Anda di halaman 1dari 58

Karakteristik

RXQ-PY1 Servis space


RXQ-PHY1 HI-COP
Receiver Gas
Discharging:SVG
EV1 Inverter
Electronic
Non-operating Expansion Fan
unit Liq pipe EV2
Valve
Closing:SVSL

Four way
valve
Hot gas:SVP

INV kompresor

STD kompresor
Piping Heat
Exchange
Fusible
HP Pressure
Plug
Switch

Pressure
Regulating
Valve (Liq pipe High Pressure
to Receiver) Sensor

Low Pressure
Sensor
Thermistor
Outdoor
Receiver outlet
Air Ta
liq pipe Tl
Heat
Exchanger
Subcooling deicer Tb
heat
exchanger
gas pipe Tsh STD1
Discharge
pipe Tds2
INV discharge
pipe Tdi

Suction
Pipe Ts

STD1 Discharge
pipe Tds1
Cooling
Operation
Heating
Operation
Refrigerant Flow
Basic Control
Prioritas pengoperasian & Rotasi kompresor

Eg. RXQ46PY1,48PY1

No.1 No.4 No.7 No.2 No.5 No.8 No.3 No.6 No.9

No.3 No.6 No.9 No.1 No.4 No.7 No.2 No.5 No.8

No.2 No.5 No.8 No.3 No.6 No.9 No.1 No.4 No.7

INV STD1 STD2 INV STD1 STD2 INV STD1 STD2

Master Slave 1 Slave 2


Protection Control
Kontrol Proteksi High Pressure

 Untuk mencegah pengaktivan alat proteksi karena


kenaikan HP yang abnormal.
 Untuk melindungi kompresor dari kenaikan
sementara HP.
Protection Control
Control Proteksi High Pressure
 Cooling – pendeteksian Hp dengan sensor HP unit
outdoor Individual
.
HP tdk terbatas
freq batas atas INV = 210Hz
Pc>3.47Mpa
Pc: Hnilai HP yang terdeteksi
oleh sensor untuk Setiap unit
freq batas atas INV: 3-
step/10sec dibawah outdoor
freq comp saat ini

Pc>3.47Mpa Pc<3.24Mpa freq batas atas INV: lebih


HP terbatas 1-step dari freq comp
Pc>3.55Mpa Saat ini

STD comp standby (5min) Pc>3.64Mpa

Ketika terjadi 3 kali dalam 30mins, HPS


HP standby diaktifkan tanpa HP standby, hal ini
mengeluarkan code kerusakan “E3”
Protection Control
Kontrol Proteksi Low Pressure
Untuk melindungi kompresor dari penurunan sementara dari LP.
Cooling – Pendeteksian LP oleh sensor LP unit outdoor Master.
LP tak terbetas

Pe<0.34Mpa Pe>0.39Mpa

LP terbatas
Semua comp. STD Pe: Nilai LP yang terdeteksi
Stop.
sensor unit Master
Pe<0.25Mpa

Master unit:
52Hz+OFF+OFF
Slave unit: Stop

Pe<0.07Mpa
Ketika terjadi 3 kali dalam 30min, keluar
LP standby
kode kerusakan “E4”.
Protection Control
Kontrol Proteksi Pipa Discharge
Untuk melindungi temp internal kompresor dari kerusakan atau
kenaikan sementara temp pipa discharge
Kontrol proteksi temp pipa kompresor INV
discharge tdk terbatas
HTdi >115°C HTdi: Temp pipa discharge comp
Or
Tp >140°C INV T(di) diimbangi dengan temp
HTdi <100°C udara outdoor
freq batas atas INV: 1- & Tp: Temp port Comp dihitung oleh
Tp <110°C
STEP turun dari freq Tc & Te & derajat superheat
comp saat ini. suction.
Setisp 30sec. Setiap 60sec.
HTdi >115°C
Or HTdi <110°C
Tp >140°C & Tp <125°C
Control proteksi
temp pipa discharge freq batas atas INV: 1-STEP
bagian dalam. naik dari freq kompresor saat
HTdi >130°C
ini.
HTdi >120°C for
& 90sec. Atau lebih
Tp > 130°C
HTdi >135°C
Or
INV62Hz+OFF+OFF HTdi >120°C for 10min. atau lebih.

Kontrol standby temp. Ketika terjadi 3 kali dalam 100mins,


pipa Discharge. keluar kode kerusakan “F3”..
Protection Control
Kontrol Proteksi Pipa Discharge

kompresor STD

HTds: Temp pipa discharge comp


STD(Tds) diimbangi dengan temp
udara outdoor
Tp: Temp port Comp dihitung
dengan Tc & Te & derajat superheat
suction.

