SiMT281416E

Panduan

Servis

Seri RZR-LV/RZR-LU
Pendingin Saja R410A 50Hz
RZR50-140LVVM(4) RZR100-140LUY1(4)
SiMT281416E

Seri RZR-LV/LU
Pendingin Saja
R410A 50Hz
Referensi Data Teknik
Untuk item di bawah ini, silakan lihat Data Teknik.
No. Item No. Data Teknik Halaman Keterangan
1 Spesifikasi EDMT281406 Hal. 13~74
2 Daftar Opsional EDMT281406 Hal. 235~241

1. Pendahuluan ..............................................................................................iv
1.1 Tindakan Pencegahan Keselamatan .................................................... iv
1.2 Ikon yang Digunakan ......................................................................... viii

Bagian 1 Informasi Umum ............................................................1


1. Nama Model Unit Indoor/Outdoor ............................................................. 2
2. Tampilan Eksternal .................................................................................... 4

Bagian 2 Fungsi ............................................................................6


1. Fungsi ......................................................................................................... 7

Bagian 3 Remote Control ..............................................................8


1. Remote Control Berkabel .......................................................................... 9
1.1 Model yang Diaplikasikan .....................................................................9
1.2 Nama dan Fungsi .................................................................................9
1.3 Pengaturan UTAMA/SUB jika Menggunakan 2 Remote Control ...........14
1.4 Pengaturan No. Grup Kontrol Terpusat ...............................................15
2. Remote Control Nirkabel ......................................................................... 17
2.1 Model yang Diapliaksikan ...................................................................17
2.2 Nama dan Fungsi ...............................................................................17
2.3 Pengaturan Alamat dan UTAMA/SUB .................................................19
3. Mode Layanan.......................................................................................... 21
3.1 BRC1C61/BRC1D61...........................................................................21
3.2 BRC1E62 ...........................................................................................23
4. Mode Pemeriksaaan ................................................................................ 25
4.1 BRC1C61/BRC1D61...........................................................................25

Bagian 4 Fungsi and Kontrol....................................................... 26

i Table of Contents
SiMT281416E
1. Fungsi Komponen Utama dan Termistor................................................ 27
2. Bagan Alur Operasi.................................................................................. 31
2.1 Operasi Pendinginan/Kering ...............................................................31
3. Detail Fungsi ............................................................................................ 32
3.1 Unit Indoor..........................................................................................32
3.2 Unit Outdoor .......................................................................................37

Bagian 5 Pengaturan Lapangan .................................................. 52


1. Operasi Uji coba....................................................................................... 53
1.1 Pemeriksaan Operasi Uji coba ............................................................53
2. Pengaturan Lapangan dari Remote Control........................................... 54
2.1 Remote Control Berkabel ....................................................................54
2.2 Remote Control Nirkabel .....................................................................57
2.3 Isi Pengaturan dan No. Kode untuk Unit Indoor ...................................58
2.4 Isi Pengaturan dan No. Kode untuk Unit Outdoor ................................59
3. Pengaturan Lapangan dari Demand Adaptor
(Untuk selain RZR50-71LVVM(4)) .......................................................... 62
3.1 Fungsi i-Demand ................................................................................62
4. Pengaturan Lapangan dari PCB Unit Outdoor
(Untuk RZR100-140LVVM(4), RZR100-140LUY1(4)) ........................... 63
4.1 Pengaturan dengan Tombol BS ..........................................................63
4.2 Mode Pengaturan 1 ............................................................................63
4.3 Mode Pengaturan 2 ............................................................................64
4.4 Mode Monitor .....................................................................................66
4.5 Daftar Isi Coba Lagi dan Kesalahan ....................................................67
5. Operasi Darurat ........................................................................................ 69

Bagian 6 Diagnosis Layanan ....................................................... 71


1. Pemeriksaan Pemeliharaan .................................................................... 73
1.1 Ikhtisar ...............................................................................................73
2. Pemecahan Masalah Berdasarkan Gejala ............................................. 75
2.1 Ikhtisar ...............................................................................................75
2.2 Peralatan tidak Berfungsi ....................................................................76
2.3 Kipas Unit Indoor Berfungsi, tapi Kompresor tidak Berfungsi................77
2.4 Operasi Pendinginan Mulai tapi Langsung Berhenti .............................78
2.5 Setelah Unit Mati, tidak Bisa Direstart untuk Beberapa Saat ................79
2.6 Peralatan Berfungsi tapi tidak Memberikan Pendinginan......................81
2.7 Peralatan Mengeluarkan Kabut Putih ..................................................82
2.8 Peralatan Mengeluarkan Suara atau Goncangan Keras.......................83
2.9 Peralatan Mengeluarkan Debu ............................................................85
2.10 LCD Remote Control Menampilkan “88”...............................................85
2.11 Sirip Sayap Ayun tidak Berfungsi ........................................................86
3. Pemecahan Masalah Berdasarkan Indikasi LED ................................... 88
3.1 Pemecahan Masalah Berdasarkan LED pada Unit Indoor...................88
3.2 Pemecahan Masalah Berdasarkan LED pada PCB Unit Outdoor ........88
4. Pemecahan Masalah Berdasarkan Remote Control ............................ 89
4.1 Operasi Akses Mode...........................................................................89
4.2 Prosedur Diagnosis Sendiri dengan Remote Control ...........................90
4.3 Kode Kesalahan dan Deskripsi ...........................................................94
4.4 Kode Kesalahan - Sub Kode ...............................................................95
4.5 Alat Pengaman ...................................................................................98

Table of Contents ii
SiMT281416E
5. Pemecahan Masalah Berdasarkan Indikasi pada Remote Control ..... 99
5.1 Kesalahan Alat Pelindung Eksternal ....................................................99
5.2 Kelainan PCB Unit Indoor ................................................................. 100
5.3 Kelainan Sistem Permukaan Air Buang ............................................. 101
5.4 Kelainan Motor Kipas Unit Indoor ...................................................... 102
5.5 Kelainan Motor Sirip Sayap Ayun/Terkunci ........................................ 104
5.6 Tegangan Catu Daya tidak Normal.................................................... 106
5.7 Kelainan Sistem Buang .................................................................... 107
5.8 Kelainan Pengaturan Kapasitas ........................................................ 109
5.9 Kelainan Termistor............................................................................ 110
5.10 Kesalahan Gabungan antara PCB Unit Indoor dan PCB Kipas ......... 111
5.11 Kelainan Sistem Sensor Kelembaban ............................................... 112
5.12 Termistor Suhu Ruang pada Kelainan Remote Control ...................... 113
5.13 Kelainan PCB Unit Outdoor............................................................... 114
5.14 Kelainan Tekanan Tinggi (Terdeteksi oleh Saklar Tekanan Tinggi)….115
5.15 Motor Kompresor Terkunci ............................................................... 117
5.16 Kelainan Motor Kipas Unit Outdoor ................................................... 118
5.17 Kelainan Katup Ekspansi Elektronik ................................................. 120
5.18 Kelainan Suhu Pipa Buang ............................................................... 123
5.19 Kelainan Sistem Saklar Tekanan Tinggi ............................................ 125
5.20 Kelainan Sistem Termistor ................................................................ 126
5.21 Kelainan Sensor Tekanan ................................................................. 127
5.22 Kelainan PCB Unit Outdoor............................................................... 128
5.23 Suhu Sirip Radiasi Meningkat ........................................................... 130
5.24 Kelebihan Arus Output DC (Instan) ................................................... 132
5.25 Panas Elektronik (Jeda Waktu) ......................................................... 134
5.26 Pencegahan Berhenti (Jeda Waktu) .................................................. 136
5.27 Kelainan Sistem Transmisi antara PCB Unit Outdoor......................... 138
5.28 Fasa Terbuka atau Ketidakseimbangan Tegangan Catu Daya ........... 139
5.29 Kelainan Termistor Sirip Radiasi ....................................................... 140
5.30 Kelainan Pengaturan Kapasitas ........................................................ 141
5.31 Kekurangan Refrigeran (Kesalahan) ................................................. 142
5.32 Kelainan Tegangan Catu Daya ......................................................... 143
5.33 Kesalahan Transmisi antara Unit Indoor dan Outdoor ........................ 144
5.34 Kesalahan Transmisi antara Unit Indoor dan Remote Control ............ 147
5.35 Kesalahan Transmisi antara Remote Control UTAMA dan SUB remote
control .............................................................................................. 148
5.36 Kelainan Saklar Pengaturan Lapangan ............................................. 149
5.37 Kesalahan Pengaturan Alamat Terpusat ........................................... 150
5.38 Kesalahan Transmisi antara Unit Indoor dan Outdoor/Pipa dan Kabel
tidak Cocok/Kekurangan Refrigeran .................................................. 151

Bagian 7 Lampiran .................................................................... 161


1. Diagram Pengkabelan ........................................................................... 162
1.1 Unit Indoor........................................................................................ 162
1.2 Unit Outdoor ..................................................................................... 169

i Table of Contents
SiMT281416E Introduction

1. Pendahuluan
1.1 Petunjuk Keselamatan
Kewaspadaan  Pastikan untuk membaca petunjuk keselamatan berikut ini sebelum melakukan
dan perbaikan.
Peringatan  Simbol-simbol kewaspadaan diklasifikasikan kedalam “ Peringatan” dan “
Perhatian”.“ Peringatan” sangat penting karena dapat menyebabkan kematian
atau cedera serius jika tidak diikuti dengan benar. Simbol “ Perhatian” dalam
kondisi tertentu juga dapat menimbulkan kecelakaan yang serius jika tidak dipatuhi.
Oleh karena itu, pastikan memperhatikan semua simbol petunjuk keselamatan yang
dijelaskan berikut ini.
 Piktogram
Simbol ini menunjukkan hal-hal yang harus dilakukan dengan hati-hati.
Piktogram menunjukkan hal-hal yang harus diperhatikan.
Simbol ini menunjukkan tindakan yang dilarang.
Hal atau tindakan yang dilarang ditunjukkan dalam ilustrasi atau di dekat simbol.
Simbol ini menunjukkan tindakan yang harus dilakukan, atau petunjuk.
Petunjuk ini ditunjukkan dalam ilustrasi atau di dekat simbol.
 Setelah perbaikan selesai, pastikan untuk melakukan uji coba coba operasi guna
memastikan bahwa peralatan beroperasi secara normal. Jelaskan petunjuk operasi
peralatan tersebut kepada pelanggan.

1.1.1 Kewaspadaan tentang Keselamatan Pekerja


Peringatan

Pastikan untuk mencabut steker kabel listrik dari stop kontak sebelum memperbaiki
peralatan.
Melakukan perbaikan pada peralatan yang terhubung dengan catu daya dapat
menyebabkan sengatan listrik. Jika peralatan memerlukan catu daya untuk melakukan
perbaikan atau memeriksa sirkuit, jangan menyentuh bagian yang bermuatan listrik.

Jangan menyentuh gas refrigeran yang dikeluarkan saat proses perbaikan.


Gas refrigeran dapat menyebabkan radang dingin.

Saat melepas pipa hisap atau pipa buang kompresor di bagian yang dilas, pindahkan
seluruh gas refrigeran ke tempat berventilasi baik.
Jika masih tersisa gas di dalam kompresor, gas refrigeran atau mesin pendingin akan
mengeluarkan minyak saat pipanya dilepas, dan hal itu dapat menyebabkan cedera.

Jika gas refrigeran bocor selama pekerjaan perbaikan, beri ventilasi di area tersebut. Gas
refrigeran dapat menghasilkan gas beracun saat melakukan kontak dengan nyala api.

Jika terjadi kebocoran gas refrigan saat perbaikan, alirkan udara ke area tersebut.
Gas refrigeran dapat menghasilkan gas beracun jika terkena api.

Jangan menyalakan atau mematikan AC dengan mencolokkan atau mencabut steker


kabel listrik.
Mencolokkan atau mencabut steker kabel listrik untuk mengoperasikan peralatan dapat
menimbulkan sengatan listrik atau kebakaran.

Table of Contents ii
SiMT281416E Introduction

Peringatan

Pastikan untuk menggunakan helm pengaman, sarung tangan dan sabuk keselamatan
saat bekerja di tempat yang tinggi (lebih dari 2 meter)
Tindakan keselamatan yang kurang memadai dapat menyebabkan kecelakaan terjatuh.

Untuk model refrigeran R410A, pastikan menggunakan pipa, mur penyambung dan alat
khusus yang digunakan untuk refrigeran R410A.
Penggunaan material untuk model refrigeran R22 dapat menimbulkan kecelakaan serius,
seperti kerusakan siklus refrigeran dan kerusakan peralatan.

Perhatian

Jangan memperbaiki komponen listrik dengan tangan yang basah.


Melakukan perbaikan dengan tangan yang basah dapat menyebabkan sengatan listrik.

Jangan membersihkan AC dengan memercikkan air.


Mencuci AC dengan air dapat menyebabkan sengatan listrik.

Pastikan melakukan pembumian saat memperbaiki peralatan di tempat yang basah atau
lembab untuk menghindari sengatan listrik.

Pastikan untuk mematikan AC dan mencabut kabel listrik saat membersihkan peralatan
tersebut.
Kipas internal berputar dengan kecepatan tinggi dan dapat menyebabkan cedera.

Pastikan melakukan perbaikan dengan alat-alat yang sesuai.


Penggunaan peralatan yang tidak sesuai dapat menyebabkan cedera.

Pastikan memeriksa bahwa siklus pendinginan sudah cukup dingin sebelum melakukan
perbaikan.
Perbaikan pada AC saat bagian siklus pendinginan dapat meyebabkan luka bakar.

Gunakan las di tempat yang berventilasi baik.


Penggunaan las di ruang tertutup dapat menyebabkan kekurangan oksigen.

v
Introduction SiMT281416E

1.1.2 Petunjuk Keselamatan Pengguna


Peringatan

Pastikan menggunakan komponen yang tercantum dalam daftar komponen servis dari
model yang tersedia dan alat yang cocok untuk melakukan pekerjaan perbaikan. Jangan
mencoba memodifikasi peralatan tersebut.
Penggunaan komponen atau alat yang tidak sesuai dapat menimbulkan sengatan listrik,
panas berlebih atau kebakaran.

Jika kabel listrik dan kabel lead tergores atau rusak, pastikan untuk menggantinya.
Kabel dan kawat yang rusak dapat menimbulkan sengatan listrik, panas berlebih atau
kebakaran.

Jangan menggunakan kabel listrik sambungan atau kabel perpanjangan, atau membagi
stopkontak yang sama dengan peralatan listrik lain, karena dapat menimbulkan sengatan
listrik, panas berlebih atau kebakaran.

Pastikan menggunakan sirkuit listrik khusus untuk peralatan, dan mengikuti standar teknis
setempat terkait dengan peralatan listrik tersebut, peraturan pengkabelan internal, dan
panduan petunjuk pemasangan ketika melakukan pekerjaan listrik.
Kapasitas sirkuit listrik yang tidak memadai dan pekerjaan listrik yang tidak tepat dapat
menimbulkan sengatan listrik atau kebakaran.

Pastikan menggunakan kabel khusus untuk pengkabelan antara unit indoor dan outdoor.
Buat sambungan yang aman dan atur jalur kabel dengan tepat sehingga tidak ada
kekuatan yang menarik kabel di terminal sambungan.
Sambungan yang tidak benar dapat menimbulkan panas berlebih atau kebakaran.

Ketika melakukan pengkabelan antara unit indoor dan outdoor, pastikan penutup terminal
tidak terangkat atau turun akibat kabel.
Jika penutup tidak terpasang dengan benar, bagian ujung sambungan dapat menimbulkan
sengatan listrik, panas berlebih atau kebakaran

Jangan merusak atau memodifikasi kabel listrik.


Kabel listrik yang rusak atau dimodifikasi dapat menimbulkan sengatan listrik atau
kebakaran. Menempatkan benda berat di atas kabel listrik, dan memanasi atau menarik
kabel listrik dapat merusak kabel.

Jangan mencampur udara atau gas selain dari refrigeran yang ditentukan (R410A/R22)
dalam sistem refrigeran.
Jika udara memasuki sistem pendingin, maka akan menimbulkan tekanan tinggi yang
berlebihan, yang menyebabkan kerusakan peralatan dan cedera.

Jika gas refrigeran bocor, pastikan untuk menemukan titik kebocoran dan
memperbaikinya sebelum mengisi refrigeran. Setelah mengisi refrigeran, pastikan tidak
ada kebocoran refrigeran.
Jika titik kebocoran tidak dapat ditemukan dan pekerjaan perbaikan harus dihentikan,
pastikan untuk melakukan pump down dan menutup katup servis, untuk mencegah gas
refrigeran yang bocor masuk ke dalam ruang. Gas refrigeran tidak berbahaya, tetapi dapat
menghasilkan gas beracun ketika terkena nyala api, seperti kipas dan pemanas lainnya,
tungku dan kompor

Ketika memindahkan peralatan, pastikan bahwa lokasi pemasangan yang baru memiliki
kekuatan yang memadai untuk menahan bobot peralatan.
Jika lokasi pemasangan tersebut tidak memiliki kekuatan yang memadai dan jika
pekerjaan instalasi tidak dilakukan dengan aman, peralatan bisa jatuh dan menyebabkan
cedera.

vi
SiMT281416E Introduction

Peringatan

Periksalah guna memastikan bahwa steker kabel listrik tidak kotor atau longgar, kemudian
masukkan steker ke stopkontak dengan aman.
Jika steker berdebu atau sambungannya longgar, dapat menimbulkan sengatan listrik
atau kebakaran.

Hanya untuk tipe


unit tertentu
Pastikan memasang produk secara benar dengan menggunakan rangka pemasangan
standar yang disediakan.
Penggunaan rangka pemasangan yang tidak tepat dan pemasangan yang tidak benar
dapat menyebabkan peralatan jatuh, yang mengakibatkan cedera.

Hanya untuk tipe unit


tertentu
Pastikan memasang produk dengan aman dalam rangka pemasangan yang dipasang
pada rangka jendela.
Jika unit tidak terpasang dengan aman, unit bisa jatuh dan menyebabkan cedera.

Ketika mengganti baterai koin di remote control, pastikan membuang baterai lama agar
tidak tertelan anak kecil.
Jika baterai koin tertelan oleh anak kecil, segera periksakan ke dokter.

Perhatian

Dalam beberapa kasus, pemasangan pemutus kebocoran diperlukan untuk mencegah


sengatan listrik, bergantung pada kondisi lokasi pemasangan.

Jangan memasang peralatan di tempat yang memiliki kemungkinan kebocoran gas


mudah terbakar.
Jika gas yang mudah terbakar bocor dan berada di sekitar unit, gas tersebut dapat
menyebabkan kebakaran.

Periksalah untuk mengetahui apakah komponen dan kabel telah terpasang dan
tersambung dengan benar, dan apakah sambungan di ujung telah disolder atau
dirapatkan dengan aman.
Pemasangan dan sambungan yang tidak tepat dapat menimbulkan panas berlebihan,
kebakaran atau sengatan listrik.

Jika landasan pemasangan atau rangka telah berkarat, gantilah.


Landasan atau rangka pemasangan yang berkarat dapat menyebabkan unit jatuh,
mengakibatkan cedera.

Periksa pembumian, dan perbaiki jika peralatannya tidak dibumikan dengan benar.
Pembumian yang tidak tepat dapat menimbulkan sengatan listrik.

vii
Introduction SiMT281416E

Perhatian

Pastikan mengukur tahanan isolasi setelah perbaikan, dan pastikan bahwa tahanannya
sebesar 1 Matau lebih besar.
Isolasi yang rusak dapat menimbulkan sengatan listrik.

Pastikan memeriksa saluran air unit indoor setelah perbaikan.


Saluran air yang rusak dapat menyebabkan air masuk ke ruang dan membasahi perabot
dan lantai.

Jangan memiringkan unit saat memindahkannya.


Air yang ada di dalam unit tersebut dapat tumpah dan membasahi perabot, serta lantai.

Hanya untuk tipe unit


tertentu
Pastikan memasang kemasan dan segel pada rangka pemasangan dengan benar.
Jika kemasan dan segel tidak terpasang dengan benar, air dapat memasuki ruang dan
membasahi perabot serta lantai.

1.2 Ikon yang Digunakan


Ikon berikut digunakan untuk menarik perhatian pembaca pada informasi khusus . Arti ikon dijelaskan
dalam tabel di bawah:

Ikon Jenis Deskripsi


Informasi

Catatan “Catatan” memberikan informasi yang tidak terlalu diperlukan, tetapi


Catatan: mungkin tetap berharga bagi pembaca, seperti tips dan trik.

“Perhatian” digunakan ketika ada bahaya bahwa pembaca, melalui


Perhatian manipulasi yang salah, dapat merusak peralatan, hilangnya data,
Perhatian memperoleh hasil yang tak terduga atau harus memulai ulang (sebagian
dari) prosedur.

Peringatan “Peringatan” digunakan bila ada bahaya cedera pribadi.


Peringatan

“Referensi” memandu pembaca ke tempat-tempat lain di map atau dalam


Referesi panduan ini, di mana pembaca akan menemukan informasi tambahan
tentang topik tertentu.

viii
SiMT281416E Model Name of Indoor / Outdoor Units

Bagian 1
Informasi Umum
1. Nama Model Unit Indoor/Outdoor ............................................................. 2
2. Tampilan Eksternal .................................................................................... 4

ix General Information
SiMT281416E

1. Nama Model Unit Indoor/Outdoor


Unit indoor Unit outdoor
Intake catu daya
Tipe Nama model Nama model
FCQ50LUV1 RZR50LVVM
FCQ60LUV1 RZR60LVVM
FCQ71LUV1 RZR71LVVM
Unit outdoor: 1 fasa, 220-240V, 50Hz
FCQ100LUV1 RZR100LVVM
FCQ125LUV1 RZR125LVVM
FCQ140LUV1 RZR140LVVM
FCQ50LUV14 RZR50LVVM4
FCQ60LUV14 RZR60LVVM4
FCQ71LUV14 RZR71LVVM4
Unit outdoor: 1 fasa, 220-240V, 50Hz
FCQ100LUV14 RZR100LVVM4
FCQ125LUV14 RZR125LVVM4
FCQ140LUV14 RZR140LVVM4
Tipe ceiling mounted FCQ100LUV1 RZR100LUY1
cassette (Round flow)
FCQ125LUV1 RZR125LUY1 Unit outdoor: 3 fasa, 380-415V, 50Hz
FCQ140LUV1 RZR140LUY1
FCQ100LUV14 RZR100LUY14
FCQ125LUV14 RZR125LUY14 Unit outdoor: 3 fasa, 380-415V, 50Hz
FCQ140LUV14 RZR140LUY14
FCQ60LUV1 x 2 RZR125LVVM
Unit outdoor: 1 fasa, 220-240V, 50Hz
FCQ71LUV1 x 2 RZR140LVVM
FCQ60LUV14 x 2 RZR125LVVM4
Unit outdoor: 1 fasa, 220-240V, 50Hz
FCQ71LUV14 x 2 RZR140LVVM4
FCQ60LUV1 x 2 RZR125LUY1
Unit outdoor: 3 fasa, 380-415V, 50Hz
FCQ71LUV1 x 2 RZR140LUY1
FCQ60LUV14 x 2 RZR125LUY14
Unit outdoor: 3 fasa, 380-415V, 50Hz
FCQ71LUV14 x 2 RZR140LUY14
FHQ50BVV1G RZR50LVVM
FHQ60BVV1G RZR60LVVM
FHQ71BVV1B RZR71LVVM Unit outdoor: 1 fasa, 220-240V, 50Hz
FHQ100BVV1B RZR100LVVM
FHQ125BVV1B RZR125LVVM
FHQ140CAVEB RZR140LVVM Unit outdoor: 1 fasa, 220-240/220-230V, 50/60Hz

FHQ50BVV1G4 RZR50LVVM4
FHQ60BVV1G4 RZR60LVVM4
FHQ71BV1B4 RZR71LVVM4 Unit outdoor: 1 fasa, 220-240V, 50Hz
FHQ100BV1B4 RZR100LVVM4
FHQ125BV1B4 RZR125LVVM4
Tipe ceiling suspended FHQ100BVV1B RZR100LUY1
Unit outdoor: 3 fasa, 380-415V, 50Hz
FHQ125BVV1B RZR125LUY1
FHQ100BV1B4 RZR100LUY14
Unit outdoor: 3 fasa, 380-415V, 50Hz
FHQ125BV1B4 RZR125LUY14
FHQ60BVV1G x 2 RZR125LVVM
Unit outdoor: 1 fasa, 220-240V, 50Hz
FHQ71BVV1B x 2 RZR140LVVM
FHQ60BVV1G4 x 2 RZR125LVVM4
Unit outdoor: 1 fasa, 220-240V, 50Hz
FHQ71BV1B4 x 2 RZR140LVVM4
FHQ60BVV1G x 2 RZR125LUY1
Unit outdoor: 3 fasa, 380-415V, 50Hz
FHQ71BVV1B x 2 RZR140LUY1
FHQ60BVV1G4 x 2 RZR125LUY14
Unit outdoor: 3 fasa, 380-415V, 50Hz
FHQ71BV1B4 x 2 RZR140LUY14

General Information 2
SiMT281416E External Appearance

Unit indoor Unit outdoor


Intake catu daya
Tipe Nama model Nama model
FAQ71CVEA RZR71LVVM Unit outdoor: 1 fasa, 220-240/220-230V, 50/60Hz
FAQ100CVEA RZR100LVVM
Tipe wall mounted
FAQ100CVEA4 RZR100LVVM4 Unit outdoor: 1 fasa, 220-240V, 50Hz
FAQ100CVEA RZR100LUY1 Unit outdoor: 3 fasa, 380-415V, 50Hz
FBQ50DV1 RZR50LVVM
FBQ60DV1 RZR60LVVM
FBQ71DV1 RZR71LVVM Unit indoor: 1 fasa, 220-240V, 50Hz
FBQ100DV1 RZR100LVVM Unit outdoor: 1 fasa, 220-240V, 50Hz
FBQ125DV1 RZR125LVVM
FBQ140DV1 RZR140LVVM
FBQ50DV14 RZR50LVVM4
FBQ60DV14 RZR60LVVM4
FBQ71DV14 RZR71LVVM4 Unit indoor: 1 fasa, 220-240V, 50Hz
FBQ100DV14 RZR100LVVM4 Unit outdoor: 1 fasa, 220-240V, 50Hz
FBQ125DV14 RZR125LVVM4
FBQ140DV14 RZR140LVVM4
Tipe duct connection FBQ100DV1 RZR100LUY1
middle and high static Unit indoor: 1 fasa, 220-240V, 50Hz
pressure FBQ125DV1 RZR125LUY1
Unit outdoor: 3 fasa, 380-415V, 50Hz
FBQ140DV1 RZR140LUY1
FBQ100DV14 RZR100LUY14
FBQ125DV14 RZR125LUY14 Unit indoor: 1 fasa, 220-240V, 50Hz
Unit outdoor: 3 fasa, 380-415V, 50Hz
FBQ140DV14 RZR140LUY14
FBQ60DV1 x 2 RZR125LVVM Unit indoor: 1 fasa, 220-240V, 50Hz
FBQ71DV1 x 2 RZR140LVVM Unit outdoor: 1 fasa, 220-240V, 50Hz
FBQ60DV14 x 2 RZR125LVVM4 Unit indoor: 1 fasa, 220-240V, 50Hz
FBQ71DV14 x 2 RZR140LVVM4 Unit outdoor: 1 fasa, 220-240V, 50Hz
FBQ60DV1 x 2 RZR125LUY1 Unit indoor: 1 fasa, 220-240V, 50Hz
FBQ71DV1 x 2 RZR140LUY1 Unit outdoor: 3 fasa, 380-415V, 50Hz
FBQ60DV14 x 2 RZR125LUY14 Unit indoor: 1 fasa, 220-240V, 50Hz
FBQ71DV14 x 2 RZR140LUY14 Unit outdoor: 3 fasa, 380-415V, 50Hz
FVQ50CVE RZR50LVVM
FVQ60CVE RZR60LVVM
FVQ71CVEB RZR71LVVM Unit outdoor: 1 fasa, 220-240/220-230V, 50/60Hz
FVQ100CVEB RZR100LVVM
FVQ125CVEB RZR125LVVM
FVQ140CVEB RZR140LVVM
FVQ50CVE4 RZR50LVVM4
FVQ60CVE4 RZR60LVVM4
FVQ71CVEB4 RZR71LVVM4
Unit outdoor: 1 fasa, 220-240V, 50Hz
FVQ100CVEB4 RZR100LVVM4
FVQ125CVEB4 RZR125LVVM4
FVQ140CVEB4 RZR140LVVM4
FVQ100CVEB RZR100LUY1
Tipe Floor Standing
FVQ125CVEB RZR125LUY1 Unit outdoor: 3 fasa, 380-415V, 50Hz
FVQ140CVEB RZR140LUY1
FVQ100CVEB4 RZR100LUY14
FVQ125CVEB4 RZR125LUY14 Unit outdoor: 3 fasa, 380-415V, 50Hz
FVQ140CVEB4 RZR140LUY14
FVQ60CVE x 2 RZR125LVVM Unit outdoor: 1 fasa, 220-240/220-230V, 50/60Hz
FVQ71CVEB x 2 RZR140LVVM
FVQ60CVE4 x 2 RZR125LVVM4
Unit outdoor: 1 fasa, 220-240V, 50Hz
FVQ71CVEB4 x 2 RZR140LVVM4
FVQ60CVE x 2 RZR125LUY1
Unit outdoor: 3 fasa, 380-415V, 50Hz
FVQ71CVEB x 2 RZR140LUY1
FVQ60CVE4 x 2 RZR125LUY14
Unit outdoor: 3 fasa, 380-415V, 50Hz
FVQ71CVEB4 x 2 RZR140LUY14

3 General Information
Model Name of Indoor / Outdoor Units SiMT281416E

2. Tampilan Eksternal
Unit Indoor

FCQ FHQ-BV FHQ-CA

FAQ-C FBQ-D FVQ

Remote control
berkabel

BRC1C61 BRC1D61 BRC1E62

General Information 4
SiMT281416E

Remote control
nirkabel

BRC7F633F (untuk FCQ)


BRC7EA66 (untuk FHQ-BV)
BRC7GA56 (untuk FHQ-CA)
BRC7EB519 (untuk FAQ-C)
BRC4C64 (untuk FBQ-D)

Unit penerima sinyal Unit penerima sinyal Unit penerima sinyal


(untuk FCQ) (untuk FHQ-BV) (untuk FHQ-CA)

Unit penerima sinyal Unit penerima sinyal


(untuk FAQ-C) (untuk FBQ-D)

Unit outdoor

RZR125LVVM(4)
RZR50LVVM(4) RZR140LVVM(4)
RZR60LVVM(4) RZR100LVVM(4) RZR100LUY1(4)
RZR71LVVM(4) RZR125LUY1(4)
RZR140LUY1(4)

5 General Information
External Appearance SiMT281416E

Bagian 2
Fungsi
1. Fungsi ......................................................................................................... 7

