo, Capasitor Trafo Trafo Trafo Trafo Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter Trafo Trafo Trafo Trafo Trafo
S S S S S S S S S S S S S S S
A A A A A A A A I A A A A A A
191
IEDF
IED Faulty
192
SOTF
Switch on to fault Partial discharge (primary-secondarytersier) Online filtering OLTC Dissolve gas analysis Neutral voltage displacement (tersier) Tap changer trip
S S S S S
I I I I A
KETERANGAN: A = Announciation of abnormal condition (audible alarm, flashing display, etc) I = Event/Indication (normal condition)
13
A-2: Telemeasurement
No
Kode
Fungsi
Implementasi
AMF
Feeder, Trafo, Capasitor Reaktor Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor Feeder, Trafo
CCB
CNTA
Counter arester
CTPI
Trafo
Frekuensi
Gardu induk
6 7 8 9 10 11 12 13 14 15 16
Arus Kilovar hour Kilowatt hour Daya Aktif Real power setting Maksimum power variation setting Pressure Daya Reaktif Relative humidity Temperature Tegangan
Feeder, Trafo, Kopel Feeder, Trafo Feeder, Trafo Feeder, Trafo, Generator Generator Generator Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor Feeder, Trafo, Generator, Capasitor, Reaktor Gardu Induk Trafo, Reaktor Feeder, Trafo, Generator, Busbar
14
15
CB
CD
CSO
Gardu induk
DCBC
Remote Station Feeder, Transformer, Capasitor, Reaktor Gardu Induk, Kopel, Bus Section, Feeder, Transformer, Capasitor, Reaktor, Diameter Trafo
LI
LR
Local remote
LRT
RMT
Gardu Induk Gardu Induk, Kopel, Bus Section, Feeder, Transformer, Diameter Trafo
10
SAM
Synchronization auto/manual
11
TC
12
TCC
Trafo
13
TFAM
Trafo
16
17
P Q V
L/R
L/R
L/R
L/R
L/R
L/R BUSBAR -B V
L/R P Q V I
BAY TRANSMISI
P Q V I
L/R
P Q V I
BAY TRAFO TENAGA
BAY IBT
18
Teleinformasi Data Untuk Konfigurasi Umum Pada 1 Breaker Group Bay Data TM No 1 14 15 22 23 24 25 26 27 28 29 30 31 32 61 76 107 109 110 111 113 121 132 137 142 153 154 155 157 5 13 17 18 3 7 9 10 7 37 38 39 40 77 106 126 127 138 182 183 Kode F RH TEMP 110RF 110SF 220F 220RF 220SF 24RF 24SF 380F 48RF 48SF AIRCF DCG DOOR FOTF FRA FRSF GFRF GRE MTO PBXF PLCF RADF RSTA RTN RTUA SIA CSO LR RMT SAM CSO LR RMT SAM V BPA BPAF BPB BPBF DSDF ERF OVR OVRF POT UVR UVRF Fungsi Frekuensi Relative humidity Temperature 110 VDC rectifier failure 110 VDC supply failure 220 VAC failure 220 VDC rectifier failure 220 VDC supply failure 24 VDC rectifier failure 24 VDC supply failure 380 VAC failure 48 VDC rectifier failure 48 VDC supply failure Air conditioning failure DC ground Door activated FO terminal faulty Fire alarm Fire alarm system failure Ground fault relay failure Genset ready Master trip operate Pabx faulty PLC terminal faulty Radio link faulty Reset alarm Relay tegangan nol Remote station alarm Station intruder alarm Check synchronizing override Local remote Reset master trip Synchronization auto/manual Check synchronizing override Local remote Reset master trip Synchronization auto/manual Tegangan Busbar protection (a) Busbar protection (a) failure Busbar protection (b) Busbar protection (b) failure Disconnecting switch driving fault Event recorder failure Over voltage relay operate Over voltage relay failure Protection on test Under voltage relay operate Under voltage relay failure Tipe Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2
TSS
GARDU INDUK
TSD
A A A A A A A A A A A A A A A A A I A A A A A A A A I I I I
RCD TM
BUSBAR
TSS
A A A A A A A A I A A
19
Group Bay
No 184 7 59 115 4 3 5 2 12 41 42 43 44 46 47 48 58 106 118 119 120 121 133 134 135 136 138 145 157 158 159 160 169 170 190 191 192 1
Kode VS ES CTE IR CD CD DCBC CCB PRES CBDF CBFA CBFB CBM CCPA CCPB CCPF CSP ERF LPA LPB LPT MTO PD PHR PHS PHT POT RCBF SYNF SZPA SZPB SZPF TCS1 TCS2 SIB IEDF SOTF BI CB CSO LR SAM BI CB CSO
Fungsi Voltage status Earth switch closed/opened Cabinet temperatur Internal remote station Control disable switch Control disable switch Dummy circuit breaker closed/opened Counter of circuit breaker Pressure Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance Circulating current protection (a) operate Circulating current protection (b) operate Circulating current protection failure Check synchronizing in progress Event recorder failure Low pressure alarm Low pressure block Low pressure trip Master trip operate Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Relay circuit breaker fail failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Trip coil supervisory 1 Trip coil supervisory 2 Software interlocking bypass IED Faulty Switch on to fault Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Local remote Synchronization auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override
Tipe I I A A I
Jmh 2 2 1 1 1 1 1 3 3 3 3 3 3 1 1 3 3 3 3 3 3 1 3 3 3 3 1 3 3 3 3 3 3 3 3 3 3 6 3 3 3 3 6 3 3
REMOTE STATION
TSD RCD TM
A A A I A A A I A A A A A A A A A I A A A A A A A A A A I I I I I
TSS
DIAMETER
TSD
3 5 13 18 1
RCD
2 4
20
Group Bay
Data
No 7 10 1 3 6 7 8 9 12 13 16 49 50 51 52 53 54 55 56 57 58 60 62
Kode LR SAM AMF CNTA *) I KVARH KWH P PRES Q V CDAF CDAR CDAS CDAT CDBF CDBR CDBS CDBT CF *) CSP DCF DEARX *) DEATX *) DEBRX *) DEBTX *) DEFAF *) DEFAR DEFAS DEFAT DEFBF *) DEFBR DEFBS DEFBT DFRF DSDF DTARX *) DTATX *) DTBRX *) DTBTX *) DZ1AR *) DZ1AS *) DZ1AT *) DZ1BR *) DZ1BS *)
Fungsi Local remote Synchronization auto/manual Amperes fault ( per phase ) Counter arester Arus Kilovar hour Kilowatt hour Daya aktif Pressure Daya reaktif Tegangan Current differential relay (a) failure Current differential (a) phase R Current differential (a) phase S Current differential (a) phase T Current differential relay (b) failure Current differential (b) phase R Current differential (b) phase S Current differential (b) phase T Carrier faulty Check synchronizing in progress DC supply failure Directional earth fault (a) relay receive Directional earth fault (a) relay transmit Directional earth fault (b) relay receive Directional earth fault (b) relay transmit Directional earth fault (a) failure Directional earth fault (a) phase R Directional earth fault (a) phase S Directional earth fault (a) phase T Directional earth fault (b) failure Directional earth fault (b) phase R Directional earth fault (b) phase S Directional earth fault (b) phase T Disturbance fault recorder faulty Disconnecting switch driving fault Direct transfer trip (a) receive Direct transfer trip (a) transmit Direct transfer trip (b) receive Direct transfer trip (b) transmit Distance (a) phase R zone 1 Distance (a) phase S zone 1 Distance (a) phase T zone 1 Distance (b) phase R zone 1 Distance (b) phase S zone 1
Tipe
Jmh 3 3 1 1 1 1 1 1 1 1 1
TM
A A A A A A A A A I A A A A A A A A A A A A A A A I I I I A A A A A
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
BAY TRANSMISI
63 64 TSS 65 66 67 68 69 70 71 72 73 74 77 78 79 80 81 82 83 84 85 86
21
Group Bay
Data
No 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 111 117 121 122 123 126 127 130 131 138 141 145 157 158 159 160 175 176 180 182 183 185 190 191 192 7
Kode DZ1BT DZ2AR *) DZ2AS *) DZ2AT *) DZ2BR *) DZ2BS *) DZ2BT *) DZ3AR *) DZ3AS *) DZ3AT *) DZ3BR *) DZ3BS *) DZ3BT *) DZAF *) DZARX *) DZATX *) DZBF *) DZBRX *) DZBTX *) ERF GFRF LOWCT** ) MTO OCPA**) OCRF OVR *) OVRF *) P2GFR P2OCR POT PWF RCBF SYNF SZPA SZPB SZPF TPAF *) TPBF *) UFR UVR *) UVRF *) VTF SIB IEDF SOTF ES LI LI
*)
Fungsi Distance (b) phase T zone 1 Distance (a) phase R zone 2 Distance (a) phase S zone 2 Distance (a) phase T zone 2 Distance (b) phase R zone 2 Distance (b) phase S zone 2 Distance (b) phase T zone 2 Distance (a) phase R zone 3 Distance (a) phase S zone 3 Distance (a) phase T zone 3 Distance (b) phase R zone 3 Distance (b) phase S zone 3 Distance (b) phase T zone 3 Distance relay (a) failure Distance (a) relay receive Distance (a) relay transmit Distance relay (b) failure Distance (b) relay receive Distance (b) relay transmit Event recorder failure Ground fault relay failure Low oil pressure cable trip Master trip operate Oil cable pressure alarm Over current relay failure Over voltage relay operate Over voltage relay failure Ground fault relay Over current relay Protection on test Pilot wire failure Relay circuit breaker fail failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Teleprotection (a) failure Teleprotection (b) failure Under frequency relay operate Under voltage relay operate Under voltage relay failure Voltage transformer failure Software interlocking bypass IED Faulty Switch on to fault Earth switch closed/opened Line isolator switch closed/opened Line isolator switch
Tipe A A A A A A A A A A A A A A I I A I I A A A A A A A A A A I A A A A A A A A A A A A A A A I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSD RCD
12 6
22
Group Bay
Data TC
No 1 1 3 4 6 7 8 9 12 13 15 16 41 42 43 44 58 60 74 75 77 106 108 111 118 119 120 121 123 124 125 128 129 130 131 133 134 135 136 138 139 145 147 157 158 159 160 161
Kode TPI AMF CNTA CTPI I KVARH KWH P PRES Q TEMP V CBDF CBFA CBFB CBM CSP DCF DFRF DIFF DSDF ERF FPO GFRF LPA LPB LPT MTO OCRF OTA OTT P1DIF P1REF P2GFR P2OCR PD PHR PHS PHT POT PRDT RCBF REFF SYNF SZPA SZPB SZPF TAF
Fungsi closed/opened Tap position indication Amperes fault ( per phase ) Counter arester Counter tap position indication Arus Kilovar hour Kilowatt hour Daya aktif Pressure Daya reaktif Temperature Tegangan Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance Check synchronizing in progress DC supply failure Disturbance fault recorder faulty Differential failure Disconnecting switch driving fault Event recorder failure Fire protection operated Ground fault relay failure Low pressure alarm Low pressure block Low pressure trip Master trip operate Over current relay failure Oil temperature alarm Oil temperatur trip Differential Restricted earth fault Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pressure relay device trip Relay circuit breaker fail failure Restricted earth fault failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Tranformer AVR failure
Tipe I
Jmh 3 3 3 3 3 1 1 1 3 1 12 3 1 1 1 1 1 1 1 1 1 1 3 1 1 1 1 1 1 3 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3
TM
BAY IBT
TSS
A A A I I A A A A A A A A A A A A A A A A A A A A A A I A A A A A A A A
23
Group Bay
Data
No 162 163 164 165 166 167 168 169 170 171 172 173 174 177 178 179 180 185 186 187 188 189 190 191 192 193 194 195 196 197 3 5 7 12
Kode TBUC2 TBUCA TCA TCFF TCH TCL TCPF TCS1 TCS2 TFDP TJANT TOLA TOOS TPIF TSPA TSPT UFR VTF WTHVA WTHVT WTLVA WTLVT SIB IEDF SOTF PD OFO DGA NVD TCT CB CSO ES LI LR LRT SAM TCC TFAM CB CSO LI LR LRT
Fungsi Transformer bucholz trip Transformer bucholz alarm Tap changer alarm Transformer cooling fan failure Tap changer high limit Tap changer low limit Transformer cooling pump failure Trip coil supervisory 1 Trip coil supervisory 2 Transformer fire detection & protection Transformer jansen trip Transformer oil level alarm Transformer out of step alarm Tap position indication failure Transformer sudden pressure alarm Transformer sudden pressure trip Under frequency relay operate Voltage transformer failure HV winding temperatur alarm HV winding temperatur trip LV winding temperatur alarm LV winding temperatur trip Software interlocking bypass IED Faulty Switch on to fault Partial discharge (primarysecondary-tersier) Online filtering OLTC Dissolve gas analysis Neutral voltage displacement (tersier) Tap changer trip Circuit breaker closed/opened Check synchronizing override Earth switch closed/opened Line isolator switch closed/opened Local remote Local/remote switch for tapchanger Synchronization auto/manual Tap changer auto/manual Transformer fan auto/manual Circuit breaker closed/opened Check synchronizing override Line isolator switch closed/opened Local remote Local/remote switch for
Tipe A A A A A A A A A A A A A A A A A A A A A A A A A I I I I A I I I I I I I I I
Jmh 3 3 3 3 3 3 3 1 1 3 3 3 3 3 3 3 1 3 3 3 3 3 1 1 1 9 3 3 3 3 1 1 2 1 1 3 1 3 3 1 1 1 1 3
TSD
13 14 18 20 21 2 4
RCD
6 7 8
24
Group Bay
Data
No 10 11 12 13 1 1 3 4 6 7 8 9 12 13 15 16 60 74 75 77 106 108 111 121 123 124 125 126 127 128 129 130 131 138 139 145 147 158 159 160 161 162 163 164 165 166 167 168
Kode SAM TC TCC TFAM TPI AMF CNTA CTPI I KVARH KWH P PRES Q TEMP V DCF DFRF DIFF DSDF ERF FPO GFRF MTO OCRF OTA OTT OVR OVRF P1DIF P1REF P2GFR P2OCR POT PRDT RCBF REFF SZPA SZPB SZPF TAF TBUC2 TBUCA TCA TCFF TCH TCL TCPF
Fungsi tapchanger Synchronization auto/manual Tap changer raise/lower Tap changer auto/manual Transformer fan auto/manual Tap position indication Amperes fault ( per phase ) Counter arester Counter tap position indication Arus Kilovar hour Kilowatt hour Daya aktif Pressure Daya reaktif Temperature Tegangan DC supply failure Disturbance fault recorder faulty Differential failure Disconnecting switch driving fault Event recorder failure Fire protection operated Ground fault relay failure Master trip operate Over current relay failure Oil temperature alarm Oil temperatur trip Over voltage relay operate Over voltage relay failure Differential Restricted earth fault Ground fault relay Over current relay Protection on test Pressure relay device trip Relay circuit breaker fail failure Restricted earth fault failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Tranformer avr failure Transformer bucholz trip Transformer bucholz alarm Tap changer alarm Transformer cooling fan failure Tap changer high limit Tap changer low limit Transformer cooling pump failure
Tipe
Jmh 1 3 3 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TC
TM
TSS
A A A A A A A A A A A A A A A A A I A A A A A A A A A A A A A A
25
Group Bay
Data
No 171 172 173 174 177 178 179 180 182 183 185 186 187 188 189 190 191 192 7 12
Kode TFDP TJANT TOLA TOOS TPIF TSPA TSPT UFR UVR UVRF VTF WTHVA WTHVT WTLVA WTLVT SIB IEDF SOTF ES LI LRT TCC TFAM LI LRT TC TCC TFAM AMF PRES Q TEMP DCF DFRF ERF MTO P1DIF P2GFR P2OCR POT PRDT RCBF RF SZPA SZPB
Fungsi Transformer fire detection & protection Transformer jansen trip Transformer oil level alarm Transformer out of step alarm Tap position indication failure Transformer sudden pressure alarm Transformer sudden pressure trip Under frequency relay operate Under voltage relay operate Under voltage relay failure Voltage transformer failure HV winding temperatur alarm HV winding temperatur trip LV winding temperatur alarm LV winding temperatur trip Software interlocking bypass IED Faulty Switch on to fault Earth switch closed/opened Line isolator switch closed/opened Local/remote switch for tapchanger Tap changer auto/manual Transformer fan auto/manual Line isolator switch closed/opened Local/remote switch for tapchanger Tap changer raise/lower Tap changer auto/manual Transformer fan auto/manual Amperes fault ( per phase ) Pressure Daya reaktif Temperature DC supply failure Disturbance fault recorder faulty Event recorder failure Master trip operate Differential Ground fault relay Over current relay Protection on test Pressure relay device trip Relay circuit breaker fail failure Reaktor failure Short zone protection (a) operate Short zone protection (b) operate
Tipe A A A A A A A A A A A A A A A A A A I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSD
14 20 21 6
RCD
8 11 12 13 1 12 13 15 60 74 106 121 128 130 131 138 139 145 148 158 159
TM
A A A A A A A A A A A A A
26
Group Bay
Data
Kode SZPF SIB IEDF SOTF ES LI TFAM LI TFAM I KVARH KWH P Q V DFRF DIFF ERF GTT MTO P1REF P2GFR P2OCR POT REFF SIB IEDF SOTF ES LI LI
Fungsi Short zone protection failure Software interlocking bypass IED Faulty Switch on to fault Earth switch closed/opened Line isolator switch closed/opened Transformer fan auto/manual Line isolator switch closed/opened Transformer fan auto/manual Arus Kilovar hour Kilowatt hour Daya aktif Daya reaktif Tegangan Disturbance fault recorder faulty Differential failure Event recorder failure Generator transformer trip Master trip operate Restricted earth fault Ground fault relay Over current relay Protection on test Restricted earth fault failure Software interlocking bypass IED Faulty Switch on to fault Earth switch closed/opened Line isolator switch closed/opened Line isolator switch closed/opened
Tipe A A A A I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSD
12 21
RCD
6 13 6 7 8 9 13 16 74 75 106 114 121 129 130 131 138 147 190 191 192 7 12 6
TM
BAY GENERATOR
TSS
A A A A A A A A A A A A A I I
TSD RCD
KETERANGAN: *) = Khusus untuk OHL Feeder **) = Khusus untuk Cable Feeder A = Alarm I = Indikasi Rincian Teleinformasi diatas adalah rincian per bay
27
P Q V
P Q I
BAY KOPEL
L/R
L/R I
L/R
BUSBAR - A V
BUSBAR - B V
L/R
L/R
L/R
L/R P Q V I
BAY TRANSMISI
P Q V I
BAY TRAFO TENAGA
P Q V I
BAY IBT
Teleinformasi Data Untuk Konfigurasi Umum Pada Double Busbar Group Bay Data TM No 1 14 15 22 23 24 25 26 27 28 29 Kode F RH TEMP 110RF 110SF 220F 220RF 220SF 24RF 24SF 380F Fungsi Frekuensi Relative humidity Temperature 110 VDC rectifier failure 110 VDC supply failure 220 VAC failure 220 VDC rectifier failure 220 VDC supply failure 24 VDC rectifier failure 24 VDC supply failure 380 VAC failure Tipe Jmh 1 1 1 1 1 1 1 1 1 1 1
GARDU INDUK
TSS
A A A A A A A A
28
Group Bay
Data
No 30 31 32 61 76 107 109 110 111 113 132 137 142 153 154 155 157 5 13 17 18 3 7 9 10 7 37 38 39 40 77 106 126 127 138 182 183 184 7 59 115 4 3 5 2 6 12 41 42
Kode 48RF 48SF AIRCF DCG DOOR FOTF FRA FRSF GFRF GRE PBXF PLCF RADF RSTA RTN RTUA SIA CSO LR RMT SAM CSO LR RMT SAM V BPA BPAF BPB BPBF DSDF ERF OVR OVRF POT UVR UVRF VS ES CTE IR CD CD DCBC CCB I PRES CBDF CBFA
Fungsi 48 VDC rectifier failure 48 VDC supply failure Air conditioning failure DC ground Door activated FO terminal faulty Fire alarm Fire alarm system failure Ground fault relay failure Genset ready Pabx faulty PLC terminal faulty Radio link faulty Reset alarm Relay tegangan nol Remote station alarm Station intruder alarm Check synchronizing override Local remote Reset master trip Synchronization auto/manual Check synchronizing override Local remote Reset master trip Synchronization auto/manual Tegangan Busbar protection (a) Busbar protection (a) failure Busbar protection (b) Busbar protection (b) failure Disconnecting switch driving fault Event recorder failure Over voltage relay operate Over voltage relay failure Protection on test Under voltage relay operate Under voltage relay failure Voltage status Earth switch closed/opened Cabinet temperatur Internal remote station Control disable switch Control disable switch Dummy circuit breaker closed/opened Counter of circuit breaker Arus Pressure Circuit breaker drive failure Circuit breaker failure (a) operate
Tipe A A A A A A A A A I A A A A A A A I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 2 2 1 1 1 1 1 1 1 1 1 1
TSD
RCD TM
BUSBAR
TSS
A A A A A A A A I A A I I A A I
A A
29
Group Bay
Data
No 43 44 58 60 77 106 111 118 119 120 121 123 130 131 133 134 135 136 138 145 157 158 159 160 169 170 190 191 192 1 3 5 13 18 1 2 4 7 10 1 2 3 6 7 8 9 12 13 16
Kode CBFB CBM CSP DCF DSDF ERF GFRF LPA LPB LPT MTO OCRF P2GFR P2OCR PD PHR PHS PHT POT RCBF SYNF SZPA SZPB SZPF TCS1 TCS2 SIB IEDF SOTF BI CB CSO LR SAM BI CB CSO LR SAM AMF CCB CNTA *) I KVARH KWH P PRES Q V
Fungsi Circuit breaker failure (b) operate Circuit breaker maintenance Check synchronizing in progress DC supply failure Disconnecting switch driving fault Event recorder failure Ground fault relay failure Low pressure alarm Low pressure block Low pressure trip Master trip operate Over current relay failure Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Relay circuit breaker fail failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Trip coil supervisory 1 Trip coil supervisory 2 Software interlocking bypass IED Faulty Switch on to fault Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Local remote Synchronization auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Local remote Synchronization auto/manual Amperes fault ( per phase ) Counter of circuit breaker Counter arester Arus Kilovar hour Kilowatt hour Daya aktif Pressure Daya reaktif Tegangan
