Abstract— Klungkung Hospital has 2 pieces of distribution sebesar 2%. Nilai THD V pada tiap-tiap S DP setelah penambahan
transformers 20kV / 400V with each capacity of 200kVA. Almost Damped Filter juga mengalami penurunan dengan rata-rata
all electrical equipment installed is a non-linear load equipment. penurunan sebesar 1.74%.
This study analyzes the use of damped filter to reduce Total
Harmonic Distrostion (THD) in Klungkung Hospital with ETAP Kata kunci : Beban non linier, Total Harmonic Distortion, Damped
S oftware. Based on the analysis, the standard limit ITHD in Filter
accordance with IEEE S tandard 519-2014 was 8.0%, and the
standard limit of VTHD is 8.0%. ITHD value of simulation results do
I. PENDAHULUAN
not meet the standard IEEE 519-2014, which is almost the entire
S DP has ITHD percentage above 8.0%. The highest percentage of Sistem distribusi memiliki peran penting dalam proses
ITHD amounted to 45.73% at S DP P.AC, and the lowest is 3.93%
at S DP UGD. VTHD value in simulation results show the entire SDP penyaluran energi listrik dari sumber PLN ke konsumen. Energi
meets the standard IEEE 519-2014. After the addition of a damped listrik yang disalurkan harus memiliki kualitas yang baik dan
filter, ITHD value in simulation results has decreased in each of the tanpa adanya gangguan. Kualitas daya listrik menjadi hal
S DP. However, only a few S DP with ITHD in accordance with the penting yang harus dijaga karena melayani banyak beban -
IEEE 519-2014 standard. The decrease ITHD highest is 10.63% at beban listrik yang menuntut kualitas daya listrik sebaik
S DP P.AC, and the lowest is 2% at S DP IPS RS . VTHD value at mungkin untuk kelancaran operasional suatu sistem. Terdapat
each S DP after the addition of a damped filter also decreased with beberapa faktor yang menimbulkan penurunan kualitas daya
an average decrease of 1.74%. listrik, salah satunya adalah distorsi harmonisa. [3]
Penggunaan beban-beban listrik dalam jumlah yang besar
Intisari— RS UD Klungkung memiliki 2 buah transformator
khususnya beban nonlinier merupakan penyebab timbulnya
distribusi 20kV/400V dengan kapasitas masing-masing sebesar
200kVA. Hampir seluruh peralatan listrik yang terpasang harmonisa. Saat ini permasalahan terkait dengan harmonisa
merupakan peralatan beban non linier. Penelitian ini menjadi hal yang perlu diwaspadai karena memberikan
menganalisis penggunaan Damped Filter untuk mereduksi Total implikasi negatif terhadap sistem seiring dengan
Harmonic Distrostion (THD) di RS UD Klungkung dengan berkembangnya peralatan-peralatan listrik dengan beban
Software ETAP. Berdasarkan hasil analisis, batas standar THD I nonlinier. Salah satu contohnya yaitu sarana publik seperti
berdasarkan IEEE S tandard 519-2014 adalah 8,0%, dan batas rumah sakit dengan pengoperasian peralatan-peralatan medis
standar THD V adalah 8,0%. Nilai THD I hasil simulasi tidak yang merupakan beban nonlinier. Beban nonlinier memili ki
memenuhi standard IEEE 519-2014, yaitu hampir seluruh SDP bentuk gelombang yang tidak sinusoidal karena telah terdistorsi
memiliki persentase THD I di atas 8,0%. Persentase THD I tertinggi
oleh arus harmonisa. Distortion (kerusakan) gelombang
terdapat pada S DP P.AC sebesar 45,73%, dan terendah pada SDP
UGD sebesar 3,93%. Nilai THD V hasil simulasi menunjukkan sinusoidal yang mengalir pada sistem tenaga listrik disebut
seluruh S DP memenuhi standard IEEE 519-2014. S etelah dengan Total Harmonic Distortion (THD) yang dinyatakan
penambahan Damped Filter, nilai THD I hasil simulasi mengalami dalam satuan persen (%).