Functions 6
SiMT281416E

1. Fungsi
Unit indoor FCQ50-140LUV1(4) FHQ50/60BVV1G(4) FHQ140CAVEB FAQ71/100CVEA(4) FBQ50-140DV1(4) FVQ50-140CVEB(4)
FHQ71-125BVV1B
Kategori Fungsi FHQ71-125BV1B4
Unit RZR50-140LVVM(4) RZR50-125LVVM(4) RZR140LVVM RZR71/100LVVM(4) RZR50-140LVVM(4) RZR50-140LVVM(4)
outdoor RZR100-140LUY1(4) RZR100/125LUY1(4) RZR100LUY1 RZR100-140LUY1(4) RZR100-140LUY1(4)
Kontrol inverter      
Ayun otomatis     — 
Pemilihan pola ayun  — — — — —
Fungsi pencegahan aliran udara — — — — — —
(pemanas)
Aliran udara ke atas dan ke bawah — — — — — 
independen
Kecepatan kipas yang bisa diatur (2 step) (2 step) (3 steps) (3 step) (2 step)  (3 step)
Laju aliran udara otomatis — — — (*5) — (*5)
Mode kecepatan kipas tinggi — — —  — (*8)
Program “Kering”      
Kenyaman Aplikasi plafon tinggi  (*7) (*7-2) — — —
an Dua sensor-suhu yang bisa dipilih (*1)      
Pemanasan dimulai (setelah pencairan) — — — — — —

Penerapan pendinginan sepanjang tahun — — — — — —


Operasi senyap malam (*2)      
Auto reset setpoint (*5)      
Set rentang setpoint (*5)      
Jadwal timer mingguan (*3) (*3) (*3) (*3) (*3) (*5)
Remote
control Timer mati (diprogram) (*5)      
Timer nyala/mati (*6)      
Filter udara antibakteri    — (*4) 
Filter udara tahan jamur — — —  — —

Kebersihan Drain pan antibakteri ion perak  — — —  —


Drain pan tahan jamur — — — — — —
Mekanisme pompa kuras  (*4) (*4) (*4)  —
Sebelum diisi sampai 30 m (*2)      
Sebelum diisi sampai 10 m (*2) — — — — — —
Filter tahan lama    — (*4) 
Tanda filter      

Kerja Pencegahan plafon kotor  — — — — —


dan Deteksi tekanan gas rendah (*2)      
layanan
Operasi darurat      
Fungsi diagnosis sendiri      
Restart otomatis      
Beralih ke pendinginan/pemanasan — — — — — —
otomatis
Kontrol dengan 2 remote control      
Kontrol grup dengan 1 remote control      
Kontrol perintah eksternal      
Fitur
kontrol Remote control pusat      
Kontrol interlock      
Standar komunikasi DIII-NET  —    
Filter efisiensi tinggi  — — —  —
Filter yang sangat tahan lama  — — — — —
Opsional
Kit intake udara segar  —  — — —

Lain-lain Penukar panas anti korosi (*2)      

Catatan: : Berfungsi
—: Tidak berfungsi
*1: Bisa diaplikasikan jika menggunakan remote control berkabel
*2: Untuk unit outdoor
*3: Bisa diaplikasikan untuk penggunaan BRC1D61 atau BRC1E62
*4: Opsional
*5: Bisa diaplikasikan untuk penggunaan BRC1E62
*6: Bisa diaplikasikan untuk penggunaan BRC1C61
*7: Bisa dipasang pada ketinggian plafon maks. 3,5 m

7 Functions
Functions SiMT281416E
*7-2: Bisa dipasang pada ketinggian plafon maks. 4,3 m
*8: Bisa diaplikasikan untuk FVQ50-100

Functions 8
Functions SiMT281416E

Bagian 3
Remote Control
1. Remote Control Berkabel .......................................................................... 9
1.1 Model yang Diaplikasikan .....................................................................9
1.2 Nama dan Fungsi .................................................................................9
1.3 Pengaturan UTAMA/SUB jika Menggunakan 2 Remote Control ...........14
1.4 Pengaturan No. Grup Kontrol Terpusat ...............................................15
2. Remote Control Nirkabel ......................................................................... 17
2.1 Model yang Diaplikasikan ...................................................................17
2.2 Nama dan Fungsi ...............................................................................17
2.3 Pengaturan Alamat dan UTAMA/SUB .................................................19
3. Mode Layanan.......................................................................................... 21
3.1 BRC1C61/BRC1D61...........................................................................21
3.2 BRC1E62 ...........................................................................................23
4. Mode Pemeriksaan .................................................................................. 25
4.1 BRC1C61/BRC1D61...........................................................................25

Remote Controller 8
SiMT281416E Wired Remote Controller

1. Remote Control Berkabel


1.1 Model yang Diaplikasikan
Seri Model FCQ FHQ FAQ FBQ-D FVQ
Remote Control BRC1C61
Remote Control Berkabel dengan Jadwal BRC1D61
Timer Mingguan
Navigasi Remote Control BRC1E62

1.2 Nama dan Fungsi


1.2.1 BRC1C61
5 4 2 1

3
7 9
6 11
10
8 13
14 21
20

19

16 15 17 18 22
TOMBOL ON/OFF TAMPILAN TIDAK-BERFUNGSI
Tekan tombol ON/OFF maka sistem akan mulai.
1
Tekan tombol ON/OFF lagi maka sistem akan Jika fungsi tertentu tidak tersedia, ketika tombol ditekan akan
berhenti. menampilkan kata "TIDAK TERSEDIA" selama beberapa
LAMPU OPERASI (MERAH) detik.
2
Lampu menyala selama operasi. 13 Saat menghidupkan beberapa unit sekaligus, pesan "TIDAK
TAMPILAN (SEDANG DIKONTROL TERSEDIA" hanya akan muncul jika tidak ada unit indoor
3 TERPUSAT) yang dilengkapi dengan fungsi. Meskipun ada 1 unit yang
Ketika tampilan ini muncul, sIstem dalam keadaan dilengkapi dengan fungsi, tampilan tidak akan muncul.
SEDANG DIKONTROL TERPUSAT.
TAMPILAN TOMBOL MODE TIMER MULAI/BERHENTI
(VENTILASI/ PEMBERSIHAN UDARA) 14
4 Tampilan ini menunjukkan bahwa pengubahan
panas total dan unit pembersih udara beroperasi (ini TOMBOL TIMER ON/OFF
adalah aksesori opsional). 15
TAMPILAN (MODE TOMBOL PEMERIKSAAN/OPERASI UJI COBA
OPERASI)
Tampilan ini menunjukkan MODE OPERASI saat ini. 16 Tombol ini hanya digunakan oleh petugas servis yang
5
berpengalaman untuk pemeliharaan.
Untuk tipe Pendingin Saja, (Otomatis) dan
(Pemanasan) tidak dipasang. TOMBOL PEMROGRAM AN WAKTU
TAMPILAN (PEMERIKSAAN/ OPERASI
UJI COBA) 17 Gunakan tombol ini untuk memprogram waktu "MULAI
dan/atau BERHENTI".
6 Jika TOMBOL PEMERIKSAAN/ OPERASI UJI
TOMBOL PENG ATURAN SUHU
COBA ditekan, tampilan menunjukkan mode sistem
18 Gunakan tombol ini untuk MENGATUR SUHU
yang berlaku.
TAMPILAN (WAKTU TERPROGRAM) TOMBOL RESET TANDA FILTER
7 19
Tampilan ini menunjukkan WAKTU TERPROGRAM
sistem dimulai atau dihentikan. TOMBOL KONTROL KECEPATAN KIPAS
8 TAMPILAN (SUHU YANG DIATUR) 20 Tekan tombol ini untuk memilih kecepatan kipas, TINGGI
Tampilan ini menunjukkan suhu yang diatur. atau RENDAH, yang Anda inginkan.
TAMPILAN (KECEPATAN KIPAS) TOMBOL PEMILIH MODE OPERASI
9 Tampilan ini menunjukkan kecepatan kipas yang 21 Tekan tombol ini untuk memilih MODE OPERASI.
diatur. TOMBOL PENGATURAN ARAH ALIRAN UDARA
TAMPILAN (SIRIP ALIRAN UDARA) 22
10
CATATAN
TAMPILAN (WAKTU UNTUK
• Untuk penjelasan, semua tanda yang ditunjukkan di tampilan
11 MEMBERSIHKAN FILTER UDARA)
gambar di atas berbeda dengan situasi yang sebenarnya.

C: 3PA59583-16Z

9 Remote Controller
Wired Remote Controller SiMT281416E

1.2.2 BRC1D61

1. TOMBOL ON/OFF 8. IKON KONTROL EKSTERNAL


Tekan tombol ON/OFF untuk memulai atau Ikon ini menunjukkan bahwa pengontrol lain dengan prioritas
memberhentikan sistem. yang lebih tinggi mengendalikan atau menonaktifkan
pemasangan Anda.
2. LAMPU OPERASI
Lampu operasi menyala selama operasi atau 9. IKON PENGALIHAN SEDANG DIKONTROL TERPUSAT
berkedip jika terjadi kesalahan.
Ikon ini menunjukkan bahwa pengalihan pemasangan
3. IKON MODE OPERASI sedang dikontrol terpusat yang ditetapkan ke unit indoor lain
Ikon ini menunjukkan mode operasi saat ini atau pemilih dingin/panas opsional yang terhubung ke unit
(KIPAS, KERING, OTOMATIS, PENDINGIN, outdoor (= remote control utama)
PEMANAS)
10. INDIKATOR KERING SEMINGGU
4. IKON MODE VENTILASI SEN SEL RAB KAM JUM SAB MIN
Ikon ini menunjukkan mode ventilasi saat ini Hari indikator mingguan menunjukkan hari kerja saat ini
(ventilator pembaruan panas saja) (OTOMATIS, (atau hari yang diatur ketika membaca atau memprogram
PENGUBAHAN PANAS, BYPASS) jadwal timer).

5. IKON VENTILASI 11. TAMPILAN JAM


Ikon ventilasi muncul jika ventilasi diatur dengan Tampilan jam menunjukkan waktu saat ini (atau waktu
tombol jumlah ventilasi (ventilator pembaruan panas tindakan ketika membaca atau memprogram jadwal timer).
saja). Secara bersamaan, jumlah ventilasi
ditunjukkan dengan ikon kecepatan kipas (lihat 22). 12. PENGATURAN SUHU MAKSIMUM
Ini menunjukkan suhu maksimum yang diatur saat dalam
6. IKON PEMBERSIHAN UDARA operasi pembatasan.
Ikon ini menunjukkan bahwa unit pembersih udara
(opsional) beroperasi. 13. PENGATURAN SUHU MINIMUM
Ini menunjukkan suhu minimum yang diatur saat dalam
7. IKON KELUAR RUMAH operasi pembatasan.
Ikon keluar rumah menunjukkan status fungsi keluar
rumah 14. IKON JADWAL TIMER
Ikon ini menunjukkan bahwa jadwal timer diaktifkan.
ON Keluar rumah diaktifkan
Berkedip Keluar rumah aktif
OFF Keluar rumah dinonaktifkan

C: 3P107422-3D

Remote Controller 10
SiMT281416E Wired Remote Controller

.
15. IKON TINDAKAN 30. TOMBOL JADWAL TIMER
Ikon ini menunjukkan tindakan setiap hari untuk
Tombol ini mengaktifkan atau menonaktifkan jadwal timer.
jadwal timer.

16. IKON OFF 31. TOMBOL PENGATURAN WAKTU


Ikon ini menunjukkan bahwa tindakan OFF dipilih Tombol ini digunakan untuk mengatur jam atau, jika dalam
saat memprogram jadwal timer. mode pemrograman, untuk mengatur waktu tindakan yang
diprogram. Kedua tombol memiliki fungsi repeat otomatis.
17. PEMERIKSAAN DIPERLUKAN
32. TOMBOL PENGATURAN SUHU
Ikon ini menunjukkan bahwa pemeriksaan
diperlukan. Konsultasikan dengan installer Anda. Tombol ini digunakan untuk mengatur setpoint saat ini atau,
jika dalam mode pemrograman, untuk mengatur suhu
setpoint yang diprogram (tingkat = 1 C). Kedua tombol juga
18. TAMPILAN PENGATURAN SUHU
digunakan untuk mengatur hari dalam seminggu.
Ini menunjukkan suhu pemasangan yang diatur
saat ini (tidak ditampilkan dalam operasi
PEMBATASAN atau di mode KIPAS atau 33. TOMBOL PERUBAHAN OPERASI/MIN-MAKS
KERING). Ini adalah tombol serba guna. Tergantung pada manipulasi
sebelumnya oleh pengguna, tombol ini memiliki fungsi
19. PENGATURAN sebagai berikut:
Tidak digunakan, untuk layanan saja. 1. Memilih mode operasi pemasangan
(KIPAS, KERING, OTOMATIS, PENDINGIN,
PEMANAS)
20. IKON ARAH ALIRAN UDARA 2. Beralih dari suhu minimum ke maksimum jika di operasi
Ikon ini menunjukkan arah aliran udara (hanya pembatasan.
untuk pemasangan dengan sirip aliran udara
bermotor).
34. TOMBOL SETPOINT/BATAS
Tombol ini mengalihkan antara setpoint, operasi
21. TIDAK TERSEDIA pembatasan atau (mode pemrograman saja).
ditampilkan jika opsional yang tidak
dipasang ditekan atau fungsi tidak tersedia. 35. TOMBOL KECEPATAN KIPAS
Tombol ini mengalihkan antara L (Rendah), H (Tinggi), HH
22. IKON KECEPATAN KIPAS (sangat Tinggi), (Otomatis).
Ikon ini menunjukkan kecepatan kipas yang
diatur. 36. TOMBOL PENGATURAN ARAH ALIRAN UDARA
Tombol ini untuk mengatur arah aliran udara.
24. IKON WAKTU UNTUK MEMBERSIHKAN FILTER
37. TOMBOL RESET IKON WAKTU UNTUK MEMBERSIHKAN
UDARA
Ikon ini menunjukkan filter udara harus FILTER UDARA
dibersihkan. Tombol ini dugunakan untuk me-reset ikon waktu untuk
Lihat panduan unit outdoor. membersihkan filter udara.

25. IKON WAKTU UNTUK MEMBERSIHKAN


ELEMEN
Ikon ini menunjukkan elemen harus dibersihkan
(ventilator pembaruan panas saja).

26. TOMBOL MODE VENTILASI


Tombol mode ventilasi mengoperasikan ventilator
pembaruan panas; lihat panduan ventilator
pembaruan panas untuk lebih jelasnya.

27. TOMBOL JUMLAH VENTILASI


Tombol ini mengatur jumlah ventilasi; lihat
panduan ventilator pembaruan panas untuk lebih
jelasnya.

28. TOMBOL PEMERIKSAAN/ OPERASI UJI COBA

Tidak digunakan, untuk servis saja.

29. TOMBOL PEMROGRAMAN


Ini adalah tombol serba guna. Tergantung pada
manipulasi sebelumnya oleh pengguna, tombol C: 3P107422-3D
pemrograman memiliki berbagai fungsi.
11 Remote Controller
Wired Remote Controller SiMT281416E

1.2.3 BRC1E62
1. Tombol Pemilih Mode

11. LCD (dengan lampu latar)

4. Tombol ke atas
5. Tombol ke bawah
6. Tombol ke kanan
7. Tombol ke kiri
9. Lampu operasi (Hijau)

8. Tombol ON/OFF
3. Tombol Menu/Enter

10. Tombol batal

2. Tombol Pengaturan Aliran Udara

Operasi dasar (yaitu, ON/OFF, Mode Operasi, Laju Aliran Udara (Volume Udara/Kecepatan Kipas),
Arah Aliran Udara dan Pengaturan Suhu) bisa dimanipulasi secara langsung dengan tombol di atas.
Pengaturan lanjutan bisa dimanipulasi dari layar Menu yang ditampilkan tombol Menu/Enter.

 Jangan menekan tombol remote control dengan benda runcing yang keras.
Karena remote control bisa rusak atau malfungsi.
Catatan
: 1. Tombol Pemilih Mode
 Digunakan untuk memilih mode operasi pilihan Anda.
* Mode yang tersedia bervariasi sesuai dengan model sambungan.

2. Tombol Pengaturan Aliran Udara


 Digunakan untuk menunjukkan layar Laju Aliran Udara (Volume Udara/Kecepatan Kipas)/Arah
ALiran Udara.
* Kecepatan kipas dan arah aliran udara yang tersedia bervariasi sesuai dengan model sambungan.

3. Tombol Menu/Enter
 Digunakan untuk menunjukkan Menu Utama.
 Digunakan untuk memasukkan item pengaturan yang dipilih.

4. Tombol ke atas " "


 Digunakan untuk menaikkan suhu yang diatur.
 Digunakan untuk menyorot item di atas pilihan saat ini.
(Item yang disorot akan bergulir terus jika tombol terus ditekan.)
 Digunakan untuk mengubah item yang dipilih.
* Pastikan untuk menekan bagian tersebut dengan simbol " "

5. Tombol ke bawah " "


 Digunakan untuk menurunkan suhu yang diatur.
 Digunakan untuk menyorot item di bawah pilihan saat ini.
(Item yang disorot akan bergulir terus jika tombol terus ditekan.)
 Digunakan untuk mengubah item yang dipilih.
* Pastikan untuk menekan bagian tersebut dengan simbol " "

Remote Controller 12
SiMT281416E Wired Remote Controller
6. Tombol ke kanan " "
 Digunakan untuk menyorot item berikutnya pada sisi kanan.
 Isi tampilan berubah ke layar berikutnya per halaman.
* Pastikan untuk menekan bagian tersebut dengan simbol " "

Tombolke
7. Tombol kiri"" " "
kekiri
 Digunakan untuk menyorot item berikutnya pada sisi kiri.
 Isi tampilan berubah ke layar sebelumnya per halaman.
* Pastikan untuk menekan bagian tersebut dengan simbol " "

8. Tombol ON/OFF
 Tekan tombol ini maka sistem akan dimulai.
 Tekan tombol ini lagi maka sistem akan berhenti.

9. Lampu operasi (Hijau)


 Lampu ini menyala selama operasi.
 Lampu ini berkedip jika terjadi kerusakan.

10. Tombol batal


 Digunakan untuk kembali ke layar sebelumnya.

11. LCD (dengan lampu latar)


 Lampu latar akan menyala selama kurang lebih 30 detik dengan menekan tombol operasi.
Tekan tombol pada saat lampu latar menyala. (tidak termasuk tombol ON/OFF)
 Jika 2 remote control digunakan untuk mengontrol unit indoor tunggal, lampu latar remote control
yang diakses pertama akan menyala.

13 Remote Controller
Wired Remote Controller SiMT281416E

1.3 Pengaturan UTAMA/SUB jika Menggunakan 2 Remote


Control
Situasi
Pengaturan UTAMA/SUB diperlukan jika 1 unit indoor dikontrol dengan 2 remote control.
Jika Anda menggunakan 2 remote control (panel kontrol dan remote control terpisah), atur satu remote
control sebagai UTAMA dan yang satunya sebagai SUB.
Pengat Remote control diatur oleh pabrik sebagai UTAMA, jadi Anda hanya perlu mengubah satu remote
uran control dari UTAMA ke SUB. Berikut adalah cara mengubah remote control dari UTAMA ke SUB:

1.3.1 BRC1C61/BRC1D61
1. Masukkan obeng minus ke dalam lubang antara bagian atas dan bawah remote control, seperti
yang ditunjukkan pada ilustrasi di bawah. Dengan hati-hati bongkar bagian atas remote control,
lakukan dari 2 posisi.

Bagian atas
remote control

Bagian bawah
remote control

2. Putar saklar pengganti UTAMA/SUB pada PCB ke “S”.


Saklar diatur sebagai UTAMA
M (pengaturan dari pabrik)
S

M
Atur saklar ke SUB.
S

1.3.2 BRC1E62
Penentuan remote control utama dan sub bisa tertukar. Perhatikan bahwa pengubahan ini dilakukan
dengan memutar daya ke OFF lalu ke ON lagi.
Layar utama Pilih "Remote
ditampilkan. control utama" atau
"Sub remote control"
Tekan tombol Tekan dan tahan tombol Batal menggunakan
Batal sekali. selama 4 detik atau lebih. tombol /
(Atas/Bawah), lalu
tekan tombol
Pilih "Ganti Control Utama
Menu/Enter.
ke Sub " dan tekan tombol Tekan tombol
Menu/Enter. Menu/Enter.
Menu pengaturan Item22 is
Item Item 2
layanan ditampilkan ditampilkan
ditampilkan. Tekan tombol Batal. displayed.

Menu pengaturan layanan Item 2


Ganti Control Utama ke Sub RC Utama
Sub RC

Remote Controller 14
SiMT281416E Wired Remote Controller

1.4 Pengaturan No. Grup Kontrol Terpusat


1.4.1 BRC1C61/BRC1D61
Untuk melakukan remote control terpusat menggunakan remote control dan pengontrol ON/OFF
terpusat, pengaturan No. Grup harus dilakukan oleh grup menggunakan remote control operasi.
Lakukan pengaturan No. Grup untuk remote control terpusat menggunakan remote control operasi.

1. TEST

Jika di mode normal, tekan dan tahan saklar “ “


selama 4 detik atau lebih untuk mengatur sistem ke "Mode Pengaturan Lapangan ".
2. Pilih No. MODE “00” dengan tombol “ ”.
3. Gunakan tombol “ ” untuk memilih No. grup untuk tiap grup.
(Nomor grup naik dengan urutan 1-00, 1-01, ... 1-15, 2-00, ... 4-15.)
4. Tekan “ ” atau “ ” untuk mengatur No. grup yang dipilih.
5. Tekan “
TEST
” untuk kembali ke MODE NORMAL.

BRC1C61

NO. MODE
NO. GRUP
MODE
PENGATURAN
LAPANGAN

BRC1D61

NO. MODE
NO. GRUP
MODE
PENGATURAN
LAPANGAN

Catatan:
 Untuk mengatur No. grup ventilator pembaruan panas dan adaptor kabel untuk AC lain, dll, lihat
panduan operasi yang terlampir.

PEMBERITAHUAN
Masukkan No. grup dan tempat pemasangan unit indoor ke tabel pemasangan yang terlampir.
Pastikan untuk menyimpan tabel pemasangan dengan panduan operasi untuk pemeliharaan.

15 Remote Controller
Wired Remote Controller SiMT281416E

1.4.2 BRC1E62
<Pengaturan No. Grup (Grup)>
Layar utama
ditampilkan.

Tekan tombol Tekan dan tahan tombol Batal selama 4 detik atau lebih.
Batal sekali
Pilih "alamat Grup" lalu
tekan tombol Menu/Enter.
Menu
Item 2
pengaturan
ditampilkan.
layanan Tekan tombol
ditampilkan. Batal sekali.
Tekan tombol
Pilih "pengaturan Batal sekali
No. Grup (Grup)"
lalu tekan tombol
Menu/Enter.

Item 2
ditampilkan.

Tekan tombol Pilih No. Grup yang


Menu/Enter diinginkan dengan
menggunakan
tombol /
(Atas/Bawah), lalu
tekan tombol
Menu/Enter.
Item 2
ditampilkan

< Pengaturan No. Grup (Unit)>


Layar utama
ditampilkan.

Tekan tombol Tekan dan tahan tombol Batal selama 4 detik atau lebih .
Batal sekali
Pilih "alamat Grup" lalu tekan
Service
Menu pengaturan tombol Menu/Enter. Item
Item 2 2is
settings
layanan menu ditampilkan.
displayed.
ditampilkan. Tekan tombol
is displayed. Batal sekali.
Pilih Tekan tombol
“pengaturan No. Batal sekali
Grup (Unit)” lalu
tekan tombol
Menu/Enter

Item 2
ditampilkan.

Tekan tombol Pilih No. Grup yang


Menu/Enter diinginkan dengan
menggunakan
tombol /
(Atas/Bawah), lalu
tekan tombol
Menu/Enter.
Item 2
ditampilkan.

Menu pengaturan layanan Item 2  Deskripsi


Menu ini digunakan untuk mengatur No. grup kontrol terpusat.
Alamat Grup Pengaturan No. Grup (Grup) Menu ini juga digunakan untuk mengatur No. grup unit indoor.
Pengaturan No. Grup (Unit)

Remote Controller 16
SiMT281416E Wireless Remote Controller

2. Remote Control Nirkabel


2.1 Model yang Diaplikasikan
Seri Model FCQ FHQ FAQ FBQ-D FVQ
Remote Control BRC7F633F BRC7EA66 BRC7EB519 BRC4C64 —
BRC7GA56

2.2 Nama dan Fungsi


1-1
(1)
(8)
1-2
(3)
(10)

(6)

(11)
(4)

(9)
(2) (13)

(5) (12)

(15)
(7)
(14)
(16)
(17)

Penerima
FCQ FHQ

(22) (23)
(23)

(18) (22)

(19)
(19) (21) (20) (18)

(20) (21)
FAQ FBQ-D
(18)

(20) (22)

(21) (20)
(21)
(19) (19)

(23)

(18)

(23) (22)

17 Remote Controller
Wireless Remote Controller SiMT281416E

TAMPILAN “ ” (PENGIRIMAN SINYAL) 14 TOMBOL PENGATURAN ARAH ALIRAN


UDARA
1 Tampilan ini menyala ketika sinyal sedang TOMBOL PEMILIH MODE OPERASI
dikirim. 15
Tekan tombol ini untuk memilih MODE
OPERASI.
TAMPILAN “ ”“ ” “ ”“ ” “
TOMBOL RESET TANDA FILTER
” (MODE OPERASI)
2 16 Lihat bagian PEMELIHARAAN di panduan
Tampilan ini menunjukkan MODE OPERASI
operasi yang dilampirkan di unit indoor.
saat ini. Untuk tipe pendingin saja, “ ”
TOMBOL PEMERIKSAAN/OPERASI UJI
(Otomatis) dan “ ” (Pemanasan) tidak 17 COBA
dipasang. Tombol ini hanya digunakan oleh petugas
servis yang berpengalaman untuk
H M L pemeliharaan.
3 TAMPILAN “ ” (SUHU YANG
DIATUR) SAKLAR OPERASI DARURAT
C
Tampilan ini menunjukkan suhu yang diatur. 18
saklar ini mudah digunakan jika remote
kontrol tidak berfungsi.
TAMPILAN “ hr. hr. ” (WAKTU
4 PENERIMA
TERPROGRAM) 19
Ini untuk menerima sinyal dari remote kontrol.
Tampilan ini menunjukkan WAKTU
TERPROGRAM sistem dimulai atau LAMPU INDIKATOR OPERASI (Merah)
dihentikan. Lampu ini tetap menyala saat AC hidup.
5 20 Lampu ini berkedip jika unit bermasalah.
TAMPILAN “ ” (SIRIP ALIRAN
UDARA)
LAMPU INDIKATOR TIMER (Hijau)
6 TAMPILAN “ ” “ ” (KECEPATAN 21
KIPAS) Lampu ini tetap menyala saat timer diatur.
Tampilan ini menunjukkan kecepatan kipas LAMPU INDIKATOR WAKTU UNTUK
yang diatur. MEMBERSIHKAN FILTER UDARA (Merah)
22
TAMPILAN “ TEST ” (PEMERIKSAAN/ Lampu menyala jika saatnya untuk
OPERASI UJI COBA) membersihkan filter udara.
7
Jika TOMBOL PEMERIKSAAN OPERASI/UJI LAMPU PENCAIRAN (Oren)
COBA ditekan, tampilan menunjukkan mode
sistem yang berlaku. 23 Lampu menyala jika operasi pencairan
dimulai. (Untuk tipe pendingin saja, lampu ini
TOMBOL ON/OFF tidak menyala.)
Tekan tombol ON/OFF maka sistem akan
8 CATATAN
dimulai.
Tekan tombol ON/OFF lagi maka sistem akan • Untuk penjelasan, semua tanda yang
berhenti. ditunjukkan dalam gambar 1-1 berbeda dengan
TOMBOL KONTROL KECEPATAN KIPAS situasi sesungguhnya.
9
Tekan tombol ini untuk memilih kecepatan • Gambar 1-2 menunjukkan remote control
kipas, TINGGI atau RENDAH, yang Anda dengan penutup depan dibuka.
inginkan. • Jika lampu indikator waktu untuk
membersihkan filter udara menyala, bersihkan
TOMBOL PENGATURAN SUHU
filter udara seperti yang dijelaskan dalam
10 Gunakan tombol ini untuk MENGATUR panduan operasi yang disediakan dengan unit
SUHU (Operasikan dengan tutup depan indoor.
remote control dipasang.) • Setelah membersihkan dan memasang ulang
filter udara, tekan tombol reset tanda filter pada
TOMBOL PEMROGRAMAN TIMER
remote control. Lampu indikator waktu untuk
11 Gunakan tombol ini untuk memprogram membersihkan filter udara pada penerima akan
waktu “MULAI dan/atau BERHENTI”. mati.
(Operasikan dengan tutup depan remote • Lampu pencairan akan berkedip jika daya
control dipasang.) diputar ke ON. Ini bukan kesalahan.
12 TOMBOL MODE TIMER MULAI/BERHENTI
13 TOMBOL BATAL/CADANGAN TIMER

C: 3P107422-11J
Remote Controller 18
SiMT281416E Wireless Remote Controller

2.3 Pengaturan Alamat dan UTAMA/SUB


Pendahuluan
Untuk mengatur remote control nirkabel, Anda harus mengatur alamat untuk:
 Penerima remote control nirkabel
 Remote control nirkabel.

Pengaturan Alamat untuk Penerima


Alamat penerima remote control nirkabel diatur oleh pabrik ke 1. Untuk mengubah pengaturan ini,
lakukan hal berikut:
Atur saklar alamat nirkabel (SS2) pada PCB sesuai dengan tabel di bawah ini.
No. Unit No. 1
1
No. 2 No. 3

1
Saklar alamat
2

2
nirkabel (SS2)
3

3
Jika menggunakan remote control berkabel dan nirkabel untuk 1 unit indoor, control berkabel harus
diatur ke UTAMA. Oleh karena itu, atur saklar UTAMA/SUB (SS1) penerima ke SUB.
UTAMA/SUB UTAMA SUB

Saklar SM SM
UTAMA/SUB
(SS1)

Pengaturan Alamat untuk Remote Control Nirkabel


Alamat remote control nirkabel diatur oleh pabrik ke 1. Untuk mengubah pengaturan ini, lakukan hal berikut:

1. Tahan tombol “ ” dan “ ” selama 4 detik untuk


masuk ke mode Pengaturan Lapangan.
(Ditunjukkan dalam area tampilan pada gambar
di sebelah kanan.)
2. Tekan tombol dan pilih pengaturan multiple
(A/b). setiap kali tombol ditekan, layar akan
beralih antara "A" dan "b".
3. Tekan tombol atau untuk mengatur
alamat.
1 2 3 4 5 6
Alamat bisa diatur dari 1 sampai 6, tapi atur Alamat
alamat ke 1 ~ 3 dan ke alamat yang sama
dengan penerima. (Penerima tidak berfungsi
Pengaturan
dengan alamat 4 ~ 6.) multiple
4. Tekan tombol “ ” untuk memasukkan
pengaturan.
5. Tahan tombol “ ” selama 1 detik untuk keluar
dari mode Pengaturan Lapangan dan kembali ke
tampilan normal.

