Anda di halaman 1dari 42

STANDAR SPLN D5.

004-1: 2012
Lampiran Surat Keputusan Direksi
PT PLN (PERSERO) PT PLN (PERSERO) No. xxx.K/DIR/2012

POWER QUALITY
(REGULASI HARMONISA, FLICKER DAN
KETIDAKSEIMBANGAN TEGANGAN)

PT PLN (PERSERO)
Jl. Trunojoyo Blok M-1/135 Kebayoran Baru
Jakarta Selatan 12160

i
STANDAR SPLN D5.004-1: 2012
Lampiran Surat Keputusan Direksi
PT PLN (PERSERO) PT PLN (PERSERO) No. xxx.K/DIR/2012

POWER QUALITY
(REGULASI HARMONISA, FLICKER DAN
KETIDAKSEIMBANGAN TEGANGAN)

PT PLN (PERSERO)
Jl. Trunojoyo Blok M-1/135 Kebayoran Baru
Jakarta Selatan 12160
POWER QUALITY
(REGULASI HARMONISA, FLICKER DAN
KETIDAKSEIMBANGAN TEGANGAN)

Disusun oleh:

Kelompok Bidang Distribusi Standardisasi


dengan Surat Keputusan Direksi
PT PLN (Persero) No. 277.K/DIR/2012

Kelompok Kerja Standardisasi


Regulasi Harmonisa (Power Quality)
dengan Surat Keputusan Direksi
PT PLN (Persero) No.082.K/DIR/2012

Diterbitkan oleh:
PT PLN (PERSERO)
Jl. Trunojoyo Blok M-1/135, Kebayoran Baru
Jakarta Selatan 12160
Sk Dir
Sk Dir
Susunan Kelompok Bidang Distribusi Standardisasi
Surat Keputusan Direksi PT PLN (Persero): No. 277.K/DIR/2012

1. Ir. Ratno Wibowo : Sebagai Ketua merangkap Anggota


2. Hendi Wahyono, ST : Sebagai Sekretaris merangkap Anggota
3. Ir. Dany Embang : Sebagai Anggota
4. Ir. Lukman Hakim : Sebagai Anggota
5. Ir. Adi Subagio : Sebagai Anggota
6. Ir. Zairinal Zainuddin : Sebagai Anggota
7. Ir. Pranyoto : Sebagai Anggota
8. Ir. Rutman Silaen : Sebagai Anggota
9. Ir. Iskandar Nungtjik : Sebagai Anggota
10. Ir. Satyagraha A K, ST : Sebagai Anggota
11. Ir. Indradi Setiawan : Sebagai Anggota
12. Ir. Ignatius Rendroyoko. M.EngSc : Sebagai Anggota

Susunan Kelompok Kerja Standardisasi


Regulasi Harmonisa (Power Quality)
Keputusan Direksi PT PLN (Persero): No.082.K/DIR/2012

1. Ir. Ignatius Rendroyoko.M.Eng.Sc : Sebagai Ketua merangkap Anggota


2. M. Firmansyah, ST, MT : Sebagai Sekretaris merangkap Anggota
3. Ir.Anang Mawardi,MT : Sebagai Anggota
4. Ir. Victor T. Sitorus : Sebagai Anggota
5. Ir. Iskandar Nungtjik : Sebagai Anggota
6. Hendi Wahyono, ST : Sebagai Anggota
7. Ir. M. Rusli.MM.MT : Sebagai Anggota
8. Ir.. Bob Saril. M.Eng.Sc : Sebagai Anggota
9. Tri Wahyudi, ST.MM : Sebagai Anggota
10. Ir. Isfaisal : Sebagai Anggota
SPLN D5.004-1: 2012

Daftar Isi

Daftar Isi ...................................................................................................................................... i


Daftar Gambar............................................................................................................................ ii
Daftar Tabel................................................................................................................................ iii
Daftar Lampiran.......................................................................................................................... iii
Prakata .......................................................................................................................................v
1 Ruang Lingkup .................................................................................................................... 1
2 Tujuan ................................................................................................................................. 1
3 Acuan Normatif ................................................................................................................... 1
4 Istilah dan Definisi ............................................................................................................... 2
4.1 Harmonisa ................................................................................................................. 2
4.2 Batasan Nilai Harmonisa ........................................................................................... 2
4.3 Distorsi Harmonisa..................................................................................................... 2
4.4 Distorsi Harmonisa Individu ....................................................................................... 2
4.5 Distorsi Harmonisa Total (THD) ................................................................................. 2
4.6 Distorsi Harmonisa Tegangan Total (THDv) .............................................................. 2
4.7 Distorsi Harmonisa Arus Total (THDi)........................................................................ 3
4.8 Distorsi Arus Total (Total Demand Distortion - TDD) ................................................. 3
4.9 Hertz .......................................................................................................................... 3
4.10 Pelanggan .................................................................................................................. 3
4.11 Beban Non Linier ....................................................................................................... 3
4.12 Meter Energi Listrik .................................................................................................... 3
4.13 Titik Sambung Pelanggan atau Titik Transaksi (Point of Common Coupling) ........... 4
4.14 Daya Aktif .................................................................................................................. 4
4.15 Faktor Daya ............................................................................................................... 4
4.16 Faktor Bobot (Weighting Factor - Wi)......................................................................... 4
4.17 Filter Aktif ................................................................................................................... 4
4.18 Filter Pasif .................................................................................................................. 4
4.19 Kelip Tegangan (Flicker) ............................................................................................ 4
4.20 Depresi Tegangan Hubung Singkat (DTHS).............................................................. 4
4.21 Ketidakseimbangan Tegangan .................................................................................. 5
5 Regulasi Harmonisa ............................................................................................................ 5
5.1 Batasan Nilai Harmonisa ........................................................................................... 6
5.1.1 Batasan Distorsi Harmonisa Tegangan ......................................................... 6
i
SPLN D5.004-1: 2012

