Service
Manual
RNQ26/30/36MV1(4)
RNQ26MV19
RNQ26/30/36/42/48MY1(4)
Refrigrant saja 50 Hz
SiMT281501EA
Bag 2 Spesifikasi..................................................................... 7
1. Spesifikasi ........................................................................................... 8
1.1 FHNQ (Tipe Ceiling Suspended)................................................. 8
Bag 7 Lampiran........................................................................ 54
1. Diagram Pemipaan............................................................................. 55
1.1 FHNQ26MV1(4) + RNQ26MV1(4)(9)
FHNQ26MV1(4) + RNQ26MY1(4)............................................... 55
1.2 FHNQ30MV1(4) + RNQ30MV1(4)
FHNQ30MV1(4) + RNQ30MY1(4)
FHNQ36MV1(4) + RNQ36MV1(4)
FHNQ36MV1(4) + RNQ36MY1(4)............................................... 56
1.3 FHNQ42MV1(4) + RNQ42MY1(4)
FHNQ48MV1(4) + RNQ48MY1(4)............................................... 57
2. Diagram Pengkabelan........................................................................... 58
2.1 Unit Indoor................................................................................... 58
2.2 Unit Outdoor (1 Fasa) ................................................................. 59
2.3 Unit Outdoor (3 Fasa) ................................................................. 62
ii
Perhatian Keselamatan SiMT281501EA
1. Perhatian Keselamatan
Pastikan untuk membaca peringatan keselamatan berikut sebelum melakukan
pekerjaan perbaikan.
Setelah pekerjaan perbaikan selesai, pastikan untuk melakukan Test Operasi untuk
memastikan bahwa peralatan beroperasi secara normal, dan menjelaskan
memperingatkan untuk operasi produk kepada pelanggan.
Peringatan Items Item perhatian diklasifikasikan ke dalam Peringatan dan Perhatian. Item
Peringatan sangat penting karena kematian atau cedera serius dapat terjadi jika tidak
diikuti. Item Peringatan juga dapat menyebabkan kecelakaan serius dalam beberapa
kondisi jika tidak diikuti. Oleh karena itu, pastikan untuk mengamati semua item perhatian
keselamatan dijelaskan di bawah ini.
Pictograms Simbol ini menunjukkan item yang perhatian yang harus diikuti.
Piktogram ini menunjukkan item yang harus diperhatikan.
Simbol ini menunjukkan tindakan yang dilarang.
Item atau tindakan yang dilarang ditampilkan dalam ilustrasi atau dekat simbol.
Simbol ini menunjukkan suatu tindakan yang harus diambil, atau instruksi.
Instruksi ditampilkan dalam ilustrasi atau dekat simbol.
Pastikan untuk lepaskan kabel daya dari stop kontak sebelum peralatan
dibongkar untuk perbaikan.
Bekerja pada peralatan yang terhubung ke catu daya dapat menyebabkan
sengatan listrik.
Jika diperlukan untuk memasok listrik ke peralatan untuk melakukan
perbaikan atau memeriksa sirkuit, jangan menyentuh bagian bermuatan
listrik dari peralatan.
Jika refrigerant habis selama pekerjaan perbaikan, jangan sentuh
gas refrigeran yang keluar.
Refrigeran dapat menyebabkan radang dingin.
iii
SiMT281501EA Perhatian Keselamatan
Peringatan
Jangan menghidupkan atau mematikan AC dengan mencolokkan atau
mencabut kabel listrik.
Mencolokkan atau mencabut kabel listrik untuk mengoperasikan peralatan
dapat menyebabkan sengatan listrik atau kebakaran.
Peringatan
Jangan memperbaiki komponen listrik dengan tangan basah.
Bekerja pada peralatan dengan tangan basah dapat menyebabkan sengatan
listrik.
Pastikan untuk mematikan saklar daya dan cabut kabel listrik saat
membersihkan peralatan.
Kipas internal berputar pada kecepatan tinggi, dan dapat menyebabkan
cedera.
iv
Perhatian Keselamatan SiMT281501EA
Perhatian
Lakukan pekerjaan pengelasan di tempat yang berventilasi baik.
Menggunakan alat las di ruang tertutup dapat menyebabkan kekurangan
oksigen.
Jika kabel listrik dan kabel utama yang tergores atau telah usang,
pastikan untuk menggantinya.
Kabel dan kawat yang rusak dapat menyebabkan sengatan listrik, ,
peningkatan panas yang berlebihan atau kebakaran.
Ketika kabel antara unit indoor dan outdoor, pastikan bahwa penutup
terminal tidak mengangkat atau turun karena kabel.
Jika penutup tidak terpasang dengan benar, bagian sambungan terminal
dapat menyebabkan kejutan listrik, pembangkit panas yang berlebihan atau
kebakaran.
v
SiMT281501EA Perhatian Keselamatan
Peringatan
Jangan mencampur udara atau gas selain refrigeran yangditentukan
(R-32, R-410A, R-22) dalam sistem Refrigant.
Jika udara memasuki sistem Refrigant, hasil tekanan terlalu tinggi, dapat
menyebabkan kerusakan peralatan dan cedera.
Periksa untuk memastikan bahwa kabel konektor daya tidak kotor atau
longgar, kemudian masukkan steker ke stop kontak dengan aman.
Jika steker berdebu atau memiliki sambungan yang longgar, hal itu dapat
menyebabkan sengatan listrik atau kebakaran.
Peringatan
Pemasangan pemutus kebocoran diperlukan dalam beberapa kasus
tergantung pada kondisi tempat instalasi, untuk mencegah sengatan
listrik.
Periksa untuk melihat apakah part dan kabel terpasang dan terhubung
dengan benar, dan jika koneksi yang disolder atau berkerut pada
terminal aman.
instalasi yang tidak tepat dan koneksi dapat menyebabkan generasi panas
yang berlebihan, kebakaran atau sengatan listrik.
vi
Ikon yang digunakan SiMT281501EA
Perhatian
Periksa pembumian / landasan, dan perbaiki jika peralatan tidak
dengan benar dibumikan.
Pembumian / landasan yang tidak tepat dapat menyebabkan sengatan listrik.
Tipe
Ikon Deskripsi
Informasi
Peringatan Peringatan digunakan ketika ada bahaya cedera pribadi.