19 Remote Controller
Wireless Remote Controller SiMT281416E

Pengaturan Multiple A/b


Ketika unit indoor dioperasikan kontrol eksternal (remote control pusat, dll), terkadang unit outdoor
tidak merespon perintah pengaturan suhu dan ON/OFF dari remote control ini. Periksa pengaturan
apa yang diinginkan pelanggan dan lakukan pengaturan multiple seperti yang ditunjukkan di bawah
ini.
Remote control FCQ FHQ, FAQ, FBQ-D
Pengaturan Tampilan Gerakan ketika operasi dikontrol oleh AC Untuk mengontrol AC dan Untuk selain
multiple remote control dan peralatan lain unit lain di sebelah kiri
Ketika peralihan operasi, pengaturan suhu
atau sejenisnya dilakukan dengan remote Perintah selain ON/OFF
control, unit indoor menolak instruksi. dan pengaturan suhu
(Bunyi penerimaan sinyal “peeh” atau “pick- diterima.
pick-pick”) (mengeluarkan 1 BUNYI
Semua item Akibatnya, ketidaksesuaian antara kondisi BEEP PANJANG atau 3
A: Standar
ditampilkan. operasi unit indoor dan indikasi tampilan BUNYI BEEP PENDEK)
remote control terjadi.
Operasi tetap
Karena indikasi remote control dimatikan,
b: Multi ditampilkan secara Semua perintah diterima (2 BUNYI BEEP
tidak ada ketidaksesuaian seperti yang
Sistem singkat setelah PENDEK)
disebutkan di atas terjadi.
pelaksanaan.

Remote Controller 20
SiMT281416E Service Mode

3. Mode Layanan
3.1 BRC1C61/BRC1D61
3.1.1 Tampilan Data Layanan

No. Unit No. Mode


No. Kode Unit NO.
Mode
Kedua Pengaturan
SETTI NG
Lapangan
3 4
No. Kode
Pertama

1 2 7 T EST
5 3
6

1. Masukkan mode pengaturan lapangan.


Tekan tombol operasi PEMERIKSAAN/UJI COBA selama 4 detik atau lebih.
2. Masukkan mode layanan.
Setelah memasukkan mode pengaturan lapangan, tekan tombol operasi PEMERIKSAAN/UJI
COBA selama 4 detik atau lebih.
3. Pilih No. mode
Atur No. mode yang diinginkan dengan tombol pengaturan suhu ke atas/ke bawah.
4. Pilih No. unit
Pilih pengaturan No. unit indoor dengan tombol mode waktu MULAI/BERHENTI.
5. Pilih No. riwayat kesalahan atau No. data termistor yang diinginkan dengan tombol “ ” atau “ ”.
6. Tampilan data (Lihat tabel tampilan di bawah)
7. Kembali ke mode operasi normal.
tekan tombol operasi PEMERIKSAAN/UJI COBA sekali.
No. Mode Fungsi Isi dan Metode Operasi Contoh Tampilan Remote Control
40 Riwayat Kesalahan Anda bisa mengubah riwayat
dengan tombol pemrograman waktu
ke atas-ke bawah.

41 Tampilan Data Pilih tampilan termistor dengan


Termistor tombol pemrograman waktu ke
atas-ke bawah.
Tampilan termistor
00: Termistor suhu ruang pada
remote control
01: Termistor udara hisap
02: Termistor penukar panas

21 Remote Controller
Service Mode SiMT281416E

3.1.2 Pengaturan Layanan

NO. MODE
MODE PENGATURAN LAPANGAN
NO. UNIT NO. MODE
5
NO. KODE
KEDUA MODE
5
PENGA TURA N
LAPA NGAN
NO. KODE 3 4
PERTAMA

1 2 6 NO. KODE KEDUA


5 3
5
NO. KODE PERTAMA

1, 2, 6

1. Masukkan mode pengaturan lapangan.


Tekan terus tombol operasi PEMERIKSAAN/UJI COBA selama minimal 4 detik.
2. Masukkan mode pemeliharaan.
Setelah memasukkan mode pengaturan lapangan, tekan terus tombol operasi PEMERIKSAAN/UJI
COBA selama minimal 4 detik.
3. Pilih No. mode
Atur No. mode yang diinginkan dengan tombol pengaturan suhu ke atas/ke bawah.
4. Pilih No. unit
Pilih pengaturan No. unit indoor dengan tombol MODE WAKTU MULAI/BERHENTI.
5. Lakukan pengaturan yang diperlukan untuk setiap mode. (Mode 43 hanya berlaku untuk remote
control nirkabel)
• Untuk Mode 43
Tekan TOMBOL TIMER ON/OFF untuk memilih Kipas paksa ON.
• Untuk Mode 44
Atur “Kecepatan kipas” dengan TOMBOL KONTROL KECEPATAN KIPAS dan “Arah aliran
udara” dengan TOMBOL PENGATURAN ARAH ALIRAN UDARA, lalu tekan TOMBOL TIMER
ON/OFF untuk memilih.
• Untuk Mode 45
Pilih ganti No. unit dengan tombol “ ” atau “ ”, lalu tekan TOMBOL TIMER ON/OFF untuk
memilih.
6. Kembali ke mode operasi normal.
Tekan tombol operasi PEMERIKSAAN/UJI COBA sekali.
No. Mode Fungsi Isi dan Metode Operasi Contoh Tampilan Remote Control
43 Kipas Paksa Putar kipas ke ON untuk setiap unit UNIT No.
meyala (ON) secara individual.

SETTING
44 Pengaturan Atur kecepatan kipas dan arah
individual aliran udara untuk setiap unit
secara individual dengan
menggunakan kontrol grup.
Pengaturan dilakukan dengan
menggunakan tombol “pengaturan
arah aliran udara” dan “pengaturan
kecepatan kipas”.
45 Mengubah No. Ubah No. unit
Unit Atur No. unit setelah mengubah
No. unit dengan tombol
pemrograman waktu ke atas-ke
bawah.

Remote Controller 22
SiMT281416E Service Mode

3.2 BRC1E62
Pengoperasian remote control memugkinkan data layanan bisa diperoleh dan pengaturan berbagai layanan.

Layar
utama
ditampilkan
.
Tekan tombol Tekan tombol
Batal sekali. Tekan dan tahan tombol Batal Batal.
selama 4 detik atau lebih.

Menu
pengaturan
layanan
ditampilkan.

Tekan tombol Tekan dan


tahan tombol
Batal sekali.
Batal selama 4
detik atau lebih.
Pilih item yang diinginkan
dari menu Layanan, lalu Pilih No. Unit yang diinginkan
tekan tombol Menu/Enter.
Menu
Menu menggunakan tombol
ItemItem22 is (Atas/Bawah). Data yang sesuai
pemeliharaan
pemeliharaan ditampilkan
ditampilkan
ditampilkan Tekan tombol Batal.
displayed. akan ditampilkan.

Menu Pemeliharaan Item 2 Keterangan


2-1. Nama Model 1. No. Unit Pilih No. Unit yang ingin Anda periksa.
2. Unit indoor
3. Unit outdoor
2-2. Jam Operasi 1. No. Unit Pilih No. Unit yang ingin Anda periksa.
2. Jam operasi unit Semua ini ditampilkan dalam jam.
indoor
3. Jam operasi kipas unit
indoor
4. Waktu penyalaan unit
indoor
5. Jam operasi outdoor

6. Jam operasi kipas 1


unit outdoor
7. Jam operasi kipas 2
unit outdoor
8. Jam operasi
komponen 1 outdoor
9. Jam operasi
komponen 2 outdoor
2-3. Status Unit Indoor 1. No. Unit Pilih No. Unit yang ingin Anda periksa.
1/3 2. KIPAS Tap, kecepatan (rpm)
3. SIRIP Ayun, tetap
4. Kecepatan Kecepatan kipas (rpm)
5. EV Derajat sejauh mana katup ekspansi elektronik terbuka (pls)
6. MP Pompa buang ON/OFF
7. 52H Pemanas listrik ON/OFF
8. Hu Humidifier ON/OFF
9. TBF Kontrol anti-beku ON/OFF
2-3. Status Unit Indoor 1. No. Unit Pilih No. Unit yang ingin Anda periksa.
2/3 2. APUNG SAKLAR APUNG ON/OFF
3. T1/T2 Input T1/T2 ON/OFF yang berasal dari luar

23 Remote Controller
Service Mode SiMT281416E

Menu Pemeliharaan Item 2 Keterangan


2-3. Status Unit 1. No. Unit Pilih No. Unit yang ingin Anda periksa.
Indoor 3/3 2. Th1 Termistor udara hisap
3. Th2 Termistor penukar panas
4. Th3 —
5. Th4 Termistor udara buang
6. Th5 —
7. Th6 —
2-4. Status Unit 1. No. Unit Pilih No. Unit yang ingin Anda periksa.
Outdoor 2. step KIPAS Tap kipas
3. KOM Frekuensi catu daya kompresor (Hz)
4. EV1 Derajat sejauh mana katup ekspansi elektronik terbuka (pls)
5. SV1 Katup solenoid ON/OFF
6. Th1 Termistor udara outdoor
7. Th2 Termistor penukar panas
8. Th3 Termistor pipa buang
9. Th4 —
10.Th5 —
11.Th6 —
2-5. Pencairan 1. Pencairan paksa ON Mengaktifkan operasi pencairan paksa.
paksa 2. Pencairan paksa OFF Menonaktifkan operasi pencairan paksa.
2-6. Tampilan 1. Tampilan peringatan ON Menampilkan peringatan pada layar jika terjadi kesalahan.
kesalahan 2. Tampilan peringatan OFF Tidak ada peringatan yang ditampilkan.
3. Tampilan kesalahan ON Menampilkan kesalahan pada layar.
4. Tampilan kesalahan OFF Tidak menampilkan kesalahan atau peringatan.
2-7. Tukar No. Unit 1. No. Unit saat ini No. unit bisa dipindah ke unit lain.
2. Memindah No. Unit
2-8. Alamat Nilai No. Unit: 0 - 15 Pilih No. Unit yang ingin Anda periksa.
Sensor Kode
00: Termistor remote control (°C)
01: Termistor udara hisap (°C)
02: Termistor pipa cairan penukar panas (°C)
03: Termistor pipa gas penukar panas (°C)
04: No. alamat unit indoor
05: No. alamat unit outdoor
06: No. alamat unit BS
07: No. alamat kontrol zona
08: No. alamat bets Pendingin/Pemanas
09: No. alamat demand/suara-pelan
Data Data yang sesuai akan ditampilkan, berdasarkan No. unit dan
Kode yang dipilih.

Remote Controller 24
SiMT281416E

4. Mode Pemeriksaan
4.1 BRC1C61/BRC1D61

Tampilan normal (Tidak ada tampilan)


Tekan tombol PEMERIKSAAN/UJI COBA sekali.

Unit 0
Kode kesalahan L0
Pemeriksaan
(1) Mode pemeriksaan (1) Mode pemeriksaan
Tekan tombol PEMERIKSAAN/UJI COBA Unit 0
sekali Kode kesalahan L0
Pemeriksaan
Kode kesalahan berkedip ketika terjadi kesalahan.

–––
5F2

(2) Kode model unit indoor


(2) Tampilan kode model unit indoor
Tekan tombol PEMERIKSAAN/UJI COBA Tampilan Model
sekali 5F2 FCQ
5H2 FHQ
5A3 FAQ
5U2 FBQ-D
––– 513 FVQ
AA1

(3) Tampilan kode model unit outdoor


Tekan tombol PEMERIKSAAN/UJI COBA
sekali

Operasi uji coba


Operasi uji coba (3) Kode model unit outdoor

Tampilan Model
Mode operasi uji coba 2AA RZR
Tekan tombol PEMERIKSAAN/UJI COBA
sekali
Catatan:
Mode pemeriksaan tidak tersedia untuk BRC1E62.

25 Remote Controller
Inspection Mode SiMT281416E

Bagian 4
Fungsi dan Kontrol
1. Fungsi Komponen Utama dan Termistor................................................ 27
2. Bagan Alur Operasi.................................................................................. 31
3. Operasi Pendinginan/Kering ........................................................................31
4. Detail Fungsi ............................................................................................ 32
4.1 Unit Indoor..........................................................................................32
4.2 Unit Outdoor .......................................................................................37

Function and Control 26


SiMT281416E Function of Main Components and Thermistors

1. Fungsi Komponen Utama dan Termistor


Penempatan termistor
 RZR50 • 60 • 71LVVM(4)

Katup ekspansi elektronik


Filter Penukar panas unit
outdoor
(B)

Penukar panas
R1T
indoor

R3T R5T
R4T
Saklar tekanan
(tinggi)

Katup penghenti S1PH


Katup
(dengan port layanan
R2T cek
5/16 "flare) Aki
Pemipaan lapangan 9,5 kompre
C 1220T-O sor

Aki Kompresor (A)


Pemipaan lapangan 15,9
C 1220T-O
Unit indoor Unit outdoor Port pengukur
(5/16’’ flare)
C: 3D076471E

 RZR100LVVM(4)

Katup ekspansi elektronik


Filter Penukar panas unit
outdoor
(B)

Penukar panas R1T


indoor

R3T Katup
cek R5T * 
R4T R10T
Saklar tekanan
(tinggi)
Katup penghenti S1PH
(dengan port layanan
5/16 "flare) R2T
Aki
Pemipaan lapangan 9,5 Port
kompre
C 1220T-O pengukur
sor
(5/16’’
flare)
Aki Kompresor (A)
Pemipaan lapangan 15,9
C 1220T-O
Unit indoor Unit outdoor

*Termistor ini dekat kotak komponen listrik

C: 3D076443E

27 Function and Control


Function of Main Components and Thermistors SiMT281416E

 RZR125 • 140LVVM(4)

Outdoor unit
Electronic
heat exchanger
expansion valve
Filter

(B)
R1T

S1NPL
Pre ssure
sen so r
R5T
(low) Pre ssure
switch
R4T
Indoor heat exchanger (high)
R3T S1PH

 R10T

Gauge port
(5/16" flare)

Field piping  9.5 R2T


C1220T-O Accumulator
Field piping  15.9 Compre ssor
C1220T-O (A)

Indoor unit Outdoor unit


Stop valve
(with se rvice port 5/16" flare)

This thermistor is near the el. comp. box.

C: 3D065869D

 RZR100LUY1(4)

Outdoor unit
Electronic
heat exchanger
expansion valve
Filter

(B)
R1T

Pressure
sensor Gauge port R5T
S1NPH
(5/16" flare) R4T
Indoor heat exchanger
R3T
Pressure 
switch R10T
(high)
S1PH

Field piping 9.5


R2T
C1220T-O Accumulator
Field piping 15.9 Compressor
C1220T-O (A)

Indoor unit Outdoor unit


Stop valve
(with service port 5/16" flare)

The thermistor is near the el. comp. box.

3D079463

Function and Control 28


SiMT281416E Function of Main Components and Thermistors

 RZR125 • 140LUY1(4)

Outdoor unit
Electronic heat exchanger
expansion valve
Filter

(B)
R1T

Pre ssure R5T


S1NPH sen so r
Gauge port R4T
(5/16" flare)
Indoor heat exchanger
R3T

Pre ssure
R10T
switch
(high)

S1PH

Field piping  9.5


R2T
C1220T-O Accumulator
Field piping  15.9 Compre ssor
(A)
C1220T-O

Indoor unit Outdoor unit


Stop valve
(with se rvice port 5/16" flare)

The thermistor is near the el. comp. box.

3D079464A

 RZR-LVVM(4), RZR-
LUY1(4)
(A) Kompresor
Unit penggerak inverter mengubah frekuensi operasi kompresor ke kapasitas kontrol dan faktor lain.

(B) Katup Ekspansi Elektronik


Menyediakan kontrol untuk menjaga kondisi operasi optimum untuk efisiensi tinggi.

R1T (Termistor Udara Outdoor)


Digunakan untuk kontrol kondisi startup.

R2T (Termistor Pipa Buang)


Digunakan untuk perlindungan suhu pipa buang selama operasi kompresi.

R3T (Termistor Pipa Hisap)


Digunakan untuk kontrol panas pipa hisap dengan katup ekspansi elektronik.

R4T (Termistor Pipa Pembagi Penukar Panas)


• Digunakan untuk menghitung sub pendinginan penukar panas unit outdoor selama operasi
pendinginan.

R5T (Termistor Penukar Panas Menengah)


Digunakan untuk menghitung tekanan tinggi selama operasi pendinginan. (Menghitung Pc dengan suhu
yang terdeteksi dan karakteristik refrigeran R410A)

R10T (Termistor Sirip Radiasi)


• Digunakan untuk kontol kecepatan kipas unit outdoor.
• Digunakan untuk kontrol suhu sirip radiasi.
• Digunakan untuk kontrol perbedaan tekanan.

S1NPH (Sensor Tekanan Tinggi)


• Digunakan untuk mendeteksi tekanan tinggi.

S1NPL (Sensor Tekanan Rendah)


• Digunakan untuk mendeteksi tekanan rendah.

29 Function and Control


Function of Main Components and Thermistors SiMT281416E
S1PH (Saklar Tekanan Tinggi)
• Saklar ini diaktifkan pada tekanan tinggi 4.0MPa atau lebih untuk menghentikan operasi
kompresor.

Function and Control 30


SiMT281416E Function of Main Components and Thermistors

Simbol listrik RZR50- RZR100LVVM RZR125/140LV RZR100-


Termistor udara outdoor R1T 71LVVM
 (4) (4)
 VM
(4) 140LUY1
 (4)
Termistor pipa buang R2T    
Termistor pipa hisap R3T    
Termistor pipa pembagi
penukar panas R4T    
Termistor penukar
panas menengah R5T    
Termistor sirip radiasi R10T —   
Sensor tekanan tinggi S1NPH — — — 
Sensor tekanan rendah S1NPL — —  —
Saklar tekanan tinggi S1PH    

 Unit Indoor
Termistor Udara Hisap Indoor
Pendingin: • Kontrol termostat
• Kontrol PMV
• Kontrol frekuensi umum
Pemanas: • Kontrol termostat
• Kontrol PMV
• Kontrol frekuensi umum

Termistor Penukar Panas Indoor


Pendingin: • Kontrol frekuensi kompresor (target Te)
• Kontrol perlindungan arus inverter
• Kontrol pembekuan
Pemanas: • Kontrol frekuensi kompresor (target Tc)
• Kontrol perlindungan arus inverter
• Kontrol hot start
• Peak cut-off

Termistor Udara Buang


Digunakan untuk kontrol udara buang.

Simbol listrik FCQ FHQ-BV FHQ-CA FAQ FBQ-D FVQ


Termistor pipa hisap R1T      
R2T      
Termistor penukar panas
R3T — —   — 
Termistor udara buang R3T — — — —  —

31 Function and Control


Operation Flow Chart SiMT281416E

2. Bagan Alur Operasi


2.1 Operasi Pendinginan/Kering
Catu daya ON

Menginisialisasi katup ekspansi elektronik


Menginisialisasi mikro-komputer

Kontrol operasi pemanasan awal

Penilaian operasi Remote control

Keadaan darurat
Penilaian mode Emergency
operasi

Pendinginan/Kering operasi darurat


Pendinginan/Kering

Penilaian termostat ON

Kontrol startup
B

Kontrol normal
Kontrol step kompresor Kontrol perlindungan arus inverter
Kontrol katup ekspansi elektronik PI Kontrol perlindungan suhu sirip radiasi (1)
Kontrol perlindungan tekanan rendah Kontrol Perlindungan keseluruhan arus
Kontrol perlindungan tekanan tinggi Kontrol pendinginan suhu udara outdoor rendah
Kontrol suhu pipa buang Operasi yang disimulasikan

Penilaian termostat OFF


Penilaian
Penilaian dimulainya Kontrol termostat ruang Penilaian Penilaian
operasi OFF
operasi pemulihan Termostat OFF dengan siaga penghentian
remote control
minyak pencegahan pembekuan tidak normal
Indikasi kode
Operasi pemulihan minyak kesalahan
Oil recovery operation Pump down
Operasi residual
residual operation
penampungan

Penilaian berakhirnya Siaga restart


operasi pemulihan minyak

B A

1. Untuk selain RZR50-71LVVM (4)

Function and Control 32


SiMT281416E Function Details

3. Detail Fungsi
3.1 Unit Indoor
3.1.1 Kontrol Termostat Ruang
Berdasarkan perbedaan antara suhu yang diatur dengan remote control dan suhu ruang yang
terdeteksi sebenarnya (1), termostat diputar ke ON atau OFF.
 Dalam operasi normal
Dalam pendinginan

ATAU • T  -0.5ºC diteruskan selama 1 menit.


Operasi normal • T  -2ºC
Termostat OFF
(Termostat ON)
T  +0.5ºC
T: Suhu ruang yang terdeteksi – Suhu yang diatur dengan remote control

 Dalam Program Operasi Kering


Suhu Startup operasi kering
(Tro: Suhu udara ruang pada startup)
Termostat ON
T Diferensial 1.0
2
atau 1.5ºC (4)
Tr
Tr
Termostat OFF
3
Dry operation
Operasi kering Thermo. OFF Dry operation
Operasi kering

Waktu
T < -1.0 atau 1.5ºC (4)
(3)
Operasi kering Termostat OFF
T  0
(2)
Tro: Suhu udara ruang yang terdeteksi saat operasi kering dimulai
Tr: Suhu termistor ruang (terdeteksi dengan termistor suhu ruang)
T: Suhu ruang yang terdeteksi (Tr) – suhu udara ruang pada startup (Tro)

4: Nilai ini bervariasi sesuai dengan model.

Catatan:
1. Termistor untuk mendeteksi suhu ruang adalah sebagai berikut sesuai dengan pengaturan
lapangan.
a. Pengaturan dari pabrik: Termistor udara hisap di unit indoor
b. Ketika mengatur ke termistor suhu ruang: Termistor suhu ruang pada remote control

33 Function and Control


Function Details SiMT281416E

3.1.2 Menggunakan Kondisi untuk Termistor Suhu Ruang


Dapat diaplikasikan
Termistor suhu ruang pada remote control hanya tersedia di remote control berkabel.

Metode
Termistor suhu ruang adalah standar yang dinonaktifkan untuk unit SkyAir. Penggunaan termistor suhu
ruang dapat diaktifkan dengan mengubah pengaturan lapangan 10 (20) -2-02 ke 10 (20) -2-01.

Kondisi
Tabel berikut berisi kondisi ketika termistor suhu ruang pada remote control tidak digunakan:
Kondisi Termistor suhu ruang tidak digunakan ketika...
1 Kelainan termistor suhu ruang.
2 Kontrol grup digunakan.
3 Suhu yang diatur/kombinasi suhu udara hisap yang berada di luar jangkauan. (Lihat grafik di bawah)

Pendingi
nan Diagram berikut menunjukkan jangkauan operasi suhu yang diatur/kombinasi suhu udara hisap di
pendinginan:
˚C
32
Suhu yang diatur TH1=Ts - 1
(Ts)
30
TH1=Ts + 1
28 TH1=Ts - 3

26 TH1=Ts + 3

A B C D E F
24

22

20

18

16 ˚C
12 14 16 18 20 22 24 26 28 30 32 34
Suhu udara hisap (TH1)
Range in which
Jangkauan Diferensial
Jangkauan
suction air udara
termistor thermistor
termistor suhu inhisap
the indoor
ruang dapat di unitunit can
indoor
bedapat
useddigunakan
digunakan
Contoh
Dengan asumsi suhu yang diatur adalah 24 ° C atau lebih, dan suhu udara hisap berubah dari
18°C ke 30°C (A -> F):
(Contoh ini juga mengasumsikan ada beberapa AC lain, sistem VRV OFF, dan suhu berubah bahkan
ketika termistor suhu ruang OFF.)
Termistor udara hisap di unit indoor digunakan untuk suhu dari 18°C sampai 23°C (A -> C).
Termistor suhu ruang digunakan untuk suhu dari 23°C sampai 27°C (C --> E).
Termistor udara hisap di unit indoor digunakan untuk suhu dari 27°C sampai 30°C (E --> F).

Dan dengan asumsi bahwa suhu udara hisap berubah dari 30°C ke 18°C (F --> A):
Termistor udara hisap di unit indoor digunakan untuk suhu dari 30°C sampai 25°C (F --> D).
Termistor suhu ruang digunakan untuk suhu dari 25°C sampai 21°C (D --> B).
Termistor udara hisap di unit indoor digunakan untuk suhu dari 21°C sampai 18°C (B --> A).

Function and Control 34


SiMT281416E Function Details

3.1.3 Fungsi Identifikasi Unit Outdoor


Tujuan
Tujuan fungsi identifikasi unit outdoor adalah untuk memungkinkan unit indoor secara otomatis
menentukan mode operasi yang harus diatur dalam fungsi jenis unit outdoor yang terhubung.

Mode operasi
Mode operasi yang mungkin adalah:
Unit outdoor Operating modes
Pendingin Saja  Kipas
 Pendinginan
 Program kering

Input yang digunakan


Fungsi identifikasi unit outdoor menggunakan input berikut:
Input Koneksi pada Koneksi pada
PCB unit indoor PCB unit outdoor
PCB unit indoor TC & RC —
PCB unit outdoor — TC & RC

TC: Sirkuit transmisi


RC: Sirkuit penerima

3.1.4 Operasi Kipas dan Sirip Sayap


Operasi pendinginan
Tabel berikut berisi operasi kipas dan sirip sayap.

Sirip Sayap Indikasi remote


Fungsi Di… Kipas (FCQ, FHQ dan FAQ) control
Operasi ayun Ayun Ayun
Termostat ON di L
Program Mode Kering Pengaturan arah aliran udara Posisi yang diatur Posisi yang diatur
Operasi ayun Ayun Ayun
Termostat OFF di OFF
Program Mode Kering Pengaturan arah aliran udara Posisi yang diatur Posisi yang diatur

Termostat OFF di Mode Operasi ayun Ayun Ayun


Diatur
Pendinginan Pengaturan arah aliran udara Set position Posisi yang diatur
Operasi ayun Horisontal
Berhenti (Kesalahan) OFF —
Pengaturan arah aliran udara Posisi yang diatur
Pencegahan Operasi ayun Ayun Ayun
L ()
pembekuan Pengaturan arah aliran udara Posisi yang diatur Posisi yang diatur
() LL Operasi pada unit tipe cassette

35 Function and Control


Function Details SiMT281416E

3.1.5 Kontrol Kipas Unit Indoor


Ikhtisar
Selama kompresor memulai dan menghentikan kontrol, kipas unit indoor akan menerima instruksi dari
unit outdoor untuk melindungi kompresor agar tidak terkena cairan dan untuk menjamin bahwa
kompresor melancarkan start up:
 Kontrol kipas unit indoor selama kompresor berhenti
 Kontrol kipas unit indoor sebelum kompresor startup
 Kontrol kipas unit indoor saat kompresor startup

Selama kompresor berhenti


Tap kipas unit indoor
Termostat OFF Pengaturan remote control
Pendinginan indoor/Pendinginan otomatis
Remote control OFF OFF
Termostat OFF OFF
Program kering
Remote control OFF OFF

Sebelum kompresor startup


Tap kipas unit indoor
Pendinginan indoor/Pendinginan otomatis Pengaturan remote control
Program kering L

3.1.6 Kontrol pencegahan kondensasi embun


 FHQ dan FAQ
Di pendinginan dan operasi kering, kontrol berikut dilakukan untuk mencegah kondensasi embun
ketika blade horisontal meniupkan udara ke bawah.

[Kondisi mulai]

& • Blade horisontal diatur untuk aliran ke bawah


Operasi pendinginan (operasi kompresor) berlangsung selama 20 menit.

[Kontrol pencegahan kondensasi embun]


Operasi kering dengan aliran udara horisontal dilakukan selama 1 jam.

Catatan:
1. Ketika ada perubahan ke mode pemanasan/kipas, arah aliran udara dan keadaan ON/OFF operasi
selama kontrol pencegahan kondensasi embun, reset kontrol ini.

Function and Control 36


SiMT281416E Function Details

3.1.7 Kontrol Pompa Kuras


 Operasi Pendinginan, Operasi Kering
FCQ dan FAQ
Biasanya pompa kuras ON (Termostat ON/OFF)

Tidak termasuk FCQ

· Operasi Pendinginan atau Kering


&
· Termostat ON

Pompa kuras OFF Pompa kuras OFF

Tidak termasuk yang


disebutkan di atas
(1)

1. Ketika mengubah ON ke OFF, operasi residual dilakukan selama 5 menit.

3.1.8 Fungsi Pencegahan Pembekuan


Unit akan melakukan fungsi termostat OFF paksa dalam kondisi berikut:

Termostat OFF yang disebabkan oleh pencegahan pembekuan.


Berdasarkan penilaian untuk mencegah penukar panas indoor dari pembekuan, termostat secara paksa
diputar ke OFF.

suhu
penukar panas Kontrol pencegahan pembekuan
unit indoor
Reset setelah 10 menit berkelanjutan
Reset dan timer kumulatif
dihapus setelah 10 menit berkelanjutan
10 minutes
7ºC
Timer kumulatif dihapus setelah 20 menit berkelanjutan
4ºC
Termostat berputar ke OFF setelah kumulatif 40
menit
-1ºC
Termostat berputar ke OFF setelah 1 menit berkelanjutan
setelah 8 menit dari startup
-3ºC Termostat berputar ke OFF setelah 1 menit berkelanjutan
setelah 8 menit dari startup
-5ºC

3.1.9 Restart Otomatis


Tujuan
Tujuan fungsi auto-restart adalah untuk secara otomatis melanjutkan mode operasi yang sama ketika
unit beroperasi saat catu daya dipulihkan setelah gagal daya.

Jangan menggunakan fungsi "Restart Otomatis" untuk memulai/menghentikan unit setiap hari.

Tindakan pencegahan saat memutar daya ke OFF


 Ketika Anda harus memutar catu daya ke OFF untuk melakukan pemeliharaan, pastikan untuk
memutar saklar ON/OFF remote control ke OFF terlebih dahulu.
 Jika Anda memutar catu daya ke OFF sementara saklar ON/OFF remote control masih ON, "fungsi
restart otomatis" secara otomatis memulai kipas unit indoor dengan segera dan kipas unit outdoor
dimulai secara otomatis 3 menit setelah catu daya direstart.
 Jangan memulai/menghentikan unit dengan mencabut catu daya. Hentikan unit dengan
menghentikan komando dari remote kontrol atau kontrol opsional sebelum mencabut catu daya.
Pastikan bahwa kompresor dan kipas unit outdoor dihentikan sebelum mencabut catu daya
sehingga "fungsi Pemulihan Refrigeran" diselesaikan dengan benar.
 Ketika merestart unit setelah daya dicabut selama jangka waktu yang lama membiarkan unit ke
OFF dengan catu daya yang terhubung selama sekitar setengah jam (Lihat "Kontrol Pemanas Bak
Mesin" dan "Kontrol Operasi Pemanasan Awal").

