PROGRAM PERHITUNGAN FLOORDECK

Diketahui Floordeck :
F'c = 30 Mpa
Lx = 3000 mm
Ly = 4000 mm
Tebal Deck = 0.95 mm
Berat Deck = 11.3 kg/m2
Fy Deck = 5500 kg/cm2
BJ Beton = 2400 kg/m3
qLL Pekerja = 100 kg/m2
qLL Ruang = 250 kg/m2
Tebal Lantai = 120 mm 4 m

Tahap 1 : Saat beton di cor dan belum mengeras ( belum terjadi aksi komposit ), beban dipikul oleh floordeck
1 Menghitung modulus section floordeck
Statis momen terhadap sisi bawah :
1000 mm

120 mm 1 1 1
Ў 2 2 3 2 3 2
40 40 40

ΣMo = 0 1 2 3
= (11 x 40 x 25) + (22 x 28 x 28/2) + (1000-(11 x 40))x 0 = (1000+ 22 x 25) x Ў
Ў= 13 mm

Sx = [11 x 40 x 0,75 x ( 25-13 )] + [22 x ( 25-13 ) x 0,75 x (25-13)/2]


Sx = 6659.1 mm3 = 6.6590790 cm3
Zx = 2 x Sx = 13318.16 mm3 13.3181580 cm3

2 Menghitung momen perlu


Beban Mati :
qDL = Berat beton + Berat Floordeck
qu = 1,2 qDL + 1,6 qLL Pekerja
= 519.16 kg/m

3000 m 3000 m
M lap ( positif ) = (9/128) qu x L^2 = 328.5309375 kgm
M (negatif ) = (1/8) qu x L^2 = 584.055 kgm

Cek daerah Mu positif (Lapangan)


Mp = Fy x Zx = 732.4987 kgm
Mu + = 328.530938 kgm < ØMp = 659.2488 kgm

Cek daerah Mu positif (Tumpuan)


Mp = Fy x Zx = 732.4987 kgm
Mu - = 584.055 kgm < ØMp = 659.2488 kgm

Tahap 2 : Komposit
Beban yang bekerja
Berat Floordeck = 11.3 kg/m2
B. Pelat Beton = 180 kg/m2
B. Penutup Lantai = 60 kg/m2
qDL = 299.3 kg/m
qLL = 250 kg/m

qu = 759.16 kg/m
M Lap (positif) = 160.135313 kgm
M (negatif) = 284.685 kgm

Ec = 25742.9602 Mpa
Es = 200000 Mpa
n= Es/Ec = 7.77

1000 mm

120 mm 1 1 1
ya 2 2 3 2 2 3 2
40 40 40

Statis momen terhadap sisi bawah


ΣMo = 0
(1000 + 22 x 22) x 0,75 x 13 + [(1000 x 100)/n] x (13 + 100/2) = [(1000 +22 x 25) x 0,75 + (1000 x 100
ya = 68 mm

Sx = (1000 x (120 - ya)/n) x (120 - ya)/2


= 176900.6 mm3
= 176.9006 cm3
Zx = 2 x Sx = 353.8012 cm3

Cek daerah Mu positif (Lapangan)


Mp = Fy x Zx = 19459.07 kgm
Mu + = 480.405938 kgm < ØMp = 17513.16 kgm

Cek daerah Mu positif (Tumpuan)


Mp = Fy x Zx = 19459.07 kgm
Mu - = 854.055 kgm < ØMp = 17513.16 kgm
m

ul oleh floordeck
Panjang efektif floordeck = 1000 mm
Jumlah bukit dalam 1m = 11
Jumlah lembah dalam 1m = 12
Jumlah miring dalam 1m = 22
Panjang bukit / lembah = 40 mm
2 25 mm Tinggi bukit ke lembah = 25 mm
panjang sisi miring = 28 mm
OK

OK

Panjang efektif floordeck = 1000 mm


Jumlah bukit dalam 1m = 11
Jumlah lembah dalam 1m = 12
Jumlah miring dalam 1m = 22
2 25 mm Panjang bukit / lembah = 40 mm
40 Tinggi bukit ke lembah = 25 mm
panjang sisi miring = 28 mm

