002: 2008
Lampiran Surat Keputusan Direksi
PT PLN (PERSERO)
JALAN TRUNOJOYO BLOK M-I/135 KEBAYORAN BARU
Disusun oleh:
Kelompok Kerja
Teleinformasi Data Untuk Pemeliharaan Instalasi Sistem Tenaga Listrik
dengan Surat Keputusan General Manager
PT PLN (Persero) Penelitian dan Pengembangan Ketenagalistrikan
No. 006.K/LITBANG/2007
Diterbitkan oleh:
PT PLN (PERSERO)
Jalan Trunojoyo Blok M-I /135, Kebayoran Baru
Jakarta Selatan
Susunan Kelompok Bidang SCADA
Standardisasi
Surat Keputusan Direksi PT PLN (PERSERO) No: 094.K/DIR/2006
DAFTAR ISI
1. Ruang Lingkup........................................................................................................ 1
2. Tujuan ..................................................................................................................... 1
5. Umum ..................................................................................................................... 3
5.1 Fasilitas SCADA...................................................................................................... 3
i
SPLN S3.001: 2008
ii
SPLN S3.001: 2008
DAFTAR TABEL
iii
SPLN S3.001: 2008
DAFTAR GAMBAR
iv
SPLN S3.001: 2008
DAFTAR LAMPIRAN
v
SPLN S3.001: 2008
vi
SPLN S3.001: 2008
PRAKATA
Standar SCADA ini merupakan pengganti dari Pola SCADA SPLN No. 109 Tahun 1996,
dalam rangka mengikuti perkembangan teknologi SCADA. Standar ini menjelaskan
mengenai master station, komunikasi dan remote station yang terdiri dari enam bagian,
yaitu:
Keenam standar di atas adalah yang telah diselesaikan dalam tahun 2008 dan
direncanakan akan ditambah dengan beberapa standar lainnya mengenai SCADA.
Standar ini mencakup definisi, perangkat keras, perangkat lunak, kebutuhan teleinformasi
data, pengujian, kinerja, kajian kelayakan dalam pembangunan, operasi dan
pemeliharaan yang memiliki hubungan dengan sistem SCADA.
Standar ini dapat menjadi acuan dalam setiap perencanaan, pembangunan, operasi dan
pemeliharaan sistem SCADA di PT PLN (PERSERO) secara nasional.
vii
SPLN S5.001: 2008
1. Ruang Lingkup
Teleinformasi data terdiri dari telecontrol, telesignal dan telemetering. Sesuai dengan
penggunaannya, teleinformasi data dibedakan untuk kepentingan operasi dan kebutuhan
pemeliharaan. Standar ini dimaksudkan untuk menetapkan standar teleinformasi data
yang diaplikasikan untuk kebutuhan pemeliharaan sistem tenaga listrik dan mencakup
sistem transmisi dan sistem distribusi.
Standar ini, berlaku untuk sistem SCADA:
a. National Control Center, disingkat NCC;
b. Inter Regional Control Center, disingkat IRCC;
c. Regional Control Center, disingkat RCC;
d. Inter Distribution Control Center, disingkat IDCC;
e. Distribution Control Center, disingkat DCC.
2. Tujuan
Standar ini ditujukan untuk memberikan pedoman yang terarah dan seragam dalam
penerapan teleinformasi data bagi kebutuhan pemeliharaan sistem transmisi dan sistem
distribusi tenaga listrik yang mengutamakan mutu, keandalan dan ekonomi. Standar ini
merupakan acuan dalam pembangunan sistem SCADA baru dan pengembangan sistem
SCADA yang telah ada.
3. Acuan Normatif
4.1 Alarm
Perubahan kondisi dari peralatan atau sistem yang telah terdeteksi sebelumnya karena fungsi
yang tidak dilakukan oleh operator/dispatcher, atau kegagalan peralatan untuk merespon
secara benar. Indikasi alarm berupa audible atau visual, atau keduanya.
1
SPLN S3.001: 2008
Pusat kendali pengoperasian sistem tenaga listrik dimana master station ditempatkan.
Gardu yang merupakan titik tengah beban atau titik tengah feeder.
4.10 Keypoint
Peralatan switching dimana bisa dilakukan manuver antara dua feeder atau lebih.
2
SPLN S5.001: 2008
Pusat kendali yang terhubung dengan beberapa inter regional control center.
4.13 Operator
Petugas yang mengawasi dan mengeksekusi secara lokal peralatan di gardu induk.
Sistem yang mengawasi dan mengendalikan peralatan proses yang tersebar secara
geografis. [ IEC 870-1-3 ]
4.17 Telecontrol
Kendali peralatan operasional jarak jauh menggunakan transmisi informasi dengan teknik
telekomunikasi. [IEV 371-01-01]
CATATAN: Telekontrol dapat berisi kombinasi perintah, alarm, indikasi, metering/pengukuran,
proteksi dan fasilitas tripping, tidak menggunakan pesan suara.
4.18 Telesignal
Pengawasan status dari peralatan operasional dalam jarak tertentu dengan menggunakan
teknik telekomunikasi seperti kondisi alarm, posisi switch atau posisi katup. [IEV 371-01-
04]
4.19 Telemetering
Transmisi nilai variabel yang diukur dengan menggunakan teknik telekomunikasi. [IEV
371-01-03]
5. Umum
Setiap pembangunan pembangkit, gardu induk, gardu hubung, gardu tengah, key point
dan fasilitas sistem tenaga listrik yang baru harus dapat dipantau dari control center dan
3
SPLN S3.001: 2008
Standar ini membedakan teleinformasi data untuk transmisi dan distribusi. Teleinformasi
data untuk pemeliharaan instalasi sistem tenaga listrik dapat dilihat pada pada Lampiran
A – Daftar Teleinformasi (Transmisi) sampai dengan Lampiran D - Bidang Distribusi
(Teleinformasi pada Berbagai Konfigurasi Jaringan Distribusi).
Untuk daerah yang fungsi transmisi dan distribusi masih dalam satu organisasi maka
master station dapat digunakan untuk fungsi RCC dan DCC. Dalam hal ini teleinformasi
yang digunakan mengacu pada teleinformasi data transmisi dan distribusi.
Teleinformasi data untuk pemeliharaan instalasi sistem tenaga listrik ditampilkan pada
Maintenance Center dan Local HMI (Human Machine Interface). Konfigurasi workstation
di luar control center yang difungsikan untuk Maintenance Center, menampilkan
kebutuhan teleinformasi data untuk pemeliharaan instalasi sistem tenaga listrik, dapat
dilihat pada SPLN S3.001: 2008 Butir 5.2 dan untuk Local HMI (Human Machine
Interface) dapat dilihat pada SPLN S3.001: 2008 Butir 7.2.
Setiap pembangunan SCADA untuk fasilitas sistem tenaga listrik, kebutuhan teleinformasi
datanya harus mengacu pada SPLN S5.001:2008 Teleinformasi data untuk operasi
jaringan tenaga listrik dan SPLN S5.002: 2008 Teleinformasi data untuk pemeliharaan
instalasi sistem tenaga listrik.
