Sistem retikulasi bermula dari punca air bersih sehinggalah kepada pengguna.
Booster
Pumping Station
Distribution
Clear Mains
Water
Tank
Customers
Storage
Reservoir
Reticulation System
Water Treatment
Plant Customers
nurtechnologies@wordpress.com Page 1
Water Academy SAJHSB PELAN DAN REKABENTUK
Gravity Flow
Supply Source
Gravity Flow
Treatment Plant
Gravity Flow
Reservoir
Service Area
Pumped Flow
Service Area
Booster Station
Pumped Flow
Treatment Plant
Supply Source
Pumped Flow
Gravity Flow
Reservoir
Pumped Flow
Booster Station
Treatment Plant
Service Area
Booster Station
Supply Source
(c) GRAVITY AND PUMPED COMBINATION
nurtechnologies@wordpress.com Page 2
Water Academy SAJHSB PELAN DAN REKABENTUK
Keperluan air yang diperlukan dari sistem bekalan air adalah terbahagi
kepada enam (6) jenis iaitu:-
nurtechnologies@wordpress.com Page 3
Water Academy SAJHSB PELAN DAN REKABENTUK
Q2
Q1 Q3
Q4
Q1 + Q2 = Q3 + Q4
L V2
Darcy Weisbach, hL 4 f
D 2g
10.69 LQ 1.852
Hazen Williams, hL
C 1.852 D 4.87
f = friction factor
hL = head loss (m)
L = pipe length (m)
Q = flow rate (m3/s)
C = Hazen Williams pipe roughness coefficient
D = pipe diameter (m)
nurtechnologies@wordpress.com Page 4
Water Academy SAJHSB PELAN DAN REKABENTUK
hL1 hL 4 hL 3 hL 2 0
nurtechnologies@wordpress.com Page 5
Water Academy SAJHSB PELAN DAN REKABENTUK
Qbaru = Qlama + Q
hLi
Q
dh
L
dQ i
hL
Q
2ri Qi
nurtechnologies@wordpress.com Page 6
Water Academy SAJHSB PELAN DAN REKABENTUK
nurtechnologies@wordpress.com Page 7
Water Academy SAJHSB PELAN DAN REKABENTUK
- Atau turus minima adalah 7.6m (25 kaki) diatas aras tanah
tertinggi. Keperluan ini hanya terhad kepada bangunan yang tidak
mempunyai tangki simpanan sahaja atau penggunaan air secara
terus tanpa tangki.
- Turus maksima ialah 61m.
nurtechnologies@wordpress.com Page 8
Water Academy SAJHSB PELAN DAN REKABENTUK
Large buildings,
shopping complexes,
high rise buildings,
large industrial estate,
warehouse and ports.
Shop house up to 3
storey, light industry
Class D Risk
1140 120-terrace 1
Residential terrace 150-detached /
house, detached, semi semi detached
detached
Class E Risk
nurtechnologies@wordpress.com Page 9
Water Academy SAJHSB PELAN DAN REKABENTUK
nurtechnologies@wordpress.com Page 10
Water Academy SAJHSB PELAN DAN REKABENTUK
nurtechnologies@wordpress.com Page 11
Water Academy SAJHSB PELAN DAN REKABENTUK
nurtechnologies@wordpress.com Page 12
Water Academy SAJHSB PELAN DAN REKABENTUK
Average Flow Peak Flow Rate Calculation = Average Flow Rate x Peak Factor
Node Rate Average Flow Peak Flow Rate
(liter/s) Peak Factor
(liter/s) (liter/s)
1 0.8137 2.5 0.8137 2.0341
2 0.3148 2.5 0.3148 0.7870
3 0.3148 2.5 0.3148 0.7870
Average Flow Fire Flow Rate Calculation = Average Flow Rate + Hydrant Flow
Node Rate Average Flow (liter/s) Hydrant Flow Fire Flow Rate
