Anda di halaman 1dari 164

SiMT281515E

Panduan
Servis

Seri RZR-LU
Pendinginan Saja R-410A 50 Hz
RZR100/125/140LUY1(4)
SiMT281515E

Seri RZR-LU
Pendinginan
Saja R-410A 50
Hz
Referensi ED
Untuk item di bawah ini, lihat Data Teknik.
No. Item No. ED Halaman Keterangan
1 Spesifikasi EDMT281511 P. 12 - 23
2 Aksesoris EDMT281511 P. 79 - 80

1. Pendahuluan ..............................................................................................iv
1.1 Peringatan Keselamatan ....................................................................... iv
1.2 Ikon yang Digunakan............................................................................viii

Bagian 1 Informasi Umum ............................................................1


1. Nama Model Unit Indoor / Outdoor ........................................................... 2
2. Penampilan eksternal ................................................................................ 3

Bagian 2 Fungsi ............................................................................4


1. Fungsi ......................................................................................................... 5

Bagian 3 Remote Kontrol..............................................................6


1. Remote Kontrol Berkabel .......................................................................... 7
1.1 Model yang Berlaku ...............................................................................7
1.2 Nama dan Fungsi...................................................................................8
1.3 Pengaturan MAIN/SUB saat Menggunakan 2 Remote Kontrol ...............12
1.4 Pengaturan No. Grup Kendali Terpusat ................................................13
1.5 Mode Servis .........................................................................................15
1.6 Mode Inspeksi......................................................................................19
2. Remote Kontrol Nirkabel ......................................................................... 20
2.1 Model yang berlaku ..............................................................................20
2.2 Nama dan Fungsi.................................................................................20
2.3 Pengaturan MAIN/SUB dan Alamat ......................................................22

Bagian 4 Fungsi dan Kontrol ......................................................24


1. Fungsi Termistor dan Komponen Utama
(Diagram Pemipaan)................................................................................ 25
2. Garis Besar Fungsi .................................................................................. 28

i Daftar Isi
SiMT281515E
2.1 Unit Indoor ...........................................................................................28
2.2 Unit Outdoor ........................................................................................29

3. Diagram Alir Operasi ............................................................................... 30


3.1 Operasi Pendinginan/Kering (Cooling/Dry) ............................................30
4. Rincian Fungsi ......................................................................................... 31
4.1 Unit Indoor ...........................................................................................31
4.2 Unit Outdoor ........................................................................................36

Bagian 5 Operasi Uji Coba dan Pengaturan Bidang .................... 44


1. Operasi Uji Coba ...................................................................................... 45
1.1 Periksa sebelum Operasi Uji Coba .......................................................45
1.2 Pemeriksaan Operasi Uji Coba.............................................................45
2. Pengaturan Bidang dari Remote Kontrol ................................................ 46
2.1 Remote Kontrol Berkabel ......................................................................46
2.2 Remote Kontrol Nirkabel .......................................................................49
2.3 Nomor Kode dan Isi Pengaturan untuk Unit Indoor .................................50
2.4 Nomor Kode dan Isi Pengaturan untuk Unit Outdoor..............................51
3. Pengaturan Bidang dari Adaptor Demand .............................................. 53
3.1 Fungsi i-Demand...................................................................................53
4. Pengaturan Bidang dari PCB Unit Outdoor ........................................... 54
4.1 Pengaturan dengan Tombol BS............................................................54
4.2 Mode 1 Pengaturan ..............................................................................54
4.3 Mode 2 Pengaturan..............................................................................55
4.4 Mode Monitor.......................................................................................57
4.5 Daftar Isi tentang Coba lagi dan Kesalahan ...........................................58
5 Operasi Darurat ........................................................................................ 60

Bagian 6 Diagnosis Servis .........................................................62


1. Inspeksi Pemeliharaan ............................................................................ 64
1.1 Gambaran Umum ................................................................................64
2. Pemecahan Masalah Berbasis Gejala ................................................... 66
2.1 Gambaran Umum .................................................................................66
2.2 Peralatan tidak Beroperasi ....................................................................67
2.3 Kipas Unit Indoor Beroperasi, tetapi Kompresor tidak Beroperasi ...........68
2.4 Operasi Pendinginan Mulai tetapi Berhenti Segera ................................69
2.5 Setelah Unit dimatikan, tidak dapat dihidupkan ulang untuk sementara ..70
2.6 Peralatan Beroperasi tetapi tidak memberikan Pendinginan ...................72
2.7 Peralatan Mengeluarkan Kabut Putih.....................................................73
2.8 Peralatan Menghasilkan suara keras atau Getaran ................................74
2.9 Peralatan Mengeluarkan Debu ..............................................................76
2.10 LCD Remote Kontrol Menampilkan "88" ...............................................76
3 Pemecahan Masalah berdasarkan Indikasi LED................................... 77
3.1 Pemecahan Masalah berdasarkan LED pada Unit Indoor .....................77
3.2 Pemecahan Masalah berdasarkan LED pada PCB Unit Outdoor...........77
4 Pemecahan Masalah menggunakan Remote Kontrol ........................... 78
4.1 Penggantian Mode................................................................................78
4.2 Prosedur diagnosis sendiri menggunakan Remote Kontrol .....................79
4.3 Deskripsi dan Kode Kesalahan ..............................................................83
4.4 Kode Kesalahan – Kode Sub .................................................................84
4.5 Gambaran Umum tentang Perangkat keselamatan Outdoor...................87

Daftar Isi ii
SiMT281515E
4.6 Gambaran Umum tentang Perangkat keselamatan Indoor ....................87
5 Pemecahan Masalah berdasarkan Indikasi pada Remote Kontrol ...... 88

5.1 Ketidaknormalan PCB Unit Indoor .........................................................88


5.2 Ketidaknormalan Sistem Permukaan Air Saluran ...................................89
5.3 Kunci Motor Kipas Unit Indoor ..............................................................91
5.4 Ketidaknormalan Motor Kipas Unit Indoor ..............................................92
5.5 Ketidaknormalan PCB Kipas .................................................................94
5.6 Ketidaknormalan Sistem Saluran ..........................................................95
5.7 Ketidaknormalan Pengaturan Kapasitas ................................................96
5.8 Kesalahan Transmisi (antara PCB Unit Indoor dan PCB Kipas).............97
5.9 Kesalahan Transmisi (antara PCB Unit Indoor dan PCB Kipas).............99
5.10 Ketidaknormalan Termistor .............................................................. 101
5.11 Kesalahan Kombinasi antara PCB Unit Indoor dan PCB Kipas ......... 102
5.12 Ketidaknormalan Termistor Remote Kontrol ...................................... 103
5.13 Ketidaknormalan PCB Unit Outdoor .................................................. 104
5.14 Ketidaknormalan Tekanan Tinggi
( Terdeteksi oleh Saklar Tekanan Tinggi) .......................................... 105
5.15 Kunci Motor Kompresor ................................................................... 107
5.16 Ketidaknormalan Motor Kipas Unit Outdoor....................................... 108
5.17 Ketidaknormalan Katup Ekspansi Elektronik...................................... 110
5.18 Ketidaknormalan Suhu Pipa Pembuangan ........................................ 112
5.19 Ketidaknormalan Sistem Saklar Tekanan Tinggi................................ 113
5.20 Ketidaknormalan Termistor ............................................................... 114
5.21 Ketidaknormalan Sensor Tekanan .................................................... 115
5.22 Ketidaknormalan PCB Unit Outdoor .................................................. 116
5.23 Peningkatan Suhu Sirip Radiasi ........................................................ 118
5.24 Arus Berlebih Output DC (Sesaat)..................................................... 120
5.25 Termal Elektronik (Jeda waktu) ......................................................... 122
5.26 Pencegahan Stall (Jeda waktu)........................................................ 124
5.27 Kesalahan Sistem Transmisi antar PCB Unit Outdoor....................... 126
5.28 Ketidakseimbangan Tegangan Catu Daya atau Fasa Terbuka........... 127
5.29 Ketidaknormalan Termistor Sirip Radiasi........................................... 128
5.30 Ketidaknormalan Pengaturan Kapasitas............................................ 129
5.31 Kekurangan Refrigeran ..................................................................... 130
5.32 Ketidaknormalan Tegangan Catu Daya ............................................. 131
5.33 Kesalahan Transmisi antara Unit Indoor dan Unit Outdoor .................. 132
5.34 Kesalahan Transmisi antara Unit Indoor dan Remote Kontrol ............ 134
5.35 Kesalahan Transmisi antara Remote Kontrol MAIN dan
Remote Kontrol SUB ........................................................................ 135
5.36 Ketidaknormalan Saklar Pengaturan Bidang ..................................... 136
5.37 Kesalahan Pengaturan Alamat Terpusat ........................................... 137
5.38 Kesalahan Transmisi antara Unit Indoor dan Outdoor / Pemipaan dan
Ketidakcocokan Pengkabelan / Kekurangan Refrigeran ...................... 138
5.39 Pemeriksaan .................................................................................... 139

Bagian 7 Lampiran .................................................................... 149


1. Diagram Pengkabelan ........................................................................... 150
1.1 Unit Indoor .......................................................................................... 150
1.2 Unit Outdoor ....................................................................................... 151

i Daftar Isi
SiMT281515E Pendahuluan

1. Pendahuluan
1.1 Peringatan Keselamatan
Perhatian  Pastikan untuk membaca peringatan keselamatan berikut sebelum melakukan pekerjaan
dan perbaikan.
Peringatan  Item-Perhatian diklasifikasikan ke dalam “ Peringatan” dan “ Perhatian”. Item-
item “ Peringatan” sangat penting karena mereka dapat menyebabkan kematian
atau cedera serius jika tidak dipatuhi. Item-item “ Perhatian” juga dapat
menyebabkan kecelakaan serius dalam beberapa kondisi jika tidak dipatuhi. Oleh
karena itu, pastikan untuk mematuhi semua item perhatian keselamatan yang
dijelaskan di bawah ini.
 Tentang Piktogram
Simbol ini menunjukkan item perhatian yang harus dilakukan.
Piktogram menunjukkan item-item yang harus diperhatikan.
Simbol ini menunjukkan tindakan yang dilarang.
Item atau tindakan yang dilarang ditampilkan dalam ilustrasi atau dekat simbol.
Simbol ini menunjukkan tindakan, atau instruksi yang harus dilakukan.
Instruksi ditampilkan dalam ilustrasi atau dekat simbol.
 Setelah pekerjaan perbaikan selesai, pastikan melakukan operasi uji coba untuk
memastikan bahwa peralatan beroperasi secara normal, dan menjelaskan kehati-
hatian pengoperasian produk kepada pelanggan.

1.1.1 Perhatian Mengenai Keselamatan Pekerja


Peringatan
Pastikan untuk mencabut steker kabel listrik dari stopkontak steker sebelum membongkar
peralatan untuk perbaikan.
Bekerja pada peralatan yang terhubung ke catu daya dapat menyebabkan sengatan listrik.
Jika perlu mengalirkan listrik ke peralatan untuk melakukan perbaikan atau memeriksa
sirkuit, jangan menyentuh bagian peralatan yang bermuatan listrik.

Jika gas refrigeran dibuang selama pekerjaan perbaikan, jangan sentuh gas refrigeran yang
dibuang.
Gas refrigeran dapat menyebabkan radang dingin.

Saat melepas pipa hisap atau pembuangan kompresor di bagian yang dilas, terlebih
dahulu keluarkan gas refrigeran di tempat yang berventilasi baik.
Jika ada gas yang tersisa di dalam kompresor, gas refrigeran atau minyak mesin refrigerasi
akan keluar ketika pipa dilepaskan, dan dapat menyebabkan cedera.

Jika gas refrigeran bocor selama pekerjaan perbaikan, beri ventilasi di area tersebut. Gas
refrigeran dapat menghasilkan gas beracun saat melakukan kontak dengan api.

Kapasitor step-up mengalirkan listrik tegangan tinggi ke komponen listrik dari unit outdoor.
Pastikan untuk membuang kapasitor sepenuhnya sebelum melakukan pekerjaan
perbaikan. Kapasitor yang bermuatan listrik dapat menyebabkan sengatan listrik.

Jangan menyalakan atau menghentikan operasi AC dengan mencolokkan atau mencabut


steker kabel listrik.
Mencolokkan atau mencabut steker kabel listrik untuk mengoperasikan peralatan dapat
menyebabkan sengatan listrik atau kebakaran.

Daftar Isi ii
SiMT281515E Pendahuluan

Peringatan
Pastikan untuk mengenakan helm pengaman, sarung tangan, dan sabuk pengaman saat
bekerja di tempat yang tinggi (lebih dari 2 m). Tindakan keselamatan yang tidak memadai
dapat menyebabkan kecelakaan jatuh.

Dalam kasus model refrigeran R-410A, pastikan untuk menggunakan pipa, mur flare dan
alat untuk penggunaan eksklusif refrigeran R-410A.
Penggunaan bahan untuk model refrigeran R-22 dapat menyebabkan kecelakaan serius
seperti kerusakan siklus refrigeran serta kegagalan peralatan.

Perhatian
Jangan memperbaiki komponen listrik dengan tangan basah.
Bekerja pada peralatan dengan tangan basah dapat menyebabkan sengatan listrik.

Jangan membersihkan pendingin ruangan dengan memercikkan air.


Mencuci unit dengan menggunakan air dapat menyebabkan sengatan
listrik.

Pastikan untuk memberikan arde (pembumian) saat memperbaiki peralatan di tempat yang
lembab atau basah, untuk menghindari sengatan listrik.

Pastikan untuk menonaktif(OFF)-kan saklar daya dan mencabut kabel listrik saat
membersihkan peralatan.
Kipas internal berputar pada kecepatan tinggi, dan menyebabkan cedera.

Pastikan untuk melakukan pekerjaan perbaikan dengan alat yang tepat.


Penggunaan alat-alat yang tidak sesuai dapat menyebabkan cedera.

Pastikan untuk memeriksa bahwa bagian siklus refrigerasi telah didinginkan dengan cukup
sebelum melakukan pekerjaan perbaikan.
Bekerja pada unit saat bagian siklus refrigerasi panas dapat menyebabkan luka bakar.

Gunakan alat las di tempat yang berventilasi baik.


Penggunaan alat las di ruang tertutup dapat menyebabkan kekurangan oksigen.

v
Pendahuluan SiMT281515E

1.1.2 Perhatian Mengenai Keselamatan Pengguna


Peringatan
Pastikan untuk menggunakan komponen yang tercantum dalam daftar komponen servis
dari model yang berlaku dan alat yang tepat untuk melakukan pekerjaan perbaikan. Jangan
pernah mencoba memodifikasi peralatan.
Penggunaan komponen atau alat yang tidak sesuai dapat menyebabkan sengatan listrik,
pembangkitan panas berlebihan atau kebakaran.

Jika kabel listrik dan kawat timah memiliki goresan atau memburuk, pastikan untuk
menggantinya.
Kabel dan kawat yang rusak dapat menyebabkan sengatan listrik, pembangkitan panas
berlebihan atau kebakaran.

Jangan menggunakan sambungan kabel listrik atau kabel perpanjangan, atau berbagi
stopkontak yang sama dengan peralatan listrik lainnya, karena dapat menyebabkan
sengatan listrik, pembangkitan panas berlebihan atau kebakaran.

Pastikan untuk menggunakan sirkuit listrik eksklusif untuk peralatan, dan mematuhi standar
teknis lokal terkait dengan peralatan listrik, peraturan pengkabelan internal, dan panduan
petunjuk untuk pemasangan ketika melakukan pekerjaan listrik.
Kapasitas sirkuit listrik yang tidak memadai dan pekerjaan listrik yang tidak tepat dapat
menyebabkan sengatan listrik atau kebakaran.

Pastikan untuk menggunakan kabel yang ditentukan untuk kabel antara Unit indoor dan
outdoor. Buatlah sambungan aman dan rute kabel dengan benar sehingga tidak ada
kekuatan yang menarik kabel di terminal sambungan.
Sambungan yang tidak tepat dapat menyebabkan timbulnya panas berlebihan atau
kebakaran.

Ketika melakukan pengkabelan antara unit indoor dan outdoor, pastikan bahwa penutup
terminal tidak terangkat atau turun karena kabel.
Jika penutup tidak terpasang dengan benar, bagian sambungan terminal dapat
menyebabkan sengatan listrik, pembangkitan panas berlebihan atau kebakaran.

Jangan merusak atau memodifikasi kabel listrik.


Kabel listrik yang rusak atau dimodifikasi dapat menyebabkan sengatan listrik atau
kebakaran. Menempatkan benda-benda berat di atas kabel listrik, dan memanaskan atau
menarik kabel listrik dapat merusak kabel.

Jangan mencampur udara atau gas selain refrigeran yang ditentukan (R-410A / R-22) di
dalam sistem refrigeran.
Jika udara memasuki sistem refrigeran, akan menghasilkan tekanan yang terlalu tinggi,
menyebabkan kerusakan peralatan dan cedera.

Jika gas refrigeran bocor, pastikan menemukan titik bocor dan memperbaikinya sebelum
mengisi refrigeran. Setelah pengisian refrigeran, pastikan tidak ada kebocoran refrigeran.
Jika titik bocor tidak dapat ditemukan dan pekerjaan perbaikan harus dihentikan, pastikan
untuk melakukan pump down dan menutup katup servis, untuk mencegah gas refrigeran
bocor ke dalam ruangan. Gas refrigeran tidak berbahaya, tetapi dapat menghasilkan gas
beracun saat melakukan kontak dengan nyala api, seperti kipas dan pemanas lainnya,
tungku dan kompor.
Ketika memindahkan peralatan, pastikan bahwa tempat pemasangan baru memiliki
kekuatan yang cukup untuk menahan berat peralatan tersebut.
Jika tempat pemasangan tidak memiliki kekuatan yang memadai dan jika pekerjaan
pemasangan tidak dilakukan dengan aman, peralatan bisa jatuh dan menyebabkan cedera.

vi
SiMT281515E Pendahuluan

Peringatan
Periksa untuk memastikan bahwa steker kabel listrik tidak kotor atau longgar, kemudian
masukkan steker ke stopkontak dengan aman.
Jika steker berdebu atau sambungannya longgar, dapat menyebabkan sengatan listrik atau
kebakaran.

Pastikan untuk memasang produk secara benar dengan menggunakan rangka Untuk tipe kesatuan
pemasangan standar yang disediakan. saja
Penggunaan rangka pemasangan yang tidak benar dan pemasangan yang tidak benar
dapat menyebabkan peralatan jatuh, yang mengakibatkan cedera.

Pastikan untuk memasang produk secara aman dalam rangka pemasangan yang dipasang Untuk tipe kesatuan
di rangka jendela. saja
Jika unit tidak dipasang dengan aman, akan jatuh dan menyebabkan cedera.

Saat mengganti baterai koin di remote kontrol, pastikan membuang baterai lama untuk
mencegah anak-anak menelannya.
Jika seorang anak menelan baterai koin, segera periksakan ke dokter.

Perhatian
Pemasangan pemutus kebocoran diperlukan dalam beberapa kasus tergantung pada
kondisi tempat pemasangan, untuk mencegah sengatan listrik.

Jangan memasang peralatan di tempat yang ada kemungkinan terjadinya kebocoran gas
mudah terbakar.
Jika gas mudah terbakar bocor dan berada di sekitar unit, dapat menyebabkan kebakaran.

Periksa untuk melihat apakah komponen-komponen dan kabel terpasang dan terhubung
dengan benar, dan apakah sambungan di terminal telah disolder atau diatur dengan aman.
Pemasangan dan sambungan yang tidak tepat dapat menyebabkan timbulnya panas
berlebihan, kebakaran atau sengatan listrik.

Jika platform atau rangka pemasangan telah berkarat, menggantinya.


Platform atau rangka pemasangan yang berkarat dapat menyebabkan unit jatuh, yang
mengakibatkan cedera.

Periksa arde (pembumian), dan memperbaikinya jika peralatan dibumikan


dengan tidak benar. Pembumian yang tidak tepat dapat menyebabkan
sengatan listrik.

vii
Pendahuluan SiMT281515E

Perhatian
Pastikan untuk mengukur hambatan isolasi setelah perbaikan, dan pastikan bahwa
hambatannya sebesar 1 M atau lebih.
Isolasi yang rusak dapat menyebabkan sengatan listrik

Pastikan untuk memeriksa saluran pembuangan unit indoor setelah perbaikan.


Saluran pembuangan yang rusak dapat menyebabkan air masuk ke ruangan dan
membasahi furnitur dan lantai.

Jangan memiringkan unit saat melepaskannya.


Air di dalam unit bisa tumpah dan membasahi furnitur dan lantai.

Pastikan untuk memasang kemasan dan segel pada rangka pemasangan dengan benar. Untuk tipe kesatuan
Jika kemasan dan segel tidak terpasang dengan baik, air dapat masuk ke dalam ruangan saja
dan membasahi furnitur dan lantai.

1.2 Ikon yang Digunakan


Ikon digunakan untuk menarik perhatian pembaca untuk informasi spesifik. Arti dari setiap ikon dijelaskan
dalam tabel di bawah:

Ikon Tipe Deskripsi


Informasi
Catatan "Catatan" memberikan informasi yang tidak diperlukan, tetapi mungkin tetap
berharga untuk pembaca, seperti tips dan trik.
Catatan:

Perhatian "Perhatian" digunakan ketika ada bahaya dimana pembaca, melalui


manipulasi yang salah, dapat merusak peralatan, kehilangan data,
Perhatian mendapatkan hasil yang tak diinginkan atau harus memulai ulang (bagian
dari) prosedur.
Peringatan "Peringatan" digunakan bila ada bahaya cedera pribadi.

Peringatan

Referensi "Referensi" memandu pembaca ke tempat-tempat lain di buku ini atau dalam
panduan ini, di mana dia akan menemukan informasi tambahan tentang topik
tertentu.

viii
SiMT281515E

Bagian 1
Informasi Umum
1. Nama Model Unit Indoor / Outdoor ......................................................... 2
2. Penampilan eksternal ................................................................................ 3

1 Informasi Umum
SiMT281515E Nama Model Unit Indoor / Outdoor

1. Nama Model Unit Indoor / Outdoor


Unit Indoor Unit Outdoor
Asupan Catu Daya
Tipe Nama Model Nama Model
FBQ100EVE(4) RZR100LUY1(4)
FBQ125EVE(4) RZR125LUY1(4)
Tipe Tekanan statis Unit Indoor: 1 fasa, 50 Hz, 220 - 240 V
tinggi dan menengah FBQ140EVE(4) RZR140LUY1(4)
sambungan Duct Unit Outdoor : 3 fasa, 50 Hz, 380 - 415 V
FBQ60EVE(4) × 2 RZR125LUY1(4)
FBQ71EVE(4) × 2 RZR140LUY1(4)

Informasi Umum 2
SiMT281515E

2. Penampilan eksternal
Unit Indoor

FBQ-E

Remote kontrol berkabel

BRC1C61 BRC1D61 BRC1E62

Remote kontrol nirkabel

( unit penerima
sinyal )

BRC4C66

Unit Outdoor

RZR100LUY1(4)
RZR125LUY1(4)
RZR140LUY1(4)

3 Informasi Umum
External Appearance SiMT281515E

Bagian 2
Fungsi-Fungsi
1. Fungsi-Fungsi ............................................................................................ 5

Fungsi - Fungsi 4
SiMT281515E

1. Fungsi- Fungsi
unit Indoor FBQ60-140EVE(4)
Kategori Fungsi
unit Outdoor RZQ100-140LUY1(4)
Kontrol inverter 
Ayunan otomatis —
Pilihan pola ayunan —
Fungsi pencegahan aliran udara dingin (pemanasan) —
Aliran udara naik turun sendiri —
Kecepatan kipas dapat diganti  (3 langkah)
Laju aliran udara otomatis  (*3)
Kenyamanan Mode kecepatan kipas tinggi —
Program “Dry” 
Aplikasi plafon tinggi —
Dua sensor suhu yang dapat dipilih (*1) 
Mulai panas (setelah pencairan bunga es) —
Pendinginan sepanjang tahun berlaku 
Operasi kebisingan malam rendah (*2) 
Pengaturan ulang otomatis Setpoint (*5) 
Pengaturan rentang Setpoint (*5) 
Remote Kontrol Pengatur waktu jadwal mingguan  (*3)
Pengatur waktu mati (off timer) (diprogram) (*5) 
Pengatur waktu Nyala/mati (On/Off timer) (*6) 
Filter udara anti-bakteri  (*4)
Filter udara tahan jamur —
Kebersihan
Penampung saluran anti bakteri ion perak 
Penampung saluran tahan jamur —
Mekanisme pompa saluran 
Diisi daya sebelumnya hingga 30 m (*2) 
Diisi daya sebelumnya hingga 10 m (*2) —
Filter tahan lama  (*4)
Kerja & Tanda Filter 
penservisan Pencegahan pengotor plafon —
Deteksi tekanan gas rendah (*2) 
Operasi darurat 
Fungsi diagnosis sendiri 
Memulai ulang otomatis 
Penggantian pemanasan/pendinginan otomatis —
Kontrol dengan 2 remote kontrol 
Kontrol grup dengan 1 remote kontrol 
Fitur kendali
Kontrol perintah eksternal  (*4)
Remote kontrol terpusat 
Kendali interlock 
Standar komunikasi DIII-NET 
Filter efisiensi tinggi 
Pilihan Filter sangat tahan lama —
Perkakas asupan udara segar —
Lain-lain Penukar panas anti korosi (*2) 

Catatan:
 : Tersedia
—: Tidak tersedia
*1: Berlaku jika remote kontrol berkabel digunakan
*2: Untuk unit outdoor
*3: Berlaku jika BRC1D61 atau BRC1E62 digunakan
*4: Pilihan
*5: Berlaku jika BRC1E62 digunakan
*6: Berlaku jika BRC1C61 digunakan

5 Fungsi-fungsi
Fungsi-fungsi SiMT281515E

Bagian 3
Remote Kontrol
1. Remote kontrol Berkabel ........................................................................... 7
1.1 Model yang berlaku ..............................................................................7
1.2 Nama dan Fungsi .................................................................................8
1.3 Pengaturan MAIN/SUB saat menggunakan 2 Remote Kontrol .............12
1.4 Pengaturan Nomor Grup Kontrol Terpusat ..........................................13
1.5 Mode Servis .......................................................................................15
1.6 Mode Inspeksi ....................................................................................19
2. Remote Kontrol Nirkabel ........................................................................ 20
2.1 Model yang Berlaku ............................................................................20
2.2 Nama dan Fungsi ...............................................................................20
2.3 Pengaturan MAIN/SUB dan Alamat ....................................................22

Remote Kontrol 6
SiMT281515E Remote Kontrol Berkabel

1. Remote kontrol berkabel


1.1 Model yang berlaku
Seri Model FBQ-E
Remote Kontrol BRC1C61
Remote kontrol berkabel dengan BRC1D61
Pengatur Waktu Jadwal Mingguan
Remote Kontrol Navigasi BRC1E62

7 Remote Kontrol
Remote Kontrol Berkabel SiMT281515E

1.2 Nama dan Fungsi


1.2.1 BRC1C61
4 2 1

3
6 8
10
5
9
7 11
12 19
18

17

14 13 15 16 20

1. Tombol ON/OFF 11. TAMPILAN TIDAK BERFUNGSI


Tekan tombol ini dan sistem akan mulai. Tekan tombol ini Jika fungsi tertentu tidak tersedia, tekan tombol ini akan
lagi dan sistem akan berhenti. menampilkan kata “NOT AVAILABLE” selama beberapa detik.
2. Lampu OPERATION (MERAH) 12. Tombol START/STOP MODE PENGATUR WAKTU
lampu ini menyala selama operasi. 13. Tombol ON/OFF PENGATUR WAKTU
3. TAMPILAN “ ” (DI BAWAH KENDALI 14. Tombol OPERASI UJI COBA/INSPEKSI
TERPUSAT) Tombol ini digunakan hanya oleh orang servis yang
Ketika muncul tampilan ini, sistem berada DI BAWAH memenuhi syarat untuk tujuan pemeliharaan.
KENDALI TERPUSAT. Jangan menggunakannya dalam operasi normal.
(Ini bukan spesifikasi standar) 15. Tombol WAKTU PEMROGRAMAN
4. Tampilan “ ”“ ” “ ” (MODE OPERASI) Gunakan tombol ini untuk memprogram waktu “START
Tampilan ini menunjukkan MODE OPERASI saat ini. dan/atau STOP”.
16. Tombol PENGATURAN SUHU
5. TAMPILAN “ TEST ” (OPERASI UJI COBA/INSPEKSI) Gunakan tombol ini untuk MENGATUR SUHU termostat.
Ketika TOMBOL OPERASI UJI COBA/INSPEKSI
ditekan, tampilan menunjukkan mode sistem berada di 17.Tombol ATUR ULANG TANDA FILTER
dalam.
hr
18.Tombol KONTROL KECEPATAN KIPAS
6. TAMPILAN “ ” (WAKTU YANG
DIPROGRAM) Tekan tombol ini untuk memilih kecepatan kipas, RENDAH
hr
atau TINGGI, tergantung pilihan anda.
Tampilan ini menunjukkan WAKTU YANG DIPROGRAM
sistem memulai atau berhenti. 19. Tombol PEMILIH MODE OPERASI
7. TAMPILAN “ C ” (SUHU YANG DIATUR) Tekan tombol ini untuk memilih MODE OPERASI.
Tampilan ini menunjukkan suhu yang diatur. 20. Tombol PENYESUAI ARAH ALIRAN UDARA
8. TAMPILAN “ ” (KECEPATAN KIPAS)
L H CATATAN
Tampilan ini menunjukkan kecepatan kipas: “RENDAH”
atau “TINGGI”.  Untuk kepentingan penjelasan, semua indikasi ditampilkan
9. TAMPILAN “ ” (KISI-KISI ALIRAN UDARA) pada tampilan tersebut berbeda dengan situasi sebenarnya
saat berjalan.
10. TAMPILAN “ ” (WAKTU UNTUK MEMBERSIHKAN
FILTER UDARA)
C: 3P177429-9S

Remote Kontrol 8
SiMT281515E Remote Kontrol Berkabel

1.2.2 BRC1D61
3 6 7 8 9 2 1

10
4 11
12
14 22
17
24

16 13 1518 19 20 21 5 23
28 32

25 34

26 35

36

27 29 30 31 33

1. Tombol ON/OFF ” 8. Ikon kontrol eksternal ”


Tekan tombol ON/OFF untuk memulai atau control icon “
Ikon ini menunjukkan bahwa pengendali lain dengan
menghentikan sistem. prioritas lebih tinggi mengendalikan atau
menonaktifkan instalasi Anda.
2. Lampu Operasi ”
Lampu operasi menyala selama operasi atau 9. Ikon penggantian di bawah kontrol
berkedip jika terjadi kesalahan. terpusat “ ”
Ikon ini menunjukkan bahwa penggantian instalasi di
3. Ikon mode operasi ”“ ” ” bawah kontrol terpusat yang ditetapkan untuk unit
Ikon-ikon ini mengindikasikan mode operasi indoor lain atau pemilih dingin /panas opsional yang
saat ini (FAN, DRY, COOLING). terhubung ke unit outdoor (= remote kontrol utama).

4. Ikon mode ventilasi 10. Indikator hari dalam seminggu


“MON TUE WED THU FRI SAT SUN”
“ ”“ ”“ ”
Ikon-ikon ini mengindikasikan mode ventilasi Indikator hari dalam seminggu menunjukkan hari
saat ini (ventilator pembaruan panas saja) minggu saat ini (atau hari yang diatur ketika
membaca atau memprogram pengatur waktu
(AUTOMATIC, HEAT EXCHANGE, BYPASS).
jadwal).
5. Ikon ventilasi ” 11. Tampilan jam “88:88 ”
Ikon ventilasi muncul jika ventilasi disesuaikan Tampilan jam menunjukkan waktu saat ini (atau
dengan tombol jumlah ventilasi (ventilator pembaruan waktu tindakan ketika membaca atau memprogram
panas saja). Secara bersamaan, jumlah ventilasi pengatur waktu jadwal).
ditunjukkan dengan ikon kecepatan kipas (lihat 22).
12. Suhu yang diatur maksimum “88
max
˚C ”
6. Ikon pembersih udara ” Suhu yang diatur maksimum menunjukkan suhu
Ikon ini menunjukkan bahwa unit pembersih udara yang diatur maksimum ketika dalam operasi batas.
(pilihan) bersifat opsional.
13. Suhu yang diatur minimum “88
min
˚C ”

Suhu yang diatur minimum menunjukkan suhu yang


7. Ikon leave home “ ” diatur minimum ketika dalam operasi batas.
Ikon leave home menunjukkan status fungsi leave
home. 14. Ikon pengatur waktu jadwal ”
Ikon ini menunjukkan bahwa pengatur waktu jadwal
Menyala (ON) Leave home diaktifkan. diaktifkan.
Berkedip Leave home aktif.
Mati (OFF) Leave home dinonaktifkan.