Event dan alarm pemeliharaan merupakan informasi kepada regu pemeliharaan dan
operator tentang kejadian pada peralatan sistem tenaga listrik yang tampil di monitor dan
disimpan di data historikal. Struktur informasi event dan alarm SCADA dapat dilihat pada
Lampiran E – Struktur Informasi.
Simbol dan warna diperlukan untuk penyajian diagram sistem tenaga listrik pada monitor
dan layar tayang. Simbol dan warna untuk tiap jenis dan kondisi peralatan bersifat
informatif dan dipilih sedemikian rupa sehingga jenis dan kondisi peralatan tersebut
mudah dikenali oleh regu pemeliharaan dan operator. Simbol dan warna dapat dilihat
pada Lampiran F – Simbol dan Warna.
Teleinformasi data yang dikirim ke/dari suatu control center ditentukan oleh
kewenangannya dalam operasi sistem, sehingga dibutuhkan adanya batas yang jelas
antara kewenangan IRCC dan RCC serta RCC dan DCC. Berikut ini dijelaskan
perbatasan kebutuhan teleinformasi data antara IRCC dan RCC serta antara RCC dan
DCC.
4
SPLN S5.001: 2008
Perbatasan kebutuhan teleinformasi data antara IRCC dan RCC adalah di titik pelayanan
tegangan ekstra tinggi atau tegangan tinggi yang ditentukan, dan atau seperti Gambar 1
dan Gambar 2.
BUSBAR TET/TT
IRCC
RCC
BUSBAR TT
BUSBAR
TT
IRCC
RCC
BUSBAR
TT
5
SPLN S3.001: 2008
Perbatasan kebutuhan teleinformasi data antara RCC dan DCC di gardu induk ditunjukan
pada Gambar 3.
BUSBAR TT
L /R
P
Q
V
I
RCC
DCC
BUSBAR TM
Untuk daerah yang fungsi transmisi dan distribusi masih dalam satu organisasi (belum
dipisahkan antara fungsi RCC dan DCC) maka perbatasan kebutuhan teleinformasi data
dapat mengacu pada perbatasan fungsi RCC dan DCC atau disesuaikan dengan SOP
yang berlaku di daerah tersebut.
6
SPLN S5.001: 2008
7
SPLN S3.001: 2008
A-1: Telesignal
Kopel, Feeder,
3 CB Circuit breaker closed/opened Trafo, Diameter, D I
Capasitor, Reaktor
4 CD Control disable switch RTU D I
Gardu induk,
5 CSO Check synchronizing override Kopel, Feeder, D I
Diameter
6 DCBC Dummy breaker closed/opened Gardu induk D I
Kopel, Feeder,
7 ES Earth Switch Closed/Opened Trafo, Diameter, D I
Capasitor, Reaktor
8 GUC Generator unit run/stop Generator D I
9 LFA Load frequency available/not available Generator D I
10 LFC Load frequency control on/off switch Generator D I
11 LFR Load frequency request on/off Generator D I
12 LI Line isolator switch closed/opened Feeder, Trafo D I
Gardu induk,
Kopel, Feeder,
13 LR Local remote D I
Trafo, Diameter,
Capasitor, Reaktor
14 LRT Local remote switch for tapchanger Trafo D I
15 PSO Power station operated Generator D I
Distribution
16 RACK Circuit Breaker Rack-In/Rack-Out D I
Transformer
17 RMT Reset Master Trip Gardu induk D I
Gardu induk,
18 SAM Synchronization Auto/Manual Kopel, Feeder, D I
Trafo, Diameter
19 TC Tap changer raise/lower Trafo D I
20 TCC Tap changer auto/manual Trafo D I
21 TFAM Transformer Fan Auto/Manual Transformer D I
22 110RF 110 VDC Rectifier failure Gardu Induk S A
23 110SF 110 VDC Supply failure Gardu Induk S A
24 220F 220 VAC Failure Gardu Induk S A
25 220RF 220 VDC Rectifier failure Gardu Induk S A
26 220SF 220 VDC Supply failure Gardu Induk S A
27 24RF 24 VDC Rectifier failure Gardu Induk S A
28 24SF 24 VDC Supply failure Gardu Induk S A
29 380F 380 VAC Failure Gardu Induk S A
30 48RF 48 VDC Rectifier failure Gardu Induk S A
31 48SF 48 VDC Supply failure Gardu Induk S A
32 AIRCF Air conditioning failure Gardu Induk S A
33 AQR Automatic power factor regulator Generator S I
8
SPLN S5.001: 2008
9
SPLN S3.001: 2008
10
SPLN S5.001: 2008
11
SPLN S3.001: 2008
12
SPLN S5.001: 2008
KETERANGAN:
A = Announciation of abnormal condition (audible alarm, flashing display, etc)
I = Event/Indication (normal condition)
13
SPLN S3.001: 2008
A-2: Telemeasurement
14
SPLN S5.001: 2008
15
SPLN S3.001: 2008
16
SPLN S5.001: 2008
17
SPLN S3.001: 2008
TA-01
P
Q
V
P
Q Q
I
BUSBAR -A
L/R L/R
BUSBAR -B
V
L/R
P P P
Q Q Q
V V L/R V
I I I
BAY TRANSMISI BAY IBT BAY TRAFO TENAGA
18
SPLN S5.001: 2008
19
SPLN S3.001: 2008
20
SPLN S5.001: 2008
21
SPLN S3.001: 2008
22
SPLN S5.001: 2008
23
SPLN S3.001: 2008
24
SPLN S5.001: 2008
25
SPLN S3.001: 2008
26
SPLN S5.001: 2008
KETERANGAN:
*)
= Khusus untuk OHL Feeder
**)
= Khusus untuk Cable Feeder
A = Alarm
I = Indikasi
Rincian Teleinformasi diatas adalah rincian per bay
27
SPLN S3.001: 2008
TA-02
P
Q
V
P
Q Q
I
BAY KOPEL
BUSBAR - A
BUSBAR - B
L/R
P P P
Q Q Q
V V V
I I I
BAY TRANSMISI BAY TRAFO TENAGA BAY IBT
28
SPLN S5.001: 2008
29
SPLN S3.001: 2008
30
SPLN S5.001: 2008
31
SPLN S3.001: 2008
32
SPLN S5.001: 2008
33
SPLN S3.001: 2008
34
SPLN S5.001: 2008
35
SPLN S3.001: 2008
36
SPLN S5.001: 2008
37
SPLN S3.001: 2008
KETERANGAN:
*)
= Khusus untuk OHL Feeder
