LAMPIRAN A: SPESIFIKASI TEKNIS SEKTOR AIR MINUM

NO PARAMETER STANDARD DAN SPESIFIKASI


1 Unit Air Baku 1. Peraturan Pemerintah No 82/2001 tentang Pengelolaan Kualitas Air
dan Pengendalian Pencemaran Air
2. Metode Pengambilan Contoh Kualitas Air, SNI 06-2412-1991
3. Metode analisa uji fisik, meliputi parameter:
 Suhu, SNI 19-1141-989
 Rasa, SNI 03-6859-2002
 Bau, SNI 03-6860-002
 pH, DHL, turbidity, warna, SNI M-03-1989
4. BOD /COD:
 Biochemical Oxygen Demand (BOD), SNI 06-2503-1991
 Chemical Oxygen Demand (COD), SNI 06-2504-1991
 Oxygen Demand (DO) SNI 06-2424-1991
5. Biologi:
 Coliform SNI 03-6858-2002.
6. Pengukuran debit, SNI 03-2414-1991
7. Penjernihan air (jika ada) mengikuti Peraturan pemerintah No 82/2001
tentang Pengelolaan Kualitas Air dan Pengendalian Pencemaran Air
8. Ketentuan yang disyaratkan oleh perijinan yang dikeluarkan oleh
Pemerintah
9. Fasilitas/bangunan pengambalian air tidak berdampak buruk pada
lingkungan sekitar
2 Unit Produksi 1. Perencanaan teknis instalasi pengolahan air minum konvensional
(lengkap secara proses) sesuai SNI 19-6774-2002 tentang Tata Cara
Perencanaan Unit Paket Instalasi Penjernihan Air.
2. Peraturan Menteri Kesehatan 492/2010
3 Perpipaan 1. Bahan/material perpipaan harus memenuhi standar berikut:
 PVC SNI 03-6419-2000
 SK SNI S-20-1990-2003
 SNI 06-4829-2005
 Pipe steel medium class BS 1387-67
 Pipe steel fabricated AWWA C 200 atau SNI-07-0822-1989 atau
 SII 2527-90 atau JIS G 3452 dan JIS G 3457
 Ductile Pipe ISO 2531 dan BS 4772
 Standar internasional lain
2. Pengujian pipa:
a. PIPA PVC:
 RSNI T-17-2004
 SNI 06-2550-1991
 SNI 06-2551-1991
 SNI 06-2552-1991
 SNI 06-2553-1991
 SNI 06-2554-1991
 SNI 06-2555-1991
 SNI 06-2556-1991
 SNI 06-2548-1991
 SNI 06-2549-1991.
b. Pipa Polietilena (PE)
 SNI 06-4829-2005

A-1
NO PARAMETER STANDARD DAN SPESIFIKASI
 SNI 19-6778-2002
 SNI 19-6779-2002
 SNI 19-6780-2002
 SNI 19-6781-2002
 SNI 19-6778-2002
 SNI 06-4821-1998
 ISO 6964-1986, Polyolefin pipes and fittings – Determination of
carbon black content by calcinations pyrolysis – Test method
and basic spesification
 ISO 11420 : 1996, Method for the assesment of the degree of
carbon black dispersion in polyolefin pipes, fittings and
compounds
 ISO 6259/1985, Pipe for polyethylene-Part 1: Determination of
tensile properties
 ISO 3126:1974, Plastic pipe-measurement of dimension ISO
1167:1996, Thermoplastic pipes for the conveyance of fluids –
resistance to internal pressure- Test Method
 ISO 1133:1991, Plastic – Determination of the melt mass flow
rate (MFR) and melt volume flow rate (MVR) of thermoplastics
 ISO 2505-1-1994, Thermoplastics pipe-Longitudinal reversion–
part 1:determination methods ISO 3607:19977/E, Tolerances
on outside diameters and wall thickenesses
 AS / NZS 4130:97, Polyethylene pipes for pressure aplication
 ASTM D 3350 – 1999, Standard spesification polyethylene
plastics pipe and fittings material
 JIS 6762 – 1998, Double wall polyethylene pipes for water
supply
c. Pipa besi dan baja;
 SNI 07-0068-1987
 SNI 0039-1987
 SNI 07-0242-1989
 SNI 07-0822-1989
 SNI 07-1338-1989
 SNI 07-0949-1991
 SNI 07-1769-1990
 SNI 07-1969-1991
 SNI 07-2255-1991
 SNI 07-3080-1991
 SNI 07- 3078-1992
 SNI 07-3073-1992
 SII 2527-90, Water Supply Steel Pipe
 ISO 7/1, Pipe Threads Where Pressuretight Joins are Made on
The Threads
 ISO 1459, Metalic croating-Protection Against Corrosion by Hot
Dip Galvanzing Guilding Principles
 ISO 1461 Metalic Coating Hot-Dip Galvanized Coating on
Fabricated Ferrous Products Requirments
 ASTM A 283F, Flow and Intermediate tensile Strenght Carbon
Steel Plates, Shapes and Bars

