ACUAN SNI 03 - 2453 - 2002 Tabel 1

Luas rumah (A) 150 m2

Tabel Harga c
No Komposisi Presentase Luasan Presentase x Luasan c
1 Halaman 40% 150 60 0.600
2 Atap 40% 150 60 0.600
3 Jalan Aspal 20% 150 30 0.300
c Tadah 0.540

c Tadah 0.540
A Tadah 150 m2
R24 52.194 mm/hari
Diameter Sumur (d) 0.98 m
Kedalaman Sumur (H) 2 m
Waktu Konsentrasi (tc) 0.570561801 jam
K Tanah Kv 0.48 m3/m2/hari
Kh 0.96 m3/m2/hari

Volume Air yang Melimpas


C tadah = 0.540
A tadah = 150
R24 = 52.19406516
Vab = 0,855 x c Tadah x A Tadah x R24
= 3614.699983 liter
= 3.614699983 m3

Volume Air yang Meresap dalam Sumur


d = 0.98 m
H = 2 m
tc = 0.570561801 jam
Kv = 0.48 m3
/m 2
/hari
Kh = 0.96 m3/m2/hari
Ah = 0.753914 m2
Av = 6.1544 m2
A total = 6.908314 m2
Krata-rata = 0.907616927
Vresap = (tc / 24) x A total x K rata-rata
= 0.149061713 m3
Vstorasi = Vab - Vresap
= 3.46563827 m3
Tinggi Vstorasi = 4.596861539 m

Ketinggian Total Sumur Resapan


Ah = 0.753914 m2
Vstorasi = 3.46563827 m3
Htotal = Vstorasi / Ah
= 4.597 m

n = 2.298430769 3