Jumlah titik sprinkler

No Jumlah ø Pipa
1 2 titik sprinkler 25 mm
2 3 titik sprinkler 32 mm
3 5 titik sprinkler 40 mm
4 10 titik sprinkler 50 mm
5 20 titik sprinkler 65 mm
6 40 titik sprinkler 80 mm
7 100 titik sprinkler 100 mm
8 160 titik sprinkler 125 mm
9 275 titik sprinkler 150 mm

Standart kapasitas ( Q ) di dalam pipa

No Kapasitas ( Gpm ) ø Pipa


1 0- 2 Gpm 15 mm
2 3- 5 Gpm 20 mm
3 5- 10 Gpm 25 mm
4 10 - 20 Gpm 32 mm
5 20 - 30 Gpm 40 mm
6 30 - 60 Gpm 50 mm
7 60 - 100 Gpm 65 mm
8 100 - 200 Gpm 80 mm
9 200 - 400 Gpm 100 mm
10 400 - 600 Gpm 125 mm
11 600 - 1,000 Gpm 150 mm
12 1,000 - 1,800 Gpm 200 mm
13 1,800 - 3,000 Gpm 250 mm
14 3,000 - 4,000 Gpm 300 mm
15 4,000 - 5,000 Gpm 350 mm
16 5,000 - 6,000 Gpm 400 mm
17 6,000 - 7,000 Gpm 450 mm
18 7,000 - 9,000 Gpm 500 mm
19 9,000 - 13,000 Gpm 600 mm

Mechanical Ventilation / Number of Air Changes per Hour ( ACH )


- Toilet = 8 - 15 ACH ( Diasumsikan 12x )

- Stroge = 3 - 6 ACH ( Diasumsikan 6x )

- Mechanical Room = 10 - 20 ACH ( Diasumsikan 20x )

- Parking Area = 6 - 8 ACH ( Diamsusikan 6x )

Menghitung Besar Diameter Pipa Air Hujan

Dibagi Riser dan Pipa Cabang

Riser Luas atap ( Mtr² ) Area Atap ( Mtr² ) Dan Kemiringan Air
Φ ( in ) Hujan ( Pipa Cabang )
4% 2%
2 67
2.5 121
3 204 153 108
4 427 349 246
5 804 621 437
6 1,256 994 701
8 2,694 2,137 1,514
10 3,846 2,713
12 6,187 4,366
16 11,055 7,804

Bisa juga dengan rumus setiap Mtr² luas atap = 1 cm² luas pipa
Contoh : Atap dengan luas 100 Mtr²

D =√ 4 x 100 / 3.14

Φ pipa = 11.28 cm
Hour ( ACH )
) Dan Kemiringan Air

1%

76
175
310
497
1,086
1,923
3,094
5,528