Peringatan
vii
SiMT281501EA
Bagian 1
Informasi Umum
1. Nama Model dan Catu Daya................................................................... 2
2. Tata Nama .............................................................................................. 3
3. Tampilan Luar ......................................................................................... 4
4. Fungsi ..................................................................................................... 6
1
Informasi Umum
Nama Model dan Catu Daya SiMT281501EA
2
Informasi Umum
SiMT281501EA Tata Nama
2. Tata Nama
Unit Indoor
Simbol Standar
Kosong: Umum
4: Indonesia
Simbol Catu Daya
V1: 1 Fasa, 220-240 V, 50 Hz
Mengindikasikan kategori desain umum
Indikasi Kapasitas
Refrigeran, Refrigrant Saja/Heat pump
Q: R-410A, Refrigrant Saja
Inverter/Non-inverter
N: Non-inverter
Tipe
C: Ceiling mounted cassette (Round flow)
H: Ceiling Suspended
DB: Duct connection low static pressure
DM: Duct connection middle static pressure
Kategori Unit
F: Unit Indoor AC Split
Unit Outdoor
Simbol Standar
Kosong: Umum
4: Indonesia
9: Simbol Managemen (Peraturan EMC baru diterapkan)
Simbol Catu Daya
V1: 1 Fasa, 220-240 V, 50 Hz
Y1: 3 Fasa, 380-415 V, 50 Hz
Mengindikasikan kategori desain umum
Indikasi Kapasitas
Refrigeran, Refrigrant Saja/Heat pump
Q: R-410A, Refrigrant Saja
Inverter/Non-inverter
N: Non-inverter
Kategori Unit
R: Unit Outdoor AC Split
3
Informasi Umum
Tampilan Luar SiMT281501EA
3. Tampilan Luar
Unit Indoor
FHNQ
BRC1NU61
4
Informasi Umum
SiMT281501EA Tampilan Luar
Unit Outdoor
RNQ36MV1(4)
RNQ26MV1(4)(9) RNQ30MV1(4) RNQ36MY1(4)
RNQ26MY1(4) RNQ30MY1(4) RNQ42MY1(4)
RNQ48MY1(4)
5
Informasi Umum
Fungsi SiMT281501EA
4. Fungsi
FHNQ26-48MV1(4)
Kategori Fungsi RNQ26-36MV1(4)
RNQ26MV19
RNQ26-48MY1(4)
Kenyamanan Auto swing
Pemilihan pola ayunan —
Fungsi pencegahan Draft (Pemanasan) —
Aliran udara up-dan-down independen —
Kecepatan kipas (2 langkah)
Tingkat aliran udara auto —
Mode kecepatan fan tinggi —
Program kering
Aplikasi langit-langit tinggi (*1)
Dua Pilihan suhu-sensor —
Hot start (Setelah defrost) —
Refrigrant sepanjang tahun —
Operasi malam yang tenang —
Remot Kontrol Auto reset setpoint —
Berbagai setpoint set —
Jadwal waktu mingguan —
Off Timer (Terprogram) —
On / off Timer
Kebersihan Filter udara Anti-bakteri
Filter udara anti jamur —
Saluran pan anti-bakteri —
Pekerjaan & Perbaikan Mekanisme Drain pump —
Pre-charged hingga 15 m (* 2)
Pre-charged hingga 10 m (* 3)
Filter tahan lama
Tanda Filter —
Pencegahan mengotori atap —
Deteksi tekanan gas rendah —
Operasi darurat —
Fungsi Self-diagnosis —
Fitur kontrol Auto-restart
Perubahan otomatis Refrigrant / pemanasan —
Kontrol dengan 2 remote controller —
Grup kontrol dengan 1 remote kontrol —
Kontrol perintah eksternal —
Remote kontrol sentral —
Kontrol interlock —
Standar komunikasi DIII-NET —
(Pilihan) Filter dengan efisiensi tinggi —
Filter yang sangat awer —
Kotak asupan udara segar —
Lain-lain Penukar panas Anti-korosi (* 4)
Catatan: : Tersedia
— : Tidak tersedia
*1 : Dapat di pasang pada plafon dengan tinggi maksimal 3,5 m
*2 : Berlaku untuk Unit Outdoor RNQ30-48M
*3 : Berlaku untuk Unit Outdoor RNQ26M
*4 : Untuk Unit Outdoor
6
Informasi Umum
SiMT281501EA
Part 2
Spesifikasi
1. Spesifikasi............................................................................................... 8
1.1 FHNQ (Tipe Ceiling Suspended) .......................................................... 8
7
Spesifikasi
Spesifikasi SiMT281501EA
1. Spesifikasi
1.1 FHNQ (Tipe Ceiling Suspended)
Unit Indoor FHNQ26MV1 FHNQ26MV14
Model
Unit Outdoor RNQ26MV1, RNQ26MV19 RNQ26MV14
Catu Daya 1 Fasa, 220-240 V, 50 Hz (2 kabel)
Colokan Catu Daya Di Samping Unit Outdoor
kW 7.6
Kapasitas Refrigrant *1 *2 Btu/h 26,000
kcal/h 6,550
Unit Indoor FHNQ26MV1 FHNQ26MV14
Warna Putih
Dimensi H×W×D mm 195 × 1,400 × 680
Tipe Cross Fin Koil
Koil Baris × Tahapan × Fin Pitch 3 × 12 × 1.75
Area Muka m² 0.293
Tipe Sirocco Fan
Fan Output Motor W 98
Laju Aliran Udara (H/L) m³/min 26-27/22-23
cfm 918-953/777-812
Tingkat Kebisingan 220 V dB(A) 45/40
(H/L) *3
Filter udara Jaring Resin (anti jamur)
Berat kg 32
Cair mm Φ9.5 (Flare)
Koneksi
Pipa Gas mm Φ15.9 (Flare)
Drain mm VP20 (I.D.Φ20 × O.D.Φ26)
Remot Kontrol Wired BRC1NU61
(Pilihan) Wireless BRC7NU66
Unit Outdoor RNQ26MV1, RNQ26MV19 RNQ26MV14
Warna Putih Gading
Dimensi H×W×D mm 735 × 825 × 300
Tipe Cross Fin Koil
Koil Baris × Tahapan × Fin Pitch 2 × 32 × 1.6
Area Muka m² 0.595
Model PN31VBBMT
Kompresor Tipe Tipe Hermetically Sealed Rotary
Output Motor kW 2.2
Tipe Propeller Fan
Fan Output Motor W 70
Laju Aliran Udara m³/min 38.5
Tingkat dB(A) 54
Refrigrant
Kebisingan *3
Berat kg 56
Cair mm Φ9.5 (Flare)
Koneksi
Gas mm Φ15.9 (Flare)
Pipa
Drain mm Φ18.0 (Hole)
Alat Pengaman Pelindung termal fan motor indoor dan indoor, sakelar tekanan tinggi, pelindung internal (Kompresor), fuse,
saklar thermo (pipa discharge)
Langkah Kapasitas % 100-0
Kontrol Refrigeran Pipa Kapiler
Pemipaan Panjang Maks m 30 (Setara panjang 50 m)
Refrigeran Selisih Tinggi Maks m 20
Refrigeran Model R-410A
Charge (Factory Charge) kg 2.0 (Charged for 10 m)
Oli Refrigeran Model Merujuk pada nameplate Kompresor.
Charge L 0.9
Nomor Gambar C: 3D089665
Catatan: *1. Tabel di atas berdasarkan pada kondisi berikut. Rumus Konversi
Refrigrant Panjang Pipa kcal/h = kW × 860
Indoor : 27°CDB, 19.0°CWB 7.5 m Btu/h = kW × 3412
Outdoor : 35°CDB, 24°CWB (Horizontal) cfm = m³/min × 35.3
*2. Kapasitas bersih, termasuk pengurangan Refrigrant untuk panas fan motor indor.