**)
= Khusus untuk Cable Feeder
A = Alarm
I = Indikasi
Rincian Teleinformasi diatas adalah rincian per bay
38
SPLN S5.001: 2008
TA-03
P
Q
V
P
Q Q
I
L/R L/R
BUSBAR
L/R
P P P
Q Q Q
V V V
I I I
BAY TRANSMISI BAY TRAFO TENAGA BAY IBT
39
SPLN S3.001: 2008
40
SPLN S5.001: 2008
41
SPLN S3.001: 2008
42
SPLN S5.001: 2008
43
SPLN S3.001: 2008
44
SPLN S5.001: 2008
45
SPLN S3.001: 2008
46
SPLN S5.001: 2008
47
SPLN S3.001: 2008
48
SPLN S5.001: 2008
KETERANGAN:
*)
= Khusus untuk OHL Feeder
**)
= Khusus untuk Cable Feeder
A = Alarm
I = Indikasi
Rincian Teleinformasi diatas adalah rincian per bay
49
SPLN S3.001: 2008
TB-01
GENERATOR COMBINED CYCLE
PADA KONFIGURASI 1½ BREAKER
Joint Control
P P P P
Q Q Q Q
V V V V
P P P
Q Q Q
I I I BUSBAR- A
BUSBAR- B
50
SPLN S5.001: 2008
51
SPLN S3.001: 2008
TB-02
P P
Q Q
V V
P
Q
I
BUSBAR - A
BUSBAR - B
Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 3-Belitan Pada Konfigurasi 1½ Breaker
Data No Kode Fungsi Tipe Jmh
6 I Arus 1
7 KVARH Kilovar hour 2
8 KWH Kilowatt hour 2
TM
9 P Daya aktif 3
13 Q Daya reaktif 3
16 V Tegangan 2
52
SPLN S5.001: 2008
53
SPLN S3.001: 2008
TB-03
2 GENERATOR TERHUBUNG KE MTR 3-BELITAN
PADA KONFIGURASI DOUBLE BUSBAR
P P
Q Q
V V
P
Q
I
L/R
BUSBAR - A
BUSBAR - B
Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 3-Belitan Pada Konfigurasi Double
Busbar
Data No Kode Fungsi Tipe Jmh
6 I Arus 1
7 KVARH Kilovar hour 2
8 KWH Kilowatt hour 2
TM
9 P Daya aktif 3
13 Q Daya reaktif 3
16 V Tegangan 2
41 CBDF Circuit breaker drive failure A 1
44 CBM Circuit breaker maintenance A 1
58 CSP Check synchronizing in progress A 1
74 DFRF Disturbance fault recorder faulty A 1
75 DIFF Differential failure A 1
TSS 106 ERF Event recorder failure A 1
114 GTT Generator transformer trip A 1
118 LPA Low pressure alarm A 1
119 LPB Low pressure block A 1
120 LPT Low pressure trip A 1
121 MTO Master trip operate A 1
54
SPLN S5.001: 2008
55
SPLN S3.001: 2008
TB-04
2 GENERATOR TERHUBUNG KE MTR 3-BELITAN
PADA KONFIGURASI SINGLE BUSBAR
P P
Q Q
V V
P
Q
I
L/R
BUSBAR
Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 3-Belitan Pada Konfigurasi Single
Busbar
Data No Kode Fungsi Tipe Jmh
6 I Arus 1
7 KVARH Kilovar hour 2
8 KWH Kilowatt hour 2
TM
9 P Daya aktif 3
13 Q Daya reaktif 3
16 V Tegangan 2
41 CBDF Circuit breaker drive failure A 1
44 CBM Circuit breaker maintenance A 1
58 CSP Check synchronizing in progress A 1
74 DFRF Disturbance fault recorder faulty A 1
75 DIFF Differential failure A 1
106 ERF Event recorder failure A 1
114 GTT Generator transformer trip A 1
TSS
118 LPA Low pressure alarm A 1
119 LPB Low pressure block A 1
120 LPT Low pressure trip A 1
121 MTO Master trip operate A 1
129 P1REF Restricted earth fault A 1
130 P2GFR Ground fault relay A 1
131 P2OCR Over current relay A 1
56
SPLN S5.001: 2008
57
SPLN S3.001: 2008
TB-05
P
Q
V
P
Q
I
BUSBAR - A
BUSBAR - B
Teleinformasi Data Untuk 1 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi 1½ Breaker
Data No Kode Fungsi Tipe Jmh
6 I Arus 1
7 KVARH Kilovar hour 1
8 KWH Kilowatt hour 1
TM
9 P Daya aktif 2
13 Q Daya reaktif 2
16 V Tegangan 1
74 DFRF Disturbance fault recorder faulty A 1
75 DIFF Differential failure A 1
TSS 106 ERF Event recorder failure A 1
114 GTT Generator transformer trip A 1
121 MTO Master trip operate A 1
58
SPLN S5.001: 2008
59
SPLN S3.001: 2008
TB-06
1 GENERATOR TERHUBUNG KE MTR 2-BELITAN
PADA KONFIGURASI DOUBLE BUSBAR
P
Q
V
P
Q
I
L/R
BUSBAR - A
BUSBAR - B
Teleinformasi Data Untuk 1 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Double
Busbar
Data No Kode Fungsi Tipe Jmh
6 I Arus 1
7 KVARH Kilovar hour 1
8 KWH Kilowatt hour 1
TM
9 P Daya aktif 2
13 Q Daya reaktif 2
16 V Tegangan 1
41 CBDF Circuit breaker drive failure A 1
44 CBM Circuit breaker maintenance A 1
58 CSP Check synchronizing in progress A 1
74 DFRF Disturbance fault recorder faulty A 1
75 DIFF Differential failure A 1
106 ERF Event recorder failure A 1
TSS 114 GTT Generator transformer trip A 1
118 LPA Low pressure alarm A 1
119 LPB Low pressure block A 1
120 LPT Low pressure trip A 1
121 MTO Master trip operate A 1
129 P1REF Restricted earth fault A 1
130 P2GFR Ground fault relay A 1
60
SPLN S5.001: 2008
61
SPLN S3.001: 2008
TB-07
1 GENERATOR TERHUBUNG KE MTR 2-BELITAN
PADA KONFIGURASI SINGLE BUSBAR
P
Q
V
P
Q
I
L/R
BUSBAR
Teleinformasi Data Untuk 1 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Single
Busbar
Data No Kode Fungsi Tipe Jmh
6 I Arus 1
7 KVARH Kilovar hour 1
8 KWH Kilowatt hour 1
TM
9 P Daya aktif 2
13 Q Daya reaktif 2
16 V Tegangan 1
41 CBDF Circuit breaker drive failure A 1
44 CBM Circuit breaker maintenance A 1
58 CSP Check synchronizing in progress A 1
74 DFRF Disturbance fault recorder faulty A 1
