1. Differential * *
2. Restriced earth fault * *
3. Stator turn to turn fault *
4. Time Over Current * *
5. Temperature
* * *
(thermo-detector)
6. Negative sequence
* * *
Current
7. Loss of Load * *
8. Loss of input-anti-
* * *
Motoring
9. Loss of field * *
10. Loss of synchronism * *
11. Over speed * Hanya untuk hydrogenerator
12. Over voltage * Hanya untuk hydrogenerator
13. Rotor earth fault * *
14. Back-up overcurrent * * *
15. Bearing temperature * *
16. Bearing insulation *
Stator overload
protection with
overcurrent relay
2. Gangguan diluar Beban tidak Negative sequence
generator seimbang, tekanan protection untuk
pada kumparan mesin yang besar.
dan poros, panas
berlebihan yang Overload protection
memperpanjang untuk mesin yang
hubung singkat. kecil
3. Gangguan pada stator: Kumparan Blased differential
- antar phasa terbakar, protection, sensitive
- phasa ke tanah pengelasan pada earth fault protection,
- inter turn inti laminasi, mati inter turn fault
protection
Table
Types of protection for Generators and their setting
Generator Type of Drive Type of protection used Suggested fault current Protection for exciter
Rating setting circuit and neutral
1 2 3 4 5
1. 20 percent full load 1. Neutral
Time graded earth fault current isolating switch
relay 125 percent full load 2. Field switch
2. current in the exciter field
Time graded over 10 to 20 percent of its circuit
Steam
current relay normal power rating
Turbine
3.
Reverse power relay
Below
(only for back pressure
1000 KVA
turbines)
Generator Type of Drive Type of protection used Suggested fault current Protection for exciter
Rating setting circuit and neutral
1 2 3 4 5
1. Differential protections 10 to 25 percent full 1. Field earth fault for
(Merz-Price) load current protecting 96% of the
or field winding (only for
Time graded earth fault 20 percent full generator above
relay load current 20.000 KVA)
Above Steam 2. Phase unbalance 10 to 25 percent 2.Automatic field
5000 KVA Turbine negative phase suppression switch
sequence only
3. Reverse power (only 10 to 25 percent full 3.Automatic neutral
back pressure turbine) load current breaker.
1. Buchholz relay trips the Buchholz relay too slow and less
circuit breaker sensitive
Large internal faults phase to phase, 2. Merz Price percentage Merz Price percentage
phase to ground, below oil level differential protection differential protection used for
3. High speed high set transformers of and above 5 MVA
overcurrent relay
Buchholz relay
Overcurrent protection
Winding and oil temperature sensors
in certain applications