5.1.2 Batasan Distorsi Harmonisa Arus .................................................................. 6


6 Pengukuran dan Penilaian (Assesment) Harmonisa........................................................... 8
6.1 Titik Pengukuran ........................................................................................................ 8
6.2 Pengukuran Harmonisa Tegangan dan Arus............................................................. 8
6.2.1 Pengukuran Harmonisa Tegangan ................................................................ 8
6.2.2 Pengukuran Harmonisa Arus ......................................................................... 9
6.2.3 Durasi Pengukuran Harmonisa ...................................................................... 9
6.3 Peralatan Pengukuran Harmonisa ............................................................................. 9
6.3.1 Jenis Peralatan Pengukuran Harmonisa........................................................ 9
6.4 Penilaian (Assesment) Harmonisa........................................................................... 10
6.4.1 Prosedur Tahap 1 ........................................................................................ 11
6.4.2 Prosedur Tahap 2 ........................................................................................ 13
7 Mitigasi Pengaruh Harmonisa ........................................................................................... 13
7.1 Kewajiban Pelanggan dan Utilitas ........................................................................... 13
7.1.1 Kewajiban Pihak Pelanggan ........................................................................ 13
7.1.2 Kewajiban PLN / Pihak Utilitas ..................................................................... 14
7.2 Mitigasi Pengaruh Harmonisa .................................................................................. 14
8 Kelip Tegangan (Flicker) dan Fluktuasi Tegangan............................................................ 14
8.1 Depresi Tegangan Hubung Singkat ......................................................................... 14
8.2 Kelip Tegangan (Flicker) .......................................................................................... 15
8.3 Mitigasi Pengaruh Kelip Tegangan (Flicker) dan Fluktuasi Tegangan .................... 18
9 Ketidakseimbangan Tegangan (Voltage Unbalance) ........................................................ 18
9.1 Batasan Ketidakseimbangan Tegangan .................................................................. 18
9.2 Mitigasi Pengaruh Tegangan Tidak Seimbang ........................................................ 18

Daftar Gambar

Gambar 1 Harmonisa Pada Tegangan dan Arus Terukur Pada Instalasi Peleburan
Logam ................................................................................................................. 5
Gambar 2 Pengukuran pada Titik Transaksi Pelanggan ..................................................... 8
Gambar 3 Prosedur Evaluasi Harmonisa Pada Titik Sambung Pelanggan ....................... 11
Gambar 4 Kurva Flicker Pada Fluktuasi Perubahan Tegangan ........................................ 16
Gambar 5 Gelombang RMS Fluktuasi Tegangan (Flicker) ................................................ 16
Gambar 6 Contoh hasil pengukuran Flicker (dalam % Plt) ................................................ 17

ii
SPLN D5.004-1: 2012

Daftar Tabel

Tabel 1 Batasan Harmonisa Tegangan...................................................................................... 6


Tabel 2 Batasan Distorsi Harmonisa Arus ................................................................................. 7
Tabel 3 Nilai faktor bobot untuk beberapa tipe beban penghasil Harmonisa .......................... 12
Tabel 4 Batasan Depresi Tegangan Hubung Singkat (DTHS) ................................................. 15
Tabel 5 Level Kompatibilitas untuk Flicker pada Sistem TR dan Level Tahap
Perencanaan untuk Flicker pada Sistem TM dan TT .................................................. 17

Daftar Lampiran

LAMPIRAN 1 CONTOH PERHITUNGAN ARUS HUBUNG SINGKAT PADA TITIK


SAMBUNG PELANGGAN ................................................................................ 19
LAMPIRAN 2 CONTOH PELAKSANAAN ASSESMENT HARMONISA DI SUATU
INSTALASI ....................................................................................................... 21
LAMPIRAN 3 CONTOH PERHITUNGAN DTHS .................................................................... 23

iii
SPLN D5.004-1: 2012

iv
SPLN D5.004-1: 2012

Prakata

Dengan banyaknya penggunaan peralatan listrik non-linier yang menggunakan teknologi


peralatan berbasis switching elektronik seperti: komputer, programmable logic control (PLC),
adjustable speed drive (ASD), pulse width modulation (PWM), peralatan tanur induksi
(induction furnace), tanur busur listrik (arc furnace) dan peralatan listrik berbasis switching
elektronik lainnya, yang menyebabkan distorsi harmonisa arus pada titik sambung pelanggan
dan sistem tenaga listrik dan yang selanjutnya akan berdampak pada kualitas listrik termasuk
distorsi tegangan.

Oleh karena itu, level distorsi harmonisa arus dan tegangan harus dibatasi dan dikendalikan
dengan cara menjaga level emisi harmonisa arus pada peralatan listrik non-linier serta
membatasi penyebaran pengaruh harmonisa ke seluruh sistem tenaga listrik.

Dalam pemenuhan kualitas listrik PLN berkewajiban untuk menjaga kualitas tegangan pada
sistem tenaga listrik yang memenuhi kriteria yang dipersyaratkan pada standar ini. PLN telah
melakukan kajian mengenai kondisi kualitas listrik pada titik sambung pelanggan maupun
pada jaringan PLN.

Untuk menjaga kualitas listrik sesuai yang dipersyaratkan maka diperlukan penerapan standar
Power Quality (Regulasi Harmonisa, Flicker dan Ketidakseimbangan) ini.

v
SPLN D5.004-1: 2012

Power Quality
(Regulasi Harmonisa, Flicker dan Ketidakseimbangan Tegangan)

1 Ruang Lingkup

Standar ini disusun untuk menetapkan batasan maksimum level distorsi harmonisa yang
diperbolehkan di titik sambung pelanggan pada jaringan tegangan rendah (TR), tegangan
menengah (TM) dan tegangan tinggi (TT), termasuk prosedur pengukuran, langkah
evaluasi/penilaian dan mitigasi distorsi harmonisa pada titik sambung pelanggan.

Standar ini juga menetapkan batasan maksimum: ketidakseimbangan tegangan dan fluktuasi
tegangan yang dinyatakan dalam depresi tegangan hubung singkat (DTHS) pada titik
sambung pelanggan, serta Kelip Tegangan (Flicker), termasuk prosedur pengukuran dan
langkah evaluasi/penilaian, serta langkah mitigasi pada titik sambung pelanggan.

2 Tujuan

Sebagai pedoman umum dalam penetapan syarat dan kondisi kelistrikan yang harus dipenuhi
pada perjanjian jual beli tenaga listrik, dalam mengatur nilai batasan distorsi harmonisa, flicker
dan ketidakseimbangan tegangan, melakukan pengukuran pada titik sambung pelanggan dan
melakukan langkah-langkah mitigasinya.

3 Acuan Normatif

Dokumen-dokumen referensi/acuan berikut sangat diperlukan dalam penggunaan standar ini.


