Anda di halaman 1dari 41

SISTEM PERPIPAAN & APLIKASI POMPA

BY : MA. BUDIMAN

By : MA Budiman PT. Nusantara Teknik

Curicculum Vitae

Name : MA. Budiman


Education : Mechanical Engineering, Diponegoro University
Experience : ● PT. Nusantara Teknik (Director)
● Grundfos Pompa Indonesia (15 years)
● Wilo Pumps Indonesia (3 years)
● Steel Fabricator (3 years)

Professional Skill : Trainner & Consultant for


● Pumps & Piping System
● Central Air Conditioning System
● Plumbing & sewage system for comm. building
● Fire fighting/Hydrant system, NFPA 20Std
● STP/WTP system
● Pump energy audit

Hp. No. : 0812 9049 3938, 0877 7067 8615 (WA)


Email : nusantarapompa@gmail.com
Website : www.nusantarapompa.com
Office/workshop : Jln. SDN Jatijaya, Kp. Jati No.88,Rt.03/Rw.03
Parung-Bogor

By : MA Budiman PT. Nusantara Teknik

1
Sistem perpipaan & aplikasi

A. Sistem Perpipaan Terbuka


B. Sistem Perpipaan Tertutup

1. Negatif suction dengan positif geodetic


2. Positif suction dengan positif geodetic
3. Pompa deep well dengan positif geodetic
4. Pompa sewage dengan positif geodetic
5. Positif suction dengan negatif geodetic/sistem grafitasi
6. Negatif suction dengan negatif geodetic/efek siphone
7. Sirkulasi tertutup/cloose loop
8. Pipa bercabang

