INTRO
 Electrical Cable Sizing dipersiapkan oleh
seorang Electrical Engineer untuk
menentukan ukuran kabel yang tepat
sesuai dengan kebutuhan load, jarak,
instalasi dan jenis kabel.
www.paulrumahorbo.com

SOURCE
Dalam mempersiapkan Cable Sizing, seorang
Electrical Engineer membutuhkan data:
 Layout: Dari layout akan didapatkan jarak
dari load ke panel sumber, instalasi tanah
atau udara, dll
 Load: Berapa amper beban yang akan di-
sizing, Power Factor, LRC (IS)dll
 Power System: short circuit rating, CB rating,
cable catalogue, dll
www.paulrumahorbo.com

STANDARD
 IEC 60287-1-2-3: Electric cables – calculation of the
current rating
 IEC 60364-5-523: Selection and Erection of Electrical
Equipment and Current-Carrying Capacities in wiring
 IEC 228_1978: Conductor of Insulated Cables
 IEC 60287: Electric cables – Calculation of the current
rating
 IEC 60092-352: Electrical Installation in Ships, Part 352:
Choice and Installation of Electrical Cable
 IEC 60949: Calculation of thermally permissible short
circuit currents
 IEC 60947-2: LV Switchgear and Control Gear –
Circuit Breaker
www.paulrumahorbo.com

CALCULATION METHOD
 Voltage Drop yang diijinkan
 Arus beban penuh (Full Load Current)
 Cable Ampacity
 Derating Factor (terhadap temperatur
dan pemasangan kabel)
 Short Circuit Current
www.paulrumahorbo.com

VOLTAGE DROP
 Voltage Drop 3 Phasa:
L 100 % 1
VD %  I LF  R cos   X sin    
1000 V / 3 N
 Voltage Drop 1 Phasa:
L 100% 2
VD %  I LF  R cos   X sin    
1000 V N
 Voltage Drop DC
L 100 % 2
VD %  I LF  RDC   
1000 V N
www.paulrumahorbo.com

VOLTAGE DROP
Dimana:
 VD% = Rugi-rugi Tegangan (%)
 ILF = Arus Beban Penuh (Ampere)
 R = Resistansi AC pada temperatur kabel
90ºC (/km)
 RDC = Resistansi DC pada temperatur kabel
20ºC (/km)
 X = Reaktansi (/Km)
  = Faktor Daya
 L = Panjang Kabel (km)
 V = Tegangan
 N = Jumlah tarikan kabel secara parallel
www.paulrumahorbo.com

VOLTAGE DROP
Maksimum rugi-rugi tegangan yang diijinkan
adalah sebagai berikut :
 Untuk Busbar Switchgear/MCC 2%
 Untuk Busbar penerangan 3%
 Untuk motor keadaan stabil (Pada Terminal
Motor) 5%
 Untuk motor selama starting (Pada
Terminal Motor) 15%
 Untuk penyulang Distribution Panel (DP) 2%
www.paulrumahorbo.com

SHORT CIRCUIT CURRENT


 Kapasitas hubung singkat kabel
K x S x n
I SC 
Dimana: t
 Isc = Kemampuan kabel hubung singkat (kA)
 K = konstanta 143 untuk kabel XLPE ( IEC 60364-
4-43 ). 115 untuk kabel PVC ≤300 sqmm, 103 >300
sqmm.
 S = Diameter Penghantar (mm²)
 t = breaker clearing time dalam detik (0.05 for
AC & 0.1 for DC)
 n = Jumlah tarikan kabel secara paralel
www.paulrumahorbo.com

SHORT CIRCUIT CURRENT


 Arus gangguan pada ujung kabel
V
I LF 
3xZT
Dimana:
V = Tegangan Nominal
 ZT = Total Impedansi (Zbus+Zcable)

ZT  Z BUS  ZCABLE

V  R x L 2
  X x L 
2

      
3 x I SC  n x 1000   n x 1000
 

 
BUS
 
www.paulrumahorbo.com

DERATING FACTOR (K1)


 Temperature (IEC 364-5-523)
Ambient Insulation
temperature XLPE and
PVC
(oC) EPR

10 1.22 1.15
15 1.17 1.12
25 1.12 1.08
30 1.06 1.04
35 0.94 0.96
40 0.87 0.91
45 0.79 0.87
50 0.71 0.82
55 0.61 0.76
60 0.5 0.71
65 - 0.65
70 - 0.58
75 - 0.5
80 - 0.41
www.paulrumahorbo.com

DERATING FACTOR (K2)


 Cable Laying in Air (IEC 364-5-523)
Number Number of Cables
Method of Installation
of Tray 1 2 3 4 6 9
Touching 1 1 0.88 0.82 0.76 0.73 0.73
and 2 1.00 0.87 0.8 0.73 0.66 0.68
Perforated Tray Multicore 3 1.00 0.86 0.79 0.71 0.66 0.66

(Horizontal) Spaced 1 1.00 1.00 0.98 0.95 0.91 -


> 20 mm 2 1.00 0.99 0.96 0.92 0.87 -
3 1.00 0.98 0.95 0.91 0.85 -

Touching 1 1.00 0.88 0.82 0.78 0.73 0.72


and 2 1.00 0.88 0.81 0.76 0.71 0.7
Perforated Tray Multicore

(Vertical) Spaced 1 1.00 0.91 0.89 0.88 0.87 -


> 225
mm 2 1.00 0.91 0.88 0.87 0.85 -

Touching 1 1.00 0.87 0.82 0.8 0.79 0.78


and 2 1.00 0.86 0.8 0.78 0.76 0.73
Ladder Multicore 3 1.00 0.85 0.79 0.76 0.73 0.7