37 Function and Control


Function Details SiMT281416E

3.2 Unit Outdoor


3.2.1 Siaga Restart
Untuk mencegah kompresor dari seringnya ON/OFF dan menyeimbangkan tekanan di saluran
refrigeran, lakukan termostat OFF paksa selama 3 menit setelah kompresor berhenti. Selain itu, kipas
unit outdoor melakukan operasi residual selama beberapa saat untuk mempercepat penyeimbangan
dan mencegah refrigeran masuk ke evaporator.
 RZR50-71LVVM(4)
Termostat OFF Siaga restart selesai
ON
Kompresor OFF 
Operasi 
selesai 

Katup ekspansi
480 pls

elektronik 

Beralih ke "Berhenti" atau "Mulai kontrol" setelah "Siaga
restart" selesai.

0 pls 


30 detik.
Kipas unit outdoor ON 

OFF 

operasi residual

 RZR100-140LVVM(4), RZR100-140LUY1(4)
Termostat OFF Siaga restart selesai
Kompresor ON
OFF

Operasi 
selesai 
D 

A
Katup ekspansi
elektronik
C

B E 
0 pls
10 30 30 30  Beralih ke "Berhenti" atau "Mulai kontrol"
det.det.det. det.  setelah "Siaga restart" selesai.



 RZR100 RZR125·140

 A Membuka derajat
ON  300 pls sebelum berhenti
kipas unit outdoor 
Operasi OFF
 B 300 pls 110 pls
residual
C 480 pls 130 pls
selama 3 menit D 480 pls 166 pls
E 0 pls 87 pls

Function and Control 38


SiMT281416E Function Details

3.2.2 Kontrol Operasi Pemanasan Awal


Ikhtisar
Setelah kompresor diputar ke OFF, operasi pemanasan awal akan diaktifkan untuk menghindari
pelarutan refrigeran dalam minyak kompresor.

Kondisi pemicu
Kondisi startup
• Selama kompresor berhenti

• 6 jam atau kurang berlalu setelah daya ON


&
ATAU • 60 menit atau lebih berlalu setelah kompresor berhenti
& • Suhu udara outdoor tidak turun.
• Suhu pipa buang < 40˚C

Kondisi akhir • Konfirmasi termostat ON

& • 6 jam atau lebih berlalu setelah daya ON


& • 60 menit atau lebih berlalu setelah kompresor berhenti
ATAU • Suhu udara outdoor turun.
• Suhu pipa buang > 43˚C

39 Function and Control


Function Details SiMT281416E

3.2.3 Kontrol Startup


Kontrol startup
Ketika kompresor start up, frekuensi start ditetapkan selama jangka waktu tertentu pada frekuensi
rendah untuk mencegah kembalinya refrigeran.
 RZR50-71LVVM(4)
Penyeimbangan Penyeimbangan Kontrol startup
tekanan mulai tekanan selesai selesai
Kontrol penyeimbangan
tekanan sebelum Kontrol startup
kompresor mulai
(60 detik)
0 Hz 144 Hz
Kompresor

480 pls
Katup ekspansi 0 pls
elektronik
40 detik 60 detik

8 Step ON

Kipas unit outdoor


OFF

Kecepatan kipas
yang diatur L

Kipas unit indoor


(Termostat OFF)
OFF
(Remote control OFF)

 RZR100LVVM(4), RZR100LUY1(4)
Penyeimbangan
Penyeimbangan Kontrol startup
tekanan mulai tekanan selesai selesai
kontrol penyeimbangan
tekanan sebelum Kontrol startup
kompresor mulai

228 Hz
Kompresor
Pendinginan
(<25˚C) 65 pls

Katup ekspansi
elektronik
8 Step ON
(Pendinginan Ta 
40˚C)

Kipas unit outdoor

OFF
(Pendinginan Ta > 40˚C)

Kecepatan kipas yang


diatur
(Pendinginan) L
Kipas unit indoor
(Termostat OFF)

(Remote control OFF)


OFF
10~120 detik

Function and Control 40


SiMT281416E Function Details

 RZR125·140LVVM(4), RZR125·140LUY1(4)
Penyeimbangan Penyeimbangan Kontrol startup
tekanan mulai tekanan selesai selesai
Kontrol penyeimbangan
tekanan sebelum Kontrol startup
kompresor mulai

112 Hz
Kompresor
Pendinginan
(<25˚C)(<25˚C)
Cooling 65 pls
65 pls
Katup ekspansi
elektronik
8 Step ON
(Pendinginan Ta 
840˚C)
Step ON
(Cooling Ta  40˚C)

Kipas unit outdoor


OFF
OFF
(Cooling Ta > 40˚C)
(Pendinginan Ta > 40˚C)

Kecepatan kipas yang


diatur
Set fan speed
(Pendinginan) L
(Cooling)
Kipas unit indoor
(Termostat OFF)

(Remote control OFF) OFF

10~120 detik

41 Function and Control


Function Details SiMT281416E

3.2.4 Kontrol Frekuensi Start


Ikhtisar
Kompresor inverter akan start up dengan nilai frekuensi tetap yang terbatas selama jangka waktu
tertentu untuk mencegah cairan kembali ke kompresor, dan untuk membatasi arus start.

Umum
Waktu kontrol startup normal adalah 2~3 menit. Waktu kontrol frekuensi start maksimum dibatasi
hingga 10 menit.

Selama startup kompresor, perbedaan tekanan akan ditambah agar memiliki perbedaan tekanan
yang cukup untuk pergantian katup empat arah.

Grafik

Hz
Kontrol normal
A Hz

Step 1

ON ± 1 menit. 2~3 menit. waktu

1 tahap 3 tahap
RZR50-71LVVM(4) RZR100LVVM(4) RZR125-140LVVM(4) RZR100-140LUY1(4)
A Hz 144 Hz 228 Hz 112 Hz 112 Hz

Kondisi akhir
Kontrol startup akan dihentikan ketika nilai tekanan rendah < 0,6 MPa atau ketika waktu start
maksimal 10 menit sudah tercapai jika nilai tekanan rendah tetap di > 0,6 Mpa.

3.2.5 Kontrol Step Kompresor


Ikhtisar
Setelah fungsi "Kontrol frekuensi start" dihentikan, frekuensi kompresor yang ideal akan ditentukan
dengan "Kontrol step kompresor".

Umum
Frekuensi operasi kompresor dikontrol untuk menjaga suhu penguapan konstan dalam pendinginan.

Frekuensi dapat diubah setiap 20 detik. Perubahan frekuensi maksimum = 2 step/perubahan. (= max 6
step/menit)

Pada saat situasi tidak normal (misalnya perlindungan arus inverter) perubahan per step juga = 2 step/
perubahan, tetapi interval 20 detik dapat berkurang, sehingga perubahan bisa lebih cepat.

Cata
tan Ketika fungsi kontrol lainnya diaktifkan (misalnya kontrol pipa buang), mereka dapat mengubah
frekuensi kompresor menggunakan input selain yang biasanya digunakan oleh fungsi "Kontrol step
kompresor".

Function and Control 42


SiMT281416E Function Details

Pendin
ginan Pada pendinginan, target frekuensi operasi akan ditentukan dengan t indoor dan suhu penguapan.

t pendinginan= Suhu yang diatur remote control – Suhu udara hisap indoor.

Tergantung pada beban pendinginan, target suhu penguapan (Te) bernilai antara 2°C  Te  20°C.

Step frekuensi
Frekuensi operasi untuk unit inverter SkyAir RZR merupakan nilai yang dipilih dari daftar dengan
pengaturan frekuensi tetap yang diprogram dalam memori unit:

Frekuensi operasi kompresor


No. Step
RZR50~71LVVM(4) RZR100LVVM(4) RZR125~140LVVM(4) RZR100~140LUY1(4)
3 42 Hz 19.0 Hz 41 Hz 41 Hz
4 51 Hz 21.0 Hz 44 Hz 44 Hz
5 63 Hz 23.0 Hz 48 Hz 48 Hz
6 72 Hz 26.0 Hz 52 Hz 52 Hz
7 81 Hz 29.0 Hz 57 Hz 57 Hz
8 93 Hz 32.5 Hz 62 Hz 62 Hz
9 102 Hz 36.5 Hz 67 Hz 67 Hz
10 111 Hz 41.5 Hz 72 Hz 72 Hz
11 123 Hz 46.5 Hz 78 Hz 78 Hz
12 132 Hz 52.0 Hz 84 Hz 84 Hz
13 144 Hz 56.0 Hz 90 Hz 90 Hz
14 156 Hz 61.0 Hz 94 Hz 94 Hz
15 165 Hz 64.0 Hz 98 Hz 98 Hz
16 177 Hz 68.0 Hz 102 Hz 102 Hz
17 189 Hz 72.0 Hz 107 Hz 107 Hz
18 201 Hz 76.0 Hz 112 Hz 112 Hz
19 213 Hz 79.0 Hz 117 Hz 117 Hz
20 217.5 Hz 82.0 Hz 123 Hz 123 Hz
21 222 Hz 85.0 Hz 131 Hz 131 Hz
22 258 Hz 88.5 Hz 139 Hz 139 Hz
23 264 Hz 94.0 Hz 147 Hz 147 Hz
24 276 Hz 99.0 Hz 155 Hz 155 Hz
25 288 Hz 103.0 Hz 164 Hz 164 Hz
26 297 Hz 109.0 Hz — —
27 321 Hz — — —
28 333 Hz — — —
29 348 Hz — — —
30 354 Hz — — —

43 Function and Control


Function Details SiMT281416E

3.2.6 Kontrol Kecepatan Kipas Unit Outdoor


Kontrol kecepatan kipas
Kecepatan kipas unit outdoor akan dikontrol dalam fungsi suhu udara outdoor yang sebenarnya,
tekanan kondensasi, perbedaan tekanan antara tekanan rendah dan tinggi, dan rasio kompresi .

Untuk detailnya silahkan lihat "Kontrol Perbedaan Tekanan".

Tabel step kipas


RZR50-71LVVM(4) RZR100LVVM(4)

Pendinginan Pendinginan
Step M1F Step M1F
0 0 rpm 0 0 rpm
1 200 rpm 1 200 rpm
2 250 rpm 2 250 rpm
3 320 rpm 3 300 rpm
4 390 rpm 4 360 rpm
5 430 rpm 5 430 rpm
6 515 rpm 6 515 rpm
7 620 rpm 7 620 rpm
8 940 rpm 8 800 rpm

RZR125-140LVVM(4)

Pendinginan
Step M1F M2F
0 0 rpm 0 rpm
1 250 rpm 0 rpm
2 400 rpm 0 rpm
3 285 rpm 250 rpm
4 360 rpm 325 rpm
5 445 rpm 410 rpm
6 545 rpm 510 rpm
7 660 rpm 625 rpm
8 830 rpm 830 rpm

RZR100-140LUY1(4)

Pendinginan
Step M1F M2F
0 0 rpm 0 rpm
1 250 rpm 0 rpm
2 400 rpm 0 rpm
3 285 rpm 250 rpm
4 360 rpm 325 rpm
5 445 rpm 410 rpm
6 545 rpm 510 rpm
7 660 rpm 625 rpm
8 RZR100 800 rpm 800 rpm
RZR125 790 rpm 755 rpm
RZR140 786 rpm 751 rpm

Catatan:
Lihat "Kontrol Perbedaan Tekanan" pada halaman 48

Function and Control 44


SiMT281416E Function Details

3.2.7 Kontrol Perlindungan Tekanan Rendah


Untuk mencegah tekanan rendah yang tidak normal dalam sistem, fungsi kontrol berikut akan
diaktifkan. Tekanan rendah terdeteksi oleh sensor tekanan rendah.

 RZR50-140LVVM(4)

Operasi normal

Lp > 0.15Mpa terus


Lp < 0.12MPa selama 30 detik

Frekuensi batas atas kompresor A Hz

Lp < 0.12Mpa terus


selama 5 menit

Berhenti 10 kali atau


kurang di 200 menit
Kompresor berhenti: 0 Hz

Berhenti 11 kali di 200 menit

Berhenti tidak normal (indikasi " ")

RZR50-71 RZR100 RZR125-140


A Hz 42 Hz 57 Hz 41 Hz

 RZR100-140LUY1(4)

Operasi normal

LPS LPS mereset terus


mengaktifkan selama 30 detik

Frekuensi batas atas kompresor 41 Hz

LPS mengaktifkan terus


selama 5 menit

Berhenti 10 kali atau


kurang di 200 menit
Kompresor berhenti: 0 Hz + OFF

Berhenti 11 kali di 200 menit

Berhenti tidak normal (indikasi " ")

45 Function and Control


Function Details SiMT281416E

3.2.8 Kontrol Perlindungan Tekanan Tinggi


Untuk mencegah tekanan tinggi yang tidak normal dalam sistem dan karenanya menghindari aktivasi
alat pengaman tekanan tinggi, fungsi kontrol berikut akan diaktifkan.

Bagan alur

Operasi normal

Hp > B MPa Hp  F MPa


Frekuensi operasi kompresor – Frekuensi operasi kompresor
1 step/10 detik. +1 step/1 menit.

Hp > C MPa Hp  G MPa


Frekuensi operasi kompresor Frekuensi operasi kompresor
A Hz Hp < E MPa +1 step/5 menit.

 HPS mengaktifkan (kecuali


ATAU RZR100LUV1)
 Hp > D MPa selama 1 menit

Kompresor berhenti
Berhenti 15 kali atau
kurang di 300 menit
 HPS mengaktifkan (RZR-HUY1)
OR
ATAU  Berhenti
• HPS activates16(RZR-HUY1)
kali di 300 menit
• Stopped 16 times in 300 minutes

Berhenti tidak normal (indikasi " ")

Jika tekanan batas resistensi bantalan menurun selama operasi lamban kompresor, batas bawah
frekuensi dibatasi.
[Dalam pendinginan]

Hp  3.04 MPa Batas bawah


Operasi normal frekuensi kompresor
Hp < 2.84 MPa H Hz
Setelah 30 detik

Parameter

RZR50-71LVVM(4) RZR100LVVM(4) RZR125-140LVVM(4) RZR100-140LUY1(4)


A Hz 51 Hz 124.5 Hz 62 Hz 123 Hz
B MPa 3.57 MPa 3.68 MPa 3.68 MPa 3.19 MPa
C MPa 3.67 MPa 3.77 MPa 3.77 MPa 3.29 MPa
D MPa 3.92 MPa 3.92 MPa 3.92 MPa 3.19 MPa
E MPa 3.52 MPa 3.63 MPa 3.63 MPa 3.14 MPa
F MPa 3.42 MPa 3.43 MPa 3.43 MPa 3.94 MPa
G MPa 3.42 MPa 3.58 MPa 3.58 MPa 3.04 MPa
H Hz 63 Hz 57 Hz 48 Hz 48 Hz

Function and Control 46


SiMT281416E Function Details

3.2.9 Kontrol Suhu Pipa Buang


Ikhtisar
Frekuensi operasi kompresor akan dikontrol untuk menghindari suhu kompresor tinggi yang tidak
normal (lihat juga kontrol katup ekspansi elektronik).

Bagan alur

Operasi normal
• Td <Td
A <°CA C
OR
ATAU  •&Frekuensi batas atas
Td > B °C  Frekuensi batas atas= Frekuensi
• & = Frekuensi
maksimummaksimum
• Td < BTd °C< B C

Compressor
Frekuensi batasupper
atas limit frequency
kompresor – Compressor
Frekuensi upper
batas limit
atas frequency
kompresor +
–1 step/20
1 step/20 sec.
detik. +11step/1
step/1min.
menit.
• Td  C °C
 Td ≥ C C terus selama 5 menit  •TdTd< <A C
• & continues for 5 minutes Td  B °C A °C
 300 detik• 300 seconds
OR ATAUOR  &
ATAU  & • & • Td ≤ B
 Td C
B °C
 Td > D C • 55 minutes
menit berlalu
elapsed
Frekuensi batas
Compressor upperatas
limitkompresor
frequency
HHHz
Hz

• Td  E °C terus selama
ATAU G menit
• Td  F °C
Berheti 10 kali atau kurang di 200 menit
Kompresor berhenti

Berhenti 11 kali
di 200 menit
Berhenti tidak normal (indikasi " ")

Parameter

RZR50-71LVVM(4) RZR100LVVM(4) RZR125-140LVVM(4) RZR100-140LUY1(4)


A °C 70 °C 100 °C 100 °C 100 °C
B °C 105 °C 105 °C 105 °C 105 °C
C °C 110 °C 110 °C 110 °C 110 °C
D °C 115 °C 120 °C 120 °C 120 °C
E °C 105 °C 110 °C 115 °C 115 °C
F °C 120 °C 125 °C 135 °C 135 °C
G min. 15 min. 15 min. 10 min. 10 min.
H Hz 102 Hz 87 Hz 62 Hz 58 Hz
Td = Suhu pipa buang

[Kontrol derajat bukaan katup ekspansi elektronik]


Kontrol normal

Td  95˚C Td  80˚C
Batas bawah derajat bukaan katup Td  90˚C Batas bawah derajat bukaan katup
ekspansi elektronik ekspansi elektronik
+5 pulse/Pendinginan selama 2 menit -5 pulse/Pendinginan selama 2 menit

Td  100˚C
Batas bawah derajat bukaan katup
ekspansi elektronik
+10 pulse/Pendinginan selama 2
menit

47 Function and Control


Function Details SiMT281416E

3.2.10 Kontrol Perlindungan Arus Inverter


 Kontrol oleh suhu sirip radiasi (RZR100-140LVVM(4), RZR100-140LUY1(4))
Membatasi frekuensi batas atas operasi kompresor untuk mencegah tripping pada kompresor yang
disebabkan leh suhu sirip radiasi.
Suhu sirip radiasi  A˚C Frekuensi kompresor
Operasi normal
–1 step/6 detik.
Compressor frequency
Frekuensi kompresor
Frekuensi batas atas inverter +1step/2
+1 step/2menit.
min. Suhu sirip  B˚C berlangsung
= Frekuensi maksimum selama 2 menit

RZR100LVVM(4) RZR125-140LVVM(4) RZR100-140LUY1(4)


A°C 86°C 84°C 86°C
B°C 83°C 81°C 83°C

 Kontrol perlindungan arus inverter


Membatasi frekuensi operasi kompresor untuk mencegah tripping pada kompresor yang disebabkan
oleh arus lebih inverter.

Arus inverter Operasi normal Frekuensi batas atas inverter


>Arus turun = Frekuensi maksimum
Frekuensi kompresor Frekuensi kompresor
–1 step/6 detik. +1 step/2 menit.
Kondisi arus Inverter<Arus turun terus selama 2
menit

 Untuk semua model


 Outdoor unit panas
Suhu penukar heat exchanger
unit outdoor (cairan) ≥
temperature unitindoor
(liquid)
suhu penukar panas Indoor unit heat
&  exchanger temperature
Suhu penukar panas unit outdoor (cairan) ≥
25 C
Outdoor unit heat exchanger
temperature (liquid)  25˚C
Arus turun P A Arus turun Q A

 Outdoor unit heat


Suhu penukar panasexchanger
unit outdoor (cairan) <
temperature (liquid)
suhu penukar panas  indoor
unit Indoor unit heat
ATAU  exchanger temperature
Suhu penukar panas unit outdoor (cairan) <
Outdoor
25 C unit heat exchanger
temperature (liquid)  25˚C

RZR50-71LVVM(4) RZR100LVVM(4) RZR125-140LVVM(4) RZR100-140LUY1(4)


PA 9.0 A 18.0 A 20 A 13 A
QA 6.6 A 17.5 A 20 A 11 A

Function and Control 48


SiMT281416E Function Details

3.2.11 Kontrol Perbedaan Tekanan


Untuk memastikan rasio kompresi (perbedaan tekanan antara tekanan tinggi dan rendah) pada kondisi
suhu udara outdoor yang rendah dalam mode pendinginan, kipas unit outdoor dan target frekuensi
kompresor dapat bervariasi.
Hp - Lp > 1.08MPa
Hp - Lp < 0.93MPa OR
ATAU Hp < 2.94MPa
& Rasio kompresi < 2.1 Operasi normal ATAU Rasio kompresi > 2.4
Hp < 1.86MPa Ta > 27˚C
Ta < 25˚C Outdoor
Kipas unitunit fan
outdoor
Pembatasan frekuensi operasi ++1 step/90 detik.
1 step/90 sec.
kompresor (lihat berikut ini)
Hp - Lp > 0.98MPa
&
Hp - Lp < 0.78MPa Rasio kompresi > 2.2
& ATAU ATAU
Rasio kompresi  1.8 Hp > 2.25MPa
Hp < 1.57MPa Kipas
Outdoor unitunit
outdoor
fan Kipas unitunit
Outdoor outdoor
fan
–-11 step/90
step/90 sec.
detik. Step 1
Hp - Lp > 0.88MPa
Hp - Lp < 0.78MPa &
ATAU
Rasio kompresi < 1.8 ATAU Rasio kompresi > 2.0
& Hp < 1.57MPa Hp > 1.66MPa
Tfin < 66˚C Tfin  81˚C
Kipas unit outdoor: Berhenti

Pembatasan frekuensi operasi kompresor


 RZR-LVVM

Suhu udara outdoor ≤ 20C Frekuensi batas bawah


Outdoor air temperature  20˚C Step 22
Pembatasan
frekuensi Frekuensi batas atas
Suhu udara outdoor > 25C Step 2

 RZR-LUY1(4)

RZR100 RZR125-140
Suhu udara outdoor < 20˚C
Frekuensi batas
Frequency
Pembatasan atas 112 Hz 139 Hz
restriction
frekuensi
Suhu udara outdoor  21˚C Frekuensi batas
bawah 72 Hz

49 Function and Control


Function Details SiMT281416E

3.2.12 Kontrol Perlindungan Arus Keseluruhan


Amati arus keseluruhan dan batasi frekuensi operasi kompresor batas atas agar pemutus sirkuit tidak
melebihi nilai kapasitasnya.
Operasi normal Arus unit outdoor ≤ nilai arus
batas atas
Arus unit outdoor > nilai & Frekuensi operasi kompresor
arus batas atas batas atas= Frekuensi maksimum
Arus unit
Outdoor unitoutdoor
current ≤ nilai
upper
arus batas
limit current valueatas
Frekuensi operasi kompresor batas atas Frekuensi operasi kompresor batas atas
–1 step/E detik. +1 step/2 menit.
Outdoor unitoutdoor
Arus unit current >> nilai
upper
arus batas atas

Arus batas atas (A)


Nilai berikut tergantung pada suhu udara outdoor.
Juga bervariasi tergantung pada model.
Arus
keseluruhan (A)

Arus A
Arus B
Arus C

Arus D

25 28 43 50 Suhu udara outdoor (˚C)

RZR50-71LVVM(4) RZR100LVVM(4) RZR125-140LVVM(4) RZR100-140LUY1(4)


AA 14.5 A 25.0 A 24.0 A 13.5 A
BA 13.2 A 25.0 A 24.0 A 10.0 A
CA 13.2 A 24.0 A 23.0 A 8.5 A
DA 8.0 A 21.0 A 16.0 A 3.0 A
E detik 6 detik 10 detik 10 detik 6 detik

Function and Control 50


SiMT281416E Function Details

3.2.13 Operasi Penampungan


 RZR125·140LUV1, RZR100-140HUY1
Ikhtisar
Jika unit harus dipindah atau dilepas, lakukan operasi penampungan sebelum melepas pemipaan
lapangan. Dengan melakukan operasi penampungan, semua refrigeran akan dikumpulkan di unit
outdoor.

Prosedur

Prosedur Tindakan Pencegahan


Pastikan bahwa katup penghenti cairan dan
1 Mulai "Operasi kipas saja" dari remote control.
gas terbuka.
Tekan tombol penampungan (BS1) pada PCB unit Kompresor dan kipas unit outdoor akan
2
outdoor. mulai secara otomatis.
Setelah operasi berhenti (setelah 3 ~ 5 menit) tutup
3 katup penghenti cairan dulu kemudian katup
penghenti gas.

Setelah "Operasi Penampungan" selesai, layar


remote control berkabel kosong atau menunjukkan
Pastikan bahwa katup penghenti terbuka
4 indikasi kesalahan " ". Anda tidak dapat memulai
sebelum merestart unit.
unit dari remote control sebelum memutar catu
daya ke OFF lebih dulu.

Perhatian
 Menekan tombol penampungan (BS1) pada PCB unit outdoor dapat menyebabkan kipas unit
outdoor dan indoor mulai beroperasi secara otomatis.
 Pastikan untuk membuka katup penghenti setelah pekerjaan pemipaan selesai. Pastikan untuk
tidak mengoperasikan unit dengan katup penghenti tertutup, atau kompresor akan rusak.

3.2.14 Operasi Pemulihan Minyak


Ikhtisar
Ketika kompresor beroperasi selama jangka waktu tertentu pada frekuensi rendah, muka minyak di
kompresor menjadi rendah karena pengembalian minyak yang tidak lengkap. Untuk mencegah
kerusakan kompresor dan dalam kasus terburuk menghindari kompresor terkunci, operasi pemulihan
minyak akan dilakukan.

Detail
Selama operasi pemulihan minyak, frekuensi operasi kompresor akan ditingkatkan selama jangka
waktu 5 menit. Operasi pemulihan minyak hanya dijalankan dalam mode pendinginan.

3.2.15 Fungsi Operasi yang Disimulasikan


 RZR50-140LVVM(4)
Untuk termistor, operasi yang disimulasikan dilakukan dengan 2 cara yang berbeda sebagaimana
ditunjukkan berikut bahkan ketika kesalahan terdeteksi.
A. Operasi berlanjut meskipun kode kesalahan ditampilkan pada remote control.
Termistor yang berlaku
· Termistor udara outdoor
· Termistor pipa distribusi penukar panas
· Termistor pipa cairan
· Termistor udara hisap unit indoor
· Termistor penukar panas unit indoor
B. Operasi berlanjut meskipun kesalahan terdeteksi. Jika tombol Pemeriksaan/Operasi Uji coba
ditekan, kode kesalahan ditampilkan.
Termistor yang berlaku
· Termistor remote control
· Termistor sirip radiasi

51 Function and Control


Function Details SiMT281416E

Catatan
Untuk kesalahan termistor selain A dan B di atas, berhenti tidak normal dilakukan dan tidak ada
operasi yang disimulasikan yang dilakukan.
Termistor yang dapat berlaku
· Termistor pipa hisap
· Termistor pipa buang
· Termistor penukar panas menengah

 RZR100-140LUY1(4)
Ketika kesalahan pada salah satu termistor berikut terjadi, operasi akan berlanjut sekaligus
menampilkan alarm yang dapat berlaku pada remote control. Kesalahan termistor sirip radiasi hanya
ditampilkan ketika menekan tombol Pemeriksaan/Operasi Uji coba pada remote control.
· Termistor udara outdoor
· Termistor penukar panas udara outdoor
· Termistor sirip radiasi
· Termistor pipa buang
· Termistor udara hisap unit indoor
· Termistor penukar panas indoor

Catatan:
Operasi yang disimulasikan tidak akan dilakukan jika termistor yang disebutkan berikut rusak:
· Termistor udara hisap
· Termistor penukar panas indoor
· Termistor penukar panas udara outdoor

3.2.16 Kontrol Operasi Uji coba


Tujuan
Saat mengoperasikan unit RZR untuk pertama kalinya setelah pemasangan, unit akan - tergantung
pada mode operasi yang dipilih - melakukan operasi uji coba dulu.

Situasi 1
Pendinginan – operasi pertama setelah pemasangan di "Mode pendinginan"
Operasi pendinginan di
Termostat pendinginan ON "Mode operasi uji coba" Operasi pendinginan normal
selama 3 menit

Situasi 2
Pendinginan – operasi pertama setelah pemasangan di "Mode operasi uji coba"
Operasi Pendinginan Operasi pendinginan di Operasi pendinginan di
dengan tombol Operasi Uji "Mode operasi uji coba" termostat ON paksa.
coba selama 3 menit

Catatan:
 Ketika menghidupkan dalam mode operasi uji coba, unit akan merasakan parameter pemasangan
di tempat (misalnya: lupa untuk membuka katup penghenti, ..) dan menunjukkan kode kesalahan
yang berlaku jika diperlukan.
 Jika remote control menunjukkan " ", " " atau " " sebagai kode kesalahan, ada kemungkinan
katup penghenti tertutup atau saluran keluar aliran udara terhambat.
 Periksa sambungan kabel cabang antar unit (kabel 1-2-3) jika kode kesalahan " " atau " "
ditampilkan pada remote control.
 Jika kode kesalahan “ ” ditampilkan pada remote control, periksa ketidakseimbangan tegangan.
 Jika kode kesalahan " " ditampilkan pada remote control, ada kemungkinan bahwa bagian aliran
udara tertutup.
 Jika tidak ada tampilan kode kesalahan, operasi pendinginan berlanjut tanpa gangguan. (Tetapi,
kontrol ini dilakukan setelah refrigeran pulih dengan menggunakan saklar penampungan dan pada
saat operasi pertama setelah penggantian PCB unit outdoor.)

Function and Control 52


SiMT281416E

Bagian 5
Pengaturan Lapangan
1. Operasi Uji Coba ...................................................................................... 53
1.1 Pemeriksaan Operasi Uji Coba ...........................................................53
2. Pengaturan Lapangan dari Remote Control........................................... 54
2.1 Remote Control Berkabel ....................................................................54
2.2 Remote Control Nirkabel .....................................................................57
2.3 Isi Pengaturan dan No. Kode untuk Unit Indoor ...................................58
2.4 Isi Pengaturan dan No. Kode untuk Unit Outdoor ................................59
3. Pengaturan Lapangan dari Demand Adaptor
(Untuk selain RZR50-71LVVM(4)) .......................................................... 62
3.1 Fungsi i-Demand ................................................................................62
4. Pengaturan Lapangan dari PCB Unit Outdoor
(Untuk RZR100-140LVVM(4), RZR100-140LUY1(4)) ........................... 63
4.1 Pengaturan dengan Tombol BS ..........................................................63
4.2 Mode Pengaturan 1 ............................................................................63
4.3 Mode Pengaturan 2 ............................................................................64
4.4 Mode Monitor .....................................................................................66
4.5 Daftar Isi Coba Lagi dan Kesalahan ....................................................67
5. Operasi Darurat ........................................................................................ 69

Field Setting 52
Test Operation SiMT281416E

1. Operasi Uji Coba


1.1 Pemeriksaan Operasi Uji Coba
1.1.1 Pemeriksaan sebelum Operasi Uji Coba
Sebelum melakukan operasi uji coba, lakukan hal berikut:
Step Tindakan
1 Pastikan tegangan pada sisi primer pemutus pengaman:
 (220-240 V) ± 10% untuk unit 1-fasa
 (380-415 V) ± 10% untuk unit 3-fasa.
2 Buka sepenuhnya katup penghenti cairan dan gas.

1.1.2 Pemeriksaan Operasi Uji Coba


Untuk melakukan operasi uji coba, periksa hal berikut:
 Pastikan bahwa pengaturan suhu remote control berada pada tingkat terendah dalam mode
pendinginan atau gunakan mode uji coba.
 Periksa daftar periksa berikut:

Daftar periksa Perhatian atau peringatan


 Berbahaya jika membongkar unit selama badai.
Apakah semua unit terpasang dengan aman?  Kemungkinan kerusakan pada sambungan
pipa.
Apakah kabel bumi dipasang sesuai dengan Berbahaya jika kebocoran listrik terjadi.
standar lokal yang berlaku?
Apakah semua saluran keluar dan masuk  Pendinginan buruk.
udara unit indoor dan outdoor tidak terhambat?
Apakah saluran mengalir dengan lancar? Kebocoran air.
Apakah pipa dengan memadai diisolasi dengan
Kebocoran air.
panas?
Apakah kebocoran gas pada sambungan  Pendinginan buruk.
sudah diperiksa?  Berhenti.
Apakah tegangan catu daya sesuai dengan Pengoperasian yang salah.
spesifikasi pada plat nama?
Apakah ukuran kabel ditentukan dan sesuai Kerusakan kabel.
dengan peraturan lokal?
Apakah sinyal remote control diterima oleh
Tidak ada operasi.
unit?

