Anda di halaman 1dari 4

Disain Upper Structure Mesjid Al Hijrah

Cek Disain Sengkang SMF Kolom K1-70X70 Lantai 3

Data Material :
f'c = 24.9 MPa fy = 420  MPa Ey = 200000 MPa

Ec = 4700 f'c MPa Ec = 23452.953  MPa

Data Dimensi kolom Yang di Disain (K-1.3) :


bc = 700  mm hc = 700  mm

2 1 3 4
Agr = bc h c = 490000 mm Ix =  b c hc = 20008333333.33334  mm
12

Data Dimensi kolom Bawah (K-1.1):

bb = 750  mm hb = 750  mm

2 1 3 4
Agrb = b b h b = 562500 mm Ixb =  b b h b = 26367187500  mm
12

Data Dimensi kolom Atas (K-1.3) :

Tidak ada kolom atas

selimut beton d' = 30 mm

d = h c - d' d = 670  mm

Tinggi kolom : Lk = 6000mm

Data Beban :

Gaya geser akibat goyang ke kiri Balok Atas : M kapnt = 1027.6kN m M kappt = 626.5kN m

Gaya geser akibat goyang ke kiri Balok Bawah : M kapnb = 1249kN m M kappb = 740.5kN m

Faktor distribusi kolom atas : DFt = 1

Ix
Faktor distribusi kolom bawah : DFb = = 0.431442
Ix + Ixb

Gaya geser termobilisasi Kapasitas Balok :

(Mkapnt + Mkappt ) DFt + (Mkapnb + Mkappb)  DFb


Vsw = = 418.742209 kN
Lk

Gaya geser akibat kombinasi 1.2 DL + 1 LL : Vgrav1 = 158  kN

Gaya Geser Total : Vgab = Vsw + Vgrav1 = 576.742209 kN

Sengkang SMF Kolom K1 Lt-3- 1


Disain Upper Structure Mesjid Al Hijrah

Gaya Geser Akibat Beban Kombinasi :

Ve = 144  kN ϕ = 0.75

Vd = max( Vgab , Ve) = 576.742209 kN

Vd
Vn = = 768.989612 kN
ϕ

Gaya aksial terkecil dari kombinasi yang terjadi :

Ntot = 1170 kN

1. Data Tulangan Confinement Zona Lo :


Gunakan diameter sengkang confinement :

Tulangan Hoops : ϕseng1 = 13 mm Tulangan Cross Ties : ϕseng2 = 10 mm

Diameter tulangan longitudinal kolom : ϕlc = 22mm

2 2 2
Luas sengkang pakai : Ascon = 2  0.25 π ϕseng1 + 2  0.25 π ϕseng2 = 422.544212 mm

bcon = b c - 2  ( d' + 0.5 ϕseng1 ) = 627  mm

Ach = ( b c - 2  d')  ( h c - 2  d') = 409600 mm


2

2
  b c f'c   Agr  0.09 bc f'c mm
Luas sengkang butuh/spasi : Acon = max0.3  
 - 1  ,  = 3.735
  fy   Ach  fy  mm

 350mm -   b c 
2
1  3   100mm = 100  mm
Spmaxcon = 100mm if min  b c , 6  ϕlc , 100mm + 
4 3 
 350mm -   b c 
2
1  3   otherwise
min  b c , 6  ϕlc , 100mm +
 4 3 
Spasi dipakai : Scon = 100mm

2
Luas sengkang butuh : Acond = Acon  Scon = 373.5 mm

Catatan1 = "Tulangan Terpasang Ok !" if Ascon  Acond = "Tulangan Terpasang Ok !"