C: 3P107422-3D

9 Remote Kontrol
Remote Kontrol Berkabel SiMT281515E

15. Ikon tindakan “1 2 3 4 5” 28. Tombol Pemrograman “ ”


Ikon-ikon ini menunjukkan tindakan untuk setiap Tombol ini adalah tombol multi tujuan.
hari dari pengatur waktu jadwal. Tergantung pada manipulasi pengguna
sebelumnya, tombol pemrograman dapat
16. Ikon non-aktif “OFF” memiliki berbagai fungsi.
Ikon ini menunjukkan bahwa tindakan non-
aktif(OFF) dipilih ketika memprogram pengatur 29. Tombol pengatur waktu jadwal ” “ ”
waktu jadwal. Tombol ini mengaktifkan atau menonaktifkan
pengatur waktu jadwal.
17. Inspeksi yang diperlukan ” dan ”
Ikon-ikon ini menunjukkan bahwa inspeksi 30. Tombol penyesuai waktu “ ”“ ”
diperlukan. Konsultasikan dengan installer Anda. Tombol ini digunakan untuk menyesuaikan jam atau,
ketika dalam mode pemrograman, untuk
18. Tampilan suhu yang diatur “ ” menyesuaikan waktu tindakan yang diprogram.
Ini menunjukkan suhu instalasi yang diatur saat ini Kedua tombol memiliki fungsi pengulang otomatis
(tidak ditampilkan dalam operasi LIMIT atau mode (auto-repeat).
FAN atau DRY). 31. Tombol penyesuai suhu “ ”“ ”
Tombol ini digunakan untuk menyesuaikan setpoint
19. Pengaturan “SETTING” saat ini atau, ketika dalam mode pemrograman,
Tidak digunakan, untuk tujuan servis saja. untuk menyesuaikan suhu setpoint yang diprogram
(step = 1˚C). Kedua tombol juga digunakan untuk
20. Ikon arah aliran udara “ ” menyesuaikan hari dalam seminggu.
Ikon ini menunjukkan arah aliran udara (hanya
untuk instalasi dengan kisi-kisi aliran udara 32. Tombol min-max/ perubahan operasi “ ”
bermotor). Tombol ini merupakan tombol multi tujuan.
Tergantung pada manipulasi pengguna
21. Tidak tersedia ” sebelumnya, tombol ini dapat memiliki fungsi
“ ” ditampilkan kapanpun ketika pilihan sebagai berikut:
tidak terpasang dialamatkan atau fungsi tidak (1) Pilih mode operasi instalasi (FAN, DRY,
tersedia. COOLING)
(2) Beralih di antara suhu minimum dan suhu
22. Ikon kecepatan kipas “ ” ” ” ” maksimum ketika dalam operasi batas
Ikon ini menunjukkan kecepatan kipas yang diatur.

23. Ikon waktu pembersihan filter udara “ ” 33. Tombol batas/ setpoint “ ”“ ”
Ikon ini menunjukkan filter udara harus Tombol ini mengganti mode antara setpoint, operasi
batas atau OFF (mode pemrograman saja).
dibersihkan. Baca panduan tentang unit indoor.
34. Tombol kecepatan kipas “ ” ”
24. Ikon waktu pembersihan Elemen “ ”
Tombol ini mengganti antara L (rendah), H
Ikon ini menunjukkan elemen harus dibersihkan
(ventilator pembaruan panas saja). (tinggi), HH (sangat tinggi), (otomatis).

25. Tombol mode ventilasi “ ” 35. Tombol penyesuai arah aliran udara “ ”
Tombol mode ventilasi beroperasi pada ventilator Tombol ini memungkinkan untuk menyesuaikan arah
pembaruan panas; lihat panduan ventilator aliran udara.
pembaruan panas untuk lebih jelasnya
36. Tombol pengatur ulang ikon waktu pembersihan
26. Tombol jumlah ventilasi “ ” filter udara “ ”
Tombol ini mengatur jumlah ventilasi; lihat Tombol ini digunakan untuk mengatur ulang ikon
panduan ventilator pembaruan panas untuk lebih waktu pembersihan filter udara.
jelasnya.

27. Tombol UJI COBA/INSPEKSI “ ”


Tidak digunakan, hanya untuk tujuan servis.

C: 3P107422-3D

Remote Kontrol 10
SiMT281515E Remote Kontrol Berkabel

1.2.3 BRC1E62

1
11

4
5
6
7

9
8
3

10

1. Tombol Pemilih Mode 7. Tombol kiri " "


Digunakan untuk memilih mode operasi. • Digunakan untuk menyorot item berikutnya di
sisi kiri.
2. Tombol pengaturan aliran udara • Isi Tampilan berubah ke layar sebelumnya per
Digunakan untuk menunjukkan laju aliran udara ( halaman.
Volume Udara/ Kecepatan Kipas) / Layar arah aliran
udara. 8. Tombol ON/OFF
• Tekan tombol ini dan sistem akan mulai.
3. Tombol Menu/Enter • Tekan tombol ini lagi dan sistem akan berhenti.
• Digunakan untuk menunjukkan menu utama.
(Untuk rincian menu utama, lihat panduan operasi.) 9. Lampu operasi (Hijau)
• Digunakan untuk memasukkan item pengaturan Lampu ini menyala selama operasi. lampu berkedip
yang dipilih. jika terjadi kesalahan.

4. Tombol naik " " 10. Tombol pembatalan


• Digunakan untuk menaikkan suhu yang diatur. • Digunakan untuk kembali ke layar sebelumnya.
• Gunakan untuk menyorot item di atas pilihan saat • Tekan dan tahan tombol ini selama 4 detik atau
ini. (item yang disorot akan bergulir terus ketika lebih untuk menampilkan menu Pengaturan
tombol terus ditekan.) Servis.
• Digunakan untuk mengubah item yang dipilih.
11. LCD (dengan lampu latar)
5. Tombol Turun " " cahaya latar akan menyala selama kurang lebih 30
• Digunakan untuk menurunkan suhu yang diatur. detik dengan menekan setiap tombol operasi.
• Gunakan untuk menyorot item di bawah pilihan saat
ini. (item yang disorot akan bergulir terus ketika
tombol terus ditekan.)
• Digunakan untuk mengubah item yang dipilih.

6. Tombol Kanan " "


• Digunakan untuk menyorot item berikutnya di
sisi kanan.
• Isi Tampilan berubah ke layar berikutnya per
halaman.

11 Remote Kontrol
Remote Kontrol Berkabel SiMT281515E

1.3 Pengaturan MAIN/SUB ketika menggunakan 2 Remote


Kontrol
Situasi
Pengaturan MAIN/SUB diperlukan jika 1 unit indoor dikendalikan dengan 2 remote kontrol. Jika anda
menggunakan 2 remote kontrol (panel kontrol dan remote kontrol terpisah), Atur salah satu sebagai MAIN
dan lainnya sebagai SUB.
Pengat
uran Remote kontrol pengaturan pabrik ke MAIN, sehingga Anda hanya perlu mengubah salah satu remote
kontrol dari MAIN ke SUB. Untuk mengubah remote kontrol dari MAIN ke SUB, lakukan sebagai berikut:

1.3.1 BRC1C61/BRC1D61
Langkah Tindakan
1 Masukkan obeng pipih ke dalam ceruk antara bagian atas dan bawah remote kontrol, seperti yang
ditunjukkan pada ilustrasi di bawah ini. Pelan-pelan bongkar bagian atas remote kontrol, kerjakan
dari 2 posisi yang mungkin.

Bagian atas
remote kontrol

Bagian bawah remote


kontrol

2 Ubah saklar perubah MAIN/SUB pada PCB ke posisi “S”.


Saklar diatur ke posisi
M MAIN (pengaturan pabrik)
S

M
Atur saklar ke posisi SUB.
S

1.3.2 BRC1E62
Penunjukkan Remote kontrol utama dan sub dapat ditukar. Perhatikan bahwa perubahan ini dengan
mematikan daya ( OFF) dan kemudian menyalakan (ON) lagi.
Layar dasar
ditampilkan.
Pilih "Main RC" atau
tekan dan "Sub RC" dengan
Tekan tahan tombol menggunakan
tombol Cancel selama
tombol ▲/▼
4 detik atau
Cancel lebih (Up/Down), dan
sekali. kemudian tekan
Pilih "Switch Main Sub tombol Menu/Enter.
Controller" dan tekan tombol Tekan tombol
menu Menu/Enter. Menu/Enter.
pengaturan Item 2 Item 2
bidang ditampilkan ditampilkan
Tekan tombol Cancel.
ditampilkan . .

Remote Kontrol 12
SiMT281515E Remote Kontrol Berkabel

1.4 Pengaturan Nomor Grup Kendali Terpusat


1.4.1 BRC1C61/BRC1D61
Dalam rangka untuk melakukan remote kontrol terpusat dengan menggunakan remote kontrol pusat dan
pengendali ON/OFF terpadu, Pengaturan nomor Grup harus dibuat oleh grup dengan menggunakan
remote kontrol pengoperasian.
Lakukan pengaturan nomor Grup untuk remote kontrol terpusat dengan menggunakan remote kontrol
pengoperasian.
1. Selama dalam mode normal, tekan dan tahan saklar “ ” selama 4 detik atau lebih untuk
TEST

mengatur sistem ke "Mode Pengaturan Bidang (Field Setting Mode)".


2. Pilih Nomor MODE “00” dengan tombol “ ”.
3. Gunakan tombol “ ” untuk memilih Nomor grup untuk setiap grup.
(Nomor grup meningkat dalam urutan 1-00, 1-01, ... 1-15, 2-00, ... 4-15.)
4. Tekan “ ” atau “ ” untuk mengatur nomor grup yang dipilih.
5. Tekan “ TEST” untuk kembali ke MODE NORMAL.

BRC1C61

NO. MODE
NO. GRUP
MODE
PENGATUR
AN BIDANG

BRC1D61

NO. MODE
NO. GRUP
MODE
PENGATUR
AN BIDANG

Catatan :
 Untuk nomor grup pengaturan ventilator pembaruan panas dan adaptor pengkabelan untuk pendingin
ruangan lain, dll., Lihat panduan operasi.

CATATAN
Masukkan nomor grup dan tempat instalasi unit indoor ke dalam tabel instalasi yang terlampir. Pastikan
untuk menyimpan tabel instalasi ini bersama dengan panduan operasi untuk pemeliharaan.

13 Remote Kontrol
Remote Kontrol Berkabel SiMT281515E

1.4.2 BRC1E62
< Group No. Setting (Group)>
Layar dasar
ditampilkan.
Tekan dan tahan tombol
Tekan Tombol Cancel selama 4 detik atau
Cancel sekali lebih
Pilih "Group No. setting"
dan kemudian tekan
Tombol Menu/Enter.
Menu Field
Item 2
setting
ditampilkan
ditampilkan Tekan tombol
Cancel sekali.
Tekan Tombol
Pilih "Group Cancel sekali
No. setting
(Group)"
dan
kemudian
tekan
tombol
Menu/Enter
Item 2
ditampilkan.
Pilih Group No.
yang diinginkan
Tekan dengan
tombol menggunakan
Menu/Enter
tombol
(Up/Down) ▲/▼,
dan kemudian
tekan tombol
Menu/Enter
Item 2
ditampilkan.

Layar dasar
ditampilkan.
Tekan dan tahan tombol
Tekan Tombol Cancel selama 4 detik atau
Cancel sekali lebih

Pilih "Group No. setting"


dan kemudian tekan
Menu Field Tombol Menu/Enter.
Item 2
setting Tekan tombol
ditampilkan.
ditampilkan. Cancel sekali.
Pilih “Group Tekan tombol
No. setting Cancel sekali
(Unit)” dan
kemudian
tekan tombol
Menu/Enter

Item
Item 2
2 is
displayed.
ditampilkan.
Pilih Group No.
Tekan yang diinginkan
tombol dengan
Menu/Enter menggunakan
tombol
(Up/Down) ▲/▼,
dan kemudian
tekan tombol
Menu/Enter
Item 2
ditampilkan.

Remote Kontrol 14
SiMT281515E Remote Kontrol Berkabel

1.5 Mode Servis


1.5.1 BRC1C61/BRC1D61
(1) Menampilkan Data Servis

No. Unit No. Mode

No. Kode Mode


Kedua Pengatura
n Bidang
3 4
No. Kode
Pertama
.

1 2 7
5 3
6

1. Masuk mode pengaturan bidang.


Tekan tombol operasi INSPECTION/TEST selama 4 detik atau lebih.
2. Masuk mode servis.
Setelah masuk mode pengaturan bidang, Tekan tombol operasi INSPECTION/TEST selama 4 detik atau
lebih.
3. Pilih No. mode
Atur No. mode yang diinginkan dengan tombol pengaturan suhu up/down.
4. Pilih No. unit
Pilih No. unit indoor yang diatur dengan tombol START/STOP mode waktu.
5. Pilih error history No. (nomor riwayat kesalahan) yang diinginkan atau thermistor data No. (nomor data
termistor) dengan tombol “ ” atau “ ”.
6. Tampilan setiap data (Lihat tabel tampilan di bawah ini)
7. Kembali ke mode operasi normal.
Tekan tombol operasi INSPECTION/TEST sekali.
No. Mode Fungsi Isi dan Metode Operasi Contoh Tampilan Remote Kontrol
40 Riwayat Anda dapat mengubah riwayat ini
Kesalahan dengan tombol up-down waktu Past error
code
pemrograman.
UNIT No.
CODE
1
2-C4 40
SETTING
Error history 1: Newest

3: Oldest
 "00" displayed for 4 and subsequent.

41 Tampilan Data Pilih display thermistor dengan


Termistor tombol up-down waktu Thermistor type
pemrograman
Display thermistor Temperature
00: Termistor suhu kamar di remote
kontrol
01
01: Termistor udara hisap
02: Termistor penukar panas
UNIT No.

27 41
SETTING

15 Remote Kontrol
Remote Kontrol Berkabel SiMT281515E

(2) Pengaturan servis

NO. MODE
NO. UNIT NO. MODE MODE FIELD SETTING
NO. KODE
4, 5
MODE
KEDUA FIELD 4, 5
3 SETTING
NO. KODE 4
PERTAMA

1 2 6
NO. KODE KEDUA
5 3
5 NO. KODE PERTAMA

1, 2, 6

1. Masuk mode pengaturan bidang.


Terus tekan tombol operasi INSPECTION/TEST setidaknya selama 4 detik.
2. Masuk mode pemeliharaan.
Setelah masuk mode pengaturan bidang, terus tekan tombol operasi INSPECTION/TEST setidaknya
selama 4 detik.
3. Pilih No. mode
Atur No. mode yang diinginkan dengan tombol pengatur suhu up/down. (Mode 43 hanya dapat
dilakukan untuk remote kontrol nirkabel)
4. Pilih No. unit
Pilih No. unit indoor yang diatur dengan tombol START/STOP MODE TIME.
(Pilih No. unit indoor dengan tombol up/down untuk remote kontrol nirkabel.)
5. Lakukan pengaturan yang diperlukan untuk setiap mode. (Mode 43 hanya dapat dilakukan untuk
remote kontrol nirkabel)
• Dalam hal Mode 43
Tekan TOMBOL TIMER ON/OFF untuk menentukan Kipas Dinyalakan paksa (forced Fan ON).
• Dalam hal Mode 44
Atur “Kecepatan kipas (Fan speed)” dengan TOMBOL KONTROL KECEPATAN KIPAS dan “Arah
aliran udara (Airflow direction)” dengan TOMBOL PENYESUAI ARAH ALIRAN UDARA, kemudian
tekan TOMBOL TIMER ON/OFF untuk menentukannya.
• Dalam hal Mode 45
Pilih No. unit yang diubah dengan tombol “ ” atau “ ”, lalu tekan TOMBOL TIMER ON/OFF untuk
menentukannya.
6. Kembali ke mode operasi normal.
Tekan tombol operasi INSPECTION/TEST sekali.
No. Mode Fungsi Isi dan Metode Operasi Contoh Tampilan Remote Kontrol
43 Kipas Menyalakan kipas untuk UNIT No.
Dinyalakan paksa setiap unit secara individual.
SETTING
44 Pengaturan Mengatur kecepatan kipas dan arah aliran
individual udara untuk setiap unit secara individual
Fan 1 : Low
speed
ketika menggunakan kendali grup. 3 : High 0: Upper
Pengaturan dilakukan dengan Airflow direction
menggunakan tombol “airflow UNIT No. 4: Lowest
direction adjust” dan “fan speed
adjust”.
CODE SETTING

45 Perubahan No. Mengubah No. Unit


Unit Mengatur No. unit setelah melakukan
perubahan dengan tombol up-down
waktu pemrograman.

Remote Kontrol 16
SiMT281515E Remote Kontrol Berkabel

1.5.2 BRC1E62
Mengoperasikan remote kontrol memungkinkan data servis untuk diperoleh dan berbagai servis untuk
diatur.
Layar dasar
ditampilkan .

Tekan Tekan tombol


tombol Tekan dan tahan tombol Cancel
Cancel.
Cancel selama 4 detik atau lebih.
sekali.

Menu pengaturan
servis ditampilkan.

Tekan Tekan dan tahan


tombol
tombol Cancel selama 4
Cancel detik atau lebih.
sekali.
Pilih item yang diinginkan dari
menu Maintenance, dan kemudian Pilih No. Unit yang
menu tekan tombol Menu/Enter .
Item 2 diinginkan dengan
Maintenance ditampilkan menggunakan tombol
Tekan tombol Cancel. (Up/Down)▲/▼. Data yang
ditampilkan . sesuai akan ditampilkan.
.
Menu Servis Item 2 Keterangan
1. Nama Model 1. Unit No. Pilih No. Unit yang anda ingin periksa.
2. Indoor unit
3. Outdoor unit
2. Jam operasi 1. Unit No. Pilih No. Unit yang anda ingin periksa.
2. Indoor unit operating Semua ini ditampilkan dalam jam.
time
3. Indoor unit fan operation
time
4. Indoor unit energized
time
5. Outdoor unit operating
time
6. Outdoor unit fan 1
operation time
7. Outdoor unit fan 2
operation time
8. Outdoor comp. 1
operation time
9. Outdoor comp. 2
operation time
3. Status Unit Indoor 1/3 1. Unit No. Pilih No. Unit yang anda ingin periksa.
2. FAN Tap, kecepatan (rpm)
3. FLAP Berayun, tetap
4. Speed Kecepatan kipas (rpm)
5. EV Derajat katup ekspansi elektronik terbuka (pulsa)
6. MP ON/OFF pompa saluran
7. EH ON/OFF Pemanas listrik
8. Hu ON/OFF kelembaban udara
9. TbF ON/OFF kendali Anti-pembekuan
3. Status Unit Indoor 2/3 1. FLOAT
2. T1/T2

17 Remote Kontrol
Remote Kontrol Berkabel SiMT281515E

Menu Servis Item 2 Keterang


3. Tampilan Status Indoor 1. Unit No. an periksa.
Pilih Unit No. yang ingin anda
3/3 2. Th1 Termistor udara hisap
3. Th2 Termistor penukar panas
4. Th3 —
5. Th4 Termistor udara buangan
6. Th5 —
7. Th6 —
4. Tampilan Status Unit 1. Unit No. Pilih Unit No. yang ingin anda periksa.
Outdoor 1/2 2. FAN Step Kecepatan kipas
3. COMP Frekuensi catu daya kompresor (Hz)
4. EV1 Derajat katup ekspansi elektronik terbuka
5. SV1 ON/OFF katup Solenoid
4. Tampilan Status Unit 1. Th1 Termistor udara Outdoor
Outdoor 2/2 2. Th2 Termistor penukar panas
3. Th3 Termistor pipa pembuangan
4. Th4
5. Th5
6. Th6
5. Pencairan paksa 1. Forced defrost ON Mengaktifkan operasi pembersihan bunga es paksa.
(Tidak tersedia) 2. Forced defrost OFF Menonaktifkan operasi pembersihan bunga es paksa.
6. Tampilan kesalahan 1. Display Error ON Menampilkan kesalahan pada layar.
2. Display Error OFF Menampilkan tidak ada kesalahan maupun peringatan.
3. Display warning ON Menampilkan peringatan pada layar jika terjadi kesalahan.
4. Display warning OFF Tidak ada peringatan ditampilkan.
7. No. Unit Swap 1. Current Unit No. Sebuah unit No. dapat dialihkan ke yang lain.
2. Transfer Unit No.
8. Nilai Sensor yang  Unit No.: 0 - 15 Pilihthe Unit No. yang anda ingin periksa.
dialamatkan  Code
00: Termistor remote kontrol (°C)
01: Termistor udara hisap (°C)
02: Termistor pipa cair penukar panas (°C)
03: Termistor pipa gas penukar panas (°C)
04: No. alamat unit Indoor
05: No. alamat unit Outdoor
06: No. alamat unit BS
07: No. alamat zona kendali
08: No. alamat jumlah pendinginan/pemanasan
09: No. alamat Demand.
 Data Data yang sesuai akan ditampilkan, berdasarkan No.
Unit dan Kode yang dipilih.

Remote Kontrol 18
SiMT281515E Remote Kontrol Berkabel

1.6 Mode Inspeksi


1.6.1 BRC1C61/BRC1D61

Tampilan Normal (Layar kosong)


Tekan tombol INSPECTION/TEST sekali.

Unit 0
Error code L0
Inspection
(1) mode Inspeksi
(1) Mode Inspeksi
Tekan tombol INSPECTION/TEST sekali Unit 0
Error code L0
Inspection
Kode kesalahan berkedip jika terjadi kesalahan.

–––
5U2

(2) Kode model unit Indoor


(2) Tampilan kode model unit Indoor
Tampilan Model
Tekan tombol INSPECTION/TEST sekali 5U2 FBQ-E

–––
2AA

(3) Tampilan kode model unit outdoor


Tekan tombol INSPECTION/TEST sekali

(3) Kode model unit Outdoor


Test operation Tampilan Model
Mode operasi uji coba
2AA RZR

Tekan tombol INSPECTION/TEST sekali

Catatan:
Mode Inspeksi tidak tersedia untuk BRC1E62.

19 Remote Kontrol
Remote Kontrol Nirkabel SiMT281515E

2. Remote Kontrol Nirkabel


2.1 Model yang berlaku
Seri Model FBQ-E
Remote Kontrol BRC4C66

2.2 Nama dan Fungsi

(1)
ON OFF (8)

(3) H L
DOWN (10)
C
ON OFF
(6) UP

TEMP
FAN H M L TIME (11)
(4)
C
hr. UP
(9) FAN
DOWN
(2) hr. (13)
RESERVE CANCEL
hr.
(5) TI MER (12)
TEST hr.
MODE (15)
(7)
SWING (14)
(16)
TEST
TEST (17)

Penerima

(18)

(20)
(22)

(19)
(21)

Remote Kontrol 20
SiMT281515E Remote Kontrol Nirkabel

TAMPILAN “ ” (TRANSMISI SINYAL) 12 TOMBOL START/STOP MODE TIMER


1 13 TOMBOL RESERVE/CANCEL TIMER
Menyala ketika sinyal sedang dikirim. TOMBOL PENYESUAI ARAH ALIRAN
14
UDARA
TAMPILAN ”“ ”“ ” (MODE TOMBOL PEMILIH MODE OPERASI
OPERASI)
2
Tampilan ini menunjukkan MODE 15 Tekan tombol ini untuk memilih MODE
OPERASI saat ini. OPERASI. “ ” (COOL), “ ”
H M L
(FAN),“ ” (DRY).
TAMPILAN “ ” (SUHU YANG DIATUR) TOMBOL ATUR ULANG TANDA FILTER
C
3
Tampilan ini menunjukkan suhu 16 Lihat bagian MAINTENANCE dalam
yang diatur. panduan operasi yang terlampir pada
unit indoor.
TAMPILAN “ hr. hr. ” TOMBOL OPERASI UJI COBA /
(WAKTU YANG DIPROGRAM) INSPEKSI
4
17 Tombol ini digunakan hanya oleh orang
Tampilan ini menunjukkan WAKTU YANG
DIPROGRAM mengenai sistem mulai atau berhenti.
servis yang memenuhi syarat untuk
tujuan pemeliharaan.
5 TAMPILAN “ ” (SIRIP ALIRAN UDARA) SAKLAR OPERASI DARURAT
TAMPILAN “ ” “ ” “ ”( KECEPATAN KIPAS) 18 Saklar ini siap digunakan jika remote
6
Tampilan ini menunjukkan kecepatan kipas yang diatur.
kontrol tidak bekerja.
PENERIMA
TAMPILAN “ TEST” (OPERASI
19 Menerima sinyal dari remote kontrol.
INSPEKSI/ UJI COBA)
Jika TOMBOL OPERASI
7 INSPECTION/TEST ditekan, tampilan LAMPU INDIKATOR OPERASI
(merah)
menunjukkan mode sistem berada di
dalam. Jangan mengoperasikan tombol 20 Lampu ini tetap menyala selama
ini selama penggunaan normal. pendingin ruangan berjalan. Lampu
berkedip saat unit bermasalah.
TOMBOL ON/OFF
LAMPU INDIKATOR TIMER (Hijau)
8 Tekan tombol ini dan sistem akan 21
Lampu ini tetap menyala selama timer diatur.
mulai. Tekan tombol ini lagi dan
sistem akan berhenti. LAMPU INDIKATOR WAKTU
TOMBOL KONTROL KECEPATAN KIPAS PEMBERSIHAN FILTER UDARA (Merah)
22
Menyala ketika saatnya untuk
9 Tekan tombol ini untuk memilih
kecepatan kipas, Rendah atau Sedang membersihkan filter udara.
atau Tinggi, tergantung pilihan anda.
TOMBOL PENGATURAN SUHU
10 Gunakan tombol ini untuk MENGATUR
SUHU.
TOMBOL TIMER PEMOGRAMAN /
PENYESUAIAN SUHU

11 Gunakan tombol ini untuk pengaturan suhu


dan memprogram waktu “START dan/atau
STOP”. (Beroperasi dengan penutup depan
remote kontrol yang terbuka.)

3P107422-8S

21 Remote Kontrol
Remote Kontrol Nirkabel SiMT281515E

2.3 Pengaturan MAIN/SUB dan Alamat


Pendahuluan
Untuk mengatur remote kontrol nirkabel, Anda harus mengatur alamat untuk:
 Penerima remote kontrol nirkabel.
 Remote kontrol nirkabel.

Mengatur Alamat untuk Penerima


Alamat untuk penerima remote kontrol nirkabel adalah pengaturan pabrik ke 1. Untuk mengubah pengaturan
ini, lakukan sebagai berikut:
Atur saklar (SS2) alamat nirkabel pada PCB sesuai dengan tabel di bawah ini.
No. Unit No. 1
1 No. 2 No. 3

1
Saklar (SS2) OW
2

2
alamat nirkabel

2
3

3
Bila menggunakan kedua remote kontrol berkabel dan nirkabel untuk 1 unit indoor, remote kontrol berkabel
harus diatur ke MAIN. Oleh karena itu, atur saklar (SS1) MAIN/SUB penerima ke SUB.
MAIN/SUB MAIN SUB

saklar (SS1) S S
MAIN/SUB M M

Mengatur Alamat untuk Remote Kontrol Nirkabel


Alamat untuk remote kontrol nirkabel adalah pengaturan pabrik ke 1. Untuk mengubah pengaturan ini,
lakukan sebagai berikut:

1. Tahan tombol “ ” dan tombol “ ”


setidaknya selama 4 detik untuk masuk ke mode Field
Setting.
(Ditunjukkan di bidang tampilan pada gambar di sebelah kanan.)

2. Tekan tombol “ ” dan pilih beberapa pengaturan (A/ b).


Setiap kali tombol ditekan saklar tampilan antara “A”
dan ”b”

3. Tekan tombol “ ” atau tombol “ ” untuk mengatur


alamat.
1 2 3 4 5 6

Alamat dapat diatur dari 1 sampai 6, namun atur alamat


ke 1 ~ 3 dan untuk alamat yang sama sebagai penerima
(penerima tidak bekerja dengan alamat 4 ~ 6.)

4. Tekan tombol “ ” untuk masuk ke pengaturan.

5. Tekan tombol “ ” setidaknya selama 1 detik


untuk menghentikan mode Field Setting dan kembali ke
tampilan normal.

Remote Kontrol 22
SiMT281515E Remote Kontrol Nirkabel

Beberapa pengaturan A/b


Ketika unit indoor sedang beroperasi dengan kontrol eksternal (remote kontrol pusat, dll), terkadang tidak
merespon perintah pengaturan suhu dan ON/OFF dari remote kontrol ini. Periksa apa pengaturan yang
diinginkan oleh pelanggan dan lakukan beberapa pengaturan seperti yang ditunjukkan di bawah ini.
Remote Kontrol FBQ-E
Beberapa pengaturan Tampilan remote kontrol Untuk mengendalikan unit dan pendingin ruangan lainnya Untuk selain di sebelah kiri

Perintah selain ON / OFF dan pengaturan suhu


A: Standar Semua item ditampilkan. diterima. (1 BUNYI BIP PANJANG atau 3
BUNYI BIP PENDEK dikeluarkan )
Operasi tetap ditampilkan
b: Multi Sistem tak lama setelah eksekusi. Semua perintah diterima (2 BUNYI BIP PENDEK)

23 Remote Kontrol
SiMT281515E

Bagian 4
Fungsi dan Kontrol
1. Fungsi Komponen Utama dan termistor
(Diagram Pemipaan)................................................................................ 25
2. Garis besar fungsi .................................................................................... 28
2.1 Unit Indoor ............................................................................................28
2.2 Unit Outdoor ..........................................................................................29
3. Diagram Alir Operasi................................................................................ 30
3.1 Operasi Kering / Pendinginan ................................................................30
4. Rincian Fungsi ......................................................................................... 31
4.1 Unit Indoor .............................................................................................31
4.2 Unit Outdoor ..........................................................................................36

Fungsi dan Kontrol 24


SiMT281515E Remote Kontrol Nirkabel
25

1. Fungsi Komponen utama dan Termistor


Fungsi Komponen utama dan Termistor (Diagram Pemipaan)
(Diagram Pemipaan)
RZR100LUY1(4)
Penukar panas Outdoor
(B) katup ekspansi
elektronik
Filter

Port pengukur
Sensor R5T
S1NPH tekanan
R1T
(5/16" flare)
R2T R3T R3T
Penukar panas Indoor

R4T Saklar 
Tekanan R10T
(tinggi)
 S1PH


R1T

R2T
perpipaan bidang 9.5
C1220T-O Aki
perpipaan bidang 15.9 (A) Kompresor
C1220T-O

unit Indoor unit Outdoor


Katup penghenti
(dengan port servis 5/16"
Fungsi dan Kendalil

flare)  Termistor R10T terletak dekat kotak komponen listrik.

SiMT281515E
C: 3D079463
Fungsi dan Kendali

SiMT281515E
 RZR125LUY1(4) / RZR140LUY1(4)
(B) Katup ekspansi
elektrik Penukar panas Outdoor
Filter

Fungsi komponen utama dan Termistor (Diagram Pemipaan)


R5T
S1NPH Sensor
tekanan R1T
port pengukur
R2T R3T R3T
Penukar panas Indoor (5/16" flare)

R4T 
Saklar R10T
tekanan
(tinggi)
S1PH

R1T

R2T
Perpipaan bidang 9.5
C1220T-O Aki
Perpipaan bidang 15.9 (A) Kompresor
C1220T-O

unit Indoor unit Outdoor


Katup penghenti
(dengan port servis 5/16"
flare)  Termistor R10T terletak dekat kotak komponen listrik.

C: 3D079464
26
Fungsi Komponen Utama dan Termistor (Diagram Pemipaan) SiMT281515E

 Unit Outdoor

(A) Kompresor
Unit pengerak Inverter mengubah frekuensi operasi kompresor untuk mengendalikan kapasitas dan
faktor lainnya.

(B) Katup Ekspansi Elektronik (Y1E)


Memberikan kontrol untuk menjaga kondisi operasi optimum untuk efisiensi tinggi.

R1T (Termistor Udara Outdoor)


• Digunakan untuk kontrol kecepatan kipas unit outdoor.
• Digunakan untuk kontrol perbedaan tekanan.
• Digunakan untuk keseluruhan kontrol perlindungan arus.

R2T (Termistor Pipa Pembuangan)


• Digunakan untuk perlindungan suhu pipa pembuangan selama operasi kompresi.

R3T (Termistor Pipa Hisap)


• Digunakan untuk kontrol super panas hisap dengan katup ekspansi elektronik.

R4T (Termistor Pipa Cair)


• Digunakan untuk mendeteksi suhu pipa cair.

R5T (Termistor Penukar Panas Sedang)


• Digunakan untuk perhitungan tekanan tinggi selama operasi pendinginan.
(Dihitung berdasarkan suhu yang terdeteksi dan karakteristik refrigeran R-410A)

R10T (Termistor sirip Radiasi)


• Digunakan untuk kontrol kecepatan kipas unit outdoor.
• Digunakan untuk kontrol suhu sirip radiasi.
• Digunakan untuk kontrol perbedaan tekanan.

S1NPH (Sensor Tekanan Tinggi)


• Digunakan untuk mendeteksi tekanan tinggi.

S1PH (Saklar Tekanan Tinggi)


• Saklar diaktifkan pada tekanan tinggi untuk menghentikan operasi kompresor.

 Unit Indoor

R1T (Termistor Udara Hisap)

R2T (Termistor Pipa Cair Penukar Panas Indoor)

R3T (Termistor Penukar Panas Indoor)

27 Fungsi dan Kontrol


SiMT281515E Garis besar fungsi

2. Garis Besar Fungsi


2.1 Unit Indoor

(Input) (Output)
Unit Indoor
(Fungsi)
Kontrol Termostat
2 termostat yang digunakan,
Sensor hisap termostat hisap dan remote kontrol. Motor Kipas
Fungsi pemantauan

Pompa saluran
Program Kering
Sensor Penukar Panas

Operasi Kipas
Tampilan LED

Kontrol Pompa saluran

Bel, LED
unit nirkabel saja
Saklar apung Fungsi Pencegahan
Beku

Kontrol Kipas Unit Indoor


Kontrol Fasa

Fungsi Pencegahan Udara


Jumlah Putaran Kipas
Dingin

Fungsi Penjagaan Mode


Operasi

Fungsi Deteksi Kesalahan

Fungsi Pencegahan
Saklar Operasi Pengotor Plafon
Darurat
Fungsi mulai ulang otomatis
Unit nirkabel saja

Remote Kontrol
dengan Kristal cair

ON/OFF
Kecepatan
Kecepatan .
kipas , dllkipas , dll

Sensor Remote
Kontrol
(Tidak disediakan untuk
remote kontrol nirkabel.)