75 DIFF Differential failure A 1
106 ERF Event recorder failure A 1
114 GTT Generator transformer trip A 1
118 LPA Low pressure alarm A 1
TSS 119 LPB Low pressure block A 1
120 LPT Low pressure trip A 1
121 MTO Master trip operate A 1
129 P1REF Restricted earth fault A 1
130 P2GFR Ground fault relay A 1
131 P2OCR Over current relay A 1
133 PD Pole discrepancy A 1
134 PHR Trip phase R A 1
135 PHS Trip phase S A 1
62
SPLN S5.001: 2008
63
SPLN S3.001: 2008
TB-08
P
Q
V
P
Q
I BUSBAR - A
BUSBAR - B
Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi 1½ Breaker
Data No Kode Fungsi Tipe Jmh
6 I Arus 1
7 KVARH Kilovar hour 1
8 KWH Kilowatt hour 1
TM
9 P Daya aktif 2
13 Q Daya reaktif 2
16 V Tegangan 1
74 DFRF Disturbance fault recorder faulty A 1
TSS 75 DIFF Differential failure A 1
106 ERF Event recorder failure A 1
64
SPLN S5.001: 2008
65
SPLN S3.001: 2008
TB-09
2 GENERATOR TERHUBUNG KE MTR 2-BELITAN
PADA KONFIGURASI DOUBLE BUSBAR
P
Q
V
P
Q
I
L/R
BUSBAR - A
BUSBAR - B
Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Double
Busbar
Data No Kode Fungsi Tipe Jmh
6 I Arus 1
7 KVARH Kilovar hour 1
8 KWH Kilowatt hour 1
TM
9 P Daya aktif 2
13 Q Daya reaktif 2
16 V Tegangan 1
41 CBDF Circuit breaker drive failure A 1
44 CBM Circuit breaker maintenance A 1
58 CSP Check synchronizing in progress A 1
74 DFRF Disturbance fault recorder faulty A 1
75 DIFF Differential failure A 1
TSS 106 ERF Event recorder failure A 1
114 GTT Generator transformer trip A 1
118 LPA Low pressure alarm A 1
119 LPB Low pressure block A 1
120 LPT Low pressure trip A 1
121 MTO Master trip operate A 1
66
SPLN S5.001: 2008
67
SPLN S3.001: 2008
TB-10
2 GENERATOR TERHUBUNG KE MTR 2-BELITAN
PADA KONFIGURASI SINGLE BUSBAR
P
Q
V
P
Q
I
L/R
BUSBAR
Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Single
Busbar
Data No Kode Fungsi Tipe Jmh
6 I Arus 1
7 KVARH Kilovar hour 1
8 KWH Kilowatt hour 1
TM
9 P Daya aktif 2
13 Q Daya reaktif 2
16 V Tegangan 1
41 CBDF Circuit breaker drive failure A 1
44 CBM Circuit breaker maintenance A 1
58 CSP Check synchronizing in progress A 1
74 DFRF Disturbance fault recorder faulty A 1
75 DIFF Differential failure A 1
106 ERF Event recorder failure A 1
114 GTT Generator transformer trip A 1
TSS
118 LPA Low pressure alarm A 1
119 LPB Low pressure block A 1
120 LPT Low pressure trip A 1
121 MTO Master trip operate A 1
129 P1REF Restricted earth fault A 1
130 P2GFR Ground fault relay A 1
131 P2OCR Over current relay A 1
68
SPLN S5.001: 2008
69
SPLN S3.001: 2008
TB-11
INTERBUS TRANSFORMER
Secondary Side Connected to 1½ Breaker
BUSBAR (IRCC)
L/R
P
Q
BUSBAR - A V
I
Download to RCC
Dioperasikan dari RCC
BUSBAR - B
70
SPLN S5.001: 2008
71
SPLN S3.001: 2008
72
SPLN S5.001: 2008
TB-12
INTERBUS TRANSFORMER
Secondary Side Connected to Double Busbar
BUSBAR (IRCC or RCC)
L/R
P
Q
V
I
Operation Responsibility
L/R by IRCC or RCC
BUSBAR - B
Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to Double Busbar)
Data No Kode Fungsi Tipe Jmh
TC 1 TPI Tap position indication I 3-1 *)
1 AMF Amperes fault ( per phase ) 3-1 *)
3 CNTA Counter arester 3-1 *)
4 CTPI Counter tap position indication 3-1 *)
6 I Arus 3-1 *)
7 KVARH Kilovar hour 1
TM 8 KWH Kilowatt hour 1
9 P Daya aktif 1
12 PRES Pressure 3-1 *)
13 Q Daya reaktif 1
15 TEMP Temperature 12-3 *)
16 V Tegangan 3-1 *)
73
SPLN S3.001: 2008
74
SPLN S5.001: 2008
KETERANGAN:
*)
= (Primary Side Connected to 1½ Breaker)–(Primary Side Connected to Double Busbar)
75
SPLN S3.001: 2008
TB-13
INTERBUS TRANSFORMER
Secondary Side Connected to Single Busbar
BUSBAR (IRCC or RCC)
L/R
P
Q
V
I
Operation Responsibility
by IRCC or RCC
L/R
Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to Single Busbar)
Data No Kode Fungsi Tipe Jmh
TC 1 TPI Tap position indication I 1
1 AMF Amperes fault ( per phase ) 1
3 CNTA Counter arester 1
4 CTPI Counter tap position indication 1
6 I Arus 1
7 KVARH Kilovar hour 1
TM 8 KWH Kilowatt hour 1
9 P Daya aktif 1
12 PRES Pressure 1
13 Q Daya reaktif 1
15 TEMP Temperature 3
16 V Tegangan 1
41 CBDF Circuit breaker drive failure A 1-2 *)
42 CBFA Circuit breaker failure (a) operate A 1-2 *)
TSS
43 CBFB Circuit breaker failure (b) operate A 1-2 *)
44 CBM Circuit breaker maintenance I 1-2 *)
76
SPLN S5.001: 2008
77
SPLN S3.001: 2008
KETERANGAN:
*)
= (Primary Side Connected to 1½ Breaker)–(Primary Side Connected to Double Busbar)
78
SPLN S5.001: 2008
L/R
Q
P
Q
V
I
BUSBAR - A
Operation Responsibility
by IRCC
79
SPLN S3.001: 2008
80
SPLN S5.001: 2008
81
SPLN S3.001: 2008
Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to Double Busbar
Dilengkapi Shunt Reaktor Pada Kumparan Tersier)
Data No Kode Fungsi Tipe Jmh
