Anda di halaman 1dari 5

STRUKTUR DAN UTILITAS 4

RENCANA AC

DISUSUN OLEH:
Dwi Agung Nugraha D300200083
Difa Alya Malik D300200120

DOSEN PEMBIMBING:
RONIM AZIZAH ST, MT

FAKULTAS TEKNIK
PROGRAM STUDI ARSITEKTUR
UNIVERSITAS MUHAMMADIYAH SURAKARTA
TAHUN PELAJARAN 2020/2021

`
Lantai 2 Ruang  BSB Barat Daya
Aula UKURAN
RUANGAN
 BSB Dinding Barat Daya
= Luas bidang dinding x Beban kalor
= (luas bidang dinding - luas bidang kaca) x (2,16 x t0-t1)
LUAS RUANGAN TOTAL AULA = 475+33,25 = ((28,5 x 4) - (( 2 x (2 x 2)) x (2,16 x 5)
=508,25 = ( 114 - ( 2 x 4 )) x 10,8
Luas Perorang 20 m² = ( 114 – 8 ) x 10,8
Ukuran Jendela Sisi Tenggara = 106 x 10,8
• Tinggi =2m = 1.144,8
• Lebar =2m
• Jumlah =2  BSB Kaca Barat Daya
= Luas bidang x beban kalor
BSB = (luas jendela) x 1000
 BSB Tenggara = (4 (2 x 2) x 1000
= 16 x 1000
 BSB Dinding Tenggara
=16.000
= Luas bidang dinding x Beban kalor
= (luas bidang dinding - luas bidang kaca) x (2,15 x  Total BSB Barat Daya
t0-t1) = BSB Dinding + BSB Kaca
= ((28,5 x 4) – 0) x (2,15 x 5) = 1.144,8 + 16.000
= ( 114 - 0) x 10,75 = 17.144,8
= 114 x 10,75
= 1.548  BSB Barat Laut
 BSB Kaca Tenggara  BSB Dinding Barat Laut
=0 = luas bidang x beban kalor
 Total BSB Tenggara = (luas bidang dinding - luas bidang kaca) x (2,16 x t0-t1)
= ((25 x 4) -0 ) x (2,16 x 5)
= BSB Dinding + BSB Kaca
= 100 x 10,8
= 1.548 + 0
= 1080
= 1.548
 BSB Kaca Barat Laut
=0
 Total BSB Barat Laut
= BSB Dinding + BSB Kaca
= 1080 + 0
= 1080

`
 BSB Timur Laut
 BSB Dinding Timur Laut
= luas bidang x beban kalor
= (luas bidang dinding - luas bidang kaca) x (2,15 x t0-t1)
= ((19 x 4) - 0 ) x (2,15 x 5)

= 76x 10,75
= 817
 BSB Kaca Timur Laut
=0
 BSB Total Timur Laut
= BSB Dinding + BSB Kaca
= 817+ 0
= 817

 BSB Total
= Tenggara + Barat Daya + Barat Laut + Timur Laut
= 1.548 + 17.144,8 + 1.080 + 817
= 20.589,8

BSO
= Okupasi x 200
= (luas bruto/luas per orang) x 200
= (508,25 : 20) x 200
= 25,4125x 200
= 5.082,5 BTU jam

BLO
= Okupasi x 250
= (luas bruto/luas perorang) x 250
= (508,25: 20) x 250
= 25,4125 x 250
= 6.353,125 BTU jam

`
 Watt = 40.000 / 100 lumen
= 400 watt
 AC = 5
 t₀-t₁ = 5°C
 RH₀ - RH₁ = 0,75 - 0,6
= 0,15

BSL = ∑watt x (1,25) x (3,4)


Hall x Luas bruto
=( 100 )x(1,25) x (3,4)
250 x 508,25
=( 100 )x(1,25) x (3,4)
= 1.270,625 x 1,25x 3,4
= 5.400,15

CFM1
= LUAS RUANG x t x AC x 35,31 / 60 BTU jam
= 508,25 x 4 x 5 x 35,31 / 60 BTU jam
= 358.926,15/ 60 BTU jam
= 5.982,1025 BTU jam

CFM2
= ((t₀-t₁) x 1,08) + ((RH₀ - RH₁) x 0,67)
= (5 x1,08) + (0,15 x 0,67)
= 5,4 + 0,10065
= 5,5005 BTU jam

BP
= BSB + BSO+ BLO+ BSL+ CFM1+ CFM2
= 20.589,8+ 5.082,5 + 6.353,125 + 5.400,15+ 5.982,1025 + 5,5005
= 43.413,178

KAPASITAS TATA UDARA


Kapasitas = BP / 12.000 TR
=43.413,178 / 12.000
= 3,617 TR

`
 Cek Beban Pendinginan ( Tabel 6.2 )
 Kantor = 1,5 - 2,0 per 100m² ruangan (TR) Diambil 1,5 TR

Maka :
Luas.Ruangan =508,25 m² dengan kapasitas tata 3,617 TR
= 508,25 / 100 = 5,08 TR
= 1,5 x 5,08 = 7,62 TR

 Kapasitas Tata Udara = 3,617 TR< 7,62 TR sudah sesuai


1 TR = 1,5 PK
7,62 TR= 11,43 PK
= 11 PK