Untuk referensi yang bertanggal, maka hanya terbitan tersebut yang berlaku sedangkan
referensi yang tidak bertanggal, yang berlaku adalah terbitan terakhir dari dokumen referensi
tersebut (termasuk amandemennya).

a. IEEE Standard 519-1992 Recommended Practices and Requirements for Harmonic


Control in Electrical Power System;
b. IEEE Standard 1453-2004 Recommended Practice for Measurement and Limits of
Voltage Fluctuations and Associated Light Flicker on AC Power Systems;
c. IEEE Standard 1159-1995 Recommended Practice for Monitoring Electric Power Quality;
d. IEC 61000-3-6 Limits Assessment of emission limits for the connection of distorting
installations to MV, HV and EHV power systems;
e. IEC 61000-3-7 Limits Assessment of emission limits for the connection of fluctuating
installations to MV, HV and EHV power systems;
f. IEC 61000-4-7 Testing and measurement techniques General guide on harmonics and
interharmonics measurements and instrumentation, for power supply systems and
equipment connected thereto;
g. IEC 61000-4-13 Testing and measurement techniques Harmonics and interharmonics
including mains signalling at a.c. power port, low frequency immunity tests;
h. IEC 61000-4-15 (1997-11) EMC Part 4 Testing and measurement techniques section
15 : Flickermeter Functional and design specification;
i. IEC 61000-4-27, Electromagnetic compatibility Part 427: Testing and
measurement techniques Unbalance, immunity test, 2000;
j. IEC 61000-4-30 Testing and measurement techniques Power quality measurement
methods;
k. EN 50160 - Voltage Characteristic in Public Distribution Systems;

1
SPLN D5.004-1: 2012

l. Engineering Recommendation G5/4-1;


m. Aturan Distribusi Tenaga Listrik, Permen ESDM No. 4 Tahun 2009;
n. Aturan Jaringan Tenaga Listrik Jawa Madura Bali Tahun 2007;
o. Aturan Jaringan Sistem Sumatera Tahun 2009;
p. SPLN 1: 1995, Tegangan-Tegangan Standar;
q. SPLN D5.001: 2008, Pedoman Pemilihan dan Penggunaan Meter Energi Listrik;
r. SPLN D3.014-1: 2009, Transformator Instrumen Untuk Sistem Distribusi,
Bagian 1: Transformator Arus;
s. SPLN D3.014-2: 2010, Transformator Instrumen Untuk Sistem Distribusi,
Bagian 2: Transformator Tegangan Induktif.

4 Istilah dan Definisi

4.1 Harmonisa

Gelombang sinusoidal tegangan atau arus yang besar frekuensinya merupakan kelipatan
bulat dari frekuensi dasar. Harmonisa timbul disebabkan oleh beban non-linier yang terhubung
pada sistem tenaga listrik.

4.2 Batasan Nilai Harmonisa

Batas nilai maksimum harmonisa yang diperbolehkan terjadi pada suatu titik sambung
pelanggan atau titik sambung peralatan pada sistem tenaga listrik.

4.3 Distorsi Harmonisa

Deviasi gelombang sinusoidal 50 Hz pada gelombang tegangan atau arus yang disebabkan
oleh komponen harmonisa.

4.4 Distorsi Harmonisa Individu

Rasio nilai RMS komponen harmonisa orde tertentu terhadap nilai RMS komponen
fundamental.

Ihd

4.5 Distorsi Harmonisa Total (THD)

Rasio penjumlahan nilai RMS seluruh komponen harmonisa hingga orde tertentu terhadap
nilai RMS komponen fundamental.

4.6 Distorsi Harmonisa Tegangan Total (THDv)

Rasio penjumlahan nilai RMS seluruh komponen harmonisa tegangan hingga orde tertentu
terhadap nilai RMS komponen tegangan fundamental.

2
SPLN D5.004-1: 2012

x 100%

4.7 Distorsi Harmonisa Arus Total (THDi)

Rasio penjumlahan nilai RMS seluruh komponen harmonisa arus hingga orde tertentu
terhadap nilai RMS komponen arus fundamental.

4.8 Distorsi Arus Total (Total Demand Distortion - TDD)

Rasio jumlah akar kuadrat nilai RMS komponen harmonisa arus hingga orde tertentu terhadap
nilai RMS arus beban maksimum.

4.9 Hertz

Satuan dari frekuensi yang dinyatakan dalam putaran (cycle) per detik.

4.10 Pelanggan

Suatu individu, badan, perusahaan, atau institusi pemerintah yang mendapatkan pelayanan
sambungan tenaga listrik.

4.11 Beban Non Linier

Beban atau peralatan listrik yang menghasilkan arus yang tidak sinusoidal ketika disuplai oleh
tegangan yang sinusoidal.

4.12 Meter Energi Listrik

Instrumen ukur arus bolak balik yang digunakan untuk mengukur besarnya energi listrik
dengan cara penggabungan antara daya dan besaran-besaran listrik lainnya terhadap waktu.

3
SPLN D5.004-1: 2012

4.13 Titik Sambung Pelanggan atau Titik Transaksi (Point of Common Coupling)

Titik terdekat dimana instalasi milik pelanggan disambungkan kepada terminal dan meter
transaksi milik utilitas atau PLN.

4.14 Daya Aktif

Besar daya nyata yang disalurkan ke beban listrik.

4.15 Faktor Daya

Besar rasio antara daya aktif (kW) dan daya total (kVA).

Dimana P: daya aktif total, dan S1: daya semu total

Dimana P1: daya aktif fundamental, dan S1: daya semu fundamental

4.16 Faktor Bobot (Weighting Factor - Wi)

Faktor yang memperhitungkan kontribusi distorsi harmonisa dari sebuah tipe peralatan.

4.17 Filter Aktif

Peralatan elektronika daya yang dapat memproduksi komponen harmonik yang


mengkompensasi komponen harmonik dari beban nonlinier.

4.18 Filter Pasif

Peralatan berupa rangkaian listrik yang terdiri dari induktor dan kapasitor yang secara khusus
disetel untuk mengeliminasi harmonisa arus tertentu.

4.19 Kelip Tegangan (Flicker)

Impresi ketidak-stabilan pada sensasi visual yang terlihat melalui cahaya lampu dan timbul
karena variasi perubahan tegangan dengan amplitudo di bawah 10% dari nilai nominal
tegangan sistem.

4.20 Depresi Tegangan Hubung Singkat (DTHS)

Perbandingan antara MVA hubung singkat tanur terhadap MVA hubung singkat titik sambung
bersama.

4
SPLN D5.004-1: 2012

4.21 Ketidakseimbangan Tegangan

Rasio dari komponen tegangan urutan negatif atau nol dengan komponen tegangan urutan
positif. Ketidakseimbangan tegangan dihitung dengan perbandingan antara tegangan urutan
negatif ( ) terhadap tegangan urutan positif ( ) yang diukur pada titik sambung pelanggan.