53 Field Setting
Field Setting from Remote Controller SiMT281416E

2. Pengaturan Lapangan dari Remote Control


Fungsi individual unit indoor dapat diubah dari remote control. Pada saat pemasangan atau setelah
pemeriksaan layanan/perbaikan, membuat lakukan pengaturan lapangan sesuai dengan uraian berikut.
Pengaturan yang salah dapat menyebabkan kesalahan.
(Ketika aksesori opsional dipasang pada unit indoor, pengaturan untuk unit indoor harus diubah. Lihat
informasi pada buku pegangan opsi.)

2.1 Remote Control Berkabel


2.1.1 BRC1C61/BRC1D61

UNIT NO. MODE NO.


SECOND FIELD
CODE NO. SETTING
FIRST MODE
CODE NO. 3 4

1 7
6 5 2

1. Ketika
1. Jika pada mode pada mode normal,
normal, tekan tekan
tombol “ ” “ selama
tombol ” button4fordetik
TEST
4 seconds
atau or more,kemudian
lebih, and the FIELD
masukSETTING
ke MODE
MODE is
PENGATURAN LAPANGAN. entered.
2. Select
2. Pilih NO. MODEthe yangdesired MODEdengan
diinginkan the “ “ ”” button
NO. withtombol . (g).
3. Pada kontrol grup, saat pengaturan oleh masing-masing unit (mode
3. During group control, when setting by each indoor unit indoorNo.
(No.20, 22 and
mode 20,23 have
22, danbeen selected),
23 dipilih), tekan
tombol “ ”press the “ ” button (g) and select the INDOOR UNIT NO. to be set. (This
dan pilih NO. UNIT INDOOR yang akan diatur (Operasi ini tidak perlu bila pengaturan operation is unnecessary
oleh
grup) when setting by group.)
4. Tekan4.tombol the ““ ” ” upper
Pressatas button
dan pilih NO.( KODE
) and select
PERTAMA FIRST CODE NO.
5. Press the “ ” lower button
5. Tekan tombol bawah “ ” dan pilih NO. KODE KEDUA (g) and select the SECOND CODE NO.
6. Press
6. Tekan tombol “ ” the “ ”
sekali dan pengaturan ini DISETEL.settings are SET.
button ( ) once and the present
Press“ the” “ untuk
7. Tekan7.tombol ” button
TEST
(g) toke
kembali return
MODE to the NORMAL MODE.
NORMAL.

(Contoh) (Example)
if during
Jika selama group setting
pengaturan and waktu
grup dan the time to clean
untuk air filter is setfilter
membersihkan to filter
udaracontamination, no. to “10”
heavy, set modeFILTERAN,
diatur ke KONTAMINASI
BERAT, atur
first code no. to “0”,
NO. MODE ke and
"10",second
NO. KODE
code no. to “02”. ke "0", dan NO. KODE KEDUA ke "02".
PERTAMA

Field Setting 54
SiMT281416E Field Setting from Remote Controller

2.1.2 BRC1E62

<Layar utama>

(1) (1) Tekan dan tahan tombol Batal selama


4 detik atau lebih.
Menu pengaturan lapangan
ditampilkan.

(2) Pilih Pengaturan lapangan di menu


pengaturan lapangan, dan tekan
tombol Menu/Enter. Layar daftar
pengaturan lapangan ditampilkan.

(3) Sorot mode, dan pilih “No. Mode” yang


diinginkan dengan menggunakan
tombol (Up/Down).
<Layar menu pengaturan lapangan>

(2) (4) Untuk pengaturan per unit indoor saat


kontrol grup (Ketika No. Mode 20 , 21
, 22 , 23 , 25 dipilih), sorot No. unit
dan pilih “No. unit indoor” untuk diatur
dengan menggunakan tombol
(Up/Down). (Untuk pengaturan total
grup, operasi ini tidak diperlukan.)
Untuk pengaturan individual per unit
indoor, pengaturan saat ini
ditampilkan. Dan, NO. KODE
KEDUA “ - ” berarti tidak ada fungsi.
Tekan tombol Menu/Enter.
(5) Sorot NO. KODE KEDUA dari NO.
KODE PERTAMA yang akan diubah,
<Layar pengaturan lapangan>
dan pilih “NO. KODE KEDUA” dengan
menggunakan tombol (Up/Down).
Untuk pengaturan individual per Untuk pengatuan total Beberapa pengaturan nomor
unit indoor grup
model yang sama tersedia.
(3) (3) Untuk pengaturan total grup, semua
(4) (5) NO. KODE KEDUA yang akan diatur
(5) ditampilkan sebagai “  ”.
Ganti “” dengan NO. KODE KEDUA
yang akan diatur. Dan, NO. KODE
KEDUA “ - ” berarti tidak ada fungsi.

SECOND CODE NO.

FIRST CODE (SW) NO.

Tekan tombol Menu/Enter.

55 Field Setting
Field Setting from Remote Controller SiMT281416E

(6) Tekan tombol Menu/Enter. Layar


<Layar konfirmasi pengaturan> konfirmasi pengaturan ditampilkan.
(6)
(7) (7) Pilih Ya dan tekan tombol Menu/Enter.
Detail pengaturan ditentukan dan layar
daftar pengaturan lapangan kembali.

(8) Untuk beberapa perubahan pengaturan,


ulangi “(3)” sampai “(7)”.

(9) Setelah semua perubahan pengaturan


selesai, tekan tombol Batal dua kali.
Tekan tombol Menu/Enter.
(10) Lampu latar padam, dan “Koneksi
sedang diperiksa, Harap tunggu
Konfirmasi pengaturan sebentar” ditampilkan untuk inisialisasi.
Setelah inisialisasi, layar utama kembai.

PERHATIAN
• Ketika aksesori opsional dipasang pada unit indoor, pengaturan unit indoor
dapat diubah. Lihat panduan aksesori opsional.
• Untuk detail pengaturan lapangan unit outdoor, lihat panduan pemasangan
yang dilampirkan pada unit outdoor.

Field Setting 56
SiMT281416E Field Setting from Remote Controller

2.2 Remote Control Nirkabel

Tombol UP
Mode No.
Field setting mode Tombol DOWN

Tombol RESERVE
No. kode pertama

Tombol MODE
No. kode kedua

Tombol PEMERIKSAAN/UJI COBA

Pengat
uran Untuk mengatur pengaturan lapangan, Anda harus mengubah:
 No. Mode
 No. kode pertama
 No. kode kedua

Untuk mengubah pengaturan lapangan, lakukan hal berikut:


Langkah Tindakan
1 Tahan tombol PEMERIKSAAN/UJI COBA selama 4 detik pada mode normal untuk masuk ke
"Mode pengaturan lapangan."
2 Tekan tombol MODE untuk memilih “No. Mode” yang diinginkan
3 Tekan tombol UP untuk memilih “No. kode pertama”
4 Tekan tombol DOWN untuk memilih “No. kode kedua”
5 Tekan tombol RESERVE untuk mengatur pengaturan saat ini.
6 Tekan tombol PEMERIKSAAN/UJI COBA unuk kembali ke “Mode normal.”

57 Field Setting
Field Setting from Remote Controller SiMT281416E

2.3 Isi Pengaturan dan No. Kode untuk Unit Indoor


: Pengaturan pabrik
No. Kode Kedua
No. No. Kode
Mode Pertama Deskripsi pengaturan
01 02 03 04
10 (20) Berat/ringan Filter Ringan Sekitar Berat Sekitar —
kontaminasi filter sangat 10.000 5.000 jam.
(Pengaturan untuk tahan jam.
tampilan waktu untuk lama
membersihkan filter Filtera Sekitar Sekitar
udara)
0 tahan 2.500 1.250 jam. —
(Atur tampilan waktu lama jam.
untuk membersihkan
filter udara sampai Standar Sekitar Sekitar 100
setengah ketika ada filter 200 jam.
kontaminasi filter jam.
yang berat)
Filter tahan lama Filter sangat tahan —
1 Tipe filter tahan lama lama —

Termistor remote dari remote TH1 = remote TH1 = udara hisap —


2 control —
control
3 Tampilan filter Tampilan Tidak ada tampilan — —
11 (21) 0 Jumlah indoor untuk 1 outdoor Pair Twin Triple Double twin
Pengaturan ganda terpadu atau Pengaturan grup pengaturan individual —
1 —
individual
2 Kipas OFF saat termostat OFF LL-kecepatan OFF — —
OFF Selesai penyesuaian Mulai
7 Penyesuaian aliran udara aliran udara penyesuaian —
aliran udara
12 (22) Termostat pemanas kecepatan LL-kecepatan Mengatur kecepatan —
3 —
kipas OFF
5 Restart otomatis Dinonaktifkan Diaktifkan — —

Termostat pendingin kecepatan LL-kecepatan Mengatur kecepatan —


6 —
kipas OFF
13 (23) 0 Pengaturan tinggi plafon Normal Tinggi Sangat tinggi —
Aliran 4-arah Aliran 3-arah Aliran 2-arah
Pemilihan arah aliran udara
1 (pengaturan ketika blocking pad —
kit dipasang).

Pencegahan Standar Pencegahan


Pengaturan jangkauan aliran udara plafon kotor
4 —
penyesuaian arah aliran udara

6 Tekanan statis eksternal Normal Tinggi Rendah —


15 (25) Kelebihan kelembaban termostat Tidak lengkap Lengkap —
1 —
OFF

Pemilihan interlock pelembap


Tidak lengkap Lengkap —
3 —
pompa kuras
Tidak lengkap Lengkap —
Pemilihan pengaturan lapangan
5 untuk pengaturan ventilasi —
individual dengan remote control

1
FCQ Normal Tinggi Sangat tinggi
FCQ50 - 71  2,7 m 2,7 – 3,0 m 3,0 – 3,5 m
FCQ100 - 140  3,2 m 3,2 – 3,6 m 3,6 – 4,2 m

FHQ Normal Tinggi


FHQ71 - 125  2,7 m 2,7 – 3,5 m
FHQ140 Normal —

Field Setting 58
SiMT281416E Field Setting from Remote Controller

2.4 Isi Pengaturan dan No. Kode untuk Unit Outdoor


Pegaturan remote control
Tabel berikut berisi pengaturan remote control.
: Pengaturan pabrik

No. Kode Kedua


No. No. Kode
Isi pengaturan Mode Pertama 01 02 03 04 05 06
Pilih No. Kode Kedua “02” untuk Pengaturan Suara
0 –
Pengaturan Suara Pelan di Malam Hari Pelan di Malam Hari

Pilih No. Kode Kedua “06” untuk waktu 16 22h00~


(26) –
mulai dan berhenti 1 08h00

59 Field Setting
Field Setting from Remote Controller SiMT281416E

2.4.1 Operasi di Malam Hari dengan Suara Pelan


Tujuan
Merendahkan suara operasi unit outdoor.

Pengat
uran Operasi di malam hari dengan suara pelan dapat diaktifkan dengan:
1. Kontrol otomatis (Dengan pengaturan lapangan dari remote control)
2. Aktivasi eksternal (dari PCB KRP58M opsional)

 Operasi di Malam Hari dengan Suara Pelan oleh Kontrol Otomatis


Operasi di malam hari dengan suara pelan dapat diatur dengan pengaturan
lapangan dari remote control berkabel: : Pengaturan pabrik

No. Kode Kedua


No. No. Kode
Isi pengaturan Mode Pertama 01 02 03 04 05 06
Pilih No. Kode Kedua “02” untuk Pengaturan Suara
0 –
Pengaturan Suara Pelan di Malam Hari Pelan di Malam Hari
16
Pilih No. Kode Kedua “06” untuk waktu 22h00~
(26)
1 –
mulai dan berhenti 08h00

Metode Penentuan Waktu Mulai dan Berhenti


Pada mode pengaturan 16(26)-0-02, operasi di malam hari dengan suara pelan akan dilakukan
dengan asumsi bahwa waktu saat ini sesuai dengan suhu udara outdoor.
Mode otomatis akan dimulai ketika suhu udara ourdoor = rata-rata maksimum 10 hari terakhir -5°C
dan akan dilakukan selama 10 jam.
Suhu udara outdoor maksimum seharusnya terjadi pada jam 14:00.
Karena penilaian waktu dibuat sesuai dengan suhu udara outdoor, waktu yang disebutkan di atas
hanya perkiraan.

Grafik

Mulai operasi Mengakhiri


Suhu udara di malam hari operasi di malam
outdoor +8 jam Start lowsuara
dengan night +10 jam End
hari low night
dengan suara
maksimum noise
pelanoperation noise
pelanoperation

Garis kecenderungan yang


menunjukkan fluktuasi suhu
udara outdoor dalam 24 jam.

Pengaturan Prioitas Kapasitas


Pada mode pengaturan 16(26)-0-04, operasi di malam hari dengan suara pelan akan berhenti ketika
beban pendinginan meningkat. Dalam hal ini, operasi akan kembali ke operasi normal. Unit akan
kembali ke operasi di malam hari dengan suara pelan jika beban pendinginan berkurang lagi.

Field Setting 60
SiMT281416E Field Setting from Remote Controller

 Aktivasi Eksternal dari PCB Opsional


Grafik
Operasi di malam hari dengan suara pelan juga dapat diaktifkan dari PCB (KRP58M51) opsional.

Konektor transmisi
DS 1 (pada PCB X6A unit outdoor)
Konektor catu daya ON

(pada PCB X77A unit outdoor) OFF


1 2 34

X80A
X81A
X800M

X801M

3 2 1 LNOP COM

Output pada X801M = 12VDC, 12mA


Panjang kabel maksimum = 100 meter
X801M

3 2 1 LNOP COM

Operasi di malam hari dengan suara pelan akan mulai ketika kontak pada LNOP-COM ditutup dan akan
tetap aktif selama kontak tersebut ditutup. Tidak ada pengaturan lapangan pada unit outdoor atau dengan
remote control yang diperlukan.
Operasi di malam hari dengan suara pelan akan berakhir saat kontak dibuka kembali.
Penggunaan KRP58M51 memungkinkan penggunaan time clock eksternal.
Pengecualian
Operasi di malam hari dengan suara pelan akan ditolak dalam kondisi berikut:
 Operasi residual penampungan
 Kontrol startup
 Pemulihan minyak

61 Field Setting
Field Setting from Outdoor Unit PCB (For RZR100-140LVVM(4), RZR100-140LUY1(4)) SiMT281416E

3. Pengaturan Lapangan dari Demand Adaptor


(Untuk selain RZR50-71LVVM(4))

3.1 Fungsi i-Demand


Tujuan
Mengatur batasan terhadap konsumsi daya dari sistem. (misalnya kontrol anggaran, membatasi
konsumsi daya pada saat puncak, ..)

Peng
atutr 3 pengaturan demand yang berbeda dapat dipilih dengan menggunakan terminal X801M:
an  Demand 1  Tutup kontak antara COM dan kontak 1
 Demand 2  Tutup kontak antara COM dan kontak 2
 Demand 3  Tutup kontak antara COM dan kontak 3
Konektor transmisi
DS1 (pada PCB X6A unit outdoor)
Konektor catu daya ON
OFF
(pada X77A unit outdoor) 1 2 34

X80A
X81 A

X800M

X801M
Output pada X801M = 12VDC, 12mA
3 2 1 LNOP COM Panjang kabel maksimum = 100 meter

X801M

3 2 1 LNOP COM

Demand 1
Pembatasan konsumsi daya dalam fungsi pengaturan pada DS1:

PENGATURAN DS1
Konsumsi Daya
1 2 Maksimum
OFF OFF 60%

ON OFF 70%

OFF ON 80%

ON ON 100%

Demand 2
Pembatasan konsumsi daya diatur ke 40%.

Demand 3
Termostat paksa OFF.

Field Setting 62
SiMT281416E Field Setting from Demand Adaptor (For except RZR50-71LVVM(4))

4. Pengaturan Lapangan dari PCB Unit Outdoor


(Untuk RZR100-140LVVM(4), RZR100-140LUY1(4))

4.1 Pengaturan dengan Tombol BS


Dengan "Mode pengaturan 1," "Mode pengaturan 2" dan "Mode monitor," berbagai pengaturan dan
data dapat diperiksa.
(1) Mode pengaturan 1
Status awal (operasi normal) adalah "Mode pengaturan 1." Mode ini menunjukkan status operasi -
"UJI COBA (operasi uji coba)," "HWL (kesalahan)," "L.N.O.P (operasi di malam hari dengan suara
pelan)" atau "DEMAND (operasi demand)"
(2) Mode pengaturan 2
Setiap status operasi dapat diubah.
(3) Mode monitor
Mode ini menunjukkan "operasi pengembalian minyak," "kelas unit outdoor," "isi coba lagi," "isi
kesalahan," "penyebab operasi droop," dll.
Dengan menggunakan tombol MODE, mode dapat diubah sebagai berikut.

Tekan dan tahan


(Normal) Tekan MODE
MODE (BS1) selama 5
detik (BS1) sekali.
Mode pengaturan 2 Mode pengaturan 1 Mode monitor
MODE MODE MODE
.Tekan MODE (BS1) sekali.
ON OFF Berkedip
H1P H1P H1P

4.2 Mode Pengaturan 1


Dengan menggunakan mode ini, kondisi berikut dapat diperiksa:
• Kondisi operasi saat ini (operasi/pemeriksaan saluran normal/uji coba dan normal/kesalahan)
• Kondisi operasi di malam hari dengan suara pelan (tingkat normal/suara pelan di malam hari 1, 2
dan 3)
• Kondisi operasi demand (tingkat normal/demand 1, 2 dan 3)
Kondisi di atas dapat diperiksa dengan melakukan langkah berikut:

Prosedur untuk memeriksa item periksa

Sistem ini biasanya diatur ke "Mode MODE TEST HWL L.N.O.P DEMAND : ON : OFF : BERKEDIP
pengaturan 1." H1P H2P H3P H4P H5P H6P H7P
h h h h h h h
Jika sistem diatur ke mode lain,
tekan MODE (BS1) untuk mengatur
sistem ke "Mode pengaturan 1." Selama "Mode pengaturan 1," lampu
selalu OFF.
Tampilan operasi uji coba
Di operasi normal
Periksa sistem untuk setiap Di operasi uji coba
kondisi melalui tampilan LED. Di operasi pemeriksaan saluran
(Lihat informasi dalam tabel di
sebelah kanan.) Tampilan kesalahan
Normal
Kesalahan
Tampilan operasi di malam hari dengan
suara pelan
Operasi normal
Pengaturan tingkat suara pelan
Tampilan tingkat demand
Operasi normal
Tingkat demand 1
Tingkat demand 2
Tingkat demand 3

63 Field Setting
Field Setting from Outdoor Unit PCB (For RZR100-140LVVM(4), RZR100-140LUY1(4)) SiMT281416E

4.3 Mode Pengaturan 2


Di mode ini, pengatuan untuk item berikut dapat dilakukan dengan menggunakan tombol BS.

Tekan dan tahan MODE (BS1) selama 5


detik dan atur ke “Mode pengaturan 2.” <Pemilihan kondisi pengaturan>
Tekan SET (BS2) dan atur ke kondisi
pengaturan yang Anda inginkan.

Tekan RETURN (BS3) dan pilih kondisi.
<Pemilihan item pengaturan>
Tekan SET (BS2) dan atur tampilan
LED ke item pengaturan yang
ditunjukkan pada tabel di bawah.

Tekan RETURN (BS3) dan pilih item. Tekan RETURN (BS3) dan atur ke
(kondisi pengaturan saat ini berkedip.) status awal “Mode pengaturan 2.”

 Jika Anda ragu bagaimana cara


melakukannya, tekan MODE (BS1) dan
kembali ke mode pengaturan 1.

Tampilan item pengaturan Tampilan kondisi pengaturan


Tampilan LED Tampilan LED
No. Item Kondisi
pengatuan H1P H2P H3P H4P H5P H6P H7P pengaturan H1P H2P H3P H4P H5P H6P H7P
30% demand k h h h k h h
3 Operasi k h h h h k k 40% demand k h h h h k h
demand 2 (pengaturan pabrik)
50% demand k h h h h h k
k h h h h h k
28 Mode OFF (pengaturan
pemulihan k h k k k h h pabrik)
refrigeran k h h h h k h
ON
Angka dalam kolom “No.” merupakan jumlah berapa kali untuk menekan SET (BS2).

Pengaturan Operasi Demand 2


Dengan pengaturan ini, operasi kompresor dapat dikontrol untuk mengurangi konsumsi daya.
(60% - 80% demand tersedia ketika demand adaptor (aksesori opsional) digunakan.)
Item pengaturan Kondisi pengaturan Deskripsi
30% demand Beroperasi dengan 30% dari konsumsi daya
40% demand (pengaturan yang dinilai. dengan 40% dari konsumsi daya
Beroperasi
Operasi Demand 2
pabrik) yang dinilai.
50% demand Beroperasi dengan 50% dari konsumsi daya
yang dinilai.

[Prosedur kerja] h: OFF l: BERKEDIP k: ON


Prosedur operasi H1P H2P H3P H4P H5P H6P H7P
Tekan dan tahan MODE (BS1) "Mode pengaturan 1" selama 5 detik atau k h h h h h h
lebih dan atur ke "Mode pengaturan 2."
Tekan SET (BS2) 3 kali untuk mengatur tampilan LED seperti yang k h h h h k k
ditunjukkan pada tabel di sebelah kanan.
Tekan RETURN (BS3) sekali. (Pengaturan saat ini ditampilkan.) k h h h h l h
30% dari konsumsi daya yang dinilai k h h h l h h
Tekan SET (BS2) untuk mengatur
40% dari konsumsi daya yang dinilai k h h h h l h
tampilan LED seperti yang ditunjukkan
pada tabel di sebelah kanan. 50% dari konsumsi daya yang dinilai k h h h h h l
30% dari konsumsi daya yang dinilai k h h h k h h
Tekan RETURN (BS3) sekali untuk 40% dari konsumsi daya yang dinilai k h h h h k h
memilih. 50% dari konsumsi daya yang dinilai k h h h h h k
Tekan RETURN (BS3) sekali lagi untuk pelaksanaan. (Tampilan LED dalam k h h h h h h
status awal "Mode pengaturan 2".)

Field Setting 64
SiMT281416E Field Setting from Outdoor Unit PCB (For RZR100-140LVVM(4), RZR100-140LUY1(4))
Tekan MODE (BS1) sekali untuk kembali ke Mode pengaturan 1 (operasi h h h h h h h
normal).

65 Field Setting
Field Setting from Outdoor Unit PCB (For RZR100-140LVVM(4), RZR100-140LUY1(4)) SiMT281416E

Pengaturan Mode Pemulihan Refrigeran


Ketika unit pemulihan refrigeran terhubung di tempat untuk memulihkan refrigeran, buka sepenuhnya
katup ekspansi elektronik unit outdoor untuk membantu pemulihan.
[Prosedur kerja]
(1) Hentikan operasi.
(2) Putar mode pemulihan refrigeran ke ON dengan melakukan prosedur berikut.

h: OFF l: BERKEDIP k: ON
Prosedur operasi H1P H2P H3P H4P H5P H6P H7P
Tekan dan tahan MODE (BS1) "Mode pengaturan 1" selama 5 k h h h h h h
detik atau lebih dan atur ke "Mode pengaturan 2."
Tekan SET (BS2) 28 kali untuk mengatur tampilan LED seperti k h k k k h h
yang ditunjukkan pada tabel di sebelah kanan. (1)
Tekan RETURN (BS3) sekali. (Pengaturan saat ini ditampilkan.) k h h h h h l
Tekan SET (BS2) sekali untuk mengatur tampilan LED seperti k h h h h l h
yang ditunjukkan pada tabel di sebelah kanan.
Tekan RETURN (BS3) sekali untuk memilih. k h h h h k h
Ketika RETURN (BS3) ditekan sekali lagi, katup ekspansi k h h h h h h
elektronik terbuka sepenuhnya.
(3) Sambungkan unit pemulihan refrigeran untuk melakukan pemulihan refrigeran.
(4) Setelah pemulihan refrigeran, putar mode pemulihan refrigeran ke OFF dengan melakukan
prosedur berikut atau putar daya unit outdoor ke OFF.
Prosedur operasi H1P H2P H3P H4P H5P H6P H7P
Tekan SET (BS2) 28 kali untuk mengatur tampilan LED seperti k h k k k h h
yang ditunjukkan pada tabel di sebelah kanan. (1)
Tekan RETURN (BS3) sekali. (Pengaturan saat ini ditampilkan.) k h h h h l h
Tekan SET (BS2) sekali untuk mengatur tampilan LED seperti k h h h h h l
yang ditunjukkan pada tabel di sebelah kanan.
Tekan RETURN (BS3) sekali untuk memilih. k h h h h h k
Ketika RETURN (BS3) ditekan sekali lagi, katup ekspansi k h h h h h h
elektronik tertutup sepenuhnya.
1. Jika Anda ragu berapa kali Anda sudah menekan tombol, tekan MODE (BS1) sekali untuk kembali
ke "Mode pengaturan 1" dan mulai prosedur operasi dari awal lagi.

Field Setting 66
SiMT281416E Field Setting from Outdoor Unit PCB (For RZR100-140LVVM(4), RZR100-140LUY1(4))

4.4 Mode Monitor


Di mode ini, item berikut dapat diperiksa dengan menggunakan tombol BS.

Untuk masuk ke mode monitor, tekan Tampilan LED


MODE (BS1) saat dalam "Mode H H H H H H H
pengaturan 1". No. Item pengaturan 1 2 3 4 5 6 7 Tampilan data
P P P P P P P
Indikasi operasi
0 pengembalian minyak l h h h h h h Lihat Tampilan
data (1).
<Pemilihan item pengaturan>
Lihat Tampilan
Tekan SET (BS2) dan atur tampilan 1 Indikasi kelas unit outdoor l h h h h h k data (2).
LED ke item pengaturan.
2 Isi coba lagi (terbaru) l h h h h k h

<Konfirmasi isi pengaturan> Isi coba lagi (1 siklus l h h h h k k


3 sebelumnya)
Tekan RETURN (BS3) untuk menampilkan Isi coba lagi (2 siklus l h h h k h h Lihat
data yang berbeda dari item pengaturan. 4 sebelumnya)
"Tampilan
5 Isi kesalahan (terbaru) l h h h k h k kode
kesalahan"
Isi kesalahan (1 siklus l h h h k k h pada halaman
6 sebelumnya) berikutnya.
Tekan RETURN (BS3) dan beralih ke
Isi kesalahan (2 siklus l h h h k k k
status awal "Mode monitor". 7 sebelumnya)
 Tekan MODE (BS1) dan kembali ke Indikasi penyebab operasi l h h k h k h Lihat Tampilan
10 drooping data (3).
"Mode pengaturan 1".
Angka dalam kolom “No.” merupakan jumlah berapa kali untuk
menekan SET (BS2).

Tampilan data (1)


Tampilan LED
Isi tampilan H1P H2P H3P H4P H5P H6P H7P
Dalam operasi normal l h h h h h h
Dalam operasi l h h h h h l
pengembalian minyak

Tampilan data (2) Tampilan data (3)


Tampilan LED Tampilan LED
Isi tampilan H1P H2P H3P H4P H5P H6P H7P Isi tampilan H1P H2P H3P H4P H5P H6P H7P
No. pengaturan l h h h h h l Normal (tidak l h h h h h l
RZR100LVVM(4) l h h l h h h dalam operasi
RZR125LVVM(4) l h h l h h l drooping)
Drooping tekanan l h h h h l h
RZR140LVVM(4) l h h l h l h rendah
RZR100LUY1(4) l h h l h h h Drooping tekanan l h h h h l l
RZR125LUY1(4) l h h l h h l tinggi
RZR140LUY1(4) l h h l h l h Drooping pipa l h h h l h h
buang inverter
Drooping arus l h h h l h l
inverter
Drooping suhu sirip
radiasi l h h h l l h

Drooping inverter l h h h l l l

Drooping l h h l h h h
keseluruhan arus
Drooping lainnya l h h l h h l

67 Field Setting
Field Setting from Outdoor Unit PCB (For RZR100-140LVVM(4), RZR100-140LUY1(4)) SiMT281416E

4.5 Daftar Isi Coba Lagi dan Kesalahan


Lakukan langkah berikut untuk memeriksa isi coba lagi dan kesalahan.
Untuk masuk ke “Mode monitor”, tekan MODE
(BS1) saat dalam "Mode pengaturan 1". <Tampilan RETURN 2>
Ketika SET (BS2) ditekan, tampilan LED untuk
RETURN 2 berubah ke ON.

<Pemilihan ite m coba lagi atau kesalahan>


<Tampilan RETURN 3>
Tekan SET (BS2) untuk mengatur tampilan LED
ke item coba lagi atau kesalahan. Ketika SET (BS2) ditekan, tampilan LED untuk
RETURN 3 berubah ke ON.