By : MA Budiman PT. Nusantara Teknik

Perpipaan-Open System

Kurva karakteristik pompa


Kurva karakteristik pipa

20 mtr

20 mtr, Static head

By : MA Budiman PT. Nusantara Teknik

2
Perpipaan-Closed System
Hot water

Kurva karakteristik pompa


Kurva karakteristik pipa

Hot
Water
Tank

Cold water

Heater

0 mtr, Static head

By : MA Budiman PT. Nusantara Teknik

1. Negatif suction dengan positif geodetic

Isolation valve

Non return valve


Hg Hd
Ld Pompa

Q = 3 x 80 m3/h @ t = 300C

Ls : Panjang pipa hisap : 5 m


Hs Ls
Hs : Tinggi hisap : 5 m

Ld : Panjang pipa discharge : 2000 m

Hg : Tinggi geodetic pipa discharge : 50 m

Hd : Tekanan discharge (tekanan kran) : 5 m

By : MA Budiman PT. Nusantara Teknik

3
Aplikasi : Pompa transfer

By : MA Budiman PT. Nusantara Teknik

2. Positif suction dengan positif geodetic

Isolation valve

Non return valve

Pompa Hd

Hg Ld Q = 30 m3/h @ t = 900C

Ls : Panjang pipa hisap : 5m

Hs : Tinggi hisap : 2m
Hs
Ls Ld : Panjang pipa discharge : 8m

Hg : Tinggi geodetic discharge : 2m

Hd : Hdischarge (tekanan kran) : 60m

By : MA Budiman PT. Nusantara Teknik

4
Aplikasi : Pompa transfer

Positif suction dg positif geodetic

By : MA Budiman PT. Nusantara Teknik

Aplikasi : Pompa transfer

By : MA Budiman PT. Nusantara Teknik

5
3. Pompa deep well dengan positif geodetic

Isolation valve

Non return valve


Ld
Hd
Hg Pompa

Q = 100 m3/h @ t = 300C

Ls : Panjang pipa riser : 80m


Hs Ls
Hs : Dynamic water level (DWL) : 50m

Ld : Panjang pipa discharge : 2000m

Hg : Tinggi geodetic pipa discharge : 60m

Hd : Tekanan discharge (tekanan kran) : 5m

By : MA Budiman PT. Nusantara Teknik

Aplikasi : Pompa transfer

Pompa deep well dengan positif geodetic

1. Gedung tingkat/perumahan

2. Industri/pabrik

3. Water supply/PDAM

By : MA Budiman PT. Nusantara Teknik

6
4. Pompa sewage dengan positif geodetic

Isolation valve

Non return valve


Ld
Hd
Hg Pompa

Q = 80 m3/h @ t = 300C

Ls : Panjang pipa riser : 5m


Hs Ls
Hs : Dynamic water level (DWL) : 4.5m

Ld : Panjang pipa discharge : 5

Hg : Tinggi geodetic pipa discharge : 1m

Hd : Tekanan discharge (tekanan kran) : 1m

By : MA Budiman PT. Nusantara Teknik

Aplikasi : Pompa transfer

Pompa sewage dengan positif geodetic

Sewage/intake
Drain pit
Flood control
Dewatering

By : MA Budiman PT. Nusantara Teknik

7
5. Positif suction dengan negatif geodetic

Q = 3 x 20 m3/h @ t = 300C Ls : Panjang pipa hisap : 3m

Hs : Tinggi hisap : 1m

Ld : Panjang pipa discharge : 30m


Hs Ls Hg : Tinggi geodetic discharge : 1m

Hd : Tekanan discharge : 8m

Ld Hg
Isolation valve

Non return valve

Pompa
Hd

By : MA Budiman PT. Nusantara Teknik

Aplikasi : Booster/distribusi

Positif suction dengan negatif geodetic

1. Tanpa Pompa

2. Dengan Pompa

By : MA Budiman PT. Nusantara Teknik

8
6. Negatif suction dengan negatif geodetic/efek siphone

Hs Ls Q = 5 m3/h @ t = 300C
Hg
Ls : Panjang pipa hisap : 10m

Hs : Tinggi hisap : 5m
Ld
Ld : Panjang pipa discharge : 25m

Hg : Tinggi geodetic discharge : 15m


Isolation valve
Hd : Tekanan discharge : 5m
Non return valve

Pompa
Hd

By : MA Budiman PT. Nusantara Teknik

Negatif suction dengan negatif geodetic/efek siphone

By : MA Budiman PT. Nusantara Teknik

9
7. Sirkulasi tertutup/cloose loop

Ld
Isolation valve

Ls Non return valve

Pompa
Ld Hpd

Chiller Q = 3 x 100 m3/h @ t = 50C


Ls : Panjang pipa hisap : 10

Hpd Hs : Tinggi hisap : 0 mtr


AHU (Air handling unit) Ld : Panjang pipa discharge : 500m

Hg : Tinggi geodetic pipa disch : 0 mtr

Hpd : Pressure drop peralatan : 10m


Ld

By : MA Budiman PT. Nusantara Teknik

Aplikasi : AC Central

Sirkulasi tertutup/cloose loop

By : MA Budiman PT. Nusantara Teknik

10
Aplikasi : Pompa sirkulasi

Sirkulasi tertutup/cloose loop

By : MA Budiman PT. Nusantara Teknik

8. Total Head Pipa Bercabang

Q:20%
Q:60% Ld3
Ld2 Q:40%

Q:40%
Q:100%
= 3 x 80 m3/h @ t = 300C
Q Ld1

Menentukan Tot. Head Pipa Bercabang

1.Estimasi Q masing2 cabang


2.Tentukan/hitung pipa seri saja
3.Coba2, tentukan hasil total head tertinggi

By : MA Budiman PT. Nusantara Teknik

11
Tot. Head : Software

CALCULATOR
TOTAL HEAD & CAVITATION

1. TOTAL HEAD (H)


● Material pipa
● Diameter pipa
● Velocity ideal

2. CEK KAVITASI

By : MA Budiman PT. Nusantara Teknik

Total Head Pompa

H : Total Head

Q : Flow Rate
v : Velocity
d : Dia Pipa

By : MA Budiman PT. Nusantara Teknik

12
Tekanan/pressure

TEKANAN STATIS TEKANAN HIDROSTATIS

F F

1m h (mtr)

PB ? PA ?