penurunan di tiap-tiap S DP. Namun hanya beberapa S DP dengan Tingkat THD yang tinggi pada saluran distribusi sehingga
kandungan THD I sesuai dengan standar IEEE 519-2014. melebihi standar yang ditetapkan dapat dikategorikan sebagai
Penurunan THD I tertinggi terdapat pada S DP P.AC sebesar gangguan sistem. Semakin besar THD-nya maka semakin besar
10,63%, dan penurunan terendah terdapat pada S DP IPS RS losses (rugi-rugi) pada saluran sehingga efisiensinya akan
semakin menurun. Salah satu upaya untuk meminimalis as i
1 harmonisa pada sistem distribusi adalah penggunaan filter
Mahasiswa, Jurusan Teknik Elektro dan Komputer Fakultas harmonik. Salah satu filter harmonik yang digunakan adalah
Teknik Universitas Udayana, Jln. Kampus Bukit Jimbaran 80361
damped filter yang dapat mengurangi harmonisa pada frekuensi
INDONESIA (telp: 0361-703315; fax: 0361-4321; e-mail:
dekarya94@gmail.com yang tinggi. Damped filter tidak begitu sensitif terhadap
2,3
Dosen, Jurusan Teknik Elektro dan Komputer Fakultas Teknik perubahan temperatur, perubahan frekuensi, dan rugi-rugi
Universitas Udayana, Jln. Kampus Bukit Jimbaran 80361 kapasitor. Pada sejumlah kasus, penggunaan satu atau lebih
INDONESIA (telp: 0361-703315; fax: 0361-4321; e-mail: damped filter dapat menjadi alternatif yang dapat diterima. [3]
1
rinas@unud.ac.id , 2artawijaya@unud.ac.id RSUD Klungkung memiliki 2 buah transformator
distribusi 20kV/400V dengan kapasitas maksimum masing-
I Kadek Arya Wiguna: ANALISIS PENGGUNAAN FILTER DAMPED… p-ISSN:1693 – 2951; e-ISSN: 2503-2372
2
Teknologi Elektro, Vol. nn, No. nn, Bulan20nn
masing sebesar 200kVA. Terdapat masing-masing 1 buah MDP
(Main Distribution Panel) pada kedua transformator yang
terpasang yang kemudian dibagi menjadi 18 SDP (Sub
Distributin Panel). Dalam penelitian ini dilakukan pengukuran
awal terhadap kandungan THD baik teganagn maupun arus saat
beban puncak di tiap-tiap Sub Distribution Panel (SDP) yang
terpasang di RSUD Klungkung. Hasil pengukuran yang
diperoleh akan dibandingkan dengan standar IEEE 519 tahun
2014 yang dijadikan sebagai acuan analisis. Setelah dilakukan
pengukuran awal diketahui bahwa rata-rata THD tegangan
(THDV) pada transformator 1 dan trans formator 2 yaitu sebesar Gambar 1. Dist orsi gelombang akibat harmonisa [3]
1.51%, dan 1.78%. Sedangkan rata-rata THD arus (THDI) pada
transformator 1 dan transformator 2 yaitu sebesar 16.73%, dan 1) Penyebab Distorsi Harmonik : Penyebab utama distorsi
13.04%. Berdasarkan standar IEEE 519 tahun 2014 bahwa harmonisa adalah penggunaan peralatan dengan beban non
batasan THDV sistem dengan tegangan nominal dibawah 1kV linier pada sistem tenaga listrik. Beban non linier pada
yaitu sebesar 8%. Sedangkan untuk menentukan batasan THD umumnya merupakan komponen semikonduktor yang pada
arus (THDI) disesuaikan dengan nilai rasio hubung singkat (SC
proses kerjanya bekerja sebagai saklar (switch) yang bekerja
ratio). Hasil perhitungan rasio hubung singkat yang telah
pada setiap setengah siklus gelombang atau beban yang
dilakukan, rata-rata nilai SCratio-nya yaitu sebesar 25. Dengan
SCratio sebesar 25 maka batasan THDI adalah sebesar 8%. membutuhkan arus listrik tidak tetap pada setiap periode
Sehingga diketahui bahwa THDV untuk Transformator 1 dan 2 waktunya. Proses kerjanya inilah yang akan menghasilkan
masih memenuhi standar, sedangkan THDI pada transformator gangguan atau distorsi arus maupun tegangan yang tidak
1 maupun transformator 2 yang terukur tidak memenuh i sinusoidal.
standar.