<Tampilan RETURN 1> Tekan RETURN (BS3) untuk mengembalikan


Ketika RETURN (BS3) ditekan, tampilan LED sistem ke keadaan awal "Mode monitor."
untuk RETURN 1 berubah ke ON.
Menekan MODE (BS1) akan kembali ke
"Mode pengaturan 1."

k: ON h : OFF l: BERKEDIP
1 2 3
Kode H H H H H H H H H H H H H H H H H H H H H H H H
kesala Isi coba lagi atau kesalahan A 1 2 3 4 5 6 7 A 1 2 3 4 5 6 7 A 1 2 3 4 5 6 7
han P P P P P P P P P P P P P P P P P P P P P P P P
E1 Kelainan PCB unit outdoor l l h k h h l l l l k h h h h ll l k k h h h h
Kelainan tekanan tinggi (terdeteksi oleh l l k h h h l ll l k k h h h h
E3 saklar tekanan tinggi)
E4 Kelainan tekanan rendah l l k h hl h h l l k k h h h h
E5 Motor kompresor terkunci l l k h hl h l l l k k h h h h
Motor DC 1 terkunci l l k h h l l l l l k k h h h l
Kelainan Motor DC 2 terkunci l l k k h h l h
E7 motor kipas Kelainan transmisi l l k k h h l l
unit outdoor inverter
Konektor katup ekspansi l l k h l h h l l l k k h h hl
Kelainan
katup elektronik terputus
E9 ekspansi Kesalahan karena kondisi l l k k h h l h
elektronik basah
Kelainan suhu pipa buang l l h k h l h l l l k h h h l l l l k k h h h l
Kontrol suhu l l k k h h l h
F3 pipa buang Termistor pipa buang
terputus
H3 Kelainan sistem saklar Tekanan Tinggi l l h k h l h h l l k h h h l ll l k k h h h h
H9 Kelainan sistem termistor l l k h l h h l l l k k h h h h
J1 Kelainan sensor tekanan l l h k h l l h l l k h h h hl l l k k h h h h
J3 Kelainan termistor pipa buang l l k h h h l ll l k k h h h h
J5 Kelainan termistor pipa hisap l l k h hl h l l l k k h h h h
J6 Kelainan termistor penukar panas l l k h hl l h l l k k h h h h
Kelainan termistor penukar panas l l k h h l l ll l k k h h h h
J7 menengah
J8 Kelainan termistor pipa cairan l l k h l h h hl l k k h h h h
L1 Kelainan PCB unit outdoor l l h k h l l l l l k h h h h ll l k k h h h h
L4 Kenaikan suhu sirip radiasi l l k h hl h h l l k k h h h h
L5 Deteksi arus berlebih output l l k h hl h l l l k k h h h h
L8 Panas elektronik (Jeda waktu) l l k h l h h hl l k k h h h h
L9 Pencegahan berhenti (Jeda waktu) l l k h l h h l l l k k h h h h
Kelainan sistem transmisi (antara PCB l l k h l l h hl l k k h h h h
LC unit outdoor)

Field Setting 68
SiMT281416E Field Setting from Outdoor Unit PCB (For RZR100-140LVVM(4), RZR100-140LUY1(4))

k: ON h : OFF l: BERKEDIP
1 2 3
Kode Isi coba lagi atau kesalahan H H H H H H H H H H H H H H H H H H H H H H H H
kesala A 1 2 3 4 5 6 7 A 1 2 3 4 5 6 7 A 1 2 3 4 5 6 7
han P P P P P P P P P P P P P P P P P P P P P P P P
Fasa terbuka atau ketidakseimbangan l l h k l h h h l l k h h h hl l l k k h hh h
P1
tegangan catu daya
P4 Termistor sirip radiasi tidak normal l l k h h l h h l l k k h hh h
PJ Pengaturan kapasitas rusak l l k h l l h l l l k k h hh h
Peringatan kekurangan l l h k l h h l l l k h h h h h l l k k h hh l
U0 Kekurangan refrigeran
refrigeran l l k k h hl h
Kekurangan refrigeran
Inverter kekurangan l l k h h h l h l l k k h hh l
U2 Kelainan tegangan dan kelebihan
tegangan tegangan
catu daya SP-PAM (1) kelebihan l l k k h hl h
tegangan
Kesalahan transmisi antara unit indoor dan l l k h h l h h l l k k h hh h
U4
outdoor
UA Saklar pengaturan lapangan rusak l l k h l h l h l l k k h hh h
Kesalahan transmisi antara unit indoor dan l l k h l l l l l l k k h hh h
UF outdoor / pipa dan kabel tidak cocok /
kekurangan refrigeran

Catatan:
1. SP: Pulsa Tunggal
PAM: PAM merupakan bentuk modulasi sinyal yang mengontrol tegangan atau arus output.

69 Field Setting
Emergency Operation SiMT281416E

5. Operasi Darurat
Tujuan
Tabel berikut menjelaskan tujuan mode operasi paksa.
Jika... Maka...
 Remote control rusak Mode operasi paksa dapat digunakan untuk pendinginan. Dalam mode operasi
 PCB unit indoor rusak paksa, kompresor dipaksa untuk beroperasi sampai PCB unit indoor dan
 PCB unit outdoor rusak outdoor yang rusak kembali online.

Kondisi startup
Anda dapat mengoperasikan sistem secara manual dengan mengubah saklar darurat pada PCB unit
indoor dan outdoor dari "normal" ke "darurat". Ketika sistem beroperasi di "darurat", sistem tidak bisa
mengontrol suhu kamar.

Unit indoor dan outdoor harus diatur ke "darurat" ketika daya OFF.

Kondisi akhir
Anda dapat mengakhiri operasi darurat dengan mengubah saklar "darurat" kembali ke "normal" ketika
daya OFF.

Operasi darurat
Tabel berikut menjelaskan apa yang akan terjadi ketika saklar diatur ke "darurat":
Mengubah saklar ke "darurat" untuk… Ubah ke ON…
Unit indoor  Kipas unit indoor
 Pompa kuras
Unit outdoor  Kompresor
 Kipas unit outdoor

Cara mengatur Operasi Darurat


Untuk mengatur operasi darurat, lakukan hal berikut:
Langkah Tindakan

1 Putar daya ke OFF.


2 Switch
Ubah ON thedarurat
saklar emergency
(SS1)switch
ke ON (SS1)
padaon the unit
PCB indoor unit PCB.
indoor

(NORM.) (EMG.) (NORM.) (EMG.)


<Pengaturan pabrik> <Operasi darurat>

3 Ubah saklar darurat ke ON pada PCB unit outdoor


RZR-LVVM(4), RZR-LUY1(4) <Pengaturan pabrik> <Operasi darurat>
ON
COOL

ON
COOL

ON ON
EMG DS1

EMG DS1

1 2 1 2
12 12
OFF

HEAT

OFF

HEAT

Field Setting 70
SiMT281416E Emergency Operation

Langkah Tindakan

4 Atur saklar darurat pada PCB unit outdoor ke Pendinginan.


RZR-LVVM(4), RZR-LUY1(4)

COOL

COOL
ON

ON
EMG DS1

EMG DS1
ON ON

1 2 1 2

OFF

HEAT

OFF

HEAT
12 12

<Pengaturan pabrik> <Operasi darurat>


5 Putar catu daya ke ON.

Komponen aktif
Komponen Pendinginan paksa
Kompresor ON
Kipas unit outdoor Kecepatan kipas H
Kipas unit indoor Kecepatan kipas H
Pompa kuras ON

Informasi tambahan
 Selama operasi darurat, jangan mencoba untuk mengoperasikan peralatan dari remote control.
Remote control menunjukkan ketika operasi darurat aktif pada unit indoor.
 Jika alat pengaman diaktifkan selama darurat, semua aktuator diputar ke OFF.
 Pada pendinginan, unit hidup selama 20 menit dan kemudian berhenti selama 10 menit untuk
menghindari pembekuan koil indoor.
 Operasi darurat tidak dapat dilakukan ketika PCB rusak.
 Pastikan untuk mengatur saklar darurat di unit outdoor dan indoor.
 Unit tidak akan mengatur suhu selama operasi darurat.
 Ubah posisi saklar darurat hanya saat daya diputar ke OFF.

71 Field Setting
SiMT281416E

Bagian 6
Diagnosis Layanan
1. Pemeriksaan Pemeliharaan .................................................................... 73
1.1 Ikhtisar ...............................................................................................73
2. Pemecahan Masalah Berdasarkan Gejala ............................................. 75
2.1 Ikhtisar ...............................................................................................75
2.2 Peralatan tidak Berfungsi ....................................................................76
2.3 Kipas Unit Indoor Berfungsi, tapi Kompresor tidak Berfungsi................77
2.4 Operasi Pendinginan Mulai tapi Langsung Berhenti .............................78
2.5 Setelah Unit Mati, tidak Bisa Direstart untuk Beberapa Saat ................79
2.6 Peralatan Berfungsi tapi tidak Memberikan Pendinginan......................81
2.7 Peralatan Mengeluarkan Kabut Putih ..................................................82
2.8 Peralatan Mengeluarkan Suara atau Goncangan Keras.......................83
2.9 Peralatan Mengeluarkan Debu ............................................................85
2.10 LCD Remote Control Menampilkan“88”................................................85
2.11 Sirip Sayap Ayun tidak Berfungsi ........................................................86
3. Pemecahan Masalah Berdasarkan Indikasi LED ................................... 88
3.1 Pemecahan Masalah Berdasarkan LED pada Unit Indoor....................88
3.2 Pemecahan Masalah Berdasarkan LED pada PCB Unit Outdoor .........88
4. Pemecahan Masalah Berdasarkan Remote Control ............................. 89
4.1 Operasi Akses Mode...........................................................................89
4.2 Prosedur Diagnosis Sendiri dengan Remote Control ...........................90
4.3 Kode Kesalahan dan Deskripsi ..........................................................94
4.4 Kode Kesalahan - Sub Kode ...............................................................95
4.5 Alat Pengaman ...................................................................................98
5. Pemecahan Masalah Berdasarkan Indikasi pada Remote Control ...... 99
5.1 Kesalahan Alat Pelindung Eksternal ....................................................99
5.2 Kelainan PCB Unit Indoor ................................................................. 100
5.3 Kelainan Sistem Permukaan Air Buang ............................................. 101
5.4 Kelainan Motor Kipas Unit Indoor ...................................................... 102
5.5 Kelainan Motor Sirip Sayap Ayun/Terkunci ........................................ 104
5.6 Tegangan Catu Daya tidak Normal.................................................... 106
5.7 Kelainan Sistem Buang ..................................................................... 107
5.8 Kelainan Pengaturan Kapasitas ........................................................ 109
5.9 Kelainan Termistor............................................................................ 110
5.10 Kesalahan Gabungan antara PCB Unit Indoor dan PCB Kipas .......... 111
5.11 Kelainan Sistem Sensor Kelembaban ............................................... 112
5.12 Termistor Suhu Ruang pada Kelainan Remote Control ...................... 113
5.13 Kelainan PCB Unit Outdoor............................................................... 114
5.14 Kelainan Tekanan Tinggi (Terdeteksi oleh Saklar Tekanan Tinggi).....115
5.15 Motor Kompresor Terkunci ............................................................... 117
5.16 Kelainan Motor Kipas Unit Outdoor ................................................... 118
5.17 Kelainan Katup Ekspansi Elektronik .................................................. 120
5.18 Kelainan Suhu Pipa Buang ............................................................... 123
5.19 Kelainan Sistem Saklar Tekanan Tinggi ............................................ 125
5.20 Kelainan Sistem Termistor ................................................................ 126
5.21 Kelainan Sensor Tekanan ................................................................. 127
71 Service Diagnosis
SiMT281416E

5.22 Kelainan PCB Unit Outdoor............................................................... 128


5.23 Suhu Sirip Radiasi Meningkat ........................................................... 130
5.24 Kelebihan Arus Output DC (Instan) ................................................... 132
5.25 Panas Elektronik (Jeda Waktu) ......................................................... 134
5.26 Pencegahan Berhenti (Jeda Waktu) .................................................. 136
5.27 Kesalahan Sistem Transmisi antara PCB Unit Outdoor ...................... 138
5.28 Fasa Terbuka atau Ketidakseimbangan Tegangan Catu Daya ........... 139
5.29 Kelainan Termistor Sirip Radiasi ....................................................... 140
5.30 Kelainan Pengaturan Kapasitas ........................................................ 141
5.31 Kekurangan Refrigeran (Kesalahan) ................................................. 142
5.32 Kelainan Tegangan Catu Daya ......................................................... 143
5.33 Kesalahan Transmisi antara Unit Indoor dan Outdoor ........................ 144
5.34 Kesalahan Transmisi antara Unit Indoor dan Remote Control ............ 147
5.35 Kesalahan Transmisi antara Remote Control UTAMA dan
SUB Remote Control ........................................................................ 148
5.36 Kelainan Saklar Pengaturan Lapangan ............................................. 149
5.37 Kesalahan Pengaturan Alamat Terpusat ........................................... 150
5.38 Kesalahan Transmisi antara Unit Indoor dan Outdoor/Pipa dan Kabel
tidak Cocok/Kekurangan Refrigeran……………………...……………….151

Service Diagnosis 72
SiMT281416E Maintenance Inspection

1. Pemeriksaan Pemeliharaan
1.1 Ikhtisar
Ketika melakukan pemeliharaan, Anda setidaknya harus melakukan pemeriksaan berikut:

Unit indoor

Kabel transmisi antara unit


indoor dan outdoor
Apakah filter udara kotor?
Bagaimana dengan kapasitas saklar?
Bagaimana dengan ketebalan kabel?

Bagaimana dengan tegangan dan arus? Ke pemutus


khusus

Pipa refrigeran

Pipa buang
Unit outdoor
Outdoor
Pembumian
Pembumian

Pedoman untuk Kondisi Operasi Optimal


Pedoman nilai operasi ketika beroperasi dalam kondisi standar (pada Frekuensi yang dinilai) dengan
menekan tombol operasi uji coba pada remote control seperti tertera dalam tabel berikut.

Kipas unit indoor: tap H


Tekanan Tekanan Suhu pipa buang Suhu udara Unit Indoor: Unit Outdoor:
tinggi rendah hisap Diferensial Diferensial
Suhu antara Suhu antara
Udara Hisap Udara Hisap
dan Udara dan Udara
Buang Buang
Pendinginan 2.6 MPa ~ 0.6 MPa ~ 60°C ~ 100°C –2°C ~ 10°C 8°C ~ 18°C 7°C ~ 12°C
3.4 MPa 1.0 MPa

Kondisi Standar
Indoor Outdoor
Operasi Pendinginan 27°C DB/19°C WB 35°C DB
Selama atau setelah pemeliharaan, ketika catu daya di-restart, operasi restart secara otomatis oleh
"fungsi auto restart." Harap berhati-hati.

73 Service Diagnosis
Maintenance Inspection SiMT281416E

Korelasi antara Status Operasi Dan Tekana/Arus Berjalan AC


Kondisi dibanding nilai normal diringkas dalam tabel berikut.
(Diukur dari 15 - 20 menit atau lebih setelah operasi dimulai.)

Pendinginan
Status AC Tekanan Rendah Tekanan Tinggi Arus Berjalan
Kotoran pada Filter Udara Rendah Rendah Rendah
KorsletingSaluran Masuk/Saluran Keluar Rendah Rendah Rendah
Udara Unit Indoor
Kotoran pada Sirip Unit Outdoor Tinggi Tinggi Tinggi
KorsletingSaluran Masuk/Saluran Keluar Tinggi Tinggi Tinggi
Udara Unit Outdoor
Udara Tercampur di Refrigeran Tinggi Tinggi Tinggi
Air Tercampur di Refrigeran Rendah 1 Rendah Rendah
Kotoran Tercampur di Refrigeran Rendah 2 Rendah Rendah
Kekurangan Refrigeran (Gas) Rendah Rendah Rendah
Kompresi tidak Memadai Tinggi 3 Rendah Rendah

Catatan:
*1. Air dalam refrigeran membeku di dalam pipa kapiler atau katup ekspansi elektronik, dan
merupakan fenomena yang sama pada penampungan.
*2. Kotoran di refrigeran menyumbat filter dalam pipa, dan merupakan fenomena yang sama pada
penampungan.
*3. Diferensial tekanan antara tekanan tinggi dan rendah menjadi kecil.

Service Diagnosis 74
SiMT281416E Troubleshooting Based on Equipment Condition

2. Pemecahan Masalah Berdasarkan Gejala


2.1 Ikhtisar
Gejala Detail Tindakan
1 Peralatan tidak Berfungsi. Lihat halaman 76
2 Kipas unit indoor berfungsi, tapi kompresor tidak Lihat halaman 77
berfungsi.
Operasi pendinginan mulai tapi langsung
3 Lihat halaman 78
berhenti.
4 Setelah unit mati, tidak bisa direstart untuk Lihat halaman 79
beberapa saat.
5 Peralatan berfungsi tapi tidak memberikan Lihat halaman 81
pendinginan.
6 Peralatan mengeluarkan kabut putih. Lihat halaman 82
Peralatan mengeluarkan suara atau goncangan
7 Lihat halaman 83
keras.
8 Peralatan mengeluarkan debu. Lihat halaman 85
9 LCD remote control menampilkan . Lihat halaman 85
10 Sirip sayap ayun tidak berfungsi. Lihat halaman 86
Bau ruang dan rokok terkumpul di dalam unit
11 Peralatan mengeluarkan bau. indoor yang kemudian dibuang ke udara. Bagian
dalam unit indoor harus dibersihkan.

12 Sirip sayap beroperasi saat daya diputar ke ON. Hal ini normal. Sirip sayap melakukan inisialisasi
untuk penentuan posisi yang akurat.
Perubahan mode operasi menyebabkan sirip Hal ini normal. Ada fungsi kontrol yang
13 menggerakkan sirip sayap ketika mode operasi
sayap bergerak. diubah.
Sirip sayap secara otomatis bergerak selama Hal ini normal. Hal ini disebabkan oleh aktivasi
14 fungsi pencegahan kondensasi embun atau
pendinginan. fungsi pencegahan plafon kotor.
Kipas unit indoor beroperasi di tap "L" selama 1 Hal ini normal. Fungsi pemantauan secara
15 menit dalam mode "program kering" meskipun paksa mengoperasikan kipas selama 1 menit.
kompresor tidak beroperasi.

16 Pompa kuras beroperasi saat peralatan tidak Hal ini normal. Pompa kuras terus beroperasi
selama beberapa menit setelah peralatan
beroperasi. diputar ke OFF.
Ayun horisontal mengeluarkan udara ke arah Hal ini normal. Arah aliran udara dalam operasi
17 yang berbeda dalam pendinginan meskipun pendinginan/kering berbeda dengan dalam
sudah diatur ke posisi yang sama. operasi kipas.
18 Sirip sayap tetap horisontal meskipun sudah Hal ini normal. Sirip sayap tidak berayun dalam
diatur ke mode ayun. mode termostat OFF.

75 Service Diagnosis
Symptom-based Troubleshooting SiMT281416E

2.2 Peralatan tidak Berfungsi


Model yang Semua model seri SkyAir
Berlaku

Dugaan  Sekring putus atau kontak di sirkuit operasi terganggu


Penyebab  Saklar operasi atau titik kontak rusak
 Saklra tekanan tinggi rusak
 Saklar magnetik untuk motor kipas rusak
 Aktivasi atau kesalahan pada relay arus lebih untuk motor kipas
 Relay arus lebih untuk kompresor rusak
 Termostat pelindung kompresor rusak
 Isolasi tidak memadai dalam sistem listrik
 Titik kontak saklar magnetik untuk kompresor rusak
 Kompresor rusak
 Remote control rusak atau baterai habis (nirkabel)
 Pengaturan alamat remote control nirkabel salah

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa
rusak.

Apakah saklar daya OFF


YA
atau sekring untuk saklar daya putus? Putar saklar daya ke ON atau
ganti sekring.
TIDAK

YA
Apakah ada gagal daya? Tunggu sampai daya kembali.

TIDAK

Apakah saklar operasi YA


ditekan berulang kali? Normal.
Operasi start up setelah 3 menit
(3-menit siaga).
TIDAK

Apakah termostat diubah YA


Normal.
dan direset lagi?
Operasi start up setelah 3 menit
TIDAK (3 menit siaga).

Apakah lampu operasi YA


pada LCD remote Diagnosis berdasarkan kode
control berkedip? kesalahan pada remote control.
TIDAK

Apakah lampu operasi YA


pada bagian penerima sinyal Diagnosis berdasarkan kode
unit indoor berkedip? kesalahan pada remote control.

TIDAK

Komponen listrik rusak Periksa sistem listrik.

Service Diagnosis 76
SiMT281416E Troubleshooting Based on Equipment Condition

2.3 Kipas Unit Indoor Berfungsi, tapi Kompresor tidak


Berfungsi
Model yang Semua model seri SkyAir
Berlaku

Dugaan  Sekring putus atau kontak di sirkuit operasi terganggu


Penyebab  PCB kontrol unit outdoor rusak
 PCB unit indoor/outdoor rusak
 PCB inverter unit outdoor rusak
 Termistor udara hisap rusak

Pemecahan Masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa
rusak.

· Kipas unit indoor hidup pada pengaturan laju aliran udara.


· (Dalam pendinginan) Jika suhu udara hisap lebih tinggi dari suhu yang diatur
· (Dalam pemanasan) Ketika suhu udara hisap lebih rendah dari suhu yang diatur

Apakah saklar daya


YA
OFF atau sekring untuk Putar saklar daya ke ON atau ganti
saklar daya putus? sekring.
TIDAK

Apakah saklar
pemanas diputar ke ON pada YA
suhu udara outdoor > Normal.
32˚C? (Termostat OFF oleh suhu udara
outdoor)
TIDAK * Dalam operasi pemanasan,
kompresor tidak hidup pada
suhu udara outdoor 32C atau
HAP pada PCB unit lebih.
outdoor terus berkedip
YA Termostat secara paksa diputar
pada interval panjang (*1)
selama jangka waktu lima ke OFF.
menit berturut-turut atau (Lihat informasi pada bagian
lebih..
“Fungsi dan Kontrol” untuk setiap
unit outdoor.)
TIDAK
Putar catu daya ke OFF, kemudian Ganti PCB kontrol unit outdoor
periksa transistor daya. CHECK4 atau PCB unit indoor.

TIDAK
Apakah transistor Ganti PCB inverter unit outdoor.
daya normal?

YA

Apakah termistor TIDAK


udara hisap normal? Ganti termistor udara hisap.

YA
Ganti PCB kontrol unit outdoor.

Catatan:
1 HAP berputar ke ON selama 0,4 detik dan OFF selama 1,2 detik (berkedip sekitar 6 kali dalam
jangka waktu 10 detik)
(Biasanya, HAP berputar ke ON selama 0,4 detik dan OFF selama 0,4 detik (berkedip sekitar 12
kali dalam jangka waktu 10 detik)
CHECK 4 Lihat halaman 155.

77 Service Diagnosis
Troubleshooting Based on Equipment Condition SiMT281416E

2.4 Operasi Pendinginan Mulai tapi Langsung Berhenti


Model yang Semua model seri SkyAir
Berlaku

Dugaan  Refrigeran kelebihan isi


Penyebab  Udara tercampur di sistem refrigeran
 Saklar tekanan rusak
 Saklar magnetik untuk motor kipas unit outdoor rusak
 Relay bantu untuk motor kipas unit outdoor rusak
 Penukar panas unit outdoor kotor
 Ada sesuatu yang menyumbat aliran udara unit outdoor
 Kipas unit outdoor rusak
 Filter unit indoor kotor
 Penukar panas unit indoor kotor
 Ada sesuatu yang menyumbat aliran udara unit indoor
 Kipas unit indoor rusak

Pemecahan Masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa
rusak.

berkabel
Apakah jenis remote wired Apakah lampu operasi YA
control berkabel atau remote control berkedip? Diagnosis berdasarkan kode
nirkabel? kesalahan pada remote control
TIDAK
Nirkabel

Apakah lampu
operasi bagian YA
penerima sinyal unit
indoor berkedip?

TIDAK
Pendinginan:
Unit Outdoor

TIDAK
Apakah kipas berputar? Motor kipas rusak. Periksa saklar
YA magnetik dan saklar bantu untuk
motor kipas.

YA
Apakah filter kotor? Bersihkan
TIDAK

Apakah ada sesuatu YA


yang menyumbat aliran
Buang sesuatu yang menyumbat.
udara?
TIDAK

Apakah penukar YA
panas kotor? Bersihkan penukar panas
TIDAK

Kemungkinan penyebab:
• Refrigeran kelebihan isi
Setelah pengeringan vakum, isi
• Udara tercampur di sistem refrigeran
• Saklar tekanan rusak
refrigeran dengan jumlah yang
benar. Periksa saklar tekanan.

Service Diagnosis 78
SiMT281416E Troubleshooting Based on Equipment Condition

2.5 Setelah Unit Mati, tidak Bisa Direstart untuk Beberapa


Saat
Model yang Semua model seri SkyAir
Berlaku

Dugaan  Relay arus lebih (untuk kompresor)


Penyebab Relay arus lebih bekerja karena sebab berikut
• Tegangan catu daya rendah
• Tingkat tekanan tinggi yang berlebih
• Ukuran kabel listrik tidak memadai
• Kompresor rusak
 Termostat pelindung kompresor
Termostat pelindung kompresor bekerja karena sebab berikut
• Kompresi kompresor tidak memadai
• Refrigeran tidak tepat
• Katup ekspansi elektronik rusak
• Sirkulasi refrigeran tidak memadai

79 Service Diagnosis
Troubleshooting Based on Equipment Condition SiMT281416E

Pemecahan Masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa rusak.

Putar saklar operasi ke ON dan OFF,


lalu tunggu pada sisi ON.

Apakah unit mulai beroperasi YA


Normal. Unit dalam 3 menit mode
setelah 3 menit?
siaga.
TIDAK

Apakah bagian buang TIDAK Tidak terlalu panas


kompresor panas setelah Periksa kompresor.
unit berhenti?
YA

Periksa penyebab mengapa relay arus


lebih (untuk kompresor) atau termostat
pelindung kompresor bekerja.

[Sistem listrik]

TIDAK
Tegangan catu daya berada NO
dalam ±10 % tegangan yang Hubungi perusahaan listrik.
ditentukan.

YA

TIDAK
Apakah ukuran kabel daya di NO
seluruh total panjangnya Ganti kabel daya.
benar?
YA

[Sirkuit refrigeran]
Setelah pengeringan vakum, isi
refrigeran dengan jumlah yang
benar. Lalu, mulai operasi lagi.

Apakah ada perbedaan TIDAK


suhu antara saluran masuk NO
dan keluar katup ekspansi
Ganti katup ekspansi elektronik.
elektronik?

YA

Kompresor rusak
Periksa kompresor.

Service Diagnosis 80
SiMT281416E Troubleshooting Based on Equipment Condition

2.6 Peralatan Berfungsi tapi tidak Memberikan Pendinginan


Model yang Semua model seri SkyAir
Berlaku

Dugaan  Salah memilih model


Penyebab  Kekurangan refrigeran
 Aliran udara di unit indoor tidak memadai
 Tekanan tinggi meningkat
 Selain itu, kesalahan berikut mungkin menjadi penyebab
• Kompresi kompresor tidak memadai
• Sirkulasi refrigeran tidak memadai
• Katup ekspansi elektronik rusak

Pemecahan Masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau kerusakan
komponen dapat terjadi.

Ukur suhu udara hisap dan udara


buang.
Perbedaan suhu = Suhu udara hisap
– Suhu udara buang

Perbedaan suhu Apakah beban panas


untuk pendinginan YA YA
meningkat setelah Normal.
harus antara 8 dan
18˚C. pemasangan unit?
TIDAK TIDAK
• Salah memilih model
• Terkena matahari langsung Pemasangan unit tambahan harus
dipertimbangkan.
Apakah ada es di
sekitar port saluran masuk Apakah arus operasi
penukar panas unit indoor atau YA kurang dari tingkat yang YA
port saluran keluar katup ditentukan? Kekurangan refrigeran mungkin
ekspansi elektronik? menyebabkan masalah.
Setelah pengeringan vakum, isi
NO refrigeran dengan jumlah yang
TIDAK
TIDAK benar.

Apakah laju aliran udara YA Periksa setiap bagian berikut.


unit indoor menurun?
• Filter udara tersumbat
• Penukar panas kotor
NOTIDAK
• Motor kipas rusak
(lihat pemecahan masalah .)
Apakah tingkat tekanan YA Periksa setiap item berikut.
tinggi lebih tinggi dari
tingkat normal?
• Refrigeran kelebihan isi
• Udara tercampur di sistem
refrigeran
TIDAK
• Penukar panas kotor
• Korsletingudara buang
• Ada sesuatu yang menyumbat
aliran udara
• Motor kipas unit outdoor rusak
(Lihat pemecahan masalah .)
Periksa setiap item berikut.
• Kompresi kompresor tidak
memadai
• Sirkulasi refrigeran tidak
memadai
• Katup ekspansi elektronik rusak

81 Service Diagnosis
Troubleshooting Based on Equipment Condition SiMT281416E

2.7 Peralatan Mengeluarkan Kabut Putih


Model yang Semua model seri SkyAir
Berlaku

Dugaan  Tempat pemasangan lembab


Penyebab  Tempat pemasangan kotor dan ada kabut minyak padat.
 Penukar panas kotor
 Filter udara tersumbat
 Motor kipas rusak

Pemecahan Masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa rusak.

Apakah suhu ruang Lanjutkan operasi unit.


lebih tinggi dari nilai yang YA TIDAK
Apakah kabut putih keluar dari Normal
ditetapkan dalam pendingin?
unit?

NOTIDAK YA

Hilangkan sumber kondisi


lembab.

Apakah penukar panas YA


unit indoor kotor? Penting untuk membersihkan
penukar panas.
TIDAK

Apakah tempat berdebu atau YA


ada kabut minyak padat?
Hilangkan sumber kabut minyak
atau debu.
NO
TIDAK

Apakah laju aliran YA Bersihkan filter udara


udara terlalu kecil?
Periksa motor kipas.
NOTIDAK (Lihat pemecahan masalah )

Apakah ada kesulitan saat beralih ke


mode pemanasan setelah pencairan Normal
dalam pemanasan selesai? (Kabut keluar karena operasi
pencairan)

Service Diagnosis 82
SiMT281416E Troubleshooting Based on Equipment Condition

2.8 Peralatan Mengeluarkan Suara atau Goncangan Keras


Model yang Semua model seri SkyAir
Berlaku

Dugaan  Pemasangan yang salah


Penyebab  Kontak kipas, pipa, casing, dll.
 Suara aliran refrigeran
 Suara operasi dari peralatan buang
 Suara komponen resin yang berkontraksi
 Selain itu, kesalahan berikut mungkin menjadi penyebab
• Refrigeran kelebihan isi
• Percampuran udara
• Suara aliran karena refrigeran tidak memadai (suara hening)

Pemecahan Masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa
rusak.

[Bagian pekerjaan pemasangan]


Apakah suara disertai YA
dengan goncangan pada Perbaiki pemasangan.
seluruh plafon dan Perkuat plafon atau dinding
dinding?
TIDAK

Apakah suara
YA
disertai dengan goncangan
pada bagian pemasangan Pasang peredam kejut pada
unit? bagian pemasangan, atau perkuat
bagian pemasangan.
TIDAK

TIDAK
Apakah pipa aman? Pasang kain bantalan untuk
menyangga pipa seperti pelana.
[Bagian catu daya] YA

Apakah kipas YA
kontak dengan komponen Bongkar dan lepas kontak
lain? komponen.
TIDAK

YA
Apakah pipa kontak
dengan casing? Perbaiki pipa secara manual atau
ikatkan beban berat pada pipa.
TIDAK

Apakah suara YA
aliran tersebut dari katup
penurun tekanan atau Normal.
pipa kapiler?

NO

83 Service Diagnosis
Troubleshooting Based on Equipment Condition SiMT281416E

Suara pelan “shoo…” YA


berlanjut selama pendinginan Normal. Ini adalah suara aliran gas
atau pencairan (refrigeran) dalam unit AC.

TIDAK

Bunyi “shoo..”
keluar setelah operasi mulai YA Normal. Suara tersebut keluar pada
atau berhenti, atau pencairan
mulai atau berhenti.
saat aliran gas (refrigeran) berubah
atau berhenti.
TIDAK

Bunyi "shoo..."
keluar selama pendinginan YA
Normal. Bunyi operasi alat buang.
atau setelah operasi
berhenti.
TIDAK

Berderit selama pemanasan YA Normal. Bunyi derit keluar disebabkan


dan setelah operasi berhenti oleh penyusutan bagian resin karena
perubahan suhu.
NO
Hal ini normal.
Is this an impact YA Dampak suara dapat dikurangi
noise at the start/end of dengan menggunakan "Pengaturan
defrosting? Pengurangan Suara Pencairan."
Untuk lebih jelasnya, lihat
TIDAK "Pengaturan Lapangan dari
• Refrigeran kelebihan isi Remote Control".
• Udara tercampur d sistem refrigeran
• Suara aliran karena kekuangan Setelah pengeringan vakum, isi
refrigeran. (Bunyi shoo...) refrigeran dengan jumlah yang benar.