Tipe A I I A A A A A A A A A A A A A A A I A A A A A A A A A A I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSD
RCD
BAY TRANSMISI
TM
30
Group Bay
Data
No 34 35 41 42 43 44 49 50 51 52 53 54 55 56 57 58 60 62 63 64 65
Kode AR ARO *) CBDF CBFA CBFB CBM CDAF CDAR CDAS CDAT CDBF CDBR CDBS CDBT CF *) CSP DCF DEARX *) DEATX *) DEBRX *) DEBTX *) DEFAF DEFAR DEFAS DEFAT DEFBF *) DEFBR DEFBS DEFBT DFRF DSDF DTARX *) DTATX *) DTBRX *) DTBTX *) DZ1AR *) DZ1AS *) DZ1AT *) DZ1BR *) DZ1BS *) DZ1BT *) DZ2AR *) DZ2AS *) DZ2AT *) DZ2BR *) DZ2BS *)
*) *)
Fungsi Circuit breaker auto reclose Auto reclose off Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance Current differential relay (a) failure Current differential (a) phase R Current differential (a) phase S Current differential (a) phase T Current differential relay (b) failure Current differential (b) phase R Current differential (b) phase S Current differential (b) phase T Carrier faulty Check synchronizing in progress DC supply failure Directional earth fault (a) relay receive Directional earth fault (a) relay transmit Directional earth fault (b) relay receive Directional earth fault (b) relay transmit Directional earth fault (a) failure Directional earth fault (a) phase R Directional earth fault (a) phase S Directional earth fault (a) phase T Directional earth fault (b) failure Directional earth fault (b) phase R Directional earth fault (b) phase S Directional earth fault (b) phase T Disturbance fault recorder faulty Disconnecting switch driving fault Direct transfer trip (a) receive Direct transfer trip (a) transmit Direct transfer trip (b) receive Direct transfer trip (b) transmit Distance (a) phase R zone 1 Distance (a) phase S zone 1 Distance (a) phase T zone 1 Distance (b) phase R zone 1 Distance (b) phase S zone 1 Distance (b) phase T zone 1 Distance (a) phase R zone 2 Distance (a) phase S zone 2 Distance (a) phase T zone 2 Distance (b) phase R zone 2 Distance (b) phase S zone 2
Tipe I I A A A I A A A A A A A A A I A A A A A A A A A A A A A A A I I I I A A A A A A A A A A A
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSS
66 67 68 69 70 71 72 73 74 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92
31
Group Bay
Data
No 93 94 95 96 97 98 99 100 101 102 103 104 105 106 111 117 118 119 120 121 122 123 126 127 130 131 133 134 135 136 138 141 145 157 158 159 160 169 170 175 176 180 182 183 185 190 191 192 1
Kode DZ2BT DZ3AR *) DZ3AS *) DZ3AT *) DZ3BR *) DZ3BS *) DZ3BT *) DZAF *) DZARX *) DZATX *) DZBF *) DZBRX *) DZBTX *) ERF GFRF LOWCT** ) LPA LPB LPT MTO OCPA**) OCRF OVR *) OVRF *) P2GFR P2OCR PD PHR PHS PHT POT PWF RCBF SYNF SZPA SZPB SZPF TCS1 TCS2 TPAF *) TPBF *) UFR UVR *) UVRF *) VTF SIB IEDF SOTF BI
*)
Fungsi Distance (b) phase T zone 2 Distance (a) phase R zone 3 Distance (a) phase S zone 3 Distance (a) phase T zone 3 Distance (b) phase R zone 3 Distance (b) phase S zone 3 Distance (b) phase T zone 3 Distance relay (a) failure Distance (a) relay receive Distance (a) relay transmit Distance relay (b) failure Distance (b) relay receive Distance (b) relay transmit Event recorder failure Ground fault relay failure Low oil pressure cable trip Low pressure alarm Low pressure block Low pressure trip Master trip operate Oil cable pressure alarm Over current relay failure Over voltage relay operate Over voltage relay failure Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pilot wire failure Relay circuit breaker fail failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Trip coil supervisory 1 Trip coil supervisory 2 Teleprotection (a) failure Teleprotection (b) failure Under frequency relay operate Under voltage relay operate Under voltage relay failure Voltage transformer failure Software interlocking bypass IED Faulty Switch on to fault Bus isolator switch closed/opened
Tipe A A A A A A A A I I A I I A A A A A A A A A A A A A A A A A I A A A A A A A A A A A A A A A A A I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2
TSD
32
Group Bay
Data
No 3 5 7 12 13 18 1 2 4 6 7 10 1 1 2 3 4 6 7 8 9 12 13 15 16 41 42 43 44 58 60 74 75 77 106 108 111 118 119 120 121 123 124 125 128 129 130 131 133
Kode CB CSO ES LI LR SAM BI CB CSO LI LR SAM TPI AMF CCB CNTA CTPI I KVARH KWH P PRES Q TEMP V CBDF CBFA CBFB CBM CSP DCF DFRF DIFF DSDF ERF FPO GFRF LPA LPB LPT MTO OCRF OTA OTT P1DIF P1REF P2GFR P2OCR PD
Fungsi Circuit breaker closed/opened Check synchronizing override Earth switch closed/opened Line isolator switch closed/opened Local remote Synchronization auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Line isolator switch closed/opened Local remote Synchronization auto/manual Tap position indication Amperes fault ( per phase ) Counter of circuit breaker Counter arester Counter tap position indication Arus Kilovar hour Kilowatt hour Daya aktif Pressure Daya reaktif Temperature Tegangan Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance Check synchronizing in progress DC supply failure Disturbance fault recorder faulty Differential failure Disconnecting switch driving fault Event recorder failure Fire protection operated Ground fault relay failure Low pressure alarm Low pressure block Low pressure trip Master trip operate Over current relay failure Oil temperature alarm Oil temperatur trip Differential Restricted earth fault Ground fault relay Over current relay Pole discrepancy
Tipe I I I I I I
Jmh 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
RCD
TC
TM
BAY IBT
TSS
A A A I I A A A A A A A A A A A A A A A A A A A
33
Group Bay
Data
No 134 135 136 138 139 145 147 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 177 178 179 180 185 186 187 188 189 190 191 192 197 1 3 5 7 13 14 18 20 21 1 2
Kode PHR PHS PHT POT PRDT RCBF REFF SYNF SZPA SZPB SZPF TAF TBUC2 TBUCA TCA TCFF TCH TCL TCPF TCS1 TCS2 TFDP TJANT TOLA TOOS TPIF TSPA TSPT UFR VTF WTHVA WTHVT WTLVA WTLVT SIB IEDF SOTF TCT BI CB CSO ES LR LRT SAM TCC TFAM BI CB
Fungsi Trip phase R Trip phase S Trip phase T Protection on test Pressure relay device trip Relay circuit breaker fail failure Restricted earth fault failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Tranformer AVR failure Transformer bucholz trip Transformer bucholz alarm Tap changer alarm Transformer cooling fan failure Tap changer high limit Tap changer low limit Transformer cooling pump failure Trip coil supervisory 1 Trip coil supervisory 2 Transformer fire detection & protection Transformer jansen trip Transformer oil level alarm Transformer out of step alarm Tap position indication failure Transformer sudden pressure alarm Transformer sudden pressure trip Under frequency relay operate Voltage transformer failure HV winding temperatur alarm HV winding temperatur trip LV winding temperatur alarm LV winding temperatur trip Software interlocking bypass IED Faulty Switch on to fault Tap changer trip Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Earth switch closed/opened Local remote Local/remote switch for tapchanger Synchronization auto/manual Tap changer auto/manual Transformer fan auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened
Tipe A A A I A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A I I I I I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 2 1 1 1 1 1 2 1
TSD
RCD
34
Group Bay
Data
No 4 7 8 10 11 12 13 1 1 2 3 4 6 7 8 9 12 13 15 16 41 42 43 44 60 74 75 77 106 108 111 118 119 120 121 123 124 125 126 127 128 129 130 131 133 134 135 136 138
Kode CSO LR LRT SAM TC TCC TFAM TPI AMF CCB CNTA CTPI I KVARH KWH P PRES Q TEMP V CBDF CBFA CBFB CBM DCF DFRF DIFF DSDF ERF FPO GFRF LPA LPB LPT MTO OCRF OTA OTT OVR OVRF P1DIF P1REF P2GFR P2OCR PD PHR PHS PHT POT
Fungsi Check synchronizing override Local remote Local/remote switch for tapchanger Synchronization auto/manual Tap changer raise/lower Tap changer auto/manual Transformer fan auto/manual Tap position indication Amperes fault ( per phase ) Counter of circuit breaker Counter arester Counter tap position indication Arus Kilovar hour Kilowatt hour Daya aktif Pressure Daya reaktif Temperature Tegangan Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance DC supply failure Disturbance fault recorder faulty Differential failure Disconnecting switch driving fault Event recorder failure Fire protection operated Ground fault relay failure Low pressure alarm Low pressure block Low pressure trip Master trip operate Over current relay failure Oil temperature alarm Oil temperatur trip Over voltage relay operate Over voltage relay failure Differential Restricted earth fault Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test
Tipe
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TC
TM
TSS
A A A I A A A A A A A A A A A A A A A A A A A A A A A A I
35
Group Bay
Data
No 139 145 147 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 177 178 179 180 182 183 185 186 187 188 189 190 191 192 1 3 7 13 14 16 20 21 1 2 7 8 11 12 13
Kode PRDT RCBF REFF SZPA SZPB SZPF TAF TBUC2 TBUCA TCA TCFF TCH TCL TCPF TCS1 TCS2 TFDP TJANT TOLA TOOS TPIF TSPA TSPT UFR UVR UVRF VTF WTHVA WTHVT WTLVA WTLVT SIB IEDF SOTF BI CB ES LR LRT RACK TCC TFAM BI CB LR LRT TC TCC TFAM
Fungsi Pressure relay device trip Relay circuit breaker fail failure Restricted earth fault failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Tranformer avr failure Transformer bucholz trip Transformer bucholz alarm Tap changer alarm Transformer cooling fan failure Tap changer high limit Tap changer low limit Transformer cooling pump failure Trip coil supervisory 1 Trip coil supervisory 2 Transformer fire detection & protection Transformer jansen trip Transformer oil level alarm Transformer out of step alarm Tap position indication failure Transformer sudden pressure alarm Transformer sudden pressure trip Under frequency relay operate Under voltage relay operate Under voltage relay failure Voltage transformer failure HV winding temperatur alarm HV winding temperatur trip LV winding temperatur alarm LV winding temperatur trip Software interlocking bypass IED Faulty Switch on to fault Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened Local remote Local/remote switch for tapchanger Circuit breaker rackin/rackout Tap changer auto/manual Transformer fan auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Local remote Local/remote switch for tapchanger Tap changer raise/lower Tap changer auto/manual Transformer fan auto/manual
Tipe A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A I I I I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 2 1 1 1 1 1 1
TSD
RCD
36
Group Bay
Data
No 1 2 12 13 15 41 42 43 44 60 74 106 118 119 120 121 128 130 131 133 134 135 136 138 139 145 148 158 159 160 169 170 190 191 192 1 3 7 12 13 21 1 2 6 7 13 6 7 8
Kode AMF CCB PRES Q TEMP CBDF CBFA CBFB CBM DCF DFRF ERF LPA LPB LPT MTO P1DIF P2GFR P2OCR PD PHR PHS PHT POT PRDT RCBF RF SZPA SZPB SZPF TCS1 TCS2 SIB IEDF SOTF BI CB ES LI LR TFAM BI CB LI LR TFAM I KVARH KWH
Fungsi Amperes fault ( per phase ) Counter of circuit breaker Pressure Daya reaktif Temperature Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance DC supply failure Disturbance fault recorder faulty Event recorder failure Low pressure alarm Low pressure block Low pressure trip Master trip operate Differential Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pressure relay device trip Relay circuit breaker fail failure Reaktor failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Trip coil supervisory 1 Trip coil supervisory 2 Software interlocking bypass IED Faulty Switch on to fault Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened Line isolator switch closed/opened Local remote Transformer fan auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Line isolator switch closed/opened Local remote Transformer fan auto/manual Arus Kilovar hour Kilowatt hour
Tipe
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 2 1 1 1 1 1 1 1
TM
TSD
A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A I I I I I I
RCD
BAY GENERATOR
TM
37
Group Bay
Data
No 9 13 16 41 44 58 74 75 106 114 118 119 120 121 129 130 131 133 134 135 136 138 147 157 169 170 190 191 192 1 3 7 12 13 1 2 6 7
Kode P Q V CBDF CBM CSP DFRF DIFF ERF GTT LPA LPB LPT MTO P1REF P2GFR P2OCR PD PHR PHS PHT POT REFF SYNF TCS1 TCS2 SIB IEDF SOTF BI CB ES LI LR BI CB LI LR
Fungsi Daya aktif Daya reaktif Tegangan Circuit breaker drive failure Circuit breaker maintenance Check synchronizing in progress Disturbance fault recorder faulty Differential failure Event recorder failure Generator transformer trip Low pressure alarm Low pressure block Low pressure trip Master trip operate Restricted earth fault Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Restricted earth fault failure Synchronizing failure Trip coil supervisory 1 Trip coil supervisory 2 Software interlocking bypass IED Faulty Switch on to fault Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened Line isolator switch closed/opened Local remote Bus isolator switch closed/opened Circuit breaker closed/opened Line isolator switch closed/opened Local remote
Tipe
Jmh 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 2 1 1 1
TSS
TSD
A A A A A A A A A A A A A A A A A A A A A A A A A A I I I I I
RCD
KETERANGAN: *) = Khusus untuk OHL Feeder **) = Khusus untuk Cable Feeder A = Alarm I = Indikasi Rincian Teleinformasi diatas adalah rincian per bay
38
P Q V P Q I L/R L/R
BUSBAR V
L/R
L/R
L/R
L/R P Q V I
BAY TRANSMISI
P Q V I
BAY TRAFO TENAGA
P Q V I
BAY IBT
Teleinformasi Data Untuk Konfigurasi Umum Pada Single Busbar Group Bay Data TM No 1 14 15 22 23 24 25 26 27 28 29 30 31 32 Kode F RH TEMP 110RF 110SF 220F 220RF 220SF 24RF 24SF 380F 48RF 48SF AIRCF Fungsi Frekuensi Relative humidity Temperature 110 VDC rectifier failure 110 VDC supply failure 220 VAC failure 220 VDC rectifier failure 220 VDC supply failure 24 VDC rectifier failure 24 VDC supply failure 380 VAC failure 48 VDC rectifier failure 48 VDC supply failure Air conditioning failure Tipe Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1
GARDU INDUK
TSS
A A A A A A A A A A A
39
Group Bay
Data
No 61 76 107 109 110 111 113 132 137 142 153 154 155 157 5 13 17 18 3 7 9 10 7 37 38 39 40 77 106 126 127 138 182 183 184 7 59 115 4 3 5 1 2 3 6 7 8 9 12
Kode DCG DOOR FOTF FRA FRSF GFRF GRE PBXF PLCF RADF RSTA RTN RTUA SIA CSO LR RMT SAM CSO LR RMT SAM V BPA BPAF BPB BPBF DSDF ERF OVR OVRF POT UVR UVRF VS ES CTE IR CD CD DCBC AMF CCB CNTA *) I KVARH KWH P PRES
Fungsi DC ground Door activated FO terminal faulty Fire alarm Fire alarm system failure Ground fault relay failure Genset ready Pabx faulty PLC terminal faulty Radio link faulty Reset alarm Relay tegangan nol Remote station alarm Station intruder alarm Check synchronizing override Local remote Reset master trip Synchronization auto/manual Check synchronizing override Local remote Reset master trip Synchronization auto/manual Tegangan Busbar protection (a) Busbar protection (a) failure Busbar protection (b) Busbar protection (b) failure Disconnecting switch driving fault Event recorder failure Over voltage relay operate Over voltage relay failure Protection on test Under voltage relay operate Under voltage relay failure Voltage status Earth switch closed/opened Cabinet temperatur Internal remote station Control disable switch Control disable switch Dummy circuit breaker closed/opened Amperes fault ( per phase ) Counter of circuit breaker Counter arester Arus Kilovar hour Kilowatt hour Daya aktif Pressure
Tipe A A A A A A I A A A A A A A I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSD
RCD TM
BUSBAR
TSS
A A A A A A A A I A A I I A A I
BAY TRANSMISI
TM
40
Group Bay
Data
No 13 16 34 35 41 42 43 44 49 50 51 52 53 54 55 56 57 58 60 62 63 64
Kode Q V AR *) ARO *) CBDF CBFA CBFB CBM CDAF CDAR CDAS CDAT CDBF CDBR CDBS CDBT CF *) CSP DCF DEARX *) DEATX *) DEBRX *) DEBTX *) DEFAF *) DEFAR DEFAS DEFAT DEFBF *) DEFBR DEFBS DEFBT DFRF DSDF DTARX *) DTATX *) DTBRX *) DTBTX *) DZ1AR *) DZ1AS *) DZ1AT *) DZ1BR *) DZ1BS *) DZ1BT *) DZ2AR *) DZ2AS *)
Fungsi Daya reaktif Tegangan Circuit breaker auto reclose Auto reclose off Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance Current differential relay (a) failure Current differential (a) phase R Current differential (a) phase S Current differential (a) phase T Current differential relay (b) failure Current differential (b) phase R Current differential (b) phase S Current differential (b) phase T Carrier faulty Check synchronizing in progress DC supply failure Directional earth fault (a) relay receive Directional earth fault (a) relay transmit Directional earth fault (b) relay receive Directional earth fault (b) relay transmit Directional earth fault (a) failure Directional earth fault (a) phase R Directional earth fault (a) phase S Directional earth fault (a) phase T Directional earth fault (b) failure Directional earth fault (b) phase R Directional earth fault (b) phase S Directional earth fault (b) phase T Disturbance fault recorder faulty Disconnecting switch driving fault Direct transfer trip (a) receive Direct transfer trip (a) transmit Direct transfer trip (b) receive Direct transfer trip (b) transmit Distance (a) phase R zone 1 Distance (a) phase S zone 1 Distance (a) phase T zone 1 Distance (b) phase R zone 1 Distance (b) phase S zone 1 Distance (b) phase T zone 1 Distance (a) phase R zone 2 Distance (a) phase S zone 2
Tipe
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
I I A A A I A A A A A A A A A I A A A A A A A A A A A A A A A I I I I A A A A A A A A
TSS 65 66 67 68 69 70 71 72 73 74 77 78 79 80 81 82 83 84 85 86 87 88 89
41
Group Bay
Data
No 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 111 117 118 119 120 121 122 123 126 127 130 131 133 134 135 136 138 141 145 157 158 159 160 169 170 175 176 180 182 183 185 190
Kode DZ2AT DZ2BR *) DZ2BS *) DZ2BT *) DZ3AR *) DZ3AS *) DZ3AT *) DZ3BR *) DZ3BS *) DZ3BT *) DZAF *) DZARX *) DZATX *) DZBF *) DZBRX *) DZBTX *) ERF GFRF LOWCT** ) LPA LPB LPT MTO OCPA**) OCRF OVR *) OVRF *) P2GFR P2OCR PD PHR PHS PHT POT PWF RCBF SYNF SZPA SZPB SZPF TCS1 TCS2 TPAF *) TPBF *) UFR UVR *) UVRF *) VTF SIB
*)
Fungsi Distance (a) phase T zone 2 Distance (b) phase R zone 2 Distance (b) phase S zone 2 Distance (b) phase T zone 2 Distance (a) phase R zone 3 Distance (a) phase S zone 3 Distance (a) phase T zone 3 Distance (b) phase R zone 3 Distance (b) phase S zone 3 Distance (b) phase T zone 3 Distance relay (a) failure Distance (a) relay receive Distance (a) relay transmit Distance relay (b) failure Distance (b) relay receive Distance (b) relay transmit Event recorder failure Ground fault relay failure Low oil pressure cable trip Low pressure alarm Low pressure block Low pressure trip Master trip operate Oil cable pressure alarm Over current relay failure Over voltage relay operate Over voltage relay failure Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pilot wire failure Relay circuit breaker fail failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Trip coil supervisory 1 Trip coil supervisory 2 Teleprotection (a) failure Teleprotection (b) failure Under frequency relay operate Under voltage relay operate Under voltage relay failure Voltage transformer failure Software interlocking bypass
Tipe A A A A A A A A A A A I I A I I A A A A A A A A A A A A A A A A A I A A A A A A A A A A A A A A A
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
42
Group Bay
Data
No 191 192 1 3 5 7 12 13 18 1 2 4 6 7 10 1 1 2 3 4 6 7 8 9 12 13 15 16 41 42 43 44 58 60 74 75 77 106 108 111 118 119 120 121 123 124
Kode IEDF SOTF BI CB CSO ES LI LR SAM BI CB CSO LI LR SAM TPI AMF CCB CNTA CTPI I KVARH KWH P PRES Q TEMP V CBDF CBFA CBFB CBM CSP DCF DFRF DIFF DSDF ERF FPO GFRF LPA LPB LPT MTO OCRF OTA