5 Regulasi Harmonisa

Harmonisa timbul akibat adanya beban non-linier yang tersambung pada sistem tenaga listrik.
Beban non-linier seperti komputer, programmable logic control (PLC), variable speed drive
(VSD), pulse width modulation (PWM), peralatan tanur induksi (induction furnace), tanur busur
listrik (arc furnace), konverter, ballast elektronik untuk lampu neon, las listrik, dll menimbulkan
arus harmonisa pada jaringan distribusi listrik yang menyebabkan distorsi harmonisa tegangan
pada jaringan tenaga listrik. Distorsi harmonisa ini mengakibatkan terganggunya operasi
peralatan antara lain: komputer, transformator, motor-motor, kabel listrik, peralatan kontrol
elektronik yang terhubung pada jaringan yang sama.

Harmonisa arus dapat menyebabkan penurunan faktor daya (PF - true power factor) meski
faktor daya fundamental-nya (cos phi) tetap baik. Pada perhitungan faktor daya, akan lebih
tepat menggunakan rumusan PF (true power factor) karena sudah mengakomodir pengaruh
harmonisa.

Karena itu level harmonisa arus di titik sambung pelanggan harus dijaga agar tidak melebihi
batasan tertentu sehingga level harmonisa tegangan diseluruh sistem tenaga listrik masih
memenuhi persyaratan.

Gambar 1 Harmonisa Pada Tegangan dan Arus Terukur Pada Instalasi Peleburan Logam

5
SPLN D5.004-1: 2012

5.1 Batasan Nilai Harmonisa

PLN berkewajiban untuk menjaga kualitas tegangan pada sistem tenaga listrik dalam batas
seperti tercantum pada tabel 1 dan kondisi pelanggan dapat memenuhi batasan distorsi
harmonisa arus seperti tercantum pada tabel 2.

5.1.1 Batasan Distorsi Harmonisa Tegangan

Batasan distorsi harmonisa tegangan untuk tingkat tegangan sistem yang berbeda ditunjukkan
pada tabel 1 dibawah ini.

Tabel 1 Batasan Harmonisa Tegangan

Distorsi Harmonisa
Tegangan Pada Titik Distorsi Harmonisa
Tegangan Total THDVn
Sambung (Vn) Tegangan Individu (%)
(%)
Vn 66 kV 3.0 5.0
66 kV < Vn 150 kV 1.5 2.5
Vn > 150 kV 1.0 1.5

CATATAN: Tabel diatas berlaku untuk tegangan sesuai SPLN No. 1 Tahun 1995, Tegangan-Tegangan
Standar

Distorsi Harmonisa Tegangan Total atau THDVn dihitung berdasarkan rumusan sebagai
berikut:

Dimana: Vh = besar komponen harmonisa individu (rms volt)


h = orde harmonisa
Vn = Tegangan nominal sistem (rms volt)

5.1.2 Batasan Distorsi Harmonisa Arus

Pelanggan harus menjaga distorsi harmonisa arus pada titik sambung pelanggan di bawah
batas yang ditentukan dalam Tabel 2 sesuai pedoman IEEE Standard 519-1992
Recommended Practices and Requirements for Harmonic Control in Electrical Power
Systems.

6
SPLN D5.004-1: 2012

Tabel 2 Batasan Distorsi Harmonisa Arus

Batasan distorsi harmonisa arus

Vn 66kV
Distorsi Harmonisa Arus Maksimum dalam Persen IL
Ihs/IL Orde Harmonisa Individu h Harmonisa Ganjil Total
Demand
h < 11 11h<17 17h<23 23h<35 35h Distortion
< 20 4.0% 2.0% 1.5% 0.6% 0.3% 5.0%
20 50 7.0% 3.5% 2.5% 1.0% 0.5% 8.0%
50 100 10.0% 4.5% 4.0% 1.5% 0.7% 12.0%
100 1000 12.0% 5.5% 5.0% 2.0% 1.0% 15.0%
>1000 15.0% 7.0% 6.0% 2.5% 1.4% 20.0%
66 kV Vn 150 kV

Orde Harmonisa Individu h Harmonisa Ganjil Total


Demand
Ihs/IL
h < 11 11h<17 17h<23 23h<35 35h Distortion
(TDD)
< 20 2.0% 1.0% 0.75% 0.3% 0.15% 2.5%
20 50 3.5% 1.75% 1.25% 0.5% 0.25% 4.0%
50 100 5.0% 2.25% 2.0% 0.75% 0.35% 6.0%
100 1000 6.0% 2.75% 2.5% 1.0% 0.5% 7.5%
>1000 7.5% 3.5% 3.0% 1.25% 0.7% 10.0%
Vn 150 kV

Orde Harmonisa Individu h Harmonisa Ganjil Total


Demand
Ihs/IL
< 11 11h<17 17h<23 23h<35 35h Distortion
(TDD)
< 20 2.0% 1.0% 0.75% 0.3% 0.15% 2.5%
20 50 3.5% 1.75% 1.25% 0.5% 0.25% 4.0%

CATATAN 1: Tegangan yang termasuk pada tabel diatas merujuk pada SPLN No. 1 Tahun 1995,
Tegangan-Tegangan Standar.
CATATAN 2: hal-hal yang menjadi perhatian antara lain,
1. Harmonisa genap dibatasi 25% dari Harmonisa ganjil diatasnya;
2. Distorsi arus searah (Direct Current DC) tidak diperbolehkan;
3. Aplikasi semua peralatan pembangkit listrik dibatasi oleh nilai-nilai distorsi arus diatas terlepas dari
rasio hubung singkat ISC / IL;
4. Isc adalah Arus hubung singkat maksimum di titik sambung pelanggan;
5. IL adalah Arus beban maksimum (dihitung berdasarkan daya kontrak);
6. TDD adalah Total Demand Distortion, distorsi harmonisa arus (%) dari arus beban maksimum
(diukur selama 15 menit).

7
SPLN D5.004-1: 2012

Nilai arus hubung singkat (Isc) dapat dihitung dengan menggunakan rumus berikut:

Dimana kVATF adalah daya terpasang kVA, Zpu per unit impedansi trafo pada daya terpasang
dan kV adalah tegangan nominal.

6 Pengukuran dan Penilaian (Assesment) Harmonisa

6.1 Titik Pengukuran

Batasan nilai harmonisa sebagaimana pada tabel 1 dan tabel 2 diatas ditujukan untuk evaluasi
level distorsi harmonisa pada titik sambung pelanggan (titik transaksi pelanggan).