*3. Nilai konversi ruang anechoic, diukur sesuai dengan parameter dan kriteria JIS. Selama operasi
nilai ini agak tinggi karena dipengaruhi kondisi sekitar.
8 Spesifikasi
SiMT281501EA Spesifikasi
Catatan: *1. Tabel di atas berdasarkan pada kondisi berikut. Rumus Konversi
Cooling Panjang Pipa kcal/h = kW × 860
Indoor : 27°CDB, 19.0°CWB 7.5 m Btu/h = kW × 3412
Outdoor : 35°CDB, 24°CWB (Horizontal) cfm = m³/min × 35.3
*2. Kapasitas bersih, termasuk pengurangan Refrigrant untuk panas fan motor indor.
*3. Nilai konversi ruang anechoic, diukur sesuai dengan parameter dan kriteria JIS. Selama operasi
nilai ini agak tinggi karena dipengaruhi kondisi sekitar.
9
Spesifikasi
Spesifikasi SiMT281501EA
Catatan: *1. Tabel di atas berdasarkan pada kondisi berikut. Rumus Konversi
Cooling Panjang Pipa kcal/h = kW × 860
Indoor : 27°CDB, 19.0°CWB 7.5 m Btu/h = kW × 3412
Outdoor : 35°CDB, 24°CWB (Horizontal) cfm = m³/min × 35.3
*2. Kapasitas bersih, termasuk pengurangan Refrigrant untuk panas fan motor indor.
*3. Nilai konversi ruang anechoic, diukur sesuai dengan parameter dan kriteria JIS. Selama operasi
nilai ini agak tinggi karena dipengaruhi kondisi sekitar.
10
Spesifikasi
SiMT281501EA Spesifikasi
Catatan: *1. Tabel di atas berdasarkan pada kondisi berikut. Rumus Konversi
Cooling Panjang Pipa kcal/h = kW × 860
Indoor : 27°CDB, 19.0°CWB 7.5 m Btu/h = kW × 3412
Outdoor : 35°CDB, 24°CWB (Horizontal) cfm = m³/min × 35.3
*2. Kapasitas bersih, termasuk pengurangan Refrigrant untuk panas fan motor indor.
*3. Nilai konversi ruang anechoic, diukur sesuai dengan parameter dan kriteria JIS. Selama operasi
nilai ini agak tinggi karena dipengaruhi kondisi sekitar.
11
Spesifikasi
Spesifikasi SiMT281501EA
Catatan: *1. Tabel di atas berdasarkan pada kondisi berikut. Rumus Konversi
Cooling Panjang Pipa kcal/h = kW × 860
Indoor : 27°CDB, 19.0°CWB 7.5 m Btu/h = kW × 3412
Outdoor : 35°CDB, 24°CWB (Horizontal) cfm = m³/min × 35.3
*2. Kapasitas bersih, termasuk pengurangan Refrigrant untuk panas fan motor indor.
*3. Nilai konversi ruang anechoic, diukur sesuai dengan parameter dan kriteria JIS. Selama operasi
nilai ini agak tinggi karena dipengaruhi kondisi sekitar.
12
Spesifikasi
SiMT281501EA Spesifikasi
Catatan: *1. Tabel di atas berdasarkan pada kondisi berikut. Rumus Konversi
Cooling Panjang Pipa kcal/h = kW × 860
Indoor : 27°CDB, 19.0°CWB 7.5 m Btu/h = kW × 3412
Outdoor : 35°CDB, 24°CWB (Horizontal) cfm = m³/min × 35.3
*2. Kapasitas bersih, termasuk pengurangan Refrigrant untuk panas fan motor indor.
*3. Nilai konversi ruang anechoic, diukur sesuai dengan parameter dan kriteria JIS. Selama operasi
nilai ini agak tinggi karena dipengaruhi kondisi sekitar.
Spesifikasi 13
Spesifikasi SiMT281501EA
Catatan: *1. Tabel di atas berdasarkan pada kondisi berikut. Rumus Konversi
Cooling Panjang Pipa kcal/h = kW × 860
Indoor : 27°CDB, 19.0°CWB 7.5 m Btu/h = kW × 3412
Outdoor : 35°CDB, 24°CWB (Horizontal) cfm = m³/min × 35.3
*2. Kapasitas bersih, termasuk pengurangan Refrigrant untuk panas fan motor indor.
*3. Nilai konversi ruang anechoic, diukur sesuai dengan parameter dan kriteria JIS. Selama operasi
nilai ini agak tinggi karena dipengaruhi kondisi sekitar.
14
Spesifikasi
SiMT281501EA Spesifikasi
Catatan: *1. Tabel di atas berdasarkan pada kondisi berikut. Rumus Konversi
Cooling Panjang Pipa kcal/h = kW × 860
Indoor : 27°CDB, 19.0°CWB 7.5 m Btu/h = kW × 3412
Outdoor : 35°CDB, 24°CWB (Horizontal) cfm = m³/min × 35.3
*2. Kapasitas bersih, termasuk pengurangan Refrigrant untuk panas fan motor indor.
*3. Nilai konversi ruang anechoic, diukur sesuai dengan parameter dan kriteria JIS. Selama operasi
nilai ini agak tinggi karena dipengaruhi kondisi sekitar.
15
Spesifikasi
SiMT281501EA
Bagian 3
Remot Kontrol
1. Model yang digunakan .......................................................................... 17
2. Nama dan Fungsi .................................................................................. 18
2.1 BRC1NU61............................................................................................. 18
2.2 BRC7NU66............................................................................................. 19
16
Remot Kontrol
SiMT281501EA Model yang digunakan
17
Remot Kontrol
Nama dan Fungsi SiMT281501EA
COOL
POWER TIMER SLEEP COMP.
2
MODE
MODE 3
1 TEMP
TEMP 4
FAN
SW 6
SLEEP SLEEP
SLEEP 5
CLOCK HR 9
START MINSTART
STOP STOP 10
7 8
18
Remot Kontrol
SiMT281501EA Nama dan Fungsi
2.2 BRC7NU66
2 ON OFF
COOL
TINGGI
3 TEMP
5
6 SLEEP
MODE 7
8
9 SWEEP
CANCEL
SEND
10
11
19
Remot Kontrol
Nama dan Fungsi SiMT281501EA
Receiver
14
17
16
13
15
12
13. Penerima:
• Menerima sinyal dari remote kontrol.
20
Remot Kontrol
SiMT281501EA
Bagian 4
Fungsi dan Kontrol
1. Garis Besar Fungsi ............................................................................... 22
1.1 Unit Indoor..................................................................................... 22
1.2 Unit Outdoor ................................................................................... 22
2. Detail Fungsi ......................................................................................... 23
2.1 Unit Indoor (FHNQ)........................................................................23
21
Fungsi dan Kontrol
Garis Besar Fungsi SiMT281501EA
(Input) (Output)
Unit Indoor
(Fungsi)
Thermostat Control
(Fungsi)
Thermostat Pipa Discharge Control ON/OFF Kompresor
(Q1) Kompresor
Kelas 26/42/48
22
Fungsi dan Kontrol
SiMT281501EA Detail Fungsi
2. Detail Fungsi
2.1 Unit Indoor (FHNQ)
2.1.1 Power On/Off
Menekan tombol ON / OFF akan menghidupkan AC atau menonaktifkan. Ketika dihidupkan, akan
beroperasi sesuai dengan pengaturan. POWER LED pada unit display akan menyala.