2 x 25) x 0,75 + (1000 x 100)/n] x ya


OK

OK
L = 4m
Jarak Antara Balok = 3m
F'c = 30 mpa
fy = 250 Mpa
t pelat lantai = 120 mm tw tf
Digunakan Profil = 150 75 5 7
Properti Penampang
A = 17.85 cm2 1785
r = 8 mm
h = 136 mm
E = 200000 mpa
Ec = 25742.960203 mpa
Cek Kekuatan Momen Penampang komposit tersebut & beberapa shear connector yg diperlukan!

1. Cek Rasio Penampang Badan


h/tw = 27.2
λ = 3,76sqrt(E/fy)
= 106.34885989
Analisa Plastis
ø = 0.9

2. Menentukan PNA (plastic Neutral Axis)


be = 1/8 L balok
= 0.5 m
be=jarak antar balok = 3m 27691.47

Jadi lebar efektif balok (be) = 0.5


Letak PNA:
a=Xpl = As.Fy
0,85.f'c.be
= 35 < 120 mm
Letak PNA di dalam pelat beton

3. Menghitung Kuat Momen


Mn=Mp As.Fy(H/2+t-(a/2)
760856.3 Knmm
760.8563 Knm
øMn 684.7706

4. Menentukan shear connector


Kuat geser shear connector (Qc)
diameter shear connector = 16 mm
Asc = 200.96
Fu = 410 Mpa
Qc = 0,5.Asc.sqrtf'c.Ec < Asc . Fu
= 91582.654335 > 82393.6
Qc = 82393.6 N
82.3936 KN

Gaya Geser Horizontal = As.Fy


446250 = 446.25 Kn
0,85.F'c.Be.a
446250 = 446.25 Kn

Jumlah Shear Connector = Vh/Qc


n 5.4160760059
n = 6 jumlah shear connector yang dibutuhkan

Jarak Shear Connector


Arah Transversal
4 Dsc = 64 mm
Arah Longitudinal
6 Dsc (min) = 96 mm
8 tp (max) = 960 mm
x = L/0,5n
= 666.66666667

Karena,
Min. < x < Max. OK
Perhitungan Balok Utama
n balok = 4

Lx = 6
Ly = 4
Lb = 3

Beban Mati (dl) Tebal (m) Berat (kg/ Berat (kg/m)


Berat Pelat Lantai = 0.12 2400 864
Berat Spesi = 0.02 21 126
Berat Keramik = 24 72
Berat Plafond = 18 54
Instalasi = 25 75
Berat Sendiri = 31.5
Berat Floordeck = 0.0095 11.3 33.9
Total Beban Mati (dl) = 2512.8 Kg/m

Beban Hidup (ll) Berat (kg/ Berat (kg/m)


beban hidup untuk res= 250 750
Total Beban Hidup = 1500 kg/m

Momen akibat beban mati (MD)


1/8.qdl.L^2 = 5025.6 Kg.m
= 50.256 Kn.m
Momen akibat beban hidup (ML)
1/8.ql.L^2 = 3000 Kg.m
30 Kn.m
Momen akibat beban (Mu1) = 1,2 MD + 1,6ML
1,2 MD + 1,6 ML = 108.3072 Kn.m

2. Preliminary design
Mu = 108.3072 Kn.m
Fy = 250 Mpa
Ø = 0.9 Lentur
Zx = Mu/ Ø Fy
= 0.000481 m3
481.3653 Cm3

Pilih Profil Dekat Dengan Zx


IWF
H = 200 mm
B = 200 mm
tw = 8 mm
tf = 12 mm
r = 13 mm
A = 65.53 cm2
Berat = 49.9 kg/m
Ix = 4720 cm4
Iy = 1600 cm4
ix = 8.62 cm
iy = 5.02 cm
Sx = 472 cm3
Zx = 525.48 cm3
200 200 8 12
Cek Kekompakan Penampang
Pasal F2,bahwa
Profil I kompak simetris ganda, maka berlaku KASUS 11 (Sayap) dan KASUS 15 (Badan)
Badan : Kompak (C), Sayap : kompak (C)
Keadaan batas : Pelelehan dan Tekuk Torsi-Lateral (LTB)