1m

F = m . g = V. ρ . g = A. h . ρ . g ρ = 1000 kg/m3
P = F/A ….. N/m2 PA = F/A = h . ρ . g g = 9,8 m/sec2

Satuan P (Tekanan hidrostatis)


● Bar (Barometic)
1 N/m2 = 1 Pascal ● Meter (H2O)
● Psig
● 1 Bar = 10,2 Meter = 14,5 Psig

By : MA Budiman PT. Nusantara Teknik

Tekanan/pressure

SATUAN PRESSURE

1 pa 1 bar 1 m H2O 1 atm mm Hg psi


(N/m2)
1 pa 1 10 1.020 10 9.869 10 7.5 10 1.450 10
1 bar 105 1 10.2 0.9869 750 14.5
1 m H2O 9806.7 0.09807 1 0.09678 73.55 1.422
1 atm 101.325 1.013 10.33 1 760 14.70
1 mm Hg 133.32 1.333 10 0.01360 1.316 10 1 1.934 10
1 psi 6895 0.06895 0.7031 0.06804 51.71 1

By : MA Budiman PT. Nusantara Teknik

13
Debit/flow

PERS. KONTINUITAS FLUIDA


Q1 = Q2

Q= A.v V = Q/t

Q1 Q2

Q : Flow rate (m3/sec)


v : Kecepatan air (m/sec)
A : лd2/4 (m2)
d : Diameter dalam (m)

A1 . v1 = A2 . v2

Satuan Q : Flow rate


● M3/jam, M3/sec
● Ltr/mnt, L/sec V : Volume air (m3)
● Gpm (US Gpm) t : Waktu (sec)

● 1 m3/jam = 1/3,6 Lps = 1/0,06 Lpm = 1/0,227 Gpm

By : MA Budiman PT. Nusantara Teknik

Pers. Bernoulli

ENERGI …….. Wtot = ∆Em = ∆Ep + ∆Ek

m.g.h1 + m.P1/ρ + m.v12/2 = Konstan ……. Nm

g.h1 + P1/ρ + v12/2 = Konstan ……. Nm/kg

P1 v1

h1 v2 P2
h2

h1 + P1/g.ρ + v12/2.g = Konstan ... (Nm/kg) . (s2/m) = (kg.m/s2) (m/kg) . (s2/m) = m

h1 + P1/g.ρ + v12/2.g = h2 + P2/g.ρ + v22/2.g

(h1 - h2) + (P1/g.ρ - P2/g.ρ) + (v12/2.g - v22/2.g) = 0 …….. m

By : MA Budiman PT. Nusantara Teknik

14
Pers. Bernoulli

P2/g.ρ = (h1 - h2) + (v12/2.g - v22/2.g) + P1/g.ρ .. mtr

Head Total Head


Pump Geodetic/suction
Head Head
Velocity Pressure

HTot = Hs + Hg + Hf fitting + Hf pipe + Hd + Hpd

By : MA Budiman PT. Nusantara Teknik

Pers. Bernoulli

h1 = P1/(ρ x g) Ø 5 cm
h = 50 cm
h2 = P1/(ρ x g) + v12/2g

∆h = v12/2g

v1 = √(2g x ∆h)

Q = A x v1 ........m3/sec

Ø 5 cm
h = v2/2g

∆h = 1m v = √(2g x h) = 3,13 m/s


h2
A = л d2/4 = 0,002 m2
h1
Q=Ax v = 0,006 ........m3/sec

By : MA Budiman PT. Nusantara Teknik

15
Total Head Formula

HTot = Hs + Hg + Hf fitting + Hf pipe + Hd + Hpd ….. mtr


Hpd Filter

Hg Hd
Ld

HTot Hs : Tinggi hisap

Hg : Tinggi geodetic pipa discharge

Hs Hd : Tekanan discharge (tekanan kran)


Ls Hpd : Pressure drop (peralatan)

Ls : Panjang pipa hisap

Ld : Panjang pipa discharge

By : MA Budiman PT. Nusantara Teknik

Geodetic Head-Negatif suction


Geodetic 95 meter

Berapa tot. geodetic head sistem ?


100 meter

100 meter

95 meter
Suction

Geodetic Suction = 5 meter


Geodetic Discharge = 95 meter

By : MA Budiman PT. Nusantara Teknik

16
Geodetic Head-Positif suction

60 meter
Berapa geodetic head sistem ?

60 meter
100 meter

100 meter

By : MA Budiman PT. Nusantara Teknik

Geodetic Head-Grafitasi

Berapa tot. geodetic head sistem ?