(liter/s) (liter/s) (liter/s)
1 0.8137 0.8137 0.8137
2 0.3148 0.3148 19.0000 19.3148
3 0.3148 0.3148 0.3148
* Based on MWA requirement: One hydrant flow (Class D Risk) = 1140 liter/minute or 19 liter/s
nurtechnologies@wordpress.com Page 13
Water Academy SAJHSB PELAN DAN REKABENTUK
nurtechnologies@wordpress.com Page 14
Water Academy SAJHSB PELAN DAN REKABENTUK
nurtechnologies@wordpress.com Page 15
Water Academy SAJHSB PELAN DAN REKABENTUK
10.69 LQ1.852
hL (1)
C 1.852 D 4.87
10.69(1000)(0.0020)1.852
hL (1)
(130)1.852 (0.2) 4.87
0.1107
hL (1)
3.2437
hL (1) 0.0341 m
Halaju air, V;
Q1
V1
A
0.0020
V1 2
0 .2
2
V1 0.0647 m/s < 2.6m/s (Mematuhi keperluan MWA)
P0 V02 P V2
z 0 1 1 Z 1 hL
2g 2g
P1 P0 V02 V12
Z0 Z 1 hL
2g 2g
P1
28 0 20
0.0647
2
27 0.0341
2g
P1
20.966 m > 13.7m (Mematuhi tekanan min. bangunan 2 tingkat)
nurtechnologies@wordpress.com Page 16
Water Academy SAJHSB PELAN DAN REKABENTUK
10.69 LQ1.852
hL ( 2 ) 1.852 4.87
C D
10.69(800)(0.0008)1.852
hL ( 2 )
(120)1.852 (0.15) 4.87
0.0153
hL ( 2 )
0.689
hL ( 2 ) 0.022 m
Halaju air, V;
Q2
V2
A
0.0008
V2 2
0.15
2
V2 0.0445 m/s < 2.6m/s (Mematuhi keperluan MWA)
P1 V12 P V2
z1 2 2 Z 2 hL
2g 2g
P2 P1 V12 V22
Z1 Z 2 hL
2g 2g
P2
20.966
0.0647
2
27
0.0445
2
18 0.022
2g 2g
P2
29.944 m > 10.7m (Mematuhi tekanan min. bangunan 1 tingkat)
nurtechnologies@wordpress.com Page 17
Water Academy SAJHSB PELAN DAN REKABENTUK
10.69 LQ1.852
hL ( 3 ) 1.852 4.87
C D
10.69(800)(0.0008)1.852
hL ( 3)
(120)1.852 (0.15) 4.87
0.0153
hL ( 3 )
0.689
hL (3) 0.022 m
Halaju air, V;
Q3
V3
A
0.0008
V3 2
0.15
2
V3 0.0445 m/s < 2.6m/s (Mematuhi keperluan MWA)
P2 V22 P3 V32
z2 Z 3 hL
2g 2g
P3 P2 V22 V32
Z2 Z 3 hL
2g 2g
P3
29.944
0.0445
2
18
0.0445
2
29 0.022
2g 2g
P3
18.921 m > 10.7m (Mematuhi tekanan min. bangunan 1 tingkat)
nurtechnologies@wordpress.com Page 18
Water Academy SAJHSB PELAN DAN REKABENTUK
a. Keterangan projek
b. Kriteria rekabentuk
h. Ringkasan jadual:-
- Nombor nod
- Bilangan unit bangunan
- Keperluan air seunit
- Jumlah keperluan air
- Aliran purata dan aliran puncak
k. Skematik diagram
- Maklumat teknikal: saiz paip, jenis paip, no. nod, panjang
paip.
- Lokasi paip utama (proposed connection at existing
pipeline).
- Aliran puncak.
- Aliran kebakaran.
nurtechnologies@wordpress.com Page 19
Water Academy SAJHSB PELAN DAN REKABENTUK
a. Pelan lokasi
b. Pelan kunci
c. Nama taman
f. Paip masuk
- Mestilah dari jenis mild steel pipe atau jenis paip yang
diluluskan oleh pihak berkuasa bekalan air.
- Jika perlu: menyediakan bulk meter, pressure reducing valve,
sluice valve dan sebagainya.
g. Injap-injap (valve)
h. Jenis paip
nurtechnologies@wordpress.com Page 20
Water Academy SAJHSB PELAN DAN REKABENTUK
i. Nombor-nombor nod
j. Jenis bangunan
- Diwarnakan
- Bilangan unit mengikut jenis.
nurtechnologies@wordpress.com Page 21