Periksa
Batasan Untuk Sayap
Es = 200000 Mpa
Fy = 250 Mpa
Kc = 4/sqrt(h/tw)
0.8
λp = 0,38.sqrt(E/fy)
= 10.74802 Batas Kompak
λr = 0,95.sqrt(Kc.E/Fy)
= 24.03331 Batas Non Kompak
λsayap = b/2.tf
8.333333 Kompak

Batasan Untuk Badan


λp = 3,76.sqrt(E/fy)
= 106.3489 Batas Kompak
λr = 5,76.sqrt(E/fy)
= 162.9174 Batas Non Kompak
λbadan = h/tw
= 25 Kompak

Tekuk Torsi Lateral


Lb = 3
Lp = 1,76.ry.sqrt(E/fy)
= 647.1441 mm
= 0.647144 m

rts = bf/sqrt12(1+1/6.htw/bftf)
54.77226
J = 26.45 cm4
Lr = 10.45

karena Lp<Lb<Lr, berlaku


Mn = Cb (Mp - (Mp-0,7.Fy.Sx).(Lb-Lp)/(Lr-Lp))

Mencari momen untuk mendapatkan Cb


q = 4012.8 kg/m
= 40.128 KN/m
L = 6m
RA = 120.384
RB = 120.384
Jarak Momen
0 0
1.2 48.1536
1.5 60.192
2.4 96.3072
2006.4 80512.82
3.6 144.4608
4.5 180.576
4.8 192.6144
6 240.768

Ma (1/4L) = 60.192
MB(1/2L) = 80512.82
Mc (3/4L) = 180.576
Cb = 12,5 Mmaks/2,5Mmaks+3Ma+4Mb+3Mc
= 1.920426
C = 1

1. pelelehan
Mn = Mp penampang kompak
Mp = Fy . Zx
Mp = 1.31E+08 Nmm
= 131.37 KNm

2. Tekuk Torsi Lateral


Mn = 290.3594 KNm

Dipilih Mn terkecil
Mn = 131.37 KNm

6. Perhitungkan berat sendiri profil ke dalam Mu


Mu = Mu1 + 1,2 Mberat profil = 109.5048 kN.m
7. Bandingkan nilai Mu dan Mn
Apakah : Mu ≤ Ø Mn
109.50 118.23
OK
PROGRAM PERHITUNGAN KOLOM
Diketahui :
Beban Terfakor (PU)
DI atas floordeck = 310.61 KN
Di balok utama = 1.89 KN
Di balok anak = 1.02
Dl total = 313.52 LI total

PU = 1,2 DI + 1,6 LI
= 722 KN

1. Preliminari design =
PU < Ø Pn
Pu < Ø Ag x Fcr
Ag = Pu/Ø x Fcr
Ag = 0.0037604167 37.60417 cm2
B H Tw Tf
Profil IWF 300 300 10 15
A = 119.8 cm2
berat = 94 kg/m
Ix = 20400 cm4
Iy = 6750 cm4
ix = 13.1 cm
iy = 7.51 cm
r = 18 mm
Sx = 1360 cm2
Zx = 1501.12 cm3

3. Syarat Kelangsingan
Syarat : K x L /r < 200
K = 0.8 Tumpuan sendi jepit
Tinggi Kolom = 3.85 m
= 3850 mm

Maka, K x L /r = 41.011984021 < 200

4. Klasifikasi Penampang
Batasan Rasio tebal terhadap lebar = 1,49 x sqrt(E/Fy)
= 43.012595055 Badan
Sayap = Bx0,5 / tf
10 KOMPAK Sayap
Badan = (H-2 x tf)/tw
= 27 KOMPAK