Pengukuran Harmonisa pada titik sambung pelanggan tersebut dapat dilihat pada gambar 1.

Gambar 2 Pengukuran pada Titik Transaksi Pelanggan

6.2 Pengukuran Harmonisa Tegangan dan Arus

Pengukuran Harmonisa Tegangan dan Arus dilakukan sesuai IEC 61000-4-7 Harmonics dan
Inter-Harmonics Measurement.

6.2.1 Pengukuran Harmonisa Tegangan

Pada sistem tegangan rendah pengukuran harmonisa tegangan dilakukan secara langsung.
Pada tegangan yang lebih tinggi, yaitu pada tegangan menengah (medium voltage MV) atau
tegangan tinggi (high voltage HV) pengukuran harmonisa dilakukan secara tidak langsung
dengan menggunakan trafo tegangan (PT).

Pada pelaksanaan pengukuran harmonisa tegangan ini diperhatikan beberapa hal sebagai
berikut:

1. Besaran pengukuran harmonisa tegangan adalah: Distorsi Harmonisa Tegangan


Individu (IHDV) dan Distorsi Harmonisa Tegangan Total (Total Harmonic Distortion
THDV);

8
SPLN D5.004-1: 2012

2. Pengukuran dilakukan dengan langsung mengukur nilai prosentase setiap


komponen harmonisa tegangan dan prosentase distorsi harmonisa tegangan total;
3. Pada pengukuran tidak langsung dengan menggunakan trafo tegangan (PT), maka
trafo tegangan tersebut harus memiliki karakteristik frekuensi respon yang baik
dengan bandwith sampai dengan 3150 Hz. Karakteristik trafo tegangan (PT) yang
digunakan mengacu pada SPLN No. D3.014-2 Tahun 2010.

6.2.2 Pengukuran Harmonisa Arus

Pada pelaksanaan pengukuran Harmonisa arus ini perlu diperhatikan beberapa hal sebagai
berikut:

1. Besaran pengukuran harmonisa arus adalah: distorsi harmonisa arus Individu (IHDi)
dan distorsi harmonisa arus demand total (Total Demand Distortion TDD);
2. Pengukuran dilakukan dengan mengukur besaran ampere absolut untuk arus
fundamental dan besaran setiap komponen harmonisa arus;
3. Pada pengukuran ini perlu diperhatikan juga tentang karakteristik trafo arus (CT).
Karakteristik respons frekuensi dari trafo arus harus dievaluasi untuk setiap
pengukuran yang dilakukan. Peralatan trafo arus (CT) yang digunakan memiliki
atenuasi kurang dari 3dB dengan bandwidth sampai dengan 3150 Hz. Kelas trafo
arus (CT) yang digunakan mengacu pada SPLN No. D3.014-1 Tahun 2009.

6.2.3 Durasi Pengukuran Harmonisa

Pengukuran harmonisa dilakukan pada periode waktu tertentu untuk mendapatkan


karakteristik level harmonisa. Pengukuran dengan periode waktu ini dilakukan untuk
kebutuhan assesment instalasi pelanggan dan dalam rangka penyambungan baru dan
perubahan daya. Pengukuran Harmonisa dilaksanakan dengan kondisi sebagai berikut:

1. Dilaksanakan selama periode minimum 7 (tujuh) hari pada kondisi instalasi beban
listrik beroperasi dengan beban dan siklus normal;
2. Minimum 95% dari data pengukuran harus memenuhi batasan yang dipersyaratkan
pada tabel 1 dan tabel 2 diatas.

6.3 Peralatan Pengukuran Harmonisa

Peralatan pengukuran harmonisa digunakan untuk mengukur besar harmonisa individu dan
distorsi harmonisa total (total harmonic distortion) sampai orde harmonisa ke 63.

6.3.1 Jenis Peralatan Pengukuran Harmonisa

Pengukuran harmonisa dilakukan dengan menggunakan meter energi transaksi yang memiliki
karakteristik sebagai berikut:

1. Kemampuan pengukuran energi sesuai IEC 62053-22;


2. Kemampuan pengukuran harmonisa sesuai EN 50160 dan/atau IEC 61000-4-7
Testing and measurement techniques General guide on harmonics and
interharmonics measurements and instrumentation dan/atau IEEE 1159-1995
Recommended Practice for Monitoring Electric Power Quality.

9
SPLN D5.004-1: 2012

Dalam hal tertentu dan atas kesepakatan antara pihak PLN dan pihak Pelanggan, untuk
pengukuran harmonisa dapat juga menggunakan jenis peralatan sebagai berikut:

1. Peralatan Analisa Harmonisa Portabel;


2. Peralatan Power Quality Monitoring (Power Quality Monitoring Devices).

Kedua jenis peralatan pengukuran harmonisa diatas juga wajib memiliki kemampuan
pengukuran harmonisa sesuai butir 6.3.1 ayat 2 diatas.

6.4 Penilaian (Assesment) Harmonisa

Langkah-langkah dan tahapan penilaian (assesment) harmonisa untuk pelanggan eksisting


dan pelanggan baru (calon pelanggan) dilaksanakan dengan merujuk kepada aturan IEEE
Standard 519-1992 Recommended Practices and Requirements for Harmonic Control in
Electrical Power Systems.

Langkah-langkah asesmen tersebut mengikuti prosedur 2 (dua) tahap yang dapat


diilustrasikan seperti gambar 2 berikut ini.

10
SPLN D5.004-1: 2012

Gambar 3 Prosedur Evaluasi Harmonisa Pada Titik Sambung Pelanggan

Persyaratan evaluasi dari dua tahapan tersebut dijelaskan secara rinci seperti di bawah ini.

6.4.1 Prosedur Tahap 1

Pada tahap 1 ini, harmonisa dari pelanggan dengan jumlah beban penghasil harmonisa yang
kecil dapat langsung diterima tanpa harus dilakukan evaluasi secara rinci mengenai
karakteristik beban pembangkit harmonik.

Untuk penilaian tahap 1 ini dilakukan dengan menghitung jumlah beban yang menyebabkan
harmonisa (weighted disturbing load) yang disebut SDW (jumlah beban yang menyebabkan
harmonisa dalam fasilitas pelanggan).