2.1.2 Fan
Tekan tombol FAN untuk memilih kecepatan kipas (TINGGI, MEDIUM, LOW, atau AUTO). LCD pada
remote kontrol akan menunjukkan status..
Ketika kecepatan kipas diatur ke AUTO, kecepatan kipas akan disesuaikan secara otomatis sesuai dengan
perbedaan antara Temperatur ruangan dan Set temperatur.
• Jika perbedaannya adalah 3°C atau lebih, kecepatan fan tinggi.
• Jika perbedaannya adalah 2°C, kecepatan fan medium.
• Jika perbedaannya adalah 1°C atau kurang, kecepatan fan rendah.
Catatan:
• Tombol FAN hanya dapat digunakan dalam operasi fan atau operasi Refrigrant, itu tidak dapat digunakan
dalam operasi kering.
• Kecepatan kipas akan disesuaikan 2 detik setelah tombol ditekan.
2.1.3 Mode
Dengan menekan tombol MODE, AC dapat di set ke dalam 3 mode operasi (FAN, COOL, DRY).
FAN: LCD pada remote kontrol akan menunjukkan FAN. sistem akan menyalakan fan saja.
Tombol SLEEP dan TEMP tidak digunakan.
COOL: LCD pada remote kontrol akan menunjukkan COOL. Sistem akan melakukan operasi
Refrigrant. kompresor akan
• Beroperasi jika Truangan Tset + 1
• Berhenti jika Truangan <Tset
Namun, kompresor akan delay 3 menit perlindungan setiap kali berhenti.
Catatan:
Mode akan berubah 3 detik setelah menekan tombol mode.
2.1.5 Sweep
Menekan SW atau tombol SWEEP akan menghidupkan atau menonaktifkan motor sweep.
2.1.6 Sleep
Menekan tombol SLEEP akan memulai fungsi tidur. LCD pada remote kontrol akan menampilkan simbol
.
Dalam operasi Refrigrant, Set temperatur akan secara otomatis meningkat 1°C setelah satu jam.
23
Fungsi dan Kontrol
Detail Fungsi SiMT281501EA
TEMPERATUR
RUANGAN REFRIGRANT
23.0
SUHUE
MENINGKAT
1°C
22.0
Catatan:
• Ketika sistem dalam mode sleep, menekan tombol SLEEP lagi akan membatalkan fungsi sleep.
• Ketika sistem dalam mode sleep dan tombol TEMP ditekan, maka akan menaikkan suhu pengaturan 1°C
dari pengaturan terakhir.
• Ketika sistem dalam mode sleep dan AC berhenti karena mati listrik atau dimatikan, hal tersebut akan
membatalkan fungsi sleep.
2.1.7 Jam
Untuk mengatur jam pada remote kontrol kabel:
• Tekan tombol . Tampilan waktu akan berkedip.
• Tekan tombol HR untuk mengatur jam.
• Tekan tombol MIN untuk menyetel menit.
• Tekan lagi. Tampilan waktu akan berhenti berkedip.
2.1.10 Monitoring
Ada sirkuit Monitoring untuk memantau operasi mikroprosesor. Jika Tidak berfungsi, sirkuit ini akan
mengatur ulang mikroprosesor secara otomatis.
24
Fungsi dan Kontrol
SiMT281501EA Detail Fungsi
Jika ada perubahan dalam parameter, akan disimpan dalam memori non-volatile 5 detik kemudian.
Memasuki proses Pembekuan Saat dalam porses Pembekuan Keluar dari proses Pembekuan
Tindoor heat exchanger ≤ 0°C, dan Kompresor berhenti, fan indoor pada Tindoor heat exchanger ≥ 7°C, atau
kompresor bekerja terus menerus kecepatan rendah, dan LED power Sistem OFF
untuk lebih dari 10 menit berkedip.
Ketika thermistor penukar panas dalam ruangan telah gagal (open / short circuit), sistem akan beroperasi
seolah-olah tidak ada penukar panas thermistor dalam ruangan.
ON
Gambar A
OFF
ON
Gambar B
OFF
25
Fungsi dan Kontrol
SiMT281501EA
Bagian 5
Pengaturan
1. Pengaturan dari Remot Kontrol............................................................. 27
1.1 Ikhtisar Pengaturan .............................................................................. 27
1.2 Penjelasan detail mengenai Mode Pengaturan..................................... 28
26
Pengaturan
SiMT281501EA Pengaturan dari Remot Kontrol
TH1: thermistor
2 Pemilihan thermistor TH1: thermistor —
remote suction udara
kontrol
3 Tanda Pembersihan filter Tampil Tidak tampil —
Catatan:
1. Gunakan Nomor mode dalam tanda kurung () untuk memeriksa pengaturan terdaftar.
2. Jangan mengatur item selain yang diberikan pada tabel di atas.
3. Fungsi unit indoor yang tidak dilengkapi tidak ditampilkan.
4. Ketika kembali ke mode normal, 88 dapat ditampilkan pada remote kontrol untuk menginisialisasi.
* 5. Pengaturan dibuat di semua unit dalam kelompok. Untuk mengatur masing-masing unit dalam
ruangan atau untuk memeriksa pengaturan, gunakan mode No.S (dengan 2 di digit atas) dalam
tanda kurung ().
* 6. Untuk rincian, lihat manual instalasi.
Perhatian
Ketika memiliki fungsi auto-restart, pastikan untuk mematikan AC, kemudian putus suplai listrik sebelum
melakukan perawatan, inspeksi dan pekerjaan lain. Jika catu daya terputus dengan saklar daya yang
dibiarkan pada posisi ON, AC otomatis akan memulai operasi saat listrik dihidupkan.
27
Pengaturan
Pengaturan from Remot Kontrol SiMT281501EA
Tipe Filter
Ketika ultra long life filter diinstal, filter tanda pengaturan waktu harus diubah.
Nomor Kode
Nomor mode Nomor Kode Kedua Pengaturan
Pertama
01 Long Life Filter
10 (20) 1
02 Ultra Long Life Filter
Pemilihan thermistor
Pilih thermistor untuk mengontrol Temperatur ruangan.
Nomor Kode
Nomor mode Nomor Kode Kedua Pengaturan
Pertama
28
Pengaturan
SiMT281501EA Pengaturan from Remot Kontrol
Untuk alasan di atas, ketika “fungsi Auto restart mati listrik” diaktifkan, perhatian ekstra harus diberikan
ketika terjadi situasi berikut.