Fungsi IED Faulty Switch on to fault Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Earth switch closed/opened Line isolator switch closed/opened Local remote Synchronization auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Line isolator switch closed/opened Local remote Synchronization auto/manual Tap position indication Amperes fault ( per phase ) Counter of circuit breaker Counter arester Counter tap position indication Arus Kilovar hour Kilowatt hour Daya aktif Pressure Daya reaktif Temperature Tegangan Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance Check synchronizing in progress DC supply failure Disturbance fault recorder faulty Differential failure Disconnecting switch driving fault Event recorder failure Fire protection operated Ground fault relay failure Low pressure alarm Low pressure block Low pressure trip Master trip operate Over current relay failure Oil temperature alarm
Tipe A A I I I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSD
RCD
TC
TM
BAY IBT
TSS
A A A I I A A A A A A A A A A A A A
43
Group Bay
Data
No 125 128 129 130 131 133 134 135 136 138 139 145 147 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 177 178 179 180 185 186 187 188 189 190 191 192 197 1
Kode OTT P1DIF P1REF P2GFR P2OCR PD PHR PHS PHT POT PRDT RCBF REFF SYNF SZPA SZPB SZPF TAF TBUC2 TBUCA TCA TCFF TCH TCL TCPF TCS1 TCS2 TFDP TJANT TOLA TOOS TPIF TSPA TSPT UFR VTF WTHVA WTHVT WTLVA WTLVT SIB IEDF SOTF TCT BI CB CSO
Fungsi Oil temperatur trip Differential Restricted earth fault Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pressure relay device trip Relay circuit breaker fail failure Restricted earth fault failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Tranformer AVR failure Transformer bucholz trip Transformer bucholz alarm Tap changer alarm Transformer cooling fan failure Tap changer high limit Tap changer low limit Transformer cooling pump failure Trip coil supervisory 1 Trip coil supervisory 2 Transformer fire detection & protection Transformer jansen trip Transformer oil level alarm Transformer out of step alarm Tap position indication failure Transformer sudden pressure alarm Transformer sudden pressure trip Under frequency relay operate Voltage transformer failure HV winding temperatur alarm HV winding temperatur trip LV winding temperatur alarm LV winding temperatur trip Software interlocking bypass IED Faulty Switch on to fault Tap changer trip Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override
Tipe A A A A A A A A A I A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSD
3 5
44
Group Bay
Data
No 7 13 14 18 20 21 1 2 4 7
Kode ES LR LRT SAM TCC TFAM BI CB CSO LR LRT SAM TC TCC TFAM TPI AMF CCB CNTA CTPI I KVARH KWH P PRES Q TEMP V CBDF CBFA CBFB CBM DCF DFRF DIFF DSDF ERF FPO GFRF LPA LPB LPT MTO OCRF OTA OTT OVR
Fungsi Earth switch closed/opened Local remote Local/remote switch for tapchanger Synchronization auto/manual Tap changer auto/manual Transformer fan auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Local remote Local/remote switch for tapchanger Synchronization auto/manual Tap changer raise/lower Tap changer auto/manual Transformer fan auto/manual Tap position indication Amperes fault ( per phase ) Counter of circuit breaker Counter arester Counter tap position indication Arus Kilovar hour Kilowatt hour Daya aktif Pressure Daya reaktif Temperature Tegangan Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance DC supply failure Disturbance fault recorder faulty Differential failure Disconnecting switch driving fault Event recorder failure Fire protection operated Ground fault relay failure Low pressure alarm Low pressure block Low pressure trip Master trip operate Over current relay failure Oil temperature alarm Oil temperatur trip Over voltage relay operate
Tipe I I I I I I
Jmh 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
RCD
8 10 11 12 13 1 1 2 3 4 6 7 8 9 12 13 15 16 41 42 43 44 60 74 75 77 106 108 111 118 119 120 121 123 124 125 126
TC
TM
TSS
A A A I A A A A A A A A A A A A A A A
45
Group Bay
Data
No 127 128 129 130 131 133 134 135 136 138 139 145 147 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 177 178 179 180 182 183 185 186 187 188 189 190 191 192 1
Kode OVRF P1DIF P1REF P2GFR P2OCR PD PHR PHS PHT POT PRDT RCBF REFF SZPA SZPB SZPF TAF TBUC2 TBUCA TCA TCFF TCH TCL TCPF TCS1 TCS2 TFDP TJANT TOLA TOOS TPIF TSPA TSPT UFR UVR UVRF VTF WTHVA WTHVT WTLVA WTLVT SIB IEDF SOTF BI CB ES
Fungsi Over voltage relay failure Differential Restricted earth fault Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pressure relay device trip Relay circuit breaker fail failure Restricted earth fault failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Tranformer avr failure Transformer bucholz trip Transformer bucholz alarm Tap changer alarm Transformer cooling fan failure Tap changer high limit Tap changer low limit Transformer cooling pump failure Trip coil supervisory 1 Trip coil supervisory 2 Transformer fire detection & protection Transformer jansen trip Transformer oil level alarm Transformer out of step alarm Tap position indication failure Transformer sudden pressure alarm Transformer sudden pressure trip Under frequency relay operate Under voltage relay operate Under voltage relay failure Voltage transformer failure HV winding temperatur alarm HV winding temperatur trip LV winding temperatur alarm LV winding temperatur trip Software interlocking bypass IED Faulty Switch on to fault Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened
Tipe A A A A A A A A A I A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSD
3 7
46
Group Bay
Data
No 13 14 16 20 21 1 2 7
Kode LR LRT RACK TCC TFAM BI CB LR LRT TC TCC TFAM AMF CCB PRES Q TEMP CBDF CBFA CBFB CBM DCF DFRF ERF LPA LPB LPT MTO P1DIF P2GFR P2OCR PD PHR PHS PHT POT PRDT RCBF RF SZPA SZPB SZPF TCS1 TCS2 SIB IEDF SOTF
Fungsi Local remote Local/remote switch for tapchanger Circuit breaker rackin/rackout Tap changer auto/manual Transformer fan auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Local remote Local/remote switch for tapchanger Tap changer raise/lower Tap changer auto/manual Transformer fan auto/manual Amperes fault ( per phase ) Counter of circuit breaker Pressure Daya reaktif Temperature Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance DC supply failure Disturbance fault recorder faulty Event recorder failure Low pressure alarm Low pressure block Low pressure trip Master trip operate Differential Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pressure relay device trip Relay circuit breaker fail failure Reaktor failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Trip coil supervisory 1 Trip coil supervisory 2 Software interlocking bypass IED Faulty Switch on to fault
Tipe I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
RCD
8 11 12 13 1 2 12 13 15 41 42 43 44 60 74 106 118 119 120 121 128 130 131 133 134 135 136 138 139 145 148 158 159 160 169 170 190 191 192
TM
A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A
47
Group Bay
Data
No 1 3 7 12 13 21 1 2
Kode BI CB ES LI LR TFAM BI CB LI LR TFAM I KVARH KWH P Q V CBDF CBM CSP DFRF DIFF ERF GTT LPA LPB LPT MTO P1REF P2GFR P2OCR PD PHR PHS PHT POT REFF SYNF TCS1 TCS2 SIB IEDF SOTF BI CB ES
Fungsi Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened Line isolator switch closed/opened Local remote Transformer fan auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Line isolator switch closed/opened Local remote Transformer fan auto/manual Arus Kilovar hour Kilowatt hour Daya aktif Daya reaktif Tegangan Circuit breaker drive failure Circuit breaker maintenance Check synchronizing in progress Disturbance fault recorder faulty Differential failure Event recorder failure Generator transformer trip Low pressure alarm Low pressure block Low pressure trip Master trip operate Restricted earth fault Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Restricted earth fault failure Synchronizing failure Trip coil supervisory 1 Trip coil supervisory 2 Software interlocking bypass IED Faulty Switch on to fault Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened
Tipe I I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSD
RCD
6 7 13 6 7 8 9 13 16 41 44 58 74 75 106 114 118 119 120 121 129 130 131 133 134 135 136 138 147 157 169 170 190 191 192 1
TM
BAY GENERATOR
TSS
A A A A A A A A A A A A A A A A A A A A A A A A A A I I I
TSD
3 7
48
Group Bay
Data
No 12 13 1
Kode LI LR BI CB LI LR
Fungsi Line isolator switch closed/opened Local remote Bus isolator switch closed/opened Circuit breaker closed/opened Line isolator switch closed/opened Local remote
Tipe I I
Jmh 1 1 1 1 1 1
RCD
2 6 7
KETERANGAN: *) = Khusus untuk OHL Feeder **) = Khusus untuk Cable Feeder A = Alarm I = Indikasi Rincian Teleinformasi diatas adalah rincian per bay
49
Joint Control
P Q V
P Q V
P Q V
P Q V
P Q I
P Q I
P Q I
BUSBAR- A
BUSBAR- B
Teleinformasi Data Untuk Generator Combined Cycle Pada Konfigurasi 1 Breaker Data No 6 7 8 9 13 16 74 75 106 114 121 Kode I KVARH KWH P Q V DFRF DIFF ERF GTT MTO Fungsi Arus Kilovar hour Kilowatt hour Daya aktif Daya reaktif Tegangan Disturbance fault recorder faulty Differential failure Event recorder failure Generator transformer trip Master trip operate Tipe Jmh 3 4 4 7 7 4 3 3 3 3 3
TM
TSS
A A A A A
50
Data
Fungsi Restricted earth fault Ground fault relay Over current relay Protection on test Restricted earth fault failure Software interlocking bypass IED Faulty Switch on to fault Circuit breaker closed/opened Line isolator switch closed/opened Line isolator switch closed/opened
Tipe A A A A A A A A I I
Jmh 3 3 3 3 3 3 3 3 2 3 3
TSD RCD
51
TB-02
P Q V
P Q V
P Q I
BUSBAR - A
BUSBAR - B
Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 3-Belitan Pada Konfigurasi 1 Breaker Data No 6 7 8 9 13 16 Kode I KVARH KWH P Q V Fungsi Arus Kilovar hour Kilowatt hour Daya aktif Daya reaktif Tegangan Tipe Jmh 1 2 2 3 3 2
TM
52
Data
No 74 75 106 114 121 129 130 131 138 147 190 191 192 3 12 6
Kode DFRF DIFF ERF GTT MTO P1REF P2GFR P2OCR POT REFF SIB IEDF SOTF CB LI LI
Fungsi Disturbance fault recorder faulty Differential failure Event recorder failure Generator transformer trip Master trip operate Restricted earth fault Ground fault relay Over current relay Protection on test Restricted earth fault failure Software interlocking bypass IED Faulty Switch on to fault Circuit breaker closed/opened Line isolator switch closed/opened Line isolator switch closed/opened
Tipe A A A A A A A A A A A A A I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1
TSS
TSD RCD
53
TB-03
P Q V
P Q V
P Q I L/R
BUSBAR - A
BUSBAR - B
Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 3-Belitan Pada Konfigurasi Double Busbar Data No 6 7 8 9 13 16 41 44 58 74 75 106 114 118 119 120 121 Kode I KVARH KWH P Q V CBDF CBM CSP DFRF DIFF ERF GTT LPA LPB LPT MTO Fungsi Arus Kilovar hour Kilowatt hour Daya aktif Daya reaktif Tegangan Circuit breaker drive failure Circuit breaker maintenance Check synchronizing in progress Disturbance fault recorder faulty Differential failure Event recorder failure Generator transformer trip Low pressure alarm Low pressure block Low pressure trip Master trip operate Tipe Jmh 1 2 2 3 3 2 1 1 1 1 1 1 1 1 1 1 1
TM
TSS
A A A A A A A A A A A
54
Data
No 129 130 131 133 134 135 136 138 147 157 169 170 190 191 192 1 3 7 13 1 2 7
Kode P1REF P2GFR P2OCR PD PHR PHS PHT POT REFF SYNF TCS1 TCS2 SIB IEDF SOTF BI CB ES LR BI CB LR
Fungsi Restricted earth fault Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Restricted earth fault failure Synchronizing failure Trip coil supervisory 1 Trip coil supervisory 2 Software interlocking bypass IED Faulty Switch on to fault Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened Local remote Bus isolator switch closed/opened Circuit breaker closed/opened Local remote
Tipe A A A A A A A A A A A A A A A I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 3 1 1 2 1 1
TSD
RCD
55
TB-04
P Q V
P Q V
P Q I L/R
BUSBAR
Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 3-Belitan Pada Konfigurasi Single Busbar Data No 6 7 8 9 13 16 41 44 58 74 75 106 114 118 119 120 121 129 130 131 Kode I KVARH KWH P Q V CBDF CBM CSP DFRF DIFF ERF GTT LPA LPB LPT MTO P1REF P2GFR P2OCR Fungsi Arus Kilovar hour Kilowatt hour Daya aktif Daya reaktif Tegangan Circuit breaker drive failure Circuit breaker maintenance Check synchronizing in progress Disturbance fault recorder faulty Differential failure Event recorder failure Generator transformer trip Low pressure alarm Low pressure block Low pressure trip Master trip operate Restricted earth fault Ground fault relay Over current relay Tipe Jmh 1 2 2 3 3 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TM
TSS
A A A A A A A A A A A A A A
56
Data
No 133 134 135 136 138 147 157 169 170 190 191 192 1 3 7 13 1 2 7
Kode PD PHR PHS PHT POT REFF SYNF TCS1 TCS2 SIB IEDF SOTF BI CB ES LR BI CB LR
Fungsi Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Restricted earth fault failure Synchronizing failure Trip coil supervisory 1 Trip coil supervisory 2 Software interlocking bypass IED Faulty Switch on to fault Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened Local remote Bus isolator switch closed/opened Circuit breaker closed/opened Local remote
Tipe A A A A A A A A A A A A I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 3 1 1 1 1 1
TSD
RCD
57
TB-05
P Q V
P Q I
BUSBAR - A
BUSBAR - B
Teleinformasi Data Untuk 1 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi 1 Breaker Data No 6 7 8 9 13 16 74 75 106 114 121 Kode I KVARH KWH P Q V DFRF DIFF ERF GTT MTO Fungsi Arus Kilovar hour Kilowatt hour Daya aktif Daya reaktif Tegangan Disturbance fault recorder faulty Differential failure Event recorder failure Generator transformer trip Master trip operate Tipe Jmh 1 1 1 2 2 1 1 1 1 1 1
TM
TSS
A A A A A
58
TSD RCD
Restricted earth fault Ground fault relay Over current relay Protection on test Restricted earth fault failure Software interlocking bypass IED Faulty Switch on to fault Earth switch closed/opened Line isolator switch closed/opened Line isolator switch closed/opened
A A A A A A A A I I
1 1 1 1 1 1 1 1 1 1 1
59
TB-06
P Q V P Q I L/R
BUSBAR - A
BUSBAR - B
Teleinformasi Data Untuk 1 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Double Busbar Data No 6 7 8 9 13 16 41 44 58 74 75 106 114 118 119 120 121 129 130 Kode I KVARH KWH P Q V CBDF CBM CSP DFRF DIFF ERF GTT LPA LPB LPT MTO P1REF P2GFR Fungsi Arus Kilovar hour Kilowatt hour Daya aktif Daya reaktif Tegangan Circuit breaker drive failure Circuit breaker maintenance Check synchronizing in progress Disturbance fault recorder faulty Differential failure Event recorder failure Generator transformer trip Low pressure alarm Low pressure block Low pressure trip Master trip operate Restricted earth fault Ground fault relay Tipe Jmh 1 1 1 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TM
TSS
A A A A A A A A A A A A A
60
Data
No 131 133 134 135 136 138 147 157 169 170 190 191 192 1 3 7 13 1 2 7
Kode P2OCR PD PHR PHS PHT POT REFF SYNF TCS1 TCS2 SIB IEDF SOTF BI CB ES LR BI CB LR
Fungsi Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Restricted earth fault failure Synchronizing failure Trip coil supervisory 1 Trip coil supervisory 2 Software interlocking bypass IED Faulty Switch on to fault Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened Local remote Bus isolator switch closed/opened Circuit breaker closed/opened Local remote
Tipe A A A A A A A A A A A A A I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 2 1 1
TSD
RCD
61
TB-07
P Q V P Q I L/R
BUSBAR
Teleinformasi Data Untuk 1 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Single Busbar Data No 6 7 8 9 13 16 41 44 58 74 75 106 114 118 119 120 121 129 130 131 133 134 135 Kode I KVARH KWH P Q V CBDF CBM CSP DFRF DIFF ERF GTT LPA LPB LPT MTO P1REF P2GFR P2OCR PD PHR PHS Fungsi Arus Kilovar hour Kilowatt hour Daya aktif Daya reaktif Tegangan Circuit breaker drive failure Circuit breaker maintenance Check synchronizing in progress Disturbance fault recorder faulty Differential failure Event recorder failure Generator transformer trip Low pressure alarm Low pressure block Low pressure trip Master trip operate Restricted earth fault Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Tipe Jmh 1 1 1 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TM
TSS
A A A A A A A A A A A A A A A A A
62
Data
Kode PHT POT REFF SYNF TCS1 TCS2 SIB IEDF SOTF BI CB ES LR BI CB LR
Fungsi Trip phase T Protection on test Restricted earth fault failure Synchronizing failure Trip coil supervisory 1 Trip coil supervisory 2 Software interlocking bypass IED Faulty Switch on to fault Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened Local remote Bus isolator switch closed/opened Circuit breaker closed/opened Local remote
Tipe A A A A A A A A A I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSD
RCD
63
TB-08
P Q V
P Q I
BUSBAR - A
BUSBAR - B
Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi 1 Breaker Data No 6 7 8 9 13 16 74 75 106 Kode I KVARH KWH P Q V DFRF DIFF ERF Fungsi Arus Kilovar hour Kilowatt hour Daya aktif Daya reaktif Tegangan Disturbance fault recorder faulty Differential failure Event recorder failure Tipe Jmh 1 1 1 2 2 1 1 1 1
TM
TSS
A A A
64
Data
No 114 121 129 130 131 138 147 190 191 192 3 12 6
Kode GTT MTO P1REF P2GFR P2OCR POT REFF SIB IEDF SOTF CB LI LI
Fungsi Generator transformer trip Master trip operate Restricted earth fault Ground fault relay Over current relay Protection on test Restricted earth fault failure Software interlocking bypass IED Faulty Switch on to fault Circuit breaker closed/opened Line isolator switch closed/opened Line isolator switch closed/opened
Tipe A A A A A A A A A A I I
Jmh 1 1 1 1 1 1 1 1 1 1 2 1 1
TSD RCD
65
TB-09
P Q V
P Q I L/R
BUSBAR - A
BUSBAR - B
Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Double Busbar Data No 6 7 8 9 13 16 41 44 58 74 75 106 114 118 119 120 121 Kode I KVARH KWH P Q V CBDF CBM CSP DFRF DIFF ERF GTT LPA LPB LPT MTO Fungsi Arus Kilovar hour Kilowatt hour Daya aktif Daya reaktif Tegangan Circuit breaker drive failure Circuit breaker maintenance Check synchronizing in progress Disturbance fault recorder faulty Differential failure Event recorder failure Generator transformer trip Low pressure alarm Low pressure block Low pressure trip Master trip operate Tipe Jmh 1 1 1 2 2 1 1 1 1 1 1 1 1 1 1 1 1
TM
TSS
A A A A A A A A A A A
66
Data
No 129 130 131 133 134 135 136 138 147 157 169 170 190 191 192 1 3 7 13 1 2 7
Kode P1REF P2GFR P2OCR PD PHR PHS PHT POT REFF SYNF TCS1 TCS2 SIB IEDF SOTF BI CB ES LR BI CB LR
Fungsi Restricted earth fault Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Restricted earth fault failure Synchronizing failure Trip coil supervisory 1 Trip coil supervisory 2 Software interlocking bypass IED Faulty Switch on to fault Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened Local remote Bus isolator switch closed/opened Circuit breaker closed/opened Local remote
Tipe A A A A A A A A A A A A A A A I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 3 1 1 2 1 1
TSD
RCD
67
TB-10
P Q V P Q I
L/R
BUSBAR
Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Single Busbar Data No 6 7 8 9 13 16 41 44 58 74 75 106 114 118 119 120 121 129 130 131 Kode I KVARH KWH P Q V CBDF CBM CSP DFRF DIFF ERF GTT LPA LPB LPT MTO P1REF P2GFR P2OCR Fungsi Arus Kilovar hour Kilowatt hour Daya aktif Daya reaktif Tegangan Circuit breaker drive failure Circuit breaker maintenance Check synchronizing in progress Disturbance fault recorder faulty Differential failure Event recorder failure Generator transformer trip Low pressure alarm Low pressure block Low pressure trip Master trip operate Restricted earth fault Ground fault relay Over current relay Tipe Jmh 1 1 1 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TM
TSS
A A A A A A A A A A A A A A
68
Data
No 133 134 135 136 138 147 157 169 170 190 191 192 1 3 7 13 1 2 7