Untk menghitung pressure pada ttk terjauh

-30 meter
-25 meter

Geodetic Suction = -5 meter


Geodetic Disharge = -25 meter
5m

Note :
0m • Jika menghitung manual, nilai geodetic head
harus dimasukan negatif (-)
• Jika menghitung dg software calculator,
25 m

nilai geodetic head tetap positif (+)


• Untuk menghasilkan pressure/head “pompa”
yang maximal, maka geodetic head yang
digunakan = 0 mtr

By : MA Budiman PT. Nusantara Teknik

17
Geodetic Head-Closed loop

75 meter

Berapa geodetic head sistem ?

100 meter
100 meter

75 meter

0 meter

0m

By : MA Budiman PT. Nusantara Teknik

Suction & Geodetic

C? C?

B?

A?

A?

B?

By : MA Budiman PT. Nusantara Teknik

18
Friction loss pipa

Panjang pipa tot. (Lpipe) ?

……. TABEL

A
hL : Head loss (m/100m)
Q : Flow rate (Ltr/sec)
d : Internal diameter (mm)
C : Hazen William constants
B
C
Hf pipe = (hL/100) x Lpipe

By : MA Budiman PT. Nusantara Teknik

Friction loss fitting

Hf fitting : Friction loss fitting

Tipe fitting ?
Jumlah ?

Hf fitting tot = ( Hf1 x juml. fitting) + ( Hf2 x juml. fitting) + …

By : MA Budiman PT. Nusantara Teknik

19
Velocity & Dia. Pipa

v = Q/A
d1 A1

Q : Flow rate (m3/sec)


V : Cepat v : Kecepatan air (m/sec)
A : лd2/4 (m2)
d : Diameter dalam (m)

d2 A2

Tidak ada batasan pasti untuk menentukan


V : Lambat Nilai velocity.

Akan tetapi untuk mencapai hasil yang optimal


Nilai velocity yg ideal : 0.9m/s – 2m/s

By : MA Budiman PT. Nusantara Teknik

Velocity & Dia. Pipa

Mengganti pompa & Sistem perpipaan

P = 18.5kW
Sistem A
H = 97 m

L = 1000 mtr Dia. = 80mm


Q = 45 m3/hr

P = 7.5kW
Sistem B
H = 30 m

L = 1000 mtr Dia. = 100mm


Q = 45 m3/hr

By : MA Budiman PT. Nusantara Teknik

20
TABEL OF HEAD LOSSES (Example)

● Head losses pipa = 24,18 x 1/100 x panjang pipa


● Head losses L = 1,1 x 24,18 x 1/100 x jumlah L
● Total Head losses
● Head losses T = 4 x 24,18 x 1/100 x jumlah T
● Head losses foot valve = (4 x 2) x 24,18 x 1/100 x jumlah FV

By : MA Budiman PT. Nusantara Teknik

Contoh : Perhitungan friction loss

Pipa outlet 10 mtr, dia 27mm

Press kran 2 m

6 mtr

√ √ √ √
√ √ √ √ √
√ √ 4,2 m3/jam

2 mtr

√ √

Pipa hisap 8 mtr, dia 27mm

By : MA Budiman PT. Nusantara Teknik

21
Kavitasi

Detektor kavitasi :
Tidak bisa didekteksi
dg alat
Tanda kavitasi :
Suara pompa berisik keras
Getaran pompa tinggi

Akibat kavitasi :
Performace pompa turun
Impeler & casing rusak

By : MA Budiman PT. Nusantara Teknik

Kavitasi : NPSHa<NPSHr

Kavitasi terjadi karena :

NPSHa < NPSHr


NPSHr
1. Posisi hisap terlalu tinggi
2. Dia. pipa hisap terlalu kecil
3. Pipa hisap terlalu panjang
4. Temperatur air teralalu tinggi

5. NPSHr pompa terlalu besar


oC

By : MA Budiman PT. Nusantara Teknik

22
Simulasi kavitasi

1. Membuat tekanan udara (P bar)


rendah/ titik didih rendah yaitu
dengan cara divacum.

2. Proses terjadinya kavitasi pada


tekanan udara rendah.