Berdasarkan data awal yang diperoleh, maka tingginya 2) Akibat Yang Ditimbulkan Distorsi Harmonik : Secara
tingkat THDI yang telah melewati standar akan direduksi umum pengaruh harmonik pada peralatan listrik ada tiga, yaitu
dengan menggunakan damped filter sehingga dapat :
menurunkan nilai THD dari saluran distribusi di RSUD Nilai RMS arus atau tegangan menjadi lebih besar. Nilai
Klungkung. Analisis yang dilakukan pada penelitian ini RMS yang lebih besar dapat mengakibatkan pemanas an
disimulasikan dengan menggunakan perangkat lunak ETAP.
yang lebih tinggi pada konduktor.
Nilai puncak (peak value) tegangan dan arus lebih besar.
II. KUALITAS DAYA LISTRIK DAN TOTAL HARMONIC Nilai puncak lebih besar dapat mengganggu kerja dari alat
DISTORTION ukur, sehingga dapat terjadi kesalahan pada pembacaan.
A. Kualitas Daya Listrik Menurunnya frekuensi pada sistem. Pada frekuensi tertentu,
Kualitas daya listrik menunjukkan setiap masalah daya fenomena resonansi dapat terjadi yang dapat
listrik yang berbentuk penyimpangan tegangan, arus atau mengakibatkan arus meningkat.
frekuensi yang mengakibatkan kegagalan ataupun kesalahan
operasi pada peralatan-peralatan yang terjadi pada konsumen C. Standar Harmonisa pada Sistem Tenaga Listrik
energi listrik. Daya adalah suatu nilai dari energi listrik yang Standar harmonisa yang saat ini digunakan sebagai acuan
dikirimkan dan didistribusikan, dimana besarnya daya listrik adalah IEEE 519-2014. Standar THDV yang diperbolehkan
tersebut sebanding dengan perkalian besarnya tegangan d an diatur sesuai dengan Point of Common Coupling (PCC) dimana
arus listriknya. Satuan untuk daya listrik dinyatakan dalam setiap tingkatan tegangan memiliki standar yang berbeda-beda,
Watt atau Horsepower (HP), dimana 1 Horsepower (HP) setara begitu pula untuk standar THDI diatur sesuai PCC dan
dengan 746 Watt. [2] perhitungan rasio hubung singkatnya [4].
ISSN 1693 – 2951 I Kadek Arya Wiguna: ANALISIS PENGGUNAAN FILTER DAMPED…
3
Teknologi Elektro, Vol. nn, No. nn, Bulan 20nn
69 kV < V < 161 kV 1,5 2,5 Dimana kvrated adalah tegangan yang terukur pada tiap
161 kV < V 1,0 1,5 SDP, dan MVARrated adalah daya reaktif pada tiap SDP.
2) Standar THDI IEEE 519-2014: Batas THDI yang Besar nilai kapasitor dapat dihitung menggunakan
direkomendasikan bagi pelanggan yang terhubung dengan persamaan 3.
sistem dimana tegangan berkisar antara 120 V sampai 169 kV
1
disesuaikan dengan short circuit ratio (rasio hubung 𝐶 = (3)
2𝜋𝑓𝑋𝐶
singkat).[4]
Dengan : f = frekuensi fundamental 50 Hz
T ABEL II
CURRENT DISTORTION LIMITS FOR S YSTEMS RATED 120 V THROUGH 69 KV [4]
Besar impedansi reaktor filter dapat ddihitung
Maximum Harmonic Current Distortion menggunakan persamaan 4.
Individual Harmonic Order (odd harmonic)
3≤h 11 ≤ h 17 ≤ h 23 ≤ h 35 ≤ h THD 𝑋𝐶
ISC/IL 𝑋𝐿 = (4)
≤ 11 ≤ 17 ≤ 23 ≤ 35 ≤ 50 (%)
𝑛2
< 20 c 4,0 2,0 1,5 0,6 0,3 5,0
20 < 50 7,0 3,5 2,5 1,0 0,5 8,0 Dengan : n = orde harmonik tegangan yang difilter (disetel
50 < 100 10,0 4,5 4,0 1,5 0,7 12,0
sedikit di bawah ordenya). Pada simulasi ini, orde yang akan
100 < 1000 12,0 5,5 5,0 2,0 1,0 15,0
> 1000 15,0 7,0 6,0 2,5 1,4 20,0 difilter adalah orde 5, sehingga nilai n akan sedikit di bawahnya
yaitu 4,9. Hal ini dilakukan sebagai toleransi komponen filter
D. Damped Filter untuk mencegah adanya resonansi yang terjadi dalam sistem
pada frekuensi yang mengganggu.