11
SPLN D5.004-1: 2012

Dimana :
SDi adalah Daya individu dari beban yang menyebabkan harmonisa
Wi adalah faktor dari beban yang menyebabkan harmonisa

Kelulusan dari prosedur evaluasi tahap 1 adalah dengan membandingkan antara besar beban
yang menyebabkan harmonisa dan besar daya kapasitas hubung singkat di titik sambung
pelanggan dengan nilai sebagai berikut:

Langkah penilaian (assesment) Harmonisa dengan melakukan prosedur tahap 1 ini secara
prinsip dapat dilakukan untuk pelanggan listrik eksisting dan untuk pelanggan baru (calon
pelanggan).

Tabel 3 Nilai faktor bobot untuk beberapa tipe beban penghasil Harmonisa

Tipe Beban Bentuk Gelombang Distorsi Arus Faktor Bobot (W1)

Catu daya satu fase 80% 2.5

Pada beban
parsial terjadi
Semi Konverter harmonisa 2.5
ke-2, ke-3
dan ke-4

Konverter 6-pulsa,
Capasitive Smoothing, 80 % 2.0
Tanpa induktansi seri

Konverter 6-pulsa,
Capasitive Smoothing,
40 % 1.0
Dengan induktansi seri
> 3% atau DC drive

Konverter 6-pulsa,
dengan kapasitas
28 % 0.8
induktor besar untuk
Current Smoothing

12
SPLN D5.004-1: 2012

Konverter 12-pulsa 15 % 0.5

Bervariasi
Voltage Regulator (AC) tergantung 0.7
sudut firing

Lampu Fluoresen - 17 % 0.5

6.4.2 Prosedur Tahap 2

Evaluasi tahap 2 dilakukan apabila kondisi evaluasi tahap 1 tidak terpenuhi. Untuk pelanggan
eksisting, pelaksanaan evaluasi/assesment tahap 2 dilakukan dengan melakukan pengukuran
harmonisa individu untuk tegangan dan arus, distorsi harmonisa demand total (TDD) dan
distorsi harmonisa tegangan total (THDV) pada titik sambung pelanggan. Hasil pengukuran
tersebut kemudian dibandingkan dengan batasan harmonisa tegangan dan arus yang
tercantum pada tabel 1 dan tabel 2 diatas.

Apabila hasil pengukuran Harmonisa tidak memenuhi batasan harmonisa maka pelanggan
wajib memasang peralatan kompensator harmonisa untuk mengurangi distorsi harmonisa
sampai dibawah batasan yang dipersyaratkan.

Untuk pelanggan baru (calon pelanggan), analisa kesesuaian batasan harmonisa dilakukan
dengan menggunakan perhitungan atau simulasi yang dapat mengevaluasi sesuai Standar
IEEE 519 - 1992. Hasil keluaran yang diperlukan dari simulasi tersebut adalah nilai IHDV, IHDI,
THDV, dan TDD dimana hasil keluaran tersebut dibandingkan kesesuaiannya dengan batasan
sesuai tabel 1 dan tabel 2.

Apabila hasil simulasi tidak memenuhi batasan harmonisa maka calon pelanggan listrik wajib
menyiapkan langkah-langkah untuk perbaikan distorsi harmonisa sehingga mencapai batasan
harmonisa yang diperbolehkan.

7 Mitigasi Pengaruh Harmonisa

Bila level harmonisa pada titik sambung pelanggan melebihi batasan harmonisa sesuai tabel 1
dan tabel 2, maka pelanggan wajib melakukan langkah-langkah mitigasi level harmonisa
sehingga dapat memenuhi ketentuan batasan tersebut dalam semua kondisi pembebanan.

7.1 Kewajiban Pelanggan dan Utilitas

7.1.1 Kewajiban Pihak Pelanggan

Pelanggan harus bertanggung jawab untuk menjaga level harmonisa arus di bawah batas
yang ditentukan dalam tabel 2 pada titik sambung atau titik transaksi.
13
SPLN D5.004-1: 2012

7.1.2 Kewajiban PLN/Pihak Utilitas

PLN atau pihak Utilitas berkewajiban untuk menjaga kualitas tegangan pada sistem tenaga
listrik yang memenuhi level standar yang dipersyaratkan selama emisi distorsi harmonisa arus
di titik sambung pelanggan memenuhi batasan yang dipersyaratkan.

7.2 Mitigasi Pengaruh Harmonisa

Mitigasi harmonisa arus pada suatu sistem tenaga listrik pelanggan dapat dilakukan dengan
cara sebagai berikut:

1. Pemisahan peralatan yang menghasilkan harmonisa pada instalasi pelanggan


terpisah dari beban lainnya.

2. Pemasangan Filter Pasif


Langkah-langkah untuk mengurangi level harmonisa arus dapat dilakukan
dengan pemasangan filter pasif. Pada pemasangannya, filter pasif dapat
dipasang secara seri dan secara parallel (shunt).

3. Pemasangan Filter Aktif


Filter aktif dipasang untuk memberikan kompensasi untuk komponen harmonisa
pada sistem tenaga listrik berdasarkan level harmonisa yang ada pada saat
tertentu.

4. Pemilihan Hubungan Belitan Trafo


Dengan memilih hubungan belitan tertentu pada trafo daya dan trafo distribusi
akan dapat mengurangi distorsi harmonisa arus untuk beberapa orde harmonisa
(dengan memakai belitan stabilizer delta atau belitan zig-zag).

5. Relokasi Shunt Capacitor Banks


Level distorsi harmonisa yang berlebihan pada suatu sistem tenaga listrik
berhubungan dengan kondisi resonansi yang mungkin disebabkan penempatan
kapasitor bank pada lokasi yang kurang tepat. Untuk itu dapat dilakukan dengan
melakukan pemindahan lokasi kapasitor bank ke titik lokasi yang lebih tepat
ataupun dengan mengubah kapasitas kapasitor bank.

6. Pemindahan sambungan instalasi pelanggan ke instalasi dengan level hubung


singkat yang lebih tinggi.

8 Kelip Tegangan (Flicker) dan Fluktuasi Tegangan

8.1 Depresi Tegangan Hubung Singkat

Drop tegangan akibat beban industri yang berfluktuasi biasa disebut kelip tegangan atau
flicker. Drop tegangan di atas dinyatakan dengan Depresi Tegangan Hubung Singkat (DTHS)
dengan batasan seperti tercantum pada tabel 4 dibawah ini:

14
SPLN D5.004-1: 2012

Tabel 4 Batasan Depresi Tegangan Hubung Singkat (DTHS)

Level Tegangan DTHS (%)

150kV 2.5
66 kV 2.75
20kV 3.0

DTHS untuk sebuah tanur busur (arc furnace) dapat dihitung dengan persamaan sebagai
berikut:

Dimana :
Sf = MVA hubung singkat tanur busur = (MVA tanur busur/Xf)
Xf = Reaktansi tanur busur dalam keadaan operasi beban maksimum, dihitung dari titik
sambung.
Sj = MVA hubung singkat jaringan pada titik sambung pada kondisi pembangkitan
minimum.