By : MA Budiman PT. Nusantara Teknik

Mencegah Kavitasi

Hasil perhitungan sistem : NPSHa NPSHr : Data pompa


V

Tidak terjadi kavitasi

NPSHa=(Pb x meter)-Hf-Hv-Hs-H … (Mtr)


H : Kedalaman hisap (mtr)
Pb : Barometic pressure (1 bar)
Hf : Friction loss pressure (mtr)
Hv : Vapour pressure (mtr) …(tabel)
Hs : Safety factor (0.5m)

Tekanan udara luar : P-bar dibeberapa negara.


Indonesia : 10.20 m
China : 9.11 m
Tibet : 6.62 m NPSHr = 1.76 m
Beijing : 10.30 m
Denmark : 10.13 m

By : MA Budiman PT. Nusantara Teknik

23
Kemampuan Hisap (Suction Lift)

NPSHr Kemampuan Hisap

1. Pompa A : NPSHr = 1 meter

Hmax Hmax=10.2-2-1.2-1-1= 5 meter

2. Pompa B : NPSHr = 3 meter


Hmax=10.2-2-1.2-1-3= 3 meter
b

By : MA Budiman PT. Nusantara Teknik

Definisi NPSH

NPSHa ? NPSHr ?

Pressure positif pd sisi hisap yang Pressure positif pd sisi hisap, yang
nilainya ditentukan dari analisa perhitungan nilainya ditentukan dari konstruksi pompa
dengan menggunakan data-data sistem pipa, (inlet casing, impeler). Pressure tersebut
P vaporasi(temperatur fluida) dan Pbar bersifat menghambat kemampuan hisap.
di suatu tempat

P-barometic

0 1.013 10.33 100 ∆H=NPSH


500 0.935 9.73 99
1000 0.899 9.16 96
2000 0.795 8.10 93

By : MA Budiman PT. Nusantara Teknik

24
Definisi Kavitasi

a = front of impeler KAVITASI ?

Terjadinya gelembung-gelembung udara di


dalam pompa.
a
b Disebabkan oleh beberapa faktor, diantaranya
H : Kedalaman hisap terlalu tinggi
Hf : Friction loss terlalu besar
Hv : Vapour pressure terlalu besar
Pb : Barometic pressure terlalu rendah

Sehingga NPSHa < NPSHr

Kavitasi bisa terjadi dimana saja didalam


b = back of impeler
pompa, jika pressurenya lebih kecil dari
Karena adanya benturan dengan impeler, pressure vaporasi cairan yang di pompa
maka gelembung-gelembung tersebut
pecah dan menimbulkan energi, sehingga
menimbulkan kerusakan pada impeler.

By : MA Budiman PT. Nusantara Teknik

Metode menghindari kavitasi

NPSHa > NPSHr …………. Dg cara :


NPSHr
1. Ketinggian suction/Hs diperpendek
2. Dia. pipa hisap diperbesar
3. Panjang pipa hisap diperpendek
4. Temperatur air diturunkan

5. Diganti dg pompa yg ber NPSHr kecil


oC

By : MA Budiman PT. Nusantara Teknik

25
Test : Kavitasi & NPSH

Data sistem seperti diatas, akan tetapi suhu Jika suhu air diturunkan menjadi 30oC.
air adalah 90oC. Analisa apakah masih terjadi kavitasi?
Analisa apakah terjadi kavitasi? Berapa kedalaman max yang diijinkan?
Jika terjadi kavitasi, berapa kedalaman max
yang diijinkan?

Negatif berarti positif suction


(Level air berada diatas pompa)

By : MA Budiman PT. Nusantara Teknik

By : MA Budiman PT. Nusantara Teknik

26
By : MA Budiman PT. Nusantara Teknik

By : MA Budiman PT. Nusantara Teknik

27
Tot. Head : Metode Tabel

Sumur dangkal dengan level air pada


posisi 6 meter dari inlet pompa.
Air dari sumur akan dipompa keground
tank dengan debit 8m3/jam, panjang
Hd pipa hisap 10 meter, tinggi geodetic 2m.
panjang pipa discharge 15 meter.
Pressure discharge ditentukan 5 meter.