Kode PD PHR PHS PHT POT REFF SYNF TCS1 TCS2 SIB IEDF SOTF BI CB ES LR BI CB LR
Fungsi Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Restricted earth fault failure Synchronizing failure Trip coil supervisory 1 Trip coil supervisory 2 Software interlocking bypass IED Faulty Switch on to fault Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened Local remote Bus isolator switch closed/opened Circuit breaker closed/opened Local remote
Tipe A A A A A A A A A A A A I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 3 1 1 1 1 1
TSD
RCD
69
TB-11
L/R
BUSBAR - A
P Q V I
Download to RCC
BUSBAR - B
Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to 1 Breaker) Data TC No 1 1 3 4 6 7 8 9 12 Kode TPI
AMF CNTA CTPI I KVARH KWH P PRES
Tipe I
Jmh 3 3 3 3 3 1 1 1 3
TM
70
Data
No 13 15 16 58 60 74 75 77 106 108 111 121 123 124 125 128 129 130 131 138 139 145 147 157 158 159 160 161 162 163 164 165 166 167 168 171 172 173 174 177 178 179 180 185 186 187 188 189 190
Kode
Q TEMP V
Fungsi
Daya reaktif Temperature Tegangan
Tipe
Jmh 1 12 3 1 1 1 1 1 1 3 1 1 1 3 3 1 1 1 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 3 3 3 3 3 1
TSS
CSP DCF DFRF DIFF DSDF ERF FPO GFRF MTO OCRF OTA OTT P1DIF P1REF P2GFR P2OCR POT PRDT RCBF REFF SYNF SZPA SZPB SZPF TAF TBUC2 TBUCA TCA TCFF TCH TCL TCPF TFDP TJANT TOLA TOOS TPIF TSPA TSPT UFR VTF WTHVA WTHVT WTLVA WTLVT SIB
Check synchronizing in progress DC supply failure Disturbance fault recorder faulty Differential failure Disconnecting switch driving fault Event recorder failure Fire protection operated Ground fault relay failure Master trip operate Over current relay failure Oil temperature alarm Oil temperatur trip Differential Restricted earth fault Ground fault relay Over current relay Protection on test Pressure relay device trip Relay circuit breaker fail failure Restricted earth fault failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Tranformer AVR failure Transformer bucholz trip Transformer bucholz alarm Tap changer alarm Transformer cooling fan failure Tap changer high limit Tap changer low limit Transformer cooling pump failure Transformer fire detection & protection Transformer jansen trip Transformer oil level alarm Transformer out of step alarm Tap position indication failure Transformer sudden pressure alarm Transformer sudden pressure trip Under frequency relay operate Voltage transformer failure HV winding temperatur alarm HV winding temperatur trip LV winding temperatur alarm LV winding temperatur trip Software interlocking bypass
I A A A A A A A A A A A A A A A I A A A A A A A A A A A A A A A A A A A A A A A A A A A A A
71
Data
Kode IEDF SOTF PD OFO DGA NVD TCT ES LI LRT TCC TFAM LI LRT TC TCC TFAM
Fungsi IED Faulty Switch on to fault Partial discharge Online filtering OLTC Dissolve gas analysis Neutral voltage displacement (tersier) Tap changer trip Earth switch closed/opened Line isolator switch closed/opened Local/remote switch for tapchanger Tap changer auto/manual Transformer fan auto/manual Line isolator switch closed/opened Local/remote switch for tapchanger Tap changer raise/lower Tap changer auto/manual Transformer fan auto/manual
Tipe A A I I I I A I I I I I
Jmh 1 1 9 3 3 3 3 2 2 3 3 3 2 3 3 3 3
TSD
RCD
72
TB-12
L/R P Q V I
L/R
BUSBAR - A
Download to RCC
BUSBAR - B
Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to Double Busbar) Data TC No 1 1 3 4 6 7 8 9 12 13 15 16 Kode TPI
AMF CNTA CTPI I KVARH KWH P PRES Q TEMP V
Tipe I
TM
73
Data
No 41 42 43 44 58 60 74 75 77 106 108 111 118 119 120 121 123 124 125 128 129 130 131 133 134 135 136 138 139 145 147 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174
Kode CBDF CBFA CBFB CBM CSP DCF DFRF DIFF DSDF ERF FPO GFRF LPA LPB LPT MTO OCRF OTA OTT P1DIF P1REF P2GFR P2OCR PD PHR PHS PHT POT PRDT RCBF REFF SYNF SZPA SZPB SZPF TAF TBUC2 TBUCA TCA TCFF TCH TCL TCPF TCS1 TCS2 TFDP TJANT TOLA TOOS
Fungsi Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance Check synchronizing in progress DC supply failure Disturbance fault recorder faulty Differential failure Disconnecting switch driving fault Event recorder failure Fire protection operated Ground fault relay failure Low pressure alarm Low pressure block Low pressure trip Master trip operate Over current relay failure Oil temperature alarm Oil temperatur trip Differential Restricted earth fault Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pressure relay device trip Relay circuit breaker fail failure Restricted earth fault failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Tranformer AVR failure Transformer bucholz trip Transformer bucholz alarm Tap changer alarm Transformer cooling fan failure Tap changer high limit Tap changer low limit Transformer cooling pump failure Trip coil supervisory 1 Trip coil supervisory 2 Transformer fire detection & protection Transformer jansen trip Transformer oil level alarm Transformer out of step alarm
Tipe A A A I I A A A A A A A A A A A A A A A A A A A A A A I A A A A A A A A A A A A A A A A A A A A A
Jmh 1-2 *) 1-2 *) 1-2 *) 1-2 *) 1 1 1 1 1 1 3-1 *) 1 1 1 1 1 1 3-1 *) 3-1 *) 1 1 1 1 1-2 *) 1-2 *) 1-2 *) 1-2 *) 1 1 1 1 1 1 1 1 3-1 *) 3-1 *) 3-1 *) 3-1 *) 3-1 *) 3-1 *) 3-1 *) 3-1 *) 1-2 *) 1-2 *) 3-1 *) 3-1 *) 3-1 *) 3-1 *)
TSS
74
Data
No 177 178 179 180 185 186 187 188 189 190 191 192 193 194 195 196 197 1 3 5 7 12 13 14 18 20 21 1 2 4 6 7 8 10 11 12 13
Kode TPIF TSPA TSPT UFR VTF WTHVA WTHVT WTLVA WTLVT SIB IEDF SOTF PD OFO DGA NVD TCT BI CB CSO ES LI LR LRT SAM TCC TFAM BI CB CSO LI LR LRT SAM TC TCC TFAM
Fungsi Tap position indication failure Transformer sudden pressure alarm Transformer sudden pressure trip Under frequency relay operate Voltage transformer failure HV winding temperatur alarm HV winding temperatur trip LV winding temperatur alarm LV winding temperatur trip Software interlocking bypass IED Faulty Switch on to fault Partial discharge Online filtering OLTC Dissolve gas analysis Neutral voltage displacement (tersier) Tap changer trip Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Earth switch closed/opened Line isolator switch closed/opened Local remote Local/remote switch for tapchanger Synchronization auto/manual Tap changer auto/manual Transformer fan auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Line isolator switch closed/opened Local remote Local/remote switch for tapchanger Synchronization auto/manual Tap changer raise/lower Tap changer auto/manual Transformer fan auto/manual
Tipe A A A A A A A A A A A A I I I I A I I I I I I I I I I
Jmh 3-1 *) 3-1 *) 3-1 *) 1 3-1 *) 3-1 *) 3-1 *) 3-1 *) 3-1 *) 1 1 1 9-0 *) 3-0 *) 3-0 *) 3-0 *) 3-1 *) 2-4 *) 1-2 *) 1-2 *) 2 1-0 *) 1-2 *) 3-1 *) 1-2 *) 3-1 *) 3-1 *) 2-4 *) 1-2 *) 1-2 *) 1-0 *) 1-2 *) 3-1 *) 1-2 *) 3-1 *) 3-1 *) 3-1 *)
TSD
RCD
75
TB-13
L/R
P Q V I
Operation Responsibility by IRCC or RCC
L/R
BUSBAR
Download to RCC
Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to Single Busbar) Data TC No 1 1 3 4 6 7 8 9 12 13 15 16 41 42 43 44 Kode TPI
AMF CNTA CTPI I KVARH KWH P PRES Q TEMP V
Tipe I
TM
TSS
Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance
A A A I
76
Data
No 58 60 74 75 77 106 108 111 118 119 120 121 123 124 125 128 129 130 131 133 134 135 136 138 139 145 147 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 177 178 179 180
Kode CSP DCF DFRF DIFF DSDF ERF FPO GFRF LPA LPB LPT MTO OCRF OTA OTT P1DIF P1REF P2GFR P2OCR PD PHR PHS PHT POT PRDT RCBF REFF SYNF SZPA SZPB SZPF TAF TBUC2 TBUCA TCA TCFF TCH TCL TCPF TCS1 TCS2 TFDP TJANT TOLA TOOS TPIF TSPA TSPT UFR
Fungsi Check synchronizing in progress DC supply failure Disturbance fault recorder faulty Differential failure Disconnecting switch driving fault Event recorder failure Fire protection operated Ground fault relay failure Low pressure alarm Low pressure block Low pressure trip Master trip operate Over current relay failure Oil temperature alarm Oil temperatur trip Differential Restricted earth fault Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pressure relay device trip Relay circuit breaker fail failure Restricted earth fault failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Tranformer AVR failure Transformer bucholz trip Transformer bucholz alarm Tap changer alarm Transformer cooling fan failure Tap changer high limit Tap changer low limit Transformer cooling pump failure Trip coil supervisory 1 Trip coil supervisory 2 Transformer fire detection & protection Transformer jansen trip Transformer oil level alarm Transformer out of step alarm Tap position indication failure Transformer sudden pressure alarm Transformer sudden pressure trip Under frequency relay operate
Tipe I A A A A A A A A A A A A A A A A A A A A A A I A A A A A A A A A A A A A A A A A A A A A A A A A
77
Data
Kode VTF WTHVA WTHVT WTLVA WTLVT SIB IEDF SOTF TCT BI CB CSO ES LI LR LRT SAM TCC TFAM BI CB CSO LI LR LRT SAM TC TCC TFAM
Fungsi Voltage transformer failure HV winding temperatur alarm HV winding temperatur trip LV winding temperatur alarm LV winding temperatur trip Software interlocking bypass IED Faulty Switch on to fault Tap changer trip Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Earth switch closed/opened Line isolator switch closed/opened Local remote Local/remote switch for tapchanger Synchronization auto/manual Tap changer auto/manual Transformer fan auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Line isolator switch closed/opened Local remote Local/remote switch for tapchanger Synchronization auto/manual Tap changer raise/lower Tap changer auto/manual Transformer fan auto/manual
Tipe A A A A A A A A A I I I I I I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1-2 *) 1-2 *) 2 1-0 *) 1-2 *) 1 1-2 *) 1 1 1-3 *) 1-2 *) 1-2 *) 1-0 *) 1-2 *) 1 1-2 *) 1 1 1
TSD
RCD
78
TB-14: Interbus Transformer (Secondary Side Connected to 1 Breaker Dilengkapi Shunt Reaktor Pada Kumparan Tersier)
INTERBUS TRANSFORMER Secondary Side Connected to 1 Breaker Dilengkapi Shunt Reaktor Pada Kumparan Tersier
BUSBAR (IRCC)
TB-14
L/R Q P Q V I
BUSBAR - A
Download to RCC
BUSBAR - B
Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to 1 Breaker Dilengkapi Shunt Reaktor Pada Kumparan Tersier) Data TC No 1 1 3 4 6 7 8 9 Kode TPI
AMF CNTA CTPI I KVARH KWH P
Tipe I
Jmh 3 3 3 3 3 1 1 1
TM
79
Data
No 13 15 16 58 60 74 75 77 106 108 111 121 123 124 125 128 129 130 131 138 139 145 147 157 158 159 160 161 162 163 164 165 166 167 168 171 172 173 174 177 178 179 180 185 186 187 188 189 190 191
Kode
Q TEMP V
Fungsi
Daya reaktif Temperature Tegangan
Tipe
Jmh 2 12 3 1 1 1 1 1 1 3 1 1 1 3 3 1 1 1 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 3 3 3 3 3 1 1
TSS
CSP DCF DFRF DIFF DSDF ERF FPO GFRF MTO OCRF OTA OTT P1DIF P1REF P2GFR P2OCR POT PRDT RCBF REFF SYNF SZPA SZPB SZPF TAF TBUC2 TBUCA TCA TCFF TCH TCL TCPF TFDP TJANT TOLA TOOS TPIF TSPA TSPT UFR VTF WTHVA WTHVT WTLVA WTLVT SIB IEDF
Check synchronizing in progress DC supply failure Disturbance fault recorder faulty Differential failure Disconnecting switch driving fault Event recorder failure Fire protection operated Ground fault relay failure Master trip operate Over current relay failure Oil temperature alarm Oil temperatur trip Differential Restricted earth fault Ground fault relay Over current relay Protection on test Pressure relay device trip Relay circuit breaker fail failure Restricted earth fault failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Tranformer AVR failure Transformer bucholz trip Transformer bucholz alarm Tap changer alarm Transformer cooling fan failure Tap changer high limit Tap changer low limit Transformer cooling pump failure Transformer fire detection & protection Transformer jansen trip Transformer oil level alarm Transformer out of step alarm Tap position indication failure Transformer sudden pressure alarm Transformer sudden pressure trip Under frequency relay operate Voltage transformer failure HV winding temperatur alarm HV winding temperatur trip LV winding temperatur alarm LV winding temperatur trip Software interlocking bypass IED Faulty
I A A A A A A A A A A A A A A A I A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A
80
Data
Kode SOTF PD OFO DGA NVD TCT ES LI LRT TCC TFAM LI LRT TC TCC TFAM
Fungsi Switch on to fault Partial discharge Online filtering OLTC Dissolve gas analysis Neutral voltage displacement (tersier) Tap changer trip Earth switch closed/opened Line isolator switch closed/opened Local/remote switch for tapchanger Tap changer auto/manual Transformer fan auto/manual Line isolator switch closed/opened Local/remote switch for tapchanger Tap changer raise/lower Tap changer auto/manual Transformer fan auto/manual
Tipe A I I I I A I I I I I
Jmh 1 9 3 3 3 3 2 3 3 3 3 3 3 3 3 3
TSD
RCD
81
TB-15: Interbus Transformer (Secondary Side Connected to Double Busbar Dilengkapi Shunt Reaktor Pada Kumparan Tersier)
Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to Double Busbar Dilengkapi Shunt Reaktor Pada Kumparan Tersier) Data TC No 1 1 3 4 6 7 8 9 12 Kode TPI
AMF CNTA CTPI I KVARH KWH P PRES
Tipe I
TM
82
Data
No 13 15 16 41 42 43 44 58 60 74 75 77 106 108 111 118 119 120 121 123 124 125 128 129 130 131 133 134 135 136 138 139 145 147 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171
Kode
Q TEMP V
Fungsi
Daya reaktif Temperature Tegangan
Tipe
Jmh 2 12-3 *) 3-1 *) 1-2 *) 1-2 *) 1-2 *) 1-2 *) 1 1 1 1 1 1 3-1 *) 1 1 1 1 1 1 3-1 *) 3-1 *) 1 1 1 1 1-2 *) 1-2 *) 1-2 *) 1-2 *) 1 1 1 1 1 1 1 1 3-1 *) 3-1 *) 3-1 *) 3-1 *) 3-1 *) 3-1 *) 3-1 *) 3-1 *) 1-2 *) 1-2 *) 3-1 *)
TSS
CBDF CBFA CBFB CBM CSP DCF DFRF DIFF DSDF ERF FPO GFRF LPA LPB LPT MTO OCRF OTA OTT P1DIF P1REF P2GFR P2OCR PD PHR PHS PHT POT PRDT RCBF REFF SYNF SZPA SZPB SZPF TAF TBUC2 TBUCA TCA TCFF TCH TCL TCPF TCS1 TCS2 TFDP
Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance Check synchronizing in progress DC supply failure Disturbance fault recorder faulty Differential failure Disconnecting switch driving fault Event recorder failure Fire protection operated Ground fault relay failure Low pressure alarm Low pressure block Low pressure trip Master trip operate Over current relay failure Oil temperature alarm Oil temperatur trip Differential Restricted earth fault Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pressure relay device trip Relay circuit breaker fail failure Restricted earth fault failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Tranformer AVR failure Transformer bucholz trip Transformer bucholz alarm Tap changer alarm Transformer cooling fan failure Tap changer high limit Tap changer low limit Transformer cooling pump failure Trip coil supervisory 1 Trip coil supervisory 2 Transformer fire detection & protection
A A A I I A A A A A A A A A A A A A A A A A A A A A A I A A A A A A A A A A A A A A A A A A
83
Data
No 172 173 174 177 178 179 180 185 186 187 188 189 190 191 192 193 194 195 196 197 1 3 5 7 12 13 14 18 20 21 1 2 4 6 7 8 10 11 12 13
Kode TJANT TOLA TOOS TPIF TSPA TSPT UFR VTF WTHVA WTHVT WTLVA WTLVT SIB IEDF SOTF PD OFO DGA NVD TCT BI CB CSO ES LI LR LRT SAM TCC TFAM BI CB CSO LI LR LRT SAM TC TCC TFAM
Fungsi Transformer jansen trip Transformer oil level alarm Transformer out of step alarm Tap position indication failure Transformer sudden pressure alarm Transformer sudden pressure trip Under frequency relay operate Voltage transformer failure HV winding temperatur alarm HV winding temperatur trip LV winding temperatur alarm LV winding temperatur trip Software interlocking bypass IED Faulty Switch on to fault Partial discharge Online filtering OLTC Dissolve gas analysis Neutral voltage displacement (tersier) Tap changer trip Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Earth switch closed/opened Line isolator switch closed/opened Local remote Local/remote switch for tapchanger Synchronization auto/manual Tap changer auto/manual Transformer fan auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Line isolator switch closed/opened Local remote Local/remote switch for tapchanger Synchronization auto/manual Tap changer raise/lower Tap changer auto/manual Transformer fan auto/manual
Tipe A A A A A A A A A A A A A A A I I I I A I I I I I I I I I I
Jmh 3-1 *) 3-1 *) 3-1 *) 3-1 *) 3-1 *) 3-1 *) 1 3-1 *) 3-1 *) 3-1 *) 3-1 *) 3-1 *) 1 1 1 9-0 *) 3-0 *) 3-0 *) 3-0 *) 3-1 *) 2-4 *) 1-2 *) 1-2 *) 2 2-1 *) 1-2 *) 3-1 *) 1-2 *) 3-1 *) 3-1 *) 2-4 *) 1-2 *) 1-2 *) 2-1 *) 1-2 *) 3-1 *) 1-2 *) 3-1 *) 3-1 *) 3-1 *)
TSD
RCD
84
TB-16: Interbus Transformer (Secondary Side Connected to Single Busbar Dilengkapi Shunt Reaktor Pada Kumparan Tersier)
INTERBUS TRANSFORMER Secondary Side Connected to Single Busbar Dilengkapi Shunt Reaktor Pada Kumparan Tersier
BUSBAR (IRCC or RCC)
TB-16
L/R
P Q V I
Operation Responsibility by IRCC or RCC
L/R
Download to RCC
BUSBAR
Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to Single Busbar Dilengkapi Shunt Reaktor Pada Kumparan Tersier) Data TC No 1 1 3 4 6 7 8 9 12 13 15 16 Kode TPI
AMF CNTA CTPI I KVARH KWH P PRES Q TEMP V
Tipe I
Jmh 1 1 1 1 1 1 1 1 1 2 3 1
TM
85
Data
No 41 42 43 44 58 60 74 75 77 106 108 111 118 119 120 121 123 124 125 128 129 130 131 133 134 135 136 138 139 145 147 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174
Kode CBDF CBFA CBFB CBM CSP DCF DFRF DIFF DSDF ERF FPO GFRF LPA LPB LPT MTO OCRF OTA OTT P1DIF P1REF P2GFR P2OCR PD PHR PHS PHT POT PRDT RCBF REFF SYNF SZPA SZPB SZPF TAF TBUC2 TBUCA TCA TCFF TCH TCL TCPF TCS1 TCS2 TFDP TJANT TOLA TOOS
Fungsi Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance Check synchronizing in progress DC supply failure Disturbance fault recorder faulty Differential failure Disconnecting switch driving fault Event recorder failure Fire protection operated Ground fault relay failure Low pressure alarm Low pressure block Low pressure trip Master trip operate Over current relay failure Oil temperature alarm Oil temperatur trip Differential Restricted earth fault Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pressure relay device trip Relay circuit breaker fail failure Restricted earth fault failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Tranformer AVR failure Transformer bucholz trip Transformer bucholz alarm Tap changer alarm Transformer cooling fan failure Tap changer high limit Tap changer low limit Transformer cooling pump failure Trip coil supervisory 1 Trip coil supervisory 2 Transformer fire detection & protection Transformer jansen trip Transformer oil level alarm Transformer out of step alarm
Tipe A A A I I A A A A A A A A A A A A A A A A A A A A A A I A A A A A A A A A A A A A A A A A A A A A
Jmh 1-2 *) 1-2 *) 1-2 *) 1-2 *) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1-2 *) 1-2 *) 1-2 *) 1-2 *) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1-2 *) 1-2 *) 1 1 1 1
TSS
86
Data
No 177 178 179 180 185 186 187 188 189 190 191 192 197 1 3 5 7 12 13 14 18 20 21 1 2 4 6 7 8 10 11 12 13
Kode TPIF TSPA TSPT UFR VTF WTHVA WTHVT WTLVA WTLVT SIB IEDF SOTF TCT BI CB CSO ES LI LR LRT SAM TCC TFAM BI CB CSO LI LR LRT SAM TC TCC TFAM
Fungsi Tap position indication failure Transformer sudden pressure alarm Transformer sudden pressure trip Under frequency relay operate Voltage transformer failure HV winding temperatur alarm HV winding temperatur trip LV winding temperatur alarm LV winding temperatur trip Software interlocking bypass IED Faulty Switch on to fault Tap changer trip Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Earth switch closed/opened Line isolator switch closed/opened Local remote Local/remote switch for tapchanger Synchronization auto/manual Tap changer auto/manual Transformer fan auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Line isolator switch closed/opened Local remote Local/remote switch for tapchanger Synchronization auto/manual Tap changer raise/lower Tap changer auto/manual Transformer fan auto/manual
Tipe A A A A A A A A A A A A A I I I I I I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1-2 *) 1-2 *) 2 2-1 *) 1-2 *) 1 1-2 *) 1 1 1-3 *) 1-2 *) 1-2 *) 2-1 *) 1-2 *) 1 1-2 *) 1 1 1