Service Diagnosis 84
SiMT281416E Troubleshooting Based on Equipment Condition

2.9 Peralatan Mengeluarkan Debu


Model yang Semua model seri SkyAir
Berlaku

Dugaan  Karpet
Penyebab  Bulu hewan
 Aplikasi (toko kain,...)

Pemecahan Masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa rusak.

Apakah masalah timbul pada


saat operasi mulai lagi setelah YA
Debu yang terkumpul di dalam unit
periode operasi diperpanjang?
indoor dihembuskan keluar.
Penting untuk membersihkan
bagian dalam unit indoor.
NO
TIDAK

YA
Apakah filter udara lengkap? Debu yang terkumpul di dalam unit
indoor dihembuskan keluar.
NO Penting untuk membersihkan
TIDAK
bagian dalam unit indoor.
Pasang filter udara.

2.10 LCD Remote Control Menampilkan “ ”


Model yang Semua model seri SkyAir
Berlaku

Dugaan  Posisi SS1 pada PCB unit indoor di “Darurat”.


Penyebab

Pemecahan Masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa rusak.

Masalah timbul YA
setelah catu daya Unit memeriksa untuk mengkonfirmasi
ON. bahwa remote control normal.
TIDAK Indikasi muncul dalam waktu yang
singkat.

Apakah posisi SS1


pada PCB unit indoor di YA Ubah saklar ke “Normal”, dan reset
“Darurat”? catu daya.

TIDAK
Periksa unit berdasarkan pemecahan
masalah LED unit indoor dan LED unit
outdoor.

85 Service Diagnosis
Troubleshooting Based on Equipment Condition SiMT281416E

2.11 Sirip Sayap Ayun tidak Berfungsi


Model yang FCQ, FHQ, FAQ, FVQ
Berlaku

Metode Deteksi Gunakan ON/OFF saklar pembatas ketika motor berputar.


Kesalahan

Kondisi Ketika ON/OFF saklar mikro untuk penentuan posisi tidak dapat dikembalikan meskipun
Keputusan melalui motor sirip sayap ayun selama waktu tertentu (sekitar 30 detik).
Kesalahan

Keterangan Beberapa fungsi dapat memaksa sirip sayap ayun ke posisi tetap, meskipun mode ayun
dipilih pada remote control. Hal ini bukan kesalahan unit, namun fungsi kontrol untuk
mencegah aliran udara ke konsumen.

Sebelum memulai pemecahan masalah, pastikan sirip sayap ayun tidak dipaksa ke posisi
tetap tersebut.
Dugaan  Motor ayun rusak
Penyebab  Saklar mikro rusak
 Sambungan konektor rusak
 PCB unit indoor rusak

Service Diagnosis 86
SiMT281416E Troubleshooting Based on Equipment Condition

Pemecahan Masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa rusak.

Apakah
Konektor tersambung TIDAK
dengan benar ke AA, Sambung dengan benar.
pada PCB?

YA

Apakah konektor transfer


saklar pembatas TIDAK Sambung dengan benar.
tersambung dengan
benar?

YA

Putar catu daya ke OFF dan putar


daya ke ON, kemudian periksa
apakah motor sirip sayap ayun
berputar ketika catu daya direstart.

Lepas X36A, putar catu daya ke OFF dan


YA putar daya ke ON, kemudian periksa
Apakah sirip sayap berayun? apakah saklar pembatas memiliki
kontinuitas ketika catu daya direstart.
TIDAK

Putar catu daya ke OFF dan putar


daya ke ON, kemudain ukur tegangan Apakah kontinuitas/tanpa YA
output konektor AA ketika catu daya kontinuitas terbalik?
direstart.
NO
TIDAK

TIDAK Ganti PCB unit indoor.


220 - 240 VAC?

YA
Ganti rakitan motor ayun.

Catatan:
Konektor
AA
FHQ-BV X14A
FHQ-CA X36A
FAQ-C X36A
FCQ X36A
FVQ X36A

87 Service Diagnosis
Troubleshooting by Remote Controller SiMT281416E

3. Pemecahan Masalah Berdasarkan Indikasi LED


3.1 Pemecahan Masalah Berdasarkan LED pada Unit Indoor
Pendahuluan
Pemecahan masalah dapat dilakukan berdasarkan LED monitor layanan (hijau). (Berkedip saat normal)
k: LED ON / h: LED OFF / l: LED Berkedip / — : Tidak ada koneksi dengan pemecahan masalah
Monitor Normal
Mikro-Komputer Isi/Pemrosesan
HAP (LED-A)
l Unit indoor normal  Pemecahan masalah unit outdoor
l Kabel transmisi antara unit indoor dan outdoor salah
Jika LED-A unit outdoor OFF, lakukan pemecahan masalah unit outdoor. Jika
LED-A unit outdoor berkedip, kabel atau rakitan PCB unit indoor atau outdoor
rusak. (Catatan 4)
k Rakitan PCB unit indoor rusak (Catatan 5)
h Catu daya, rakitan PCB, atau kabel transmisi antara unit indoor dan outdoor
rusak. (Catatan 5)

Catatan: 1. Ketika tombol PEMERIKSAAN/UJI COBA pada remote control ditekan, tampilan
PEMERIKSAAN berkedip memasuki mode PEMERIKSAAN.
2. Dalam mode PEMERIKSAAN, ketika tombol ON/OFF ditekan dan ditahan selama 5 menit
atau lebih, tampilan riwayat kesalahan tersebut OFF. Dalam hal ini, setelah kode kesalahan
berkedip 2 kali, tampilan kode berubah menjadi “00” (= Normal) dan No. unit berubah
menjadi “0”. Mode PEMERIKSAAN secara otomatis beralih ke mode normal (tampilan suhu
yang diatur).
3. Operasi berhenti karena kesalahan tergantung pada model atau kondisi.
4. Jika LED-B OFF, kabel transmisi antara unit indoor dan outdoor salah atau terputus.
Sebelum melakukan pemecahan masalah yang dijelaskan sebelumnya, periksa kabel
transmisi.
5. Memecahkan masalah dengan memutar catu daya ke OFF selama minimal 5 detik,
merestart catu daya, kemudian periksa ulang tampilan LED.

3.2 Pemecahan Masalah Berdasarkan LED pada PCB Unit


Outdoor
Diagnosis berikut dapat dilakukan dengan memutar saklar daya ke ON dan memeriksa indikasi LED
pada papan sirkuit cetak (A1P) unit outdoor.

k: LED ON / h: LED OFF / l: LED Berkedip / — : Tidak ada koneksi dengan pemecahan masalah
Deteksi LED
Mikro-komputer di
HAP operasi Deskripsi
normal
(Hijau)
l Normal
k PCB unit outdoor rusak (Catatan 1)
h Kelainan catu daya, atau PCB unit outdoor rusak (Catatan 2)
l Aktivasi alat pelindung (Catatan 3)

Catatan:1. Putar saklar daya ke OFF, dan putar lagi ke ON setelah 5 detik atau lebih. Periksa kondisi
kesalahan, dan diagnosis masalah.
2. Putar saklar daya ke OFF. Setelah 5 detik atau lebih, lepas kabel sambungan (2). Kemudian
putar saklar daya ke ON. Jika HAP pada PCB unit outdoor berkedip setelah sekitar 10 detik,
PCB unit indoor rusak.
3. Periksa juga fasa terbuka.

Service Diagnosis 88
SiMT281416E Troubleshooting by LED Indications
Keterangan: Monitor deteksi kesalahan terus mengindikasi kesalahan yang timbul sebelumnya
sampai saklar daya diputar ke OFF.
Pastikan untuk memutar saklar daya ke OFF setelah pemeriksaan.

89 Service Diagnosis
Troubleshooting by Remote Controller SiMT281416E

4. Pemecahan Masalah Berdasarkan Remote Control


4.1 Operasi Akses Mode
4.1.1 BRC1C61/BRC1D61
Mode berikut dapat dipilih dengan menggunakan tombol PEMERIKSAAN/UJI COBA pada remote control.
Tekan tombol PEMERIKSAAN/UJI COBA
Pengaturan unit indoor dapat dilakukan selama lebih dari 4 detik. Data layanan dapat diperoleh.
• Waktu tanda filter Mode
• Arah aliran udara Mode • Riwayat kode kesalahan
pengaturan • Data suhu dari berbagai bagian
• Lain-lain layanan
lapangan Pengaturan layanan dapat dilakukan.
• Kipas paksa ON
Tekan tombol
• Pengaturan arah/laju aliran udara
PEMERIKSAAN/UJI COBA
Depress INSPECTION/TEST Tekan tombol PEMERIKSAAN/UJI
Press INSPECTION/TEST button once.
selama
buttonlebih dari 4
for more detik
than 4 seconds. COBA sekali

Mode
normal Tekan tombol PEMERIKSAAN/UJI
Tekan tombol COBA
Press sekali. Atau setelah
INSPECTION/TEST 30 menit
button once.
PEMERIKSAAN/UJI COBA Or after 30 minutes
sekali
Setelah 10 detik

Kode berikut dapat diperiksa.


• Kode kesalahan Mode Mode
• Kode model indoor pemeriksaa operasi uji Termostat secara paksa diputar ke ON.
• Kode model outdoor n coba

. Tekan tombol
PEMERIKSAAN/UJI COBA
sekali

4.1.2 BRC1E62
<Menu Utama>
Mode • Arah aliran udara
Menu • Mulai Cepat
Utama • Pilihan Hemat Energi
• Jadwal
<Layar Utama>
• Pembersihan Otomatis Filter
• Peralihan mode operasi
• Informasi Pemeliharaan
• Kontrol kecepatan kipas Tekan Tekan
Press
tombol Press
tombolCancel • Konfigurasi
• Tampilan menu Menu/Enter
Menu/Enter Batal once.
button sekali • Pengaturan Saat Ini
• Konfirmasi setiap pengaturan sekali once.
button • Jam & Kalendar
• Nyala
• Bahasa
• Mati
Layar
• Batal
utama
• Lampu operasi Tekan tombol
Batal sekali
Tekan tombol Batal selama
4 detik atau.lebih
Tekan
Press Cancel Tekan tombol
tombol Batal selama 4
button
Batalonce.
sekali detik atau lebih Menu
Mode
Pengaturan Pemeliharaa
Layanan n

<Pengaturan Layanan> <Menu Pemeliharaan>


• Operasi Uji Coba • Nama Model
• Kontak Pemeliharaan • Jam Operasi
• Pengaturan Lapangan • Status Unit Indoor
• Diferensial setpoint minimal • Status Unit Outdoor
• Alamat AirNet unit outdoor • Pencairan Paksa
• Riwayat Kesalahan • Tampilan Kesalahan
• Status Unit Indoor • Menukar No. Unit
• Status Unit Outdoor • Nilai Sensor yg Dialamatkan
• Kipas Paksa
• Peralihan Control Utama Sub
• Indikator Filter
• Uji Coba Pembersihan
Otomatis Filter
• Indikator Sikat/Filter
• Menonaktifkan Pembersihan
Otomatis Filter

Service Diagnosis 90
SiMT281416E Troubleshooting by Remote Controller

4.2 Prosedur Diagnosis Sendiri dengan Remote Control


4.2.1 Remote Control Berkabel — BRC1C61/BRC1D61
Jika operasi berhenti karena kesalahan, LED operasi remote control berkedip, dan kode kesalahan
ditampilkan. (Meskipun operasi berhenti, isi kesalahan ditampilkan saat masuk ke mode pemeriksaan.)
Kode kesalahan memungkinkan Anda untuk mengetahui kesalahan apa yang menyebabkan operasi
berhenti. Lihat halaman 94 untuk kode dan isi kesalahan.
LED operasi

Tombol ON/OFF

Tampilan unit outdoor


untuk kesalahan yang
terdeteksi

Tampilan pemeriksaan

Kode kesalahan
Error code

Tombol
Pemeriksaan/Uji Coba
Inspection/Test button

Catatan:
1. Menekan tombol PEMERIKSAAN/UJI COBA akan membuat indikasi periksa berkedip.
2. Saat berada di mode layanan, menekan tombol ON/OFF selama 5 detik atau lebih akan
menghapus indikasi riwayat kegagalan yang ditunjukkan di atas. Dalam hal ini, pada tampilan
kode, kode kesalahan akan berkedip dua kali kemudian berubah menjadi (= Normal), No. Unit
akan berubah menjadi , dan mode operasi akan secara otomatis beralih dari mode layanan ke
mode normal (menampilkan suhu yang diatur).

91 Service Diagnosis
Troubleshooting by Remote Controller SiMT281416E

4.2.2 Remote Control Berkabel — BRC1E62


Berikut ini akan ditampilkan pada layar ketika kesalahan (atau peringatan) terjadi selama operasi.
Periksa kode kesalahan dan lakukan tindakan perbaikan yang ditentukan untuk model tertentu.

Layar

Lampu operasi

(1) Periksa kesalahan atau peringatan


Status Operasi Tampilan

Lampu operasi (hijau) mulai


Mati secara berkedip. Pesan "Kesalahan:
Sistem berhenti beroperasi. Tekan tombol Menu" akan
tidak normal
muncul dan berkedip di bagian
bawah layar.

Lampu Operasi (hijau) tetap


menyala. Pesan "Peringatan:
Peringatan Sistem terus beroperasi. Tekan tombol Menu" akan
muncul dan berkedip di bagian
bawah layar.

(2) Lakukan tindakan perbaikan

· Tekan tombol Menu/Enter untuk memeriksa kode kesalahan.

· Lakukan tindakan perbaikan khusus untuk model.

Kode kesalahan

Nama model yang berlaku

Service Diagnosis 92
SiMT281416E Troubleshooting by Remote Controller

4.2.3 Remote Control Nirkabel


Jika unit berhenti karena kesalahan, operasi yang menunjukkan LED pada bagian penerima sinyal unit
outdoor berkedip. Kode kesalahan dapat ditentukan dengan mengikuti prosedur yang diuraikan
berikut. (Kode kesalahan ditampilkan ketika kesalahan operasi terjadi. Dalam kondisi normal, kode
kesalahan dari masalah terakhir ditampilkan.)

Tekan tombol PEMERIKSAAN/UJI COBA untuk memilih “pemeriksaan”.


1 Peralatan masuk ke mode pemeriksaan. Indikasi “Unit” ditampilkan dan
tampilan No. Unit menunjukkan indikasi berkedip.
Atur No. Unit
Tekan tombol UP atau DOWN dan ubah tampilan No. Unit sampai bunyi (1)
keluar dari unit indoor.
1. Jumlah beep
3 beep pendek: Lakukan semua operasi berikut.
2 1 beep pendek: Lakukan langkah 3 dan 4.
Lanjutkan operasi pada langkah 4 sampai bunyi tetap ON.
Bunyi terus menerus menunjukkan bahwa kode kesalahan
dikonfirmasi.
Beep terus menerus: Tidak ada kelainan.
3 Tekan tombol pemilih MODE.
Indikasi (angka atas) kiri kode kesalahan berkedip.
Diagnosis angka atas kode kesalahan
Tekan tombol UP atau DOWN dan ubah angka atas kode kesalahan sampai
bunyi kode kesalahan yang sesuai dihasilkan (2).
 Angka atas kode berubah seperti yang ditunjukkan berikut ketika tombol UP
dan DOWN ditekan.

2. Jumlah beep


Beep terus menerus: Angka atas dan bawah cocok. (Kode kesalahan
dikonfirmasi)
2 beep pendek: Angka atas cocok.
1 beep pendek: Angka bawah cocok.
5 Tekan tombol pemilih MODE.
Indikasi (angka bawah) kanan kode kesalahan berkedip.
Diagnosis angka bawah kode kesalahan
Tekan tombol UP atau DOWN dan ubah angka bawah kode kesalahan sampai
bunyi kode kesalahan terus menerus yang sesuai dihasilkan (2).
 Angka bawah kode berubah seperti yang ditunjukkan berikut ketika tombol
UP dan DOWN ditekan.
6

93 Service Diagnosis
Troubleshooting by Remote Controller SiMT281416E

Normal status
Statusinspection
normal mode from normal
Enters
Masuk ke the
mode pemeriksaan dari status normal
status when INSPECTION/TEST
ketikaistombol PEMERIKSAAN/UJI COBA ditekan.
button pressed.

TekanINSPECTION/TEST
1 Press tombol PEMERIKSAAN/UJI COBA.
button.

If no button is pressed
Jika tidak ada tombol
for 1 minute, equipment
yang ditekan selama
returns to normal
1 menit, peralatan
status.
kembali ke status
normal

3
KetikaMODE
When tombolselector
pemilih Press
Tekan
MODEisditekan
button pressed atau
or MODE
tombol
tidak
no ada istombol
button yang
pressed selector
pemilih
ditekan
for selama 1 menit,
1 minute, button.
MODE.
peralatan kembali
equipment ke
returns to Jika tidak ada
status normal
normal status. Iftombol yang
no button ditekan
is pressed
selama
for 1 menit,
1 minute,
peralatan returns
equipment kembalitoke
status status.
normal normal

5 Tekan tombol pemilih MODE.


5 Press MODE selector button.

Service Diagnosis 94
SiMT281416E Troubleshooting by Remote Controller

4.3 Kode Kesalahan dan Deskripsi


Tampilan
Remote Isi Kesalahan Halaman Referensi
Control
Unit Indoor A0 Kesalahan alat pelindung eksternal 99
A1 Kelainan PCB unit indoor 100
A3 Kelainan sistem permukaan air buang 101
A6 Kelainan motor kipas unit indoor 102
A7 Kelainan motor sirip sayap ayun/terkunci 104
A8 Tegangan catu daya tidak normal 106
AF Kelainan sistem buang 107
AJ Kelainan pengaturan kapasitas 109
C4 Kelainan termistor penukar panas 110
C5 Kelainan termistor penukar panas menengah 110
C6 Kesalahan gabungan antara PCB unit indoor dan PCB kipas 111
C9 Kelainan termistor udara hisap 110
CC Kelainan sistem sensor kelembaban 112
CJ Termistor suhu ruang pada kelainan remote control 113
Unit Outdoor E1 Kelainan PCB unit outdoor 114
E3 Kelainan tekanan tinggi (terdeteksi oleh saklar tekanan tinggi) 115
E5 Motor kompresor terkunci 117
E7 Kelainan motor kipas unit outdoor 118
E9 Kelainan katup ekspansi elektronik 120
F3 Kelainan suhu pipa buang 123
H3 Kelainan sistem saklar tekanan tinggi 125
H9 Kelainan termistor udara outdoor 126
J1 Kelainan sensor tekanan 127
J3 Kelainan termistor pipa buang 126
J5 Kelainan termistor pipa hisap 126
J6 Kelainan termistor penukar panas 126
J7 Kelainan termistor penukar panas menengah 126
L1 Kelainan PCB unit outdoor 128
L4 Suhu sirip radiasi meningkat 130
L5 Kelebihan arus output DC (instan) 132
L8 Panas elektronik (jeda waktu) 134
L9 Pencegahan berhenti (jeda waktu) 136
LC Kesalahan sistem transmisi antara PCB unit outdoor 138
P1 Fasa terbuka atau ketidakseimbangan tegangan catu daya 139
P4 Kelainan termistor sirip radiasi 140
PJ Kelainan pengaturan kapasitas 141
Sistem U0 Kekurangan refrigeran (kesalahan) 142
U2 Kelainan tegangan catu daya 143
U4 Transmission error between indoor and outdoor unit 144
U5 Kesalahan transmisi antara unit indoor dan remote control 147
U8 Kesalahan transmisi antara remote control UTAMA dan SUB remote 148
control
UA Kelainan saklar pengaturan lapangan 149
UC Kesalahan pengaturan alamat terpusat 150
Kesalahan transmisi antara unit indoor dan outdoor/pipa dan kabel tidak
UF cocok/kekurangan refrigeran 151

95 Service Diagnosis
Troubleshooting by Remote Controller SiMT281416E

4.4 Kode Kesalahan - Sub Kode


Jika kode kesalahan seperti yang ditunjukkan berikut ditampilkan saat navigasi remote control
(BRC1E62) sedang digunakan, lakukan diagnosis mendetail atau diagnosis unit yang relevan dengan
mengacu pada daftar kode kesalahan detail yang terlampir.

4.4.1 Unit Indoor


Pemecahan masalah
Kode
kesalahan Deskripsi kesalahan Deskripsi diagnosis
Arus motor kipas yang terkunci terdeteksi.
A6 - 01 Motor kipas terkunci Putar kipas dengan tangan untuk memeriksa sambungan
konektor.
Arus berlebih pada motor kipas terdeteksi.
A6 - 10 Kesalahan arus berlebih pada kipas Periksa sambungan konektor antara motor kipas dan PCB
kipas. Jika sambungan normal, ganti motor kipas. Jika
masih ada kesalahan, ganti PCB kipas.
Kesalahan dalam mendeteksi posisi motor kipas. Periksa
sambungan konektor antara motor kipas dan PCB kipas.
A6 - 11 Kesalahan deteksi posisi kipas Jika sambungan normal, ganti motor kipas. Jika masih ada
kesalahan, ganti PCB kipas.
Kesalahan transmisi (antara panel dekorasi Periksa sambungan konektor harness antara PCB panel
AH - 03 self-cleaning dan unit indoor)
dan PCB unit indoor.
[ketika panel dekorasi self-cleaning dipasang]
Kesalahan sensor deteksi debu Periksa sambungan konektor X12A pada PCB panel, dan
AH - 04 [ketika panel dekorasi self-cleaning dipasang]
konektor X18A dan X19A pada PCB sensor.
Periksa penyumbatan debu di port pengumpulan debu dan
Kesalahan tanda pengumpulan debu di unit sikat, pipa berbentuk S, dan kotak debu.
AH - 05 [ketika panel dekorasi self-cleaning dipasang]
Selanjutnya, periksa noda di bagian penerima dan
pemancar cahaya dari unit inframerah.
Kesalahan rotasi filter udara Periksa sesuatu yang menghalangi filter untuk berputar
AH - 06 [ketika panel dekorasi self-cleaning dipasang] (misalnya filter lepas atau roda pengerak tersumbat
dengam benda asing).
Kesalahan rotasi peredam Peredam tidak berputar secara normal. Periksa benda
AH - 07 [ketika panel dekorasi self-cleaning dipasang] asing di sekitar peredam dan operasi roda gigi dan saklar
pembatas.
Kesalahan operasi self-cleaning filter Unit belum menyelesaikan operasi self-cleaning filter
AH - 08 meskipun setelah selang waktu tertentu. Periksa suara
[ketika panel dekorasi self-cleaning dipasang]
eksternal, dll.

C6 - 01 Gabungan PCB unit indoor dan PCB kipas Gabungan PCB unit indoor dan PCB kipas rusak. Periksa
rusak apakah adaptor pengaturan kapasitas benar dan jenis PCB
kipas benar.

Service Diagnosis 96
SiMT281416E Troubleshooting by Remote Controller

4.4.2 Unit Outdoor


Pemecahan masalah
Kode
kesalahan Deskripsi kesalahan Deskripsi diagnosis
Motor kipas menyebabkan rotasi tidak normal. Periksa
E7 - 01 Motor kipas terkunci sambungan konektor antara motor kipas dan PCB unit
outdoor. Jika sambungan normal, ganti motor kipas. Jika
masih ada kesalahan, ganti PCB unit outdoor.
L1 - 01 Kesalahan arus sesaat (saat di operasi startup)
L1 - 02 Kesalahan sensor arus PCB
Lihat bagan alur panduan dan lakukan diagnosis unit
L1 - 03 Kesalahan offset arus
yang relevan berdasarkan kode Kesalahan yang
L1 - 04 Kesalahan IGBT (1) ditunjukkan di sebelah kiri.
L1 - 05 Kesalahan pengaturan jumper
L1 - 06 Kesalahan tegangan lebih SP/MP-PAM (2)
Arus kelebihan beban selama jangka waktu 260 detik atau
lebih.
Kesalahan ini diduga akibat dari pengisian refrigeran yang
L8 - 01 Kesalahan panas elektronik 1 berlebihan, kerusakan yang terjadi pada bantalan
kompresor, tekanan terlalu tinggi, dll. Periksa dan selidiki
penyebabnya.
Arus kelebihan beban dekat dengan arus terkunci mengalir
L8 - 02 Kesalahan panas elektronik 2 dalam panas selama jangka waktu 5 detik. Kesalahan ini
diduga akibat dari katup penghenti tertutup, kabel di motor
kompresor terputus, dll. Periksa dan selidiki penyebabnya.
Beban kompresor meningkat setelah startup. Kesalahan ini
L8 - 03 Penurunan perputaran kompresor diduga akibat dari gagal daya sesaat, kembalinya cairan,
dll. Periksa dan selidiki penyebabnya.
L8 - 04 Kesalahan deteksi guntur Lonjakan arus yang disebabkan oleh guntur
Pembatasan arus berlebih mengalir di inverter. Kesalahan
ini diduga akibat dari katup penghenti tertutup, pengisian
L8 - 05 Inverter pembatas arus refrigeran yang berlebihan, filter unit indoor tersumbat,
penukar panas unit indoor/outdoor kotor, dll. Periksa dan
selidiki penyebabnya.
Arus kelebihan muatan digunakan untuk startup
kompresor.
L9 - 01 Pencegahan berhenti (peningkatan arus) Kesalahan ini diduga akibat dari tekanan diferensial startup
tinggi, kembalinya cairan, minyak kompresor berlebihan,
koil kompresor tidak normal, poros kompresor macet, dll.
Periksa dan selidiki penyebabnya.
Kompresor belum menyelesaikan operasi startup.
Kesalahan ini diduga akibat dari tekanan diferensial startup
L9 - 02 Pencegahan berhenti (kesalahan startup) tinggi, kembalinya cairan, minyak kompresor berlebihan,
koil kompresor tidak normal, poros kompresor macet,
sirkuit deteksi posisi rusak, dll. Periksa dan selidiki
penyebabnya.
Transmisi rusak termasuk yang disebabkan saat catu daya
diputar ke ON. Kesalahan ini diduga akibat dari 1.
LC - 01 Kabel rusak Sambungan kabel di sekitar PCB rusak, 2. PCB unit
outdoor rusak, atau 3. Motor kipas rusak. Periksa dan
selidiki penyebabnya.

Transmisi antara kompresor dan pengendali Ada kesalahan dalam transmisi antara kompresor dan
LC - 02 PCB unit outoor. Jika sambungan kabel kompresor normal,
mikro rusak periksa hal yang sama pada PCB unit outdoor.
PCB unit outdoor harus diperbaiki, tapi tidak ada adaptor
PJ - 01 Pengaturan kapasitas tidak dilakukan pengaturan kapasitas yang terhubung. Sambung adaptor
pengaturan kapasitas yang benar ke PCB.
Kesalahan ini akibat dari ketidakcocokan sinyal antara
PJ - 04 Pengaturan kapasitas rusak pengontrol di PCB dan inverter. Periksa apakah jenis PCB
benar dan adaptor pengaturan kapasitas yang benar
terhubung.

Note:
1. IGBT: IGBT adalah alat semikonduktor daya yang biasanya digunakan sebagai saklar elektronik .
2. MP: Pulsa Tunggal

97 Service Diagnosis
Troubleshooting by Remote Controller SiMT281416E

Pemecahan masalah
Kode
kesalahan Deskripsi kesalahan Deskripsi diagnosis
Kesalahan ini akibat dari kekurangan refrigeran. Lihat
U0 - 02 Kekurangan refrigeran - Unit outdoor (Faktor 0) Bagan alur pemecahan masalah dan lakukan
diagnosis, kemudian lakukan tindakan penanggulangan.
Kesalahan ini akibat dari kekurangan refrigeran yang
U0 - 03 Kekurangan refrigeran - Unit outdoor (Faktor 1) disebabkan oleh kebocoran gas. Isi refrigeran sampai
dengan jumlah refrigeran normal.
Kesalahan ini akibat dari penyumbatan yang disebabkan di
U0 - 04 Kekurangan refrigeran - Unit outdoor (Faktor 2) suatu tempat dalam sistem pipa refrigeran. Periksa apakah
katup penghenti sudah dibuka dan penyumbatan dalam
sistem refrigeran.

Kesalahan ini diduga akibat dari catu daya kelebihan atau


U2 - 01 Kesalahan tegangan catu daya
kekurangan tegangan, atau sensor tegangan di PCB rusak.
U2 - 02 Fasa terbuka catu daya Periksa fasa terbuka catu daya.
Ada arus sirkuit tidak normal yang mengalir di PCB. Jika
U2 - 03 Kesalahan muatan kapasitor sirkuit utama sambungan kabel yang terkait dengan PCB normal, ganti
PCB unit outdoor.
Ada tegangan berlebih antara SP/MP dan PAM (Fasa
U2 - 04 Kesalahan tegangan berlebih SP/MP - PAM tunggal). Jika sambungan kabel yang terkait dengan PCB
normal, ganti PCB unit outdoor.
Kesalahan ini akan ditampilkan jika jumlah unit indoor yang
UA - 01 Jumlah unit indoor yang terhubung salah diatur secara local berbeda dari jumlah unit indoor yang
terdeteksi.
Ada beberapa unit indoor yang tersambung dengan remote
UA - 02 Beberapa unit master terdeteksi control.
Sambung remote control ke satu unit indoor saja.

UA - 03 Unit indoor yang terhubung terlalu banyak Kesalahan ini akan ditampilkan jika 5 atau lebih unit indoor
terhubung.
Ada kesalahan dalam transmisi antara unit outdoor dan unit
UA - 05 Kesalahan transmisi Indoor-Outdoor antara indoor slave 1. Periksa sambungan jumper antara unit
slave 1 dan unit outdoor indoor slave (tanpa remote Control yang terhubung) dan
unit outdoor.
Ada kesalahan dalam transmisi antara unit outdoor dan unit
UA - 07 Kesalahan transmisi Indoor-Outdoor antara indoor slave 2. Periksa sambungan jumper antara unit
slave 2 dan unit outdoor indoor slave (tanpa remote Control yang terhubung) dan
unit outdoor.
Ada kesalahan dalam transmisi antara unit outdoor dan unit
UA - 09 Kesalahan transmisi Indoor-Outdoor antara indoor slave 3. Periksa sambungan jumper antara unit
slave 3 dan unit outdoor indoor slave (tanpa remote Control yang terhubung) dan
unit outdoor.
Ada kesalahan dalam sambungan kabel untuk transmisi
antara unit indoor dan outdoor (dinilai dengan unit indoor).
UF - 01 Kabel salah
Periksa sambungan jumper 1, 2, dan 3 antara unit indoor
dan outdoor.
Ada kesalahan dalam mode operasi dan suhu deteksi pipa
UF - 02 Pipa tersambung ke arah sebaliknya refrigeran. Periksa pipa refrigeran yang tersambung ke arah
sebaliknya, kekurangan refrigeran, dll.