Drop tegangan pada sistem tenaga listrik dapat terjadi akibat beban industri yang dapat
menimbulkan fluktuasi tegangan, di antaranya adalah tanur busur listrik (arc furnace), beban
peleburan logam (smelter), las listrik (arc welders) dan beban sejenis lainnya.

8.2 Kelip Tegangan (Flicker)

Flicker adalah Impresi ketidak-stabilan pada sensasi visual yang diakibatkan oleh stimulasi
cahaya yang luminensinya atau distribusi spektrumnya berubah terhadap waktu akibat
fluktuasi tegangan oleh beban peralatan listrik seperti tanur busur listrik (arc furnace),
pengasutan motor dan siklus on/off dari beban listrik besar.

Terkait dengan kriteria kualitas tegangan, Flicker dapat diukur dengan menggunakan level Pst
(short term: besaran diukur setiap 10 menit) dan Plt (long term besaran diukur setiap 2
jam).

15
SPLN D5.004-1: 2012

Gambar 4 Kurva Flicker Pada Fluktuasi Perubahan Tegangan

CATATAN 1 : Nilai diatas diperoleh secara eksperimen dengan modulasi gelombang 60 Hz AC


CATATAN 2 : Mata manusia sangat sensitive terhadap fluktuasi tegangan pada 8Hz atau 16 kali
perubahan tegangan per detik
CATATAN 3 : Untuk dapat memenuhi batasan pada tabel 3.3.1, maka dV/V % harus dibawah kurva
Pst pada projected rate fluktuasi.

Contoh bentuk gelombang flicker dapat terlihat seperti pada gambar 5 dibawah ini:

Gambar 5 Gelombang RMS Fluktuasi Tegangan (Flicker)

16
SPLN D5.004-1: 2012

Tabel 5 Level Kompatibilitas untuk Flicker pada Sistem TR dan Level Tahap Perencanaan untuk
Flicker pada Sistem TM dan TT

Level
Level Tahap Perencanaan
Kompatibilitas

TR TM TT

Pst 1,0 0,9 0,8

Plt 0,8 0,7 0,6

Keterangan:

Pst = Pengukuran persepsi waktu singkat dari flicker untuk interval 10 menit
Plt = Pengukuran persepsi waktu panjang dari flicker untuk interval 2 jam

Plt dapat dihitung dengan rumusan sebagai berikut:

Batasan Flicker seperti tabel 5 diatas harus memenuhi dalam 95% rentang waktu pengukuran.
Periode pengukuran flicker tersebut dilakukan selama 1 (satu) minggu.
Sebagai contoh misalnya penyedia listrik menjamin Plt = 0,7%, maka hasil pengukuran variasi
tegangan setiap 10 menit selama seminggu, 95% nya harus masuk dalam range.
Contoh hasil pengukuran secara umum diperlihatkan pada gambar 6. Terlihat bahwa antara
tanggal 30/06/2010 pk 16.00 sampai tanggal 1/07/2010 pk 14.00 terjadi Plt > 2,5% serta
antara tanggal 1/07/2010 pk 16.00 sampai tanggal 2/7/2010 pk 12.00 terjadi Plt > 3,1%.

Gambar 6 Contoh hasil pengukuran Flicker (dalam % Plt)

17
SPLN D5.004-1: 2012

8.3 Mitigasi Pengaruh Kelip Tegangan (Flicker) dan Fluktuasi Tegangan

Mitigasi pengaruh Flicker dan fluktuasi tegangan dapat dilakukan dengan:

1. Memisahkan trafo tenaga instalasi yang menjadi sumber fluktuasi terhadap pelanggan-
pelanggan lain;
2. Memasang kompensator.

CATATAN: Untuk penilaian terhadap batasan Flicker dilaksanakan menurut standar IEC 61000-3-7.

9 Ketidakseimbangan Tegangan (Voltage Unbalance)

9.1 Batasan Ketidakseimbangan Tegangan

Ketidakseimbangan tegangan disebabkan oleh beban antar fasa yang tidak seimbang. Baik
akibat perbedaan beban antar fasa atau sifat beban dalam satu proses produksi yang
membebani setiap fasa pada waktu yang berbeda. Ketidakseimbangan tegangan
menyebabkan timbulnya tegangan urutan negatif dan tegangan urutan nol.

Dimana:
KT = Ketidakseimbangan Tegangan
= Tegangan Urutan Negatif
= Tegangan Urutan Positif

Batasan ketidakseimbangan tegangan rata-rata adalah maksimum 2 % dalam 95% rentang


waktu pengukuran. Periode pengukuran dilakukan selama 1 minggu dengan rentang
pengambilan waktu 10 menit. (Catatan: Pengukuran dengan periode pengukuran diatas
dianggap telah mewakili pengukuran untuk periode billing bulanan)

9.2 Mitigasi Pengaruh Tegangan Tidak Seimbang

Langkah-langkah untuk mengurangi pengaruh (mitigasi) ketidakseimbangan tegangan


dilakukan diantaranya adalah sebagai berikut:

1. Penyeimbangan beban pada instalasi pelanggan;


2. Pemindahan sambungan instalasi pelanggan ke instalasi dengan level hubung singkat
yang lebih tinggi;
3. Pemasangan peralatan kompesator (misal voltage compensator).