TC 1 TPI Tap position indication I 3-1 *)
1 AMF Amperes fault ( per phase ) 3-1 *)
3 CNTA Counter arester 3-1 *)
4 CTPI Counter tap position indication 3-1 *)
6 I Arus 3-1 *)
TM
7 KVARH Kilovar hour 1
8 KWH Kilowatt hour 1
9 P Daya aktif 1
12 PRES Pressure 3-1 *)
82
SPLN S5.001: 2008
83
SPLN S3.001: 2008
KETERANGAN:
*)
= (Primary Side Connected to 1½ Breaker)–(Primary Side Connected to Double Busbar)
84
SPLN S5.001: 2008
L/R
P
Q Q
V
I
Operation Responsibility
by IRCC or RCC
L/R
BUSBAR
Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to Single Busbar
Dilengkapi Shunt Reaktor Pada Kumparan Tersier)
85
SPLN S3.001: 2008
86
SPLN S5.001: 2008
KETERANGAN:
*)
= (Primary Side Connected to 1½ Breaker)–(Primary Side Connected to Double Busbar)
87
SPLN S3.001: 2008
88
SPLN S5.001: 2008
89
SPLN S3.001: 2008
90
SPLN S5.001: 2008
TB-18
BAY TRAFO TENAGA
PADA KONFIGURASI DOUBLE BUSBAR
BUSBAR - A
BUSBAR - B
L/R
P
Q
TEGANGAN TINGGI V
I
Batas wewenang
TEGANGAN MENENGAH
DOUBLE BUSBAR
Teleinformasi Data Untuk Bay Trafo Tenaga Pada Konfigurasi Double Busbar
Data No Kode Fungsi Tipe Jmh
TC 1 TPI Tap position indication I 1
1 AMF Amperes fault ( per phase ) 1
2 CCB Counter of circuit breaker 1
3 CNTA Counter arester 1
4 CTPI Counter tap position indication 1
6 I Arus 1
7 KVARH Kilovar hour 1
TM
8 KWH Kilowatt hour 1
9 P Daya aktif 1
12 PRES Pressure 1
13 Q Daya reaktif 1
15 TEMP Temperature 3
16 V Tegangan 1
41 CBDF Circuit breaker drive failure A 1
42 CBFA Circuit breaker failure (a) operate A 1
TSS
43 CBFB Circuit breaker failure (b) operate A 1
44 CBM Circuit breaker maintenance I 1
91
SPLN S3.001: 2008
92
SPLN S5.001: 2008
93
SPLN S3.001: 2008
TB-19
BAY TRAFO TENAGA
PADA KONFIGURASI SINGLE BUSBAR
BUSBAR
L/R
P
Q
TEGANGAN TINGGI V
I
Batas wewenang
TEGANGAN MENENGAH
DOUBLE BUSBAR
Teleinformasi Data Untuk Bay Trafo Tenaga Pada Konfigurasi Single Busbar
Data No Kode Fungsi Tipe Jmh
TC 1 TPI Tap position indication I 1
1 AMF Amperes fault ( per phase ) 1
2 CCB Counter of circuit breaker 1
3 CNTA Counter arester 1
4 CTPI Counter tap position indication 1
6 I Arus 1
7 KVARH Kilovar hour 1
TM
8 KWH Kilowatt hour 1
9 P Daya aktif 1
12 PRES Pressure 1
13 Q Daya reaktif 1
15 TEMP Temperature 3
16 V Tegangan 1
41 CBDF Circuit breaker drive failure A 1
42 CBFA Circuit breaker failure (a) operate A 1
43 CBFB Circuit breaker failure (b) operate A 1
TSS
44 CBM Circuit breaker maintenance I 1
60 DCF DC supply failure A 1
74 DFRF Disturbance fault recorder faulty A 1
94
SPLN S5.001: 2008
95
SPLN S3.001: 2008
96
SPLN S5.001: 2008
TB-20
BAY REAKTOR
PADA KONFIGURASI 1½ BREAKER
BUSBAR - A
BUSBAR - B
Reaktor
97
SPLN S3.001: 2008
98
SPLN S5.001: 2008
TB-21
BAY REAKTOR
PADA KONFIGURASI DOUBLE BUSBAR
BUSBAR - A
BUSBAR - B
L/R
Reaktor
99
SPLN S3.001: 2008
100
SPLN S5.001: 2008
TB-22
BAY REAKTOR
PADA KONFIGURASI SINGLE BUSBAR
BUSBAR
L/R
Reaktor
101
SPLN S3.001: 2008
102
SPLN S5.001: 2008
TB-23
BAY KAPASITOR
PADA KONFIGURASI DOUBLE BUSBAR
BUSBAR - A
BUSBAR - B
L/R
Capasitor
103
SPLN S3.001: 2008
104
SPLN S5.001: 2008
TB-24
BAY KAPASITOR
PADA KONFIGURASI SINGLE BUSBAR
BUSBAR
L/R
Capasitor
105
SPLN S3.001: 2008
106
SPLN S5.001: 2008
TB-25
BAY PENGHANTAR
PADA KONFIGURASI 1½ BREAKER
BUSBAR - A
BUSBAR - B
P
Q
V
I
107
SPLN S3.001: 2008
108
SPLN S5.001: 2008
KETERANGAN:
*)
= Khusus untuk OHL Feeder
**)
= Khusus untuk Cable Feeder
109
SPLN S3.001: 2008
TB-26
BAY PENGHANTAR
PADA KONFIGURASI DOUBLE BUSBAR
BUSBAR - A
BUSBAR - B
L/R
P
Q
V
I
110
SPLN S5.001: 2008
111
SPLN S3.001: 2008
KETERANGAN:
*)
= Khusus untuk OHL Feeder
**)
= Khusus untuk Cable Feeder
112
SPLN S5.001: 2008
113
SPLN S3.001: 2008
114
SPLN S5.001: 2008
KETERANGAN:
*)
= Khusus untuk OHL Feeder
**)
= Khusus untuk Cable Feeder
115
SPLN S3.001: 2008
BUSBAR - A
BUSBAR - B
L/R
P
Q
V
I
Teleinformasi Data Untuk Bay Penghantar Serial Dengan Reaktor Pada Konfigurasi Double Busbar
116
SPLN S5.001: 2008
117
SPLN S3.001: 2008
118
SPLN S5.001: 2008
KETERANGAN:
*)
= Khusus untuk OHL Feeder
**)
= Khusus untuk Cable Feeder
119
SPLN S3.001: 2008
BUSBAR - B
P
Q
Q V
I
L/R
Teleinformasi Data Untuk Bay Penghantar Paralel Dengan 1 Reaktor Pada Konfigurasi 1½ Breaker
Data No Kode Fungsi Tipe Jmh
1 AMF Amperes fault ( per phase ) 1
3 CNTA *) Counter arester 1
6 I Arus 1
7 KVARH Kilovar hour 1
TM
8 KWH Kilowatt hour 1
9 P Daya aktif 1
13 Q Daya reaktif 2
16 V Tegangan 1
49 CDAF Current differential relay (a) failure A 1
50 CDAR Current differential (a) phase R A 1
51 CDAS Current differential (a) phase S A 1
TSS 52 CDAT Current differential (a) phase T A 1
53 CDBF Current differential relay (b) failure A 1
54 CDBR Current differential (b) phase R A 1
55 CDBS Current differential (b) phase S A 1