Lanjut ke pasal E7 karena langsing langsing


Syarat Pn = Fcr x Ag
Tegangan krtis Fcr, harus ditentukan sebagai berikut:
bila, KL/ r ≤ 4,71 x sqrt E/fy
41.0119840213049 135.96598839

Fe = 1172.3781961
Fcr = (0,658^(Fy/Fe))
= 0.9178857791

PEMBEBANAN
Momen
M = 1/8*q*Lkuadrat
= 174.164375 Kg.m
Mu = 1/4*Mdl
= 43.54109375 Kgm
0.4354109375 KNm
435.4109375 Nm
Terpusat pada kolom
P = (qL)/2
= 180.95 Kg
Pu = 1,4 P
= 253.33 Kg
2.5333 KN
2533.3 N

Harga Konstanta Tekuk (Kc)


Ga = 1.5584415584
Gb = 10 sendi

Kc = 0.89

Kontrol Kekuatan Kolom


Lkx = Kc.L
342.65 cm
ʎx = Lkx / ix
45.625832224 < 200
Pe1 = (πkuadrat x E x A) / ʎx kuadrat
11348135.469 KN
11348.135469 N
ʎc = (ʎx/π)(sqrt Fy/E)
0.5033519717

Karena 0,25 < ʎc <1,25


Maka,
W = (1,43)/(1,6-0,67 ʎc)
= 1.1324452722

Pn = (A x Fy)/w
2538930.6402 N
2538.9306402 KN
Pu/ØPn = 0.0011738615 < 0.2

Maka digunakan rumus

Mencari nilai Mux


cmx = 0,6 + 0,4 (M1/M2)
= 0.6
σbx = cmx/(1-(Pu/Pe1)
0.7724343018

Karena σbx <1


maka
σbx = 1

Mux = σbx * Mu
0.4354109375 KNm

Kontrol Penampang
untuk sayap
b/2tf < 170/sqrtfy
10 < 10.973452814
Kompak, maka gunakan Mnx = Mpx

Untuk Badan
hw/tw = 23.4
= 1680/sqrt(fy)(1-(2,75Pu)ØPn)
108.1244
23.4 < 108.1244 Kompak
Maka gunakan Mnx = Mpx

Lateral buckling
Lb = 385 cm
3.85 m
dari tabel iwf tanpa sokongan
Lr = 771 cm
7.71 m
Lp = 155 cm
1.55 m
Maka,
Lp < Lb < Lr = bentang menengah

cb = 1 utk beban simetris


Mr = Sx (Fy-Fr)
= 231200000 Nmm
231.2 Knm
Mp = Fy x Zx
360268800 Nmm
360.2688 KNm

Mn = Cb(Mr+(Mp-Mr)(Lr-Lb)/(Lr-Lp)))
= 312.07752727 KNm

Persamaan Interaksi
Mn = Mp
= 360.2688 Knm
Mn = 312.07752727

Gunakan Mn terkecil = 312.07752727 Knm

Maka = Pu Mux
2ØPn
= 0.0015508105 < 1

AMAN-DAPAT DIGUNAKAN
= 216.11

Diketahui : Fcr = Fy 240 Mpa


E = 200,000 Mpa

OK

ʎr = 43.0126

ʎr = 28.86751
OK
Prelimanary Design
Data
F'c = 30 Mpa
Baseplate Seluasan Pedestal
Pu = 722 KN
= 722000 N
Φ = 0.85
PP = Pu
Φ
= 849.411764705882 N
PP = 0,85xf'cxA1
A1 = 33.3102652825836 mm2

1. KUAT AKSIAL
B=N = 300 mm
d = 200 mm
bf = 200 mm
m = N-0,95d
2
= 55 mm
n = B - 0,8.bf
2
= 70
PU < 0,6 x 1,7 f'c x B x N
722000 < 2754000 OK

2. PENENTUAN TEBAL BASEPLATE


fp = Pu
BxN
= 8.02222222222222 Mpa
tp = 1,49 x c x sqrt fp
Fy
= 18.6836467770318 mm
= 20 mm

