CHECK LIST KALIBRASI FQI Tag.

P INPUT FLOW COMPUTER ELLIOT MODEL 4024 SKID NO


T REF.ELLIOT MANUAL PAGE 33-38 for discussion please contact amir@ept.co.id TANGGAL
Tujuan Kalibrasi INPUT FlowComputer (FloCom) : agar indikasi FloCom sama dengan penunjukan Calibrator.
STEP ACTION DIKALIBRASI

1 PERSIAPAN KALIBRASI, Power FloCom: OFF OLEH:

2 PERSIAPAN KALIBRASI PRESSURE INPUT SETELAH SELESAI KALIBRASI FLOCOM


1.Lepas kabel dari Meter Transmitter Pressure ke Elliot TB1 Term.1(=1A+) HARUS KELUAR DARI POSISI DIAG.MODE.
dan Term 2 (=1A-). Gantikan dengan Term + dan - dari Signal injeksi dari 1.Switch Keyboard Entry posisikan : ON.
Calibrator 4-20 MA. 2.Tekan Tombol SKP,sampai muncul display:
CATATAN: Untuk Kalibrasi Input FloCom dari Transmitter lain , sambungan Press Enter Key to Exit Diagnostic Mode.
Terminasinya lihat Copy Manual PAGE : 15 s/d 19. 3.Tekan Tombol ENT.
2.Injeksi Kalibrator siapkan dengan signal 4.0 MA. 4.Switch Keyboard Entry posisikan OFF.
3.HIDUPKAN POWER FLOCOM, Switch: ON. 5.SUSUNAN KEYBOARD DEPAN NORMAL
3 POSISIKAN FLOCOM PADA: DIAGNOSTIC MODE, Dengan Cara sbb: KEMBALI DAN FLOCOM SIAP
TARIK FLOCOM DAN LIHAT KEYBOARD ENTRY. DIOPERASIKAN.
1.Switch pada Keyboard Entry posisikan : ON
2.Tekan Tombol SKP
3.Ketik 1111, enter (= security code entry).
4.Tekan Tombol ENT.
5.Switch Keyboard Entry butir 1, posisikan OFF. NILAI NILAI NOTE
6.SUSUNAN KEYBOARD DEPAN ELLIOT BERUBAH MENJADI PAGE 34. EXISTING CALIBRATED
4 PROSES KALIBRASI FLOCOM DIMULAI:
1.KALIBRASI METER PRESSURE INPUT ( = TB1 Term.1A ) .
a.Tombol Input 1A,1B,2A,2B, lihat Display input tsb.
b.Signal Calibrator posisikan 4.0 MA, Display Elliot 1A existing = ? 1000 4.0MA=1000Hz
c. " " " 20 MA, " " " =? 5000 adjust potentio

d. " " " 12 MA " " " =? 3000 meter press.card

2.KALIBRASI METER TEMPERATURE INPUT (= TB1 Term.3A) page:17.

a.Tombol Input 3A,3B,4A,4B, lihat Display input tsb.


b.Signal Calibrator posisikan 4.0 MA, Display Elliot 3A existing = ? 1000 4.0MA=1000Hz

c. " " " 20 MA, " " " =? 5000 adjust potentio

d. " " " 12 MA " " " =? 3000 meter temp.card

3.KALIBRASI PROVER PRESSURE INPUT 1 (=TB3 Term.2A) page:17.

a.Tombol Input 1A,1B,2A,2B, lihat Display input tsb.


b.Signal Calibrator posisikan 4.0 MA, Display Elliot 2A existing = ? 1000 4.0MA=1000Hz

c. " " " 20 MA, " " " =? 5000 adjust potentio

d. " " " 12 MA " " " =? 3000 prover.card

4.KALIBRASI PROVER PRESSURE INPUT 2 (=TB4 Term.2B). page:17.

a.Tombol Input 1A,1B,2A,2B, lihat Display input tsb.


b.Signal Calibrator posisikan 4.0 MA, Display Elliot 2B existing = ? 1000 4.0MA=1000Hz

c. " " " 20 MA, " " " =? 5000 adjust potentio

d. " " " 12 MA " " " =? 3000 prov. press.card

5.KALIBRASI PROVER TEMPERATURE INPUT 1 (=TB1 Term.5) page:17.

a.Tombol Input 5,6 lihat Display input tsb.


b.Signal Calibrator posisikan 4.0 MA, Display Elliot 5 existing = ? 1000 4.0MA=1000Hz

c. " " " 20 MA, " " " =? 5000 adjust potentio

d. " " " 12 MA " " " =? 3000 prov.temp.card

6.KALIBRASI PROVER TEMPERATURE INPUT 2 (TB2 Term.6) page:17.


b.Signal Calibrator posisikan 4.0 MA, Display Elliot 5 existing = ? 1000 4.0MA=1000Hz

c. " " " 20 MA, " " " =? 5000 adjust potentio

d. " " " 12 MA " " " =? 3000 prov.temp.card