120
SPLN S5.001: 2008
121
SPLN S3.001: 2008
KETERANGAN:
*)
= Khusus untuk OHL Feeder
**)
= Khusus untuk Cable Feeder
122
SPLN S5.001: 2008
TB-30
BAY PENGHANTAR
PARALEL DENGAN 2 REAKTOR SERI
PADA KONFIGURASI 1 ½ BREAKER
BUSBAR- A
BUSBAR- B
P
Q Q
V
I
Q
Teleinformasi Data Untuk Bay Penghantar Paralel Dengan 2 Reaktor seri Pada Konfigurasi 1½
Breaker
Data No Kode Fungsi Tipe Jmh
1 AMF Amperes fault ( per phase ) 1
3 CNTA *) Counter arester 1
6 I Arus 1
7 KVARH Kilovar hour 1
TM
8 KWH Kilowatt hour 1
9 P Daya aktif 1
13 Q Daya reaktif 3
16 V Tegangan 1
49 CDAF Current differential relay (a) failure A 1
50 CDAR Current differential (a) phase R A 1
51 CDAS Current differential (a) phase S A 1
TSS
52 CDAT Current differential (a) phase T A 1
53 CDBF Current differential relay (b) failure A 1
54 CDBR Current differential (b) phase R A 1
123
SPLN S3.001: 2008
124
SPLN S5.001: 2008
KETERANGAN:
*)
= Khusus untuk OHL Feeder
**)
= Khusus untuk Cable Feeder
125
SPLN S3.001: 2008
TB-31
BAY KOPEL
PADA KONFIGURASI DOUBLE BUSBAR
L/R
BUSBAR - A
BUSBAR - B
126
SPLN S5.001: 2008
127
SPLN S3.001: 2008
TB-32
BUS SECTION
Tipe-1
L/R
Tipe-2
L/R
128
SPLN S5.001: 2008
129
SPLN S3.001: 2008
TB-33
BAY DIAMETER
PADA KONFIGURASI 1½ BREAKER
BUSBAR - A
L/R
L/R
L/R
BUSBAR - B
130
SPLN S5.001: 2008
131
SPLN S3.001: 2008
132
SPLN S5.001: 2008
133
SPLN S3.001: 2008
C-1: Telesignal
Single (S) Suggested
or Double Alarm (A) or
No Kode Fungsi Implementasi
(D) Event/Indication
Indication (I)
Feeder
1 ARU Auto Recloser Use/Unuse D I
PBO
Bus Coupler
Bus Section
Feeder
2 BI Bus Isolator Switch Closed/Opened Incoming D I
Capacitor
Reactor
Gen Transf
3 CAM Capacitor Auto/Manual Capacitor D I
Bus Coupler
Bus Section
Feeder
Incoming
4 CB Circuit Breaker Closed/Opened Capacitor D I
Reactor
Gen Transf
Generator
PBO
5 CD Control Disable Switch RTU D I
134
SPLN S5.001: 2008
Feeder
12 RR Recloser Reset D I
PBO
Feeder
20 AR Circuit Breaker Auto Reclose S A
PBO
Feeder
21 ARO Auto Reclose Off S A
PBO
Bus Coupler
Bus Section
Feeder
Incoming
22 CBDF Circuit Breaker Drive Failure S A
Capacitor
Reactor
Gen Transf
PBO
Bus Coupler
Bus Section
Feeder
23 CBTR CB Trip Incoming S A
Capacitor
Reactor
PBO
RTU
24 CTE Cabinet Temperatur S A
IED
Gardu Induk
Keypoint
25 DCG DC Ground PBO S A
Gardu Tengah
Gardu Hubung
Gardu Induk
Keypoint
26 DOOR Door Activated PBO S A
Gardu Tengah
Gardu Hubung
135
SPLN S3.001: 2008
136
SPLN S5.001: 2008
137
SPLN S3.001: 2008
C-2: Telemeasurement
Feeder
Incoming
1 AMF Amperes Fault (Per Phase)
Gen Transf
PBO
Bus Coupler
Bus Section
Feeder
Incoming
2 CCB Counter of Circuit Breaker
Capacitor
Reactor
Gen Transf
PBO
3 F Frekuensi Busbar
Feeder
Incoming
Capacitor
4 I Arus Reactor
Generator
Keypoint
PBO
Feeder
Incoming
5 KVARH Kilovar Hour Capacitor
Reactor
Gen Transf
Feeder
Incoming
6 KWH Kilowatt Hour Capacitor
Reactor
Gen Transf
Feeder
Incoming
Capacitor
7 P Daya Aktif
Reactor
Generator
Keypoint
Incoming
Capacitor
9 Q Daya Reaktif
Reactor
Generator
Busbar
Generator
10 V Tegangan
Keypoint
PBO
138
SPLN S5.001: 2008
139
SPLN S3.001: 2008
Feeder
1 ARU Auto Recloser use/unuse
PBO
Bus Coupler
Bus Section
Feeder
2 CB Circuit Breaker Closed/Opened Incoming
Capacitor
Reactor
Gen Transf
Keypoint
5 LBS Load Break Switch Close/Open Gardu Tengah
Gardu Hubung
Bus Coupler
Bus Section
Feeder
Incoming
Capacitor
6 LR Local Remote Reactor
Gen Transf
Keypoint
PBO
Gardu Tengah
Gardu Hubung
Feeder
8 RR Recloser Reset
PBO
140
SPLN S5.001: 2008
141
SPLN S3.001: 2008
CAPASITOR GENERATOR
P
Q
V
Q P KOPEL
Q
I
L/ R L/R L/ R
V(R)
V(S)
BUSBAR
- A
V(T)
BUSBAR
- B
V(R)
V(S)
V(T)
L/R L/R
I (R) I
I (S) P
I (T) Q
P PF
142
SPLN S5.001: 2008
143
SPLN S3.001: 2008
Group
Data No Kode Fungsi Tipe Jmh
Bay
4 CB Circuit Breaker Closed/Opened I 1
7 ES Earth Switch Closed/Opened I 1
2 CB Circuit Breaker Closed/Opened I 1
RCD 6 LR Local Remote I 1
2 CCB Counter of Circuit Breaker 1
4 I Arus 3
5 KVARH Kilovar Hour 1
TM
6 KWH Kilowatt Hour 1
7 P Daya Aktif 1
9 Q Daya Reaktif 1
22 CBDF Circuit Breaker Drive Failure A 1
23 CBTR CB Trip A 1
35 LPA Low Pressure Alarm A 1
37 P1DEF Directional Earth Fault A 1
TSS
Capasitor 38 P2GFR Ground Fault Relay A 1
39 P2OCR Over Current Relay A 1
41 PTF Protection Faulty A 1
53 TCS1 Trip Coil Supervisory 1 A 1
2 BI Bus Isolator Switch Closed/Opened I 2
3 CAM Capacitor Auto/Manual I 1
TSD 4 CB Circuit Breaker Closed/Opened I 1
7 ES Earth Switch Closed/Opened I 1
10 LR Local Remote I 1
2 CB Circuit Breaker Closed/Opened 1
RCD
6 LR Local Remote 1
4 I Arus 3
7 P Daya aktif 1
TM
9 Q Daya reaktif 1
Generator 10 V Tegangan 1
TSS 56 UT Unit Trip A 1
4 CB Circuit breaker closed/opened I 1
TSD
8 GUC Generator unit run/stop I 1
