Anda di halaman 1dari 8

Pengadaan Barang/Jasa

Pekerjaan Relokasi Pembangkit ke Halmahera Timur

DESIGN CALCULATION OF VENTILATION AND


AIR CONDITIONING SYSTEM

02 20/09/22 FOR APPROVAL TAK RSY KRS


01 08/09/22 FOR APPROVAL TAK RSY KRS
00 18/07/22 FOR APPROVAL DDE / TAK RSY KRS
REV DATE DESCRIPTION PREP CHECK APPROVAL

PT. PEMBANGKITAN JAWA BALI


CONSULTANT :

OWNER’S DWG NO :

CONTRACTOR :

PROJECT :
PENGADAAN BARANG / JASA
PEKERJAAN RELOKASI PEMBANGKIT KE HALMAHERA TIMUR

VENDOR :

DATE SIGNATURE SCALE SHEET OF


DRAWN 20/09/2022 –
NONE 8
JOB NO 225809
DOC NO 225809 -00-M-04-SAM-001 REV 02
INT REV 02A
DESIGN CALCULATION OF JOB NO : 225809 REV

VENTILATION AND DOC NO : 225809-00-M-04-SAM-001


02

AIR CONDITIONING SYSTEM


DATE BY CHKD APVD
20 / 09 / 2022 TAK RSY KRS

REVISION HISTORICAL SHEET

Rev No Date Description

00 18 / 07 / 2022 ISSUED FOR APPROVAL


01 08 / 09 / 2022 ISSUED FOR APPROVAL
02 20 / 09 / 2022 ISSUED FOR APPROVAL

P T. R E K A D A Y A E L E K T R I K A
DESIGN CALCULATION OF JOB NO : 225809 REV

VENTILATION AND DOC NO : 225809-00-M-04-SAM-001


02

AIR CONDITIONING SYSTEM


DATE BY CHKD APVD
20 / 09 / 2022 TAK RSY KRS

CONTENTS

PAGE

1. KONSEP PERHITUNGAN SISTEM VAC 4

2. CONTOH PERHITUNGAN KEBUTUHAN SISTEM VAC 5

3. REFERENSI 6

P T. R E K A D A Y A E L E K T R I K A
DESIGN CALCULATION OF JOB NO : 225809 REV

VENTILATION AND DOC NO : 225809-00-M-04-SAM-001


02

AIR CONDITIONING SYSTEM


DATE BY CHKD APVD
20 / 09 / 2022 TAK RSY KRS

1. KONSEP PERHITUNGAN SISTEM VAC


a) Perhitungan untuk perangkat AC Split
Perhitungan dapat menggunakan persamaan :
𝑝 × 𝑙 × 12000
𝑄=
𝐶

Dimana :
Q = Beban pendingin (Btu/h)
p = Dimensi panjang ruangan (m)
l = Dimensi lebar ruangan (m)
C = Konstanta beban pendingin untuk ruangan (m2/TR)
12000 = Konversi dari TR (Tons of refrigeration to Btu/h)

Dimana nilai C dapat diperoleh dari handbook HVAC equation chapter 6 cooling load rules of thumb
sebagai berikut :
Nilai Konstanta
Jenis Ruangan C (ft2/TR) C (m2/TR)
Ruangan komputer/panel 400 14
Ruangan kantor 150 37

Nilai beban pendingin yang didapat kemudian digunakan untuk menentukan perangkat pendingin yang
akan digunakan sesuai ketersediaan equipment.

b) Perhitungan untuk perangkat Exhaust Fan


Perhitungan dapat menggunakan persamaan :
𝑄 = 𝑝 × 𝑙 × 𝑡 × 𝐴𝐶𝐻
Dimana :
Q = Beban pendingin (m3/h)
p = Dimensi panjang ruangan (m)
l = Dimensi lebar ruangan (m)
t = Dimensi tinggi ruangan (m)
ACH = Besaran sirkulasi udara untuk ruangan (/h)

P T. R E K A D A Y A E L E K T R I K A
DESIGN CALCULATION OF JOB NO : 225809 REV

VENTILATION AND DOC NO : 225809-00-M-04-SAM-001


02

AIR CONDITIONING SYSTEM


DATE BY CHKD APVD
20 / 09 / 2022 TAK RSY KRS

Nilai ACH berdasarkan proyek referensi yang telah dilaksanakan oleh PT RE yaitu kontrak PLTU Sofifi.
Dimana nilai ACH dapat diperoleh dengan pemilihan sebagai berikut :
- Maintenance room/shop 10 – 15
- Office area 2
- Toilet/shower/locker 10
- Laboratory 20
- Machine room 20
- Ware house 5
- Battery room/rectifier room 15
- Chemical storage/plant 10
- Turbine hall 12
- Other supporting building 5

2. CONTOH PERHITUNGAN KEBUTUHAN SISTEM VAC


a) Perhitungan AC split
Input data :
Ruangan : Guard house room
Dimensi : Panjang = 4 meter
Lebar = 4 meter
C = 37

Perhitungan :Q =

= 5189 btu/h
Dimana pemilihan kapasitas AC dapat mengikuti list berikut :
Equipment Availibility
Daya (pk) Capacity (Btu/h) Tipe
0,5 5000 Split, Wall Mounted
1 9000 Split, Wall Mounted
2 17500 Split, Wall Mounted
3 24000 Split, Wall Mounted

Untuk kebutuhan pendinginan ruangan 2500 Btu/h menggunakan AC split daya 1 pk sebanyak 1 pcs.