TSD
RCD
87
Teleinformasi Data Untuk Bay Trafo Tenaga Pada Konfigurasi 1 Breaker Data TC No 1 1 3 4 6 7 8 9 12 13 Kode TPI AMF CNTA CTPI I KVARH KWH P PRES Q Fungsi Tap position indication Amperes fault ( per phase ) Counter arester Counter tap position indication Arus Kilovar hour Kilowatt hour Daya aktif Pressure Daya reaktif Tipe I Jmh 1 1 1 1 1 1 1 1 1 1
TM
88
Data
No 15 16 60 74 75 77 106 108 111 121 123 124 125 126 127 128 129 130 131 138 139 145 147 158 159 160 161 162 163 164 165 166 167 168 171 172 173 174 177 178 179 180 182 183 185 186 187 188 189
Kode TEMP V DCF DFRF DIFF DSDF ERF FPO GFRF MTO OCRF OTA OTT OVR OVRF P1DIF P1REF P2GFR P2OCR POT PRDT RCBF REFF SZPA SZPB SZPF TAF TBUC2 TBUCA TCA TCFF TCH TCL TCPF TFDP TJANT TOLA TOOS TPIF TSPA TSPT UFR UVR UVRF VTF WTHVA WTHVT WTLVA WTLVT
Fungsi Temperature Tegangan DC supply failure Disturbance fault recorder faulty Differential failure Disconnecting switch driving fault Event recorder failure Fire protection operated Ground fault relay failure Master trip operate Over current relay failure Oil temperature alarm Oil temperatur trip Over voltage relay operate Over voltage relay failure Differential Restricted earth fault Ground fault relay Over current relay Protection on test Pressure relay device trip Relay circuit breaker fail failure Restricted earth fault failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Tranformer avr failure Transformer bucholz trip Transformer bucholz alarm Tap changer alarm Transformer cooling fan failure Tap changer high limit Tap changer low limit Transformer cooling pump failure Transformer fire detection & protection Transformer jansen trip Transformer oil level alarm Transformer out of step alarm Tap position indication failure Transformer sudden pressure alarm Transformer sudden pressure trip Under frequency relay operate Under voltage relay operate Under voltage relay failure Voltage transformer failure HV winding temperatur alarm HV winding temperatur trip LV winding temperatur alarm LV winding temperatur trip
Tipe
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSS
A A A A A A A A A A A A A A A A A I A A A A A A A A A A A A A A A A A A A A A A A A A A A A A
89
Data
Kode SIB IEDF SOTF ES LI LRT TCC TFAM LI LRT TC TCC TFAM
Fungsi Software interlocking bypass IED Faulty Switch on to fault Earth switch closed/opened Line isolator switch closed/opened Local/remote switch for tapchanger Tap changer auto/manual Transformer fan auto/manual Line isolator switch closed/opened Local/remote switch for tapchanger Tap changer raise/lower Tap changer auto/manual Transformer fan auto/manual
Tipe A A A I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1
TSD
RCD
90
TB-18: Bay Trafo Tenaga Pada Konfigurasi Double Busbar BAY TRAFO TENAGA PADA KONFIGURASI DOUBLE BUSBAR
BUSBAR - A TB-18
BUSBAR - B
L/R P Q V I
TEGANGAN TINGGI
Batas wewenang
TEGANGAN MENENGAH
DOUBLE BUSBAR
Teleinformasi Data Untuk Bay Trafo Tenaga Pada Konfigurasi Double Busbar Data TC No 1 1 2 3 4 6 7 8 9 12 13 15 16 41 42 43 44 Kode TPI AMF CCB CNTA CTPI I KVARH KWH P PRES Q TEMP V CBDF CBFA CBFB CBM Fungsi Tap position indication Amperes fault ( per phase ) Counter of circuit breaker Counter arester Counter tap position indication Arus Kilovar hour Kilowatt hour Daya aktif Pressure Daya reaktif Temperature Tegangan Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance Tipe I Jmh 1 1 1 1 1 1 1 1 1 1 1 3 1 1 1 1 1
TM
TSS
A A A I
91
Data
No 60 74 75 77 106 108 111 118 119 120 121 123 124 125 126 127 128 129 130 131 133 134 135 136 138 139 145 147 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 177 178 179 180
Kode DCF DFRF DIFF DSDF ERF FPO GFRF LPA LPB LPT MTO OCRF OTA OTT OVR OVRF P1DIF P1REF P2GFR P2OCR PD PHR PHS PHT POT PRDT RCBF REFF SZPA SZPB SZPF TAF TBUC2 TBUCA TCA TCFF TCH TCL TCPF TCS1 TCS2 TFDP TJANT TOLA TOOS TPIF TSPA TSPT UFR
Fungsi DC supply failure Disturbance fault recorder faulty Differential failure Disconnecting switch driving fault Event recorder failure Fire protection operated Ground fault relay failure Low pressure alarm Low pressure block Low pressure trip Master trip operate Over current relay failure Oil temperature alarm Oil temperatur trip Over voltage relay operate Over voltage relay failure Differential Restricted earth fault Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pressure relay device trip Relay circuit breaker fail failure Restricted earth fault failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Tranformer avr failure Transformer bucholz trip Transformer bucholz alarm Tap changer alarm Transformer cooling fan failure Tap changer high limit Tap changer low limit Transformer cooling pump failure Trip coil supervisory 1 Trip coil supervisory 2 Transformer fire detection & protection Transformer jansen trip Transformer oil level alarm Transformer out of step alarm Tap position indication failure Transformer sudden pressure alarm Transformer sudden pressure trip Under frequency relay operate
Tipe A A A A A A A A A A A A A A A A A A A A A A A A I A A A A A A A A A A A A A A A A A A A A A A A A
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
92
Data
No 182 183 185 186 187 188 189 190 191 192 1 3 7 13 14 16 20 21 1 2 7 8 11 12 13
Kode UVR UVRF VTF WTHVA WTHVT WTLVA WTLVT SIB IEDF SOTF BI CB ES LR LRT RACK TCC TFAM BI CB LR LRT TC TCC TFAM
Fungsi Under voltage relay operate Under voltage relay failure Voltage transformer failure HV winding temperatur alarm HV winding temperatur trip LV winding temperatur alarm LV winding temperatur trip Software interlocking bypass IED Faulty Switch on to fault Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened Local remote Local/remote switch for tapchanger Circuit breaker rackin/rackout Tap changer auto/manual Transformer fan auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Local remote Local/remote switch for tapchanger Tap changer raise/lower Tap changer auto/manual Transformer fan auto/manual
Tipe A A A A A A A A A A I I I I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 2 1 1 1 1 1 1
TSD
RCD
93
TB-19: Bay Trafo Tenaga Pada Konfigurasi Single Busbar BAY TRAFO TENAGA PADA KONFIGURASI SINGLE BUSBAR
BUSBAR TB-19
L/R P Q V I
TEGANGAN TINGGI
Batas wewenang
TEGANGAN MENENGAH
DOUBLE BUSBAR
Teleinformasi Data Untuk Bay Trafo Tenaga Pada Konfigurasi Single Busbar Data TC No 1 1 2 3 4 6 7 8 9 12 13 15 16 41 42 43 44 60 74 Kode TPI AMF CCB CNTA CTPI I KVARH KWH P PRES Q TEMP V CBDF CBFA CBFB CBM DCF DFRF Fungsi Tap position indication Amperes fault ( per phase ) Counter of circuit breaker Counter arester Counter tap position indication Arus Kilovar hour Kilowatt hour Daya aktif Pressure Daya reaktif Temperature Tegangan Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance DC supply failure Disturbance fault recorder faulty Tipe I Jmh 1 1 1 1 1 1 1 1 1 1 1 3 1 1 1 1 1 1 1
TM
TSS
A A A I A A
94
Data
No 75 77 106 108 111 118 119 120 121 123 124 125 126 127 128 129 130 131 133 134 135 136 138 139 145 147 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 177 178 179 180 182 183
Kode DIFF DSDF ERF FPO GFRF LPA LPB LPT MTO OCRF OTA OTT OVR OVRF P1DIF P1REF P2GFR P2OCR PD PHR PHS PHT POT PRDT RCBF REFF SZPA SZPB SZPF TAF TBUC2 TBUCA TCA TCFF TCH TCL TCPF TCS1 TCS2 TFDP TJANT TOLA TOOS TPIF TSPA TSPT UFR UVR UVRF
Fungsi Differential failure Disconnecting switch driving fault Event recorder failure Fire protection operated Ground fault relay failure Low pressure alarm Low pressure block Low pressure trip Master trip operate Over current relay failure Oil temperature alarm Oil temperatur trip Over voltage relay operate Over voltage relay failure Differential Restricted earth fault Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pressure relay device trip Relay circuit breaker fail failure Restricted earth fault failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Tranformer avr failure Transformer bucholz trip Transformer bucholz alarm Tap changer alarm Transformer cooling fan failure Tap changer high limit Tap changer low limit Transformer cooling pump failure Trip coil supervisory 1 Trip coil supervisory 2 Transformer fire detection & protection Transformer jansen trip Transformer oil level alarm Transformer out of step alarm Tap position indication failure Transformer sudden pressure alarm Transformer sudden pressure trip Under frequency relay operate Under voltage relay operate Under voltage relay failure
Tipe A A A A A A A A A A A A A A A A A A A A A A I A A A A A A A A A A A A A A A A A A A A A A A A A A
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
95
Data
Kode VTF WTHVA WTHVT WTLVA WTLVT SIB IEDF SOTF BI CB ES LR LRT RACK TCC TFAM BI CB LR LRT TC TCC TFAM
Fungsi Voltage transformer failure HV winding temperatur alarm HV winding temperatur trip LV winding temperatur alarm LV winding temperatur trip Software interlocking bypass IED Faulty Switch on to fault Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened Local remote Local/remote switch for tapchanger Circuit breaker rackin/rackout Tap changer auto/manual Transformer fan auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Local remote Local/remote switch for tapchanger Tap changer raise/lower Tap changer auto/manual Transformer fan auto/manual
Tipe A A A A A A A A I I I I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSD
RCD
96
BUSBAR - B
Reaktor
Teleinformasi Data Untuk Bay Reaktor Pada Konfigurasi 1 Breaker Data No Kode Fungsi 1 AMF Amperes fault ( per phase ) 12 PRES Pressure TM 13 Q Daya reaktif 15 TEMP Temperature 60 DCF DC supply failure 74 DFRF Disturbance fault recorder faulty 106 ERF Event recorder failure 121 MTO Master trip operate 128 P1DIF Differential 130 P2GFR Ground fault relay 131 P2OCR Over current relay 138 POT Protection on test TSS 139 PRDT Pressure relay device trip 145 RCBF Relay circuit breaker fail failure 148 RF Reaktor failure 158 SZPA Short zone protection (a) operate 159 SZPB Short zone protection (b) operate 160 SZPF Short zone protection failure 190 SIB Software interlocking bypass 191 IEDF IED Faulty
Tipe
A A A A A A A A A A A A A A A A
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
97
Data
TSD RCD
No 192 7 12 21 6 13
Fungsi Switch on to fault Earth switch closed/opened Line isolator switch closed/opened Transformer fan auto/manual Line isolator switch closed/opened Transformer fan auto/manual
Tipe A I I I
Jmh 1 1 1 1 1 1
98
TB-21
BUSBAR - A
BUSBAR - B
L/R Q
Reaktor
Teleinformasi Data Untuk Bay Reaktor Pada Konfigurasi Double Busbar Data No 1 2 12 13 15 41 42 43 44 60 74 106 118 119 120 121 128 130 131 133 134 135 Kode AMF CCB PRES Q TEMP CBDF CBFA CBFB CBM DCF DFRF ERF LPA LPB LPT MTO P1DIF P2GFR P2OCR PD PHR PHS Fungsi Amperes fault ( per phase ) Counter of circuit breaker Pressure Daya reaktif Temperature Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance DC supply failure Disturbance fault recorder faulty Event recorder failure Low pressure alarm Low pressure block Low pressure trip Master trip operate Differential Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Tipe Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TM
TSS
A A A A A A A A A A A A A A A A A
99
Data
No 136 138 139 145 148 158 159 160 169 170 190 191 192 1 3 7 12 13 21 1 2 6 7 13
Kode PHT POT PRDT RCBF RF SZPA SZPB SZPF TCS1 TCS2 SIB IEDF SOTF BI CB ES LI LR TFAM BI CB LI LR TFAM
Fungsi Trip phase T Protection on test Pressure relay device trip Relay circuit breaker fail failure Reaktor failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Trip coil supervisory 1 Trip coil supervisory 2 Software interlocking bypass IED Faulty Switch on to fault Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened Line isolator switch closed/opened Local remote Transformer fan auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Line isolator switch closed/opened Local remote Transformer fan auto/manual
Tipe A A A A A A A A A A A A A I I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 2 1 1 1 1
TSD
RCD
100
TB-22
L/R Q
Reaktor
Teleinformasi Data Untuk Bay Reaktor Pada Konfigurasi Single Busbar Data No 1 2 12 13 15 41 42 43 44 60 74 106 118 119 120 121 128 130 131 133 134 135 136 138 139 145 148 Kode AMF CCB PRES Q TEMP CBDF CBFA CBFB CBM DCF DFRF ERF LPA LPB LPT MTO P1DIF P2GFR P2OCR PD PHR PHS PHT POT PRDT RCBF RF Fungsi Amperes fault ( per phase ) Counter of circuit breaker Pressure Daya reaktif Temperature Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance DC supply failure Disturbance fault recorder faulty Event recorder failure Low pressure alarm Low pressure block Low pressure trip Master trip operate Differential Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pressure relay device trip Relay circuit breaker fail failure Reaktor failure Tipe Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TM
TSS
A A A A A A A A A A A A A A A A A A A A A A
101
Data
Kode SZPA SZPB SZPF TCS1 TCS2 SIB IEDF SOTF BI CB ES LI LR TFAM BI CB LI LR TFAM
Fungsi Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Trip coil supervisory 1 Trip coil supervisory 2 Software interlocking bypass IED Faulty Switch on to fault Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened Line isolator switch closed/opened Local remote Transformer fan auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Line isolator switch closed/opened Local remote Transformer fan auto/manual
Tipe A A A A A A A A I I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSD
RCD
102
TB-23
BUSBAR - A
BUSBAR - B
L/R Q
Capasitor
Teleinformasi Data Untuk Bay Capasitor Pada Konfigurasi Double Busbar Data No 1 2 12 13 15 41 42 43 44 60 74 106 118 119 120 121 128 130 131 133 134 Kode AMF CCB PRES Q TEMP CBDF CBFA CBFB CBM DCF DFRF ERF LPA LPB LPT MTO P1DIF P2GFR P2OCR PD PHR Fungsi Amperes fault ( per phase ) Counter of circuit breaker Pressure Daya reaktif Temperature Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance DC supply failure Disturbance fault recorder faulty Event recorder failure Low pressure alarm Low pressure block Low pressure trip Master trip operate Differential Ground fault relay Over current relay Pole discrepancy Trip phase R Tipe Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TM
TSS
A A A A A A A A A A A A A A A A
103
Data
No 135 136 138 139 145 148 158 159 160 169 170 190 191 192 1 3 7 12 13 21 1 2 6 7 13
Kode PHS PHT POT PRDT RCBF RF SZPA SZPB SZPF TCS1 TCS2 SIB IEDF SOTF BI CB ES LI LR TFAM BI CB LI LR TFAM
Fungsi Trip phase S Trip phase T Protection on test Pressure relay device trip Relay circuit breaker fail failure Reaktor failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Trip coil supervisory 1 Trip coil supervisory 2 Software interlocking bypass IED Faulty Switch on to fault Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened Line isolator switch closed/opened Local remote Transformer fan auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Line isolator switch closed/opened Local remote Transformer fan auto/manual
Tipe A A A A A A A A A A A A A A I I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 2 1 1 1 1
TSD
RCD
104
TB-24
L/R Q
Capasitor
Teleinformasi Data Untuk Bay Capasitor Pada Konfigurasi Single Busbar Data No 1 2 12 13 15 41 42 43 44 60 74 106 118 119 120 121 128 130 131 133 134 135 136 138 139 145 148 Kode AMF CCB PRES Q TEMP CBDF CBFA CBFB CBM DCF DFRF ERF LPA LPB LPT MTO P1DIF P2GFR P2OCR PD PHR PHS PHT POT PRDT RCBF RF Fungsi Amperes fault ( per phase ) Counter of circuit breaker Pressure Daya reaktif Temperature Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance DC supply failure Disturbance fault recorder faulty Event recorder failure Low pressure alarm Low pressure block Low pressure trip Master trip operate Differential Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pressure relay device trip Relay circuit breaker fail failure Reaktor failure Tipe Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TM
TSS
A A A A A A A A A A A A A A A A A A A A A A
105
Data
Kode SZPA SZPB SZPF TCS1 TCS2 SIB IEDF SOTF BI CB ES LI LR TFAM BI CB LI LR TFAM
Fungsi Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Trip coil supervisory 1 Trip coil supervisory 2 Software interlocking bypass IED Faulty Switch on to fault Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened Line isolator switch closed/opened Local remote Transformer fan auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Line isolator switch closed/opened Local remote Transformer fan auto/manual
Tipe A A A A A A A A I I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSD
RCD
106
TB-25: Bay Penghantar Pada Konfigurasi 1 Breaker BAY PENGHANTAR PADA KONFIGURASI 1 BREAKER
BUSBAR - A TB-25
BUSBAR - B
P Q V I
Teleinformasi Data Untuk Bay Penghantar Pada Konfigurasi 1 Breaker Data No 1 3 6 7 8 9 13 16 49 50 51 52 53 54 55 56 Kode AMF CNTA *) I KVARH KWH P Q V CDAF CDAR CDAS CDAT CDBF CDBR CDBS CDBT Fungsi Amperes fault ( per phase ) Counter arester Arus Kilovar hour Kilowatt hour Daya aktif Daya reaktif Tegangan Current differential relay (a) failure Current differential (a) phase R Current differential (a) phase S Current differential (a) phase T Current differential relay (b) failure Current differential (b) phase R Current differential (b) phase S Current differential (b) phase T Tipe Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TM
TSS
A A A A A A A A
107
Data
No 57 58 60 62 63 64 65 66 67 68 69 70 71 72 73 74 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99
100 101 102 103 104 105
Kode CF CSP DCF DEARX *) DEATX *) DEBRX *) DEBTX *) DEFAF *) DEFAR DEFAS DEFAT DEFBF *) DEFBR DEFBS DEFBT DFRF DSDF DTARX *) DTATX *) DTBRX *) DTBTX *) DZ1AR *) DZ1AS *) DZ1AT *) DZ1BR *) DZ1BS *) DZ1BT *) DZ2AR *) DZ2AS *) DZ2AT *) DZ2BR *) DZ2BS *) DZ2BT *) DZ3AR *) DZ3AS *) DZ3AT *) DZ3BR *) DZ3BS *) DZ3BT *) DZAF *) DZARX *) DZATX *) DZBF *) DZBRX *) DZBTX *) ERF GFRF
LOWCT**)
*)
Fungsi Carrier faulty Check synchronizing in progress DC supply failure Directional earth fault (a) relay receive Directional earth fault (a) relay transmit Directional earth fault (b) relay receive Directional earth fault (b) relay transmit Directional earth fault (a) failure Directional earth fault (a) phase R Directional earth fault (a) phase S Directional earth fault (a) phase T Directional earth fault (b) failure Directional earth fault (b) phase R Directional earth fault (b) phase S Directional earth fault (b) phase T Disturbance fault recorder faulty Disconnecting switch driving fault Direct transfer trip (a) receive Direct transfer trip (a) transmit Direct transfer trip (b) receive Direct transfer trip (b) transmit Distance (a) phase R zone 1 Distance (a) phase S zone 1 Distance (a) phase T zone 1 Distance (b) phase R zone 1 Distance (b) phase S zone 1 Distance (b) phase T zone 1 Distance (a) phase R zone 2 Distance (a) phase S zone 2 Distance (a) phase T zone 2 Distance (b) phase R zone 2 Distance (b) phase S zone 2 Distance (b) phase T zone 2 Distance (a) phase R zone 3 Distance (a) phase S zone 3 Distance (a) phase T zone 3 Distance (b) phase R zone 3 Distance (b) phase S zone 3 Distance (b) phase T zone 3 Distance relay (a) failure Distance (a) relay receive Distance (a) relay transmit Distance relay (b) failure Distance (b) relay receive Distance (b) relay transmit Event recorder failure Ground fault relay failure
Low oil pressure cable trip
Tipe A I A A A A A A A A A A A A A A A I I I I A A A A A A A A A A A A A A A A A A A I I A I I A A A A
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
MTO
108
Data
No 122 123 126 127 130 131 138 141 145 157 158 159 160 175 176 180 182 183 185 190 191 192 7 12 6
Kode
OCPA**)
Fungsi
Oil cable pressure alarm
Tipe A A A A A A I A A A A A A A A A A A A A A A I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSD RCD