TM 2 CCB Counter of Circuit Breaker
22 CBDF Circuit Breaker Drive Failure A 1
23 CBTR CB Trip A 1
35 LPA Low Pressure Alarm A 1
TSS 38 P2GFR Ground Fault Relay A 1
39 P2OCR Over Current Relay A 1
41 PTF Protection Faulty A 1
Kopel
53 TCS1 Trip Coil Supervisory 1 A 1
2 BI Bus Isolator Switch Closed/Opened I 2
4 CB Circuit Breaker Closed/Opened I 1
TSD
7 ES Earth Switch Closed/Opened I 1
10 LR Local Remote I 1
2 CB Circuit Breaker Closed/Opened 1
RCD
6 LR Local Remote 1
144
SPLN S5.001: 2008
CAPASITOR GENERATOR
P
Q
V
P
Q Q
I
L/R L/R
V (R)
BUSBAR
- A V (S)
V (T)
FEEDER INCOMING 20 KV
145
SPLN S3.001: 2008
146
SPLN S5.001: 2008
Group
Data No Kode Fungsi Tipe Jmh
Bay
4 CB Circuit Breaker Closed/Opened I 1
7 ES Earth Switch Closed/Opened I 1
2 CB Circuit Breaker Closed/Opened I 1
RCD 6 LR Local Remote I 1
2 CCB Counter of Circuit Breaker 1
4 I Arus 3
5 KVARH Kilovar Hour 1
TM
6 KWH Kilowatt Hour 1
7 P Daya Aktif 1
9 Q Daya Reaktif 1
22 CBDF Circuit Breaker Drive Failure A 1
23 CBTR CB Trip A 1
35 LPA Low Pressure Alarm A 1
37 P1DEF Directional Earth Fault A 1
TSS
Capasitor 38 P2GFR Ground Fault Relay A 1
39 P2OCR Over Current Relay A 1
41 PTF Protection Faulty A 1
53 TCS1 Trip Coil Supervisory 1 A 1
2 BI Bus Isolator Switch Closed/Opened I 1
3 CAM Capacitor Auto/Manual I 1
TSD 4 CB Circuit Breaker Closed/Opened I 1
7 ES Earth Switch Closed/Opened I 1
10 LR Local Remote I 1
2 CB Circuit Breaker Closed/Opened 1
RCD
6 LR Local Remote 1
4 I Arus 3
7 P Daya aktif 1
TM
9 Q Daya reaktif 1
Generator 10 V Tegangan 1
TSS 56 UT Unit Trip A 1
4 CB Circuit breaker closed/opened I 1
TSD
8 GUC Generator unit run/stop I 1
147
SPLN S3.001: 2008
DB - 01
TRAFO 150/20 KV DAN 70/20 KV
TYPE 1
RCC
I DCC
P L/R
Q
PF
148
SPLN S5.001: 2008
Group
Data No Kode Fungsi Tipe Jmh
Bay
4 CB Circuit Breaker Closed/Opened I 1
7 ES Earth Switch Closed/Opened I 1
2 CB Circuit Breaker Closed/Opened I 1
RCD 6 LR Local Remote I 1
149
SPLN S3.001: 2008
DB -02
TRAFO 150/20 KV DAN 70/20 KV
TYPE 2
RCC
DCC
I
P
Q
PF
L/R
150
SPLN S5.001: 2008
Group
Data No Kode Fungsi Tipe Jmh
Bay
7 ES Earth Switch Closed/Opened I 1
11 RACK Circuit Breaker Rackin/Rackout I 1
2 CB Circuit Breaker Closed/Opened I 1
RCD 6 LR Local Remote I 1
151
SPLN S3.001: 2008
DB -03
TRAFO 150/20 KV DAN 70/20 KV
TYPE 3
RCC
DCC
I
P L/R
Q
PF
152
SPLN S5.001: 2008
Group
Data No Kode Fungsi Tipe Jmh
Bay
7 ES Earth Switch Closed/Opened I 1
2 CB Circuit Breaker Closed/Opened I 1
RCD 6 LR Local Remote I 1
153
SPLN S3.001: 2008
DB-04
P
Q
V
P
Q
I
L/R
BUSBAR - A
BUSBAR - B
154
SPLN S5.001: 2008
Group
Data No Kode Fungsi Tipe Jmh
Bay
2 BI Bus Isolator Switch Closed/Opened I 2
TSD 4 CB Circuit Breaker Closed/Opened I 1
7 ES Earth Switch Closed/Opened I 1
2 CB Circuit Breaker Closed/Opened I 1
RCD 6 LR Local Remote I 1
4 I Arus 3
7 P Daya aktif 1
TM
9 Q Daya reaktif 1
Generator 10 V Tegangan 1
TSS 56 UT Unit Trip A 1
4 CB Circuit breaker closed/opened I 1
TSD
8 GUC Generator unit run/stop I 1
155
SPLN S3.001: 2008
DB-05
P
Q
V
P
Q
I
L/R
BUSBAR
156
SPLN S5.001: 2008
Group
Data No Kode Fungsi Tipe Jmh
Bay
RCD 6 LR Local Remote I 1
6 LR Local Remote 1
4 I Arus 3
7 P Daya aktif 1
TM
9 Q Daya reaktif 1
Generator 10 V Tegangan 1
TSS 56 UT Unit Trip A 1
4 CB Circuit breaker closed/opened I 1
TSD
8 GUC Generator unit run/stop I 1
157
SPLN S3.001: 2008
DB - 06
FEEDER 20 KV
TYPE 1
I ( R) L/R
I ( S)
I ( T)
P
158
SPLN S5.001: 2008
Group
Data No Kode Fungsi Tipe Jmh
Bay
7 ES Earth Switch Closed/Opened I 1
10 LR Local Remote I 1
12 RR Recloser Reset I 1
1 ARU Auto Recloser Use/Unuse 1
2 CB Circuit Breaker Closed/Opened 1
RCD 6 LR Local Remote 1
8 RR Recloser Reset 1
159
SPLN S3.001: 2008
DB - 07
FEEDER 20 KV
TYPE 2
L/R
I ( R)
I ( S)
I ( T)
P
160
SPLN S5.001: 2008
Group
Data No Kode Fungsi Tipe Jmh
Bay
7 ES Earth Switch Closed/Opened I 1
10 LR Local Remote I 1
11 RACK Circuit Breaker Rackin/Rackout I 1
12 RR Recloser Reset I 1
1 ARU Auto Recloser Use/Unuse 1
2 CB Circuit Breaker Closed/Opened 1
RCD 6 LR Local Remote 1
8 RR Recloser Reset 1
161
SPLN S3.001: 2008
DB - 08
FEEDER 20 KV
TYPE 3
I ( R) L/R
I ( S)
I ( T)
P
162
SPLN S5.001: 2008
Group
Data No Kode Fungsi Tipe Jmh
Bay
7 ES Earth Switch Closed/Opened I 1
10 LR Local Remote I 1
12 RR Recloser Reset I 1
1 ARU Auto Recloser Use/Unuse 1
2 CB Circuit Breaker Closed/Opened 1
RCD 6 LR Local Remote 1
8 RR Recloser Reset 1
163
SPLN S3.001: 2008
DB - 09
BUS SECTION 20 KV
TYPE 1
L/R
164
SPLN S5.001: 2008
DB -10
BUS SECTION 20 KV
TYPE 2
L/R
165
SPLN S3.001: 2008
DB-11: Kopel
DB -11
KOPEL
L/R
166
SPLN S5.001: 2008
DB -12
CAPACITOR BAY
Q L/R
167
SPLN S3.001: 2008
DB -13
SUTM RADIAL
DENGAN KEYPOINT DAN PBO
KP
L/R
I I PBO
168