Fungsi dan Kontrol 28


SiMT281515E Diagram Alir Operasi

2.2 Unit Outdoor

(Input) (Output)
Unit Outdoor

Termistor Udara Outdoor Kontrol ON/OFF Kompresor Kompresor

Termistor Penukar Panas Fungsi Siaga 3 menit Motor Kipas

Termistor Pipa Pembuangan Kontrol Kipas Unit Outdoor Katup Ekspansi elektronik

Termistor Pipa Hisap Kipas Unit Outdoor Mulai Tampilan LED

Termistor Penukar Panas


Kontrol Pendinginan Sepanjang tahun
Sedang

Termistor sirip Radiasi Kontrol Katup Ekspansi Elektronik

PS untuk Perlindungan Tekanan Tinggi


Kontrol OFF Termostat Paksa

Sensor Tekanan Tinggi


Operasi uji coba

Trafo Arus
Fungsi Deteksi Kesalahan

Sinyal Unit Indoor


Fungsi Operasi tiruan

Saklar Pengaturan

29 Fungsi dan Kontrol


Function Outline SiMT281515E

3. Diagram Alir Operasi


3.1 Operasi Kering/Pendinginan
Catu Daya Aktif ( ON)

Inisialisasi katup ekspansi elektronik


Inisialisasi mikro-komputer
A
Kontrol operasi sebelum pemanasan

Penilaian operasi Remote kontrol

Penilaian Mode
Darurat
operasi

Pendinginan/Kering Operasi Darurat

Cooling/Dry

Penilaian termostat ON

kontrol startup
B

Kontrol Normal
Kontrol langkah kompresor Kontrol perlindungan arus Inverter
Kontrol katup PI ekspansi elektronik Kontrol perlindungan suhu sirip radiasi
Kontrol perlindungan tekanan tinggi Kontrol perlindungan arus keseluruhan
Kontrol suhu pipa pembuangan Kontrol pendinginan suhu udara outdoor rendah
Operasi tiruan

Penilaian termostat OFF


Penilaian
Penilaian awal operasi Ruang kontrol termostat Penilaian Penilaian
operasi remote penghentian yang
pemulihan minyak Thermostat OFF dengan siaga
kontrol OFF tidak normal
pencegahan beku

Indikasi
operasi pemulihan minyak operasi residu pump down kode
kesalahan
Penilaian akhir operasi Memulai ulang siaga
pemulihan minyak

A
B

Fungsi dan Kontrol 30


SiMT281515E Rincian Fungsi

4. Rincian Fungsi
4.1 Unit Indoor
4.1.1 Ruang Kontrol Termostat
Berdasarkan perbedaan antara suhu yang diatur dengan remote kontrol dan suhu kamar yang sebenarnya
terdeteksi (1), termostat dinyalakan atau dimatikan.

Catatan:
1. Termistor untuk mendeteksi suhu kamar adalah sebagai berikut sesuai dengan pengaturan bidang.
a. Pengaturan pabrik: Termistor udara hisap dalam unit indoor
b. Saat mulai termistor suhu kamar: Termistor suhu kamar dalam remote kontrol

(1) Dalam Operasi Normal


T: Suhu kamar terdeteksi - Suhu diatur oleh remote kontrol

 Dalam pendinginan

atau • T  -0.5ºC terus berlanjut selama 1 menit.


Operasi Normal • T  -2ºC
Termostat OFF
(Termostat ON)
T  +0.5ºC

(2) Dalam Program Operasi Kering


Tro: Suhu udara kamar yang terdeteksi saat operasi kering dimulai
Tr: Suhu termistor kamar (terdeteksi oleh termistor suhu kamar)
T: Suhu kamar terdeteksi (Tr) – Suhu udara kamar saat startup (Tro)

Suhu Startup Operasi Kering


(Tro: Suhu udara kamar saat startup)
Termostat ON
T 2
Differential
1.0 or 1.5ºC (4) Tr
Termostat OFF
3
Operasi kering
Termo. OFF Operasi kering

Waktu
T < -1.0 or 1.5ºC (4)
(3)
Operasi kering Termostat OFF
T  0
(2)
4. Nilai ini berubah sesuai dengan model.

31 Fungsi dan Kontrol


Rincian Fungsi SiMT281515E

4.1.2 Menggunakan Kondisi untuk Termistor Suhu Kamar dalam


Remote Kontrol
Berlaku
Termistor suhu kamar dalam remote kontrol hanya tersedia dalam remote kontrol berkabel.

Metode
Termistor suhu kamar dalam remote kontrol yang standarnya dinonaktifkan untuk unit SkyAir.
Penggunaan termistor suhu kamar dalam remote kontrol dapat diaktifkan dengan mengubah pengaturan
bidang 10(20)-2-02 sampai 10(20)-2-01.

Kondisi
Tabel di bawah ini berisi kondisi di mana termistor suhu kamar dalam remote kontrol tidak digunakan:
Kondisi Termistor suhu kamar dalam remote kontrol tidak digunakan jika...
1 Ketidaknormalan termistor suhu kamar dalam remote kontrol.
2 Kontrol Grup digunakan.
3 Kombinasi suhu udara hisap / suhu yang diatur di luar jangkauan. (Lihat grafik di bawah ini)

pendingi
nan Diagram dibawah ini menunjukkan rentang operasi kombinasi suhu udara hisap / suhu yang diatur dalam
operasi pendinginan:
˚C
32
Suhu yang diatur TH1 = Ts - 1
(Ts)
30
TH1 = Ts + 1

28 TH1 = Ts - 3

26 TH1 = Ts + 3

A B C D E F
24

22

20

18

16 ˚C
12 14 16 18 20 22 24 26 28 30 32 34
Suhu udara hisap (TH1)
Rentang dimana Rentang dimana Diferensial
termistor dalam termistor udara
remote kontrol dapat hisap dalam unit
digunakan indoor dapat
digunakan
Contoh
Dengan asumsi suhu yang diatur adalah 24 ° C atau lebih, dan suhu udara hisap telah berubah dari
18°C menjadi 30°C (A --> F):
(Contoh ini juga mengasumsikan ada beberapa pendingin ruangan lain, sistem VRV MATI, dan suhu
berubah bahkan ketika termistor suhu kamar dalam remote kontrol MATI.) Termistor udara hisap
dalam unit indoor digunakan untuk suhu dari 18°C - 23°C (A --> C).
Termistor suhu kamar dalam remote kontrol digunakan untuk suhu dari 23°C - 27°C (C --> E).
Termistor udara hisap dalam unit indoor digunakan untuk suhu dari 27°C - 30°C (E --> F).

Dan dengan asumsi suhu udara hisap telah berubah dari 30°C menjadi 18°C (F --> A):
Termistor udara hisap dalam unit indoor digunakan untuk suhu dari 30°C menjadi 25°C (F --> D).
Termistor suhu kamar dalam remote kontrol digunakan untuk suhu dari 25°C menjadi 21°C (D --> B).
Termistor udara hisap dalam unit indoor digunakan untuk suhu dari 21°C menjadi 18°C (B --> A).

Fungsi dan Kontrol 32


SiMT281515E Rincian Fungsi

4.1.3 Fungsi Identifikasi Unit Outdoor


Tujuan
Tujuan fungsi identifikasi unit outdoor adalah untuk mengaktifkan unit indoor secara otomatis menentukan
mode operasi apapun harus diatur dalam fungsi dari tipe unit outdoor yang terhubung.

Mode operasi
Mode operasi yang mungkin adalah:
Unit Outdoor Mode operasi
Pendinginan saja  Fan
 Cooling
 Program dry

Input yang digunakan


Fungsi identifikasi unit outdoor menggunakan input sebagai berikut:
Input Koneksi pada Koneksi pada
PCB unit indoor PCB unit outdoor
PCB unit Indoor TC & RC —
PCB unit Outdoor — TC & RC

TC: Transmission circuit (sirkuit transmisi)


RC: Receiving circuit (sirkuit penerima)

33 Fungsi dan Kontrol


Rincian Fungsi SiMT281515E

4.1.4 Kontrol Kipas Unit Indoor


Garis besar
Selama kompresor memulai dan menghentikan kontrol, kipas unit indoor akan menerima instruksi dari unit
outdoor untuk melindungi kompresor dari menerima cairan dan untuk menjamin kompresor halus memulai:
 Kontrol kipas unit Indoor selama kompresor berhenti
 Kontrol kipas unit Indoor sebelum kompresor memulai
 Kontrol kipas unit Indoor saat kompresor memulai

Selama kompresor berhenti


Pengatur kipas unit Indoor
Pendinginan Indoor Termostat OFF Pengaturan Remote Kontrol
Remote kontrol OFF OFF
Program kering Termostat OFF OFF
Remote kontrol OFF OFF

Sebelum kompresor memulai


Pengatur kipas unit Indoor
Pendinginan Indoor Pengaturan Remote Kontrol
Program kering L

4.1.5 Kontrol Pompa Saluran


 Operasi Pendinginan, Operasi Kering

& (: Operasi kering & pendinginan


Termostat ON
Pompa saluran OFF Pompa saluran ON

Tidak termasuk
yang disebutkan di
atas (1)

1. Ketika mengubah dari ON ke OFF, operasi residual dilakukan selama 5 menit.

4.1.6 Fungsi Pencegahan Pembekuan


Tujuan
Untuk menghindari pembentukan es pada penukar panas unit indoor dalam mode pendinginan dan
kering, sistem otomatis memulai siklus pencegahan pembekuan ketika sejumlah kondisi tertentu terpenuhi.

Kondisi awal pencegahan pembekuan


Awal pencegahan pembekuan ditetapkan oleh unit indoor (pengaturan pabrik):
• Penukar panas Indoor  –1°C selama 40 menit diakumulasikan
atau • Penukar panas Indoor < –3°C selama 1 menit terus menerus
& • Kompresor berjalan selama minimal 8 menit sejak
awal atau akhir operasi siklus pembekuan
sebelumnya.

Kondisi penghentian pencegahan pembekuan

Penghentian pencegahan pembekuan ditetapkan oleh unit indoor (pengaturan pabrik):


 Penukar panas Indoor > 7°C selama 10 menit terus-menerus

Fungsi dan Kontrol 34


SiMT281515E Rincian Fungsi

4.1.7 Memulai Ulang Otomatis


Tujuan
Tujuan fungsi memulai ulang otomatis adalah secara otomatis melanjutkan mode operasi yang sama
seperti ketika unit beroperasi saat catu daya dipulihkan setelah kegagalan daya.

Jangan gunakan fungsi "Automatic Restart" setiap hari untuk memulai/menghentikan unit.

Kehati-hatian saat mematikan daya


 Ketika anda harus mematikan catu daya untuk melakukan pemeliharaan, pertama-tama pastikan
untuk mematikan saklar ON/OFF remote kontrol.
 Jika anda mematikan catu daya selama saklar ON/OFF remote kontrol masih menyala, "fungsi
memulai ulang otomatis (automatic restart function)" otomatis memulai kipas unit indoor segera dan
kipas unit outdoor memulai otomatis 3 menit setelah catu daya dihidupkan ulang.
 Jangan memulai / menghentikan unit dengan mencabut catu daya. Hentikan unit dengan perintah
berhenti dari remote kontrol atau kontrol opsional sebelum melepaskan catu daya. Pastikan bahwa
kompresor dan kipas unit outdoor berhenti sebelum mencabut catu daya sehingga "Refrigerant
Recovery function" telah selesai dengan benar.
 Ketika memulai ulang unit setelah daya terputus untuk jangka waktu lama, biarkan unit mati dengan catu
daya terhubung selama sekitar setengah jam.

35 Fungsi dan Kontrol


Rincian Fungsi SiMT281515E

4.2 Unit Outdoor


4.2.1 Memulai ulang Siaga
Untuk mencegah kompresor dari sering ON / OFF dan menyamakan tekanan saluran refrigeran, lakukan
penonaktifan termostat paksa selama 3 menit setelah kompresor berhenti. Selain itu, kipas unit outdoor
melakukan operasi residual selama jangka waktu tertentu untuk mempercepat pemerataan dan mencegah
refrigeran masuk di evaporator.
Termostat OFF Memulai ulang siaga selesai (Restart standby)
ON
Kompresor OFF 


katup ekspansi elektronik  Berpindah ke “Stop” atau “Startup control”
OFF  setelah penyelesaian “Restart standby”.

Kipas unit Outdoor 
ON 

Operasi
OFF

 residual

 For 3 min.

4.2.2 Kontrol startup


Ketika kompresor memulai, frekuensi awal tetap selama jangka waktu tertentu pada frekuensi rendah untuk
mencegah kembalinya refrigeran.
Awal Penyamaan Kontrol
penyamaan tekanan Startup
tekanan selesai selesai

Kontrol penyamaan
tekanan sebelum
kompresor mulai kontrol Startup

107 Hz
Kompresor

480 pulsa
15 sec.

katup ekspansi 65 pulsa


elektronik

8 Step ON (Ta
pendinginan  40˚C)

Kipas unit Outdoor


OFF(Ta pendinginan
> 40˚C)

Atur kecepatan kipas


L
(pen dingina n)

kipas unit Indoor


(Termostat OFF)
OFF
(Remote kontrol OFF)
10~120 dtk.

Fungsi dan Kontrol 36


SiMT281515E Rincian Fungsi

4.2.3 Kontrol Frekuensi Awal


Kompresor inverter akan memulai dengan nilai frekuensi tetap terbatas selama jangka waktu tertentu untuk
mencegah cairan kembali ke kompresor, dan membatasi arus awal.

Umum
Waktu kontrol startup normal adalah 2 ~ 3 menit. Waktu kontrol frekuensi awal dibatasi 10 menit.

Selama startup kompresor, perbedaan tekanan akan diperbesar dalam rangka untuk memiliki perbedaan
tekanan yang cukup untuk katup empat-cara beralih.

Grafik

Hz
Kontrol Normal
107 Hz

Step 1

ON 1 2~3 Waktu (menit)

Kondisi akhir
Kontrol startup akan dihentikan ketika waktu awal maksimal 10 menit telah tercapai.

4.2.4 Kontrol Langkah Kompresor


Setelah fungsi "kontrol frekuensi awal" telah dihentikan, frekuensi kompresor yang ideal akan ditentukan
oleh " Kontrol langkah kompresor ".

Umum
Frekuensi operasi kompresor dikendalikan untuk menjaga suhu penguapan konstan dalam pendinginan.

Frekuensi dapat berubah setiap 20 detik. Perubahan frekuensi maksimum = 2 langkah / perubahan. (= Maks
6 langkah / menit)

Selama situasi tidak normal (misalnya perlindungan arus inverter) perubahan per langkah juga = 2 langkah /
perubahan, tetapi interval 20 detik mungkin akan diturunkan, sehingga perubahan mungkin lebih cepat.

Catatan:
Ketika fungsi kontrol lainnya diaktifkan (misalnya kontrol suhu pipa pembuangan), fungsi tersebut dapat
mengubah frekuensi kompresor dengan menggunakan input lain selain yang biasanya digunakan oleh
fungsi " kontrol langkah kompresor".

37 Fungsi dan Kontrol


Rincian Fungsi SiMT281515E

Pendin No. Frekuensi operasi Kompresor


ginan Dalam pendinginan, frekuensi operasi target Langkah
yang akan ditentukan oleh t indoor dan suhu 3 41 Hz
penguapan. 4 44 Hz
5 48 Hz
t dingin = Suhu yang diatur remote kontrol – Suhu 6 52 Hz
udara hisap Indoor. 7 55 Hz
8 58 Hz
Tergantung pada beban pendinginan, suhu
penguapan target (Te) akan menjadi nilai antara 2°C 9 69 Hz
 Te  20°C. 10 72 Hz
11 78 Hz
Langkah frekuensi 12 84 Hz
Frekuensi operasi akan menjadi nilai yang dipilih dari 13 90 Hz
daftar dengan pengaturan frekuensi tetap yang 14 94 Hz
diprogram dalam memori unit: 15 98 Hz
16 102 Hz
17 107 Hz
18 112 Hz
19 117 Hz
20 123 Hz
21 131 Hz
22 139 Hz
23 147 Hz
24 155 Hz
25 164 Hz
26 174 Hz

4.2.5 Kontrol Kecepatan Kipas Unit Outdoor


Kecepatan kipas unit outdoor akan dikendalikan dalam fungsi suhu udara outdoor yang sebenarnya,
tekanan kondensasi, perbedaan tekanan antara tekanan rendah dan tinggi dan rasio kompresi.

Untuk lebih jelasnya silahkan lihat " Kontrol Perbedaan Tekanan ".

Tabel Langkah Kipas

Pendinginan
Langkah
M1F M2F
0 0 rpm 0 rpm
1 250 rpm 0 rpm
2 400 rpm 0 rpm
3 285 rpm 250 rpm
4 360 rpm 325 rpm
5 445 rpm 410 rpm
6 545 rpm 510 rpm
7 660 rpm 625 rpm
8 RZR100LUY1(4) 800 rpm 800 rpm
RZR125LUY1(4) 790 rpm 755 rpm
RZR140LUY1(4) 786 rpm 751 rpm

Catatan:
Lihat "Kontrol Perbedaan Tekanan" di halaman 41.

Fungsi dan Kontrol 38


SiMT281515E Rincian Fungsi

4.2.6 Kontrol Perlindungan Tekanan tinggi


Untuk mencegah tekanan tinggi yang tidak normal dalam sistem dan untuk alasan ini hindari perangkat
keselamatan tekanan tinggi, fungsi kontrol di bawah ini akan diaktifkan.

Diagram Alir

Operasi Normal

Hp > 3.19 MPa Hp  3.94 MPa


Frekuensi operasi kompresor Frekuensi operasi kompresor
–1 langkah/10 detik +1 langkah / 1 menit

Hp > 3.29 MPa Hp  3.04 MPa


Frekuensi operasi Frekuensi operasi kompresor
kompresor 123 Hz Hp < 3.14 MPa +1 langkah /5 menit

• HPS aktif
atau
• Hp > 3.19 MPa selama 1 menit

Kompresor berhenti
Berhenti 15 kali atau
kurang dalam 300 menit
atau
• HPS aktif
• Berhenti 16 kali dalam 300 menit

Penghentian yang tidak normal (Indikasi E3)

Karena tekanan batas hambatan bantalan menurun selama operasi lambat kompresor, batas bawah
frekuensi dibatasi.
[Dalam pendinginan]

Hp  3.04 MPa Batas bawah


Operasi Normal frekuensi kompresor
Hp < 2.84 MPa 48 Hz
Setelah 30 detik

39 Fungsi dan Kontrol


Rincian Fungsi SiMT281515E

4.2.7 Kontrol Suhu Pipa Pembuangan


Garis besar
Frekuensi operasi kompresor akan dikendalikan untuk menghindari suhu kompresor tinggi yang tidak
normal (lihat juga kontrol katup ekspansi elektronik).
Td: Suhu pipa pembuangan (°C)

Operasi Normal
• Td < 100 °C
atau • Frekuensi batas atas
Td > 105 °C • & = Frekuensi maksimum
• Td < 105 °C

Frekuensi batas atas kompresor Frekuensi batas atas kompresor


–1 langkah /20 detik +1 langkah/1 menit
• Td  110 °C
• & • Td < 100 °C
terus selama 5 menit
• 300 detik Td  105 °C atau
atau
• Td > 120 °C • & • Td  105 °C
• 5 menit berlalu
Frekuensi batas atas kompresor
58 Hz

• Td  115 °C terus
atau selama 10 menit
• Td  135 °C
berhenti 10 kali atau kurang dalam 200 menit
Kompresor berhenti
Berhenti 11 kali
dalam 200 menit

Penghentian tidak normal (indikasi F3)

[Kontrol derajat bukaan katup ekspansi elektronik]


Kontrol Normal

Td  95˚C Td  80˚C
Batas bawah derajat bukaan katup Td  90˚C Batas bawah derajat bukaan katup
ekspansi elektronik ekspansi elektronik
+5 pulsa / Pendinginan selama 2 menit -5 pulsa / Pendinginan selama 2 menit

Td  100˚C
Batas bawah derajat bukaan katup
ekspansi elektronik
+10 pulsa / Pendinginan selama 2 menit

Fungsi dan Kontrol 40


SiMT281515E Rincian Fungsi

4.2.8 Kontrol Perlindungan Arus Inverter


 Kontrol dengan Suhu Sirip Radiasi
Membatasi frekuensi batas atas operasi kompresor untuk mencegah kompresor dari tersandung (tripping)
karena suhu sirip radiasi.
Suhu sirip radiasi  86˚C
Operasi Normal Frekuensi kompresor
–1 langkah/6 detik
Frekuensi kompresor
Frekuensi batas atas Inverter +1 langkah/2 menit Suhu sirip radiasi  83˚C
= Frekuensi Maksimum berlangsung selama 2 menit
 Kontrol Perlindungan Arus Inverter
Membatasi frekuensi operasi kompresor untuk mencegah kompresor dari tersandung(tripping) karena arus
berlebih inverter.
Operasioperation
Normal normal
Arus Inverter Frekuensi batas atas inverter
> Arus turun = Frekuensi maksimum
Frekuensi kompresor
Compressor frequency Frekuensi kompresor
Compressor frequency
- 1 langkah / 6 detik
–1 step/6 seconds + 1+1
langkah
step/2/ 2minutes
menit

Kondisi arus Inverter < Arus turun terus selama


2 menit
 Untuk Semua Suhu penukar panas unit Outdoor
Model (cairan)  Suhu penukar panas unit
indoor
&
Suhu penukar panas unit
Outdoor (cairan)  25˚C
Arus turun Arus turun
13 A 11 A
Suhu penukar panas unit Outdoor
(cairan) Suhu penukar panas unit
indoor
atau
Suhu penukar panas unit
Outdoor (cairan)  25˚C

4.2.9 Kontrol Perbedaan Tekanan


Untuk memastikan rasio kompresi (perbedaan tekanan antara tekanan tinggi dan rendah) pada kondisi suhu
udara outdoor rendah dalam mode pendinginan, kipas unit outdoor dan frekuensi kompresor target
mungkin bervariasi.
Ta: Suhu udara Outdoor
Tfin: Suhu sirip radiasi
Hp - Lp > 1.08MPa
Hp - Lp < 0.93MPa atau
atau Hp < 2.94MPa
Rasio kompresi < 2.1 Operasi Normal atau Rasio kompresi > 2.4
&
Hp < 1.86MPa Ta > 27˚C
Ta < 25˚C Kipas unit Outdoor
Pembatasan frekuensi operasi +1 langkah/90 detik
kompresor (lihat berikut)
Hp - Lp > 0.98MPa
&
Hp - Lp < 0.78MPa atau Rasio kompresi > 2.2
& atau
Rasio kompresi  1.8 Hp > 2.25MPa
Hp < 1.57MPa Kipas unit Outdoor Kipas unit Outdoor
-1 langkah/90 detik Langkah 1
Hp - Lp > 0.88MPa
Hp - Lp < 0.78MPa &
OR
Rasio kompresi > 2.0
Rasio kompresi < 1.8 & atau
Hp < 1.57MPa Hp > 1.66MPa
Tfin < 66˚C Tfin  81˚C

Kipas unit Outdoor: Berhenti

Pembatasan frekuensi operasi kompresor

RZR100LUY1 (4) RZR125-140LUY1 (4)


Suhu udara Outdoor < 20˚C
Frekuensi
Pembatasan batas atas 112 Hz 139 Hz
frekuensi
Suhu udara Outdoor  21˚C Frekuensi
batas bawah 72 Hz

41 Fungsi dan Kontrol


Rincian Fungsi SiMT281515E

4.2.10 Kontrol Perlindungan Arus Keseluruhan


Memonitor arus keseluruhan dan membatasi frekuensi operasi kompresor batas atas untuk mencegah
pemutus sirkuit dari melebihi kapasitas ternilai.
Operasi Normal Arus unit Outdoor  Nilai arus
batas atas
& frekuensi operasi kompresor batas
Arus unit Outdoor
> Nilai arus batas atas Arus unit Outdoor  Nilai arus batas atas = frekuensi maksimum
atas
Frekuensi operasi kompresor batas atas Frekuensi operasi kompresor batas atas
+1 langkah /2 menit
–1 langkah /6 detik Arus unit Outdoor > Nilai
arus batas atas

Arus batas atas (A)


Ambil nilai-nilai berikut tergantung pada suhu udara outdoor.
Juga bervariasi tergantung pada model.
Arus
keseluruhan (A)

13.5
10.0
8.5

3.0

25 28 43 50 Suhu udara outdoor (˚C)

4.2.11 Operasi Pump Down


Setiap kali unit perlu dipindahkan atau dilepas, lakukan operasi pump down sebelum melepaskan pemipaan
bidang. Dengan melakukan operasi pump down, semua refrigeran akan terkumpul di unit outdoor.

Prosedur Kehati-hatian
1 Memulai " operasi kipas saja" dari remote Pastikan bahwa kedua katup penghenti gas dan
kontrol. cairan terbuka.
2 Tekan tombol (BS4) bawah pompa pada PCB Kompresor dan kipas unit outdoor akan
unit outdoor. mulai secara otomatis.
3 Setelah operasi berhenti (setelah 3 ~ 5 menit)
tutup katup penghenti cairan terlebih dahulu dan
kemudian katup penghenti gas.
4 Setelah " Operasi pump down " telah selesai , Pastikan katup penghenti terbuka sebelum
layar remote kontrol berkabel mungkin kosong menyalakan kembali unit.
atau menunjukkan indikasi kesalahan "U4". Ini
tidak akan dapat memulai unit dari remote
kontrol tanpa mematikan catu daya terlebih
dahulu.

Perhatian
 Menekan tombol (BS4) pump down pada PCB unit outdoor dapat menyebabkan kipas unit outdoor dan
indoor untuk mulai beroperasi secara otomatis.
 Pastikan untuk membuka katup penghenti setelah pekerjaan pipa telah selesai. Pastikan untuk tidak
mengoperasikan unit dengan katup penghenti tertutup, atau kompresor dapat pecah.

Fungsi dan Kontrol 42


SiMT281515E Rincian Fungsi

4.2.12 Operasi Pemulihan Minyak


Ketika kompresor beroperasi untuk jangka waktu tertentu pada frekuensi rendah, tingkat minyak di kompresor
dapat menjadi rendah karena kembalinya minyak tidak selesai. Untuk mencegah kerusakan kompresor dan
dalam kasus terburuk hindari kunci kompresor, operasi pemulihan minyak akan dilakukan.

Rincian
Selama operasi pemulihan minyak, frekuensi operasi kompresor akan ditingkatkan selama jangka waktu 5
menit. Operasi pemulihan minyak hanya dijalankan dalam mode pendinginan.

4.2.13 Fungsi Operasi Tiruan


Dalam kasus kesalahan termistor, operasi tiruan dilakukan dalam dua cara yang berbeda seperti
yang ditunjukkan di bawah ini bahkan ketika kesalahan terdeteksi.
A. Operasi terus berlanjut selama kode kesalahan ditampilkan pada remote kontrol.
Termistor yang dapat digunakan
· Termistor udara Outdoor
· Termistor udara hisap
· Termistor penukar panas Indoor
B. Operasi terus berlanjut bahkan ketika kesalahan terdeteksi. Tampilan remote kontrol "Inspeksi / Test
Run". Hanya jika tombol ditekan, kode kesalahan muncul.
Termistor yang dapat digunakan
· Termistor remote kontrol
· Termistor sirip radiasi

Catatan:
Dalam kasus kesalahan termistor selain A dan B di atas, penghentian kesalahan dilakukan dan tidak
ada operasi tiruan yang dilakukan.
Termistor yang dapat digunakan
· Termistor pipa hisap
· Termistor pipa pembuangan
· Termistor penukar panas sedang

4.2.14 Kontrol Operasi Uji coba


Tujuan
Saat mengoperasikan unit untuk pertama kalinya setelah instalasi, unit akan - tergantung pada mode operasi
yang dipilih – lakukan operasi uji coba terlebih dahulu.

Situasi 1
Pendinginan – Operasi pertama setelah instalasi dalam "mode pendinginan"
Termostat pendinginan Operasi pendinginan dalam Operasi pendinginan
aktif "mode operasi uji coba" Normal
selama 3 menit

Situasi 2
Pendinginan - Operasi pertama setelah instalasi dalam "mode operasi uji coba"
Operasi pendinginan Operasi pendinginan Operasi pendinginan
dengan tombol operasi uji dalam "mode operasi uji dalam termostat dipaksa
coba coba" selama 3 menit aktif.

Catatan:
 Ketika berjalan dalam mode operasi uji coba, unit akan merasakan parameter instalasi di tempat (misalnya:
kegagalan untuk membuka katup penghenti, ..) dan menunjukkan kode kesalahan yang berlaku jika
diperlukan.
 Jika remote kontrol menunjukkan "E3", "E4" atau "L8" sebagai kode kesalahan, ada
kemungkinan bahwa baik katup penghenti tertutup atau outlet aliran udara terhambat.
 Periksa sambungan kabel cabang unit tengah (kabel 1-2-3) jika kode kesalahan “U4” atau “UF”
ditampilkan pada remote kontrol.
 Jika kode kesalahan “U2” ditampilkan pada remote kontrol, periksa ketidakseimbangan tegangan.
 Jika kode kesalahan “L4” ditampilkan pada remote kontrol, ada kemungkinan bahwa bagian aliran
udara tertutup.
 Bila tidak ada tampilan kode kesalahan, operasi pendinginan terus berlanjut tanpa gangguan. (Namun,
kontrol ini sekali lagi dilakukan setelah refrigeran dipulihkan dengan menggunakan saklar pump down
dan pada saat operasi pertama setelah penggantian PCB unit outdoor.)

43 Fungsi dan Kontrol


SiMT281515E

Bagian 5
Operasi Uji Coba dan
Pengaturan Bidang
1. Operasi Uji Coba ...................................................................................... 45
1.1 Periksa sebelum Operasi Uji Coba .......................................................45
1.2 Pemeriksaan Operasi Uji Coba.............................................................45
2. Pengaturan bidang dari Remote Kontrol ................................................ 46
2.1 Remote kontrol berkabel ......................................................................46
2.2 Remote Kontrol Nirkabel ......................................................................49
2.3 No. Kode dan Isi Pengaturan untuk Unit Indoor ....................................50
2.4 No. Kode dan Isi Pengaturan untuk Unit Outdoor ..................................51
3. Pengaturan bidang dari Adaptor Demand ............................................. 53
3.1 Fungsi i-Demand..................................................................................53
4. Pengaturan bidang dari PCB Unit Outdoor ........................................... 54
4.1 Pengaturan dengan Tombol BS............................................................54
4.2 Mode 1 Pengaturan..............................................................................54
4.3 Mode 2 Pengaturan..............................................................................55
4.4 Mode Monitor.......................................................................................57
4.5 Daftar Isi coba lagi dan Kesalahan .......................................................58
5. Operasi Darurat........................................................................................ 60

Operasi Uji Coba dan Pengaturan Bidang 44


Operasi Uji Coba SiMT281515E

1. Operasi Uji Coba


1.1 Periksa sebelum Operasi Uji Coba
Sebelum melakukan operasi uji coba, lakukan sebagai berikut:
Langkah Tindakan
1 Pastikan tegangan pada sisi primer dari pemutus keselamatan adalah:
 (380 ~ 415 V) ± 10% untuk unit 3-fasa
2 Sepenuhnya buka katup penghenti cairan dan gas.

1.2 Pemeriksaan Operasi Uji Coba


Untuk melakukan operasi uji coba, lakukan sebagai berikut:
 Pastikan pengaturan suhu remote kontrol berada pada tingkat terendah dalam mode pendinginan
atau gunakan mode uji coba.
 Periksa daftar periksa berikut:
pos pemeriksaan Perhatian atau peringatan
Apakah semua unit terpasang?  Berbahaya untuk mengoperasikan selama badai
 Kemungkinan kerusakan untuk sambungan pipa
Apakah kabel arde dipasang sesuai dengan standar lokal Berbahaya jika terjadi kebocoran listrik
yang berlaku?
Apakah semua inlet dan outlet udara dari unit indoor dan  Pendinginan Buruk
outdoor terhalang?
Apakah saluran mengalir dengan lancar? Kebocoran air
Apakah pemipaan cukup terisolasi panas? Kebocoran air
Apakah sambungan sudah diperiksa untuk kebocoran  Pendinginan Buruk
gas?  Penghentian
Apakah tegangan catu daya sesuai dengan spesifikasi Operasi tidak benar
pada pelat nama?
Apakah ukuran kabel seperti yang ditentukan dan sesuai Kerusakan kabel
dengan peraturan lokal?
Apakah sinyal remote kontrol diterima oleh unit? Tidak ada operasi

45 Operasi Uji Coba dan Pengaturan Bidang


Pengaturan bidang dari Remote Kontrol SiMT281515E

2. Pengaturan Bidang dari Remote Kontrol


Fungsi individual unit indoor dapat diubah dari remote kontrol. Pada saat instalasi atau setelah pemeriksaan/
perbaikan servis, lakukan pengaturan bidang sesuai dengan uraian berikut.
Pengaturan tidak benar dapat menyebabkan kesalahan.
(Ketika aksesori opsional dipasang pada unit indoor, pengaturan untuk unit indoor mungkin diperlukan untuk
mengubahnya. Lihat informasi di buku pegangan pilihan.)

2.1 Remote kontrol berkabel


2.1.1 BRC1C61/BRC1D61

NO. UNIT NO. MODE


NO. KODE MODE
KEDUA PENGATUR
AN BIDANG
NO. KODE
PERTAMA 3 4

1 7
6 5 2

1. Ketika dalam mode normal, tekan tombol “ ” selama 4 detik atau lebih, dan FIELD SETTING MODE
TEST

dimasukkan.
2. Pilih MODE NO. yang diinginkan dengan tombol (2) “ ”.
3. Selama kontrol grup, saat pengaturan oleh setiap unit indoor (No. mode 20, 22 dan 23 telah dipilih),
tekan tombol (3) “ ” dan pilih INDOOR UNIT NO untuk diatur. (Operasi ini tidak perlu bila
pengaturan oleh grup.)
4. Tekan tombol atas (4) “ ” dan pilih FIRST CODE NO.
5. Tekan tombol bawah (5) “ ” dan pilih SECOND CODE NO.
6. Tekan tombol (6) “ ”sekali dan pengaturan sekarang adalah SET.
7. Tekan tombol (7) “ ” untuk kembali ke NORMAL MODE.