OCRF OVR *) OVRF *) P2GFR P2OCR POT PWF RCBF SYNF SZPA SZPB SZPF TPAF *) TPBF *) UFR UVR *) UVRF *) VTF SIB IEDF SOTF ES LI
LI
Over current relay failure Over voltage relay operate Over voltage relay failure Ground fault relay Over current relay Protection on test Pilot wire failure Relay circuit breaker fail failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Teleprotection (a) failure Teleprotection (b) failure Under frequency relay operate Under voltage relay operate Under voltage relay failure Voltage transformer failure Software interlocking bypass IED Faulty Switch on to fault Earth switch closed/opened Line isolator switch closed/opened
Line isolator switch closed/opened
KETERANGAN: *) = **) =
109
TB-26: Bay Penghantar Pada Konfigurasi Double Busbar BAY PENGHANTAR PADA KONFIGURASI DOUBLE BUSBAR
TB-26
BUSBAR - A
BUSBAR - B
L/R P Q V I
Teleinformasi Data Untuk Bay Penghantar Pada Konfigurasi Double Busbar Data No 1 2 3 6 7 8 9 12 13 16 34 35 41 42 43 44 49 50 51 52 53 54 55 Kode AMF CCB CNTA *) I KVARH KWH P PRES Q V AR *) ARO *) CBDF CBFA CBFB CBM CDAF CDAR CDAS CDAT CDBF CDBR CDBS Fungsi Amperes fault ( per phase ) Counter of circuit breaker Counter arester Arus Kilovar hour Kilowatt hour Daya aktif Pressure Daya reaktif Tegangan Circuit breaker auto reclose Auto reclose off Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance Current differential relay (a) failure Current differential (a) phase R Current differential (a) phase S Current differential (a) phase T Current differential relay (b) failure Current differential (b) phase R Current differential (b) phase S Tipe Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TM
TSS
I I A A A I A A A A A A A
110
Data
No 56 57 58 60 62 63 64 65 66 67 68 69 70 71 72 73 74 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99
100 101 102 103 104 105
Kode CDBT CF *) CSP DCF DEARX *) DEATX *) DEBRX *) DEBTX *) DEFAF *) DEFAR DEFAS DEFAT DEFBF *) DEFBR DEFBS DEFBT DFRF DSDF DTARX *) DTATX *) DTBRX *) DTBTX *) DZ1AR *) DZ1AS *) DZ1AT *) DZ1BR *) DZ1BS *) DZ1BT *) DZ2AR *) DZ2AS *) DZ2AT *) DZ2BR *) DZ2BS *) DZ2BT *) DZ3AR *) DZ3AS *) DZ3AT *) DZ3BR *) DZ3BS *) DZ3BT *) DZAF *) DZARX *) DZATX *) DZBF *) DZBRX *) DZBTX *) ERF GFRF
LOWCT**)
Fungsi Current differential (b) phase T Carrier faulty Check synchronizing in progress DC supply failure Directional earth fault (a) relay receive Directional earth fault (a) relay transmit Directional earth fault (b) relay receive Directional earth fault (b) relay transmit Directional earth fault (a) failure Directional earth fault (a) phase R Directional earth fault (a) phase S Directional earth fault (a) phase T Directional earth fault (b) failure Directional earth fault (b) phase R Directional earth fault (b) phase S Directional earth fault (b) phase T Disturbance fault recorder faulty Disconnecting switch driving fault Direct transfer trip (a) receive Direct transfer trip (a) transmit Direct transfer trip (b) receive Direct transfer trip (b) transmit Distance (a) phase R zone 1 Distance (a) phase S zone 1 Distance (a) phase T zone 1 Distance (b) phase R zone 1 Distance (b) phase S zone 1 Distance (b) phase T zone 1 Distance (a) phase R zone 2 Distance (a) phase S zone 2 Distance (a) phase T zone 2 Distance (b) phase R zone 2 Distance (b) phase S zone 2 Distance (b) phase T zone 2 Distance (a) phase R zone 3 Distance (a) phase S zone 3 Distance (a) phase T zone 3 Distance (b) phase R zone 3 Distance (b) phase S zone 3 Distance (b) phase T zone 3 Distance relay (a) failure Distance (a) relay receive Distance (a) relay transmit Distance relay (b) failure Distance (b) relay receive Distance (b) relay transmit Event recorder failure Ground fault relay failure
Low oil pressure cable trip
Tipe A A I A A A A A A A A A A A A A A A I I I I A A A A A A A A A A A A A A A A A A A I I A I I A A A
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
111
Data
No 118 119 120 121 122 123 126 127 130 131 133 134 135 136 138 141 145 157 158 159 160 169 170 175 176 180 182 183 185 190 191 192 1 3 5 7 12 13 18 1 2 4 6 7 10
Fungsi Low pressure alarm Low pressure block Low pressure trip Master trip operate
Oil cable pressure alarm
Tipe A A A A A A A A A A A A A A I A A A A A A A A A A A A A A A A A I I I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1
TSD
OCRF OVR *) OVRF *) P2GFR P2OCR PD PHR PHS PHT POT PWF RCBF SYNF SZPA SZPB SZPF TCS1 TCS2 TPAF *) TPBF *) UFR UVR *) UVRF *) VTF SIB IEDF SOTF BI CB CSO ES LI LR SAM BI
CB CSO LI
Over current relay failure Over voltage relay operate Over voltage relay failure Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pilot wire failure Relay circuit breaker fail failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Trip coil supervisory 1 Trip coil supervisory 2 Teleprotection (a) failure Teleprotection (b) failure Under frequency relay operate Under voltage relay operate Under voltage relay failure Voltage transformer failure Software interlocking bypass IED Faulty Switch on to fault Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Earth switch closed/opened Line isolator switch closed/opened Local remote Synchronization auto/manual Bus isolator switch closed/opened
Circuit breaker closed/opened Check synchronizing override Line isolator switch closed/opened
RCD
LR SAM
KETERANGAN: *) = **) =
112
Teleinformasi Data Untuk Bay Penghantar Pada Konfigurasi Single Busbar Data No 1 2 3 6 7 8 9 12 13 16 34 35 41 42 43 44 49 50 51 52 53 54 55 56 57 58 60 Kode AMF CCB CNTA *) I KVARH KWH P PRES Q V AR *) ARO *) CBDF CBFA CBFB CBM CDAF CDAR CDAS CDAT CDBF CDBR CDBS CDBT CF *) CSP DCF Fungsi Amperes fault ( per phase ) Counter of circuit breaker Counter arester Arus Kilovar hour Kilowatt hour Daya aktif Pressure Daya reaktif Tegangan Circuit breaker auto reclose Auto reclose off Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance Current differential relay (a) failure Current differential (a) phase R Current differential (a) phase S Current differential (a) phase T Current differential relay (b) failure Current differential (b) phase R Current differential (b) phase S Current differential (b) phase T Carrier faulty Check synchronizing in progress DC supply failure Tipe Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TM
TSS
I I A A A I A A A A A A A A A I A
113
Data
No 62 63 64 65 66 67 68 69 70 71 72 73 74 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99
100 101 102 103 104 105
Kode DEARX DEATX *) DEBRX *) DEBTX *) DEFAF *) DEFAR DEFAS DEFAT DEFBF *) DEFBR DEFBS DEFBT DFRF DSDF DTARX *) DTATX *) DTBRX *) DTBTX *) DZ1AR *) DZ1AS *) DZ1AT *) DZ1BR *) DZ1BS *) DZ1BT *) DZ2AR *) DZ2AS *) DZ2AT *) DZ2BR *) DZ2BS *) DZ2BT *) DZ3AR *) DZ3AS *) DZ3AT *) DZ3BR *) DZ3BS *) DZ3BT *) DZAF *) DZARX *) DZATX *) DZBF *) DZBRX *) DZBTX *) ERF GFRF
LOWCT**)
*)
Fungsi Directional earth fault (a) relay receive Directional earth fault (a) relay transmit Directional earth fault (b) relay receive Directional earth fault (b) relay transmit Directional earth fault (a) failure Directional earth fault (a) phase R Directional earth fault (a) phase S Directional earth fault (a) phase T Directional earth fault (b) failure Directional earth fault (b) phase R Directional earth fault (b) phase S Directional earth fault (b) phase T Disturbance fault recorder faulty Disconnecting switch driving fault Direct transfer trip (a) receive Direct transfer trip (a) transmit Direct transfer trip (b) receive Direct transfer trip (b) transmit Distance (a) phase R zone 1 Distance (a) phase S zone 1 Distance (a) phase T zone 1 Distance (b) phase R zone 1 Distance (b) phase S zone 1 Distance (b) phase T zone 1 Distance (a) phase R zone 2 Distance (a) phase S zone 2 Distance (a) phase T zone 2 Distance (b) phase R zone 2 Distance (b) phase S zone 2 Distance (b) phase T zone 2 Distance (a) phase R zone 3 Distance (a) phase S zone 3 Distance (a) phase T zone 3 Distance (b) phase R zone 3 Distance (b) phase S zone 3 Distance (b) phase T zone 3 Distance relay (a) failure Distance (a) relay receive Distance (a) relay transmit Distance relay (b) failure Distance (b) relay receive Distance (b) relay transmit Event recorder failure Ground fault relay failure
Low oil pressure cable trip
Tipe A A A A A A A A A A A A A A I I I I A A A A A A A A A A A A A A A A A A A I I A I I A A A A A A A
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Low pressure alarm Low pressure block Low pressure trip Master trip operate
114
Data
No 122 123 126 127 130 131 133 134 135 136 138 141 145 157 158 159 160 169 170 175 176 180 182 183 185 190 191 192 1 3 5 7 12 13 18 1 2 4 6 7 10
Kode
OCPA**)
Fungsi
Oil cable pressure alarm
Tipe A A A A A A A A A A I A A A A A A A A A A A A A A A A A I I I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSD
OCRF OVR *) OVRF *) P2GFR P2OCR PD PHR PHS PHT POT PWF RCBF SYNF SZPA SZPB SZPF TCS1 TCS2 TPAF *) TPBF *) UFR UVR *) UVRF *) VTF SIB IEDF SOTF BI CB CSO ES LI LR SAM BI
CB CSO LI
Over current relay failure Over voltage relay operate Over voltage relay failure Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pilot wire failure Relay circuit breaker fail failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Trip coil supervisory 1 Trip coil supervisory 2 Teleprotection (a) failure Teleprotection (b) failure Under frequency relay operate Under voltage relay operate Under voltage relay failure Voltage transformer failure Software interlocking bypass IED Faulty Switch on to fault Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Earth switch closed/opened Line isolator switch closed/opened Local remote Synchronization auto/manual Bus isolator switch closed/opened
Circuit breaker closed/opened Check synchronizing override Line isolator switch closed/opened
RCD
LR SAM
KETERANGAN: *) = **) =
115
TB-28: Bay Penghantar Paralel Dengan Reaktor Pada Konfigurasi Double Busbar BAY PENGHANTAR PARALEL DENGAN REAKTOR PADA KONFIGURASI DOUBLE BUSBAR
BUSBAR - A TB-28
BUSBAR - B
L/R P Q V I
Teleinformasi Data Untuk Bay Penghantar Serial Dengan Reaktor Pada Konfigurasi Double Busbar Data No 1 2 3 6 7 8 9 12 13 16 34 Kode AMF CCB CNTA *) I KVARH KWH P PRES Q V AR *) Fungsi Amperes fault ( per phase ) Counter of circuit breaker Counter arester Arus Kilovar hour Kilowatt hour Daya aktif Pressure Daya reaktif Tegangan Circuit breaker auto reclose Tipe Jmh 1 1 1 1 1 1 1 1 2 1 1
TM
TSS
116
Data
No 35 41 42 43 44 49 50 51 52 53 54 55 56 57 58 60 62 63 64 65 66 67 68 69 70 71 72 73 74 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97
Kode ARO CBDF CBFA CBFB CBM CDAF CDAR CDAS CDAT CDBF CDBR CDBS CDBT CF *) CSP DCF DEARX *) DEATX *) DEBRX *) DEBTX *) DEFAF *) DEFAR DEFAS DEFAT DEFBF *) DEFBR DEFBS DEFBT DFRF DSDF DTARX *) DTATX *) DTBRX *) DTBTX *) DZ1AR *) DZ1AS *) DZ1AT *) DZ1BR *) DZ1BS *) DZ1BT *) DZ2AR *) DZ2AS *) DZ2AT *) DZ2BR *) DZ2BS *) DZ2BT *) DZ3AR *) DZ3AS *) DZ3AT *) DZ3BR *)
*)
Fungsi Auto reclose off Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance Current differential relay (a) failure Current differential (a) phase R Current differential (a) phase S Current differential (a) phase T Current differential relay (b) failure Current differential (b) phase R Current differential (b) phase S Current differential (b) phase T Carrier faulty Check synchronizing in progress DC supply failure Directional earth fault (a) relay receive Directional earth fault (a) relay transmit Directional earth fault (b) relay receive Directional earth fault (b) relay transmit Directional earth fault (a) failure Directional earth fault (a) phase R Directional earth fault (a) phase S Directional earth fault (a) phase T Directional earth fault (b) failure Directional earth fault (b) phase R Directional earth fault (b) phase S Directional earth fault (b) phase T Disturbance fault recorder faulty Disconnecting switch driving fault Direct transfer trip (a) receive Direct transfer trip (a) transmit Direct transfer trip (b) receive Direct transfer trip (b) transmit Distance (a) phase R zone 1 Distance (a) phase S zone 1 Distance (a) phase T zone 1 Distance (b) phase R zone 1 Distance (b) phase S zone 1 Distance (b) phase T zone 1 Distance (a) phase R zone 2 Distance (a) phase S zone 2 Distance (a) phase T zone 2 Distance (b) phase R zone 2 Distance (b) phase S zone 2 Distance (b) phase T zone 2 Distance (a) phase R zone 3 Distance (a) phase S zone 3 Distance (a) phase T zone 3 Distance (b) phase R zone 3
Tipe I A A A I A A A A A A A A A I A A A A A A A A A A A A A A A I I I I A A A A A A A A A A A A A A A A
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
117
Data
No 98 99
100 101 102 103 104 105
Kode DZ3BS DZ3BT *) DZAF *) DZARX *) DZATX *) DZBF *) DZBRX *) DZBTX *) ERF GFRF
LOWCT**)
*)
Fungsi Distance (b) phase S zone 3 Distance (b) phase T zone 3 Distance relay (a) failure Distance (a) relay receive Distance (a) relay transmit Distance relay (b) failure Distance (b) relay receive Distance (b) relay transmit Event recorder failure Ground fault relay failure
Low oil pressure cable trip
Tipe A A A I I A I I A A A A A A A A A A A A A A A A A I A A A A A A A A A A A A A A A A A I I I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 2 2 1 1
TSD
106 111 117 118 119 120 121 122 123 126 127 130 131 133 134 135 136 138 141 145 157 158 159 160 169 170 175 176 180 182 183 185 190 191 192 1 3 5 7 12 13 18
Low pressure alarm Low pressure block Low pressure trip Master trip operate
Oil cable pressure alarm
OCRF OVR *) OVRF *) P2GFR P2OCR PD PHR PHS PHT POT PWF RCBF SYNF SZPA SZPB SZPF TCS1 TCS2 TPAF *) TPBF *) UFR UVR *) UVRF *) VTF SIB IEDF SOTF BI CB CSO ES LI LR SAM
Over current relay failure Over voltage relay operate Over voltage relay failure Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pilot wire failure Relay circuit breaker fail failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Trip coil supervisory 1 Trip coil supervisory 2 Teleprotection (a) failure Teleprotection (b) failure Under frequency relay operate Under voltage relay operate Under voltage relay failure Voltage transformer failure Software interlocking bypass IED Faulty Switch on to fault Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Earth switch closed/opened Line isolator switch closed/opened Local remote Synchronization auto/manual
118
Data
No 1 2 4 6 7 10
Kode BI
CB CSO LI
Tipe
Jmh 2 1 1 2 1 1
RCD
LR SAM
KETERANGAN: *) = **) =
119
TB-29: Bay Penghantar Paralel Dengan 1 Reaktor Pada Konfigurasi 1 Breaker BAY PENGHANTAR PARALEL DENGAN 1 REAKTOR PADA KONFIGURASI 1 BREAKER
BUSBAR - A TB-29
BUSBAR - B
Q L/R
P Q V I
Teleinformasi Data Untuk Bay Penghantar Paralel Dengan 1 Reaktor Pada Konfigurasi 1 Breaker Data No 1 3 6 7 8 9 13 16 49 50 51 52 53 54 55 Kode AMF CNTA *) I KVARH KWH P Q V CDAF CDAR CDAS CDAT CDBF CDBR CDBS Fungsi Amperes fault ( per phase ) Counter arester Arus Kilovar hour Kilowatt hour Daya aktif Daya reaktif Tegangan Current differential relay (a) failure Current differential (a) phase R Current differential (a) phase S Current differential (a) phase T Current differential relay (b) failure Current differential (b) phase R Current differential (b) phase S Tipe Jmh 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1
TM
TSS
A A A A A A A
120
Data
No 56 57 58 60 62 63 64 65 66 67 68 69 70 71 72 73 74 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99
100 101 102 103 104 105
Kode CDBT CF *) CSP DCF DEARX *) DEATX *) DEBRX *) DEBTX *) DEFAF *) DEFAR DEFAS DEFAT DEFBF *) DEFBR DEFBS DEFBT DFRF DSDF DTARX *) DTATX *) DTBRX *) DTBTX *) DZ1AR *) DZ1AS *) DZ1AT *) DZ1BR *) DZ1BS *) DZ1BT *) DZ2AR *) DZ2AS *) DZ2AT *) DZ2BR *) DZ2BS *) DZ2BT *) DZ3AR *) DZ3AS *) DZ3AT *) DZ3BR *) DZ3BS *) DZ3BT *) DZAF *) DZARX *) DZATX *) DZBF *) DZBRX *) DZBTX *) ERF GFRF
LOWCT**)
Fungsi Current differential (b) phase T Carrier faulty Check synchronizing in progress DC supply failure Directional earth fault (a) relay receive Directional earth fault (a) relay transmit Directional earth fault (b) relay receive Directional earth fault (b) relay transmit Directional earth fault (a) failure Directional earth fault (a) phase R Directional earth fault (a) phase S Directional earth fault (a) phase T Directional earth fault (b) failure Directional earth fault (b) phase R Directional earth fault (b) phase S Directional earth fault (b) phase T Disturbance fault recorder faulty Disconnecting switch driving fault Direct transfer trip (a) receive Direct transfer trip (a) transmit Direct transfer trip (b) receive Direct transfer trip (b) transmit Distance (a) phase R zone 1 Distance (a) phase S zone 1 Distance (a) phase T zone 1 Distance (b) phase R zone 1 Distance (b) phase S zone 1 Distance (b) phase T zone 1 Distance (a) phase R zone 2 Distance (a) phase S zone 2 Distance (a) phase T zone 2 Distance (b) phase R zone 2 Distance (b) phase S zone 2 Distance (b) phase T zone 2 Distance (a) phase R zone 3 Distance (a) phase S zone 3 Distance (a) phase T zone 3 Distance (b) phase R zone 3 Distance (b) phase S zone 3 Distance (b) phase T zone 3 Distance relay (a) failure Distance (a) relay receive Distance (a) relay transmit Distance relay (b) failure Distance (b) relay receive Distance (b) relay transmit Event recorder failure Ground fault relay failure
Low oil pressure cable trip
Tipe A A I A A A A A A A A A A A A A A A I I I I A A A A A A A A A A A A A A A A A A A I I A I I A A A
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
121
Data
No 121 122 123 126 127 130 131 138 141 145 157 158 159 160 175 176 180 182 183 185 190 191 192 3 7 12 2 6
Kode MTO
OCPA**)
Tipe A A A A A A A I A A A A A A A A A A A A A A A I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 1 2
TSD RCD
OCRF OVR *) OVRF *) P2GFR P2OCR POT PWF RCBF SYNF SZPA SZPB SZPF TPAF *) TPBF *) UFR UVR *) UVRF *) VTF SIB IEDF SOTF CB ES LI CB
LI
Over current relay failure Over voltage relay operate Over voltage relay failure Ground fault relay Over current relay Protection on test Pilot wire failure Relay circuit breaker fail failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Teleprotection (a) failure Teleprotection (b) failure Under frequency relay operate Under voltage relay operate Under voltage relay failure Voltage transformer failure Software interlocking bypass IED Faulty Switch on to fault Circuit breaker closed/opened Earth switch closed/opened Line isolator switch closed/opened Circuit breaker closed/opened
Line isolator switch closed/opened
KETERANGAN: *) = **) =
122
TB-30: Bay Penghantar Paralel Dengan 2 Reaktor Seri Pada Konfigurasi 1 Breaker BAY PENGHANTAR PARALEL DENGAN 2 REAKTOR SERI PADA KONFIGURASI 1 BREAKER
BUSBAR -A TB-30
BUSBAR -B Q Q P Q V I
Teleinformasi Data Untuk Bay Penghantar Paralel Dengan 2 Reaktor seri Pada Konfigurasi 1 Breaker Data No 1 3 6 7 8 9 13 16 49 50 51 52 53 54 Kode AMF CNTA *) I KVARH KWH P Q V CDAF CDAR CDAS CDAT CDBF CDBR Fungsi Amperes fault ( per phase ) Counter arester Arus Kilovar hour Kilowatt hour Daya aktif Daya reaktif Tegangan Current differential relay (a) failure Current differential (a) phase R Current differential (a) phase S Current differential (a) phase T Current differential relay (b) failure Current differential (b) phase R Tipe Jmh 1 1 1 1 1 1 3 1 1 1 1 1 1 1
TM
TSS
A A A A A A
123
Data
No 55 56 57 58 60 62 63 64 65 66 67 68 69 70 71 72 73 74 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99
100 101 102 103 104 105
Kode CDBS CDBT CF *) CSP DCF DEARX *) DEATX *) DEBRX *) DEBTX *) DEFAF *) DEFAR DEFAS DEFAT DEFBF *) DEFBR DEFBS DEFBT DFRF DSDF DTARX *) DTATX *) DTBRX *) DTBTX *) DZ1AR *) DZ1AS *) DZ1AT *) DZ1BR *) DZ1BS *) DZ1BT *) DZ2AR *) DZ2AS *) DZ2AT *) DZ2BR *) DZ2BS *) DZ2BT *) DZ3AR *) DZ3AS *) DZ3AT *) DZ3BR *) DZ3BS *) DZ3BT *) DZAF *) DZARX *) DZATX *) DZBF *) DZBRX *) DZBTX *) ERF GFRF