Mpl < Φb.Mn


Mn = Mp = Zx . Fy
Mn = 108.986 Knm
Mpl = fp(m^2/2)
= 47643.7699861778 Nmm
fp((C^2)/2) < 0,9(tp^2/4).Fy
19654.444444 < 22500

tp > 1,49 c x sqrt(Pu/B.N.Fy)


20 > 18.6836467770318 OK

3. Kuat Geser
Kolom Lt 1 Kolom Lt 2
Beban V2 (KN) V2 (KN)
DL 0.0804 0.0917
LL 0 0
1,4DL 0.11256 0.12838
1,2DL + 1,6LL 0.09648 0.11004

D baut = 16 mm
Ab = 200.96 mm2

Vu ≤ 0,75*Fv*Ab*n
24.37 = 0,75*250*1000*200,96/1000000*n
okayy
n = 1.54616331555191
n = 2 buah

24.37
4.Kuat Tarik
Kolom Lantai 1 Kolom Lantai 2
Beban
P(KN) M(KNm) P(KN) M(KNm)
DL -26.7201 -0.3427 -10.5286 0.3543
LL 0 0 0 0
1,4 DL -37.40814 -0.47978 -14.74004 0.49602
1,2 DL + 1,6 LL -32.06412 -0.41124 -12.63432 0.42516

fc1 = 8.02658987654321
fc2 = 8.01785456790124
a = 150.081666666667 mm

x1 = N/2 - a/3 = 0.116649


x2 = N - m/2 - a/3 = 0.180515

Tu = Mu - Pu . X1
x2
Tu = 24.1731203849486 KN

Ag = 200.96 mm2

Tu = Φb . Ag . Fy . n/2
24.173120385 = 0,9 . 200,96 . 250 . n/2
n/2 = 0.534614304338035
n = 1.06922860867607
n pakai = 2 buah

Panjang Angkur
ld = Tu / (Φ . phi . D . Fcl . n/2) 11.304
= 0.002566148660823 m
= 2.56614866082257 mm
Id pakai = 400 mm
m
m

lmin = fy/(4*sqrt fc'*d


= 0.260417
Sambungan las balok induk melintang, BALOK-KOLOM

Las fillet
Tebal las = 3 mm
Panjang Efektif las
Lw1 = (B-tw)/2xtebal las+Bx2
= 432 mm
Lw2 = 4xH
800 mm
LW = Lw 1 + Lw 2
= 1232 mm

Mutu Las
fy = 250 mpa
fu = 490 mpa

φ Rnw = 0,75 x (0,6.fu.0,707.tw.LW)


= 1536486 N
= 1536.486 KN

Ru
Beban Balok Lt 1

DL 4.8584
LL 0
1,4 DL 6.80176
1,2 DL 5.83008
1,2 DL + 1,6 LL 5.83008

Ru < φ Rnw
5.83008 < 1536.486 OK

2. Sambungan las Balok Komposit BALOK INDUK

Las fillet
Tebal las = 3 mm
Panjang Efektif las
Lw1 = (B-tw)/2xtebal las+Bx2
= 171.6667 mm
Lw2 = 4xH
300 mm
LW = Lw 1 + Lw 2
= 471.6667 mm

Mutu Las
fy = 250 mpa
fu = 490 mpa
φ Rnw = 0,75 x (0,6.fu.0,707.tw.LW)
= 588238.1 N
= 588.2381 KN

Ru
Beban Balok Lt 1

DL 4.8584
LL 0
1,4 DL 6.80176
1,2 DL 5.83008
1,2 DL + 1,6 LL 5.83008

Ru < φ Rnw
5.83008 < 588.2381 OK
Kolom Lantai 1 Kolom Lantai 2 Story 1 DL
Beban
P(KN) M(KNm) P(KN) M(KNm)
DL -26.7201 -0.3427 -10.5286 0.3543 LL
LL 0 0 0 0
1,4 DL -37.40814 -0.47978 -14.74004 0.49602 Story 2 DL
1,2 DL + 1,6 LL -32.06412 -0.41124 -12.63432 0.42516
LL
P max
M max
P max
M max
P max
M max
P max
M max