A-2
NO PARAMETER STANDARD DAN SPESIFIKASI
 ASTM A 570, Steel, Sheet and Strip, Carbon, Hot Rolled
Structural Quality
 AWWA C 200, Steel Water Pipe 6 Inches and Larger AWWA C
203, Coal-Tar Protective Coatings and Linings for Steel Water
Pipelines Enamel and Tape Hot Applied
 AWWA C 205, Cement Mortar Protective Lining and Coating
for Steel Water Pipe 4 Inches and Larger Shop Applied
 AWWA C 210, Liquid Epoxy Coating System for the Interior and
Exterior Steel Water Pipe
 JIS G 3101, Rolled Steel for General Structure
 JIS G 3452, Carbon Steel Pipes for Ordinary Piping
 JIS G 3457, Arc Welded Carbon Steel Pipe
 JIS B 2311, Steel Butt-Welding Pipe Fitting for Ordinary Use
 JIS G 3451, Fitting of Coating Steel Pipes for Water Service
 JIS G 550, Spheroidal Graphite Iron Castings
 JIS G 5702, Blackheart Malleable Iron Castings
 JIS G 3454, Carbon Steel Pipes for Pressure Service
 JIS K 6353, Rubber Goods Pipes for Water Works
d. Pipa Ductile
 ISO 2531
 BS 4772
e. Pipa GRP (Glass Fiber Reinforced Thermosetting Resin) Pressure
Pipe
 SNI -03-0445-1989
 SNI – 07-2053-1990
 SNI -03-6785-2002
 SNI -6-0084-2002
 ISO 7432:2002
 ISO 7509:2000
 ISO 8639:2000
 ISO 14828:2003
 ISO 15306:2003
 ISO 10467:2004 (E)
 ISO 10639:2004 (E)
 JIS A 5350
 ASTM D 3517 - 04
4 Mekanikal dan 1. Pompa
Elektrikal  Foundation slab concrete fc-22,5
 Foundation thickness:
o < 55,0 KW: 600 mm
o 55,0 – 75,0 KW: 750 mm
o 75,0 – 100,0 KW: 1000 mm
o > 100 KW, designed
2. Elektrikal
 SNI 04-0225-2000, Persyaratan Umum Instalasi Listrik (PUIL 2000)
 Standar IEE dan NEC
 British Standard Association (BS)
 Japan Industrial Standard (JIS)
 German Standard (VDE) and DIN

A-3
NO PARAMETER STANDARD DAN SPESIFIKASI
 Standar PLN (SPLN)
5 Bahan Kimia Spesifikasi air minum berdasarkan SNI dan standar internasional
 Berkualitas baik
 Food grade
 Standar SNI atau AWWA
 Mudah ditransportasikan
6 Pekerjaan Sipil 1. Semen: SNI NI-8/1972, ASTM C-150, SNI 15-2049-1994 untuk semen
portland
2. Agregat beton dan batu bata: ASTM-C33, SNI 03-1750-1990, diameter
2,5 cm
3. Agregat batu keras, tidak berpori, dengan ketajaman tidak lebih dari
20%, bersih dari bahan organik.
4. Agregat batu keras dengan keausan tidak lebih dari 50%, sesuai
dengan ASTM C-131-55 atau SNI 03-2417-1991
5. Agregat dari pasir, bukan hancuran beton
6. Penggunaan pasir laut tidak diijinkan
7. Penggunaan air minum dan tidak ada zat aditif
8. Karakteristik besi baja
 fy = 240 MPa (BJTP-24) < 12 mm
 fy = 400 MPa (BJTD-40) > 12 mm
 fy = 500 Mpa
 Struktur baja SNI 03-6764-2002, SNI 03-6861.2-2002
 Pengelasan baja SNI 07-0242.1-2000, SNI 07-6402-2000 SNI 03-
6763-2002
 Pencatan SNI 03-2408-1991

A-4