Tentukan total head pompa, tipe pompa,


diameter pipa (inlet/outlet), kecepatan air
dan cek apakah terjadi kavitasi.
Diketahui : Berapa Hmax suction sehingga tidak
Pipa suction Terjadi kavitasi
Q = 8 m3/jam
Hs = 6 m Pipa discharge
Ls = 10 mtr Ld = 15 m
Juml ball vave = 1 unit Hg = 2 m
Juml foot valve = 1unit Hd = 5 m
Juml L = 1 unit Juml ball vave = 1 unit
Juml check valve = 1 unit
Juml L = 2 unit

By : MA Budiman PT. Nusantara Teknik

Tot. Head : Metode Tabel

2x

By : MA Budiman PT. Nusantara Teknik

28
Tot. Head : Metode Tabel

CH8-30

By : MA Budiman PT. Nusantara Teknik

Tot. Head : Calculator (Budiman)

By : MA Budiman PT. Nusantara Teknik

29
Tot. Head : Calculator (Budiman)

By : MA Budiman PT. Nusantara Teknik

Case study : Total Head Pipa Bercabang

Pipa suction
Q = 200 m3/jam Q:20%
Hs = 2 m Q:60%
Ls = 8 mtr Q:40%
No. ball vave = 1Pc
No. foot valve = 1Pc
No. L = 1Pc TOTA. HEAD ?
Dia pipa = ? CEK KAVITASI ? Q:40%
V= ? Q:100%
Q = 3 x 80 m3/h @ t = 300C

Pipa-1 (100%) Pipa-2 (60%) Pipa-3 (20%)


Ld1 = 1000 m Ld2 = 1500 m Ld3 = 500 m
Hg = 20 m Hg = - m Hg = - m
Hd = 10 m Hd = - m Hd = - m
No.ball v = 1Pc No.ball v = 1Pc No.ball v = 1Pc
No. check v = 1Pc No. T = 1Pc No. T = 1Pc
No. L = 2Pc No. L = 2Pc No. L = 2Pc
Dia pipa = ? Dia pipa = ? Dia Pipa = ?
V= ? V= ? V= ?
By : MA Budiman PT. Nusantara Teknik

30
By : MA Budiman PT. Nusantara Teknik

By : MA Budiman PT. Nusantara Teknik

31
By : MA Budiman PT. Nusantara Teknik

Kavitasi : Vortex

Jarak dibawah ini terlalu dekat

E : Jarak suction dg level air


F : Jarak suction dg dasar tanki E

G : Jarak as pipa dg dinding tanki

By : MA Budiman PT. Nusantara Teknik

32
Kavitasi : Air pocket

Air pocket
Air pocket/ kantung udara menyebabkan
udara akan terperangkap didalamnya,
dan udara ini akan terbawa aliran air
masuk ke pompa sehingga dapat menye
babkan kavitasi

By : MA Budiman PT. Nusantara Teknik

Kavitasi : Turbulensi

Aliran Turbulen

Re > 4000 Salah satu penyebab turbulen adalah


kecepatan air yang terlalu tinggi
sehingga menimbulkan gelembung-
gelembung udara.

Turbulensi

By : MA Budiman PT. Nusantara Teknik

33
Pengaturan QH-Throtle

P1 P2

Setelah di throtle :
Q = 15 M3/Jam
H = 54 Meter

Q = 20 M3/Jam
H = 48 Meter

54mtr, Press. pipa Head


sebelum valve losses

25mtr, Pressure pipa


setelah valve

By : MA Budiman PT. Nusantara Teknik

Pengaturan QH-Balancing Valve

P2 < P1

P1

Syarat untuk balancing valve


●Tiap ujung out let harus ada gate valve
●Tiap cabang utama lebih baik ada PRV

Prosedure test com


•Masing-masing PRV diset dg P sama
•Semua gate valve ditutup kecuali gate
valve teratas paling ujung (open 10%)
•Satu persatu gate valve di buka
(trial min 10%-20%)

By : MA Budiman PT. Nusantara Teknik

34
Pengaturan QH-By pass

Qtot Q1

Qtot = Q1 + Q2
Q2

Qt = 20 M3/Jam
H = 48 Meter

Q2
Q1

By : MA Budiman PT. Nusantara Teknik

Aliran : Laminer & Turbulen

Aliran Laminer Aliran Turbulen

Re < 2300 Re > 4000

ρ V DH V DH Q DH μ
Re = = = v=
μ v vA ρ

● Re : Reynold number ● A : Area (m2)