•HTds >120°C berlanjut sampai 5min. atau lebh.


•HTds >135°C
Or
•Tp >140°C berlanjut selama 10min. atau lebih.
•Tp >150°C
Kontrol protection temp. pipa stop penggunaan STD
discharge tak terbatas kompresor.
10min.
Protection Control
Kontrol Proteksi Inverter

• Untuk mencegah hambatan yang dikarenakan malfungsi atau


overcurrent inverter sementara , dan temp fin/sirip naik.
Tak terbatas Kontrol proteksi
arus Inv > 13.5A overcurrent INV
Freq batas atas INV : arus Inv < 13.5A
1-STEP turun dari & Inv upper limit freq = 210Hz
freq comp saat ini.

arus Inv < 13.5A


berlanjut selama
20sec atau lebih.
arus Inv > 13.5A Dibawah kontrol Freq batas atas INV : 1-STEP
proteksi arus inv naik dari freq. Comp saat ini

arus Inv > 14.5A berlanjut sampai 260sec

•Ketika terjadi 4 kali dalam 60min, keluar


arus Inv standby
kode malfungsi “L8”.
Protection Control
Kontrol Proteksi Inverter
Kontrol temp fin INV
Tdk terbatas

Tfin > 84°C Tfin: Temp. dideteksi oleh


thermistor fin radiasi.
freq batas atas INV : Tfin < 81°C
1-STEP turun dari & freq batas atas INV = 210Hz
freq comp. saat ini

Inv current < 81°C


continues for 3mins
Dibawah control or more.
Tfin > 84°C freq batas atas INV : 1-STEP
protection
naik dari freq comp. saat ini.
temp. fin

Tfin > 98°C

Temp. Fin standby • ketika terjadi 3 kali dalam 60min,


keluar kode malfungsi “L4”.
Protection Control
Proteksi Overload kompresor STD
 Untuk mencegah heating yang tdk normal karena overcurrent ke
kompresor yang dhasilkan dari kerusakan comp. STD seperti
locking (macet).

comp. STD ON

Perlu dioperasikan. current valve mendeteksi CT > 15A


(selama 3sec)

comp. STD OFF selama * jika power supply direset


30min*. sementara dalam keadaan
dilarang beroperasi waktu
pelarangan akan berlanjut ketika
Ketika terjadi 3 kali dalam 90min, power supply di-ON kan
keluar kode malfungsi “E6”.
Protection Control
Kontrol Injection (hanya RXQ5PY1)

 Untuk kenaikan transisional pada temp. pipa discharge


 Ref. Liq. Mengalir ke dalam suction untuk mengurangi temp pipe
discharge untuk perlindungan kompresor.
Kontrol Lainnya
Rotasi unit Outdoor

 Untuk system unit multi-outdoor, untuk mencegah comp. dari kebakaran


luar karena ketidakseimbangan level oli antara unit outdoor.
 Setiap unit outdoor diberi sebuah prioritas pengoperasian untuk kontrol.
 Rotasi unit Outdoor membuat hal itu memungkinkan untuk merubah
prioritas pengoperasian dari unit outdoor.
 Sistem menjadi bebas dari comp. yang berhenti melebihi perpanjangan
dari suatu periode waktu pada waktu pembebanan parsial, pencegahan
ketidakseimbangan level oli.
 Waktu kontrol:
 Setelah pengoperasian oil return
 Setelah pengoperasian defrost
 Pada awal permulaan control.
 Ketika ada kompresor yang berhenti selama 20 min atau lebih (dalam
operasi heating)
Kontrol Lainnya
Rotasi unit Outdoor
Contoh. Rotasi unit Outdoor dalam kombinasi dari 3 unit outdoor.
Kontrol Lainnya
Operasi Emergency
 Jika comp. tak dapat beroperasi, kontrol ini mencegah setiap
pemakaian comp. atau outdoor unit dari pengoperasian untuk
melakukan pegoperasian emergency.
 Hanya dengan comp. operative atau outdoor unit.

i. Larangan:
 Sis. dengan 1 unit outdoor -
 Hanya ketika total kapasitas unit indoor mencapai 50%
atau lebih Emg. operation akan berfungsi.
 Jika Emg. Operation di set sementara outdoor unit sedang
beroperasi -
 Outdoor unit berhenti sekali setelah operasi pump-down
residual. (max. lewat 5min)
Kontrol Lainnya
Operasi Emergency

 Jenis Operasi EMG. :


 No.42 (operasi INV bermasalah)
 No.19 (operasi STD bermasalah)
 STD1 & 2 bermasalah 1
unit outdoor
 STD2 bermasalah
 No.38,39,40 (unit Outdoor bermasalah)
 No.38 (unit Master bermasalah)
 No.39 (unit Slave1 bermasalah)
 No.40 (unit Slave2 bermasalah)
unit Multi-
Outdoor
Kontrol Lainnya
Operasi Emergency

ii. Untuk sis.1 unit Outdoor (RXQ10 to 18P):

 “Setting emergency” diset pada setiap comp.