"Tulangan Terpasang Tidak OK!" otherwise

Panjang area pemasangan tulangan Hoop + Cross Ties Confinement :

Lhoop = max d ,  Lk , 500mm = 1000 mm


1
 6 

Sengkang SMF Kolom K1 Lt-3- 2


Disain Upper Structure Mesjid Al Hijrah

2. Cek Sengkang Hoops Untuk Kebutuhan Geser dalam zona Confinement :

Sumbangan kuat geser beton :

Vc =  1   f'  MPa b  d = 390.050883 kN


  c c (Kuat Geser Beton)
6
Agr f'c
Vcdis = 0.25 Vc if Vsw > 0.5 Vn  Ntot < = 97.512721  kN (Kuat Geser Disain Beton
20 Zona Sendi Plastis)
Vc otherwise

2
Vsmax =  bc d  f'c MPa = 1560.203534  kN
3

ϕVcdis = ϕ Vcdis = 73.134541  kN

Vmin = 0.5 ϕ Vcdis = 36.56727 kN

syarat1 = "Perlu sengkang" if Vn  Vmin = "Perlu sengkang"


"Tidak Perlu sengkang" otherwise

Gaya yang dipikul sengkang : Vs1 = Vn - Vcdis = 671.476891 kN

Catatan2 = "Perbesar penampang, gaya geser terlalu besar !" if Vs1 > Vsmax
"Penampang cukup untuk menahan gaya geser !" otherwise

Catatan2 = "Penampang cukup untuk menahan gaya geser !"

Spamax1 = min( 150mm , 6  ϕlc) = 132  mm

Spasi sengkang butuh untuk menahan geser :

Ascon  fy d
Sps1 = = 177.078233 mm
Vs1

Ascon  fy d
Spa1 = Spamax1 if 0 = 132  mm
Vs1

 Ascon  fy d 
min Spamax1 ,  otherwise
 Vs1 
Catatan3 = "Spasi Tulangan Confinement Memenuhi Syarat Geser" if Scon  Spamax1
"Spasi Tulangan Confinement Tidak memenuhi syarat Geser" otherwise

Catatan3 = "Spasi Tulangan Confinement Memenuhi Syarat Geser"

SLo = min( Scon , Spa1 ) = 100  mm

Pakai sengkang di zona confinement : D13-100 + 2 D10-100

Sengkang SMF Kolom K1 Lt-3- 3


Disain Upper Structure Mesjid Al Hijrah

3. Cek Sengkang diluar zona Confinement :

Sumbangan kuat geser beton :

 Ntot   f'c MPa 


1
Vckol =  1 +     ( b c)  ( d ) = 456.575597 kN
 14 Agr MPa   6 
0.3 Ntot 1
Vckolmax = 0.3 f'c MPa  bc d  1 +  = 919.800685 kN
Agr MPa

Vcdis2 = Vckol if Vckol < Vckolmax = 456.575597 kN


Vckolmax otherwise

2
Vsmax2 =  b c d  f'c MPa = 1560.203534  kN
3

ϕVcdis2 = ϕ Vcdis2 = 342.431698 kN

Vmin2 = 0.5 ϕ Vcdis2 = 171.215849 kN

syarat1 = "Perlu sengkang" if Vn  Vmin2 = "Perlu sengkang"


"Tidak Perlu sengkang" otherwise

Gaya yang dipikul sengkang : Vs2 = Vn - Vcdis2 = 312.414015 kN

Catatan1 = "Perbesar penampang, gaya geser terlalu besar !" if Vs2 > Vsmax
"Penampang cukup untuk menahan gaya geser !" otherwise

Catatan1 = "Penampang cukup untuk menahan gaya geser !"

Gunakan diameter sengkang : ϕseng3 = 10mm

2 2
Aseng3 = 2 0.25 π ϕseng3 = 157.079633 mm

 3  Aseng3  fy 16 Aseng3  fy  1


Spamax2 = min , , 0.5d  if Vs2   b c d f'c MPa = 282.743339 mm
 b c MPa bc f'c MPa  3

0.25 d otherwise

Spasi sengkang butuh :

Aseng3  fy d
Spa2 = = 141.485998 mm
Vs2

Spasi pakai :

Suse2 = Spamax2 if Spa2 < 0 = 141.485998 mm


min( Spamax2 , Spa2 ) otherwise

Jarak sengkang pakai : 10 - 150 mm


D10

Sengkang SMF Kolom K1 Lt-3- 4