(Horizontal) Spaced 1 1.00 1.00 1.00 1.00 1.00 -


> 20 mm 2 1.00 0.99 0.98 0.97 0.96 -
3 1.00 0.98 0.97 0.96 0.93 -
www.paulrumahorbo.com

DERATING FACTOR (K2)


 Cable Laying Direct Buried (IIEC 364-5-
523)
Cable to Cable Clearance

Number of Circuit Nil (Cable One Cable


0.125m 0.25m 0.5m
Touching) Diameter

2 0.75 0.8 0.85 0.9 0.9


3 0.65 0.7 0.75 0.8 0.85
4 0.6 0.6 0.7 0.75 0.8
5 0.55 0.55 0.65 0.7 0.8
6 0.5 0.55 0.6 0.7 0.8
www.paulrumahorbo.com

CABLE DATA STANDARD RESISTANCE & REACTANCE (Extracted From Kabel Metal Indo)
4 CORE CONDUCTOR 0.6/1 KV (Copper Conductor, XLPE Insulated, Galvanized Steel Wire Armor,
PVC SHEATHED)

Cross DC AC Reactance Maximum Maximum


Section Resistance Resistance at 50 Hz Rated Current Rated Current Inductance
No. mm2 at 20oC at 90oC in Air in Ground
(ohm/km) (ohm/km) (ohm/km) (Ampere) (Ampere) ( mH / km )

1 4C #2.5 7.410 9.449 0.0921 37.00 43.00 0.293


2 4C #4 4.610 5.878 0.0864 49.00 55.00 0.275
3 4C #6 3.080 3.927 0.0827 63.00 69.00 0.263
4 4C #10 1.830 2.334 0.0779 86.00 92.00 0.248
5 4C #16 1.150 1.467 0.0748 115.00 120.00 0.238
6 4C #25 0.727 0.927 0.0754 154.00 155.00 0.240
7 4C #35 0.524 0.669 0.0732 189.00 185.00 0.233
8 4C #50 0.387 0.494 0.0729 220.00 212.00 0.232
9 4C #70 0.268 0.342 0.0720 277.00 258.00 0.229
10 4C #95 0.193 0.247 0.0704 339.00 309.00 0.224
11 4C #120 0.153 0.196 0.0701 394.00 350.00 0.223
12 4C #150 0.124 0.160 0.0704 455.00 395.00 0.224
13 4C #185 0.0991 0.128 0.0707 516.00 442.00 0.225
14 4C #240 0.0754 0.099 0.0701 605.00 506.00 0.223
15 4C #300 0.0601 0.080 0.0695 687.00 565.00 0.221
www.paulrumahorbo.com

CONTOH
 Data

Tag. No K01 Air Compressor

No. Kabel P-K01 Panjang Kabel 50 meter

Kapasitas 7.5 kW, PF=0. 7, Eff=0.85 Allow. Voltage Drop dalam


keadaan Steady State 5%

Tegangan 400 Allowable Voltafe Drop saat


motor starting
Jalur Kabel Dari MCC
15%
www.paulrumahorbo.com

CONTOH
1. Menentukan Ukuran Kabel
P
IL  IL= 18.19 Ampere
3 x V n x pf x eff

2. Memilih kabel 4x2.5 mm2


I Z  I t x k1 x k 2 x n
I Z  37 x 0 . 96 x 0 . 78 x1 IZ= 27.71 Ampere
www.paulrumahorbo.com

CONTOH
3. Voltage Drop
o Motor Steady State
L 100 % 1
VD %  I L  R cos   X sin     
1000 V / 3 n
VD %  18 . 19  9 . 449 x 0 . 85  0 . 0921 x 0 . 527 
50 100 % 1
 
1000 400 / 3 1
VD %  2 . 63 %

o Motor Starting
L 100 % 1 IS=IL x 6.7
VD %  I S  R cos   X sin      Cos  = 0.5
1000 V / 3 n
VD %  12 . 68 %
www.paulrumahorbo.com

CONTOH
4. Kemampuan Hubung Singkat
o Kabel Hubung Singkat
K x S x n 143 x 2.5 x 1
I SC  I SC  I SC  1.5kA
t 0.05
(K = 143 , untuk insulasi kabel XLPE, 103 untuk PVC, sesuai tabel 43A
standard IEC 60364-4-43)

o Load end short circuit fault current (ILF) :


V 400  9.449 x50  2  0.0921x50  2 
I LF  ZT       
3 xZ T 3 x 45000  1x1000   1 x1000  

400
I LF  I LF  0.48kA ILF < ISC
3 xZT
www.paulrumahorbo.com

KESIMPULAN
 Setelah
melakukan 4 tahapan kalkulasi
maka kabel 4x2.5 mm2 dapat digunakan
untuk beban K01 - Air Compressor
www.paulrumahorbo.com

TUGAS
Tag No kW Length & Insulation
Installation
K02 7.5 50 M, Air XLPE
UPS 10 50 M, Air PVC
PDB-01 10 30 M, Air PVC
LDB-01 5 50 M, Air PVC
P-001 45 70 M, Ground XLPE
P-002 18.5 70 M, Ground XLPE
P-003 7.5 60 M, Ground XLPE
P-004 15 80 M, Ground XLPE
P-005 0.55 50 M, Air XLPE
P-006 30 40 M, Ground XLPE
P-007 30 150 M, Ground XLPE