(Contoh)
Jika selama pengaturan grup dan waktu untuk membersihkan filter udara diatur ke FILTER
CONTAMINATION, HEAVY, SET MODE NO. menjadi “10” FIRST CODE NO. menjadi “0”, dan SECOND
CODE NO. menjadi “02”.

Operasi Uji Coba dan Pengaturan Bidang 46


SiMT281515E Pengaturan bidang dari Remote Kontrol

2.1.2 BRC1E62
<Layar dasar>

(1) 1 Tekan tombol Cancel selama 4 detik


atau lebih.
Menu Field setting ditampilkan.

2 Pilih Field setting list di menu field


setting, dan tekan tombol Menu/Enter.
layar Field setting list ditampilkan.

3 Sorot mode, dan pilih “Mode No.” yang


diinginkan dengan menggunakan tombol
(Up/Down).

4 Dalam hal pengaturan per unit indoor


<Layar menu Field setting > selama kontrol grup (Ketika Mode No.
(2) seperti 20 , 21 , 22 , 23 , 25 dipilih),
sorot unit No. dan pilih “Indoor unit
No.” untuk diatur dengan
menggunakan tombol
(Up/Down). (dalam hal pengaturan
total grup , operasi ini tidak
diperlukan.)
dalam hal pengaturan individu per
unit indoor, pengaturan saat ini
ditampilkan. Dan, Second Code
No. “ - ” berarti tidak ada fungsi.
Tekan tombol Menu/Enter
5 Sorot Second Code No. dari First Code
No. untuk diubah, dan pilih “Second
<Layar Field setting >
Code No.” yang diinginkan dengan
menggunakan tombol
Dalam hal pengaturan Dalam hal pengaturan (Up/Down). Beberapa pengaturan
individu per unit total grup nomor mode yang identik tersedia.
indoor
(3) Dalam hal pengaturan total grup,
(3) (5) semua Second Code No. yang
(4) dapat diatur ditampilkan seperti “  ”.
“  ” diubah ke Second Code
(5)
No. untuk diatur. Dan, Second
Code No. “ - ” berarti tidak ada
fungsi.
Second Code No.

First Code No.

Tekan Tombol Menu/Enter

47 Operasi Uji Coba dan Pengaturan Bidang


Pengaturan bidang dari Remote Kontrol SiMT281515E

6 Tekan tombol Menu/Enter. Layar


< layar konfirmasi pengaturan> konfirmasi pengaturan
(6) ditampilkan.
(7) 7 Pilih Yes dan tekan tombol
Menu/Enter. Rincian pengaturan
ditentukan dan kembali ke layar
daftar pengaturan bidang.

8 Dalam hal beberapa perubahan


pengaturan, ulangi “(3)” sampai “(7)”.

9 Setelah semua perubahan pengaturan


selesai, tekan tombol Cancel dua kali.

10 Lampu latar keluar, dan “Connection


Tekan tombol Menu/Enter.
under check Please wait for a
moment” ditampilkan untuk inisialisasi.
Setelah inisialisasi, kembali ke layar
Konfirmasi pengaturan dasar.

PERHATIAN
• Ketika aksesori opsional dipasang pada unit indoor, pengaturan unit indoor
dapat diubah. Lihat panduan tentang aksesori opsional.
• Untuk rincian pengaturan bidang unit outdoor, lihat panduan instalasi yang
terlampir pada unit outdoor.

Operasi Uji Coba dan Pengaturan Bidang 48


SiMT281515E Pengaturan bidang dari Remote Kontrol

2.2 Remote Kontrol Nirkabel

Tombol UP
No. Mode
mode pengaturan Tombol DOWN
bidang

Tombol RESERVE
No. kode pertama

Tombol MODE
No. kode kedua

Tombol INSPECTION/TEST

Pengatu
ran Untuk mengatur pengaturan bidang, anda harus mengubah:
 Mode No. (Nomor mode)
 First code No. (Nomor kode pertama)
 Second code No. (Nomor kode kedua)

Untuk mengubah pengaturan bidang, lakukan sebagai berikut:


Langkah Tindakan
1 Tahan tombol INSPECTION/TEST selama setidaknya 4 dt selama mode normal untuk masuk ke
“Field setting mode”.
2 Tekan tombol MODE untuk memilih “Mode No.” yang diinginkan.
3 Tekan tombol UP untuk memilih “First code No.”.
4 Tekan tombol DOWN untuk memilih “Second code No.”.
5 Tekan tombol RESERVE untuk mengatur pengaturan saat ini.
6 Tekan tombol INSPECTION/TEST untuk kembali ke “Normal mode”.

49 Operasi Uji Coba dan Pengaturan Bidang


Pengaturan bidang dari Remote Kontrol SiMT281515E

2.3 No. Kode dan Isi Pengaturan untuk Unit Indoor


Pengaturan bidang
Tabel di bawah ini berisi kemungkinan pengaturan bidang semua unit indoor. : Pengaturan pabrik

No. No. kode No. Kode kedua


Keterangan pengaturan
Mode Pertama 01 02 03 04
10 (20) 0 Kontaminasi filter berat / Filter Ringan Kira-kira Berat Kira-kira — —
ringan (Pengaturan sangat 10,000 5,000
untuk waktu tampilan tahan lama jam. jam.
untuk membersihkan
filter udara) (Atur waktu Filter Kira-kira Kira-kira
tampilan untuk tahan 2,500 1,250
membersihkan filter lama jam. jam.
udara sampai separuh
ketika ada kontaminasi Filter Kira-kira Kira-kira
filter berat.) standar 200 jam. 100 jam.

1 Tipe filter tahan lama Filter tahan Filter sangat — —


lama tahan lama
2 Remote termistor dari TH1 = remote TH1 = Udara — —
remote kontrol kontrol hisap
3 Tampilan filter Tampilan Tidak ada tampilan — —
11 (21) 0 Sistem operasi serentak Sepasang Kembar Rangkap tiga Kembar
ganda
1 Pengaturan Individu /terpadu Terpadu Individual — —
2 Keadaan kipas pada saat termostat Normal OFF — —
Mati
4 Kontrol mode operasi Tersedia Larangan — —
otomatis
7 penyesuaian aliran udara OFF Penyelesaian Awal —
penyesuaian penyesuaian
aliran udara aliran udarat
12 (22) 1 Pengaturan remote kontrol Penghentian Kontrol — —
paksa Start-stop
5 Restart otomatis Dinonaktifkan Diaktifkan — —
6 Termostat pendinginan Kecepatan LL Kecepatan — —
kecepatan kipas mati yang diatur
13 (23) 6 Tekanan statis eksternal Lihat tabel. (1)
15 (25) 1 Termostat kelebihan tidak dilengkapi — —
kelembaban mati dilengkapi
3 Pilihan interlock alat pelembab tidak dilengkapi — —
pompa saluran dilengkapi
5 Pilihan pengaturan bidang untuk tidak dilengkapi — —
pengaturan ventilasi individual dilengkapi
dengan remote kontrol

Catatan: 1.
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
- - - - 50 Pa 60 Pa 70 Pa 80 Pa 90 Pa 100 Pa 110 Pa 120 Pa 130 Pa 140 Pa 150 Pa

Operasi Uji Coba dan Pengaturan Bidang 50


SiMT281515E Pengaturan bidang dari Remote Kontrol

2.4 No. Kode dan Isi Pengaturan untuk Unit Outdoor


Tabel di bawah ini berisi pengaturan remote kontrol.
: pengaturan pabrik

No. No. Keterangan No. Kode Kedua


Mode Kode Pengaturan
Pertama 01 02 03 04 05 06
16 0 Operasi kebisingan Dinonakti Operasi prioritas kebisingan — —
(26) malam rendah fkan kebisinga kapasitas malam rendah
n malam + prioritas
rendah kapasitas

1 Waktu start dan stop — — 22h00 ~ 22h00 ~ 20h00 ~ —


Operasi kebisingan 06h00 08h00 08h00
malam rendah otomatis

2.4.1 Operasi kebisingan malam rendah


Tujuan
Menurunkan suara pengoperasian unit outdoor.

Pengat
uran Operasi kebisingan malam rendah dapat diaktifkan dengan:
1. Kontrol otomatis (Dengan pengaturan bidang remote kontrol)
2. Aktivasi eksternal (dari PCB KRP58M opsional)

 Operasi kebisingan malam rendah dengan Kontrol Otomatis


Operasi kebisingan malam rendah dapat diatur dengan pengaturan bidang dari
remote kontrol berkabel: : Pengaturan
pabrik

No. No. Keterangan No. Kode Kedua


Mode Kode Pengaturan
Pertama 01 02 03 04 05 06

16(26) 0 Operasi kebisingan nonaktif Operasi Prioritas Operasi


— —
kebisingan
malam rendah kebisinga kapasita
malam
n malam s
rendah +
rendah
prioritas
kapasitas

1 Waktu start dan stop — — 22h00 ~ 22h00 ~ 20h00 ~ —


Operasi kebisingan 06h00 08h00 08h00
malam rendah otomatis

Metode Penentuan waktu Start dan Stop


Ketika mode pengaturan 16(26)-0-02, Operasi kebisingan malam rendah akan dilakukan dengan
menganggap waktu saat ini sesuai dengan suhu udara outdoor.
Mode otomatis akan dimulai ketika suhu udara outdoor adalah = rata-rata maks 10 hari terakhir -5 ° C dan
akan dilakukan selama 10 jam.
Suhu udara outdoor maksimum seharusnya terjadi pada saat 14: 00 h.
Karena keputusan waktu dibuat sesuai dengan suhu udara outdoor, penentuan waktu yang disebutkan di
atas adalah perkiraan saja.

51 Operasi Uji Coba dan Pengaturan Bidang


Pengaturan bidang dari Remote Kontrol SiMT281515E

Grafik

Awal operasi Akhir operasi


Suhu udara kebisingan kebisingan
outdoor +8 jam malam rendah +10 jam malam rendah
maksimum

Garis tren menunjukkan fluktuasi


suhu udara outdoor dalam 24 jam

Pengaturan Prioritas Kapasitas


Ketika mode pengaturan 16(26)-0-04, operasi kebisingan malam rendah akan dihentikan ketika beban
pendinginan meningkat. Dalam hal ini, operasi akan kembali ke operasi normal. Unit akan kembali ke
operasi kebisingan malam rendah ketika beban pendinginan menurun lagi.

 Aktivasi eksternal dari PCB Opsional


Grafik
Operasi kebisingan malam rendah juga dapat diaktifkan dari PCB (KRP58M51) opsional.

Konektor transmisi (pada


DS 1
PCB X6A unit outdoor)
Konektor catu daya (pada ON

PCB X77A unit outdoor) OFF


1 2 34
X80A
X81A

X800M

X801M

3 2 1 LNO P CO M

Output pada X801M = 12VDC, 12mA


Panjang kabel maksimum = 100 meter
X801M

3 2 1 LNOP COM

Operasi kebisingan malam rendah akan dimulai ketika kontak pada LNOP-COM ditutup dan akan tetap aktif
selama kontak ditutup. Tidak ada pengaturan bidang pada unit outdoor atau dengan remote kontrol
diperlukan.
Operasi kebisingan malam rendah akan berakhir saat kontak dibuka kembali.
Penggunaan KRP58M51 memungkinkan penggunaan jam waktu eksternal.

Pengecualian
Operasi kebisingan malam rendah akan dibatalkan dalam kondisi berikut:
 Operasi residual pump down
 Kontrol Startup
 Pemulihan Minyak

Operasi Uji Coba dan Pengaturan Bidang 52


SiMT281515E Field Setting from Outdoor Unit PCB

3. Pengaturan bidang dari Adaptor Demand


3.1 Fungsi i-Demand
Tujuan
Menetapkan pembatasan terhadap konsumsi daya dari sistem. (Misalnya: kontrol persediaan,
batas konsumsi daya selama momen puncak,..)

Pengat
uran 3 pengaturan demand yang berbeda dapat dipilih dengan menggunakan terminal X801M:
 Demand 1  Menutup kontak antara COM dan kontak 1
 Demand 2  Menutup kontak antara COM dan kontak 2
 Demand 3  Menutup kontak antara COM dan kontak 3
Konektor transmisi
DS1 (pada PCB X6A unit outdoor)
Konektor Catu Daya (pada ON
OFF
PCB X77A unit outdoor) 1 2 34

X80A
X81 A

X800M

X801M
Output pada X801M = 12VDC, 12mA
3 2 1 LNOP COM Panjang kabel maksimum = 100 meter

X801M

3 2 1 LNOP COM

Demand 1
Pembatasan konsumsi daya dalam fungsi pengaturan pada DS1:

PENGATURAN DS1
Konsumsi Daya
1 2 Maksimum

OFF OFF 60%

ON OFF 70%

OFF ON 80%

ON ON 100%

Demand 2
Pembatasan konsumsi daya yang diatur menjadi 40%.

Demand 3
Termostat paksa Mati.

53 Operasi Uji Coba dan Pengaturan Bidang


Field Setting from Demand Adaptor SiMT281515E

4. Pengaturan Bidang dari PCB Unit Outdoor


4.1 Pengaturan dengan Tombol BS
Dengan "Setting mode 1," "Setting mode 2" dan "Monitor mode," berbagai pengaturan dan data dapat
diperiksa.
(1) Setting mode 1
Status awal (operasi normal) adalah "Setting mode 1." Mode ini menunjukkan status operasi -
"TEST(operasi uji coba)," "HWL (kesalahan)," "L.N.O.P(operasi kebisingan malam rendah)" atau
"DEMAND(operasi demand)."
(2) Setting mode 2
Setiap status operasi dapat dimodifikasi.
(3) Monitor mode
Mode ini menunjukkan "oil return operation," "outdoor unit class," "contents of retry," "contents of
error," "causes of drooping operation," dll.
dengan menggunakan tombol MODE, mode dapat diubah sebagai berikut.
Tekan dan tahan
MODE (BS1) selama 5 detik (Normal) Tekan MODE (BS1) sekali
Setting mode 2 Setting mode 1 Monitor mode
MODE Tekan MODE MODE MODE
(BS1) sekali.
ON OFF berkedip
H1P H1P H1P

4.2 Mode 1 Pengaturan


Dengan menggunakan mode ini, kondisi berikut dapat diperiksa:
• Kondisi operasi saat ini (operasi normal/uji coba /inspeksi jalur dan normal/ ada kesalahan)
• Kondisi operasi kebisingan rendah (Tingkat kebisingan normal/rendah 1, 2 dan 3)
• Kondisi operasi Demand (normal/Tingkat demand 1, 2 dan 3)
Kondisi di atas ini dapat diperiksa dengan melakukan langkah-langkah berikut:

Prosedur untuk memeriksa item periksa


Sistem secara normal diatur ke MODE TEST HWL L.N.O.P DEMAND : ON : OFF : BERKEDIP
"Setting mode 1". H1P H2P H3P H4P H5P H6P H7P
Sebaiknya sistem diatur ke mode
lain selain itu, Tekan MODE
(BS1) untuk mengatur sistem ke Selama "Setting mode 1," lampu
"Setting mode 1".
selalu mati.
Tampilan operasi uji coba
Dalam operasi normal
Periksa sistem untuk setiap kondisi Dalam Operasi uji coba
melalui tampilan LED. (Lihat informasi
Dalam operasi pemeriksaan saluran
dalam tabel di sebelah kanan.)
Tampilan Kesalahan
Normal
Ada Kesalahan
Tampilan operasi kebisingan rendah
Operasi Normal
Pengaturan tingkat kebisingan
rendah
Tampilan tingkat Demand
operasi Normal
Tingkat 1 Demand
Tingkat 2 Demand
Tingkat 3 Demand

Operasi Uji Coba dan Pengaturan Bidang 54


SiMT281515E Pengaturan bidang dari PCB Unit Outdoor

4.3 Mode 2 Pengaturan


Dalam mode ini, pengaturan untuk item berikut bisa dilakukan dengan menggunakan tombol BS.

Tekan dan tahan MODE (BS1) selama


5 detik dan atur ke “Setting mode 2”. < Pemilihan kondisi pengaturan
>
Tekan SET (BS2) dan atur ke kondisi
pengaturan yang anda inginkan.

Tekan RETURN (BS3) dan tentukan
<Pilihan item pengaturan> kondisinya.
Tekan SET (BS2) dan atur tampilan
LED ke item pengaturan yang
ditunjukkan dalam tabel di bawah ini.

Tekan RETURN (BS3) dan tentukan Tekan RETURN (BS3) dan atur ke
item. (kondisi pengaturan saat ini status awal dari “Setting mode 2”.
berkedip.)
 Jika Anda menjadi tidak yakin bagaimana
untuk melanjutkan, tekan MODE (BS1) dan
kembali ke mode 1 pengaturan.

Tampilan item pengaturan Tampilan kondisi pengaturan


No. Tampilan LED Tampilan LED
Item pengaturan Kondisi pengaturan
H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
k h h h h k k 30% demand k h h h k h h
Operasi
3 Demand 2 40% demand k h h h h k h
(pengaturan pabrik)
50% demand k h h h h h k
k h k k k h h OFF (pengaturan pabrik) k h h h h h k
28 Mode pemulihan
refrigeran ON k h h h h k h
Jumlah dalam kolom “No.” merupakan jumlah waktu untuk menekan SET (BS2).

Pengaturan Operasi Demand 2


Dengan pengaturan ini, operasi kompresor dapat dikendalikan untuk mengurangi konsumsi daya.
(60% - 80% demand tersedia jika adaptor demand (aksesori opsional) digunakan.)
Item pengaturan Kondisi pengaturan Deskripsi
30% demand Beroperasi dengan 30% dari konsumsi daya ternilai.
Operasi Demand 2 40% demand (pengaturan pabrik) Beroperasi dengan 40% dari konsumsi daya ternilai.
50% demand Beroperasi dengan 50% dari konsumsi daya ternilai.

[prosedur kerja] h : NONAKTIF l: BERKEDIP k : AKTIF


Prosedur operasi H1P H2P H3P H4P H5P H6P H7P
Tekan dan tahan MODE (BS1) dari "Setting mode 1" selama 5 detik atau lebih k h h h h h h
dan atur ke "Setting mode 2."
Tekan SET (BS2) 3 kali untuk mengatur tampilan LED seperti yang ditunjukkan
k h h h h k k
dalam tabel sisi kanan.
Tekan RETURN (BS3) sekali. (pengaturan kini ditampilkan) k h h h h l h
30% dari konsumsi daya ternilai k h h h l h h
Tekan SET (BS2) untuk mengatur tampilan k h h h h l h
40% dari konsumsi daya ternilai
LED seperti yang ditunjukkan dalam tabel sisi
kanan. 50% dari konsumsi daya ternilai k h h h h h l
30% dari konsumsi daya ternilai k h h h k h h
Tekan RETURN (BS3) sekali untuk k h h h h k h
40% dari konsumsi daya ternilai
membuat keputusan.
50% dari konsumsi daya ternilai k h h h h h k
Tekan RETURN (BS3) sekali lagi untuk eksekusi. (Tampilan LED dalam status k h h h h h h
awal dari "Setting mode 2".)
Tekan MODE (BS1) sekali untuk kembali ke Setting mode 1 (operasi normal). h h h h h h h

55 Operasi Uji Coba dan Pengaturan Bidang


Pengaturan bidang dari PCB Unit Outdoor SiMT281515E

Pengaturan Mode pemulihan Refrigeran


Ketika unit pemulihan refrigeran terhubung pada tempat untuk memulihkan refrigeran, sepenuhnya buka katup
ekspansi elektronik dari unit outdoor untuk membantu pemulihan.
[prosedur kerja]
(1) operasi penghentian.
(2) Nyalakan mode pemulihan refrigeran dengan melakukan prosedur berikut.

h : OFF l: Berkedip k : ON
Prosedur operasi H1P H2P H3P H4P H5P H6P H7P
Tekan dan tahan MODE (BS1) dari "Setting mode 1" selama 5 detik k h h h h h h
atau lebih dan atur ke "Setting mode 2."
Tekan SET (BS2) 28 kali untuk mengatur tampilan LED seperti yang k h k k k h h
ditunjukkan pada tabel di sebelah kanan. (1)
Tekan RETURN (BS3) sekali. (Pengaturan Sekarang ditampilkan.) k h h h h h l
Tekan SET (BS2) sekali untuk mengatur tampilan LED seperti yang k h h h h l h
ditunjukkan pada tabel di sebelah kanan.
Tekan RETURN (BS3) sekali untuk membuat keputusan. k h h h h k h
Ketika RETURN (BS3) ditekan sekali lagi, katup ekspansi elektronik k h h h h h h
terbuka sepenuhnya.
(3) Hubungkan unit pemulihan refrigeran untuk melakukan pemulihan refrigeran.
(4) Setelah penyelesaian pemulihan refrigeran, matikan mode pemulihan refrigeran dengan melakukan
prosedur berikut atau mematikan daya unit outdoor.
Prosedur operasi H1P H2P H3P H4P H5P H6P H7P
Tekan SET (BS2) 28 kali untuk mengatur tampilan LED seperti yang k h k k k h h
ditunjukkan pada tabel di sebelah kanan. (1)
Tekan RETURN (BS3) sekali. (Pengaturan Sekarang ditampilkan.) k h h h h l h
Tekan SET (BS2) sekali untuk mengatur tampilan LED seperti yang k h h h h h l
ditunjukkan pada tabel di sebelah kanan.
Tekan RETURN (BS3) sekali untuk membuat keputusan. k h h h h h k
Ketika RETURN (BS3) ditekan sekali lagi, katup ekspansi elektronik k h h h h h h
sepenuhnya menutup.
1. Jika Anda menjadi tidak yakin berapa kali Anda menekan tombol, tekan MODE (BS1) sekali
untuk kembali ke "Setting mode 1" dan mulai prosedur operasi lagi.

Operasi Uji Coba dan Pengaturan Bidang 56


SiMT281515E Pengaturan bidang dari PCB Unit Outdoor

4.4 Mode Monitor


Dalam mode ini, item berikut dapat diperiksa dengan menggunakan tombol BS.

Untuk masuk ke mode monitor, Tampilan LED


tekan MODE (BS1) saat dalam No. item pengaturan H H H H H H H Tampilan
“Setting mode 1”. 1 2 3 4 5 6 7 Data
P P P P P P P
0 Indikasi operasi l h h h h h h Lihat tampilan
kembalinya minyak Data (1).
< Pemilihan item pengaturan >
Tekan SET (BS2) dan atur tampilan 1 Indikasi
outdoor
kelas unit l h h h h h k Lihat tampilan
Data (2).
LED ke item pengaturan.
2 Isi coba lagi
(terbaru) l h h h h k h

< Konfirmasi tentang isi 3 Isi coba lagi (1 siklus l h h h h k k


pengaturan > sebelumnya)
Tekan RETURN (BS3) untuk menampilkan 4 Isi coba lagi (2 siklus l h h h k h h Lihat
data yang berbeda dari item pengaturan. sebelumnya) "Error code
display" pada
5 Isi kesalahan (terbaru) l h h h k h k halama
selanjutnya.
6 Isi kesalahan (1 siklus l h h h k k h
sebelumnya)
Tekan RETURN (BS3) dan beralih ke
7 Isi kesalahan (2 siklus l h h h k k k
status awal “Monitor mode”. sebelumnya)
 Tekan MODE (BS1) dan kembali ke Indikasi penyebab
10 l h h k h k h Lihat tampilan
operasi drooping Data (3).
“Setting mode 1”.
Jumlah dalam kolom "No." merupakan jumlah berapa kali waktu
menekan SET (BS2).

Tampilan Data (1)


Tampilan LED
Isi tampilan
H1P H2P H3P H4P H5P H6P H7P
Dalam operasi normal l h h h h h h
Dalam operasi l h h h h h l
kembalinya minyak

Tampilan Data (2) Data display (3)


Tampilan LED Tampilan LED
Isi tampilan Isi tampilan
H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
Pengaturan No. l h h h h h l
Normal (tidak dalam
l h h h h h l
RZR100LUY1 (4) l h h l h h h operasi drooping)
RZR125LUY1 (4) l h h l h h l Drooping tekanan l h h h h l h
RZR140LUY1 (4) l h h l h l h rendah
Drooping l h h h h l l
tekanan tinggi
Drooping pipa l h h h l h h
pembuangan Inverter
Drooping arus l h h h l h l
Inverter
Drooping
suhu sirip l h h h l l h
radiasi
Drooping Inverter l h h h l l l

Drooping arus l h h l h h h
keseluruhan
Drooping lainnya l h h l h h l

57 Operasi Uji Coba dan Pengaturan Bidang


Pengaturan bidang dari PCB Unit Outdoor SiMT281515E

4.5 Daftar isi tentang Coba lagi dan Kesalahan


Lakukan langkah-langkah berikut untuk memeriksa isi coba lagi dan kesalahan..

Untuk masuk ke "Monitor mode," tekan MODE <Tampilan RETURN 2>


(BS1) ketika dalam "Setting mode 1."
Ketika SET (BS2) ditekan, tampilan LED untuk
RETURN 2 menyala.

< Pemilihan item coba lagi atau kesalahan >


<Tampilan RETURN 3>
Tekan SET (BS2) untuk mengatur tampilan LED
Ketika SET (BS2) ditekan, tampilan LED untuk
ke item coba lagi atau kesalahan.
RETURN 3 menyala.

<Tampilan RETURN 1> Tekan RETURN (BS3) untuk mengembalikan


sistem ke keadaan awal dari "Monitor mode."
Ketika RETURN (BS3) ditekan, tampilan LED
untuk RETURN 1 menyala.  Dengan menekan MODE (BS1) akan
kembali ke "Setting mode 1."

k: ON h : OFF l : Berkedip
1 2 3
Kode Isi coba lagi atau kesalahan H H H H H H H H H H H H H H H H H H H H H H H H
kesal A 1 2 3 4 5 6 7 A 1 2 3 4 5 6 7 A 1 2 3 4 5 6 7
ahan P P P P P P P P P P P P P P P P P P P P P P P P
C4 Ketidaknormalan termistor pipa cair penukar l l k h h h l h l l k h h l h hl l k k h h hh
panas Indoor
E1 Ketidaknormalan PCB unit Outdoor l l h k h h l l l l k h h h h ll l k k h h h h
Ketidaknormalan tekanan tinggi (Terdeteksi l l k h h hl l l l k k h h hh
E3
dengan saklar tekanan tinggi)
E5 Kunci motor kompresor l l k h h l h l l l k k h h hh
Kunci motor DC 1 l l k h h l l l l l k k h h hl
Ketidaknorm l l k k h h l h
E7 alan motor Kunci motor DC 2
kipas unit Ketidaknormalan l l k k h h l l
Outdoor transmisi Inverter
Ketidaknorm Konektor katup ekspansi l l k h l h h l l l k k h h hl
E9 alan katup elektronik terputus
ekspansi Kesalahan karena kondisi basah l l k k h h l h
elektronik
Ketidaknorm Ketidaknormalan suhu pipa l l h k h l h l l l k h h h l l l l k k h h h l
alan suhu pembuangan
F3 pipa Termistor pipa pembuangan l l k k h h l h
pembuanga terputus
n
H3 Ketidaknormalan sistem saklar tekanan tinggi l
l h k h l h h l l k h h hl l l l k k h h hh
H9 Ketidaknormalan termistor udara Outdoor l l k h l h h l l l k k h h hh
J1 Ketidaknormalan sensor tekanan l l h k h l l h l l k h h hh l l l k k h h hh
J3 Ketidaknormalan termistor pipa pembuangan l l k h h hl l l l k k h h hh
J5 Ketidaknormalan termistor pipa hisap l l k h h l h l l l k k h h hh
J6 Ketidaknormalan termistor pipa cair l l k h h l l h l l k k h h hh
Ketidaknormalan termistor penukar panas l l k h h l l l l l k k h h hh
J7 sedang
L1 Ketidaknormalan PCB unit Outdoor l l h k h l l l l l k h h h h ll l k k h h h h
L4 Suhu sirip radiasi naik l l k h h l h hl l k k h h hh
L5 Arus berlebih output DC (seketika) l l k h h l h l l l k k h h hh
L8 Termal Elektronik (Jeda waktu) l l k h l h h hl l k k h h hh
L9 Pencegahan Stall (Jeda waktu) l l k h l h h l l l k k h h hh
Kesalahan sistem transmisi antar PCB unit l l k h l l h hl l k k h h hh
LC
outdoor

Operasi Uji Coba dan Pengaturan Bidang 58


SiMT281515E Pengaturan bidang dari PCB Unit Outdoor

k: ON h : OFF l : Berkedip
1 2 3
Kode Isi coba lagi atau kesalahan H H H H H H H H H H H H H H H H H H H H H H H H
kesal A 1 2 3 4 5 6 7 A 1 2 3 4 5 6 7 A 1 2 3 4 5 6 7
ahan P P P P P P P P P P P P P P P P P P P P P P P P
Ketidakseimbangan tegangan catu l l h k l h h h l l k hh hh l l l k k h hhh
P1
daya atau fasa terbuka
P4 Ketidaknormalan termistor sirip radiasi l l k hh l h h l l k k h hhh
PJ Ketidaknormalan Pengaturan kapasitas l l k hl l h l l l k k h hhh
Peringatan kekurangan refrigeran l l h k l h h l l l k h h h h h l l k k h hh l
U0 kekurangan
refrigeran kekurangan refrigeran l l k k h hl h
Ketidaknormal Tegangan berlebih dan l l k h h h l h l l k k h hh l
U2 an Tegangan tegangan bawah Inverter
catu daya Tegangan berlebih SP-PAM (1) l l k k h hl h
Kesalahan transmisi antara unit indoor dan l l k h h l h h l l k k h hhh
U4
unit outdoor
UA Ketidaknormalan saklar pengaturan bidang l l k hl h l h l l k k h hhh
Kesalahan transmisi antara unit indoor dan l l k hl l l l l l k k h hhh
UF outdoor/ pemipaan dan ketidakcocokan
kabel/ kekurangan refrigeran

Catatan:
1. SP: Single Pulse (Pulsa tunggal)
PAM: PAM adalah bentuk modulasi sinyal yang mengontrol tegangan atau arus output.

59 Operasi Uji Coba dan Pengaturan Bidang


Emergency Operation SiMT281515E

5. Operasi Darurat
Tabel di bawah ini menjelaskan tujuan mode operasi paksa.
Jika... Maka...
 Remote kontrol rusak Mode operasi paksa dapat digunakan untuk menjalankan pendinginan. Dalam
 PCB unit Indoor rusak mode operasi paksa, kompresor dipaksa beroperasi sampai PCB unit indoor
 PCB unit Outdoor rusak atau outdoor yang rusak kembali online.

Kondisi Startup
Anda dapat mengoperasikan sistem secara manual dengan mengubah saklar darurat pada PCB unit indoor
dan outdoor dari "normal" ke "darurat". Ketika sistem operasi dalam "darurat" tidak bisa mengendalikan suhu
kamar.

Kedua unit indoor dan outdoor harus diatur ke "darurat" selama daya MATI.

Kondisi Akhir
Anda dapat mengakhiri operasi darurat dengan mengubah saklar "darurat" kembali ke "normal" selama daya
MATI.

Operasi darurat
Tabel di bawah menjelaskan apa yang akan terjadi ketika saklar diatur ke "darurat":
Mengubah saklar ke "darurat" untuk… Menyalakan…
unit Indoor  Kipas unit Indoor
 Pompa saluran
unit Outdoor  Kompresor
 Kipas unit Outdoor (s)

Cara mengatur Operasi darurat


Untuk mengatur operasi darurat, lakukan sebagai berikut:
Langkah Tindakan Langkah Tindakan
1 Matikan daya. 4 Mengatur saklar darurat pada PCB unit outdoor
untuk Pendinginan.
2 Menyalakan saklar (SS1) darurat pada PCB
unit indoor. ON COOL

Normal OFF HEAT


Darurat

3 Menyalakan saklar darurat pada 5 Menyalakan catu daya.


PCB unit outdoor.

ON COOL ON ON

1 2 3 4

OFF HEAT OFF OFF  Jangan mengubah pengaturan


pabrik.

Komponen aktif
Komponen Pendinginan paksa
Kompresor Aktif
Kipas unit Outdoor Kecepatan kipas H
Kipas unit Indoor Kecepatan kipas H
Pompa saluran Aktif

Operasi Uji Coba dan Pengaturan Bidang 60


SiMT281515E Operasi darurat

Informasi tambahan
 Selama operasi darurat, jangan mencoba untuk mengoperasikan peralatan dari remote kontrol.
Remote kontrol menunjukkan "88" selama operasi darurat aktif pada unit indoor.
 Jika perangkat keselamatan diaktifkan selama darurat, semua aktuator dimatikan.
 Dalam pendinginan, unit berjalan selama 20 menit dan kemudian berhenti selama 10 menit
untuk menghindari pembekuan kumparan indoor.
 Operasi darurat tidak dapat dilakukan ketika PCB itu sendiri rusak.
 Pastikan untuk mengatur saklar darurat di kedua unit outdoor dan indoor.
 Unit tidak akan mengatur suhu selama operasi darurat.
 Ubah posisi saklar darurat hanya ketika daya dimatikan.