18
SPLN D5.004-1: 2012

LAMPIRAN 1 CONTOH PERHITUNGAN ARUS HUBUNG SINGKAT PADA TITIK SAMBUNG


PELANGGAN

Tabel 1A Formulasi perhitungan dalam Sistem per Unit

Data elemen rangkaian Formula untuk per Unit Sistem

Kapasitas Hubung Singkat


Busbar GI

Trafo

Penghantar

Contoh Perhitungan:

CONTOH I: Pelanggan Industri PT XYZ, terhubung ke GI ABC [1] pada tegangan 70 kV


melalui kabel XLPE Z: 0,03 Ohm. Data arus hubung singkat 3 fasa pada busbar GI ABC:
5,337 kA dan daya hubung singkat pada busbar GI = 5,337 kA * 70 kV * = 648,83 MVA


DenganMVABase10MVAdanBaseTegangan70kV

19
SPLN D5.004-1: 2012

Tabel 2A Perhitungan dalam sistem per unit

Komponen Perhitungan Hasil

Sumber: 648,83 MVA Zpu = 10/648,83


hubung singkat = 0,015459 pu

Trafo 50 MVA, Zpu=7/100x10/50


Z = 7% = 0,014 pu

2
Zpu=0.04x10/(20)
Penghantar
=0,001pu

Z=0,015459+0,014+
Impedansi total Z = Z sumber + Ztrafo + Z penghantar
0,001=0,030459pu
MVAsc pada titik MVAsc = 10 / 0,030459
sambung pelayanan
= 328,30039MVA
[3]
Arus Hubung Singkat
pada titik sambung (70x ) = 2,70777 kA
pelayanan

20
SPLN D5.004-1: 2012

LAMPIRAN 2 CONTOH PELAKSANAAN ASSESMENT HARMONISA DI SUATU INSTALASI

CONTOH I: Calon pelanggan terhubung pada GI ABC sisi 70 kV, Data arus hubung singkat 3
fasa pada GI ABC: 5,337 kA dan daya hubung singkat 651 MVA. dengan beban pada tabel:

Tabel 3A Perhitungan pelaksanaan assemen harmonisa pada instalasi pelanggan

Komponen (MVA)

DC Motor digerakkan
10 1 10
oleh DC Drive
Mesin Induksi
digerakkan dengan 3 2 6
inverter
Instalasi penerangan
dengan lampu 0,1 0,5 0,05
fluoresen
Komputer Ruang
Kendali dan 0,1 2,5 0,25
Perkantoran
Sistem Pendingin
dengan penggerak 0,5 2 1
Inverter

17, 3

17,3 / 651
= 0,026575
= 2,6575 %

Syarat kelulusan tahap I , karena untuk instalasi ini sebesar 2,6575%


maka harus dilakukan analisa tahap berikutnya menggunakan software simulasi.

CONTOH II: Calon pelanggan stasiun konverter KRL terhubung pada GI ABC sisi 20 kV
melalui Trafo. Data arus hubung singkat 3 fasa pada titik sambung pelanggan 2,69 KA dan
MVAsc sebesar 329 MVA dengan beban pada tabel:

Tabel 4A Perhitungan pelaksanaan assemen harmonisa pada instalasi pelanggan

(MVA)

Konverter penyearah 6
Pulsa dengan induktor 2 0,8 1,6
perata arus
Konverter penyearah
2 0,5 1
12 pulsa

21
SPLN D5.004-1: 2012

Instalasi penerangan
dengan lampu 0,05 0,5 0,025
fluoresen
Komputer Ruang
Kendali dan 0,02 2,5 0,5
Perkantoran
Sistem Pendingin
dengan penggerak 0,02 2 0,04
Inverter

3,165

3,165 / 329 = 0,00962


= 0,962 %

Syarat kelulusan tahap I , karena untuk instalasi ini sebesar 0,962 %


maka harus dilakukan analisa tahap berikutnya menggunakan software simulasi.

CONTOH III: Calon pelanggan gedung perkantoran hubung pada GI ABC sisi 20 kV melalui
Trafo, Data arus hubung singkat 3 fasa pada titik sambung pelanggan 2,69 KA dan MVAsc
sebesar 329 MVA dengan beban pada tabel:

Tabel 5A Perhitungan pelaksanaan assemen harmonisa pada instalasi pelanggan

(MVA)

Sistem Pendingin
dengan penggerak 0,05 2 0,1
Inverter
Instalasi penerangan
dengan lampu 0,01 0,5 0,005
fluorescent
Komputer Ruang
0,02 2,5 0,05
Perkantoran
Lift dengan motor
0,02 2 0,04
penggerak inverter

0,195

0,195 / 329
= 0,00059
= 0,0593 %

Syarat kelulusan tahap I , karena untuk instalasi ini sebesar 0,0593%


maka instalasi ini memenuhi syarat kelulusan.

22
SPLN D5.004-1: 2012

LAMPIRAN 3 CONTOH PERHITUNGAN DTHS

Penyambungan untuk suatu Konsumen Tanur Busur (Arc Furnace)

Data Pelanggan tanur: Kapasitas Trafo 15 MVA, Impedansi 10% dengan tahanan arc tanur:
0,05 . 20 kV/0,38 kV. Terhubung pada gardu induk (GI) dengan daya hubung singkat pada
titik sambung pelanggan 328 MVA.

Tabel 6A Perhitungan pelaksanaan assemen harmonisa pada instalasi pelanggan

Komponen Perhitungan Hasil

Zpu = 10/100 x 10/50


Trafo 15 MVA, Z = 10 %
= 0,02 pu

Zpu = 0.05 x 10/(0,38)2


Tahanan Tanur
= 3,463 pu

MVAsc = 15 /3,483
Impedansi total Z = Ztrafo + Z tanur
= 4,307 MVA
DTHS = 4,307 / 328
DTHS
= 0,013 = 1,3 %

DTHS untuk pelanggan tersebut sebesar 1,3% hingga masih memenuhi syarat DTHS untuk
pelanggan di titik 20 kV sebesar 3 %.

23
PPeennggeelloollaa SSttaannddaarrddiissaassii ::
PPTT PPLLN N ((PPeerrsseerroo)) PPuussaatt PPeenneelliittiiaann ddaann PPeennggeem mbbaannggaann KKeetteennaaggaalliissttrriikkaann
JJll.. D
Duurreennttiiggaa,, JJaakkaarrttaa 1122776600,, TTeellpp.. 002211--77997733777744,, FFaaxx.. 002211--77999911776622,,
www ww w..ppllnn--lliittbbaanngg..ccoo..iidd
Pengelola Standardisasi :
PT PLN (Persero) Pusat Penelitian dan Pengembangan Ketenagalistrikan
Jl. Durentiga, Jakarta 12760, Telp. 021-7973774, Fax. 021-7991762,
www.pln-litbang.co.id

PPeennggeelloollaa SSttaannddaarrddiissaassii ::
PPTT PPLLN N (Persero) Pusat PPeenneelliittiiaann ddaann PPeennggeem
( P e rs e ro ) P u s a t mbbaannggaann KKeetteennaaggaalliissttrriikkaann
JJll.. D
Duurreennttiiggaa,, JJaakkaarrttaa 1122776600,, TTeellpp.. 002211--77997733777744,, FFaaxx.. 002211--77999911776622,,
www ww w..ppllnn--lliittbbaanngg..ccoo..iidd

Anda mungkin juga menyukai