Anda di halaman 1dari 10

LOAD FLOW ANALYSIS

FOR SINGLE LINE DIAGRAM

Oleh:

Kelompok 7

Roni Yuliardi
Arief Kurniadi
Alfa Hidayatullah
Tris Safri Yetno
M.Iqbal Jasmi

FAKULTAS TEKNOLOGI INDUSTRI


JURUSAN TEKNIK ELEKTRO
UNIVERSITAS BUNG HATTA
PADANG
Data Generator :

TURBINE GENERATOR
HYDROGEN INNER-COOLED
RATING CONT TYPE MB-J
353000 Kva H2 PRESS 3 bar g
20000 V H2 FLOW RATE 2000 m2/min
10190 A STATOR WINDING Y
0.85 PF INS CLASS ARM B. FIELD B
3 PHASE EXC VOLT 450 V
50 Hz FIELD CURR 2740 A
3000 rpm SERIAL 84C67301
2 POLE DATE JUNE 1987

Name Plate Generator


Single Line Diagram

Data Komponen Sistem

1. Generator

Daya Semu 353 MVA


Power factor 85%
Tegangan 20kV
Daya aktif 300.5 MW
Eff 95%
Operation mode SWING
2.Circuit Breaker 1 & 2

High voltage circuit breaker


Standard IEC
3.Busbar 1

Tegangan 20 kV
Initial 100%
Angle 0

4.Transformator 1

Trafo step up primer 20kV sec 150kV


Rating 353MVA
5 .Circuit Breaker 3,4,5,6

High voltage circuit breaker


Standard IEC

.
6.Busbar 2 & 3

Tegangan 150 kV
Initial % V 100
Angle 0

7. Transformator 2
Trafo step down primer 150kV sec 20 kV
Rating 353MVA
8. Circuit Breaker 7 & 8
High voltage circuit breaker
Standard IEC
9. Busbar 4
Tegangan 20 kV
Initial % V 100
Angle 0

10. Beban (Load)


Ratings:
20 kV
353 MVA
335.35 MW
110.224 MVAR
Power Factor 95%
Amps 10190
Analisa Aliran Beban

Keterangan:

Pada Bus 1 terlihat bahwa jumlah daya masuk yang disuplai dari generator masih
berjumlah sama yaitu 274428 kW dan 161456 kvar dan tidak ada daya yang terbuang
(100%)
Pada Bus 2 terlihat bahwa terjadi penguran daya yang masuk sebanyak 5.44% menjadi
273631 kW dan 125566 kvar.
Pada Bus 3 ,daya yang masuk masih berjumlah sama dengan Bus 2 (tidak terjadi
pengurangan daya)
Pada Bus 4, kembali terjadi pengurangan daya sebanyak 4.36% menjadi 272833 kW dan
89676 kvar.
Jadi total daya yang hilang dari pembangkit (generator) menuju Load 1 adalah sebesar
9.8%.