Damped Filter digunakan untuk memberikan pergantian
selama rentang frekuensi yang luas. Ketika arus harmonik Besar induktansi induktor dapat dihitung dengan
mencapai nilai-nilai yang besar, damped filter digunakan dalam menggunakan persamaan 5.
hubungannya dengan Tuned Filter yang mengurangi frekuensi
𝑋𝐿
rendah, sedangkan damped filter mengurangi harmonik pada 𝐿 = (5)
2𝜋𝑓
frekuensi yang tinggi [1]. Pada umumnya digunakan topologi
damped filter yang ditunjukkan pada gambar 2. Dengan : π = 3,14
𝐿
𝑋𝑛 = √
njj (6)
𝐶
Gambar 2. Damped Filter: first order, second order, dan third order [1] Besarnya resistansi filter dapat dihitung dengan persamaan
7.
Parameter damped filter yang dihitung adalah sebagai berikut
𝑅 = 𝑋𝑛 𝑄 (7)
Daya reaktif untuk memperbaiki faktor daya dapat dihitung
dengan persamaan 1. Pada perancangan filter kali ini, nilai Q yang digunakan yaitu
5. Nilai Q adalah ukuran ketajaman penyetelan filter dalam
𝑃1 2 𝑃1 2
𝑄𝑉𝐴𝑅 = √( ) − 𝑃1 2 − √( ) − 𝑃1 2 (1) mereduksi harmonik.
𝑝𝑓0 𝑝𝑓1
Dimana P1 adalah daya aktif masing-masing SDP, pf0 dan III. METODE PENELITIA N
pf1 adalah faktor daya untuk masing-masing beban.
Penelitian dilaksanakan di Rumah Sakit Umum Daerah
Nilai reaktansi dari kapasitor dapat dihitung menggunakan (RSUD) Klungkung yang berlokasi di Jalan Flamboyan No.40,
persamaan 2. Semarapura mulai pada tanggal 19 Januari 2016 sampai Maret
2016. Alur analisis pada penelitian ini dapat dilihat pada
𝑘𝑉2 𝑟𝑎𝑡𝑒𝑑 gambar 3.
𝑋𝐶 = (2)
𝑀𝑉𝐴𝑅 𝑟𝑎𝑡𝑒𝑑
I Kadek Arya Wiguna: ANALISIS PENGGUNAAN FILTER DAMPED… p-ISSN:1693 – 2951; e-ISSN: 2503-2372
4
Teknologi Elektro, Vol. nn, No. nn, Bulan20nn
ISSN 1693 – 2951 I Kadek Arya Wiguna: ANALISIS PENGGUNAAN FILTER DAMPED…
5
Teknologi Elektro, Vol. nn, No. nn, Bulan 20nn
T ABEL IV
I SC , IL, DAN SCRATIO MASING-MASING SDP
Standar
THDI Hasil
SDP IEEE 519- Ke t
Simulasi (%)
2014 (%)
Ruang A 14,70 8 Melewati standar
Ruang B 8,11 8 Melewati standar
Ruang C 14,68 8 Melewati standar
Ruang D&E 11,05 8 Melewati standar
Ruang F 16,03 8 Melewati standar
UGD 3,93 8 Sesuai standar
Bedah Sentral (IBS) 10,11 8 Melewati standar
Ponek 16,99 8 Melewati standar
Hemodialisa (HD) 19,08 8 Melewati standar
Gambar 5. Hasil running analisis T HDI dan T HDV di RSUD Klungkung Poliklinik 9,21 8 Melewati standar
Poliklinik Khusus AC 45,73 8 Melewati standar
Berikut ini hasil running spektrum harmonik dan bentuk Dapur 14,54 8 Melewati standar
gelombang dari simulasi yang dilakukan pada software ETAP, Gudang 32,25 8 Melewati standar
seperti gambar 5 dan gambar 6 dibawah ini: Laundry 26,50 8 Melewati standar
IPSRS 12,74 8 Melewati standar
Dari tabel V di atas dapat dilihat bahwa THDI pada tiap SDP
yang terpasang di RSUD Klungkung telah melewati standar
I Kadek Arya Wiguna: ANALISIS PENGGUNAAN FILTER DAMPED… p-ISSN:1693 – 2951; e-ISSN: 2503-2372
6
Teknologi Elektro, Vol. nn, No. nn, Bulan20nn
atau lebih dari 8%, kecuali pada SDP UGD yang masih sesuai
standar.