Fungsi Current differential (b) phase S Current differential (b) phase T Carrier faulty Check synchronizing in progress DC supply failure Directional earth fault (a) relay receive Directional earth fault (a) relay transmit Directional earth fault (b) relay receive Directional earth fault (b) relay transmit Directional earth fault (a) failure Directional earth fault (a) phase R Directional earth fault (a) phase S Directional earth fault (a) phase T Directional earth fault (b) failure Directional earth fault (b) phase R Directional earth fault (b) phase S Directional earth fault (b) phase T Disturbance fault recorder faulty Disconnecting switch driving fault Direct transfer trip (a) receive Direct transfer trip (a) transmit Direct transfer trip (b) receive Direct transfer trip (b) transmit Distance (a) phase R zone 1 Distance (a) phase S zone 1 Distance (a) phase T zone 1 Distance (b) phase R zone 1 Distance (b) phase S zone 1 Distance (b) phase T zone 1 Distance (a) phase R zone 2 Distance (a) phase S zone 2 Distance (a) phase T zone 2 Distance (b) phase R zone 2 Distance (b) phase S zone 2 Distance (b) phase T zone 2 Distance (a) phase R zone 3 Distance (a) phase S zone 3 Distance (a) phase T zone 3 Distance (b) phase R zone 3 Distance (b) phase S zone 3 Distance (b) phase T zone 3 Distance relay (a) failure Distance (a) relay receive Distance (a) relay transmit Distance relay (b) failure Distance (b) relay receive Distance (b) relay transmit Event recorder failure Ground fault relay failure
Tipe A A A I A A A A A A A A A A A A A A A I I I I A A A A A A A A A A A A A A A A A A A I I A I I A A
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
106 111
124
Data
No 117 121 122 123 126 127 130 131 138 141 145 157 158 159 160 175 176 180 182 183 185 190 191 192 7 12 6
Kode
LOWCT**)
Fungsi
Low oil pressure cable trip
Tipe A A A A A A A A I A A A A A A A A A A A A A A A I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 3 2
MTO
OCPA**)
TSD RCD
OCRF OVR *) OVRF *) P2GFR P2OCR POT PWF RCBF SYNF SZPA SZPB SZPF TPAF *) TPBF *) UFR UVR *) UVRF *) VTF SIB IEDF SOTF ES LI
LI
Over current relay failure Over voltage relay operate Over voltage relay failure Ground fault relay Over current relay Protection on test Pilot wire failure Relay circuit breaker fail failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Teleprotection (a) failure Teleprotection (b) failure Under frequency relay operate Under voltage relay operate Under voltage relay failure Voltage transformer failure Software interlocking bypass IED Faulty Switch on to fault Earth switch closed/opened Line isolator switch closed/opened
Line isolator switch closed/opened
KETERANGAN: *) = **) =
125
TB-31: Bay Kopel Pada Konfigurasi Double Busbar BAY KOPEL PADA KONFIGURASI DOUBLE BUSBAR
TB-31
L/R
I
BUSBAR - A
BUSBAR - B
Teleinformasi Data Untuk Bay Kopel Pada Konfigurasi Double Busbar Data TM No 2 6 12 41 42 43 44 58 60 77 106 111 118 119 120 121 123 130 131 133 134 135 136 138 145 157 158 Kode CCB I PRES CBDF CBFA CBFB CBM CSP DCF DSDF ERF GFRF LPA LPB LPT MTO OCRF P2GFR P2OCR PD PHR PHS PHT POT RCBF SYNF SZPA Fungsi Counter of circuit breaker Arus Pressure Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance Check synchronizing in progress DC supply failure Disconnecting switch driving fault Event recorder failure Ground fault relay failure Low pressure alarm Low pressure block Low pressure trip Master trip operate Over current relay failure Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Relay circuit breaker fail failure Synchronizing failure Short zone protection (a) operate Tipe Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSS
A A A I I A A A A A A A A A A A A A A A I A A A
126
Data
Kode SZPB SZPF TCS1 TCS2 SIB IEDF SOTF BI CB CSO LR SAM BI
CB CSO
Fungsi Short zone protection (b) operate Short zone protection failure Trip coil supervisory 1 Trip coil supervisory 2 Software interlocking bypass IED Faulty Switch on to fault Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Local remote Synchronization auto/manual Bus isolator switch closed/opened
Circuit breaker closed/opened Check synchronizing override
Tipe A A A A A A A I I I I I
Jmh 1 1 1 1 1 1 1 2 1 1 1 1 2 1 1 1 1
TSD
RCD
LR SAM
127
BUS SECTION
Tipe-1
L/R
Tipe-2 L/R
Teleinformasi Data Untuk Bus Section Data TM No 2 12 41 42 43 44 58 106 111 118 119 120 121 123 130 131 133 134 135 136 138 145 157 158 Kode CCB PRES CBDF CBFA CBFB CBM CSP ERF GFRF LPA LPB LPT MTO OCRF P2GFR P2OCR PD PHR PHS PHT POT RCBF SYNF SZPA Fungsi Counter of circuit breaker Pressure Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance Check synchronizing in progress Event recorder failure Ground fault relay failure Low pressure alarm Low pressure block Low pressure trip Master trip operate Over current relay failure Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Relay circuit breaker fail failure Synchronizing failure Short zone protection (a) operate Tipe Jmh Tipe-1 Tipe-2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSS
A A A I I A A A A A A A A A A A A A I A A A
128
Data
TSD
RCD
Kode SZPB SZPF TCS1 TCS2 SIB IEDF SOTF BI CB CSO LR SAM BI
CB CSO
Fungsi Short zone protection (b) operate Short zone protection failure Trip coil supervisory 1 Trip coil supervisory 2 Software interlocking bypass IED Faulty Switch on to fault Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Local remote Synchronization auto/manual Bus isolator switch closed/opened
Circuit breaker closed/opened Check synchronizing override
Tipe A A A A A A A I I I I I
Jmh 1 1 1 1 1 1 1 2 1 1 1 1 2 1 1 1 1 1 1
LR SAM
129
TB-33
L/R
L/R
L/R
BUSBAR - B
Teleinformasi Data Untuk Diameter Data TM No 2 12 41 42 43 44 46 47 48 58 106 118 119 120 121 133 134 135 136 138 145 157 Kode CCB PRES CBDF CBFA CBFB CBM CCPA CCPB CCPF CSP ERF LPA LPB LPT MTO PD PHR PHS PHT POT RCBF SYNF Fungsi Counter of circuit breaker Pressure Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance Circulating current protection (a) operate Circulating current protection (b) operate Circulating current protection failure Check synchronizing in progress Event recorder failure Low pressure alarm Low pressure block Low pressure trip Master trip operate Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Relay circuit breaker fail failure Synchronizing failure Tipe Jmh 3 3 3 3 3 3 1 1 3 3 3 3 3 3 1 3 3 3 3 1 3 3
TSS
A A A I A A A I A A A A A A A A A I A A
130
Data
Kode SZPA SZPB SZPF TCS1 TCS2 SIB IEDF SOTF BI CB CSO LR SAM BI CB CSO LR SAM
Fungsi Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Trip coil supervisory 1 Trip coil supervisory 2 Software interlocking bypass IED Faulty Switch on to fault Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Local remote Synchronization auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Local remote Synchronization auto/manual
Tipe A A A A A A A A I I I I I
Jmh 3 3 3 3 3 3 3 3 6 3 3 3 3 6 3 3 3 3
TSD
RCD
131
Teleinformasi Data Untuk Bus Bar Data TM No 7 37 38 39 40 77 106 126 127 138 182 183 184 191 7 Kode V BPA BPAF BPB BPBF DSDF ERF OVR OVRF POT UVR UVRF VS IEDF ES Fungsi Tegangan Busbar protection (a) Busbar protection (a) failure Busbar protection (b) Busbar protection (b) failure Disconnecting switch driving fault Event recorder failure Over voltage relay operate Over voltage relay failure Protection on test Under voltage relay operate Under voltage relay failure Voltage status IED Faulty Earth switch closed/opened Tipe A A A A A A A A I A A I A I Jumlah 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSS
TSD
132
133
C-1: Telesignal
No Kode Fungsi Implementasi Feeder PBO Bus Coupler Bus Section Feeder Incoming Capacitor Reactor Gen Transf Capacitor Bus Coupler Bus Section Feeder Incoming Capacitor Reactor Gen Transf Generator PBO RTU RTU Bus Coupler Bus Section Feeder Incoming Capacitor Reactor Gen Transf Keypoint Gardu Tengah Gardu Hubung Generator Key Point Gardu Tengah Gardu Hubung Bus Coupler Bus Section Feeder Capacitor Reactor Gen Transf Generator Keypoint PBO Gardu Tengah Gardu Hubung Bus Coupler Bus Section Feeder Incoming Capacitor Reactor Gen Transf D D I I Single (S) or Double (D) Indication D Suggested Alarm (A) or Event/Indication (I) I
ARU
BI
CAM
Capacitor Auto/Manual
CB
5 6
CD DCBC
D D
I I
ES
8 9
GUC LBS
10
LR
Local Remote
11
RACK
134
No
Kode
Fungsi
Implementasi Generator
12 13 14
RR 110RF 110SF
Feeder PBO Gardu Induk Gardu Induk Gardu Induk Keypoint PBO Gardu Tengah Gardu Hubung Gardu Induk Gardu Induk Keypoint PBO Gardu Tengah Gardu Hubung Gardu Induk Keypoint PBO Gardu Tengah Gardu Hubung k RTU Feeder PBO Feeder PBO Bus Coupler Bus Section Feeder Incoming Capacitor Reactor Gen Transf PBO Bus Coupler Bus Section Feeder Incoming Capacitor Reactor PBO RTU IED Gardu Induk Keypoint PBO Gardu Tengah Gardu Hubung Gardu Induk Keypoint PBO Gardu Tengah Gardu Hubung
D S S
I A A
15
220F
16
380F
17
48RF
18
48SF
19 20 21
AIRCF AR ARO
Air Conditioning Failure Circuit Breaker Auto Reclose Auto Reclose Off
S S S
A A A
22
CBDF
23
CBTR
CB Trip
24
CTE
Cabinet Temperatur
25
DCG
DC Ground
26
DOOR
Door Activated
135
No
Kode
Fungsi
Implementasi Gardu Induk IED PBO Gardu Tengah Gardu Hubung Gardu Induk Gardu Induk Gardu Induk PBO Gen Transf Keypoint Gardu Hubung Gardu Tengah RTU IED Bus Coupler Bus Section Feeder Incoming Capacitor Reactor Gen Transf PBO PBO Feeder Bus Coupler Bus Section Feeder Capacitor Reactor Bus Coupler Bus Section Feeder Capacitor Reactor Gardu Induk Bus Coupler Bus Section Feeder Capacitor Reactor Gardu Induk Keypoint PBO Gardu Tengah Gardu Hubung Gen Transf Gen Transf
27
FOTF
FO Terminal Faulty
28 29 30 31 32 33 34
Fire Protection Operated Fire Alarm Fire Alarm System Failure Ground Fault Relay Failure Generator Transformer Trip Homopolar Fault Detector Internal Remote Station
S S S S S S S
A A A A A A A
35
LPA
36 37
OCRF P1DEF
S S
A A
38
P2GFR
39
P2OCR
40
PBXF
PABX Faulty
41
PTF
Protection Faulty
42
RADF
43 44
RBUCA RBUCZ
S S
A A
136
No
Kode
Fungsi
Implementasi
45 46 47 48 49 50 51 52
Reaktor Fire Detection & Protection Reaktor Oil Level Alarm Reaktor Sudden Pressure Alarm Reaktor Bucholz Sudden Pressure Trip Reset Alarm Station Intruder Alarm Tap Changer High Limit Tap Changer Low Limit
Gen Transf Gen Transf Gen Transf Gen Transf Gardu Induk Gardu Induk Incoming Incoming Bus Coupler Bus Section Feeder Incoming Capacitor Reactor Gen Transf PBO Incoming Feeder Generator
53
TCS1
54 55 56
TPIF UFR UT
Tap Position Indication Failure Under Frequency Relay Operate Unit Trip
S S S
A A A
137
C-2: Telemeasurement
No Kode Fungsi Implementasi Feeder Incoming Gen Transf PBO Bus Coupler Bus Section Feeder Incoming Capacitor Reactor Gen Transf PBO Busbar Feeder Incoming Capacitor Reactor Generator Keypoint PBO Feeder Incoming Capacitor Reactor Gen Transf Feeder Incoming Capacitor Reactor Gen Transf Feeder Incoming Capacitor Reactor Generator Keypoint Incoming Incoming Capacitor Reactor Generator Busbar Generator Keypoint PBO
AMF
CCB
Frekuensi
Arus
KVARH
Kilovar Hour
KWH
Kilowatt Hour
Daya Aktif
PF
Power Factor
Daya Reaktif
10
Tegangan
138
TPI
Incoming
139
ARU
CB
3 4
CD DCBC
LBS
LR
Local Remote
7 8
RMT RR
140
141
P Q V
P Q I L/ R L/R
KOPEL
BUSBAR - A
L/R I P Q PF
L/R
FEEDER
INCOMING 20KV
142
Teleinformasi Data Untuk Konfigurasi Umum Pada Double Busbar Group Data No Kode Fungsi Bay 3 F Frekuensi Busbar TM 10 V Tegangan 1 AMF Ampere Fault 2 CCB Counter of Circuit Breaker 4 I Arus TM 5 KVARH Kilovar Hour 6 KWH Kilowatt Hour 7 P Daya Aktif 20 AR Circuit Breaker Auto Reclose 21 ARO Auto Reclose Off 22 CBDF Circuit Breaker Drive Failure 23 CBTR CB Trip 35 LPA Low Pressure Alarm 37 P1DEF Directional Earth Fault TSS 38 P2GFR Ground Fault Relay Feeder 39 P2OCR Over Current Relay 41 PTF Protection Faulty 53 TCS1 Trip Coil Supervisory 1 55 UFR Under Frequency Relay Operate 1 ARU Auto Reclose Use/Unuse 2 BI Bus Isolator Switch Closed/Opened 4 CB Circuit Breaker Closed/Opened TSD 7 ES Earth Switch Closed/Opened 10 LR Local Remote 12 RR Recloser Reset 1 ARU Auto Recloser Use/Unuse 2 CB Circuit Breaker Closed/Opened RCD 6 LR Local Remote 8 RR Recloser Reset 1 AMF Amperes Fault 2 CCB Counter of Circuit Breaker 4 I Arus 5 KVARH Kilovar Hour TM 6 KWH Kilowatt Hour 7 P Daya Aktif 8 PF Power Factor 9 Q Daya Reaktif 22 CBDF Circuit Breaker Drive Failure Incoming 23 CBTR CB Trip 20 kV 35 LPA Low Pressure Alarm 38 P2GFR Ground Fault Relay 39 P2OCR Over Current Relay TSS 41 PTF Protection Faulty 51 TCH Tap Changer High Limit 52 TCL Tap Changer Low Limit 53 TCS1 Trip Coil Supervisory 54 TPIF Tap Position Indication Failure TSD 2 BI Bus Isolator Switch Closed/Opened
Tipe
Jmh 1 6 3 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 3 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2
A A A A A A A A A A A I I I I I I
A A A A A A A A A A I
143
Group Bay
Data
No 4 7 2 6 2 4 5 6 7 9 22 23 35 37 38 39 41 53 2 3 4 7 10 2 6 4 7 9 10 56 4 8 2 22 23 35 38 39 41 53 2 4 7 10 2 6
Kode CB ES CB LR CCB I KVARH KWH P Q CBDF CBTR LPA P1DEF P2GFR P2OCR PTF TCS1 BI CAM CB ES LR CB LR I P Q V UT CB GUC CCB CBDF CBTR LPA P2GFR P2OCR PTF TCS1 BI CB ES LR CB LR
Fungsi Circuit Breaker Closed/Opened Earth Switch Closed/Opened Circuit Breaker Closed/Opened Local Remote Counter of Circuit Breaker Arus Kilovar Hour Kilowatt Hour Daya Aktif Daya Reaktif Circuit Breaker Drive Failure CB Trip Low Pressure Alarm Directional Earth Fault Ground Fault Relay Over Current Relay Protection Faulty Trip Coil Supervisory 1 Bus Isolator Switch Closed/Opened Capacitor Auto/Manual Circuit Breaker Closed/Opened Earth Switch Closed/Opened Local Remote Circuit Breaker Closed/Opened Local Remote Arus Daya aktif Daya reaktif Tegangan Unit Trip Circuit breaker closed/opened Generator unit run/stop Counter of Circuit Breaker Circuit Breaker Drive Failure CB Trip Low Pressure Alarm Ground Fault Relay Over Current Relay Protection Faulty Trip Coil Supervisory 1 Bus Isolator Switch Closed/Opened Circuit Breaker Closed/Opened Earth Switch Closed/Opened Local Remote Circuit Breaker Closed/Opened Local Remote
Tipe I I I I
Jmh 1 1 1 1 1 3 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1
RCD
TM
Capasitor
TSS
TSD
A A A A A A A A I I I I I
RCD
A I I A A A A A A A I I I I
TSS Kopel
TSD
RCD
144
P Q V
P Q I
L/R
BUSBAR - A
L/R
I P Q PF
L/R
FEEDER
INCOMING 20 KV
145
Teleinformasi Data Untuk Konfigurasi Umum Pada Single Busbar Group Data No Kode Fungsi Bay 3 F Frekuensi Busbar TM 10 V Tegangan 1 AMF Ampere Fault 2 CCB Counter of Circuit Breaker 4 I Arus TM 5 KVARH Kilovar Hour 6 KWH Kilowatt Hour 7 P Daya Aktif 20 AR Circuit Breaker Auto Reclose 21 ARO Auto Reclose Off 22 CBDF Circuit Breaker Drive Failure 23 CBTR CB Trip 35 LPA Low Pressure Alarm 37 P1DEF Directional Earth Fault TSS 38 P2GFR Ground Fault Relay Feeder 39 P2OCR Over Current Relay 41 PTF Protection Faulty 53 TCS1 Trip Coil Supervisory 1 55 UFR Under Frequency Relay Operate 1 ARU Auto Reclose Use/Unuse 2 BI Bus Isolator Switch Closed/Opened 4 CB Circuit Breaker Closed/Opened TSD 7 ES Earth Switch Closed/Opened 10 LR Local Remote 12 RR Recloser Reset 1 ARU Auto Recloser Use/Unuse 2 CB Circuit Breaker Closed/Opened RCD 6 LR Local Remote 8 RR Recloser Reset 1 AMF Amperes Fault 2 CCB Counter of Circuit Breaker 4 I Arus 5 KVARH Kilovar Hour TM 6 KWH Kilowatt Hour 7 P Daya Aktif 8 PF Power Factor 9 Q Daya Reaktif 22 CBDF Circuit Breaker Drive Failure Incoming 23 CBTR CB Trip 20 kV 35 LPA Low Pressure Alarm 38 P2GFR Ground Fault Relay 39 P2OCR Over Current Relay TSS 41 PTF Protection Faulty 51 TCH Tap Changer High Limit 52 TCL Tap Changer Low Limit 53 TCS1 Trip Coil Supervisory 54 TPIF Tap Position Indication Failure TSD 2 BI Bus Isolator Switch Closed/Opened
Tipe
Jmh 1 3 3 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
A A A A A A A A A A A I I I I I I
A A A A A A A A A A I
146
Group Bay
Data
No 4 7 2 6 2 4 5 6 7 9 22 23 35 37 38 39 41 53 2 3 4 7 10 2 6 4 7 9 10 56 4 8
Kode CB ES CB LR CCB I KVARH KWH P Q CBDF CBTR LPA P1DEF P2GFR P2OCR PTF TCS1 BI CAM CB ES LR CB LR I P Q V UT CB GUC
Fungsi Circuit Breaker Closed/Opened Earth Switch Closed/Opened Circuit Breaker Closed/Opened Local Remote Counter of Circuit Breaker Arus Kilovar Hour Kilowatt Hour Daya Aktif Daya Reaktif Circuit Breaker Drive Failure CB Trip Low Pressure Alarm Directional Earth Fault Ground Fault Relay Over Current Relay Protection Faulty Trip Coil Supervisory 1 Bus Isolator Switch Closed/Opened Capacitor Auto/Manual Circuit Breaker Closed/Opened Earth Switch Closed/Opened Local Remote Circuit Breaker Closed/Opened Local Remote Arus Daya aktif Daya reaktif Tegangan Unit Trip Circuit breaker closed/opened Generator unit run/stop
Tipe I I I I
Jmh 1 1 1 1 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 1 1 1 1 1 1
RCD
TM
Capasitor
TSS
TSD
A A A A A A A A I I I I I
RCD
A I I
147
DB - 01
RCC
I P Q PF
DCC
L/R
Teleinformasi Data Untuk Trafo 150/20 kV dan 70/20 kV Tipe 1 Group Data No Kode Fungsi Bay 3 F Frekuensi Busbar TM 10 V Tegangan 1 AMF Amperes Fault 2 CCB Counter of Circuit Breaker 4 I Arus 5 KVARH Kilovar Hour TM 6 KWH Kilowatt Hour 7 P Daya Aktif 8 PF Power Factor 9 Q Daya Reaktif 22 CBDF Circuit Breaker Drive Failure Incoming 23 CBTR CB Trip 20 kV 35 LPA Low Pressure Alarm 38 P2GFR Ground Fault Relay 39 P2OCR Over Current Relay TSS 41 PTF Protection Faulty 51 TCH Tap Changer High Limit 52 TCL Tap Changer Low Limit 53 TCS1 Trip Coil Supervisory 54 TPIF Tap Position Indication Failure TSD 2 BI Bus Isolator Switch Closed/Opened
Tipe
Jmh 1 6 3 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2
A A A A A A A A A A I
148
Group Bay
Data
No 4 7 2 6
Kode CB ES CB LR
Fungsi Circuit Breaker Closed/Opened Earth Switch Closed/Opened Circuit Breaker Closed/Opened Local Remote
Tipe I I I I
Jmh 1 1 1 1
RCD
149
DB -02
RCC DCC
I P Q PF
L/R
Teleinformasi Data Untuk Trafo 150/20 kV dan 70/20 kV Tipe 2 Group Data No Kode Fungsi Bay 3 F Frekuensi Busbar TM 10 V Tegangan 1 AMF Amperes Fault 2 CCB Counter of Circuit Breaker 4 I Arus 5 KVARH Kilovar Hour TM 6 KWH Kilowatt Hour 7 P Daya Aktif 8 PF Power Factor 9 Q Daya Reaktif 22 CBDF Circuit Breaker Drive Failure Incoming 23 CBTR CB Trip 20 kV 35 LPA Low Pressure Alarm 38 P2GFR Ground Fault Relay 39 P2OCR Over Current Relay TSS 41 PTF Protection Faulty 51 TCH Tap Changer High Limit 52 TCL Tap Changer Low Limit 53 TCS1 Trip Coil Supervisory 54 TPIF Tap Position Indication Failure TSD 4 CB Circuit Breaker Closed/Opened
Tipe
Jmh 1 6 3 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
A A A A A A A A A A I
150
Group Bay
Data
No 7 11 2 6
Kode ES RACK CB LR
Fungsi Earth Switch Closed/Opened Circuit Breaker Rackin/Rackout Circuit Breaker Closed/Opened Local Remote
Tipe I I I I
Jmh 1 1 1 1
RCD
151
RCC DCC
I P Q PF L/R
Teleinformasi Data Untuk Trafo 150/20 kV dan 70/20 kV Tipe 3 Group Data No Kode Fungsi Bay 3 F Frekuensi Busbar TM 10 V Tegangan 1 AMF Amperes Fault 2 CCB Counter of Circuit Breaker 4 I Arus 5 KVARH Kilovar Hour TM 6 KWH Kilowatt Hour 7 P Daya Aktif 8 PF Power Factor 9 Q Daya Reaktif 22 CBDF Circuit Breaker Drive Failure 23 CBTR CB Trip Incoming 20 kV 35 LPA Low Pressure Alarm 38 P2GFR Ground Fault Relay 39 P2OCR Over Current Relay TSS 41 PTF Protection Faulty 51 TCH Tap Changer High Limit 52 TCL Tap Changer Low Limit 53 TCS1 Trip Coil Supervisory 54 TPIF Tap Position Indication Failure 2 BI Bus Isolator Switch Closed/Opened TSD 4 CB Circuit Breaker Closed/Opened
Tipe
Jmh 1 3 3 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
A A A A A A A A A A I I
152
Group Bay
Data
No 7 2 6
Kode ES CB LR
Tipe I I I
Jmh 1 1 1
RCD
153
DB-04
P Q V
P Q I L/R
BUSBAR - A
BUSBAR - B
Teleinformasi Data Untuk Generator Pada Konfigurasi Double Busbar Group Data No Kode Fungsi Bay 3 F Frekuensi Busbar TM 10 V Tegangan 1 AMF Amperes Fault 2 CCB Counter of Circuit Breaker 4 I Arus 5 KVARH Kilovar Hour TM 6 KWH Kilowatt Hour 7 P Daya Aktif 8 PF Power Factor 9 Q Daya Reaktif 22 CBDF Circuit Breaker Drive Failure Incoming 20 kV 23 CBTR CB Trip 35 LPA Low Pressure Alarm 38 P2GFR Ground Fault Relay 39 P2OCR Over Current Relay TSS 41 PTF Protection Faulty 51 TCH Tap Changer High Limit 52 TCL Tap Changer Low Limit 53 TCS1 Trip Coil Supervisory 54 TPIF Tap Position Indication Failure