● DH : Diameter pipa (m) ● μ : Dynamic viscosity (Kg/m.s) : 10 poise

● V : Velocity/kecepatan (m/s) ● ρ : Density/massa jenis (kg/m3)

● Q : Flow rate (m3/s) ● v : Kynematic viscosity (m2/s) : 104 stokes

By : MA Budiman PT. Nusantara Teknik

35
Aliran : Vortex

G G

E E

F F

PIPA HISAP TANPA FOOT VALVE PIPA HISAP DENGAN FOOT VALVE

By : MA Budiman PT. Nusantara Teknik

Surging

Pompa bekerja tidak stabil,


sehingga aliran air juga tidak stabil
Pompa bekerja stabil
Seting OFF : Mungkin Q = 0, pump masih ON

Jika menggunakan sensor pressure maka pompa


akan stabil pada seting pressure 70m s/d 90m

By : MA Budiman PT. Nusantara Teknik

36
water hammer

Aliran balik yang terjadi pada sistem


perpipaan dikarenakan pompa berhenti
dengan tiba-tiba.

By : MA Budiman PT. Nusantara Teknik

water hammer

kN/m2 = Bar
Shock Pressure = Vs x V …….

Tabel

No. Pipe material Modulus elasticity

= Density of water (kg/m3)(1000/kg/m3) 1 Steel material 207 GN/m2

k = Bulk modulus of water (2.07 GN/m2) 2 Cast iron 100 GN/m2


D = Inner diameter of the pipe (mm)
3 Copper 11 GN/m2
t = Thickness of the pipe (mm)
E = Modulus elasticity of pipe material 4 Ductile iron 169 GN/m2
GN/m2 5 Stainless steel 304/316 193 GN/m2
(see attached table)

6 Bulk modulus of water 2.07 GN/m2


V = Q/A

V = Velocity of water (m/s)


Q = Flow rate (m3/s)
A = Area of pipe (m2)

By : MA Budiman PT. Nusantara Teknik

37
water hammer

Water density : 1000 kg/m3


Water bulk modulus : 2.07 GN/m2
Pipe modulus elasticity : 169 GN/m2
Pipe inner dia. : 96.7 mm
Pipe thickness : 1.65 mm

= 1097.73 m/s

Pipe length : 500 m Vs = 1097.73 m/s


Velocity = 2.04 m/s
Pipe outer dia. : 100 mm
Pipe inner dia. : 96.7 mm Shock Pressure = Vs x V
Flow rate : 35 l/s = 1097.73 x 2.04 (KN/m2)
Pipe material : Ductile Iron = 2241.75 (KN/m2)
= 2.24 bar

By : MA Budiman PT. Nusantara Teknik

Pondasi & Inertia block

BASEMENT
Pondasi

By : MA Budiman PT. Nusantara Teknik

38
Pondasi & Inertia block

Inertia Block

ROOF FLOOR

By : MA Budiman PT. Nusantara Teknik

Pondasi & Inertia block

Grouting

Inertia Block

Vibration
damper
Pondasi

By : MA Budiman PT. Nusantara Teknik

39
Pondasi & Inertia block

Lf = Lbaseframe + 0,2 m

Bf = Bbaseframe + 0,2 m

concrete = 2,200 kg/m3

Berat pondasi (recommended)


1.5 s/d 5 kali dari berat pompa

By : MA Budiman PT. Nusantara Teknik

Reducer & elbow

Recommended Not Recommended

Short radius elbow

Long radius elbow

Recommended

Turbulensi

Concentric reducer

By : MA Budiman PT. Nusantara Teknik

40
By : MA Budiman PT. Nusantara Teknik

PT. NUSANTARA TEKNIK


TOKO NUSANTARA POMPA
AUTHORIZED DEALER-MCKARLEN PUMP

M.A. BUDIMAN
HP. 0812 9049 3938, 087770678615 (WA),
nusantarapompa@gmail.com

By : MA Budiman PT. Nusantara Teknik

41

Anda mungkin juga menyukai