T ABEL VI
PERBANDINGAN THD V HASIL SIMULASI DENGAN ST ANDAR IEEE
519 T AHUN 2014
Standar
THDI Hasil
SDP IEEE 519- Ket
Simulasi (%)
2014 (%)
Ruang A 5,26 8 Sesuai standar
Ruang B 5,25 8 Sesuai standar
Ruang C 5,30 8 Sesuai standar
Ruang D&E 5,26 8 Sesuai standar
Ruang F 5,25 8 Sesuai standar
UGD 5,27 8 Sesuai standar
Bedah Sentral (IBS) 5,29 8 Sesuai standar Gambar 8. Parameter spesifikasi damped filter pada simulasi
Ponek 5,28 8 Sesuai standar
Hemodialisa (HD) 5,44 8 Sesuai standar
Poliklinik 5,26 8 Sesuai standar F. Simulasi Sistem Setelah penambahan Filter
Poliklinik Khusus AC 5,66 8 Sesuai standar
Dapur 5,27 8 Sesuai standar Dengan penempatan filter pada SDP PAC, spektrum
Gudang 5,26 8 Sesuai standar harmonik dan bentuk gelombang tegangannya mengalami
Laundry 5,25 8 Sesuai standar
perubahan, dimana nilai harmonisa dapat diturunkan oleh filter
IPSRS 5,24 8 Sesuai standar
yang terpasang. Berikut ini adalah gambar spektruk harmonik
dan bentuk gelombang setelah penambahan filter
Dari tabel VI di atas dapat dilihat nilai THDV hasil simulasi
untuk masing-masing SDP yang terpasang telah sesuai standar
atau tidak lebih dari 8%.
ISSN 1693 – 2951 I Kadek Arya Wiguna: ANALISIS PENGGUNAAN FILTER DAMPED…
7
Teknologi Elektro, Vol. nn, No. nn, Bulan 20nn
G. Analisis THDI dan THDV di RSUD Klungkung Setelah di Dari tabel IX dapat dilihat bahwa nilai THDV pada masing-
Pasang High Pass Damped Filter masing SDP setelah pemasangan High Pass Damped Filter
mengalami penurunan dan dapat memenuhi standar IEEE 519
Berdasarkan simulasi yang dilakukan, terdapat perbedaan tahun 2014. Penurunan terbesar terdapat pada SDP HD sebesar
nilai THDI sebelum dan setelah penambahan High Pass 1,8 %, dan penurunan terrendah terdapat pada SDP UGD, SDP
Damped Filter. Hasil analisis THDI sebelum dan setelah Laundry, dan SDP IPSRS sebesar 1,72 %.
penambahan High Pass Damped Filter serta perbandingannya
dengan Standar IEEE 519 tahun 2014 dapat dilihat pada tabel
VIII berikut ini V. KESIMPULAN
T ABEL VIII
PERBANDINGAN T HDI HASIL RUNNING T ANPA FILT ER DAN Dari simulasi yang telah dilakukan diketahui bahwa High
SET ELAH DI PASANG FILT ER Pass Damped Filter mampu mereduksi THDV dan THDI. Nilai
THDV dengan penurunan terbesar terdapat pada SDP HD
THDI THDI Standar sebesar 1,8 % dan penurunan terendah pada SDP UGD,
Selisih
SDP tanpa dengan IEEE 519-
(%) Laundry, dan IPSRS sebesar 1,72 %. Nilai THDI juga dapat
filter (%) filter (%) 2014 (%)
Ruang A 14,70 8,90 5,8 8 direduksi dengan penurunan terbesar terdapat pada SDP P.AC
Ruang B 8,11 3,96 4,15 8 sebesar 10,63 %, dan penurunan terendah terdapat pada SDP
Ruang C 14,68 8,97 5,71 8 IPSRS sebesar 2 %.