 Setting Operasi Emgergency pada Mode Setting 2.

 Jika comp.INV bermasalah pada pengoperasian, hanya 1


comp.STD yang dapat beroperasi untuk oil equalization.

Batasan:
Kontrol Lainnya
Emergency Operation

Kompresor INV bermasalah

Oil separator

beroperasi

STD 1 INV STD 2

: pemipaan silang
Pada pengoperasian dengan 3 comp.
Kontrol Lainnya
Emergency Operation

ii. Untuk sis. unit 1 Outdoor.(RXQ10 to 18P):

Batasan:

 Untuk RXQ14 & 18P (3 comp.):


 Comp. STD1 pengoperasiannya tidak dapat bermasalah
karena alasan oil equalization.
 Ketika 1 unit outdoor dipasang (RXQ10 to 18P):
 Pengoperasian backup otomatis tidak dapat dilakukan.
Kontrol Lainnya
Emergency Operation

kompresor STD2 bermasalah

Oil separator

beroperasi Beroperasi

STD 1 INV STD 2

: pemipaan silang
Pada pengoperasian dengan 3 comp.
Kontrol Lainnya
Emergency Operation

kompresor STD1 & 2 Bermasalah

Oil separator

Beroperasi

STD 1 INV STD 2

: pemipaan silang
Pada pengoperasian dengan 3 comp.
Kontrol Lainnya
Emergency Operation

Batasan : Masalaah Oil equalization

Oil separator

Beroperasi Beroperasi

STD 1 INV STD 2

: pemipaan silang
Pada pengoperasian dengan 3 comp.
Kontrol Lainnya
Emergency Operation

iii. Untuk sis. Unit Multi-Outdoor (RXYQ20 to 54P):

 “Setting emergency” adalah pengesetan pada setiap PCB outdoor.


 Semua setting dilakukan di unit MASTER.
 Pengoperasian backup otomatis:
 Jika sis. unit outdoor tertentu rusak, karena resetting sis. RC, unit
outdoor yang dapat dipakai bermasalah pemakaiaannya selama
8jam; Emg. Operation dilakukan secara otomatis.
 Pengoperasian backup otomatis dapat dilakukan dengan
kerusakan seperti di bawah ini :
• E3, E4, E5, E7 J2, J3, J5, J6, J7, J9, JA, JC
• F3 L3, L4, L5, L9, LC
• H7, H9 U2, UJ
Kontrol Lainnya
Emergency Operation

iii. Untuk sis. unit Multi-Outdoor (RXYQ20 to 54P):

Batasan:

 Untuk sis. Unit multi-outdoor :


 “Setting emergency” tidak diset pada setiap kompresor secara
individual.
 Ketika “Setting emergency” di atas di set, rotasi unit outdoor
tidak berfungsi.
Kontrol Lainnya
Emergency Operation

iii. For Multi-Outdoor unit sys.(RXQ20 to 54P):

Master Slave1 Slave2


Kontrol Lainnya
Emergency Operation

iv. Pengoperasian Backup otomatis.(RXQ20 to 54P):

Master Slave1 Slave2


Kontrol unit Indoor
Kontrol Drain Pump •Ketika float switch tripped sementara
Thermostat Cooling ON
ON
Tampilan‘A3’
OFF

ON

OFF
1 cycle

ON

OFF
5 min 5 min 5 min
5 sec
Thermostat Float Switch Drain Pump
Kontrol unit Indoor
Drain Pump Control •Ketika float switch tripped sementara
Thermostat Cooling OFF
ON
Thermostat ‘OFF’ ‘A3’ display
OFF

ON

OFF

1 cycle

ON

OFF
5 min 5 min 5 min
5 sec
Thermostat Float Switch Drain Pump
Kontrol Indoor unit
Drain Pump Control •Ketika float switch tripped & tampilan pada
RC “AF”
ON
Thermostat ‘OFF’ Tampilan‘AF’
OFF