SPLN S5.001: 2008
169
SPLN S3.001: 2008
DB -14
SUTM RADIAL
DENGAN KEYPOINT TANPA PBO
KP
L/R
I I
170
SPLN S5.001: 2008
DB -15
SUTM LOOP
DENGAN BEBERAPA KP
L/R
I
V
I
L/R
V
L/R
I
V
171
SPLN S3.001: 2008
DB-16: Spindle 20 kV
DB -16
SPINDLE 20 kV
20 kV
GI
Busbar
GD
GT L/R
GD
L/R
GH
172
SPLN S5.001: 2008
10 LR Local Remote I 1
5 LBS Load Break Switch Closed/Opened 1
RCD
6 LR Local Remote 1
173
SPLN S3.001: 2008
174
SPLN S5.001: 2008
STRUKTUR INFORMASI
Struktur informasi terdiri dari 112 karakter yang dapat dikelompokkan menjadi sembilan
bagian, yaitu:
A B C D E F G H I
A. Nomor ID
Nomor ID (bagian A) terdiri dari dua bagian. Bagian A1 terdiri dari 3 digit yang
menyatakan kode area. Bagian A2 terdiri dari 3 digit merupakan nomor RTU
bersangkutan. Nomor ID dinyatakan dengan susunan sebagai berikut
A1 A2
175
SPLN S3.001: 2008
Kode area
Kode area yang terdiri dari 3 karakter adalah sebagai berikut:
NCC : 900
IRCC : x00
IRCC Jawa-Bali : 100
IRCC Sumatera : 200
IRCC Kalimantan : 300
IRCC Sulawesi : 400
IRCC di Indonesia Timur : 500
IDCC : x00
IDCC Jawa-Bali : 100, 200, 300, 400
IDCC Sumatera : 500, 600
IDCC Kalimantan : 700
IDCC Sulawesi : 800
IDCC di Indonesia Timur : 900
176
SPLN S5.001: 2008
B. Time stamp
Struktur informasi yang menggambarkan time stamp atau waktu suatu kejadian terdiri dari
23 karakter. Struktur informasinya berturut-turut terdiri dari tanggal (2 karakter), bulan (2
karakter), tahun (4 karakter), jam (2 karakter), menit (2 karakter), dan detik (6 karakter
atau sampai dengan orde milidetik). Contohnya:
25/04/2007 00:30:35.000
19/11/2007 10:00:05.520
C. Nama GI/GH/GT
Nama GI/GH/GT dituliskan dalam bentuk nama lengkap (maksimal 20 karakter).
Contohnya adalah sebagai berikut:
Cawang
Gandul
Gondang Wetan
Rungkut
Waru
Cawang : menyatakan GI Cawang (dikontrol oleh RCC Cawang).
Gandul : menyatakan GI Gandul (dikontrol oleh RCC Cawang).
Waru : menyatakan GI Waru (dikontrol oleh RCC Waru).
Rungkut : menyatakan GI Rungkut (dikontrol oleh RCC Waru).
Gondang Wetan : menyatakan GI/GH/GT Gondang Wetan (dikontrol oleh DCC
Pasuruan).
D. Level Tegangan
Level tegangan terdiri dari 5 karakter. Contohnya dapat dilihat pada Tabel 2.
Tabel 2. Level tegangan
Tegangan Level Tegangan
500 kV 500
275 kV 275
150 kV 150
70 kV 70
66 kV 66
30 kV 30
25 kV 25
23.5 kV 23
20 kV 20
16.75 kV 16.75
16.5 kV 16.5
13 kV 13
11 kV 11
6 kV 6
177
SPLN S3.001: 2008
Pusat Listrik
Pusat Listrik Tenaga Air PLTA
Pusat Listrik Tenaga Diesel PLTD
Pusat Listrik Tenaga Gas PLTG
Pusat Listrik Tenaga Panas Bumi PLTP
Pusat Listrik Tenaga Nuklir PLTN
Pusat Listrik Tenaga Uap PLTU
Pusat Listrik Gas/Uap (Combine Cycle) PLTGU
Pusat Listrik Tenaga Mikrohidro PLTMH
Pusat Listrik Tenaga Angin/Bayu PLTB
Nama Bay
Bay 500 kV diameter 1 busbar A 7A1
Bay 500 kV diameter 3 antara busbar A 7AB3
dan B
Bay 500 kV diameter 5 busbar B 7B5
Kode tegangan dari primer dan sekunder trafo dapat dilihat pada Tabel 4.
Tabel 4. Kode tegangan dari primer dan sekunder trafo
Tegangan Range Kode
Tegangan Rendah (TR) sampai 1000 V 0
Tegangan Menengah (TM) 1 sampai 10 kV 1
Tegangan Menengah (TM) 10 sampai 30 kV 2
178
SPLN S5.001: 2008
179
SPLN S3.001: 2008
Adi
Lukman
Jufri
Joko
Syafnir
Kuncoro
I. Prioritas Alarm
Prioritas alarm terdiri dari 8 karakter, menunjukkan kelas alarm yang ditampilkan. Class 1
merupakan kelas alarm yang menempati prioritas paling tinggi.
X Y Z
Bagian X: kode referensi tegangan
Bagian Y: kode nama CB
Bagian Z: nomor diameter
Contoh:
A untuk breaker yang terhubung langsung ke busbar A
B untuk breaker yang terhubung langsung ke busbar B
AB untuk breaker yang terhubung ke breaker A dan breaker B
Contohnya dapat dilihat pada Gambar 4 dan Gambar 5.
Untuk tegangan 500 kV diameter no. 1 Untuk tegangan 150 kV diameter no.4
180
SPLN S5.001: 2008
Contoh :
GITET 500 kV
SAGULING
BANDUNG SELATAN 2
BUSBAR A
BUSBAR B
181
SPLN S3.001: 2008
182
SPLN S5.002: 2008
183
SPLN S3.001: 2008
CB CLOSED Busbar
' s color, filled
CB OPENED Busbar
' s color, blank
PBO
PBO CLOSED Feeder’s color
, filled
PBO
PBO OPENED Feeder’s color
, blank
DEAD
184
SPLN S5.002: 2008
WARNA TAMPILAN
Tabel 6 berikut ini menjelaskan mengenai warna tampilan yang berlaku untuk monitor dan
layar tayang.
Tabel 6. Warna tampilan
URAIAN WARNA
Keterangan:
• Untuk change of state gangguan, setelah acknowledge blinking hilang, warna merah
pada frame CB mengikuti warna busbar.
• Untuk level tegangan yang tidak tercantum dalam tabel di atas, menggunakan
warna pada single line diagram level tegangan terdekat.
• Warna jaringan sesuai dengan feeder colouring.
• Untuk detail kode warna akan dijelaskan pada SPLN mengenai kode simbol dan
warna.
185
SPLN S3.001: 2008
Pengelola Standardisasi:
186