CALCULATION DESIGN OF FOUNDATION

150 kV TRANSMISSION LINE OF KALTENG-1 2X100 MW


4DD6 CLASS 7W
DATA TEKNIS PERENCANAAN
Mutu Beton = K225
f'c = 225 kg/cm2
fy = 400 Mpa
g beton = 2.40 t/m3
g tanah = 1.60 t/m3
qcrata -rata = 22.30 kg/cm2
Koefisien geser = 0.45
b1 = 0.85
Es = 210000 Mpa
ec = 0.003
Selimut Beton Pondasi = 75.00 mm
Selimut Beton Kolom = 75.00 mm
Sudut geser dalam tanah = 0.00 0

DATA BEBAN =
Gaya Lateral (H) = 33.62 ton
Gaya Tekan ( C ) = 169.46 ton
Gaya Tarik (T) = 132.36 ton
DIMENSI PONDASI
Lebar lengan pelat 1 (b1) = 6.3 m
Lebar lengan pelat 2 (b2) = 3.15 m
Tebal Pelat (a) = 0.6 m
Lebar slab (h) = 3.5 m
Tebal slab (f) = 0.7 m
Dalam pondasi (df) = 4 m
Kemiringan stub (a) = 81.16 0
Tinggi Chymey di atas tanah (ht) = 0.4 m
Tinggi Chymney (L) = 3.13727 m
Lebar Chymney (b) = 1 m
Lebar lengan slab (g) = 1.25 m
Back to Back = 16.227 m
Kenggian max kolom = 3 m

BERAT PONDASI
1 Berat kolom
Volume Kolom = 3.13727 m3
Berat kolom = 7.52944 ton
2 Berat pelat
Volume pelat = 32.389 m3
Berat Pelat = 77.7336 ton
BERAT TANAH
Berat tanah sebagai penahan gaya Up li (Wsu)
dimodelkan sebagai bentuk Limas
b' Segiempat terpancung

b'

df
b1
b1