Ruang D&E 11,05 6,02 5,03 8
Ruang F 16,03 8,32 7,71 8
Kandungan THDV pada masing-masing SDP setelah
UGD 3,93 3,93 0 8 pemasangan filter telah sesuai dengan standar IEEE 519 tahun
Bedah Sentral (IBS) 10,11 5,47 4,64 8 2014 seperti pada tabel IX. Sedangkan untuk THDI terdapat
Ponek 16,99 11,49 5,5 8 beberapa SDP dengan kandungan THDI yang telah sesuai
Hemodialisa (HD) 19,08 13,68 5,4 8 dengan standar, namun terdapat pula beberapa SDP dengan
Poliklinik 9,21 4,79 4,42 8 kandungan THDI yang melewati standar IEEE 519 tahun 2014
Poliklinik Khusus AC 45,73 35,10 10,63 8
Dapur 14,54 10,24 4,3 8 seperti pada tabel VIII.
Gudang 32,25 23,06 9,19 8
Laundry 26,50 16,91 9,59 8 REFERENSI
IPSRS 12,74 10,74 2 8
[1] Ahmed, K., Jovcic, D., 2015. High Voltage Direct Current
Transmission. School of Engineering University of Aberdeen UK :
Setelah penambahan filter, kandungan THDI pada beberapa Wiley.
SDP dapat direduksi dan telah memenuhi Standar IEEE 519 - [2] Dugan, R.C., McGranaghan, M.F., Santoso, S., Beaty, H.W. 2004.
2014, namun ada beberapa SDP dengan kandungan THD I yang Electrical Power System Quality-Second Edition. T he McGraw-Hill.
masih melewati standar. [3] Harlow, J.H. 2004. Electric Power Engineering. United States of
Hasil analisis THDv sebelum dan setelah penggunaan High America : CRC Press.
Pass Damped Filter serta perbandingannya dengan Standar [4] IEEE Recommended Practices and Requirements for Harmonic Control
IEEE 519 tahun 2014 pada masing-masing SDP dapat dilihat in Electric Power Systems. IEEE Standard 519-2014
[5] Margareta, I.W., 2014. “Perancangan High Pass Damped Filter Pada
pada tabel IX.
Sistem Distribusi Standar IEEE 9 Bus Dengan Menggunakan Software
ET AP Power Station 7.0”. Surakarta : Universitas Muhamadiyah
TABEL IX Surakarta.
PERBANDINGAN T HDV HASIL RUNNING T ANPA FILT ER DAN [6] Pramnamto, A. 2008. Analisis Penggunaan Single Tuned Filter Sebagai
SET ELAH DI PASANG FILT ER
Salah Satu Solusi Masalah Harmonik Pada Beban Rumah Tangga. Jurnal
T eknik Elektro Vol. 2, No. 1, Maret 2002.
THDV THDV Standar
Selisih [7] Rinas, I.W., 2011. Analisis Perbandingan Penggunaan Filter Pasif Dan
SDP tanpa dengan IEEE 519-
(%) Filter Aktif Untuk Menanggulangi T HD Pada Sistem Kelistrikan Di
filter (%) filter (%) 2014 (%)
Ruang A 5,26 3,53 1,73 8 Ruang Puskom Jurusan T eknik Elektro Fakultas T eknik Universitas
Ruang B 5,25 3,52 1,73 8 Udayana. T eknologi Elektro, Vol. 10 (Januari - Juni) : 20 – 26.
Ruang C 5,30 3,55 1,75 8
Ruang D&E 5,26 3,53 1,73 8
Ruang F 5,25 3,52 1,73 8
UGD 5,27 3,55 1,72 8
Bedah Sentral (IBS) 5,29 3,54 1,75 8
Ponek 5,28 3,54 1,74 8
Hemodialisa (HD) 5,44 3,64 1,8 8
Poliklinik 5,26 3,53 1,73 8
Poliklinik Khusus AC 5,57 3,84 1,73 8
Dapur 5,27 3,54 1,73 8
Gudang 5,26 3,53 1,73 8
Laundry 5,25 3,53 1,72 8
IPSRS 5,24 3,52 1,72 8
I Kadek Arya Wiguna: ANALISIS PENGGUNAAN FILTER DAMPED… p-ISSN:1693 – 2951; e-ISSN: 2503-2372