61 Operasi Uji Coba dan Pengaturan Bidang


SiMT281515E

Bagian 6
Diagnosis Servis
1. Inspeksi Pemeliharaan ............................................................................ 64
1.1 Gambaran umum .................................................................................64
2. Pemecahan masalah berdasarkan gejala .............................................. 66
2.1 Gambaran umum .................................................................................66
2.2 Peralatan tidak Beroperasi ...................................................................67
2.3 Kipas unit Indoor beroperasi, namun Kompresor tidak beroperasi .........68
2.4 Operasi pendinginan mulai tetapi berhenti segera.................................69
2.5 Setelah unit dimatikan, Tidak dapat dihidupkan ulang untuk sementara.70
2.6 Peralatan beroperasi namun tidak memberikan Pendinginan ................72
2.7 Peralatan Mengeluarkan Kabut Putih....................................................73
2.8 Peralatan Menghasilkan suara keras atau Getaran ...............................74
2.9 Peralatan Mengeluarkan Debu .............................................................76
2.10 LCD Remote Kontrol Menampilkan "88"..............................................76
3. Pemecahan masalah dengan indikasi LED............................................ 77
3.1 Pemecahan masalah dengan LED pada Unit Indoor .............................77
3.2 Pemecahan masalah dengan LED pada PCB Unit Outdoor .................77
4. Pemecahan masalah Remote Kontrol ................................................... 78
4.1 Penggantian Mode ...............................................................................78
4.2 Prosedur diagnosis otomatis dengan Remote Kontrol ...........................79
4.3 Kode Kesalahan dan Deskripsi .............................................................83
4.4 Kode Kesalahan – Kode Sub ................................................................84
4.5 Gambaran umum Perangkat Keselamatan outdoor ...............................87
4.6 Gambaran umum Perangkat Keselamatan Indoor................................87
5. Pemecahan masalah dengan indikasi pada Remote Kontrol ............... 88
5.1 Ketidaknormalan PCB unit Indoor .........................................................88
5.2 Ketidaknormalan Sistem Permukaan Air Saluran ..................................89
5.3 Kunci Motor Kipas Unit Indoor ..............................................................91
5.4 Ketidaknormalan Motor Kipas Unit Indoor ............................................92
5.5 Ketidaknormalan PCB Kipas ................................................................94
5.6 Ketidaknormalan Sistem Saluran ..........................................................95
5.7 Ketidaknormalan pengaturan kapasitas ................................................96
5.8 Kesalahan transmisi (antara PCB Unit Indoor dan PCB Kipas) ...............97
5.9 Kesalahan transmisi (antara PCB Unit Indoor dan PCB Kipas)..............99
5.10 Ketidaknormalan Termistor............................................................... 101
5.11 Kesalahan Kombinasi antara PCB Unit Indoor dan PCB Kipas .......... 102
5.12 Ketidaknormalan Termistor Remote Kontrol ..................................... 103
5.13 Ketidaknormalan PCB Unit Outdoor.................................................. 104
5.14 Ketidaknormalan Tekanan Tinggi
(Terdeteksi dengan Saklar Tekanan Tinggi) ...................................... 105
5.15 Kunci Motor Kompresor .................................................................... 107
5.16 Ketidaknormalan Motor Kipas Unit Outdoor ...................................... 108
5.17 Ketidaknormalan Katup Ekspansi elektronik...................................... 110
5.18 Ketidaknormalan Suhu Pipa Pembuangan ........................................ 112
5.19 Ketidaknormalan Sistem Saklar Tekanan Tinggi ............................... 113
5.20 Ketidaknormalan Termistor............................................................... 114

Diagnosis Servis 62
SiMT281515E

5.21 Ketidaknormalan Sensor tekanan ..................................................... 115


5.22 Ketidaknormalan PCB Unit Outdoor.................................................. 116
5.23 Suhu Sirip Radiasi Naik .................................................................... 118
5.24 Arus berlebih Output DC (Seketika) .................................................. 120
5.25 Termal Elektronik (Jeda Waktu)........................................................ 122
5.26 Pencegahan Stall (Jeda Waktu)........................................................ 124
5.27 Kesalahan Sistem Transmisi antara PCB Unit Outdoor ..................... 126
5.28 Ketidakseimbangan Tegangan Catu Daya atau Fasa Terbuka ......... 127
5.29 Ketidaknormalan Termistor Sirip Radiasi .......................................... 128
5.30 Ketidaknormalan Pengaturan Kapasitas ........................................... 129
5.31 Kekurangan Refrigeran .................................................................... 130
5.32 Ketidaknormalan Tegangan Catu Daya ............................................ 131
5.33 Kesalahan Transmisi antara Unit Indoor dan Unit Outdoor ................. 132
5.34 Kesalahan Transmisi antara Unit Indoor dan Remote Kontrol ............ 134
5.35 Kesalahan Transmisi antara Remote Kontrol MAIN dan
Remote Kontrol SUB ........................................................................ 135
5.36 Ketidaknormalan Saklar Pengaturan Bidang ..................................... 136
5.37 Kesalahan Pengaturan Alamat Terpusat ........................................... 137
5.38 Kesalahan Transmisi antara Unit Indoor dan Outdoor /
Pemipaan atau Ketidakcocokan pengkabelan / Kekurangan Refrigeran138
5.39 Pemeriksaan .................................................................................... 139

63 Diagnosis Servis
Maintenance Inspection SiMT281515E

1. Inspeksi Pemeliharaan
1.1 Gambaran umum
Ketika melakukan pemeliharaan, Anda setidaknya harus melakukan inspeksi berikut:
Unit Indoor

Kabel Transmisi antara unit


indoor dan outdoor
Adalah filter udara kotor?
Bagaimana kapasitas saklar?
Bagaimana ketebalan kabel?

Bagaimana tegangan dan Ke pemutus


arusnya? khusus

Pipa Refrigeran

Pipa saluran
unit Outdoor

Pembumian
Garis pandu untuk Kondisi Operasi Optimal
Garis pandu nilai operasi ketika beroperasi di bawah kondisi standar (pada frekuensi ternilai) dengan
menekan tombol operasi uji coba pada remote kontrol adalah seperti yang diberikan dalam tabel di bawah
ini.
Kipas unit indoor: pengatur H
Tekanan Tekanan Suhu pipa Suhu udara Unit Indoor: Unit Outdoor:
tinggi rendah pembuangan hisap Perbedaan Perbedaan
suhu antara suhu antara
Udara Hisap Udara Hisap
dan Udara dan Udara
pembuangan pembuangan
Pendingina 2.6 MPa ~ 0.6 MPa ~ 60°C ~ 100°C –2°C ~ 10°C 8°C ~ 18°C 7°C ~ 12°C
n 3.4 MPa 1.0 MPa

Kondisi Standar

Indoor Outdoor
Operasi Pendinginan 27°C DB/19°C WB 35°C DB
Selama atau setelah pemeliharaan, ketika Catu Daya dihidupkan ulang, operasi memulai ulang otomatis
dengan “auto restart function.” Harap menjalankan peringatan yang sesuai.

Diagnosis Servis 64
SiMT281515E Inspeksi Pemeliharaan

Korelasi dari Status Operasi Pendingin Ruangan dan Tekanan / Arus yang mengalir
Apa yang terjadi jika dibandingkan dengan nilai normal yang dirangkum dalam tabel di bawah ini.
(Diukur selama 15 ~ 20 menit atau lebih setelah operasi dimulai.)

Pendinginan
Status Pendingin Ruangan Tekanan rendah Tekanan tinggi Arus yang mengalir
Pengotor filter udara Lebih rendah Lebih rendah Lebih rendah
Hubung singkat Udara Inlet/Outlet Unit Lebih rendah Lebih rendah Lebih rendah
Indoor
Pengotor Sirip Unit Outdoor Lebih tinggi Lebih tinggi Lebih tinggi
Hubung singkat Udara Inlet/Outlet Unit Lebih tinggi Lebih tinggi Lebih tinggi
Outdoor
Udara tercampur dalam Refrigeran Lebih tinggi Lebih tinggi Lebih tinggi
Air tercampur dalam Refrigeran Lebih rendah 1 Lebih rendah Lebih rendah
Kotoran tercampur dalam Refrigeran Lebih rendah 2 Lebih rendah Lebih rendah
Kekurangan Refrigeran (Gas) Lebih rendah Lebih rendah Lebih rendah
Kompresi tidak memadai Lebih tinggi 3 Lebih rendah Lebih rendah

Catatan:
1. Air dalam refrigeran membeku di dalam pipa kapiler atau katup ekspansi elektronik, dan pada dasarnya
merupakan fenomena yang sama seperti pump down
2. Kotoran dalam refrigeran menyumbat filter dalam pipa, dan pada dasarnya merupakan fenomena yang
sama seperti pump down.
3. Perbedaan tekanan antara tekanan tinggi dan rendah menjadi kecil.

65 Diagnosis Servis
Pemecahan masalah berdasarkan gejala SiMT281515E

2. Pemecahan masalah berdasarkan gejala


Gambaran Umum
Gejala Rincian Tindakan
1 Peralatan tidak beroperasi Lihat Halaman67
2 Kipas Unit Indoor beroperasi, namun kompresor Lihat Halaman 68
tidak beroperasi.
3 Operasi Pendinginan mulai tapi berhenti segera. Lihat Halaman 69
4 Setelah unit dimatikan, unit tidak bisa dimulai Lihat Halaman.70
ulang untuk sementara waktu.
5 Peralatan beroperasi tetapi tidak memberikan Lihat Halaman 72
pendinginan.
6 Peralatan mengeluarkan kabut putih Lihat Halaman 73
7 Peralatan menghasilkan suara keras atau Lihat Halaman 74
8 getaran.
Peralatan mengeluarkan debu. Lihat Halaman.76
9 LCD Remote kontrol menampilkan “88”. Lihat Halaman 76
10 Peralatan memancarkan bau. Bau rokok dan bau ruangan terakumulasi di dalam
unit indoor dibuang/dikeluarkan bersama udara.
Bagian dalam unit indoor harus dibersihkan.
11 Kipas unit Indoor beroperasi di pengatur “L” It is normal. The monitoring function forcibly
selama 1 menit dalam mode “program dry” operates the fan for 1 minute.
bahkan ketika kompresor tidak beroperasi.
12 Pompa saluran beroperasi saat peralatan tidak Hal ini normal. Pompa saluran terus beroperasi
beroperasi. selama beberapa menit setelah peralatan
dimatikan.

Diagnosis Servis 66
SiMT281515E Pemecahan masalah berbasis gejala

2.2 Peralatan tidak Beroperasi


Model yang Semua model seri SkyAir
berlaku

Penyebab  Sekring terbakar atau gangguan kontak dalam sirkuit operasi


seharusnya  Titik kontak atau saklar operasi rusak
 Saklar Tekanan Tinggi Rusak
 Saklar magnetik untuk motor kipas rusak
 Aktivasi atau kegagalan relai arus lebih untuk motor kipas
 Relai arus lebih untuk kompresor rusak
 Termostat perlindungan kompresor rusak
 Isolasi dalam sistem listrik tidak memadai
 Titik kontak saklar magnetik untuk kompresor rusak
 Kompresor rusak
 Remote kontrol rusak atau baterai rendah (nirkabel)
 Pengaturan alamat remote kontrol nirkabel tidak benar

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar listrik sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Apakah saklar listrik MATI YA


atau sekering saklar listrik Nyalakan saklar listrik atau ganti
terbakar? sekring.
Tidak

Apakah ada kegagalan YA


daya ?
Tunggu sampai daya kembali.

Tidak

Apakah saklar operasi YA


ditekan berulang kali? Normal.
Memulai operasi setelah
3 menit (3-menit siaga).
Tidak

Apakah termostat berubah YA


Normal.
dan diatur ulang lagi?
Memulai operasi setelah
3 menit (3-menit siaga).
Tidak

Apakah lampu
operasi pada LCD YA
remote kontrol Mendiagnosis berdasarkan kode
berkedip? kesalahan pada remote kontrol.

Tidak

Apakah lampu operasi pada YA


bagian penerima unit indoor Mendiagnosis berdasarkan kode
berkedip? kesalahan pada remote kontrol.

Tidak

Komponen listrik rusak Periksa sistem listrik.

67 Diagnosis Servis
Pemecahan masalah berdasarkan gejala SiMT281515E

2.3 Kipas Unit Indoor Beroperasi, Namun Kompresor


tidak beroperasi
Model yang Semua model seri SkyAir
berlaku

Penyebab  Sekring terbakar atau gangguan kontak dalam sirkuit operasi


seharusnya  Termistor rusak
 PCB Unit indoor/outdoor rusak
 Saklar magnetik rusak
 Transistor daya rusak
 Kompresor rusak

Pemecahan Masalah

Perhatian Pastikan untuk mematikan saklar listrik sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

· Kipas unit Indoor berjalan pada laju aliran udara yang diatur.
· Bila suhu udara hisap lebih tinggi dari suhu yang diatur

Apakah saklar daya MATI atau YA


sekring untuk saklar daya Nyalakan saklar daya atau ganti
terbakar? sekring.
TIDAK

(1)Apakah tegangan ternilai YA


diterapkan pada terminal Ganti kompresor.
kompresor?
TIDAK

(2) Apakah output tegangan YA


ternilai dari saklar magnetik atau Ganti saklar magnetik atau
transistor daya? transistor daya.

TIDAK

(3) Apakah output tegangan YA


ternilai dari PCB? Ganti PCB.

TIDAK

Periksa termistor.

Termistor
udara hisap Outdoor unit Saklar
Indoor unit PCB unit outdoor
PCB unit Indoor PCB magnetik
PCB Rela y
COMP.

(3) (2) (1)


Input Output Input Output dari Output dari Output dari
ke dari ke relai atau saklar saklar
mikro- magnetik magnetik
PCB PCB PCB komputer atau sirkuit atau U, V, W
SW transistor transistor
daya daya

Diagnosis Servis 68
SiMT281515E Pemecahan masalah berbasis gejala

2.4 Operasi Pendinginan Mulai namun Berhenti segera


Model yang Semua model seri SkyAir
berlaku

Penyebab  Isi berlebih refrigeran


seharusnya  Udara tercampur dalam sistem refrigeran
 saklar tekanan rusak
 saklar magnetik untuk motor kipas unit outdoor rusak
 Relai tambahan untuk motor kipas unit outdoor rusak
 Penukar panas unit outdoor kotor
 Ada item pengganggu dalam aliran udara unit outdoor.
 Kipas unit outdoor rusak
 Filter udara unit indoor kotor
 Penukar panas unit indoor kotor
 Ada beberapa item pengganggu dalam aliran unit indoor.
 Kipas unit indoor rusak

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Apakah tipe remote Berkabel Apakah lampu operasi YA


kontrol berkabel atau remote kontrol berkedip? Diagnosis berdasarkan kode
nirkabel? kesalahan pada remote kontrol
Nirkabel TIDAK

Apakah lampu
operasi bagian YA
Diagnosis berdasarkan kode
penerima sinyal unit kesalahan pada remote kontrol
indoor berkedip?
TIDAK

TIDAK
Apakah kipas Motor kipas rusak. Periksa saklar
berputar? magnetik dan saklar tambahan
YA
untuk motor kipas.

YA
Apakah filter Bersihkan filter.
kotor?
TIDAK

Apakah ada item YA


yang mengganggu Hilangkan item pengganggu.
aliran udara?
TIDAK

Apakah penukar YA
panas kotor? Bersihkan penukar panas.
TIDAK

Kemungkinan penyebab sebagai berikut:


• Isi refrigeran berlebih
• Pencampuran udara dalam sistem refrigeran Setelah pengeringan vakum,
• Saklar tekanan rusak isi jumlah refrigeran yang
benar. Periksa saklar tekanan.

69 Diagnosis Servis
Pemecahan masalah berdasarkan gejala SiMT281515E

2.5 Setelah Unit Dimatikan, Unit tidak dapat dihidupkan


kembali untuk Sementara
Model yang Semua model seri SkyAir
berlaku

Penyebab  Relai arus berlebih (untuk kompresor)


seharusnya Relai arus berlebih akan berpengaruh karena alasan berikut
• Tegangan catu daya lebih rendah
• Kelebihan tingkat tekanan tinggi
• Ukuran kabel daya tidak memadai
• Kompresor rusak
 Termostat Perlindungan Kompresor
Termostat Perlindungan Kompresor akan berpengaruh karena alasan berikut
• Kompresi kompresor tidak memadai
• Refrigeran tidak sesuai
• Katup ekspansi elektronik rusak
• Sirkulasi refrigeran tidak memadai

Diagnosis Servis 70
SiMT281515E Pemecahan masalah berbasis gejala

Pemecahan masalah

Peratian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Nyalakan saklar ON OFF operasi,


kemudian tunggu.

Apakah unit mulai operasi YA


YES
Does the 3unit
setelah start operation
menit? Normal.
after 3 minutes?
Unit berada dalam mode
NO
TIDAK siaga 3 menit.

Tidak (Tidak begitu panas)


Apakah sisi pembuangan dari Periksa kompresor.
kompresor panas setelah unit
berhenti?

YA

Periksa penyebab mengapa relai arus


berlebih (untuk kompresor) atau termostat
perlindungan kompresor melakukan
tindakan..

[Sistem listrik]

Tegang Catu Daya TIDAK


NO
dalam ±10 % dari Hubungi Perusahaan Listrik.
tegangan yang
ditentukan
YA

TIDAK
NO
Apakah ukuran
keseluruhan panjang
Ganti kabel daya.
kabel daya sesuai?
YA

[Sirkuit refrigeran ]
Setelah pengeringan vakum, isi jumlah
refrigeran yang benar. Kemudian, mulai
beroperasi lagi.

Apakah ada perbedaan TIDAK


suhu antara inlet dan NO
Ganti katup ekspansi
outlet katup ekspansi
elektronik?
elektronik.

YA

Defective
Kompresorcompressor
Rusak Periksa kompresor.

71 Diagnosis Servis
Pemecahan masalah berdasarkan gejala SiMT281515E

2.6 Peralatan beroperasi namun tidak memberikan


pendinginan
Model yang Semua model seri SkyAir
berlaku

Penyebab  Pilihan model Tidak Benar


seharusnya  Kekurangan Refrigeran
 Aliran udara dalam unit indoor tidak memadai
 Peningkatan tekanan tinggi
 Selain itu, kesalahan berikut mungkin dapat dibayangkan
• Kompresi kompresor tidak memadai
• Sirkulasi refrigeran tidak memadai
• Katup ekspansi elektronik rusak

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau memutuskan konektor, atau kerusakan
bagian dapat terjadi.

Ukur suhu udara hisap dan udara


pembuangan . Perbedaan suhu =
Suhu udara hisap – Suhu udara
pembuangan

perbedaan suhu untuk Apakah beban panas


pendinginan harus antara 8 YA YA
meningkat setelah instalasi Normal.
dan unit?
18C.
TIDAK
TIDAK
• Pilihan model salah
Instalasi unit tambahan
• Pengaruh matahari langsung
harus dipertimbangkan.
Apakah ada embun beku
di sekitar port inlet Apakah arus operasi
penukar panas unit indoor atau YA YA
kurang dari tingkat yang Kekurangan refrigeran dapat
port outlet katup ekspansi ditentukan? menimbulkan gangguan.
elektronik?
Setelah pengeringan vakum, isi
TIDAK jumlah refrigeran yang benar
TIDAK

Apakah laju aliran udara YA


unit indoor menurun?
Periksa setiap bagian.
• filter udara tersumbat
TIDAK
• Penukar panas kotor
• motor kipas rusak
Apakah tingkat tekanan
(Lihat Pemecahan masalah “A6”.)
YA
tinggi lebih tinggi dari Periksa setiap item.
tingkat normal?
• Isi refrigeran berlebihan
• Udara tercampur dalam sistem
TIDAK refrigeran
• Penukar panas kotor
• Hubungan pendek udara
pembuangan
• Item pengganggu dalam aliran
udara
• Motor kipas unit outdoor rusak
(Lihat pemecahan masalah “E7”.)
Periksa setiap item.
• Kompresi kompresor tidak
memadai
• Sirkulasi refrigeran tidak memadai
• Katup ekspansi elektronik rusak
Diagnosis Servis 72
SiMT281515E Pemecahan masalah berbasis gejala

2.7 Peralatan Mengeluarkan Kabut Putih


Model yang Semua model seri SkyAir
berlaku

Penyebab  Tempat instalasi lembab


seharusnya  Tempat Instalasi kotor dan dengan kabut minyak pekat.
 Penukar panas kotor
 Filter udara tersumbat
 Motor kipas rusak

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar listrik sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Apakah suhu kamar lebih tinggi Melanjutkan operasi unit.


dari nilai yang ditetapkan YA Apakah kabut putih keluar dari TIDAK
Normal
dalam pendinginan? unit?

YA
TIDAK

Hilangkan sumber kondisi lembab.

Apakah penukar panas YA


unit indoor kotor? Pembersihan penukar panas
diperlukan.
TIDAK

Apakah lokasi berdebu atau YA


dengan kabut minyak pekat?
Hilangkan sumber minyak,kabut
atau debu
TIDAK

Apakah laju aliran YA


Bersihkan filter udara.
udara terlalu kecil?
Periksa motor kipas.
(Lihat pemecahan masalah “A6”)
TIDAK

Normal

73 Diagnosis Servis
Pemecahan masalah berdasarkan gejala SiMT281515E

2.8 Peralatan Menghasilkan suara keras atau Getaran


Model yang Semua model seri SkyAir
berlaku

Penyebab  Instalasi tidak benar


seharusnya  Kontak kipas, pipa, casing, dll.
 Kebisingan aliran refrigeran
 Kebisingan operasi peralatan saluran pembuangan
 Kebisingan kontraksi komponen resin
 Selain itu, kesalahan berikut mungkin dapat dibayangkan
• Isi refrigeran yang berlebih
• Percampuran udara
• Kebisingan sekilas dari refrigeran yang tidak memadai (Meredam kebisingan)

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.
Apakah kebisingan
menimbulkan getaran [ sisi pekerjaan instalasi]
pada seluruh plafon dan YA
dinding? Koreksi instalasi.
Penguatan untuk plafon atau dinding
TIDAK

Apakah kebisingan YA
menimbulkan getaran
Masukkan peredam kejut di bagian
pada bagian bantalan bantalan, atau memperkuat
Unit? bagian bantalan .
TIDAK

TIDAK
Apakah pipa aman? Masukkan bahan bantalan untuk
dukungan pipa seperti pelana.
[sisi catu daya] YA

Apakah kipas YA
Bongkar dan hilangkan kontak bagian
bersentuhan dengan
bagian lain?
TIDAK

YA
Apakah pipa Perbaiki pipa secara manual
melakukan kontak atau ikat beban berat ke pipa.
dengan casing?

TIDAK

Apakah suara aliran


kebisingan dari katup YA
Normal.
pereduksi tekanan atau
lubang kapiler?

TIDAK

Diagnosis Servis 74
SiMT281515E Pemecahan masalah berbasis gejala

Suara "shoo..."
ringan terus menerus YA
Normal. Suara tersebut
selama pendinginan
merupakan kebisingan aliran
TIDAK gas (refrigeran) di sisi dalam
unit pendingin ruangan.
Suara "shoo..."
muncul hanya setelah YA Normal. Suara ini adalah suara
operasi mulai atau berhenti. yang ditimbulkan pada saat aliran
gas (refrigeran) berubah atau
TIDAK berhenti.

Suara "shoo..."
muncul selama YA
pendinginan setelah Normal. Suara operasi perangkat
operasi berhenti. pengeringan
TIDAK

Berderit setelah YA Normal. Derit yang


operasi berhenti ditimbulkan oleh penyusutan
bagian resin karena
TIDAK
perubahan suhu.
• Isi refrigeran berlebihan
• Udara tercampur dalam sistem refrigeran
• Kebisingan aliran karena kekurangan Setelah pengeringan vakum,
refrigeran. (suara shoo...) isi jumlah yang benar dari
refrigeran.

75 Diagnosis Servis
Pemecahan masalah berdasarkan gejala SiMT281515E

2.9 Peralatan Mengeluarkan Debu


Model yang Semua model seri SkyAir
berlaku

Penyebab  Karpet
seharusnya  Rambut Hewan
 Aplikasi (toko kain, ...)

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Apakah gangguan muncul


pada saat operasi dimulai lagi
setelah jangka waktu operasi YA
Debu yang terkumpul di bagian
yang lama? dalam unit indoor dikeluarkan.
Pembersihan untuk bagian
dalam unit indoor diperlukan.
TIDAK

YA
Apakah dilengkapi filter udara? Debu yang terkumpul di bagian
dalam unit indoor dikeluarkan.
TIDAK
Pembersihan untuk bagian
dalam unit indoor diperlukan.
Pasang filter udara.

2.10 LCD Remote Kontrol Menampilkan "88"


Model yang Semua model seri SkyAir
berlaku

Penyebab  Posisi SS1 pada PCB unit indoor pada posisi “Darurat”.
seharusnya

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Gangguan muncul YA
hanya setelah Unit ini melakukan pemeriksaan
menyalakan catu untuk mengkonfirmasi bahwa
daya.
TIDAK remote kontrol normal. Indikasi
muncul sebentar.

Apakah posisi SS1 pada YA


PCB unit indoor pada posisi Putar saklar ke "Normal," dan atur
"Darurat"? ulang catu daya.

TIDAK

Periksa unit berdasarkan


pemecahan masalah dari LED
unit indoor dan LED unit
outdoor.

Diagnosis Servis 76
SiMT281515E Troubleshooting by Remote Controller

3. Pemecahan masalah dengan indikasi LED


3.1 Pemecahan masalah berdasarkan LED pada unit Indoor
Pemecahan masalah dapat dilakukan berdasarkan LED (hijau) monitor servis. (Berkedip jika normal)
k: LED MENYALA / h : LED MATI / l: LED Berkedip / — : Tidak ada koneksi dengan pemecahan
masalah
Monitor Miro-
komputer Normal Isi / pemrosesan
HAP (LED-A)
l unit Indoor normal  Pemecahan masalah unit Outdoor
l Kabel transmisi antara unit indoor dan outdoor tidak sesuai
Jika LED-A unit outdoor MATI, pemecahan masalah unit outdoor dilakukan. Jika
LED-A unit outdoor berkedip, kabel PCB unit indoor atau outdoor rusak.
k PCB unit indoor rusak (4)
h Catu daya rusak atau PCB rusak atau kabel transmisi antara unit indoor dan outdoor
rusak. (4)

Catatan: 1. Ketika tombol INSPECTION/TEST remote kontrol ditekan, tampilan INSPECTION berkedip
masuk mode INSPECTION.
2. Dalam mode INSPECTION, jika tombol ON/OFF ditekan dan ditahan selama 5 detik atau lebih,
tampilan riwayat kesalahan tersebut OFF. Dalam hal ini, setelah kode kesalahan berkedip 2
kali, tampilan kode berganti menjadi “00” (= Normal) dan No. unit berganti menjadi “0”. Mode
INSPECTION otomatis beralih ke mode normal (tampilan suhu yang diatur).
3. Operasi berhenti karena kesalahan tergantung pada model atau kondisi.
4. Memecahkan masalah dengan menonaktifkan catu daya selama minimal 5 detik, hidupkan lagi
catu daya, dan kemudian periksa kembali tampilan LED.

3.2 Pemecahan masalah berdasarkan LED pada PCB Unit


Outdoor
Diagnosis berikut dapat dilakukan dengan menyalakan saklar daya dan memeriksa indikasi LED pada PCB
(A1P) dari unit outdoor.

k: LED MENYALA / h : LED MATI / l: LED Berkrdip / — : Tidak ada hubunganya dengan pemecahan
masalah
Deteksi LED
Mikro-komputer di
HAP operasi Deskripsi
normal
(Hijau)
l Normal
k PCB unit outdoor rusak( 1)
h Ketidaknormalan catu daya, PCB unit outdoor rusak ( 2)
l Aktivasi perangkat perlindungan ( 3)

Cat at an : 1. Matikan saklar daya, dan nyalakan lagi setelah 5 detik atau lebih. Periksa kondisi kesalahan,
dan lakukan diagnosis masalah.
2. Matikan saklar daya. Setelah 5 detik atau lebih, cabut kabel sambungan (2). Kemudian hidupkan
saklar daya. Jika HAP pada PCB unit outdoor berkedip sekitar 10 detik, PCB unit indoor yang
rusak.
3. Juga periksa untuk fasa terbuka.

Keterangan: Monitor deteksi kesalahan terus berlanjut untuk mengindikasi kesalahan yang muncul
sebelumnya sampai saklar daya dimatikan.
Pastikan untuk mematikan saklar daya setelah pemeriksaan.

77 Diagnosis Servis
Pemecahan masalah berdasarkan Indikasi LED SiMT281515E

4. Pemecahan masalah dengan Remote Kontrol


4.1 PenggantianMode
4.1.1 BRC1C61/BRC1D61
Mode berikut dapat dipilih dengan menggunakan tombol INSPECTION / TEST pada remote control .

Tekan tombol INSPECTION/TEST selama


lebih dari 4 detik. Data servis dapat diperoleh
Pengaturan unit indoor dapat dilakukan
• Waktu tanda Mode • Riwayat kode kesalahan
Pengaturan mode
filter Servis • Data suhu dari berbagai bagian
• Arah aliran bidang Pengaturan servis dapat dilakukan.
udara • Kipas dipaksa menyala
• Lain-lain • Pengaturan laju aliran udara/arah aliran udara
Tekan tombol INSPECTION/TEST Tekan tombol INSPECTION/TEST sekali.
selama lebih dari 4 detik.

mode
Normal
Tekan tombol INSPECTION/TEST sekali
Tekan tombol INSPECTION/TEST
atau setelah 30 menit
sekali.
setelah 10 detik

Kode berikut dapat diperiksa.


• Kode kesalahan mode
• Kode model Indoor mode Operasi Termostat secara paksa DIAKTIFKAN.
• Kode model Outdoor Inspeksi uji coba
Tekan tombol INSPECTION/TEST
sekali.

4.1.2 BRC1E62
<Menu Utama>
Mode • Arah aliran udara
menu • Permulaan cepat (quick start )
• Pilihan Penghematan Energi
utama • Jadwal
<Layar dasar>
• pembersihan otomatis filter
• Penggantian mode operasi
• Informasi pemeliharaan
• Kontrol kecepatan kipas Tekan tombol
Tekan Cancel • Konfigurasi
• Tampilan Menu
Menu/Enter sekali. • Pengaturan arus
• Konfirmasi setiap pengaturan
sekali. • Jam & Kalender
• Menyala
• Bahasa
• Mati
• Pembatalan
• Lampu operasi Layar
Tekan tombol Cancel dasar Tekan Cancel
sekali.
selama 4 detik atau lebih.

Tekan tombol Cancel sekali.


<Pengaturan
Mode Tekan Cancel selama < Menu Pemeliharaan>
Servis>
• Operasi uji coba
4 detik atau lebih. Menu • Nama Model
• Kontak pemeliharaan service
• Pengaturan bidang setting Maintenance • Jam operasi
• Setpoint Min. berbeda • Status unit Indoor

• Alamat AirNet unit Outdoor • Status unit Outdoor


• Riwayat kesalahan • Tampilan kesalahan
• Status unit Indoor • Menukar No. Unit
• Status unit Outdoor • Nilai Sensor yang dialamatkan
• Kipas Paksa
• Saklar Kontroller Main Sub
• Indikator Filter
• Uji pembersihan otomatis
filter
• Brush/Filter Ind.
• Menonaktifkan
pembersihan otomatis filter

Diagnosis Servis 78
SiMT281515E Pemecahan masalah dengan Remote Kontrol

4.2 Prosedur diagnosis sendiri dengan Remote Kontrol


4.2.1 Remote kontrol berkabel — BRC1C61/BRC1D61
Jika operasi berhenti karena kesalahan, LED operasi remote kontrol berkedip, dan kode kesalahan
ditampilkan. (Bahkan jika operasi penghentian dilakukan, isi kesalahan ditampilkan saat mode pemeriksaan
dimasukkan.) Kode kesalahan memungkinkan Anda untuk menceritakan apa jenis kesalahan menyebabkan
operasi berhenti. Lihat P.83 untuk kode kesalahan dan isi kesalahan.
LED Operation

tombol ON/OFF

Tampilan unit indoor


dimana kesalahan
terdeteksi

tampilan pemeriksaan

kode kesalahan

Tombol INSPECTION/TEST

Catatan:
1. Dengan menekan tombol INSPECTION/TEST akan berkedip indikasi pemeriksaan.
2. Selama dalam mode servis, tekan tombol ON / OFF selama 5 detik atau lebih akan menghapus
indikasi riwayat kegagalan yang ditunjukkan di atas. Dalam hal ini, pada tampilan kode, kode
kesalahan akan berkedip dua kali dan kemudian berubah menjadi “00” (= Normal), No. Unit akan
berubah menjadi “0”, dan mode operasi otomatis akan beralih dari mode servis ke mode normal
(Menampilkan suhu yang diatur).

79 Diagnosis Servis
Pemecahan masalah dengan Remote Kontrol SiMT281515E

4.2.2 Remote kontrol berkabel — BRC1E62


Berikut ini akan ditampilkan pada layar ketika sebuah kesalahan (atau peringatan) terjadi selama
operasi. Periksa kode kesalahan dan ambil tindakan perbaikan yang ditentukan untuk model tertentu.

Layar

Lampu operasi

(1) Memeriksa kesalahan atau peringatan


Status operasi Tampil
an

Lampu operasi(hijau) mulai


Dimatika berkedip. pesan "Error: Push
sistem berhenti beroperasi. Menu button" akan muncul dan
n tidak berkedip pada bagian bawah
normal layar

Lampu operasi(hijau) tetap


menyala. Pesan "Warning: Push
Peringatan sistem terus beroperasi. Menu button" akan muncul dan
berkedip pada bagian bawah
layar.

(2) Melakukan tindakan perbaikan

· Tekan tombol Menu/Enter untuk memeriksa kode kesalahan.

· Lakukan tindakan perbaikan khusus untuk model tersebut.

Kode kesalahan

FBQ100EVE Nama model


RZR100LUY1 yang berlaku

Diagnosis Servis 80
SiMT281515E Pemecahan masalah dengan Remote Kontrol

4.2.3 Remote Kontrol Nirkabel


Jika unit berhenti karena kesalahan, LED indikasi operasi pada bagian penerima sinyal berkedip. Kode
kesalahan dapat ditentukan dengan mengikuti prosedur yang diuraikan di bawah ini. (Kode kesalahan
ditampilkan ketika kesalahan operasi telah terjadi. Dalam kondisi normal, kode kesalahan dari masalah
terakhir ditampilkan.)