Perhatian AC mulai beroperasi seketika setelah listrik menyala kembali atau ketika
catu daya utama dihidupkan lagi. Akibatnya, pengguna mungkin akan
terkejut dan bertanya-tanya mengapa hal ini terjadi. Dalam pekerjaan
servis misalnya, mematikan saklar daya utama saat unit dalam
operasi, dan menyalakan tombol lagi setelah pekerjaan selesai mulai
operasi Unit (fan berputar).
Nomor Kode
Nomor mode Pertama Nomor Kode Kedua Pengaturan
01 F : 4-arah aliran udara
13 (23) 1 02 T : 3- arah aliran udara
03 W : 2- arah aliran udara
Nomor Kode
Nomor mode Pertama Nomor Kode Kedua Pengaturan
01 Ke atas (mencegah angin langsung)
13 (23) 4 02 Standard
03 Ke bawah (mencegah plafon kotor)
29
Pengaturan
SiMT281501EA
Bagian 6
Diagnosa Servis
1. Inspeksi Pemeliharaan .......................................................................... 31
1.1 Ikhtisar .................................................................................................... 31
2. Peralatan dikatakan Normal dalam Kasus ini ........................................ 33
2.1 Fenomena yang bukan Kerusakan......................................................... 33
2.2 Operasi yang bukan Kerusakan............................................................. 33
3. Pemecahan Masalah Bedasarkan Gejala ............................................. 34
3.1 Ikhtisar..................................................................................................... 34
3.2 Peralatan tidak beroperasi...................................................................... 35
3.3 Fan beroperasi tapi kompresor tidak....................................................... 36
3.4 Operasi Refrigrant berjalan tapi segera berhenti................................ 37
3.5 Setelah peralatan dimatikan, tidak bisa di restart untuk sementara
waktu....................................................................................................... 38
3.6 Peralatan beroperasi namun tidak memberikan Refrigrant................. 39
3.7 Peralatan mengeluarkan kabut putih...................................................... 40
3.8 Peralatan mengeluarkan suara keras atau getaran. .............................. 41
3.9 Peralatan mengeluarkan debu................................................................. 42
4. Penyelesaian Masalah berdasarkan LED pada Unit Indoor................... 43
5. Fungsi Cek Servis.................................................................................. 44
5.1 Kode Kerusakan dan Deskripsinya......................................................... 44
6. Penyelesaian Masalah berdasarkan Kode Kerusakan........................... 45
6.1 PCB Unit Indoor Rusak........................................................................... 45
6.2 Swing Flap Motor Rusak/Macet.............................................................. 46
Thermistor
6.3 Rusak...................................................................................... 47
Thermistor Remot Kontrol
6.4 Rusak............................................................... 49
6.5 Aktivasi Perangkat Keselamatan............................................................ 50
6.6 Kegagalan Transmisi (Antara Unit Indoor dan Remot Kontrol)............... 52
6.7 Kesalahan Koneksi Pengkabelan........................................................... 53
30 Diagnosa Servis
SiMT281501EA Inspeksi Pemeliharaan
1. Inspeksi Pemeliharaan
1.1 Ikhtisar
Ketika melakukan perawatan, Anda setidaknya harus melakukan pemeriksaan berikut:
Unit Indoor
Transmisi kabel
Transmission antara
wiring between
unit indoor
indoor and dan
Unit outdoor
Outdoors
Apakah fiterfiter
Apakah udara kotor?
udara kotor?
What aboutkapasitas
Bagaimana switch capacity?
switch?
What aboutketebalan
Bagaimana cable thickness?
kabel
Bagaimana tegangan dan
arus?
What about voltage and current? untuk
breaker
khusus
Pipa Refrigeran
Pipa Drain
Unit Outdoor
Bumi
Kondisi Standar
Indoor Outdoor
Operasi Refrigrant 27°CDB/19°CWB 35°CDB
Selama atau setelah perawatan, saat listrik dihidupkan kembali, operasi akan memulai ulang secara
otomatis oleh fungsi auto restart. Harap lakukan perhatian yang cukup.
31
Diagnosa Servis
Inspeksi Pemeliharaan SiMT281501EA
Cooling
Status AC Tekanan rendah Tekanan tinggi Running Current
Filter udara Kotor Lebih Rendah Lebih Rendah Lebih Rendah
Short Circuit of Unit Indoor Inlet/Outlet Lebih Rendah Lebih Rendah Lebih Rendah
Air
Fin Kotor Unit Outdoor Lebih Tinggi Lebih Tinggi Lebih Tinggi
Korsleting dari Unit Outdoor Inlet/ Lebih Tinggi Lebih Tinggi Lebih Tinggi
Outlet air
Udara bercampur dengan refrigeran Lebih Tinggi Lebih Tinggi Lebih Tinggi
Air bercampur dengan refrigeran Lebih Rendah ∗1 Lebih Rendah Lebih Rendah
Kotoran bercampur dengan refrigeran Lebih Rendah ∗2 Lebih Rendah Lebih Rendah
Kekurangan Refrigeran (Gas) Lebih Rendah Lebih Rendah Lebih Rendah
Kompresi Tidak Cukup Lebih Tinggi ∗3 Lebih Rendah Lebih Rendah
Catatan:
*1. Air dalam Refrigant membeku di dalam pipa kapiler atau katup ekspansi elektronik, menyebabkan
fenomena yang sama seperti pompa bawah.
*2. Kotoran di refrigeran menyumbat filter di dalam pipa, menyebabkan fenomena yang sama seperti
pump down.
*3. Tekanan diferensial antara penurunan Tekanan tinggi dan Tekanan rendah .
32
Diagnosa Servis
SiMT281501EA Peralatan dikatakan Normal dalam Kasus ini
Peralatan tidak Tidak beroperasi saat restart segera Peralatan dikatakan normal asalkan
beroperasi. setelah berhenti. lampu operasi remote kontrol menyala. Ini
Tidak beroperasi ketika kembali ke berarti alat pengaman unit bekerja untuk
kondisi semula segera setelah menekan mencegah unit dari yang kelebihan
beban. Operasi dimulai secara otomatis
tombol set Temperatur ruangan ruangan. setelah 3 menit berlalu.
Peralatan mengeluarkan Kabut putih yang dihasilkan ketika Jika di dalam unit indoor sangat kotor,
kabut putih. Refrigant pada kelembaban tinggi. (Unit suhu tidak teratur dapat terjadi. Dalam
terkena oli berlebihan atau debu) unit indoor perlu dibersihkan.
Peralatan menghasilkan Ada Suara setelah unit dimulai berjalan. Suara dihasilkan setelah dilakukan
suara bising. pengontrolan suhu, dan akan menjadi
lebih rendah setelah sekitar 1 menit
berlalu.
Ada suara pelan yang terus menerus Suara gas (refrigeran) yang mengalir di
diproduksi saat Refrigrant. dalam
AC.
Ada suara mendesis segera setelah Suara dihasilkan ketika aliran gas
mulai / berhenti operasi. (Refrigeran) berhenti atau berubah.
Ada suara mencicit. Suara yang disebabkan oleh ekspansi
bagian plastik karena perubahan suhu.