ON

OFF
1st 2nd 3rd 4th 5th

ON

OFF

Thermostat Float Switch Drain Pump


Kontrol Unit Indoor
Kontrol Louver untuk mencegah Ceiling kotor

(Setting Pabrik)

Position Preventif Position Setting Pencegahan pengotoran


Draft Standard Ceiling

P0

P1 P0
P1
P0
P2
P2 P1
P3 P2
P3 P3
P4 P4 P4

Si39-302; pg94
Kontrol Unit Indoor
Sensor Thermostat dalam RC

Preset
Temp
(Ts)

Suction Temp (TH1)


Kontrol Unit Indoor
Kontrol Thermostat ketika dalam Operasi Normal
Kontrol Unit Indoor
Kontrol Thermostat dalam Dry Operation
Kontrol unit indoor
Pencegahan kebekuan

i. Kondisi Operasi:

 Thermistor pipa Liquid (R2T)  -1oC dalam 40


menit atau
 Thermistor pipa Liquid(R2T)  -5oC dalam 10
menit
ii. Tindakan :

 Lepas paksa thermostat

iii. Kondisi Reset :

 Temp di atas  +7oC selama 10 menit secara berlajut


Kontrol unit Indoor
Pencegahan Freeze

Eg. Temp.  -5°C for 10mins


Outdoor Unit PC Board Layout

(2)Set mode display


(8 LEDs)
•LEDs display mode
berfungsi untuk
penyetingan.

(1)Microcomputer normal monitor Multi


outdoor
• Normal --- berkedip
Q1 Q2
• Malfunction --- nyala/ mati
Sambungan Terminal untuk transmisi yang digunakan
Outdoor Unit PC Board Layout

(3) Tombol setting mode


•Digunakan untuk
merubah mode 1
2
1234 1234
DS3 DS1 DS2

(4) Tombol Local setting


•Digunakan untuk
membuat setting local
Field Setting
Field Setting dari Outdoor Unit
• Penyetingan dengan tombol dip
Field setting dengan menggunakan tombol dip pada PCB
Dip Switch Setting
Penjelasan
No. Setting item
ON Pilih Untuk memilih cool/heat dari
DS1-1 OFF (Factory set) Cool/Heat remote controller equipped pada
outdoor unit
DS1-2 ~ ON Tidak
DS1-4 Jangan merubah setting pabrik
OFF (Factory set) digunakan
DS2-1 ~ ON Tidak
Jangan merubah setting pabrik
DS2-4 OFF (Factory set) digunakan
DS3-1 ~ ON Tidak
Jangan merubah setting pabrik
DS3-2 OFF (Factory set) digunakan
Field Setting
Field Setting dari Outdoor Unit
• Setting dengan tombol dip pada spare
part PCB
Dip Switch no Setting Setting Item
1 ON Pemilihan Cool/Heat
OFF (Factory set)
2 ON 200V
OFF 400V
DS1
3 ON Hanya Cooling only
OFF Heat Pump
4 ON Tergantung model dari
OFF outdoor unit (setting Model)
1 ON Model Jepang
DS2
OFF Model Luar Negeri
Field Setting
Field Setting dari Outdoor Unit

• Setting dengan
tombol dip

Capacity 5 Hp 8Hp 10 Hp 12 Hp 14 Hp 16 Hp 18 Hp
Dipswitch No
DS1 4 OFF ON OFF OFF OFF OFF ON

2 OFF OFF ON OFF ON OFF OFF

DS2 3 OFF ON ON OFF OFF ON ON

4 OFF OFF OFF OFF ON ON ON


Field Setting
Field Setting dari Outdoor Unit
Field Setting
Field Setting dari Outdoor Unit
Field Setting
Field Setting dari Outdoor Unit
• Prosedur untuk pengecekan check item (Setting Mode 1)
Field Setting
Field Setting dari Outdoor Unit
b. Setting Mode 2
No. Setting item Description
0 EMG (INV compressor Operates by Standard compressor only when inverter
operation prohibited) compressor malfunctions. Temporary operation until
the compressor is replaced. Since the comfortability is
extremely deteriorated, immediately replace the
compressor,(Not applicable to RSXYP5L)
1 address unified Set address untuk operasi unified cool/heat
Cool/heat
2 Low noise/demand Address untuk operasi low noise/demand
address
5 Fan Indoor unit Allows forced operation of indoor unit fan while unit is
beroperasi H stopped (H tap)
6 Indoor unit forced Allows forced operation of indoor unit.
operation
Field Setting
Field Setting From Outdoor Unit
b. Setting Mode 2