P T. R E K A D A Y A E L E K T R I K A
DESIGN CALCULATION OF JOB NO : 225809 REV

VENTILATION AND DOC NO : 225809-00-M-04-SAM-001


02

AIR CONDITIONING SYSTEM


DATE BY CHKD APVD
20 / 09 / 2022 TAK RSY KRS

b) Perhitungan Exhaust Fan


Input data :
Ruangan : Guard house toilet
Dimensi : Panjang = 1,5 meter
Lebar = 1,5 meter
Tinggi = 3 meter
ACH = 10
Perhitungan :Q = 1,5 × 1,5 × 3 × 10
= 68 m3/h

Untuk kebutuhan pendinginan ruangan 68 m3/h dapat dipilih kapasitas fan 100 m3/h sebanyak 1 pcs.

3. REFERENSI
 Bell, Arthur A.2007. HVAC Equations, Data, and Rules of Thumb. 2nd Edition.New York, America
:McGraw-Hill.

P T. R E K A D A Y A E L E K T R I K A
AIR CONDITIONING CALCULATION SHEET
No. Document 225809-00-M-04-SAM-001 Revision No. 00 01 02
Project Name PENGADAAN BARANG/JASA PEKERJAAN RELOKASI Date 18/07/2022 09/092022 20/09/2022
PEMBANGKIT KE HALMAHERA TIMUR Prepared By DDE/TAK TAK TAK
Checked By RSY RSY RSY
Approved By KRS KRS KRS
Total Cooling Equipment Equipment
Panjang Lebar Konstanta (C)
No Nama Ruangan Load pk Capacity Quantity
(m) (m) (m2/TR) (Btu/h) (Btu/h) (pcs)
1 CCR & Switch Gear Building
CCR & Switch Gear room 20 8 14 137143 3 24000 6
AC/DC Room 6 4 14 20571 2 17500 2
Meeting Room 4 4 37 5189 1 9000 1
Operator Room 4 9 37 11676 1 9000 2
Battery room 6 4 14 20571 2 17500 2

2 Admin Building
Office Room 5 9
37 38919 2 17500 3
5 15
Manager Room 1 5 3 37 4865 1 9000 1
Manager Room 2 5 3 37 4865 1 9000 1
Meeting Room 1 7 3,5 37 7946 1 9000 1
Meeting Room 2 5 4 37 6486 1 9000 1
Lobby + koridor 6 5
37 14595 2 17500 1
10 1,5
Mushola 2,5 3 37 2432 1 9000 1

3 Guard House
Office 4 4 37 5189 1 9000 1

4 Mosque
Mosque 9 9,25
37 28703 2 17500 2
3 1,75

5 Workshop, Warehouse & Laboratory


Operational room 8 6 37 15568 1 9000 2
Laboratory 6 6 14 30857 2 17500 2
Operator room 4 6 37 7784 1 9000 1

6 MCC ROOM
MCC Room 8,4 5,4 14 38880 2 17500 3

Equipment Availibility
Daya (pk) CAPACITY (BTU/H) TIPE
1 9000 Split, Wall Mounted
2 17500 Split, Wall Mounted
3 24000 Split, Wall Mounted

Nilai Konstanta
Jenis Ruangan C (ft2/TR) C (m2/TR)

Ruangan komputer/panel 150 14

Ruangan kantor 400 37


FAN CALCULATION SHEET
No. Document 225809-00-M-04-SAM-001 Revision No. 00 01 02
Project Name PENGADAAN BARANG/JASA PEKERJAAN RELOKASI Date 18/07/2022 09/092022 20/09/2022
PEMBANGKIT KE HALMAHERA TIMUR Prepared By DDE/TAK TAK TAK
Checked By RSY RSY RSY
Approved By KRS KRS KRS

Air Changes per Total Flow Fan operating Equipment


Panjang Lebar Tinggi
No Bangunan Hour needed flow rate Quantity
(m) (m) (m) (/h) m3/h m3/h (pcs)
1 CCR & Switchgear Building
Toilet & kitchen 4 4 4 10 640 700 1
Battery room 6 4 4 15 1440 1500 1
Locker room 3 4 4 10 480 500 1

2 Admin Building
Pantry 2,5 2,5 4 10 250 300 1
Toilet Pria 5 2,5 4 10 500 600 1
Toilet Wanta 2,5 3,75 4 10 375 400 1
File room 5 3 4 10 600 650 1
R. wudhu 2 2,5 4 10 200 300 1

3 Guard House
Toilet 1,5 1,5 3 10 68 100 1

4 Mosque
Men toilet 5 3,5 3 10 525 550 1
women toilet 5 3,5 3 10 525 550 1

5 Workshop, WareHouse & Laboratory


Workshop & warehouse 12 12 4
5 3600 2000 4
6 6 4
Toilet 4 2 4 10 320 350 1

6 EDG room 8 4,5 4 20 2880 1000 3

7 Pump house & Filter 10 micron 12 8 4 20 7680 2000 4

TOTAL

MINIMUM AIR CHANGES PER HOUR MINIMUM AIR CHANGES PER HOUR
- Maintenance room/shop 10 – 15 - Ware house 5
- Office area 2 - Battery room/rectifier room 15
- Toilet/shower/locker 10 - Chemical storage/plant 10
- Laboratory 20 - Turbine hall 12
- Machine room 20 - Other supporting building 5