Peralatan mengeluarkan Debu yang dikeluarkan ketika Disebabkan oleh debu yang menempel di
debu. menjalankan unit untuk pertama kalinya dalam unit indoor ditiup keluar.
setelah tidak digunakan dalam jangka
waktu yang panjang.
Bau aneh diproduksi. Bau aneh dihasilkan saat menjalankan Disebabkan oleh bau dan asap rokok
Peralatan mengeluarkan unit. yang terserap dalam unit indoor ditiup
bau. keluar. Bagian dalam unit indoor perlu
dibersihkan.
Remote controller LCD Muncul segera setelah menyalakan Ini untuk memeriksa untuk melihat
menampilkan 88. Sumber Daya listrik. apakah ada sesuatu
salah dengan remote kontrol, dan akan
ditampilkan untuk waktu yang singkat
saja.
2 Flap beroperasi saat catu daya dihidupkan. Pengaturan awal agar pemposisian lebih akurat.
3 Flap bergerak ketika modus operasi berubah. Unit dilengkapi dengan kontrol yang
menggerakkan flap jika mode operasi diubah.
4 Flap beroperasi secara otomatis ketika Pendinginan. Disebabkan oleh fungsi pencegahan embun yang
diaktifkan.
5 Selama Operasi kering mikro –komputer akan Dihidupkan paksa selama 1 menit dengan Fungsi
mengatur kipas indoor berjalan pada kecepatan L Pemantau
untuk satu menit saat kompresor dimatikan.
6 Arah aliran udara berbeda bahkan ketika flap horisontal Arah berbeda untuk Refrigrant / kering.
diatur dalam posisi yang sama.
7 Flap berada pada arah horisontal bahkan ketika diatur Flap tidak berayun ketika termostat dimatikan.
untuk berayun.
8 Flap beroperasi secara otomatis selama debit udara Disebabkan oleh fungsi pengurangan kotoran
horizontal. diaktifkan.
33
Diagnosa Servis
Pemecahan Masalah Bedasarkan Gejala SiMT281501EA
34
Diagnosa Servis
SiMT281501EA Pemecahan Masalah Bedasarkan Gejala
Penyelesaian masalah
Peringatan Pastikan untuk mematikan saklar listrik sebelum menghubungkan/mencabut konektor, jika tidak part bisa rusak.
Apakah
Catu Daya listrik
antara terminal L dan N atau TIDAK
L1, L2 dan L3 unit outdoor Periksa breaker
Check Catu Dayapower supply
breaker.
Tegangannya sesuai? breaker. the correct power
Connect
Hubungkan
supply daya yang sesuai
voltage.
tegangan suplai
YA
Apakah
arus mengalir antara
TIDAK
terminal 1 dan 3 pada unit Periksainternal
pengkabelan
indoor dan unit Check wiringinternal
of Unit
unit outdoor.
Outdoor.
outdoor?
Periksa kabel antara unit
Check wiring between indoor
indoor dan outdoor.
YA and Unit Outdoor.
Apakah
arus mengalir antara TIDAK
terminal P1 dan P2 pada Periksathe
Check sekering untuk
fuse for kontrol
control
unit indoor? sirkuit.
circuit.
Pastikan ON / OFF diatur ke
Make
sisi ON.sure the ON/OFF switch
YA
Periksa jarak jauh kabel
kontrol.
Motor fan rusak.
Defective fan motor.
Termostat
Fan perlindungan
motor protection Fan
thermostat
motor aktif.
is activated.
Check the insulation in electric
system.
Diagnosa Servis 35
Pemecahan Masalah Bedasarkan Gejala SiMT281501EA
Penyelesaian masalah
Peringatan Pastikan untuk mematikan saklar listrik sebelum menghubungkan/mencabut konektor, jika tidak part bisa rusak.
Make
Modethe following: Set
Pendingin temperature
temperatur
Pengaturan
pada remote using Remot
di posisi Kontrol.
terendah
Cooling: Lowest Pengaturan
Apakah YA
peralatan beroperasi? Normal
TIDAK
Apakah
daya tersuplai ke koil YA
magnetic kontaktor . Koil atau kontak dari
kompresor? kontaktor magnetik rusak.
Ganti kontaktor magnetik.
TIDAK
Perangkat
Nama Model Catu Daya
Q1 Q1M Q2M Q1RP S1PL S1PH
RNQ26MV1(4)(9) 1 Fasa ● ▬ ▬ ▬ ▬ ●
RNQ30MV1(4) 220-240 V ▬ ● ▬ ▬ ▬ ●
50 Hz
RNQ36MV1(4) ▬ ● ● ▬ ▬ ●
RNQ26MY1(4) ● ▬ ▬ ● ▬ ●
RNQ30MY1(4) 3 Fasa ▬ ● ▬ ● ▬ ●
RNQ36MY1(4) 380-415 V ▬ ● ● ● ▬ ●
50 Hz
RNQ42MY1(4) ● ● ● ● ● ●
RNQ48MY1(4) ● ● ● ● ● ●
● : ada
▬ : tidak ada
36 Diagnosa Servis
SiMT281501EA Pemecahan Masalah Bedasarkan Gejala
Penyelesaian masalah
Peringatan Pastikan untuk mematikan saklar listrik sebelum menghubungkan/mencabut konektor, jika tidak part bisa rusak.
Apakah
Suction suhu udara unit YA
indoor terlalu dingin setelah Termistor penukar panas indoor
operasi pendinginan? diaktifkan. Periksa hal berikut:
Filter udara unit indoor kotor
Penukar panas indoor kotor
TIDAK Aliran udaran tersumbat pada
unit indoor
Fan indoor rusak
Apakah
arus operasi kompresor YA
dan fan outdoor Perlindungan overload atau arus
sangat tinggi? berlebihuntuk kompresor dan fan
outdoor diaktifkan. Periksa hal
TIDAK
berikut:
Penukar panas unit outdoor
kotor
Aliran udaran tersumbat pada
unit outdoor
Fan outdoor rusak
Pengisian refrigerant
berlebih. Kosongkan dan ganti
dengan jumlah refrigeran yang
sesuai.
Apakah
suhu pipa discharge YA Termostat Pipa discharge
kompresor sangat diaktifkan. Periksa hal berikut:
tinggi? Kekurangan Refrigerant atau
sistem refrigeran tersumbat.
TIDAK Periksa tekanan sistem operasi
dan temukan penyebab
kebocoran atau penyumbatan
refrigeran, lalu isi dengan
jumlah refrigeran yang sesuai.
Diagnosa Servis
37
Pemecahan Masalah Bedasarkan Gejala SiMT281501EA
Penyelesaian masalah
Peringatan Pastikan untuk mematikan saklar listrik sebelum menghubungkan/mencabut konektor, jika tidak part bisa rusak.
Apakah YA
unit mulai beroperasi Normal. Unit dalam modus siaga 3
setelah 3 menit? menit.