1 Tekan tombol INSPECTION/TEST untuk memilih “inspection”. Peralatan masuk


mode inspeksi. Indikasi “Unit” ditampilkan dan tampilan No. Unit menunjukkan
indikasi “0” berkedip.
2 Atur No. Unit
Tekan tombol UP atau DOWN dan ubah tampilan No. Unit sampai bel (1)
dihasilkan dari unit indoor.
1. Jumlah bunyi bip
3 bunyi bip pendek: Melakukan semua operasi berikut.
1 bunyi bip panjang: Melakukan langkah 3 dan 4.
Melanjutkan operasi pada langkah 4 sampai bel tetap AKTIF.
Bel terus menerus menunjukkan bahwa kode kesalahan
dikonfirmasi.
Bunyi bip terus menerus: tidak ada kelainan.
3 Tekan tombol pemilih MODE.
Indikasi “0” kiri (digit atas) kode kesalahan berkedip.
4 diagnosis digit atas kode kesalahan
Tekan tombol UPatau DOWN dan ubah digit atas kode kesalahan sampai bel
pencocokan kode kesalahan (2) dihasilkan.
 Digit atas kode berubah seperti yang ditunjukkan di bawah ini jika tombol UP
dan DOWN ditekan.

0ACEHFJLPU987654
Tombol "UP" tombol "DOWN"
2 Jumlah bunyi bip
Bunyi bip terus menerus: Kedua digit atas dan bawah dicocokkan. (Kode kesalahan dikonfirmasi)
2 bunyi bip pendek: Digit atas dicocokkan.
1 bunyi bip pendek Digit bawah dicocokkan.
5 Tekan tombol pemilih MODE.
Indikasi “0” kanan (digit bawah) kode kesalahan berkedip.
6 diagnosis digit bawah kode kesalahan
Tekan tombol UP atau DOWN dan ubah digit bawah kode kesalahan terus
menerus sampai bel pencocokan kode kesalahan (2) dihasilkan.
 Digit bawah kode berubah seperti yang ditunjukkan di bawah ini jika tombol
UP dan DOWN ditekan.

0123456789AHCJEF
Tombol "UP" Tombol "DOWN"

81 Diagnosis Servis
Pemecahan masalah dengan Remote Kontrol SiMT281515E

Status normal
Normal status
Masuk mode
Enters operasi dari
inspection modestatus normal
from normal
jika tombol
status INSPECTION/TEST
when ditekan
the INSPECTION/TEST
button is pressed.

1. Tekan tombol INSPECTION/TEST


1 Press INSPECTION/TEST button.

Jika tidak ada tombol


ditekan selama 1 menit,
peralatan kembali ke
status normal.

3
Jika tombol pemilih Tekan
MODE ditekan atau tidak tombol
ada tombol ditekan pemilih
selama 1 menit, MODE
peralatan kembali ke .
status.normal Jika tidak ada tombol
ditekan selama
If no button is 1pressed
menit,
peralatan kembali ke
for 1 minute,
status normal
equipment returns to
normal status.

5 Tekan tombol pemilih MODE


5 Press MODE selector button.

Diagnosis Servis 82
SiMT281515E Pemecahan masalah dengan Remote Kontrol

4.3 Kode Kesalahan dan Deskripsi


Tampilan
Remote Isi Kesalahan Halaman
Kontrol referensi
Unit Indoor A0 Perangkat perlindungan eksternal —
A1 Ketidaknormalan PCB unit indoor 88
A3 Ketidaknormalan sistem permukaan air saluran 89
Kunci motor kipas unit indoor 91
A6
Ketidaknormalan motor kipas unit indoor 92
A8 Ketidaknormalan PCB kipas 94
AF Ketidaknormalan sistem saluran 95
AJ Ketidaknormalan pengaturan Kapasitas 96
C1 Kesalahan transmis (antara PCB unit indoor dan PCB kipas) 97
C4 Ketidaknormalan termistor pipa cair penukar panas Indoor 101
C5 Ketidaknormalan termistor penukar panas Indoor 101
C6 Kesalahan kombinasi antara PCB unit indoor dan PCB kipas 102
C9 Ketidaknormalan termistor udara hisap 101
CJ Ketidaknormalan termistor Remote kontrol 103
Unit E1 Ketidaknormalan PCB unit Outdoor 104
Outdoor E3 Ketidaknormalan Tekanan Tinggi (terdeteksi oleh saklar tekanan tinggi) 105
E5 Kunci motor kompresor 107
E7 Ketidaknormalan motor kipas unit Outdoor 108
E9 Ketidaknormalan katup ekspansi elektronik 110
F3 Ketidaknormalan suhu pipa pembuangan 112
H3 Ketidaknormalan sistem saklar tekanan tinggi 113
H9 Ketidaknormalan termistor udara Outdoor 114
J1 Ketidaknormalan sensor tekanan 115
J3 Ketidaknormalan termistor pipa pembuangan 114
J5 Ketidaknormalan termistor pipa hisap 114
J6 Ketidaknormalan termistor pipa cair 114
J7 Ketidaknormalan termistor penukar panas sedang 114
L1 Ketidaknormalan PCB unit Outdoor 116
L4 Suhu sirip radiasi naik 118
L5 Arus lebih output DC (seketika) 120
L8 Termal elektronik (jeda waktu) 122
L9 Pencegahan Stall (jeda waktu) 124
LC Kesalahan sistem transmisi antara PCB unit outdoor 126
P1 Ketidakseimbangan tegangan catu daya atau fasa terbuka 127
P4 Ketidaknormalan termistor sirip radiasi 128
PJ Ketidaknormalan pengaturan kapasitas 129
Sistem U0 Kekurangan refrigerant 130
U2 Ketidaknormalan tegangan catu daya 131
U4 Kesalahan transmisi antara unit indoor dan unit outdoor 132
U5 Kesalahan transmisi antara unit indoor dan remote kontrol 134
U8 Kesalahan transmisi antara remote kontrol MAIN dan remote kontrol SUB 135
UA Ketidaknormalan saklar pengaturan bidang 136
UC Kesalahan pengaturan alamat terpusat 137
UF Kesalahan transmisi antara unit indoor dan outdoor / pemipaan dan 138
ketidakcocokan kabel / kekurangan refrigeran

83 Diagnosis Servis
Pemecahan masalah dengan Remote Kontrol SiMT281515E

4.4 Kode Kesalahan – kode Sub


Jika kode kesalahan seperti yang ditunjukkan di bawah ini ditampilkan saat navigasi remote kontrol
(BRC1E62) sedang digunakan, buat rincian diagnosis atau diagnosis mengenai unit terkait dengan
mengacu pada daftar rincian kode kesalahan yang terlampir.

4.4.1 Unit Indoor


Pemecahan masalah
Kode
Kesalahan Deskripsi kesalahan Deskripsi diagnosis
A6 - 01 Motor kipas terkunci Arus motor kipas yang terkunci telah terdeteksi.
Putar kipas dengan tangan untuk memeriksa sambungan
Konektor .
A6 - 10 Kesalahan arus berlebih Kipas Arus berlebih motor kipas telah terdeteksi.
Periksa sambungan konektor antara motor kipas dan PCB
kipas. Jika sambungan normal, ganti motor kipas. Jika hal
ini masih tidak bisa mengatasi kesalahan, ganti PCB kipas.

A6 - 11 Kesalahan deteksi posisi kipas Kesalahan dalam pendeteksian posisi motor kipas. Periksa
sambungan konektor antara motor kipas dan PCB kipas.
Jika sambungan normal, ganti motor kipas. Jika hal ini
masih tidak bisa mengatasi kesalahan, ganti PCB kipas.
A8 - 01 Ketidaknormalan PCB kipas Kesalahan tegangan catu daya PCB kipas telah terdeteksi.
Periksa apakah ada sambungan konektor longgar atau
putus, atau sumber dari pembangkit kebisingan di
dekatnya.
C1 - 01 Kesalahan transmisi Kesalahan transmisi telah terdeteksi antara PCB unit indoor
dan PCB kipas. Periksa apakah ada sambungan konektor
transmisi longgar atau putus.
C4 - 02 Ketidaknormalan sistem termistor Penukar panas Korsleting termistor telah terdeteksi. Periksa area
(korsleting) Sambungan apakah ada penyumbatan benda asing

C4 - 03 Ketidaknormalan sistem termistor Penukar panas Pemutusan termistor telah terdeteksi. Periksa apakah ada
(Sirkuit terbuka) sambungan konektor longgar atau putus.

C5 - 02 Ketidaknormalan sistem termistor Penukar panas Korsleting termistor telah terdeteksi. Periksa area
sedang (korsleting) Sambungan apakah ada penyumbatan benda asing

C5 - 03 Ketidaknormalan sistem termistor Penukar panas Pemutusan termistor telah terdeteksi. Periksa apakah ada
sedang (Sirkuit terbuka) sambungan konektor longgar atau putus.

C6 - 01 Kombinasi PCB unit indoor danPCB kipas rusak Kombinasi PCB unit indoor dan PCB kipas rusak. Periksa
apakah adaptor pengaturan kapasitas benar dan jenis PCB
kipas benar.
C9 - 02 Ketidaknormalan sistem termistor udara hisap Korsleting termistor telah terdeteksi. Periksa area
(korsleting)
(short Sambungan apakah ada penyumbatan benda asing

C9 - 03 Ketidaknormalan sistem termistor udara hisap Pemutusan termistor telah terdeteksi. Periksa apakah ada
(Sirkuit terbuka) sambungan konektor longgar atau putus

Diagnosis Servis 84
SiMT281515E Pemecahan masalah dengan Remote Kontrol

4.4.2 Unit Outdoor


Pemecahan masalah
Kode
Kesalahan Deskripsi kesalahan Deskripsi diagnosis
E7 - 01 Kunci motor kipas Motor kipas telah menyebabkan rotasi tidak normal.
Periksa sambungan konektor antara motor kipas dan PCB
unit outdoor. Jika sambungan normal, ganti motor kipas.
Jika hal ini masih tidak bisa mencegah kesalahan, ganti
PCB unit outdoor.
L1 - 01 Kesalahan arus berlebih sesaat (selama dalam Lihat diagram alir “L1” dari setiap panduan dan lakukan
Operasi startup) diagnosis mengenai unit terkait berdasarkan kode kesalahan
L1 - 02 Kesalahan sensor arus di PCB Yang ditunjukkan pada sisi kiri.
L1 - 03 Kesalahan offset arus
L1 - 04 Kesalahan IGBT (1)
L1 - 05 Kesalahan pengaturan Jumper
L1 - 06 Kesalahan tegangan berlebih SP/MP-PAM (2, 3)
L8 - 01 Kesalahan termal elektronik 1 Beban arus berlebih selama 260 detik atau lebih
Kesalahan ini seharusnya akibat dari pengisian refrigeran
Yang berlebihan, kerusakan yang disebabkan bantalan
kompresor, tekanan terlalu tinggi, dll. periksa dan selidiki
Penyebabnya.
L8 - 02 Kesalahan termal elektronik 2 Arus beban berlebih dekat dengan arus terkunci yang dialirkan
dalam termal selama lima detik. Kesalahan ini seharusnya akibat
dari katup penghenti tertutup, kabel dalam motor kompresor
terputus, dll. Periksa dan selidiki penyebabnya.
L8 - 03 Penurunan revolusi kompresor Beban kompresor telah meningkat setelah startup. Kesalahan ini
seharusnya akibat dari kegagalan daya sesaat, kembalinya cairan,
dll. periksa dan selidiki penyebabnya.
L8 - 04 Kesalahan deteksi petir Lonjakan yang disebabkan oleh petir
L8 - 05 Arus pembatas inverter Arus batas berlebih mengalir dalam inverter. Kesalahan ini
seharusnya akibat dari kegagalan untuk membuka katup
penghenti, pengisian refrigeran yang berlebihan, penyumbatan
dalam filter unit indoor, noda dalam penukar panas unit
indoor/outdoor dll.. periksa dan selidiki penyebabnya.
L9 - 01 Pencegahan Stall (kenaikan arus) Arus beban berlebih telah diterapkan untuk memulai
kompresor.
Kesalahan ini seharusnya akibat dari tekanan diferensial
Startup tinggi, kembalinya cairan, minyak kompresor
Berlebihan, minyak kompresor tidak normal, getaran
Poros kompresor, dll..
Periksa dan selidiki penyebabnya.
L9 - 02 Pencegahan Stall (kesalahan startup) Kompresor belum menyelesaikan operasi startup.
Kesalahan ini seharusnya akibat dari tekanan diferensial
startup tinggi, kembalinya cairan, minyak kompresor
berlebihan, minyak kompresor tidak normal, getaran poros
kompresor, sirkuit deteksi posisi rusak, dll.. Periksa dan
selidiki penyebabnya.
PJ - 01 Pengaturan kapasitas tidak dilakukan Ini adalah PCB unit outdoor untuk perbaikan, tetapi tidak
Memiliki adaptor pengaturan yang terhubung. Sambungkan
capacity
correct capacity
adaptor pengaturan ke PCB.
PJ - 04 Pengaturan kapasitas rusak Kesalahan ini hasil dari ketidakcocokan sinyal antara
kontroler di PCB dan inverter. Periksa apakah jenis PCB
sesuai dan adaptor pengaturan kapasitas sesuai
terhubung.
U0 - 02 Kekurangan Refrigeran - unit Outdoor (Faktor 0) Kesalahan ini akibat dari kekurangan refrigeran. Lihat
Diagram alir pemecahan masalah “U0” dan lakukan
Diagnosis dan kemudian ambil tindakan pencegahan.
U0 - 03 Kekurangan Refrigeran - unit Outdoor (Faktor 1) Kesalahan ini akibat dari kekurangan refrigeran yang
disebabkan oleh kebocoran gas. Isi refrigeran hingga
jumlah refrigeran normal.
U0 - 04 Kekurangan Refrigeran - unit Outdoor (Faktor 2) Kesalahan ini akibat dari penyumbatan yang disebabkan sesuatu dalam
sistem pemipaan refrigeran. Periksa kegagalan untuk membuka katup
penghenti dan penyumbatan dalam sistem refrigeran.

Catatan: 1. IGBT: IGBT adalah perangkat semikonduktor daya terutama digunakan sebagai saklar
elektronik.
2. SP: Single Pulse (Pulsa tunggal)
3. MP: Multi Pulse (Beberapa pulsa)

85 Diagnosis Servis
Pemecahan masalah dengan Remote Kontrol SiMT281515E

Pemecahan masalah
kode kesalahan
Deskripsi kesalahan Deskripsi diagnosis
U2 - 01 Kesalahan tegangan catu daya Kesalahan ini seharusnya akibat dari tegangan catu daya
kurang atau berlebih, atau sensor tegangan di PCB rusak

U2 - 02 Fasa catu daya terbuka Periksa setiap fasa catu daya terbuka.
U2 - 03 Kesalahan muatan kapasitor sirkuit utama Ada arus sirkuit yang tidak normal mengalir di PCB. Jika
sambungan kabel terkait dengan PCB normal, ganti PCB
unit outdoor.
U2 - 04 Kesalahan tegangan berlebih SP/MP - PAM Ada kesalahan tegangan berlebih (fasa tunggal). Jika
sambungan kabel terkait dengan PCB normal, ganti PCB
unit outdoor.
UA - 01 Nomor unit indoor yang terhubung tidak sesuai Kesalahan ini akan ditampilkan jika jumlah unit indoor
yang diatur secara lokal berbeda dari jumlah unit indoor yang terdeteksi.
UA - 02 Beberapa unit induk terdeteksi Ada sejumlah unit indoor dengan remote kontrol yang
terhubung.
Hubungkan remote kontrol hanya ke salah satu unit indoor.
UA - 03 Unit indoor yang terhubung berlebih Kesalahan ini akan ditampilkan jika lima atau lebih unit
indoor terhubung.
UA - 05 Kesalahan transmisi Indoor-Outdoor antara Ada kesalahan dalam transmisi antara unit outdoor dan unit
slave 1 dan unit outdoor indoor slave 1. Periksa sambungan jumper antara unit
indoor slave (dengan tanpa remote kontrol yang terhubung)
dan unit outdoor.
UA - 07 Kesalahan transmisi Indoor-Outdoor antara Ada kesalahan dalam transmisi antara unit outdoor dan unit
slave 2 dan unit outdoor indoor slave 2. Periksa sambungan jumper antara unit
indoor slave (dengan tanpa remote kontrol yang terhubung)
dan unit outdoor.
UA - 09 Kesalahan transmisi Indoor-Outdoor antara Ada kesalahan dalam transmisi antara unit outdoor dan unit
slave 3 dan unit outdoor indoor slave 3. Periksa sambungan jumper antara unit
indoor slave (dengan tanpa remote kontrol yang terhubung)
dan unit outdoor.
UF - 01 Pengkabelan tidak sesuai Ada kesalahan dalam sambungan kabel untuk transmisi
antara unit indoor dan outdoor (dinilai dengan unit indoor).
periksa sambungan jumper 1, 2, dan 3 antara unit indoor
dan outdoor.
UF - 02 Pemipaan terhubung sebaliknya Ada kesalahan dalam mode operasi dan suhu deteksi
pemipaan refrigeran. Periksa pipa refrigeran yang
terhubung sebaliknya, kekurangan refrigerant, dll.

Diagnosis Servis 86
SiMT281515E Pemecahan masalah dengan Remote Kontrol

4.5 Gambaran Umum Perangkat Keselamatan Outdoor


Saklar tekanan tinggi
Model Sekring
Terbuka Tertutup

RZR-LUY1(4) +0 3.0 ± 0.15 MPa A1P


4.0 MPa
– 0.15 6.3 A / 250 V (F1U, F2U, F3U, F4U)
31.5 A / 500 V (F5U, F6U)
A2P
5.0 A / 250 V (F1U)

4.6 Gambaran Umum Perangkat Keselamatan Indoor


Model Sekring PCB Motor kipas Sekring PCB (pengerak kipas)
Sekring Termal
3.15 A / 250 V (F1U)
FBQ-E 6.3 A / 250 V (F4U) Tidak tersedia 5.0 A / 250 V (F2U)

87 Diagnosis Servis
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E

5. Pemecahan masalah dengan Indikasi pada


Remote Kontrol
5.1 Ketidaknormalan PCB Unit Indoor
Kode Kesalahan A1
Model yang Semua model indoor
berlaku

Metode Deteksi Periksa data dari E²PROM.


Kesalahan

Kondisi Kesalahan yang dihasilkan ketika data dari E²PROM tidak diterima dengan benar.
putusan
kesalahan E²PROM (Electrically Erasable Programmable Read Only Memory): Sebuah chip memori
yang menyimpan konten tanpa daya. Memori dapat dihapus, baik di dalam komputer
atau di luar dan biasanya membutuhkan lebih banyak tegangan untuk penghapusan dari
tegangan +5 volt yang umum digunakan dalam rangkaian logika. E²PROM berfungsi
seperti RAM yang tidak mudah hilang, tetapi untuk menulis ke E²PROM lebih lambat
daripada menulis ke RAM.

Penyebab  PCB unit indoor rusak


seharusnya  Faktor Eksternal (Kebisingan, dll)

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Matikan daya dan hidupkan lagi untuk


memulai ulang.

Tidak
diatur ulang normal? Ganti PCB unit indoor.
YA

Kesalahan dapat disebabkan


oleh faktor eksternal, bukan
bagian yang rusak.
Cari penyebabnya dan
perbaiki situasinya.

Diagnosis Servis 88
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol

5.2 Ketidaknormalan Sistem Permukaan Air Saluran


Kode Kesalahan A3
Model yang Semua model indoor
berlaku

Metode deteksi Dengan deteksi saklar apung OFF


kesalahan

Kondisi Kesalahan dihasilkan ketika permukaan air mencapai batas atas dan ketika saklar apung OFF
putusan
kesalahan

Penyebab  Pompa saluran rusak


seharusnya  Pekerjaan pipa saluran tidak tepat
 Penyumbatan pipa saluran
 Saklar apung rusak
 PCB Unit indoor rusak
 Konektor korsleting X15A rusak

89 Diagnosis Servis
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

TIDAK Apakah konektor hubung TIDAK


Apakah mekanisme pompa singkat terhubung ke PCB
saluran terhubung? Sambungan konektor
unit indoor? hubung pendek

YA YA

Periksa kontinuitas
konektor hubung TIDAK
Ganti konektor hubung
singkat. Apakah ada
kontinuitas?
pendek.
YA
Ganti PCB unit indoor.

Apakah pompa saluran TIDAK


terhubung ke PCB unit indoor? Hubungkan pompa saluran.

YA

Apakah pompa saluran


YA Apakah ketidaknormalan YA
bekerja setelah memulai
permukaan air saluran tinggi?
Keridaknormalan sistem saluran
ulang operasi?

TIDAK TIDAK

A pak ah s akl ar apung terhubung TIDAK


ke P CB unit indoor?
Hubungkan saklar apung.

YA

Lepas saklar apung dan hubung


singkat, kemudian mulai ulang operasi.

Atur ke “emergency” dan periksa


tegangan konektor dimana
pompa saluran terhubung.
Kesalahan TIDAK
ditampilkan lagi Ganti saklar apung.

YA
Ganti PCB unit indoor.

YA Ganti pompa saluran.


220 (±10%) VAC?
TIDAK

Ganti PCB unit indoor.

Diagnosis Servis 90
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol

5.3 Kunci Motor Kipas Unit Indoor


Kode Kesalahan A6
Model yang Semua model indoor
berlaku

Metode Deteksi Kesalahan dalam putaran kipas terdeteksi oleh sinyal dari motor kipas.
Kesalahan

Kondisi Kesalahan dihasilkan ketika rotasi kipas tidak meningkat.


Putusan
Kesalahan

Penyebab  Kipas tidak berputar karena tersumbat benda asing.


seharusnya  Sambungan harness motor kipas putus, korsleting atau longar
 Sambungan konektor antara PCB unit indoor dan PCB kipas longgar
 Kunci motor kipas (faktor eksternal atau terkait motor)
 Motor kipas rusak (kegagalan pemutusan atau isolasi)
 Kesalahan sinyal dari motor kipas (sirkuit rusak)
 PCB unit indoor rusak

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Matikan catu daya dan tunggu


selama 10 menit.

Apakah ada benda YA


asing di sekitar kipas? Hilangkan benda asing tersebut.

TIDAK

Apakah konektor kipas


terhubung ke PCB unit TIDAK
hubungkan dengan benar.
indoor dengan benar?

YA

Apakah kipas dapat diputar dengan


mudah menggunakan tangan setelah
melepaskan konektor motor kipas TIDAK
Ganti motor kipas.
dari PCB unit indoor?

YA

Periksa CHECK 4 untuk


konektor motor kipas

Apakah setiap hambatan antara


pin sama dengan atau lebih TIDAK
Ganti PCB unit indoor.
tinggi dari standar nilai?

YA
Ganti motor kipas.

CHECK 4 Lihat Halaman 143.


91 Diagnosis Servis
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E

5.4 Ketidaknormalan Motor Kipas Unit Indoor


Kode Kesalahan A6
Model yang Semua model indoor
berlaku

Metode Deteksi  Dideteksi dengan nilai arus yang mengalir melalui PCB kipas
Kesalahan  Dideteksi dengan rotasi kipas saat motor kipas diindikasikan berputar
 Dideteksi dengan sinyal lokasi dari motor kipas
 Dideteksi dengan nilai arus yang mengalir melalui PCB kipas saat motor kipas dijalankan

Kondisi  Jika aliran arus berlebih.


Putusan  Jika rotasi kipas tetap kurang dari jumlah tertentu selama enam detik.
Kesalahan  Kesalahan lokasi rotor kipas terus berlanjut selama 5 detik atau lebih.

Penyebab  Tersumbat benda asing


seharusnya  Pemutusan konektor motor kipas
 Pemutusan konektor antara PCB unit indoor dan PCB kipas
 PCB kipas rusak
 Motor kipas rusak

Diagnosis Servis 92
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Matikan catu daya dan tunggu


selama 10 menit.

Ada benda asing YA


disekitar kipas. Hilangkan benda asing tersebut.

TIDAK

Konektor motor kipas terputus YA


dari PCB kipas. Hubungkan konektor dengan benar.

TIDAK

The antara
Konektor connector
PCB
between
unit indoorthe
danindoor
PCB unit YA
PCB
kipasand
tidakthe fan PCB is
terhubung
Hubungkan konektor dengan benar.
disconnected.

Tidak ada kontinuitas di YA


sekring pada PCB kipas.
Ganti PCB kipas.

TIDAK
Nyalakan catu daya selama konektor
motor kipas tidak terhubung.

Lampu HAP pada


PCB(A1P) unit indoor
berkedip sementara lampu YA
HAP pada PCB (A2P) kipas
tidak berkedip.

TIDAK
Matikan catu daya dan tunggu Matikan catu daya dan tunggu
selama 10 menit. selama 10 menit.

Periksa CHECK 4 untuk


konektor motor kipas

Setiap hambatan antara pin YA


YES
sama dengan atau lebih Ganti motor kipas.
rendah dari 1.
Ganti PCB kipas.
TIDAK
Ganti PCB kipas.

Jika ketidaknormalan "A6"
masih terjadi lagi.
Ganti motor kipas.

Ganti motor kipas.

CHECK 4 Lihat Halaman 143.

93 Diagnosis Servis
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E

5.5 Ketidaknormalan PCB Kipas


Kode Kesalahan A8
Model yang Semua model indoor
berlaku

Metode Deteksi Mikro-komputer memeriksa kondisi tegangan PCB kipas.


Kesalahan

Kondisi Ketika tegangan berlebih atau penurunan tegangan terdeteksi pada PCB kipas.
Putusan
Kesalahan

Penyebab  Sambungan konektor catu daya rusak


seharusnya  PCB unit indoor rusak
 PCB kipas rusak
 Faktor eksternal seperti kebisingan

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Apakah konektor X3A TIDAK


pada PCB unit indoor
terhubung dengan Hubungkan dengan benar.
benar?

YA

Apakah konektor X70A TIDAK


pada PCB kipas
terhubung dengan Hubungkan dengan benar.
benar?

YA

Apakah sambungan
harness X3A dan YA
X70A tidak Ganti harness.
terhubung?

TIDAK

Apakah ada faktor YA


eksternal seperti Hilangkan faktor eksternal.
kebisingan?

TIDAK
Matikan catu daya dan kemudian
nyalakan lagi.

Masukan unit ke dalam operasi
dengan remote kontrol.

Kesalahan
ditampilkan lagi. TIDAK Normal.

YA
Periksa PCB unit indoor dan
PCB kipas.

Diagnosis Servis 94
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol

5.6 Ketidaknormalan Sistem Saluran


Kode Kesalahan AF
Model yang Semua model indoor
berlaku

Metode Deteksi Kebocoran air terdeteksi berdasarkan operasi saklar ON/OFF apung selama kompresor tidak
Kesalahan beroperasi.

Kondisi Saklar apung berubah dari ON ke OFF selama kompresor OFF.


Putusan
Kesalahan

Penyebab  Kesalahan instalasi pipa saluran


seharusnya  Saklar apung rusak
 PCB unit indoor rusak
 Sambungan konektor rusak
 Pompa saluran rusak

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar listrik sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Saklar apung

Apakah saklar apung dan pipa TIDAK


saluran normal?
Kemungkinan kegagalan saklar
apung. Periksa untuk melihat
apakah ketinggian saluran atas
YA
dan panjang pipa horizontal
melebihi spesifikasi.
Apakah sistem TIDAK
pembuangan air normal?
Sistem pembuangan air saluran
tersumbat. Pompa saluran
YA
tersumbat. Saklar apung rusak.

Ganti PCB unit indoor. Periksa


untuk melihat apakah ketinggian
Pompa saluran saluran atas dan panjang pipa
horizontal melebihi spesifikasi.

Apakah pompa TIDAK


saluran Periksa konektor X15A
terpasang?
jumper.
YA

Apakah pompa TIDAK


saluran Periksa Pompa saluran dan pipa
normal? saluran.
YA

Apakah jumlah air


saluran beredar terlalu YA
banyak setelah operasi
penghentian pompa?
Periksa sistem pembuangan.
Periksa untuk melihat apakah
ketinggian saluran atas dan
TIDAK
panjang pipa horizontal melebihi
spesifikasi.
Apakah aliran air saluran YA
ke belakang selama tidak Pengatur dalam sistem
ada operasi?
pembuangan air tidak normal
TIDAK
Ganti PCB unit indoor.

95 Diagnosis Servis
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E

5.7 Ketidaknormalan Pengaturan Kapasitas


Kode Kesalahan AJ
Model yang Semua model indoor
berlaku

Metode Deteksi Kapasitas ditentukan sesuai dengan hambatan adaptor pengaturan kapasitas dan memori
Kesalahan dalam memori IC pada PCB unit indoor, dan apakah nilai normal atau tidak normal ditentukan.

Kondisi Ketika kode kapasitas tidak disimpan ke PCB, dan adaptor pengaturan kapasitas tidak
Putusan tersambung.
Kesalahan Ketika kapasitas tersebut tidak ada untuk itu unit ditetapkan.

Penyebab  Sambungan adaptor pengaturan kapasitas rusak


seharusnya  PCB unit indoor rusak

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

TIDAK
PCB unit indoor
diganti dengan PCB Ganti PCB unit indoor.
alternatif.

YA

Adaptor
pengaturan TIDAK
kapasitas harus Ganti PCB unit indoor.
terpasang saat
mengganti
PCB.
YA
Pasang adaptor pengaturan
kapasitas.

Diagnosis Servis 96
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol

5.7 Kesalahan Transmisi (antara PCB Unit Indoor dan PCB


Kipas)
Kode Kesalahan C1
Model yang Semua model indoor
berlaku

Metode Deteksi Periksa kondisi transmisi antara PCB (A1P) Unit indoor dan PCB (A2P) kipas dengan
Kesalahan menggunakan mikro-komputer.

Kondisi Jika transmisi normal tidak dilakukan selama jangka waktu tertentu.
Putusan
Kesalahan

Penyebab  Sambungan konektor antara PCB (A1P) unit indoor dan PCB (A2P) kipas rusak
seharusnya  PCB (A1P) indoor unit rusak
 PCB (A2P) kipas rusak
 Faktor eksternal, seperti pemadaman sementara

97 Diagnosis Servis
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E

Pemecahan masalah

Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut


konektor, atau bagian dapat rusak.
Perhatian

Apakah konektor
antara PCB (A1P) unit TIDAK
indoor dan PCB (A2P) Hubungkan konektor secara akurat.
kipas secara akurat
terhubung? (1)

YA

Konfirmasi kondisi transmisi


pada PCB unit indoor
menggunakan Mode
pengaturan bidang. (2)

Dalam mode TIDAK


pengaturan bidang
Ganti PCB (A1P) unit indoor.
di atas, No. kode
kedua adalah "01".

YA

Hubungkan konektor X70A


dan nyalakan daya lagi.

Kesalahan YA
Ganti PCB (A2P) kipas.
ditampilkan lagi.

TIDAK
Hubungkan dan lanjutkan operasi
tersebut (Hal ini dimungkinkan
memiliki penyebab, seperti
pemadaman sesaat).

Catatan: 1. Tarik keluar dan masukkan konektor sekali dan pastikan benar-benar terhubung.
2. Metode untuk memeriksa bagian transmisi PCB unit indoor.
Matikan daya dan lepas konektor X70A dari PCB (A1P) unit indoor
Hubung singkat X70A.
Setelah menghidupkan daya, periksa angka di bawah ini berdasarkan pengaturan
bidang dari remote kontrol. (Konfirmasi: No. kode kedua saat kondisi No. kode pertama
21 pada No. mode 41)

Penentuan 01: Normal
Selain 01: Kesalahan transmisi pada PCB unit indoor

 Setelah konfirmasi, matikan daya, lepaskan hubung singkat dan hubungkan X70A
kembali ke kondisi aslinya.

Diagnosis Servis 98
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol

5.9 Kesalahan transmisi (antara PCB Unit Indoor dan PCB


Kipas)
Kode Kesalahan C1-01
Model yang Semua model indoor
berlaku

Metode Deteksi Periksa kondisi transmisi antara PCB unit indoor dan PCB kipas dengan menggunakan mikro-
Kesalahan komputer.

Kondisi Kesalahan diputuskan ketika transmisi antara PCB unit indoor dan PCB kipas telah hilang
Putusan selama 15 detik dan kode kesalahan akan ditampilkan pada remote kontrol 60 detik
Kesalahan kemudian.

Penyebab  Sambungan konektor transmisi antara PCB unit indoor dan PCB kipas rusak
seharusnya  PCB unit indoor rusak
 PCB kipas rusak
 Faktor eksternal seperti kebisingan

99 Diagnosis Servis
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E

Pemecahan masalah

Perhatian astikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Apakah konektor X70A TIDAK


pada PCB unit indoor
terhubung dengan Hubungkan dengan benar.
benar?

YA

Apakah konektor X3A TIDAK


pada PCB kipas Hubungkan dengan benar.
terhubung dengan
benar?

YA

Apakah konektor X10A


pada PCB kipas YA
terhubung dengan Hubungkan dengan benar.
benar?

TIDAK

Apakah YA
harness tidak terhubung? Ganti harness.

TIDAK

Apakah ada YA
faktor eksternal seperti Hilangkan faktor eksternal.
kebisingan selain
kegagalan?
TIDAK
Matikan catu daya dan kemudian
hidupkan lagi.

Masukan unit ke dalam operasi
dengan remote kontrol.

TIDAK
Kesalahan
ditampilkan lagi. Normal.

YA
Periksa PCB unit indoor dan
PCB kipas.