Tipe
Jmh 1 6 3 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
A A A A A A A A A A
154
Group Bay
Data TSD
No 2 4 7 2 6 4 7 9 10 56 4 8
Kode BI CB ES CB LR I P Q V UT CB GUC
Fungsi Bus Isolator Switch Closed/Opened Circuit Breaker Closed/Opened Earth Switch Closed/Opened Circuit Breaker Closed/Opened Local Remote Arus Daya aktif Daya reaktif Tegangan Unit Trip Circuit breaker closed/opened Generator unit run/stop
Tipe I I I I I
Jmh 2 1 1 1 1 3 1 1 1 1 1 1
A I I
155
DB-05
P Q V P Q I L/R
BUSBAR
Teleinformasi Data Untuk Generator Pada Konfigurasi Single Busbar Group Data No Kode Fungsi Bay 3 F Frekuensi Busbar TM 10 V Tegangan 1 AMF Amperes Fault 2 CCB Counter of Circuit Breaker 4 I Arus 5 KVARH Kilovar Hour TM 6 KWH Kilowatt Hour 7 P Daya Aktif 8 PF Power Factor 9 Q Daya Reaktif 22 CBDF Circuit Breaker Drive Failure 23 CBTR CB Trip 35 LPA Low Pressure Alarm Incoming 20 kV 38 P2GFR Ground Fault Relay 39 P2OCR Over Current Relay TSS 41 PTF Protection Faulty 51 TCH Tap Changer High Limit 52 TCL Tap Changer Low Limit 53 TCS1 Trip Coil Supervisory 54 TPIF Tap Position Indication Failure 2 BI Bus Isolator Switch Closed/Opened TSD 4 CB Circuit Breaker Closed/Opened 7 ES Earth Switch Closed/Opened 2 CB Circuit Breaker Closed/Opened
Tipe
Jmh 1 3 3 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
A A A A A A A A A A I I I I
156
Group Bay
Data RCD
No 6 6 4 7 9 10 56 4 8
Kode LR LR I P Q V UT CB GUC
Fungsi Local Remote Local Remote Arus Daya aktif Daya reaktif Tegangan Unit Trip Circuit breaker closed/opened Generator unit run/stop
Tipe I
Jmh 1 1 3 1 1 1 1 1 1
A I I
157
FEEDER 20 KV TYPE 1
I ( R) I ( S) I ( T) P
L/R
Teleinformasi Data Untuk Feeder 20 kV Tipe 1 Group Data No Kode Fungsi Bay 3 F Frekuensi Busbar TM 10 V Tegangan 1 AMF Ampere Fault 2 CCB Counter of Circuit Breaker 4 I Arus TM 5 KVARH Kilovar Hour 6 KWH Kilowatt Hour 7 P Daya Aktif 20 AR Circuit Breaker Auto Reclose 21 ARO Auto Reclose Off 22 CBDF Circuit Breaker Drive Failure 23 CBTR CB Trip Feeder 35 LPA Low Pressure Alarm 37 P1DEF Directional Earth Fault TSS 38 P2GFR Ground Fault Relay 39 P2OCR Over Current Relay 41 PTF Protection Faulty 53 TCS1 Trip Coil Supervisory 1 55 UFR Under Frequency Relay Operate 1 ARU Auto Reclose Use/Unuse TSD 2 BI Bus Isolator Switch Closed/Opened 4 CB Circuit Breaker Closed/Opened
Tipe
Jmh 1 6 3 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1
A A A A A A A A A A A I I I
158
Group Bay
Data
No 7 10 12 1 2 6 8
Kode ES LR RR ARU CB LR RR
Fungsi Earth Switch Closed/Opened Local Remote Recloser Reset Auto Recloser Use/Unuse Circuit Breaker Closed/Opened Local Remote Recloser Reset
Tipe I I I
Jmh 1 1 1 1 1 1 1
RCD
159
FEEDER 20 KV TYPE 2
L/R
I ( R) I ( S) I ( T) P
Teleinformasi Data Untuk Feeder 20 kV Tipe 2 Group Data No Kode Fungsi Bay 3 F Frekuensi Busbar TM 10 V Tegangan 1 AMF Ampere Fault 2 CCB Counter of Circuit Breaker 4 I Arus TM 5 KVARH Kilovar Hour 6 KWH Kilowatt Hour 7 P Daya Aktif 20 AR Circuit Breaker Auto Reclose 21 ARO Auto Reclose Off 22 CBDF Circuit Breaker Drive Failure 23 CBTR CB Trip Feeder 35 LPA Low Pressure Alarm 37 P1DEF Directional Earth Fault TSS 38 P2GFR Ground Fault Relay 39 P2OCR Over Current Relay 41 PTF Protection Faulty 53 TCS1 Trip Coil Supervisory 1 55 UFR Under Frequency Relay Operate 1 ARU Auto Reclose Use/Unuse TSD 2 BI Bus Isolator Switch Closed/Opened 4 CB Circuit Breaker Closed/Opened
Tipe
Jmh 1 3 3 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1
A A A A A A A A A A A I I I
160
Group Bay
Data
No 7 10 11 12 1 2 6 8
Fungsi Earth Switch Closed/Opened Local Remote Circuit Breaker Rackin/Rackout Recloser Reset Auto Recloser Use/Unuse Circuit Breaker Closed/Opened Local Remote Recloser Reset
Tipe I I I I
Jmh 1 1 1 1 1 1 1 1
RCD
161
FEEDER 20 KV TYPE 3
I ( R) I ( S) I ( T) P
L/R
Teleinformasi Data Untuk Feeder 20 kV Tipe 3 Group Data No Kode Fungsi Bay 3 F Frekuensi Busbar TM 10 V Tegangan 1 AMF Ampere Fault 2 CCB Counter of Circuit Breaker 4 I Arus TM 5 KVARH Kilovar Hour 6 KWH Kilowatt Hour 7 P Daya Aktif 20 AR Circuit Breaker Auto Reclose 21 ARO Auto Reclose Off 22 CBDF Circuit Breaker Drive Failure 23 CBTR CB Trip Feeder 35 LPA Low Pressure Alarm 37 P1DEF Directional Earth Fault TSS 38 P2GFR Ground Fault Relay 39 P2OCR Over Current Relay 41 PTF Protection Faulty 53 TCS1 Trip Coil Supervisory 1 55 UFR Under Frequency Relay Operate 1 ARU Auto Reclose Use/Unuse TSD 2 BI Bus Isolator Switch Closed/Opened 4 CB Circuit Breaker Closed/Opened
Tipe
Jmh 1 3 3 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
A A A A A A A A A A A I I I
162
Group Bay
Data
No 7 10 12 1 2 6 8
Kode ES LR RR ARU CB LR RR
Fungsi Earth Switch Closed/Opened Local Remote Recloser Reset Auto Recloser Use/Unuse Circuit Breaker Closed/Opened Local Remote Recloser Reset
Tipe I I I
Jmh 1 1 1 1 1 1 1
RCD
163
DB - 09
L/R
Teleinformasi Data Untuk Bus Section 20 kV Tipe 1 Group Data No Kode Fungsi Bay TM 2 CCB Counter of Circuit Breaker 22 CBDF Circuit Breaker Drive Failure 23 CBTR CB Trip 35 LPA Low Pressure Alarm TSS 38 P2GFR Ground Fault Relay 39 P2OCR Over Current Relay 41 PTF Protection Faulty Bus Section 53 TCS1 Trip Coil Supervisory 1 2 BI Bus Isolator Switch Closed/Opened 4 CB Circuit Breaker Closed/Opened TSD 7 ES Earth Switch Closed/Opened 10 LR Local Remote 2 CB Circuit Breaker Closed/Opened RCD 6 LR Local Remote
Tipe A A A A A A A I I I I
Jmh 1 1 1 1 1 1 1 1 2 1 1 1 1 1
164
DB -10
L/R
Teleinformasi Data Untuk Bus Section 20 kV Tipe 2 Group Data No Kode Fungsi Bay TM 2 CCB Counter of Circuit Breaker 22 CBDF Circuit Breaker Drive Failure 23 CBTR CB Trip 35 LPA Low Pressure Alarm TSS 38 P2GFR Ground Fault Relay 39 P2OCR Over Current Relay 41 PTF Protection Faulty Bus 53 TCS1 Trip Coil Supervisory 1 Section 2 BI Bus Isolator Switch Closed/Opened 4 CB Circuit Breaker Closed/Opened TSD 7 ES Earth Switch Closed/Opened 10 LR Local Remote 11 RACK Circuit Breaker Rackin/Rackout 2 CB Circuit Breaker Closed/Opened RCD 6 LR Local Remote
Tipe A A A A A A A I I I I I
Jmh 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1
165
DB-11: Kopel
KOPEL
DB -11
L/R
Teleinformasi Data Untuk Kopel Group Data No Kode Bay TM 2 CCB 22 CBDF 23 CBTR 35 LPA TSS 38 P2GFR 39 P2OCR 41 PTF Bus 53 TCS1 Section 2 BI 4 CB TSD 7 ES 10 LR 11 RACK 2 CB RCD 6 LR
Fungsi Counter of Circuit Breaker Circuit Breaker Drive Failure CB Trip Low Pressure Alarm Ground Fault Relay Over Current Relay Protection Faulty Trip Coil Supervisory 1 Bus Isolator Switch Closed/Opened Circuit Breaker Closed/Opened Earth Switch Closed/Opened Local Remote Circuit Breaker Rackin/Rackout Circuit Breaker Closed/Opened Local Remote
Tipe A A A A A A A I I I I I
Jmh 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1
166
CAPACITOR BAY
DB -12
L/R
Teleinformasi Data Untuk Capasitor Bay Group Data No Kode Fungsi Bay 2 CCB Counter of Circuit Breaker 4 I Arus 5 KVARH Kilovar Hour TM 6 KWH Kilowatt Hour 7 P Daya Aktif 9 Q Daya Reaktif 22 CBDF Circuit Breaker Drive Failure 23 CBTR CB Trip 35 LPA Low Pressure Alarm 37 P1DEF Directional Earth Fault TSS Capasitor 38 P2GFR Ground Fault Relay 39 P2OCR Over Current Relay 41 PTF Protection Faulty 53 TCS1 Trip Coil Supervisory 1 2 BI Bus Isolator Switch Closed/Opened 3 CAM Capacitor Auto/Manual TSD 4 CB Circuit Breaker Closed/Opened 7 ES Earth Switch Closed/Opened 10 LR Local Remote 2 CB Circuit Breaker Closed/Opened RCD 6 LR Local Remote
Tipe
Jmh 1 3 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1
A A A A A A A A I I I I I
167
DB -13
PBO
I V
Teleinformasi Data Untuk SUTM radial dengan keypoint dan PBO Group Bay Data TM No 4 10 15 17 18 25 26 27 33 42 7 9 10 5 6 1 2 4 10 15 17 20 Kode I V 220F 48RF 48SF DCG DOOR FOTF HFD RADF ES LBS LR LBS LR AMF CCB I V 220F 48RF AR Fungsi Arus Tegangan 220 VAC Failure 48 VDC Rectifier Failure 48 VDC Supply Failure DC Ground Door Activated FO Terminal Faulty Homopolar Fault Detector Radio Link Faulty Earth Switch Closed/Opened Load Break Switch Closed/Opened Local Remote Load Break Switch Closed/Opened Local Remote Amperes Fault Counter of Circuit Breaker Arus Tegangan 220VAC Failure 48VDC Rectifier Failure Circuit Breaker Auto Reclose Tipe Jmh 3 3 1 1 1 1 1 1 3 1 1 1 1 1 1 3 1 1 3 1 1 1
TSS Keypoint
TSD RCD
A A A A A A A A I I I
TM
PBO
TSS
A A A
168
Group Bay
Data
No 21 22 23 25 26 27 31 35 36 42 53 1 4 10 12 1 2 6 8
Kode ARO CBDF CBTR DCG DOOR FOTF GFRF LPA OCRF RADF TCS1 ARU CB LR RR ARU CB LR RR
Fungsi Auto Reclose Off Circuit Breaker Drive Failure CB Trip DC Ground Door Activated FO Terminal Faulty Ground Fault Relay Failure Low Pressure Alarm Over Current Relay Failure Radio Link Faulty Trip Coil Supervisory 1 Auto Recloser Use/Unuse Circuit Breaker Closed/Opened Local Remote Recloser Reset Auto Recloser Use/Unuse Circuit Breaker Closed/Opened Local Remote Recloser Reset
Tipe A A A A A A A A A A A I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSD
RCD
169
KP
Teleinformasi Data Untuk SUTM radial dengan keypoint tanpa PBO Group Bay Data TM No 4 10 15 17 18 25 26 27 33 42 7 9 10 5 6 Kode I V 220F 48RF 48SF DCG DOOR FOTF HFD RADF ES LBS LR LBS LR Fungsi Arus Tegangan 220 VAC Failure 48 VDC Rectifier Failure 48 VDC Supply Failure DC Ground Door Activated FO Terminal Faulty Homopolar Fault Detector Radio Link Faulty Earth Switch Closed/Opened Load Break Switch Closed/Opened Local Remote Load Break Switch Closed/Opened Local Remote Tipe Jmh 3 3 1 1 1 1 1 1 3 1 1 1 1 1 1
TSS Keypoint
TSD RCD
A A A A A A A A I I I
170
L/R I V
I V L/R
L/R I V
Teleinformasi Data Untuk SUTM loop dengan beberapa keypoint Group Bay Data TM No 4 10 15 17 18 25 26 27 33 42 7 9 10 5 6 Kode I V 220F 48RF 48SF DCG DOOR FOTF HFD RADF ES LBS LR LBS LR Fungsi Arus Tegangan 220 VAC Failure 48 VDC Rectifier Failure 48 VDC Supply Failure DC Ground Door Activated FO Terminal Faulty Homopolar Fault Detector Radio Link Faulty Earth Switch Closed/Opened Load Break Switch Closed/Opened Local Remote Load Break Switch Closed/Opened Local Remote Tipe Jmh 3 3 1 1 1 1 1 1 3 1 1 1 1 1 1
TSS Keypoint
TSD RCD
A A A A A A A A I I I
171
DB-16: Spindle 20 kV
SPINDLE 20 kV
DB -16
GI
20 kV Busbar
GD GT GD
L/R
GH
L/R
Teleinformasi Data Untuk Spindle 20 kV Group Bay Data No 15 17 18 25 26 27 33 42 7 9 10 5 6 15 17 18 25 26 27 33 42 7 9 Kode 220F 48RF 48SF DCG DOOR FOTF HFD RADF ES LBS LR LBS LR 220F 48RF 48SF DCG DOOR FOTF HFD RADF ES LBS Fungsi 220 VAC Failure 48 VDC Rectifier Failure 48 VDC Supply Failure DC Ground Door Activated FO Terminal Faulty Homopolar Fault Detector Radio Link Faulty Earth Switch Closed/Opened Load Break Switch Closed/Opened Local Remote Load Break Switch Closed/Opened Local Remote 220 VAC Failure 48 VDC Rectifier Failure 48 VDC Supply Failure DC Ground Door Activated FO Terminal Faulty Homopolar Fault Detector Radio Link Faulty Earth Switch Closed/Opened Load Break Switch Closed/Opened Tipe A A A A A A A A I I I Jmh 1 1 1 1 1 1 3 1 1 1 1 1 1 1 1 1 1 1 1 3 1 1 1
TSD RCD
Gardu Tengah
TSS
TSD
A A A A A A A A I I
172
Group Bay
Data
No 10
Kode LR LBS LR
Tipe I
Jmh 1 1 1
RCD
5 6
173
174
STRUKTUR INFORMASI
Struktur informasi terdiri dari 112 karakter yang dapat dikelompokkan menjadi sembilan bagian, yaitu: A B C D E F G H I
Bagian A: Nomor ID, terdiri dari 6 digit (sebagai primary key) Bagian B: Time stamp, sebanyak karakter 23 karakter Bagian C: Nama GI/GH/GT/KP, sebanyak 20 karakter Bagian D: Level tegangan, sebanyak 5 karakter Bagian E: Nama bay / feeder, sebanyak 20 karakter Bagian F: Kode nama peralatan atau nama alarm atau nama elemen, sebanyak 5 karakter Bagian G: Status peralatan atau status alarm, sebanyak 15 karakter Bagian H: Nama user yang melakukan aksi (seperti remote control, dan sebagainya), sebanyak 10 karakter Bagian I: Prioritas alarm, sebanyak 8 karakter Struktur di atas ditentukan dalam field yang berbeda. Contohnya dapat dilihat pada Tabel 1.
Tabel 1. Struktur informasi
A RCC Cawang
110007 110009
C
Cawang Gandul Rungkut Waru Gondang Wetan Gondang Wetan
D
150 150 150 150 20 20
E
Gandul-1 Cawang-1 Waru-1 Bangil-1 Bromo Semeru
F
BI1 ARO LT CB CB CBTR
G
Close Appear Disappear Invalid Open Appear
I
Class-3 Class-2 Class-1 Class-4
02/03/2007 11:10:05.320 05/03/2007 07:00:55.115 11/04/2007 17:44:21.220 12/04/2007 20:11:51.312 25/04/2007 00:30:35.000 19/11/2007 10:00:05.520
RCC Waru
140104 140085 430011 430012
DCC Pasuruan
Adi Class-1 Class-1
A. Nomor ID
Nomor ID (bagian A) terdiri dari dua bagian. Bagian A1 terdiri dari 3 digit yang menyatakan kode area. Bagian A2 terdiri dari 3 digit merupakan nomor RTU bersangkutan. Nomor ID dinyatakan dengan susunan sebagai berikut A1 Bagian A1: Kode area Bagian A2: Nomor RTU A2
175
Kode area
Kode area yang terdiri dari 3 karakter adalah sebagai berikut: NCC : 900 IRCC IRCC Jawa-Bali IRCC Sumatera IRCC Kalimantan IRCC Sulawesi IRCC di Indonesia Timur RCC di Jawa-Bali RCC Cawang RCC Cigereleng RCC Ungaran RCC Waru RCC di Sumatera RCC Medan RCC Padang RCC Palembang RCC di Kalimantan RCC Banjarbaru RCC Balikpapan RCC di Sulawesi RCC Makassar RCC Manado RCC di Indonesia Timur IDCC IDCC Jawa-Bali IDCC Sumatera IDCC Kalimantan IDCC Sulawesi IDCC di Indonesia Timur : : : : : : : : : : : : : : : : : : : : : : : : : : : : x00 100 200 300 400 500 1xx 110 120 130 140 2xx 210 220 230 3xx 310 320 4xx 410 420 5xx x00 100, 200, 300, 400 500, 600 700 800 900 : : : : : : : : 0xx 1xx 2xx 3xx 4xx 5xx 6xx 7xx 8xx 9xx
DCC di Jakarta DCC daerah Jawa bagian Barat DCC daerah Jawa bagian Tengah DCC daerah Jawa bagian Timur dan Bali DCC daerah Sumatera DCC daerah Kalimantan DCC daerah Sulawesi DCC daerah Indonesia Timur
Nomor RTU
Nomor RTU terdiri dari 3 digit (001 999)
176
B. Time stamp
Struktur informasi yang menggambarkan time stamp atau waktu suatu kejadian terdiri dari 23 karakter. Struktur informasinya berturut-turut terdiri dari tanggal (2 karakter), bulan (2 karakter), tahun (4 karakter), jam (2 karakter), menit (2 karakter), dan detik (6 karakter atau sampai dengan orde milidetik). Contohnya: 25/04/2007 00:30:35.000 19/11/2007 10:00:05.520
C. Nama GI/GH/GT
Nama GI/GH/GT dituliskan dalam bentuk nama lengkap (maksimal 20 karakter). Contohnya adalah sebagai berikut: Cawang Gandul Gondang Wetan Rungkut Waru Cawang Gandul Waru Rungkut Gondang Wetan : menyatakan GI Cawang (dikontrol oleh RCC Cawang). : menyatakan GI Gandul (dikontrol oleh RCC Cawang). : menyatakan GI Waru (dikontrol oleh RCC Waru). : menyatakan GI Rungkut (dikontrol oleh RCC Waru). : menyatakan GI/GH/GT Gondang Wetan (dikontrol oleh DCC Pasuruan).
D. Level Tegangan
Level tegangan terdiri dari 5 karakter. Contohnya dapat dilihat pada Tabel 2.
Tabel 2. Level tegangan
177
Nama Bay / Feeder Pusat Listrik Pusat Listrik Tenaga Air Pusat Listrik Tenaga Diesel Pusat Listrik Tenaga Gas Pusat Listrik Tenaga Panas Bumi Pusat Listrik Tenaga Nuklir Pusat Listrik Tenaga Uap Pusat Listrik Gas/Uap (Combine Cycle) Pusat Listrik Tenaga Mikrohidro Pusat Listrik Tenaga Angin/Bayu Peralatan di Gardu Induk Line Bay (Feeder Bay)
Kode
Bay ke Unit Generator Busbar Kopel (Bus Tie) Bus Section Trafo Diameter Shunt Reactor Shunt Capacitor Cadangan
Format penulisan: IRCC/RCC: Nama GI lawan + - + nomor penghantar. Contohnya: o Gandul-1 o Cawang-1 DCC: Nama Feeder. Contohnya: o Bromo o Semeru UNIT BUSBAR KOPEL BUSSECT TRAFOx (X adalah Kode Tegangan dari primer dan sekunder trafo) DAMTR SHTXL SHTXC SPARE
Nama Bay Bay 500 kV diameter 1 busbar A 7A1 Bay 500 kV diameter 3 antara busbar A 7AB3 dan B Bay 500 kV diameter 5 busbar B 7B5 Kode tegangan dari primer dan sekunder trafo dapat dilihat pada Tabel 4.
Tabel 4. Kode tegangan dari primer dan sekunder trafo
Tegangan Tegangan Rendah (TR) Tegangan Menengah (TM) Tegangan Menengah (TM)
Kode 0 1 2
178
Tegangan Tegangan Menengah (TM) Tegangan Tinggi (TT) Tegangan Tinggi (TT) Tegangan Tinggi (TT) Tegangan Ekstra Tinggi (TET) Tegangan Ekstra Tinggi (TET) Tegangan Ekstra Tinggi (TET)
Range 30 sampai 60 kV 60 sampai 90 kV 90 sampai 200 kV 200 sampai 400 kV 400 sampai 600 kV 600 sampai 1000 kV 1000 kV ke atas
Kode 3 4 5 6 7 8 9
Nama Circuit Breaker Bus Isolator #1 Bus Isolator #2 Line Isolator Ground Fault Over Current Line Trip Breaker Fault Power Supply Faulty Daya MW Daya MVAr Arus Load Break Switch Recloser
Kode nama peralatan dapat juga berupa kode teleinformasi (telesignal, telemeasurement atau remote kontrol seperti ditunjukan pada Lampiran A-D).
179
I. Prioritas Alarm
Prioritas alarm terdiri dari 8 karakter, menunjukkan kelas alarm yang ditampilkan. Class 1 merupakan kelas alarm yang menempati prioritas paling tinggi. Contohnya sebagai berikut: Class-1 Class-2 Class-3 Class-4
Struktur Informasi Khusus Penamaan Pemutus Tenaga Pada Gardu Induk 1 Breaker.
Struktur informasi khusus untuk pemutus tenaga pada gardu induk 1 breaker dipakai untuk tujuan komunikasi verbal diantara operator. Kode tersebut hanya ditampilkan di VDU (Video Display Unit), dan dipergunakan di dalam database. Struktur informasi dinyatakan dengan susunan sebagai berikut: X Y Z
Bagian X: kode referensi tegangan Bagian Y: kode nama CB Bagian Z: nomor diameter Contoh: A untuk breaker yang terhubung langsung ke busbar A B untuk breaker yang terhubung langsung ke busbar B AB untuk breaker yang terhubung ke breaker A dan breaker B Contohnya dapat dilihat pada Gambar 4 dan Gambar 5. Untuk tegangan 500 kV diameter no. 1 Untuk tegangan 150 kV diameter no.4
180
Contoh :
UNIT 4
BANDUNG SELATAN 2
BUSBAR A
7A1
7A2
7A3
7AB1
7AB2
7AB3
7AB4
7AB5
7B1 BUSBAR B
7B2
7B3
7B4
7B5
CIBINONG 1
CIBINONG 2
CIRATA 1
CIRATA 2
BANDUNG SELATAN 1
181
182
183
Tampilan Status
ITEMS SYMBOL REMARK
CB CLOSED CB OPENED PBO PBO CLOSED PBO PBO OPENED LBS CLOSED LBS OPENED DS CLOSED DS OPENED ES CLOSED ES OPENED RACKED IN CB CLOSED RACKED IN CB OPENED RACKED OUT CB CLOSED RACKED OUT CB OPENED GARDU PORTALTIANG GARDU TEMBOK/BESI CUT OUT FUSE GENERATOR
Busbar ' s color, filled Busbar ' s color, blank Feeders color , filled Feeders color , blank Feeders color Feeders color Feeders color , filled Feeders color , blank
Feeders color Feeders color Feeders color , filled Feeders color , blank Feeders color , filled Feeders color , blank Feeders color Feeders color Feeders color Feeders color
TRANSF . 2 WINDINGS
Feeders color
TRANSF . 3 WINDINGS
Feeders color
REACTOR
Feeders color
CAPACITOR
Feeders color
VOLTAGE STATUS :
LIVE DEAD
184
WARNA TAMPILAN
Tabel 6 berikut ini menjelaskan mengenai warna tampilan yang berlaku untuk monitor dan layar tayang.
Tabel 6. Warna tampilan
URAIAN
WARNA
Single line diagram 500 kV Single line diagram 275 kV Single line diagram 150 kV Single line diagram 70 kV Single line diagram 30 kV Single line diagram 20 kV Single line diagram 12 kV Single line diagram 6 kV Single line diagram 0.4 kV All devices Invalid device Device saat loss connection (RTU out of poll) Background color Ground color Kondisi tidak bertegangan Perubahan status karena gangguan Perubahan status karena local dari gardu induk Perubahan status karena remote dari dispatcher Telemetering Invalid telemetering Telesignal Alarm
Biru Biru-muda Merah Kuning Hijau Coklat Abu-abu Merah muda Hijau-muda Warna Busbar Ungu dan perubahan simbol Oranye Hitam Biru-tua Putih Frame CB warna merah, blinking Warna Busbar, blinking + karakter L Warna Busbar, blinking Putih Ungu Warna kuning, blinking
Keterangan: Untuk change of state gangguan, setelah acknowledge blinking hilang, warna merah pada frame CB mengikuti warna busbar. Untuk level tegangan yang tidak tercantum dalam tabel di atas, menggunakan warna pada single line diagram level tegangan terdekat. Warna jaringan sesuai dengan feeder colouring. Untuk detail kode warna akan dijelaskan pada SPLN mengenai kode simbol dan warna.
185
Pengelola Standardisasi: PT PLN (Persero) Litbang Ketenagalistrikan Jalan Durentiga Jakarta 12760, Telp. 021-7973774, Fax. 021-7991762, www. pln-litbang.co.id.
186