Sistem
TIDAK kelistrikan
Tegangan
catu daya dalam ± 10% dari TIDAK
Hubungi perusahaan listrik
tegangan yang
ditentukan
Apakah
sisi pipa discharge YA
TIDAK
kompresor panas setelah unit Periksa kompresor.
berhenti beroperasi?
Apakah
ada perbedaan suhu TIDAK
antara pipa kapiler pipa kapiler tersumbat
inlet & aoutlet?
YA
Periksa kompresor
38 Diagnosa Servis
SiMT281501EA Pemecahan Masalah Bedasarkan Gejala
Penyelesaian masalah
Peringatan Pastikan untuk mematikan saklar listrik sebelum menghubungkan/mencabut konektor, jika tidak part bisa rusak.
TIDAK TIDAK
Apakah
terbentuk es di Apakah
sekitar port inlet pengubah YA YA
Arus kurang dari tingkat yang Kekurangan refrigeran berpotensi
panas atau di port outlet ditentukan? menyebabkan masalah. Setelah
pipa kapiler? vakum kering, isi jumlah refrigeran
TIDAK dengan benar
TIDAK
.
TIDAK
Apakah
YA Kemungkinan penyebab sbb:
tingkat Tekanan tinggi lebih
tinggi dari normal? Overcharge refrigeran
Penukar panas kotor Periksa setiap item
Sirkuit pendek dari udara discharge
TIDAK Penyumbatan aliran udara
Motor Fan unit outdoor rusak
Kemungkinan penyebab sbb:
Kompresi kompresor tidak cukup
Periksa setiap item
sirkulasi refrigeran tidak cukup
katup ekspansi rusak
Diagnosa Servis 39
Pemecahan Masalah Bedasarkan Gejala SiMT281501EA
Penyelesaian masalah
Peringatan Pastikan untuk mematikan saklar listrik sebelum menghubungkan/mencabut konektor, jika tidak part bisa rusak.
Apakah
Temperatur ruangan lebih
YA
tinggi dari suhu yang di set Lanjutkan pengoperasian unit
pada operasi
pendinginan?
TIDAK
Apakah
TIDAK
unit mengeluarkan Normal
kabut putih?
YA
TIDAK
Apakah area YA
„ instalasi berdebu atau ada kabut Hilangkan sumber debu atau kabut
minyak padat? minyak.
TIDAK
40
Diagnosa Servis
SiMT281501EA Pemecahan Masalah Bedasarkan Gejala
Penyelesaian masalah
Peringatan Pastikan untuk mematikan saklar listrik sebelum menghubungkan/mencabut konektor, jika tidak part bisa rusak.
Apakah ada
Kebisingan disertai Betulkan instalasi
dengan getaran Perkuat langit-langit atau dinding.
langit-langit?
TIDAK
Apakah ada
kebisingan disertai dengan Masukkan shock absorber di
getaran bagian bagian pemasangan, atau perkuat
unit? bagian pemasangan
Suara pelan
TIDAK YA
terdengar selama operasi Normal. Ini adalah suara flushing
pendinginan gas refrigeran pada unit AC.
Suara keluar YA
sesaat setelah mulai/berhenti Normal. Ini adalah suara yang
operasi. dihasilkan pada saat gas
(refrigerant) berubah aliran atau
berhenti
Apakah TIDAK
YA
fan menyentuh bagian berhenti.dan betulkan bagian yang
Bongkar
lainnya? tersentuh.
TIDAK
Suara keluar
YA
Selama proses pendinginan Normal. Suara dari operasi
atau setelah berhenti pengurasan
operasi.
TIDAK
Diagnosa Servis 41
Pemecahan Masalah Bedasarkan Gejala SiMT281501EA
Penyelesaian masalah
Peringatan Pastikan untuk mematikan saklar listrik sebelum menghubungkan/mencabut konektor, jika tidak part bisa rusak.
Apakah
masalah muncul ketika YA
Operasi dimulai lagi setelah Debu yang terkumpul di dalam unit
Jangka panjang? indoor ditiup keluar.
Bersihkan bagian dalam unit indoor
TIDAK
Apakah terpasang YA
Debu yang terkumpul di dalam unit
filter udara? indoor ditiup keluar.
Bersihkan bagian dalam unit indoor
TIDAK
Diagnosa Servis
42
SiMT281501EA Penyelesaian Masalah berdasarkan LED pada Unit Indoor
Catatan: 1. Ketika tombol INSPEKSI / TES pada remote kontrol ditekan, layar INSPEKSI berkedip
memasuki modus INSPEKSI.
2. Dalam mode INSPEKSI, ketika tombol ON / OFF ditekan dan ditahan selama 5 detik atau
lebih, tampilan histori kerusakan adalah off. Dalam hal ini, setelah kode kerusakann berkedip
dua kali, tampilan kode berubah menjadi 00 (Normal) dan unit No. berubah menjadi 0. Mode
INSPEKSI secara otomatis beralih ke mode normal (display Set temperatur).
3. Operasi terhenti karena kerusakan tergantung pada model dan kondisi.
4. Penyelesaian masalah dengan mematikan listrik selama minimal 5 detik, diaktifkan kembali,
dan kemudian mengecek kembali tampilan LED.
Diagnosa Servis
43
Fungsi Cek Servis SiMT281501EA
Catatan:
Operasi bila terjadi kerusakan mungkin berbeda menurut model.
44 Diagnosa Servis
SiMT281501EA Penyelesaian Masalah berdasarkan Kode Kerusakan
Kondisi Kerusakan terjadi ketika data dari EEPROM tidak diterima dengan benar.
Penentu
Kerusakan EEPROM (Electrically Erasable Programmable Read Only Memory): Sebuah chip memori
yang menyimpan isinya tanpa daya. Dapat terhapus, baik di dalam komputer atau secara
eksternal dan biasanya membutuhkan tegangan lebih besar untuk penghapusan dari +5 volt
umum yang digunakan dalam sirkuit. Ini berfungsi seperti RAM non-volatile, tetapi menulis ke
EEPROM lebih lambat daripada menulis ke RAM
Penyelesaian masalah
Peringatan Pastikan untuk mematikan saklar listrik sebelum menghubungkan/mencabut konektor, jika tidak part bisa rusak.
TIDAK
Normal reset? Ganti PCB Unit Indoor.
YA
Diagnosa Servis 45
Penyelesaian Masalah berdasarkan Kode Kerusakan SiMT281501EA
Metode Deteksi Kerusakan dideteksi oleh limit switch ketika motor berubah.
Kerusakan
Kondisi Keputusan Ketika ON / OFF dari mikro-switch untuk deteksi posisi tidak dapat dibalik meskipun
Kerusakan flap swing motor diberi energiselama jumlah waktu tertentu (sekitar 30 detik).
Penyelesaian masalah
Peringatan Pastikan untuk mematikan saklar listrik sebelum menghubungkan/mencabut konektor, jika tidak part bisa rusak.
Apakah
TIDAK
konektor terkoneksi Sambungkan konektor dengan
dengan benar? benar.
FHNQ: H7,H8
YA
Apakah TIDAK
limit switch transfer terkoneksi Sambungkan konektor dengan
dengan benar? benar.