Service Diagnosis 100


SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol

5.10 Ketidaknormalan Termistor


Kode Kesalahan C4, C5, C9
Model yang Semua model indoor
berlaku

Metode Deteksi Kesalahan dideteksi dengan suhu yang terdeteksi oleh termistor.
Kesalahan

Kondisi Ketika termistor menjadi terputus atau korsleting saat unit sedang berjalan.
Putusan
Kesalahan

Penyebab  Sambungan konektor rusak


seharusnya  Termistor rusak
 PCB unit indoor rusak
 Kabel putus atau tidak tersambung

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Periksa sambungan konektor.

TIDAK
Apakah tersambung dengan benar? Perbaiki sambungan.
YA

Periksa hambatan termistor.

CHECK 1 TIDAK
apakah normal? Ganti Termistor yang
YA rusak.

Periksa kontak antara termistor dan


PCB.

TIDAK
apakah kontak OK? Perbaiki kontak.
YA

Ganti PCB unit outdoor.

C4: Termistor (R2T) pipa cair penukar panas Indoor


C5: Termistor (R3T) penukar panas Indoor
C9: Termistor (R1T) udara hisap

CHECK 1 Lihat Halaman 139, 140.

101 Service Diagnosis


Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E

5.11 Kesalahan kombinasi antara PCB Unit Indoor dan


PCB Kipas
Kode Kesalahan C6
Model yang Semua model indoor
berlaku

Metode Deteksi Melakukan deteksi jalur terbuka dengan PCB kipas dengan menggunakan PCB (A1P)
Kesalahan unit indoor.

Kondisi Ketika data komunikasi PCB kipas ditentukan sebagai data yang salah.
Putusan
Kesalahan

Penyebab  PCB kipas rusak


seharusnya  Sambungan adaptor pengaturan kapasitas rusak
 Pengaturan bidang rusak

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Apakah tipe PCB TIDAK


(A2P) kipas benar? (1)
Ganti dengan PCB (A2P) kipas
yang benar.

YA

Apakah PCB (A1P) unit


TIDAK
indoor diganti dengan Setelah membangun transmisi
PCB alternatif? untuk indoor dan outdoor,
lakukan diagnosis operasi sekali
YA lagi.

Apakah adaptor pengaturan


kapasitas yang benar
terpasang saat TIDAK
menempatkannya dengan
PCB alternatif? Pasang adaptor pengaturan
kapasitas yang benar.
YA

Setelah membangun transmisi


untuk indoor dan outdoor,
lakukan diagnosis operasi sekali
lagi.
Catatan: 1. Tipe PCB kipas.
Model yang berlaku Tipe PCB kipas
FBQ60/71EVE(4) PC14006-13(A)
FBQ100/125/140EVE(4) PC14006-14(A)

Service Diagnosis 102


SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol

5.12 Ketidaknormalan Termistor Remote Kontrol


Kode Kesalahan CJ
Model yang Semua model indoor
berlaku

Metode Deteksi Bahkan kesalahan dideteksi, sistem ini tersedia untuk operasi melalui sensor suhu hisap
Kesalahan indoor.
Kesalahan dideteksi pada suhu yang terdeteksi oleh sensor suhu udara dari remote kontrol.
¥ sistem terus beroperasi sementara kode kesalahan ditampilkan.

Kondisi Ketika termistor suhu udara remote kontrol tidak terhubung atau terputus aliran dalam
Putusan operasi.
Kesalahan

Penyebab  Termistor remote kontrol rusak


seharusnya  PCB remote kontrol rusak
 Faktor eksternal seperti kebisingan

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Hapus riwayat kode kesalahan


remote kontrol (1).

YA
Kesalahan ditampilkan lagi. Ganti remote kontrol.

TIDAK

Faktor eksternal seperti


kebisingan yang diduga.

Catatan: 1. Riwayat kode kesalahan dihapus dengan menekan dan menahan tombol On / Off
selama lima detik atau lebih di mode Pemeliharaan remote kontrol.

103 Service Diagnosis


Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E

5.13 Ketidaknormalan PCB Unit Outdoor


Kode Kesalahan E1
Model yang RZR
berlaku

Metode Deteksi Mikro-komputer memeriksa apakah E2PROM normal.


Kesalahan

Kondisi Ketika kesalahan E2PROM saat menghidupkan catu daya


Putusan
Kesalahan

Penyebab  PCB unit outdoor rusak


seharusnya  Motor kipas rusak
 Faktor eksternal (Kebisingan, dll.)

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Matikan catu daya sekali dan


kemudian hidupkan ulang

Apakah pengaturan YA
ulang memungkinkan? Masalah dapat disebabkan oleh
faktor eksternal (kebisingan, dll.)
TIDAK selain kesalahan.

Matikan catu daya, lepas konektor


motor kipas dan kemudian hidupkan
catu daya lagi.

YA
Kesalahan ditampilkan lagi. Ganti PCB (A1P) unit
outdoor.

TIDAK

Periksa motor kipas.

Service Diagnosis 104


SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol

5.14 Ketidaknormalan Tekanan Tinggi (Dideteksi


dengan saklar Tekanan Tinggi)
Kode Kesalahan E3
Model yang RZR
berlaku

Metode Dteksi Sirkuit perangkat perlindungan memeriksa kontinuitas dalam saklar tekanan tinggi.
Kesalahan

Kondisi Saklar tekanan tinggi digerakkan pada 4,0 MPa.


Putusan
Kesalahan

Penyebab  Saklar tekanan tinggi rusak


seharusnya  Pemutusan dalam harness saklar tekanan tinggi
 Sambungan konektor saklar tekanan tinggi rusak
 Penukar panas unit outdoor kotor
 Motor kipas unit outdoor rusak
 Kelebihan isi refrigeran
 Katup penghenti tidak terbuka
 PCB unit outdoor rusak

Pengaturan Tabel di bawah ini berisi nilai saklar tekanan tinggi


Saklar Tekanan Model Saklar tekanan tinggi
Tinggi
Terbuka Tertutup
RZR +0
4.0 MPa 3.0 ± 0.15 MPa
–0.15

105 Service Diagnosis


Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Periksa kondisi instalasi.

TIDAK
Apakah katup Buka katup penghenti.
penghenti terbuka?
YA

Apakah kontrol dan


perlindungan saklar tekanan TIDAK
tinggi terhubung ke Hubungkan dengan benar.
PCB Unit outdoor?

YA

Matikan catu daya. Tunggu 10 menit


setelah kompresor berhenti beroperasi,
kemudian periksa hal-hal berikut

Apakah ada kontinuitas


dalam kontrol dan TIDAK
perlindungan saklar tekanan Ganti saklar tekanan tinggi
tinggi? dengan tanpa kontinuitas.
YA

CHECK 2
YA
Apakah ketidaknormalan
Perbaiki tekanan tinggi tersebut.
tekanan tinggi tinggi?

TIDAK

Atur remote kontrol dan hidupkan


lagi.

Apakah kode YA
“H3” ditampilkan? Ganti saklar tekanan
tinggi.
TIDAK

Ganti PCB (A1P) unit


outdoor.

CHECK 2 Lihat halaman 141.

Service Diagnosis 106


SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol

5.15 Kunci Motor Kompresor


Kode Kesalahan E5
Model yang RZR
berlaku

Metode deteksi Mendeteksi kunci motor saat kompresor dinyalakan.


Kesalahan

Kondisi Jika rotor motor tidak berotasi saat kompresor dinyalakan.


Putusan
Kesalahan

Penyebab  Kunci kompresor


Seharusnya  Awal tekanan diferensial tinggi (2,6 MPa atau lebih)
 Pengkabelan UVW tidak benar
 PCB unit outdoor rusak
 Katup penghenti tidak terbuka

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Periksa kondisi instalasi.

TIDAK
Apakah katup Buka katup penghenti.
penghenti terbuka?
YA

Apakah TIDAK
pengkabelan Hubungkan pengkabelan dengan benar.
UVW normal?
YA

Apakah tekanan YA
lebih tinggi dari 2.6 Perbaiki penyebabnya.
MPa pada
permulaan?
TIDAK

Periksa dan lihat


apakah kompresor YA
Ganti kompresor.
dihubung singkat atau
dilakukan pembumian.

TIDAK

Apakah tekanan rendah


atau tinggi berbeda meski
sesaat saat menyalakan YA
Ganti PCB unit outdoor.
ulang kompresor?

TIDAK
Ganti kompresor.

107 Service Diagnosis


Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E

5.16 Ketidaknormalan Motor Kipas Unit Outdoor


Kode Kesalahan E7
Model yang RZR
berlaku

Metode Deteksi Ketidaknormalan sistem motor kipas dideteksi sesuai dengan kecepatan kipas yang dideteksi
Kesalahan oleh IC Hall ketika motor kipas berjalan.

Kondisi  Ketika kipas berjalan dengan kecepatan kurang dari salah satu yang ditentukan selama 15
Putusan detik atau lebih saat kondisi perjalanan motor kipas terpenuhi
Kesalahan  Ketika konektor pendeteksian kecepatan kipas tidak terhubung
 Ketika kesalahan dihasilkan 4 kali, sistem dimatikan.

Penyebab  Motor kipas rusak


Seharusnya  Konektor harness antara motor kipas dan PCB yang tersisa, konektornya terputus
atau rusak
 Kipas tidak berjalan karena benda asing tersangkut
 PCB unit outdoor rusak
 Ledakan sekring
 Faktor eksternal (Kebisingan, dll.)

Service Diagnosis 108


SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Apakah konektor
motor kipas terhubung TIDAK
dengan benar ke PCB Hubungkan dengan benar konektor tersebut.
unit outdoor?

YA

Apakah ada TIDAK


benda asing disekitar Hilangkan benda asing tersebut.
kipas?
YA

Lepas konektor motor kipas.

Apakah kipas dapat TIDAK


berputar dengan mudah Ganti motor kipas.
saat diputar dengan tangan?
YA
Periksa CHECK 4 untuk konektor
motor kipas.

Apakah nilai hambatan


motor kipas normal? TIDAK
Ganti motor kipas.

YA

Apakah sekring TIDAK


dengan kontinuitas?
Ganti sekring.

YA
Colokkan konektor motor kipas dengan
benar dan kemudian hidupkan Daya lagi

YA
Kesalahan ditampilkan lagi. Ganti PCB(A2P) unit outdoor.
TIDAK

Tidak ada masalah dengan unit.


Faktor eksternal (kebisingan,
dll) selain kegagalan unit
mungkin menjadi penyebab
kesalahan tersebut.
CHECK 4 Lihat Halaman
143.

109 Service Diagnosis


Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E

5.17 ketidaknormalan Katup Ekspansi elektronik


Kode Kesalahan E9
Model yang RZR
berlaku

Metode Deteksi  Mendeteksi kesalahan berdasarkan pemeriksaan kontinuitas dari katup ekspansi elektronik.
Kesalahan  Mendeteksi kesalahan dengan derajat super panas pipa hisap, derajat super panas pipa
pembuangan dan derajat bukaan katup ekspansi elektronik.

Kondisi  Tidak ada catu daya umum ketika daya diaktifkan


Putusan  Ketika kondisi berikut ditetapkan
Kesalahan Derajat super panas pipa hisap  4°C derajat
super panas pipa pembuangan  5°C
Derajat bukaan katup ekspansi elektronik  derajat bukaan Minimum

Penyebab  Katup ekspansi elektronik rusak


Seharusnya  Katup solenoid rusak
 Pemutusan harness katup ekspansi elektronik
 Sambungan konektor katup ekspansi elektronik rusak
 Setiap termistor rusak
 Setiap bantalan termistor rusak
 Sensor tekanan rusak
 PCB unit outdoor rusak
 Operasi basah

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Matikan catu daya sekali dan


kemudian hidupkan lagi.

TIDAK Apakah kode


kesalahan "E9"
terulang?
YA

Apakah konektor katup


ekspansi elektronik TIDAK
terhubung dengan benar Hubungkan dengan benar.
ke PCB unit outdoor?
(X21A)
YA

Apakah hambatan
kumparan katup ekspansi
TIDAK
elektronik normal? Ganti kumparan katup ekspansi elektronik.
CHECK 11

YA

Service Diagnosis 110


SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol

Apakah masing-masing termistor


(pipa hisap, pipa pembuangan,
penukar panas sedang, dan TIDAK
termistor pipa cair) terpasang Pasang termistor dengan benar .
dengan benar?

YA

CHECK 1
TIDAK
Apakah karakteristik masing- Ganti termistor yang tidak normal.
masing termistor normal?

YA

Sebenarnya, berada dalam operasi basah.

Lihat CHECK 8 untuk menghilangkan


penyebab dari operasi basah.

Jalankan ulang operasi.

YA
YES
Kesalahan
Error ditampilkan
is displayed again. PCB (A1P)unit outdoor.
lagi

TIDAK
Diyakini bahwa faktor
(kebisingan, dll,) selain
kegagalan menyebabkan
kesalahan.

CHECK 1 Lihat Hal. 139, 140.

CHECK 8 Lihal Hal. 146.

CHECK 11 Lihat Hal.147.

111 Service Diagnosis


Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E

5.18 Ketidaknormalan Suhu pipa Pembuangan


Kode Kesalahan F3
Model yang RZR
berlaku

Metode Deteksi Ketidaknormalan terdeteksi sesuai dengan suhu yang dideteksi oleh termistor pipa
Kesalahan pembuangan.

Kondisi  Ketika suhu pipa pembuangan naik ke tingkat tinggi yang tidak normal
Putusan  Ketika suhu pipa pembuangan naik tiba-tiba
Keslahan  Ketika suhu pipa pembuangan tidak naik setelah operasi dimulai

Penyebab  Termistor pipa pembuangan rusak


Seharusnya  Sambungan termistor pipa pembuangan rusak
 Jumlah refrigeran tidak memadai
 Kompresor rusak
 Pemutusan termistor pipa pembuangan
 PCB unit outdoor rusak

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Apakah suhu pipa YA


pembuangan tinggi? Ketidaknormalan dalam sistem
(1) refrigeran seperti kekurangan
TIDAK refrigeran, kompresor rusak, dll
Lakukan inspeksi.
Apakah termistor pipa
pembuangan dengan TIDAK
benar terhubung ke PCB Hubungkan dengan benar, dan
(A1P)? operasikan unit lagi.

YA

Apakah termistor pipa


pembuangan dipasang TIDAK
ke pipa pembuangan? Pasang termistor, dan
operasikan unit lagi.
YA

CHECK 1
Apakah karakteristik TIDAK
termistor pipa pembuangan Ganti termistor pipa
normal? pembuangan.

YA
Ganti PCB (A1P) unit outdoor

Catatan:
1. Suhu berbeda tergantung tipe model.
Model Suhu
RZR 115°C

CHECK 1 Lihat Hal. 139, 140.

Service Diagnosis 112


SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol

5.19 Ketidaknormalan Sistem Saklar Tekanan Tinggi


Kode Kesalahan H3
Model yang RZR
berlaku

Metode Deteksi Sirkuit perangkat perlindungan memeriksa kontinuitas dalam saklar tekanan tinggi.
Kesalahan

Kondisi Ketika tidak ada kontinuitas dalam saklar tekanan tinggi selama kompresor berhenti
Putusan beroperasi
Kesalahan

Penyebab  Saklar tekanan tinggi yang tidak lengkap


Seharusnya  Sambungan konektor saklar tekanan tinggi rusak
 PCB unit outdoor rusak
 Kawat Timah tidak terhubung

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Apakah perlindungan
konektor (1) saklar
tekanan tinggi dengan TIDAK
NO
benar terhubung ke PCB Hubungkan dengan benar.
unit outdoor?

YES
YA

Tunggu 10 menit setelah unit berhenti


beroperasi, kemudian periksa hal-hal
berikut.

Apakah ada kontinuitas


di setiap perlindungan TIDAK
NO
saklar tekanan tinggi? Ganti saklar tekanan tinggi
tanpa kontinuitas. Hambatan
dalam operasi normal: 10
YES atau kurang
YA

TIDAK
NO
Apakah ada kontinuitas
dalam kawat timah?
Ganti kawat timah.
in lead wire?
YES
YA

Ganti PCB unit outdoor.

Catatan:
1. Konektor
Model Konektor
RZR X32A (A1P)

113 Service Diagnosis


Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E

5.20 Ketidaknormalan Termistor


Kode Kesalahan H9, J3, J5, J6, J7
Model yang RZR
berlaku

Metode Deteksi Ketidaknormalan terdeteksi sesuai dengan suhu yang dideteksi oleh masing-masing
Kesalahan termistor.

Kondisi Ketika termistor terputus atau korsleting selama operasi


Putusan
Kesalahan

Penyebab  Termistor rusak


Seharusnya  Sambungan konektor rusak
 PCB unit outdoor rusak

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Periksa konektor untuk koneksi. (1)

TIDAK
Normal? Hubungkan konektor dengan benar.
YA

Lepas termistor dari PCB unit


outdoor, kemudian ukur hambatan
dengan menggunakan penguji.

CHECK 1 TIDAK
Ganti termistor yang rusak.
Normal?

YA
Ganti PCB (A1P) unit
outdoor.

Catatan: 1. Konektor termistor


Kode Kesalahan Termistor rusak Termistor Konektor
H9 Termistor udara Outdoor R1T X11A
J3 Termistor pipa pembuangan R2T X12A
J5 Termistor pipa hisap R3T X12A
J6 Termistor pipa cair R4T X12A
J7 Termistor penukar panas R5T X12A
sedang

CHECK 1 Lihat Halaman 139, 140.

Service Diagnosis 114


SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol

5.21 Ketidaknormalan Sensor Tekanan


Kode Kesalahan J1
Model yang RZR
berlaku

Metode Deteksi Kesalahan terdeteksi oleh tekanan yang diukur dengan sensor tekanan
Kesalahan

Kondisi Ketika tekanan terdeteksi sebagai berikut;


Putusan  Tekanan terdeteksi  4.4 MPa sekitar 185 detik
Kesalahan

Penyebab  Sensor tekanan rusak


Seharusnya  PCB unit outdoor rusak
 Sambungan konektor tidak benar

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Periksa apakah konektor untuk sensor


tekanan (X17A) dengan benar
terhubung ke PCB (A1P) unit outdoor

Apakah TIDAK
terhubung
Hubungkan konektor dengan benar.
dengan benar?
YA

Ukur tegangan (V) antara pin (1) dan


(3) konektor di atas CHECK 9 .

Apakah hubungan antara


tekanan dan tegangan TIDAK
normal? Ganti sensor tekanan
CHECK 10 (S1NPH).

YA

Ganti PCB (A1P) unit


outdoor.

CHECK 9 Lihat halaman 147.

CHECK 10 Lihat Halaman 147.

115 Service Diagnosis


Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E

5.22 Ketidaknormalan PCB Unit Outdoor


Kode Kesalahan L1
Model yang RZR
berlaku

Metode Deteksi  Mendeteksi kesalahan dengan nilai arus selama output bentuk gelombang sebelum
Kesalahan pengaktifan kompresor.
 Mendeteksi kesalahan dengan nilai sensor arus selama operasi disinkronkan pada waktu
pengaktifan
 Mendeteksi kesalahan dengan menggunakan sensor tegangan berlebih kapasitor seri MP-
PAM.

Kondisi  Ketika arus berlebih terdeteksi pada saat output bentuk gelombang sebelum
Putusan mengoperasikan kompresor
Kesalahan  Ketika kesalahan sensor arus selama operasi disinkronkan
 Ketika tegangan berlebih terjadi di MP-PAM (1)
 Dalam hal kesalahan IGBT

Penyebab  PCB (A1P) unit outdoor rusak


seharusnya  Kegagalan IPM (2)
 Kegagalan sensor arus
 Kegagalan SP-PAM
 IGBT (3) atau sirkuit pengerak rusak
 Sambungan konektor kompresor rusak
 Motor kipas unit outdoor rusak
 Sekring rusak
 Faktor eksternal (kebisingan, dll.)

Catatan:

1. MP: Multi Pulse (Beberapa pulsa)


2. IPM: IPM adalah perangkat semikonduktor untuk tenaga listrik yang menggabungkan sirkuit
pengerak dan fitur perlindungan diri dari perangkat daya yang mengontrol tenaga listrik.
3. IGBT:IGBT adalah perangkat semikonduktor daya terutama digunakan sebagai saklar
elektronik.

Service Diagnosis 116


SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Matikan catu daya sekali.

Apakah kawat timah


untuk kompresor
terhubung ke TIDAK
PCB dan kompresor
Hubungkan dengan erat dan benar.
tanpa pelepasan
yang layak?
YA

Periksa nilai hambatan untuk motor


kipas.

Apakah nilai hambatan TIDAK


motor kipas normal? Ganti motor kipas.

YA

Apakah sekring TIDAK


memiliki kontinuitas?
Ganti sekring.
Gunakan sekring yang ditentukan saja.
YA

Nyalakan lagi.

YA
Kesalahan ditampilkan lagi. Ganti PCB unit outdoor.

TIDAK

Tidak ada masalah dengan


unit. Faktor eksternal
(kebisingan, dll) selain
kegagalan unit dapat menjadi
penyebabnya.

117 Service Diagnosis


Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E

5.23 Suhu Sirip Radiasi Naik


Kode Kesalahan L4
Model yang RZR
berlaku

Metode deteksi Suhu sirip radiasi terdeteksi oleh termistor sirip radiasi.
kesalahan

Kondisi Ketika suhu sirip radiasi inverter meningkat secara tidak normal karena penyebaran panas
Putusan rusak
Kesalahan

Penyebab  Termistor sirip radiasi rusak


seharusnya  Suhu udara outdoor tinggi
 Pembukaan hisap terhalang
 Sirip radiasi kotor
 PCB unit outdoor rusak
 Aktivasi saklar termal sirip
 Pendinginan sirip radiasi inverter tidak memadai
 Sambungan konektor rusak

Service Diagnosis 118


SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Apakah dianggap bahwa


suhu sirip radiasi tinggi? (1) YA
Hilangkan penyebabnya.

TIDAK

Apakah konektor
termistor sirip radiasi
dengan benar terpasang TIDAK
ke PCB unit outdoor? Hubungkan dengan benar.

YA

Hidupkan catu daya, dan kemudian


tekan tombol periksa remote kontrol
sekali.

Apakah kode kesalahan


YA
"P4" ditampilkan pada Masuk ke diagnosis kesalahan "P4".
remote kontrol?

TIDAK

Apakah
kode kesalahan "L4" YA
terulang ketika Ganti PCB unit outdoor.
operasi awal unit?

TIDAK

Lanjutkan operasi.

Catatan: 1. Nilai deteksi sirip radiasi


Model Deteksi Atur ulang
RZR-LUY1(4) 76°C 66°C

119 Service Diagnosis


Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E

5.24 Arus Lebih Output DC (sesaat)


Kode Kesalahan L5
Model yang RZR
berlaku

Metode Deteksi Kesalahan terdeteksi dengan mengubah arus yang mengalir ke transistor daya menjadi
Kesalahan tegangan dengan CT1 (sensor arus DC).

Kondisi Ketika arus berlebih cukup untuk transistor daya.


Putusan (Digerakkan juga oleh arus berlebih seketika)
Kesalahan

Penyebab  Kumparan kompresor rusak (pemutusan, isolasi buruk)


Seharusnya  Kesalahan pengaktifan kompresor (kunci mekanis)
 PCB unit outdoor rusak
 Fluktuasi tegangan catu daya Sesaat
 Kompresor rusak (Jika bantalan tergores)
 Katup penghenti tidak terbuka

Diagnosis Servis 120


SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.
Periksa kondisi instalasi.

Apakah katup TIDAK


penghenti terbuka? Buka katup penghenti.
YA

Apakah kumparan
kompresor terputus atau YA
apakah isolasi rusak? Ganti kompresor.

TIDAK

Matikan catu daya utama, dan


kemudian putuskan sambungan antara
kompresor dan inverter.

CHECK 5
Periksa kontinuitas di transistor TIDAK
daya (IGBT). Apakah kontinuitas Ganti PCB unit outdoor.
normal? (A2P)

YA

Apakah tegangan output


inverter yang dihasilkan
kira-kira pada kecepatan
kian meningkat yang TIDAK
sama untuk setiap fasa Ganti PCB unit outdoor.
 Ketika mengoperasikan kompresor
setelah menyalakan lagi?
dengan jalur output kompresor yang
(1) (U-V, V-W,
terputus, kompresor berhenti karena
W-U)
kesalahan setelah lewat waktu 5
detik. Oleh karena itu, periksa
YA kenaikan tegangan selama 5 detik.

Periksa tegangan catu daya.

Apakah penurunan YA
Perbaiki catu daya.
tegangan sesaat
dihasilkan?

TIDAK
inspeksi Kompresor. Inspeksi
sesuai dengan prosedur
diagnosis untuk kebisingan,
getaran, status operasi normal, dll
dari kompresor.
Catatan:
1. Nilai perkiraan
Model nilai deteksi arus berlebih sesaat
RZR 32.3A
CHECK 5 Lihat Halaman 143.

121 Diagnosis Servis


Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E

5.25 Termal Elektronik (Jeda Waktu)


Kode Kesalahan L8
Model yang RZR
berlaku

Metode Deteksi Kesalahan terdeteksi dengan mengubah arus yang mengalir ke transistor daya menjadi
Kesalahan tegangan dengan menggunakan CT1 (sensor arus DC).
PCB Inverter mendeteksi gangguan sinyal posisi.

Kondisi Ketika kelebihan beban kompresor (kecuali saat pengaktifan) terdeteksi


Putusan
Kesalahan

Penyebab  Beban lebih kompresor (selama operasi)


Seharusnya  Kumparan kompresor terputus
 Kompresor rusak (jika bantalan tergores)
 PCB unit outdoor rusak

Diagnosis Servis 122


SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Apakah arus sekunder


inverter lebih tinggi dari A YA
Beban lebih kompresor.
(1) untuk setiap fasa? Pemeriksaan sistem
kompresor dan refrigeran
TIDAK diperlukan.

Matikan catu daya utama, dan


kemudian putus sambungan antara
kompresor dan inverter.

CHECK 5
Periksa kontinuitas di TIDAK
transistor daya (IGBT). Ganti PCB unit outdoor. (RZR-
Apakah kontinuitas normal? LUY1 (4): A2P)

YA

Apakah
tegangan output
inverter yang dihasilkan
kurang lebih pada kecepatan TIDAK
peningkatan yang sama pada Ganti PCB unit outdoor. (A2P)
 Ketika mengoperasikan kompresor
setiap fasa setelah menyalakan
dengan jalur output kompresor yang
lagi?
terputus, kompresor berhenti karena
() (U-V, V-W, W- kesalahan setelah waktu berlalu 5
U)
detik. Oleh karena itu, periksa
kenaikan tegangan selama 5 detik.
YA

Pemeriksaan kompresor.
Periksa sesuai dengan
prosedur diagnosis untuk
kebisingan, getaran, status
operasi yang tidak normal, dll
dari kompresor tersebut.
Catatan:
1. Nilai deteksi termal elektronik
Model Nilai Deteksi
RZR 17A × 5 detik atau 12.1A × 260 detik

CHECK 5 Lihat halaman 143.

123 Diagnosis Servis


Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E

5.26 Pencegahan Stall (Jeda waktu)


Kode Kesalahan L9
Model yang RZR
berlaku

Metode Deteksi Kesalahan dideteksi dari arus yang mengalir ke transistor daya menjadi tegangan dengan
Kesalahan menggunakan CT1 (sensor arus DC).
PCB Inverter mendeteksi gangguan sinyal posisi.

Kondisi Ketika beban lebih kompresor dan perubahan beban pada kompresor dideteksi
Putusan
Kesalahan

Penyebab  Katup penghenti tidak terbuka


seharusnya  Pengaktifan diferensial tekanan
 PCB unit outdoor rusak
 Kompresor rusak (dikunci)

Diagnosis Servis 124


SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Periksa kondisi instalasi

TIDAK
Apakah katup Buka katup penghenti.
penghenti terbuka?
YA

Apakah perbedaan antara


tekanan tinggi dan rendah TIDAK
sebelum pengaktifan tidak Pemerataan tekanan tidak
lebih dari 0.2MPa? memadai.
Periksa sistem refrigeran.
YA

Matikan catu daya utama, dan


kemudian putuskan sambungan antara
kompresor dan inverter.

CHECK 5
Periksa kontinuitas di TIDAK
transistor daya (IGBT). Ganti PCB unit outdoor. (A2P)
Apakah kontinuitas normal?

YA

Kompresor dibumikan
Ganti kompresor.
YA
dan diputus aliran
listriknya

TIDAK
Pemeriksaan kompresor.
Periksa sesuai dengan
prosedur diagnosis untuk
kebisingan, getaran, status
operasi yang tidak normal,
dll. dari kompresor tersebut.

CHECK 5 Lihat Halaman 143.

125 Diagnosis Servis


Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E

5.27 Kesalahan Sistem Transmisi antara PCB Unit Outdoor


Kode Kesalahan LC
Model yang RZR
berlaku

Metode Deteksi Memeriksa dan melihat apakah transmisi antara PCB unit outdoor dilakukan dengan
Kesalahan normal.

Kondisi Ketika transmisi tidak dilakukan dalam jangka waktu tertentu atau lebih lama
Putusan
Kesalahan

Penyebab  Pengkabelan transmisi antara PCB unit outdoor tidak benar/kontak dalam pengkabelan tidak
seharusnya memadai
 PCB unit outdoor rusak
 Faktor eksternal (kebisingan, dll.)
 Motor kipas unit outdoor rusak
 Kontak konektor motor kipas rusak

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Apakah konektor motor TIDAK


Sambungkan konektor tersebut,
kipas terhubung?
dan nyalakan lagi.
YA

Putuskan konektor motor kipas, dan


nyalakan lagi.

Apakah “E7” yang


ditampilkan pada remote YA
kontrol? (Apakah “LC” tidak Ganti motor kipas.
ditampilkan?) transmisi inverter yang
gagal berfungsi karena
TIDAK kesalahan motor kipas.

Apakah monitor mikro-


komputer (hijau) pada PCB TIDAK
(A1P) berkedip normal? Ganti PCB (A1P) unit
outdoor.

YA

Apakah monitor
mikro-komputer pada TIDAK
PCB (A2P) berkedip Ganti PCB (A2P) unit
normal? outdoor.
YA

Periksa sambungan konektor


yang rusak di pengkabelan
transmisi dan untuk klem
dengan jalur tegangan tinggi.
Diagnosis Servis 126
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol

5.28 Ketidakseimbangan Tegangan Catu Daya atau Fasa


Terbuka
Kode Kesalahan P1
Model yang RZR
berlaku

Metode Deteksi Kesalahan terdeteksi sesuai dengan bentuk gelombang tegangan dari kapasitor sirkuit utama
Kesalahan yang dibangun di inverter.

Kondisi Ketika bentuk gelombang tegangan tersebut menjadi identik dengan bentuk gelombang fasa
Putusan terbuka catu daya.
Kesalahan

Penyebab  Fasa terbuka


Seharusnya  Ketidakseimbangan tegangan antar fasa
 PCB unit outdoor rusak
  Kapasitor sirkuit utama rusak
  Unit daya (Pemutusan di modul dioda)
  Relai magnetik rusak
  Pengkabelan sirkuit utama tidak benar

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Periksa LED pada PCB unit TIDAK


outdoor (fasa terbuka?) Faktor-faktor lain selain fasa terbuka
unit PCB (Open phase?)

Ya

Fasa tegangan catu YA


Faktor bidang
daya terbuka?

TIDAK

Apakah
ketidakseimbangan YA
Faktor bidang
antar fasa besar?

TIDAK

Ganti PCB unit outdoor.

Catatan:
Target: ±10V antar fasa, R-S, S-T, T-R

127 Diagnosis Servis


Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E

5.29 Ketidaknormalan Termistor Sirip Radiasi


Kode Kesalahan P4
Model yang RZR
berlaku

Metode Deteksi Deteksi dengan sirkuit terbuka atau hubung singkat termistor sirip radiasi selama kompresor
Kesalahan berhenti beroperasi.

Kondisi Ketika sirkuit terbuka atau hubung singkat termistor sirip radiasi dideteksi selama kompresor
Putusan berhenti beroperasi
Kesalahan

Penyebab  Termistor sirip radiasi rusak


Seharusnya  PCB unit outdoor rusak
 Faktor eksternal (kebisingan, dll.)

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Periksa LED pada PCB unit outdoor.

TIDAK
Apakah ada kesalahan Selidiki faktor-faktor selain
termistor sirip radiasi?
kesalahan.

YA

Lepaskan konektor dari (1) pada


PCB, kemudian periksa hambatan
termistor pada suhu normal.

TIDAK
CHECK 1
Normal?
Ganti PCB (A2P) unit
outdoor.
YA

TIDAK
Apakah pengaturan Ganti PCB (A2P) unit
ulang mungkin? outdoor.
YA
YES

Pengaturan ulang

Catatan:
1. Konektor
Model Termistor Konektor PCB
RZR R10T X111A A2P

CHECK 1 Lihat Halaman 139, 140.

Diagnosis Servis 128


SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol

5.30 Ketidaknormalan Pengaturan Kapasitas


Kode Kesalahan PJ
Model yang RZR
berlaku

Metode Deteksi Memeriksa apakah nilai yang ditetapkan ditulis dalam E2PROM (dari pabriknya) atau nilai
Kesalahan adaptor pengaturan kapasitas yang ditetapkan (untuk penggantian) adalah sama dengan
kapasitas unit outdoor.
Kondisi
Putusan Ketika nilai yang ditetapkan pada E2PROM berbeda dari kapasitas unit outdoor atau adaptor
Kesalahan pengaturan kapasitas kecuali untuk PCB model yang berlaku diinstal. (Keputusan Kesalahan
dibuat hanya saat menghidupkan catu daya.)

Penyebab  Nilai E2PROM yang ditetapkan tidak benar


Seharusnya  Adaptor pengaturan kapasitas tidak benar
 PCB unit outdoor rusak

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Apakah adaptor
pengaturan kapasitas TIDAK
terhubung ke PCB unit Sambungkan adaptor untuk model
outdoor? (1) yang berlaku.