No. Setting item Description


8 Te setting Target temperatur evaporator untuk cooling
9 Tc setting Target temperatur Kondensor untuk heating
10 Merubah setting Merubah kondisi temperatur untuk defrost dan
Defrost menyeting cepat atau lambat defrost
12 External low noise Reception of external low noise or demand signal
setting/Demand (External control adaptor is used)
setting
13 AIRNET address Seting address untuk AIRNET.
18 High static pressure Membuat pengaturan operasi dalam (high static
setting pressure) gaya tekanan statis yang tinggi yang
menggunakan diffuser duct mounted
Field Setting
Field Setting From Outdoor Unit
b. Setting Mode 2
No. Setting item Description
19 Operasi Emergency Menghidupkan komp.Inv ketika kompresor standar
(hanya kompresor Inv rusak. Operasi ini bersifat sementara sebelum komp.
yg beroperasi ketika Standar . diganti (tidak berlaku untuk RXYQ5M)
komp. Standar
rusak))
20 Setting penambahan Operasi penambahan refrigerant
refrigerant
21 Menentukan mode Sets mode koleksi refrigerant.
koleksi Refrigerant
22 Seting Night-time low Operasi suara gaduh malam hari yang rendah yang
noise otomatis di-set secara sederhana. Operasi
didasarkan pada “ Permulaan yang di-set”& “ Akhiran
di-set”
Field Setting
Field Setting From Outdoor Unit
b. Setting Mode 2
No. Setting item Description
24 ENECUT Test Used to forcedly turn ON the ENECUT (Be noted
operation that the ENECUT is only functional with outdoor unit
in stopped state)
25 Setting Low noise Sets low noise bekerja ketika mendapat signal dari
luar
26 Pengaturan Menetapkan waktu permulaan dari operasi suara
permulaan Night-time gaduh malam hari yang rendah.
low noise control
27 Pengaturan akhir Menetapkan waktu akhir dari operasi suara gaduh
Night-time low noise malam hari yang rendah
control
28 Pengecekan Power Digunakan untuk diagnosa gangguan dari kompresor
transistor *Check DC. Untuk memeriksa apakah ganguan datang dari
setelah kabel kompresor atau PC board
kompresor dilepas
Field Setting
Field Setting From Outdoor Unit
b. Setting Mode 2
No. Setting item Description
29 Menentukan Jika kendali kapasitas digunakan, kendali suara
Kapasitas setting gaduh yang rendah secara otomatis digunakan
untuk menyelesaikan operasi suara gaduh yang
rendah& operasi suara gaduh malam hari yang
rendah
30 Permintaan setting 1 Merubah setting valve dari konsumsi tenaga ketika
menggunakan permintaan setting 1
32 Permintaan yg Secara normal memungkinkan mengendalikan 1
berlanjut (w/o permintaan tanpa menggunakan external input.
external control (efektif Untuk mencegah masalah dari circuit breaker
adaptor) yang kecil akan memutuskan arus apabila terjadi
beban yang besar.
Field Setting
Field Setting From Outdoor Unit
b. Setting Mode 2
No. Setting item Description
38 Operasi Emergency (Setting
untuk menghidupkan komp.
Standar pada master unit
apabila menggunakan multi-
outdoor-unit sistem)
39 Operasi Emergency (Setting Digunakan sementara waktu sebelum unit
untuk menghidupkan komp. yang rusak diganti. Unit yg rusak
Standar pada unit slave 1 secepatnya harus diganti.
apabila menggunakan multi-
outdoor-unit sistem (Setting hanya pada Master unit)

40 Operasi Emergency (Setting


untuk menghidupkan komp.
Standar pada unit slave 2
apabila menggunakan multi-
outdoor-unit sistem
Field Setting
Field Setting From Outdoor Unit
b. Setting Mode 2

No. Setting item Description


42 Operasi Emergency Jika kompresor mengalami kerusakan, biasanya
(setting emergency untuk menjalankan sistem hanya dengan
kompresor INV ) menggunakan Komp. STD. Running ini hanya
sementara sampai kompresor diganti, oleh karena
itu disarankan untuk menggati kompresor
secepatnya.
(Catatan : Setting ini tidak terdapat pada model
RXYQ5MAY1 )
Langkah emergency
Display sensor dan addres
Field Setting
Power Transistor Check Operation
• Menentukan kerusakan,
– Kerusakan inverter
– INV compressor

Pastikan kabel kompresor dilepas


Voltase seimbang antar phase

U-V
V-W berkisar ±5%
PCB
W-U inverter
normal