YA
TIDAK
TIDAK
TIDAK
220-240 VAC? Ganti PCB Unit Indoor
YA
46 Diagnosa Servis
SiMT281501EA Penyelesaian Masalah berdasarkan Kode Kerusakan
Kondisi Keputusan Thermistor terputus atau korsleting saat unit sedang berjalan.
Kerusakan
Penyelesaian masalah
Peringatan Pastikan untuk mematikan saklar list rik sebelum menghubungkan/mencabut konektor, jika tidak part bisa rusak.
Apakah TIDAK
termistor normal? Ganti termistor
(*1)
YA
Jika kontak OK, ganti PCB unit
outdoor
Diagnosa Servis
47
Penyelesaian Masalah berdasarkan Kode Kerusakan SiMT281501EA
48 Diagnosa Servis
SiMT281501EA Penyelesaian Masalah berdasarkan Kode Kerusakan
Metode Deteksi Bahkan jika thermistor remote kontrol rusak, sistem dapat dikontrol oleh thermistor sistem.
Kerusakan Eror terdeteksi berdasarkan suhu thermistor remote kontrol.
Kondisi Keputusan Eror dihasilkan ketika thermistor remote kontrol menjadi terputus atau korsleting ketika unit
Kerusakan sedang berjalan.
Penyelesaian masalah
Peringatan Pastikan untuk mematikan saklar listrik sebelum menghubungkan/mencabut konektor, jika tidak part bisa rusak.
Apakah
CJ ditampilkan pada YA
Ganti remot kontrol
remote kontrol?
TIDAK
Diagnosa Servis 49
Penyelesaian Masalah berdasarkan Kode Kerusakan SiMT281501EA
Metode Deteksi Aktivasi setiap perangkat keselamatan dideteksi oleh sirkuit input perangkat keselamatan.
Kerusakan (Perangkat keamanan kerusakan terpadu)
Penyelesaian masalah
Peringatan Pastikan untuk mematikan saklar listrik sebelum menghubungkan/mencabut konektor, jika tidak part bisa
rusak.
Apakah
kabel utama perangkat
TIDAK
pengaman terhubung dengan Sambungkan dengan benar
benar ke PCB unit
outdoor?
YA
Cari perangkat pengaman dengan
kontak terbuka.
50
Diagnosa Servis
SiMT281501EA Penyelesaian Masalah berdasarkan Kode Kerusakan
Dari halaman
sebelumnya A
Perangkat pengaman
Nama Model Catu Daya
Q1 Q1M Q2M Q1RP S1PL S1PH
RNQ26MV1(4)(9) 1 Fasa ● — — — — ●
RNQ30MV1(4) 220-240 V — ● — — — ●
50 Hz
RNQ36MV1(4) — ● ● — — ●
RNQ26MY1(4) ● — — ● — ●
RNQ30MY1(4) 3 Fasa — ● — ● — ●
RNQ36MY1(4) 380-415 V — ● ● ● — ●
50 Hz
RNQ42MY1(4) ● ● ● ● ● ●
RNQ48MY1(4) ● ● ● ● ● ●
●: ada
—: tidak ada
Diagnosa Servis
51
Penyelesaian Masalah berdasarkan Kode Kerusakan SiMT281501EA
Metode Deteksi Micro-computer memeriksa apakah transmisi antara Unit Indoor and Remot Kontrol normal.
Kerusakan
Penyelesaian masalah
Peringatan Pastikan untuk mematikan saklar listrik sebelum menghubungkan/mencabut konektor, jika tidak part bisa rusak.
Dikontrol Kedua
YA YA
dengan 2 remot kontrol? remot kontrol di set ke Set satu remot kontrol ke ‘sub”,
“utama”? matikan catu daya sementara, lalu
restart operasi
TIDAK TIDAK
YA
Eror bisa terjadi karena kebisingan.
Periksa area sekitar lalu restart
operasi.
Menggunakan
transmisi kabel multi-core YA
antara unit indoor dan Ganti ke kabel double-core terpisah
remot kontrol?
TIDAK
52
Diagnosa Servis
SiMT281501EA Penyelesaian Masalah berdasarkan Kode Kerusakan
Metode Deteksi Dinilai dari Sirkuit PCB untuk mendeteksi kesalahan pengkabelan
Kerusakan
Penyelesaian masalah
Peringatan Pastikan untuk mematikan saklar listrik sebelum menghubungkan/mencabut konektor, jika tidak part bisa rusak.
Apakah TIDAK
UF ditampilkan pada Faktor eksternal (kebisingan, dll)
remot kontrol?
YA
Diagnosa Servis 53
SiMT281501EA
Bagian 7
Lampiran
1. Diagram Pemipaan................................................................................ 55
1.1 FHNQ26MV1(4) + RNQ26MV1(4)(9)
FHNQ26MV1(4) + RNQ26MY1(4)....................................................... 55
1.2 FHNQ30MV1(4) + RNQ30MV1(4)
FHNQ30MV1(4) + RNQ30MY1(4)
FHNQ36MV1(4) + RNQ36MV1(4)
FHNQ36MV1(4) + RNQ36MY1(4).......................................................... 56
1.3 FHNQ42MV1(4) + RNQ42MY1(4)
FHNQ48MV1(4) + RNQ48MY1(4).......................................................... 57
2. Diagram Pengkabelan........................................................................... 58
2.1 Unit Indoor............................................................................................ 58
2.2 Unit Outdoor (1 Fasa) .......................................................................... 59
2.3 Unit Outdoor (3 Fasa) .......................................................................... 62
54 Lampiran
SiMT281501EA Diagram Pemipaan
1. Diagram Pemipaan
1.1 FHNQ26MV1(4) + RNQ26MV1(4)(9)
FHNQ26MV1(4) + RNQ26MY1(4)
3D087621A
Lampiran
55
Diagram Pemipaan SiMT281501EA
3D087962B
56 Lampiran
SiMT281501EA Diagram Pemipaan
3D087917A
57
Lampiran
Diagram Pengkabelan SiMT281501EA
2. Diagram Pengkabelan
2.1 Unit Indoor
2.1.1 FHNQ26MV1(4) / FHNQ30MV1(4) / FHNQ36MV1(4) / FHNQ42MV1(4) /
FHNQ48MV1(4)
3D052046F
58
Lampiran
SiMT281501EA Diagram Pengkabelan
3D102699
Lampiran 59
Diagram Pengkabelan SiMT281501EA
2.2.2 RNQ30MV1(4)
3D084768D
60
Lampiran
SiMT281501EA Diagram Pengkabelan
2.2.3 RNQ36MV1(4)
3D084357E
Lampiran
61
Diagram Pengkabelan SiMT281501EA
3D085837D
62
Lampiran
SiMT281501EA Diagram Pengkabelan
2.3.2 RNQ30MY1(4)
3D084816E
63
Lampiran
Diagram Pengkabelan SiMT281501EA
2.3.3 RNQ36MY1(4)
3D100617
64
Lampiran
SiMT281501EA Diagram Pengkabelan
3D084694F
Lampiran
65