YA

Pastikan bahwa kombinasi adaptor


pengaturan kapasitas yang terhubung Jika tidak benar,
benar.
perbaiki
kombinasinya.

Catatan:
1. Adaptor pengaturan kapasitas tidak terhubung dari pabriknya. (Kapasitas ditulis dalam E²PROM.) adaptor
pengaturan kapasitas diperlukan hanya jika PCB digantikan dengan PCB alternatif.

129 Diagnosis Servis


Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E

5.31 Kekurangan Refrigeran


Kode Kesalahan U0
Model yang RZR
berlaku

Metode Deteksi (Dalam operasi normal)


Kesalahan Kekurangan Refrigeran dideteksi sesuai dengan derajat bukaan katup ekspansi elektronik
dan suhu dan tekanan yang diukur.

Kondisi (Dalam Pendinginan)


Putusan Ketika katup ekspansi elektronik terbuka sepenuhnya dan tekanan rendah di bawah 0,25 MPa
Kesalahan terus berlanjut selama 30 menit.

Penyebab  Katup penghenti tidak terbuka


Seharusnya  Jumlah refrigeran tidak memadai
 Sistem perpipaan refrigeran tersumbat

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

TIDAK
Apakah katup penghenti terbuka? Buka katup penghenti.

YA

Apakah jumlah TIDAK


refrigeran sesuai? Angkat refrigeran. Setelah
pengeringan vakum selesai,
YA isi jumlah refrigerant yang
sesuai.
CHECK 3
Periksa sistem perpipaan
refrigeran untuk
penyumbatan.
Catatan:
 Alarm kekurangan refrigeran ditunjukkan tetapi operasi terus
berlanjut.

CHECK 3 Lihat Halaman142.

Diagnosis Servis 130


SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol

5.32 Ketidaknormalan Tegangan Catu Daya


Kode Kesalahan U2
Model yang RZR
berlaku

Metode Deteksi Kesalahan terdeteksi sesuai dengan tegangan kapasitor sirkuit utama yang dibangun pada
Kesalahan tegangan inverter dan catu daya.

Kondisi Ketika tegangan kapasitor sirkuit utama yang dibangun pada tegangan inverter dan catu daya
Putusan turun atau ketika kegagalan daya (listrik padam) beberapa puluh milidetik atau lebih dihasilkan
Kesalahan  Remote kontrol tidak menyimpulkan ketidaknormalan tersebut.

Penyebab  Anjloknya tegangan catu daya


Seharusnya  Kegagalan listrik seketika
 Pengkabelan sirkuit utama rusak
 PCB unit outdoor rusak
 Bagian sirkuit utama rusak

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Periksa LED
pada PCB unit outdoor. (Apakah TIDAK
tegangan tidak memadai?) Faktor-faktor lain

YA

Apakah tegangan catu TIDAK


daya antara 380 ~ Faktor bidang
415V ±10%?

YA
Apakah
pengkabelan benar? TIDAK
Perbaiki pengkabelan.
YA
Ketika kompresor berjalan, ukur
tegangan antara + dan - kapasitor
elektrolit (C+, C-).

Apakah tegangan yang YA


terukur 380 ~ 415V Pantau tegangan tersebut
±10% atau lebih? (penurunan tegangan sesaat)
TIDAK
Ganti PCB (A1P) unit
outdoor.

131 Diagnosis Servis


Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E

5.33 Kesalahan Transmisi Antara Unit Indoor Dan Unit Outdoor


Kode Kesalahan U4
Model yang RZR
berlaku

Pembangkitan Kesalahan dihasilkan ketika mikro-prosesor mendeteksi bahwa transmisi antara unit indoor
kesalahan dan outdoor tidak normal selama waktu tertentu.
Kondisi Ketika transmisi normal tidak dilakukan untuk jangka waktu tertentu atau lebih
Putusan
Kesalahan

Penyebab  Kabel transmisi (pengkabelan indoor-outdoor) tidak benar


Seharusnya  PCB unit indoor rusak
 PCB unit outdoor rusak
 Sekring habis terbakar
 Motor kipas rusak
 Faktor eksternal (kebisingan, dll.)
 Catu daya rusak

Pemecahan masalah
Diagnosis pengkabelan tidak benar atau rusak/terputus. Jika LED pada PCB unit indoor MATI, menunjukkan
bahwa pengkabelan transmisi antara unit indoor dan outdoor mungkin tidak benar atau rusak / terputus.

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Apakah tegangan
catu daya antara 380 TIDAK faktor bidang
- 415V?

YA

Apakah ada tipe


kabel yang salah,
terminal longgar, atau TIDAK
kegagalan kontak di Pasang kabel dengan benar dan aman,
pengkabelan kencangkan sekrup terminal.
transmisi antara unit
indoor dan outdoor?
YA

TIDAK Apakah ada aksesori


opsional (1) yang
terhubung?
YA

Apakah daya untuk


aksesori opsional dipasok
dari antara 1 dan 2 pada TIDAK
blok terminal X1M
Pasang kabel dengan benar.
atau X2M?

YA

Apakah HAP pada PCB unit


outdoor berkedip? (PCB unit YAS
Outdoor) B

TIDAK

Diagnosis Servis 132


SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol

Matikan catu daya dan lepaskan


konektor motor kipas unit outdoor.
Kemudian hidupkan lagi.

Apakah HAP berkedip? YA


( PCB unit Outdoor) Ganti motor kipas unit
outdoor.
TIDAK

Periksa nilai hambatan motor kipas


unit outdoor.

Apakah nilai
hambatan motor kipas TIDAK
unit outdoor normal? Ganti motor kipas unit outdoor.

YA

Apakah sekring TIDAK


memiliki Ganti sekring
kontinuitas?
YA
CHECK 13
Periksa tegangan pulsa kecepatan
kipas unit outdoor.

Apakah tegangan output


TIDAK
normal? Ganti PCB unit outdoor.

YA
Setelah mematikan catu daya, dengan
benar masukkan konektor motor kipas dan
kemudian pulihkan daya.

Apakah kesalahan "U4" YA


B Ganti PCB unit outdoor.
terjadi lagi?

TIDAK
Setelah mematikan catu daya, dengan
benar masukkan konektor motor kipas dan
kemudian pulikan daya.

Apakah kesalahan YA
Ganti PCB unit indoor.
"U4" atau "UF" terjadi
lagi?

TIDAK Tidak ada masalah dengan unit.


Faktor eksternal (kebisingan,
dll) selain kegagalan unit dapat
menjadi penyebabnya.

Catatan:
1. Aksesoris opsional mengacu pada adaptor untuk aksesoris kabel, auto grill dan aksesoris lainnya.

CHECK 13 Lihat Halaman 148.

133 Diagnosis Servis


Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E

5.34 Kesalahan transmisi antara Unit Indoor dan Remote


Kontrol
Kode Kesalahan U5
Model yang Semua model indoor
berlaku

Pembangkitan Kesalahan dihasilkan ketika mikro-prosesor mendeteksi bahwa transmisi antara unit indoor
Kesalahan dan remote kontrol tidak normal selama waktu tertentu.
Penyebab  Remote kontrol rusak
seharusnya  PCB unit indoor rusak
 Faktor eksternal (kebisingan, dll.)
 Koneksi 2 remote kontrol utama (ketika menggunakan 2 remote kontrol).

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Kontrol dengan 2 YA SS1 kedua YA


remote kontrol remote kontrol diatur ke Atur salah satu remote kontrol
MAIN. ke SUB, matikan catu daya
TIDAK TIDAK sementara, kemudian nyalakan
kembali operasi.

Atur ulang seperti


Semua lampu kedip PCB unit biasa ketika catu TIDAK
T IDAK
indoor, daya dimatikan Ganti PCB unit indoor.
mikro-komputer, monitor normal sementara.

YA YA

Kesalahan dapat
dibangkitkan oleh
kebisingan.
Menggunakan kabel Periksa daerah sekitarnya dan
transmisi multi-core YA nyalakan ulang operasi.
antara unit indoor dan
remote kontrol Ubah ke kabel independen dua
inti.
TIDAK

Apakah "U5" TIDAK


ditampilkan
terus-menerus? Kegagalan PCB remote kontrol
YA atau ganti PCB unit indoor yang
rusak.

Masalah dapat disebabkan oleh


faktor eksternal (kebisingan, dll)
selain kesalahan.

Diagnosis Servis 134


SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol

5.35 Kesalahan Transmisi antara Remote Kontrol MAIN


dan Remote Kontrol SUB
Kode Kesalahan U8
Model yang Semua model indoor
berlaku

Kesalahan dihasilkan ketika, dalam kasus mengontrol dengan menggunakan 2 remote


kontrol, mikro prosesor mendeteksi bahwa transmisi antara unit indoor dan remote kontrol
(MAIN dan SUB) tidak normal selama waktu tertentu.
Penyebab  Kesalahan Transmisi antara remote kontrol MAIN dan remote kontrol SUB
seharusnya  Koneksi antara remote kontrol SUB
 PCB remote kontrol rusak.

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Mengontrol dengan TIDAK Saklar SS-1 pada PCB TIDAK


2 remote kontrol remote kontrol diubah ke Ubah saklar SS-1 dari salah
MAIN. satu remote kontrol ke
YA YA MAIN.
Matikan catu daya, dan hidupkan
ulang operasi.
Kedua saklar SS-1 TIDAK Apakah ada kontinuitas di
pada remote kontrol pengkabelan remote YA
Y
diubah ke SUB. kontrol?
Matikan daya sekali dan nyalakan
ulang operasi.
YA Ganti PCB remote kontrol jika
TIDAK ada kesalahan dihasilkan.

Ganti kabel remote kontrol.

Ubah saklar SS-1 dari salah


satu remote kontrol ke MAIN.
Matikan catu daya, dan nyalakan
ulang operasi.

135 Diagnosis Servis


Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E

5.36 Ketidaknormalan Saklar Pengaturan Bidang


Kode Kesalahan UA
Model yang Semua model indoor
berlaku

Pembangkitan Kesalahan dihasilkan ketika pengaturan bidang yang tidak benar telah ditetapkan untuk pair /
Kesalahan twin / triple / double twin.
Penyebab  PCB unit indoor atau outdoor rusak
seharusnya  PCB catu daya rusak
 Pengkabelan transmisi unit Indoor-outdoor, indoor-indoor
 Pengkabelan remote kontrol rusak.

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Apakah remote
kontrol terhubung ke unit YA
Hubungkan remote kontrol
indoor lebih dari 1?
dengan benar.
TIDAK

Apakah pengaturan TIDAK


dari Pair/Twin/Triple Atur ke Pair dengan benar.
diatur dengan benar?

YA

Apakah monitor mikro-


komputer (HAP) dari semua Apakah jumper indoor-
PCB unit indoor berkedip T IDAK indoor dan indoor-outdoor TIDAK
Hubungkan dengan benar.
normal? dengan benar terhubung?

YA YA

Apakah PCB catu TIDAK


daya dengan benar Hubungkan dengan benar.
terhubung?

YA

Matikan daya sekali, kemudian hidupkan


ulang, dan memulai ulang operasi. Apakah VAC 220-240 TIDAK
antara No.1 dan No.3 dari Ganti transformer.
X2M (Unit indoor)?

YA
Pengkabelan bisa salah,
periksa kembali.

TIDAK Apakah jumper indoor- TIDAK


beroperasi secara normal? indoor dan indoor-outdoor Hubungkan dengan benar.
dengan benar terhubung?
YA

YA
Ganti PCB unit indoor.

Beroperasi secara normal.

Diagnosis Servis 136


SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol

5.37 Kesalahan Pengaturan Alamat Terpusat


Kode Kesalahan UC
Model yang Semua model indoor
berlaku

Metode Deteksi Mikro-komputer unit indoor mendeteksi dan menilai sinyal alamat terpusat sesuai dengan
Kesalahan transmisi antara unit indoor.

Kondisi Ketika mikro-komputer menilai sinyal alamat terpusat diduplikasi


Putusan
kesalahan

Penyebab  Pengaturan alamat terpusat rusak


seharusnya  PCB unit indoor rusak

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau kerusakan
bagian dapat terjadi.

Apakah perangkat yang


terkait dengan kontrol YA
terpusat terhubung ke Ubah pengaturan sehingga
unit indoor? alamat terpusat tidak
diduplikasi.

TIDAK

Ganti PCB unit indoor.

137 Diagnosis Servis


Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E

5.38 Kesalahan Transmisi antara Unit Indoor dan Outdoor


/ Perpipaan dan Ketidakcocokan Pengkabelan /
Kekurangan Refrigeran
Kode Kesalahan UF
Model yang RZR
berlaku

Metode Deteksi Memeriksa transmisi antara unit indoor dan outdoor dengan mikro-komputer ketika daya
Kesalahan DIHIDUPKAN.
Mendeteksi dengan memeriksa perbedaan suhu berikut selama operasi kompresor.
A: Perbedaan suhu yang dideteksi oleh termistor (R2T) pipa cair penukar panas indoor
dan termistor (R1T) udara hisap indoor
B: Perbedaan suhu uap (Te) yang dideteksi oleh termistor (R2T) pipa cair penukar panas
indoor dan sensor kompresor

Kondisi Ketika kabel transmisi antara unit indoor dan outdoor tidak benar
Putusan Ketika kondisi berikut terus berlanjut selama 20 menit selama operasi kompresor
kesalahan A: R2T – R1T < 4ºC, dan
B: R2T – Te > 14ºC

Penyebab  Pengkabelan transmisi antara unit indoor dan outdoor rusak


Seharusnya  Ketidakcocokan pengkabelan dan pemipaan
 Kekurangan refrigeran
 Sistem pemipaan refrigeran tersumbat

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.

Apakah "UF" muncul


ketika daya dihidupkan? YA

Tahap pengkabelan transmisi antara


unit indoor dan outdoor tidak benar.
TIDAK
Dengan benar hubungkan
Apakah sambungan kabel kabel transmisi antara unit
dan pipa transmisi antara indoor dan outdoor.
unit indoor dan outdoor TIDAK
cocok? Cocokkan sambungan kabel dan
pipa transmisi antara unit indoor
dan outdoor.
YA

CHECK 6 Isi ulang jumlah refrigeran


Apakah tingkat TIDAK yang sesuai setelah
refrigeran sesuai?
pemulihan refrigeran dan
pengeringan vakum.
YA
CHECK 3
Periksa sistem pemipaan
refrigeran untuk
penyumbatan.

CHECK 3 Lihat halaman 142.

CHECK 6 Lihat halaman 144.

Diagnosis Servis 138


SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol

5.39 Pemeriksaan
CHECK 1 Periksa termistor
Termistor
Jika penyebab masalah adalah terkait dengan termistor, maka termistor harus diperiksa sebelum
mengubah PCB.

Untuk informasi lebih lanjut tentang termistor ini, lihat:


 “Diagram Pengkabelan’’ di Halaman 150
 “Fungsi Komponen Utama dan termistor” di Halaman 25.

Gambaran Umum tentang Termistor


Tabel di bawah ini berisi gambaran umum tentang termistor:
Indoor
FBQ-E Termistor Tabel
(di halaman berikut)
R1T Termistor udara hisap 2
R2T Termistor pipa cair penukar panas Indoor 2
R3T Termistor penukar panas Indoor thermistor 3

Outdoor
Tabel
RZR-LUY1(4) Termistor
(di halaman berikut)
R1T Termistor udara Outdoor 2
R2T Termistor pipa pembuangan 3
R3T Termistor pipa hisap 2
R4T Termistor pipa cair 2
R5T Termistor penukar panas sedang 2
R10T Termistor sirip radiasi 1

Pemeriksaan
Untuk memeriksa termistor, lakukan sebagai berikut:
Langkah Tindakan
1 Lepaskan thermistor dari PCB
2 Baca suhu dan nilai resistor.
3 Periksa apakah nilai yang diukur sesuai dengan nilai-nilai dalam tabel di halaman berikutnya.

139 Diagnosis Servis


Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E

Karakteristik Suhu / Tahanan Termistor

Tabel 1 Tabel 2 Tabel 3


T°C k T°C k T°C k
-30 354.1 -30 361.7719 -30 3257.371
-25 259.7 -25 265.4704 -25 2429.222
-20 192.6 -20 196.9198 -20 1827.883
-15 144.2 -15 147.5687 -15 1387.099
-10 109.1 -10 111.6578 -10 1061.098
-5 83.25 -5 85.2610 -5 817.9329
0 64.10 0 65.6705 0 635.0831
5 49.70 5 50.9947 5 496.5712
10 38.85 10 39.9149 10 391.0070
15 30.61 15 31.4796 15 309.9511
20 24.29 20 25.0060 20 247.2696
25 19.41 25 20.0000 25 198.4674
30 15.61 30 16.1008 30 160.2244
35 12.64 35 13.0426 35 130.0697
40 10.30 40 10.6281 40 106.1517
45 8.439 45 8.7097 45 87.0725
50 6.954 50 7.1764 50 71.7703
55 5.761 55 5.9407 55 59.4735
60 4.797 60 4.9439 60 49.5180
65 4.014 65 4.1352 65 41.4168
70 3.375 70 3.4757 70 34.7923
75 2.851 75 2.9349 75 29.3499
80 2.418 80 2.4894 80 24.8586
85 2.060 85 2.1205 85 21.1360
90 1.762 90 1.8138 90 18.0377
95 1.513 95 1.5575 95 15.4487
100 1.304 100 1.3425 100 13.2768
105 1.128 105 1.1614 105 11.4395
110 0.9790 3SA48001 (AD87A001J) 110 9.8902
115 0.8527 115 8.5788
120 0.7450 120 7.4650
125 0.6530 125 6.5156
130 0.5741 130 5.7038
3PA61998L (AD92A057) 135 5.0073
140 4.4080
145 3.8907
150 3.4429
3SA48006 (AD87A001J)

Diagnosis Servis 140


SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol

CHECK 2 Evaluasi Tekanan Tinggi yang tidak normal


Tidak normalnya tingkat tekanan tinggi sebagian besar terjadi di sisi kondensor. Isi berikut disediakan oleh
insinyur servis berdasarkan pemeriksaan bidang miliknya.

Dalam pendinginan
Periksa item (Kemungkinan penyebab) Penilaian
Apakah kipas unit outdoor berjalan dengan normal? Inspeksi visual
Apakah penukar panas unit outdoor tersumbat? Inspeksi visual
Apakah ada penyumbatan sebelum atau sesudah katup Periksa apakah ada perbedaan suhu sebelum dan
ekspansi elektronik? sesudah katup ekspansi elektronik.
Periksa apakah unit katup utama dari katup ekspansi
elektronik beroperasi
(dengan kebisingan, getaran).
Apakah katup balik tersumbat? Periksa apakah ada perbedaan suhu sebelum dan
sesudah katup balik.
 Jika YA, katup balik terperangkap.
Apakah saklar tekanan tinggi normal? Periksa kontinuitas dengan menggunakan penguji.
Apakah unit outdoor dipasang di bawah kondisi seperti Inspeksi visual
itu sehingga arus pendek mudah terjadi?
Apakah panjang pipa 5 m atau kurang? Inspeksi visual
Apakah udara memasuki sistem refrigeran? Lakukan koleksi refrigeran dan pengeringan vakum,
dan kemudian tambahkan jumlah refrigeran yang tepat.
Apakah refrigeran diisi berlebihan? Lakukan koleksi refrigeran dan pengeringan vakum,
dan kemudian tambahkan jumlah refrigeran yang tepat.

141 Diagnosis Servis


Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E

CHECK 3 Titik tersumbat


Perbedaan suhu dapat terjadi sebelum atau sesudah titik tersumbat!

3 3

4 5

ACC COM P

Unit Indoor Unit Outdoor

Titik pemeriksaan Faktor pemeriksaan Penyebab Perbaikan

1 Sekitar Perbedaan  Debu Ganti katup ekspansi


mekanisme suhu  Uap lembap tersumbat elektronik.
ekspansi  Diameter pipa efektif
berkurang karena
kontaminasi zat perekat,
dll.
2 Aki Pembekuan  Uap lembap tersumbat Tiupkan gas nitrogen,
dan kemudian ganti
refrigeran.

3 Penyalur Perbedaan suhu  Debu Ganti penyalur atau


 Uap lembap tersumbat
penukar panas.
 Diameter pipa efektif
berkurang karena
kontaminasi zat perekat,
dll.
4 Pemipaan bidang Perbedaan suhu  Pipa runtuh Ganti pipa.

5 Katup Perbedaan  Katup penghenti tidak Buka katup penghenti


penghenti suhu sepenuhnya terbuka. sepenuhnya.

Diagnosis Servis 142


SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol

CHECK 4 Jalur Sinyal Motor Kipas


Ukur setiap hambatan antar pin dua kali saat konektor kipas motor tidak terhubung dan periksa apakah sama
atau lebih tinggi dari nilai pada tabel berikut. Tukar bar penguji (merah /hitam) antara pengukuran pertama
dan kedua.

Pengukuran pertama Pengukuran kedua Standar penilaian


1 Putih FG Penguji Hambatan Penguji Hambatan Kedua nilai pengukuran
pertama dan kedua sama
2 Oranye Vsp Merah Hitam  Merah Hitam  dengan atau lebih tinggi
3 Coklat Vcc FG GND GND FG dari 1.
Vsp GND GND Vsp
4 Biru GND
Vcc GND GND Vcc
5 – Vdc GND GND Vdc
6 –

7 Merah Vdc

CHECK 5 Periksa Transistor Daya


Penilaian sesuai dengan pemeriksaan kontinuitas dengan menggunakan penguji analog:
(1) Jangan Sentuh bidang bermuatan (tegangan tinggi) selama 10 menit setelah mematikan catu daya.
(2) Jika anda harus menyentuh bidang tersebut, pastikan bahwa tegangan catu daya dari transistor
daya adalah 50 V atau kurang.
(3) Lepaskan konektor motor kipas unit outdoor.
Ketika kipas unit outdoor berputar melawan angin kencang, kondensor bermuatan dan sengatan listrik
bisa terjadi. Oleh karena itu, lepaskan konektor dari motor kipas unit outdoor setelah mengkonfirmasi
bahwa kipas unit outdoor telah berhenti.
(4) Sebelum mengukur kontinuitas, putuskan koneksi antara kompresor dan transistor daya.
(5) Ukur kontinuitas dalam prosedur berikut.
[Penilaian] Normal jika hasil pemeriksaan kontinuitas sebagai serikut.

Transistor daya (pada PCB)

C+— U Kontinuitas C- — U 
C+— V Kontinuitas  C- — V 
C+— W Kontinuitas C- — W 
U — C+  U — C- Kontinuitas
V — C+  V — C- Kontinuitas 
W — C+  W — C- Kontinuitas

Catatan:
 Jika ada kontinuitas, hambatan harus sama dengan setiap fasa.
 Jika penguji digital digunakan untuk pengukuran kontinuitas,  dan kontinuitas dapat dibalik.

143 Diagnosis Servis


Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E

CHECK 6 Memeriksa Refrigeran yang tidak memadai


Sebagai kriteria untuk menilai apakah refrigeran memadai atau tidak, lihat pada kondisi operasi berikut.

< Diagnosis refrigeran tidak memadai >


Dalam pendinginan
(1) Ketika derajat super panas hisap meningkat karena kekurangan refrigeran, katup ekspansi
elektronik cenderung terbuka (terbuka penuh) untuk menghindari operasi panas yang berlebihan.
(2) Sebagai respon terhadap kapasitas evaporator berkurang yang disebabkan oleh kekurangan
refrigeran, kapasitas dikendalikan di inverter untuk menjaga tekanan rendah, yang berakibat pada
penurunan frekuensi.
(3) Karena (1) dan (2) di atas, frekuensi kompresor menurun meskipun perbedaan besar (beban besar)
antara suhu yang ditetapkan oleh remote kontrol dan suhu udara hisap indoor, mengakibatkan
kapasitas pendinginan menjadi tidak tersedia.
(4) Jika kekurangan refrigeran menjadi lebih buruk, katup ekspansi elektronik tetap terbuka penuh dan
derajat super panas hisap selanjutnya meningkat. Selain itu, karena frekuensi kompresor turun ke
tingkat frekuensi terendah (52 Hz) dan laju aliran refrigeran menurun, tekanan rendah tidak dapat
dipertahankan.

Pendinginan Peringatan kekurangan kek urangan refrigeran


refrigeran yang tidak normal

Tekanan tinggi
(Termistor penukar
panas sedang)
Karena frekuensi tekanan tinggi
kompresor turun, yang sebenarnya
tekanan tinggi turun.

(Mempertahankan tingkat
tertentu tekanan rendah)
Tekanan rendah )

Ketika laju aliran refrigeran turun,


mustahil untuk mempertahankan
tekanan rendah.

Karena derajat bukaan katup ekspansi


elektronik mencapai maksimum,
derajat super panas isapan meningkat.

Derajat super panas isapan

Frekuensi kompresor

Sebagai respon terhadap kapasitas evaporator berkurang yang Mencapai frekuensi


disebabkan oleh kekurangan refrigeran, kapasitas dikendalikan terendah
di inverter dalam rangka untuk mempertahankan tekanan
rendah, yang mengakibatkan penurunan frekuensi.

Derajat bukaan maksimum katup


ekspansi elektronik (480 pulsa)

Hindari operasi panas yang berlebihan


dengan mengubah nilai target SH
Katup ekspansi elektronik

(Derajat refrigeran yang tidak memadai)


tingkat yang memadai tidak memadai

Diagnosis Servis 144


SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol

CHECK 7 Periksa Pengisian Refrigeran yang berlebihan


Sebagai kriteria untuk menilai apakah refrigeran secara berlebihan diisikan atau tidak, Lihat kondisi operasi
berikut.

< Diagnosis pengisian refrigeran yang berlebihan >


Dalam Pendinginan
(1) Sebab tekanan tinggi naik karena pengisian yang berlebihan, kontrol yang berlebihan dilakukan dan
kapasitas cenderung berjalan secara singkat.
(2) Dengan mempertimbangkan beban tekanan, suhu pipa pembuangan kompresor rendah.
Pendinginan

Karena frekuensi
Tekanan Tinggi kompresor turun,
(termistor penukar tekanan rendah naik.
panas sedang)
Tekanan rendah
Frekuensi kompresor
Frekuensi maksimum turun karena kontrol
perlindungan tekanan tinggi
Frekuensi
kompresor Frekuensi minimum
Frekuensi kompresor
meningkat dalam rangka
untuk mempertahankan derajat bukaan katup
tekanan rendah. elektronik menurun karena
Katup ekspansi kontrol perlindungan basah
elektronik Derajat bukaan minimum

Derajat super panas derajat super panas hisap adalah sekitar. 0 derajat.
hisap
Derajat super panas
pembuangan

(Derajat pengisian refrigeran yang berlebihan)


tingkat yang memadai Isi yang berlebihan

145 Diagnosis Servis


Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E

CHECK 8 Periksa Faktor yang menyebabkan Operasi basah

Mengacu pada Fault Tree Analysis (FTA) yang ditunjukkan di bawah ini, mengidentifikasikan titik-titik yang rusak.

Tempat Kompresor sering memulai dan berhenti


refrigeran

pengisian refrigeran yang berlebihan  Lihat CHECK 7 .

Defective valve  Apakah hambatan


Katup ekspansi Kumparan katup coil
rusak
kumparan dan isolasi normal?
elektronik rusak Defective
Bodi katup valve
rusak body
Kontrol derajat super
Sensor tekanan rendah rusa k  Apakah karakteristik tegangan normal?
panas rusak
Kontrol rusak Termistor pipa hisap rusak PCB  Apakah konektor dengan tepat terhubung?
Wet operation
Operasi basah Apakah karakteristik resistansi termistor
unit outdoor rusak
normal?
 Apakah nilai tekanan yang
diperiksa dengan Service Checker
sesuai dengan pengukuran sensor?
Dirty evaporator
Evaporator kotor  Apakah penukar panas tersumbat?
Kapasitas
penguapan Motor kipas rusak  Apakah motor kipas
berkurang bisa diputar
Decreased
Laju aliran output menggunakan tangan?
fan airflow kipas turun
udara PCB unitoutdoor rusak Apakah hambatan
kipas
rate turun (termasuk pengaturan kumparan motor dan
kapasitas)
isolasi normal?

Catatan:
 Nilai referensi untuk derajat super panas yang akan digunakan dalam penilaian operasi basah
(1) Derajat super panas pipa hisap: 4°C atau lebih
(2) Derajat super panas pipa pembuangan: 5°C atau kurang
(Nilai-nilai di atas harus digunakan hanya untuk tujuan referensi. Bahkan dioperasikan dalam kisaran di
atas, operasi mungkin normal dalam kondisi lain.)

Diagnosis Servis 146


SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol

CHECK 9 Titik Pengukuran Tegangan

PCB (A1P) unit Outdoor +5V

(Merah)

Merah

sensor tekanan
GND Hitam

input A/D
Mikro-komputer Putih

Ukur tegangan DC di sini.

CHECK 10 “Sensor tekanan”, Grafik Karakteristik Tekanan / Tegangan.

3.0 4.15 4.15


PH
PH (MPa) = × VH – × 0.5
3.0
Tekanan terdeteksi P H (MPa)

3.0
2.5

2.0

1.5

1.0

0.5

–0.5
–0.5 0 0.5 1 1.5 2 2.5 3 3.5 4
Tegangan Output VH (VDC)

CHECK 11 Kriteria Hambatan Kumparan dan Konektor Katup Ekspansi

Kriteria
(Jingga) 1
40 - 50
(Merah) 2 Titik Pengukuran
(Kuning) 3 1- 5
3- 5
(Hitam) 4
2- 6
(abu-abu) 5 4- 6
(Putih) 6

RZR100/125/140

147 Diagnosis Servis


Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E

CHECK 13 Pulsa Kecepatan Kipas

(1) Atur operasi OFF dan daya OFF. Lepaskan konektor (1).
(2) Periksa tegangan antara pin 3 - 4 adalah sekitar 15 VDC.
(3) Periksa tegangan antara pin 1 - 4 adalah sekitar 5 VDC.
(4) Jaga operasi tetap OFF dan daya OFF. Sambungkan konektor (1).
(5) Periksa apakah 2 pulsa (0 dan 5 VDC) adalah output 4 kali di pin 1 - 4 ketika motor kipas diputar 1 putaran
dengan tangan.

Periksa Ukur
Jika NG di langkah 2 dan 3 PCB yang rusak
Ganti PCB unit outdoor.
Jika NG di langkah 5 IC Hall yang rusak
Ganti motor kipas unit outdoor.
Jika OK di langkah 2, 3 dan 5 Ganti PCB unit outdoor.

PCB

(1)
1 Input pulsa perintah rotasi (0 dan5 VDC) 0
2 VDC
3 15 VDC
4
5
6
7 250~320 VDC

Catatan:
1. Konektor dan PCB unit outdoor
Model Konektor untuk motor kipas (1) PCB
RZR-LUY1 (4) X106A, X107A A2P

Diagnosis Servis 148


SiMT281515E

Bagian 7
Lampiran
1. Diagram Pengkabelan ........................................................................... 150
1.1 Unit Indoor .................................................................................. 150
1.2 Unit Outdoor ............................................................................... 151

149 Lampiran
SiMT281515E Diagram Pengkabelan

1. Diagram Pengkabelan
1.1 Unit Indoor
FBQ60EVE(4) / FBQ71EVE(4) / FBQ100EVE(4) / FBQ125EVE(4) / FBQ140EVE(4)

3D092733A

Appendix 150
SiMT281515E

1.2 Unit Outdoor


RZR100LUY1(4) / RZR125LUY1(4) / RZR140LUY1(4)

3D079826C

151 Lampiran
Diagram Pengkabelan SiMT281515E

Riwayat Revisi
Bulan / Tahun Versi Isi yang direvisi

09 / 2015 SiMT281515E Edisi pertama

Appendix 152
Peringatan  Produk Daikin diproduksi untuk ekspor ke berbagai negara di seluruh dunia. Sebelum membeli,
harap konfirmasikan dengan importir, distributor dan / atau pengecer resmi setempat apakah produk
ini sesuai dengan standar yang berlaku, dan cocok untuk digunakan, di daerah di mana produk akan
digunakan. Pernyataan ini tidak dimaksudkan untuk mengecualikan, membatasi atau memodifikasi
aplikasi dari setiap peraturan setempat.
 Ajukan installer atau kontraktor yang memenuhi syarat untuk memasang produk ini. Jangan
mencoba untuk memasang produk ini sendiri. instalasi yang tidak tepat dapat mengakibatkan
kebocoran air atau refrigeran, sengatan listrik, kebakaran atau ledakan.
 Gunakan hanya komponen dan aksesori yang disediakan atau yang ditentukan oleh Daikin.
Minta installer atau kontraktor yang memenuhi syarat untuk memasang komponen dan aksesori
tersebut. Penggunaan komponen dan aksesori yang tidak resmi atau instalasi komponen dan
aksesori yang tidak tepat dapat mengakibatkan kebocoran air atau refrigeran, sengatan listrik,
kebakaran atau ledakan.
 Baca panduan pengguna dengan seksama sebelum menggunakan produk ini. panduan
pengguna memberikan petunjuk keselamatan dan peringatan penting. Pastikan untuk mengikuti
petunjuk dan peringatan ini.
Jika Anda memiliki pertanyaan, silahkan hubungi importir, distributor dan / atau pengecer
setempat.

Perhatian terhadap korosi produk


1. Pendingin ruangan sebaiknya tidak dipasang di daerah di mana gas korosif, seperti gas asam atau gas alkali, dihasilkan.
2. Jika unit outdoor akan dipasang dekat dengan tepi laut, paparan langsung angin laut harus dihindari. Jika Anda perlu
memasang unit outdoor dekat dengan tepi laut, hubungi distributor setempat.
Pedagang Kantor pusat:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Kantor di Tokyo:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/products/ac/
c Seluruh hak cipta

 Spesifikasi, desain dan konten lainnya yang muncul dalam brosur ini berlaku sejak September 2015 namun dapat berubah tanpa
pemberitahuan. SiMT281515E
09/2015 AK.K