Service Diagnosis 98
SiMT281416E Troubleshooting by Remote Controller

4.5 Alat Pengaman


4.5.1 Unit Outdoor

Saklar tekanan tinggi Saklar tekanan rendah


Model Sekring
Terbuka Tertutup Terbuka Tertutup
4.0 3.0 – – 6.3A/250A (F1U),
RZR50 - 71LVVM(4)
+0/-0.15MPa +/-0.15MPa 3.15A/250V (F6U)

6.3A/250A (F1U, F3U, F4U),


RZR100LVVM(4)
3.15A/250V (F6U)

RZR125 • 6.3A/250A (F1U, F3U, F4U),


140LVVM(4) 5A/250V (F6U)

6.3A/250A
RZR100 - (F1U, F2U, F3U, F4U),
140LUY1(4) 5A/250V (F1U: A2P),
31.5A/500V (F5U, F6U)

4.5.2 Unit Indoor


Pelindung panas
Model Motor kipas sekring panas
Tidak normal Reset (otomatis)
FCQ50 - 140 – – Tidak berlaku
FHQ50 - 125 >130°C +/-5°C <83°C +/-20°C Tidak berlaku

FHQ140 – – Tidak berlaku

FAQ71 - 100 – – Tidak berlaku

FBQ50 - 140 – – 6.3A/250V (F3U)


FVQ50 - 140 – – Tidak berlaku

99 Service Diagnosis
Troubleshooting by Remote Controller SiMT281416E

5. Pemecahan Masalah Berdasarkan Indikasi pada


Remote Control
5.1 Kesalahan Alat Pelindung Eksternal
Kode Kesalahan

Model FCQ
yang
Berlaku

Metode Mendeteksi sirkuit terbuka atau pendek antara terminal inout eksternal di unit indoor.
Deteksi
Kesalahan

Kondisi Ketika sirkuit terbuka terjadi antara terminal input eksternal dengan remote control yang
Keputusan diatur ke "terminal ON/OFF eksternal."
Kesalahan

Dugaan  Aktivasi alat pelindung eksternal


Penyebab  Pengaturan lapangan salah
 PCB unit indoor rusak

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa
rusak.

Alat pelindung
eksternal tersambung
ke terminal T1 dan T2 YA
blok terminal unit Aktivasi alat pelindung eksternal.
indoor.

NOTIDAK

Periksa keadaan pengaturan input


ON/OFF dari luar dengan remote
control.

Input ON/OFF
eksternal (No. mode 12, Ganti No. kode kedua ke "01"
No. kode pertama 1) diatur ke YA
input alat pelindung eksternal
atau "02".
(No. kode kedua 03) dengan
remote control.

NO
TIDAK

Ganti PCB unit indoor.

Service Diagnosis 10
0
Troubleshooting by Remote Controller SiMT281416E

5.2 Kelainan PCB Unit Indoor


Kode Kesalahan

Model Semua model indoor (kecuali FVQ)


yang
Berlaku

Metode Memeriksa data dari E²PROM.


Deteksi
Kesalahan

Kondisi Kesalahan timbul ketika data dari E²PROM tidak diterima dengan benar.
Keputusan
Kesalahan E²PROM (Read Only Memory yang Dapat Dihapus dan Diprogram Secara Elektronik):
Chip memori yang menyimpan isinya tanpa daya. Memori ini dapat dihapus, baik di
dalam komputer atau secara eksternal dan biasanya membutuhkan lebih banyak
tegangan untuk penghapusan daripada +5 volt umum yang digunakan dalam sirkuit
logika. Memori ini berfungsi seperti non-volatile RAM, tapi menulis ke E²PROM lebih
lambat daripada menulis ke RAM.

Dugaan  PCB unit indoor rusak


Penyebab  Faktor eksternal (Suara, dll.)

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa
rusak.

Putar daya ke OFF dan ON lagi untuk


restart.

TIDAK
Reset normal? Ganti PCB unit indoor.
YA

Kesalahan dapat disebabkan oleh


faktor eksternal, bukan komponen
yang rusak.
Cari penyebabnya dan perbaiki
situasi.

Service Diagnosis 100


SiMT281416E Troubleshooting by Remote Controller

5.3 Kelainan Sistem Permukaan Air Buang


Kode Kesalahan A3
Model Semua model indoor (kecuali FVQ)
yang
Berlaku

Metode dengan deteksi saklar apung OFF


Deteksi
Kesalahan

Kondisi Kesalahan timbul ketika permukaan air mencapai batas atasnya dan ketika saklar apung
Keputusan berputar ke OFF.
Kesalahan

Dugaan  Pompa kuras rusak


Penyebab  Pekerjaan pipa buang salah
 Pipa buang tersumbat
 Saklar apung rusak
 PCB unit indoor rusak
 Konektor korsletingX15A pada PCB rusak

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa
rusak.

Is a drain
Apakah pump
pompa kuras TIDAK
NO
tersambung ke PCB unit
connected to the indoor unit
indoor?
Sambung pompa kuras.
PCB?
YA

Doespompa
the drain TIDAK Atur ke
Apakah kuras N TIDAK TIDAK
pump work afteroperasi
restarting "darurat" dan periksa
bekerja setelah Ganti PCB unit indoor.
direstart?
operation? tegangan X25A. 220-240
VAC?
YES
YA YA
Ganti pompa kuras.
YA
Apakah permukaan air
Is buang
the drain water level YES
secara tidak normal Sistem buang rusak
abnormally
tinggi? high?

NO
TIDAK

Is the float
Apakah saklarswitch
apung TIDAK
Sambung saklar apung.
connected
tersambung keto X15A?
X15A?

YA

Remove
Lepas the float switch
saklar apungfromdariX15A,
X15A,
short circuit X15A,dan
korsletingZ15A, andrestart
restartoperasi.
operation.

TIDAK
Apakah"A3muncul
Does " appeardi NO
on tampilan
the remote
remotecontroller
control?
Ganti saklar apung .
display?
YA
Ganti PCB unit indoor.

Catatan:
Jika terdeteksi oleh PCB tanpa X15A, PCB rusak.
101 Service Diagnosis
Troubleshooting by Remote Controller SiMT281416E

5.4 Kelainan Motor Kipas Unit Indoor


Kode Kesalahan

Model Semua model indoor


yang
Berlaku

Metode Perputaran kipas tidak normal terdeteksi oleh sinyal output dari motor kipas.
Deteksi
Kesalahan

Kondisi Ketika perputaran kipas tidak meningkat


Keputusan
Kesalahan

Dugaan  Kabel rusak di, korsleting, atau konektor lepas dari harness motor kipas
Penyebab  Motor kipas rusak
(Kabel atau isolasi rusak)
 Sinyal output dari motor kipas tidak normal (sirkuit rusak)
 PCB unit indoor rusak
 Motor kipas terkunci
(Karena motor atau penyebab eksternal)
 Kipas tidak berputar karena benda asing menghalangi kipas.

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa rusak.

Putar catu daya ke OFF.


Tunggu 10 menit.

Apakah ada YA
benda asing di sekitar Singkirkan benda asing.
kipas?
TIDAK

Apakah harness motor


kipas tersambung ke PCB TIDAK
Sambung dengan benar.
unit indoor (1)?

YA
Jika konektor
untuk motor kipas (1) dilepas, TIDAK
apakah kipas dapat dengan Ganti motor kipas.
mudah diputar dengan tangan?

YA
Periksa konektor motor kipas
(2)

Apakah resistensi antara TIDAK


NO
masing-masing pin di atas Ganti motor kipas.
standar penilaian?

YA
Ganti PCB unit indoor.

Catatan:
1 Konektor dan PCB unit indoor
Model Konektor untuk motor kipas PCB
FCQ X20A A1P
FHQ50-125 X20A and X26A A1P
FHQ140 X20A A1P
FAQ X20A A2P

Service Diagnosis 102


SiMT281416E Troubleshooting by Remote Controller
FBQ X1A and X2A A2P
FVQ X20A A1P

103 Service Diagnosis


Troubleshooting by Remote Controller SiMT281416E

2 Saluran Sinyal Motor Kipas


Periksa konektor motor kipas (Kabel catu daya)
Putar catu daya ke OFF.
Ukur resistensi antara fasa U, V, W di konektor bagian motor (3-kabel inti) untuk memeriksa bahwa
nilai seimbang dan tidak ada korsleting, saat konektor atau konektor relay terputus.

<FHQ50 • 60BVV1G(4), FHQ71BVV1B(4)>


Tempat pengukuran Penilaian
Hitam – Merah 71.0 ± 10%
Hitam – Putih 73.5 ± 10%

<FHQ100 • 125BVV1B>
Red Tempat pengukuran Penilaian
Hitam – Merah 53.5 ± 10%
White
Hitam – Putih 31.6 ± 10%
Black

<FBQ50-140DV1(4)>
Tempat pengukuran Penilaian
Hitam – Merah 3.5 ± 10%
Hitam – Putih 3.5 ± 10%

Pemeriksaan Konektor Motor Kipas


<FHQ140CAVEB, FAQ71-100CVEB, FVQ50-60CVE(4), FVQ71-140CVEB(4)>
Periksa konektor saluran sinyal motor kipas
Putar catu daya ke OFF.
Dengan konektor motor kipas terputus, ukur resistensi antara setiap pin, kemudian pastikan bahwa
resistensi lebih dari nilai yang disebutkan dalam tabel berikut.

1 —

2 White FG

3 Orange Vsp

4 Brown Vcc

5 Blue GND

6 —

7 —

8 Red Vdc

Tempat pengukuran Penilaian


Putih – Biru
Orange – Biru
1 atau lebih
Coklat – Biru
Merah – Biru

Pemeriksaan konektor motor kipas tidak tersedia untuk model berikut.


FCQ50-140LUV1(4)

Service Diagnosis 104


SiMT281416E Troubleshooting by Remote Controller

5.5 Kelainan Motor Sirip Sayap Ayun/Terkunci


Kode Kesalahan

Model FCQ, FHQ50-125, FAQ-C, FVQ


yang
Berlaku

Metode Deteksi Penggunaan ON/OFF saklar pembatas ketika motor berputar.


Kesalahan

Kondisi Ketika ON/OFF saklar mikro untuk deteksi posisi tidak dapat diputar meskipun motor sirip
Keputusan sayap ayun diaktifkan selama jangka waktu tertentu (sekitar 30 detik).
Kesalahan  Kode kesalahan ditampilkan tetapi sistem beroperasi terus

Dugaan  Motor sirip sayap ayun rusak


Penyebab  Saklar mikro rusak
 Sambungan konektor rusak
 PCB unit indoor rusak

105 Service Diagnosis


Troubleshooting by Remote Controller SiMT281416E

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa
rusak.

Apakah konektor
(1) tersambung TIDAK
Sambung dengan benar.
dengan benar?

YA

Apakah konektor
transfer saklar pembatas TIDAK
tersambung dengan benar? Sambung dengan benar.

YA

Putar catu daya ke OFF sekali dan


restart, kemudian periksa apakah
motor sirip sayap ayun berputar ketika
catu daya direstart.

Lepas konektor (2), putar catu daya


ke OFF sekali dan restart, kemudian
Apakah motor sirip YA periksa apakah saklar pembatas
sayap ayun berputar?
memiliki kontinuitas ketika catu daya
direstart.
TIDAK

Putar catu daya ke OFF sekali dan


Apakah kontinuitas
restart, kemudian ukur tegangan /tanpa kontinuitas YA
output konektor (3) ketika catu daya
Ganti PCB unit indoor.
terbalik?
direstart.
TIDAK

TIDAK
220-240 VAC? Ganti PCB unit indoor.
YA

Ganti motor sirip sayap ayun.

Catatan:
 Konektor dan PCB unit indoor
Konektor untuk motor sirip sayap ayun
Model 1 2 3 PCB
FHQ X29A, X14A X14A X29A A1P

Service Diagnosis 106


SiMT281416E Troubleshooting by Remote Controller

5.6 Tegangan Catu Daya Tidak Normal


Kode Kesalahan

Model FBQ-D
yang
Berlaku

Metode Deteksi Mendeteksi kesalahan dengan memeriksa tegangan input motor kipas
Kesalahan

Kondisi Ketika tegangan input motor kipas 150V dan kurang, atau 386V dan lebih
Keputusan
Kesalahan

Dugaan  Kesalahan tegangan catu daya


Penyebab  Sambungan pada saluran sinyal rusak
 Kabel rusak
 Listrik mati sesaat, lain-lain

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa
rusak.

Periksa kondisi catu daya.


1. Periksa apakah tegangan catu daya
220V-240V ± 10%.
2. Periksa apakah ada fasa terbuka daya
atau kabel yang rusak.
3. Periksa apakah ketidakseimbangan
bagian tegangan catu daya berada
dalam 6V.

Ada masalah pada


kondisi catu daya yang YA
Perbaiki kesalahan.
dijelaskan di atas.

NO
TIDAK

Kesalahan YA
ditampilkan lagi. Periksa dan perbaiki kabel.

NO
TIDAK

Faktor eksternal mungkin menjadi


penyebab, seperti listrik mati dan
listrik mati sesaat.

107 Service Diagnosis


Troubleshooting by Remote Controller SiMT281416E

5.7 Kelainan Sistem Buang


Kode Kesalahan

Model Semua model indoor (kecuali FVQ)


yang
Berlaku

Metode Deteksi Kebocoran air terdeteksi dengan operasi saklar apung ON/OFF sementara kompresor
Kesalahan tidak beroperasi.

Kondisi Saklar apung berubah dari ON ke OFF sementara kompresor OFF.


Keputusan  Kode kesalahan ditampilkan tapi sistem terus beroperasi
Kesalahan

Dugaan  Kesalahan dalam pemasangan pipa buang


Penyebab  Saklar apung rusak
 PCB unit indoor rusak
 Sambungan konektor rusak
 Pompa kuras rusak

Service Diagnosis 108


SiMT281416E Troubleshooting by Remote Controller

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa rusak.
Untuk selain FHQ

Apakah saklar apung TIDAK


dan pipa buang normal? Kemungkinan saklar apung rusak.
Periksa apakah tinggi saluran dan
YA panjang pipa horisontal tidak sesuai
spesifikasi.

Apakah sistem TIDAK


Sistem buang pada air buang
saluran air normal?
tersumbat
YA Pompa kuras tersumbat
Saklar apung rusak
Ganti PCB unit indoor.
Periksa apakah tinggi saluran dan
panjang pipa horisontal tidak sesuai
spesifikasi.

Untuk FHQ

TIDAK
Apakah kit pompa kuras terpasang? Periksa konektor jumper (1).
YA

TIDAK Periksa pompa kuras dan pipa


Apakah pompa kurasnormal? NO
Is drain pump buang.
normal?

YA

Apakah jumlah air buang YA Periksa sistem saluran air.


yang bersirkulasi terlalu YES
Periksa apakah tinggi saluran dan
banyak setelah pompa berhenti
beroperasi? panjang pipa horisontal tidak
sesuai spesifikasi.
TIDAK

Apakah air buang YES


mengalir secara terbalik selama non
YA Trap di sistem saluran air rusak.
operasi?

TIDAK

Ganti PCB unit indoor.

Catatan:
1. Konektor
Model Konektor Jumper
FHQ X15A

109 Service Diagnosis


Troubleshooting by Remote Controller SiMT281416E

5.8 Kelainan Pengaturan Kapasitas


Kode Kesalahan

Model Semua model indoor


yang
Berlaku

Metode Deteksi Kapasitas ditentukan sesuai dengan resistensi adaptor pengaturan kapasitas dan memori
Kesalahan dalam memori IC pada PCB unit indoor, dan apakah nilai normal atau tidak normal juga
ditentukan.

Kondisi Ketika kode kapasitas tidak disimpan ke PCB, dan adaptor pengaturan kapasitas tidak
Keputusan tersambung.
Kesalahan Ketika kapasitas yang tidak ada untuk unit tersebut diatur.

Dugaan  Sambungan adaptor pengaturan kapasitas rusak


Penyebab  PCB unit indoor rusak

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa
rusak.

TIDAK
PCB unit indoor NO
diganti dengan PCB Ganti PCB unit indoor.
cadangan.

YA

Adaptor
pengaturan TIDAK
NO
kapasitas Ganti PCB unit indoor .
dipasang ketika
mengganti PCB.
YA

Pasang adaptor pengaturan


kapasitas.

Service Diagnosis 110


Troubleshooting by Remote Controller SiMT281416E

5.9 Kelainan Termistor


Kode Kesalahan

Model Semua model indoor


yang
Berlaku

Metode Deteksi Kesalahan terdeteksi dengan suhu yang terdeteksi oleh termistor.
Kesalahan

Kondisi Ketika thermistor terputus atau korsleting saat unit hidup.


Keputusan
Kesalahan

Dugaan  Sambungan konektor rusak


Penyebab  Termistor rusak
 PCB unit indoor rusak
 Kabel rusak atau putus

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa rusak.

Periksa sambungan konektor.

TIDAK
Apakah tersambung dg benar? Perbaiki sambungan.
YA

Periksa resistensi termistor.

CHECK 1 TIDAK
Apakah normal?
Ganti termistor.
YA

Periksa kontak antara termistor


dan PCB.

TIDAK
Apakah kontak OK? Perbaiki kontak.
YA

Ganti PCB unit outdoor.

Termistor penukar panas (R2T)


Termistor penukar panas menengah (R3T)
Termistor udara hisap(R1T)

CHECK 1 Lihat halaman 152, 153.

Service Diagnosis 110


SiMT281416E Troubleshooting by Remote Controller

5.10 Kesalahan Gabungan antara PCB Unit Indoor dan PCB


Kipas
Kode Kesalahan

Model FBQ
yang
Berlaku

Metode Deteksi Melakukan deteksi saluran terbuka dengan PCB kipas menggunakan PCB unit indoor
Kesalahan (A1P).

Kondisi Ketika data komunikasi PCB kipas salah


Keputusan
Kesalahan

Dugaan  PCB kipas rusak


Penyebab  Sambungan adaptor pengaturan kapasitas rusak.
 Pengaturan lapangan rusak

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa rusa k.

Apakah tipe PCB kipas TIDAK


(A2P) benar? (1) Ganti dengan PCB kipas (A2P)
yang benar.

YA

TIDAK
NO Apakah PCB unit indoor
(A1P) diganti dengan PCB
cadangan?

YA

Apakah adaptor
pengaturan kapasitas yang
benar dipasang saat TIDAK
menggantinya dengan PCB Pasang adaptor pengaturan
cadangan? kapasitas yang benar.

YA

Setelah memasang transmisi


untuk indoor dan outdoor,
diagnosis operasi lagi.

Catatan: 1. Tipe PCB kipas.


Model yang berlaku Tipe PCB kipas
FBQ50 - 71 PC0609-2
FBQ100-140 PC0609-3

111 Service Diagnosis


Troubleshooting by Remote Controller SiMT281416E

5.11 Kelainan Sistem Sensor Kelembaban


Kode Kesalahan

Model FCQ
yang
Berlaku

Metode Deteksi The error is detected by humidity detected by humidity sensor.


Kesalahan

Kondisi The error is generated when the humidity sensor becomes disconnected or shorted when the
Keputusan unit is running.
Kesalahan
 Error code is displayed but the system operates continuously

Dugaan  Sensor rusak


Penyebab  Kabel rusak
 Faktor eksternal (Suara, dll.)

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa rusa k.

Lepas sensor kelembaban dari PCB


unit indoor dan pasang lagi.

YA
Apakah berfungsi secara normal? Hal ini normal.
(Kontak konektor buruk)

NO
TIDAK

Hapus riwayat kode kesalahan dari


remote control. (1)

Kesalahan ditampilkan lagi. YA


Ganti PCB sensor kelembaban
(2)
(A2P).
3
NO
TIDAK

Diduga faktor eksternal (suara


atau lainnya), selain kerusakan
yang menyebabkan kesalahan.

Catatan:
1. Untuk menghapus riwayat, tombol ON/OFF remote control harus ditekan dan ditahan 5 detik
dalam mode periksa.
2. Untuk menampilkan kode, tombol Operasi PEMERIKSAAN/UJI COBA remote control harus
ditekan dan ditahan dalam mode normal .
3. Jika ditampilkan meskipun setelah mengganti rakitan PCB sensor kelembaban (A2P) dan
melakukan langkah 1 dan 2, ganti rakitan PCB unit indoor (A1P).

Service Diagnosis 112


SiMT281416E Troubleshooting by Remote Controller

5.12 Termistor Suhu Ruang pada Kelainan Remote Control


Kode Kesalahan

Model Semua model indoor


yang
Berlaku

Metode Deteksi Meskipun termistor suhu ruang rusak, sistem masih bisa beroperasi dengan termistor
Kesalahan sistem.
Kesalahan terdeteksi oleh suhu pada termistor suhu ruang.

Kondisi Kesalahan muncul ketika termistor suhu kamar terputus atau korsleting saat unit hidup.
Keputusan
Kesalahan  Meskipun termistor suhu kamar salah, sistem dapat beroperasi dengan termistor
sistem.

Dugaan  Termistor suhu ruang rusak


Penyebab  PCB remote control rusak
 Faktor eksternal (Suara, dll.)

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa
rusak.

Hapus riwayat kode kesalahan. (Saat


dalam mode pemeriksaan, tekan dan
tahan tombol ON/OFF selama jangka
waktu 5 detik atau lebih.)

YA
Kesalahan ditampilkan lagi. Ganti remote control.

NO
TIDAK
Faktor eksternal selain kesalahan
peralatan. (Misalnya, suara dll)

Catatan:
1. Cara menghapus “riwayat kode kesalahan”.
Tekan tombol ON/ OFF selama 5 detik atau lebih saat kode kesalahan ditampilkan dalam mode
pemeriksaan.

113 Service Diagnosis


Troubleshooting by Remote Controller SiMT281416E

5.13 Kesalahan PCB Unit Outdoor


Kode Kesalahan

Model RZR
yang
Berlaku

Metode Deteksi Mikro-komputer memeriksa apakah E2PROM normal.


Kesalahan

Kondisi Ketika E2PROM salah saat memutar catu daya ke ON


Keputusan
Kesalahan

Dugaan  PCB unit outdoor rusak


Penyebab  Motor kipas rusak
 Faktor eksternal (Suara, dll.)

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa rusa k.

Putar catu daya ke OFF sekali


kemudian restart

Apakah reset YA
normal? Masalah dapat disebabkan oleh
faktor eksternal (suara, dll.)
NO
TIDAK selain kesalahan.

Putar catu daya ke OFF, lepas


konektor motor kipas kemudian
putar catu daya ke ON lagi.

YA
Kesalahan ditampilkan lagi. Ganti PCB unit outdoor (A1P).

NO
TIDAK

Periksa motor kipas.

Service Diagnosis 114


SiMT281416E Troubleshooting by Remote Controller

5.14 Kelainan Tekanan Tinggi (Terdeteksi oleh Saklar


Tekanan Tinggi)
Kode Kesalahan

Model RZR
yang
Berlaku

Metode Deteksi Sirkuit alat pelindung memeriksa kontinuitas pada saklar tekanan tinggi.
Kesalahan

Kondisi Ketika saklar tekanan tinggi diaktifkan


Keputusan Tekanan operasi: 4.0 MPa
Kesalahan

Dugaan  Saklar tekanan tinggi rusak


Penyebab  Harness saklar tekanan tinggi putus
 Sambungan konektor saklar tekanan tinggi rusak
 Penukar panas unit outdoor kotor
 Motor kipas unit outdoor rusak
 Refrigeran kelebihan isi
 Katup penghenti tidak dibuka
 PCB unit outdoor rusak

Pengaturan Tabel berikut berisi nilai saklar tekanan tinggi


Saklar Tekanan Model Saklar tekanan tinggi
Tinggi Terbuka Tertutup
RZR
4.0+0/-0.15MPa 3.0+/-0.15MPa

115 Service Diagnosis


Troubleshooting by Remote Controller SiMT281416E

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa rusa k.

Periksa kondisi pemasangan.

TIDAK
Apakah katup penghenti terbuka? Buka katup penghenti.
YA

Apakah saklar
tekanan tinggi kontrol dan
pelindung tersambung ke TIDAK
Sambung dengan benar.
PCB unit outdoor?
(Catatan)

YA

Putar catu daya ke OFF. Tunggu 10 menit


setelah kompresor berhenti beroperasi,
kemudian periksa hal berikut.

Apakah ada
kontinuitas dalam saklar TIDAK
tekanan tinggi kontrol dan Ganti saklar tekanan tinggi dengan
pelindung? tanpa kontinuitas.
YA

CHECK 2
YA
Apakah tekanan tinggi
secara tidak normal
Perbaiki tekanan tinggi.
tinggi?

NO
TIDAK

Atur remote control dan putar ke


ON lagi.

Apakah kode kesalahan YA


ditampilkan? Ganti saklar tekanan tinggi.

NO
TIDAK

Ganti PCB unit outdoor (A1P).

CHECK 2 Lihat halaman 154.

Service Diagnosis 116


SiMT281416E Troubleshooting by Remote Controller

5.15 Motor Kompresor Terkunci


Kode Kesalahan

Model RZR
yang
Berlaku

Metode Deteksi Mendeteksi motor yang terkunci saat kompresor diaktifkan.


Kesalahan

Kondisi Jika rotor motor tidak berputar ketika kompresor diaktifkan.


Keputusan
Kesalahan

Dugaan  Kompresor terkunci


Penyebab  Start tekanan diferensial tinggi (2.6MPa atau lebih)
 Katup penghenti tidak dibuka

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa rusa k.

Periksa kondisi pemasangan.

TIDAK
Apakah katup penghenti terbuka? Buka katup penghenti.
YA

Apakah kabel TIDAK


UVWN normal? Sambung dengan benar.
YA

Apakah tekanan tinggi YA


lebih tinggi dari 2.6 Perbaiki penyebabnya.
Mpa saat start?

TIDAK

Periksa dan pastikan


apakah kompresor YA
korsleting atau Ganti kompresor.
dibumikan?

NO
TIDAK

Apakah tekanan
rendah atau tinggi
berubah meskipun sesaat YA
Ganti PCB unit outdoor.
saat merestart
kompresor?

NO
TIDAK

Ganti kompresor.

117 Service Diagnosis


Troubleshooting by Remote Controller SiMT281416E

5.16 Kelainan Motor Kipas Unit Outdoor


Kode Kesalahan

Model RZR
yang
Berlaku

Metode Deteksi Kelainan sistem motor kipas terdeteksi dengan kecepatan kipas yang terdeteksi oleh hall
Kesalahan IC ketika motor kipas hidup.

Kondisi  Ketika kipas berputar dengan kecepatan kurang dari yang ditentukan selama 15 detik
Keputusan atau lebih saat kondisi perputaran motor kipas terpenuhi
Kesalahan  Ketika konektor pendeteksi kecepatan kipas terputus
 Ketika kesalahan muncul 4 kali, sistem mati.

Dugaan  Motor kipas rusak


Penyebab  Konektor harness antara motor kipas dan PCB terputus, atau konektor rusak
 Kipas tidak berputar karena ada benda asing yang tersangkut
 PCB unit outdoor rusak
 Sekring putus
 Faktor eksternal (Suara, dll.)

Service Diagnosis 118


SiMT281416E Troubleshooting by Remote Controller

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa rusa k.

Apakah
Konektor motor kipas
TIDAK
dengan benar Sambung konektor dengan benar.
tersambung ke PCB unit
outdoor?

YA

TIDAK
Apakah ada benda Singkirkan benda asing.
asing di sekitar
kipas?
YA
Lepas konektor motor kipas.

Apakah TIDAK Ganti motor kipas.


kipas dapat diputar dengan
mudah menggunakan
tangan?
YA
Periksa nilai resistensi motor
kipas. (1)

Apakah nilai
resistensi motor kipas TIDAK
Ganti motor kipas.
normal?
YA

Apakah ada sekring TIDAK


Ganti sekring.
dengan kontinuitas?

YA kipas dengan
Colokkan konektor motor
benar kemudian putar daya ke ON lagi.

YA
Kesalahan ditampilkan lagi. Ganti PCB unit outdoor.
RZR-LVVM(4): A1P
TIDAK
RZR-LUY1(4): A2P
Tidak ada masalah dengan unit.
Faktor eksternal (suara, dll) selain
kerusakan unit mungkin menjadi
penyebab kesalahan.

Catatan:
1. Periksa nilai resistensi motor kipas.
(1) Putar catu daya ke OFF.
(2) Saat konektor motor kipas terputus, ukur resistensi antara setiap pin, kemudian pastikan
bahwa resistensi lebih dari nilai yang disebutkan dalam tabel berikut.

1 Putih FG
2 Orange Vsp Tempat pengukuran
3 Coklat Vcc 1-4
4 Biru GND 2-4
3-4
5 –
4-7
6 –
7 Merah Vdc
119 Service Diagnosis
Troubleshooting by Remote Controller SiMT281416E

5.17 Kelainan Katup Ekspansi Elektronik


Kode Kesalahan

Model RZR
yang
Berlaku

Metode Deteksi  Mendeteksi kesalahan berdasarkan pemeriksaan kontinuitas katup ekspansi


Kesalahan elektronik.
 Mendeteksi kesalahan dengan derajat super panas pipa hisap, derajat super panas
pipa buang, dan derajat bukaan katup ekspansi elektronik.

Kondisi  Tidak ada catu daya umum ketika daya diputar ke ON


Keputusan  Ketika kondisi berikut terjadi
Kesalahan Derajat super panas pipa hisap  4°C
Derajat super panas pipa buang  5°C
Derajat bukaan katup ekspansi elektronik  Derajat bukaan minimum

Dugaan  Katup ekspansi elektronik rusak


Penyebab  Katup solenoid rusak
 Terputusnya harness katup ekspansi elektronik
 Sambungan konektor katup ekspansi elektronik rusak
 Setiap termistor rusak
 Pemasangan setiap termistor rusak
 Sensor tekanan rusak
 PCB unit outdoor rusak
 Operasi basah

Service Diagnosis 120


SiMT281416E Troubleshooting by Remote Controller

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa
rusak.

Putar catu daya ke OFF sekali


kemudian putar ke ON lagi.

TIDAK
NO Apakah kode
kesalahan
muncul lagi?

YA

Apakah konektor
katup ekspansi elektronik TIDAK
dengan benar tersambung Sambung dengan benar.
ke PCB unit outdoor?
(1)
YA

Apakah
resistensi koil katup TIDAK
ekspansi elektronik Ganti koil katup ekspansi elektronik.
normal? (2)

YA

Apakah setiap termistor


(termistor pipa hisap, pipa
buang, dan pipa distribusi TIDAK
penukar panas) dipasang Pasang dengan benar.
dengan benar?

YA

CHECK 1
Apakah karakteristik setiap TIDAK
termistor normal?
Ganti termistor yang tidak normal.

YA

121 Service Diagnosis


Troubleshooting by Remote Controller SiMT281416E

Sebenarnya, unit dalam operasi basah.

Lihat CHECK 6 untuk menghilangkan


penyebab operasi basah.

Restart operasi.

YA
Kesalahan ditampilkan lagi. Ganti PCB unit outdoor (A1P).

NO
TIDAK

Diduga faktor (suara, dll), selain


kerusakan yang menyebabkan
kesalahan.
Catatan:
1. Katup ekspansi elektronik dan konektor No.: X21A
2. Konektor katup ekspansi elektronik dan kriteria resistensi koil

CHECK 1 Lihat halaman 152, 153.


CHECK 6 Lihat halaman 157.

Service Diagnosis 122


SiMT281416E Troubleshooting by Remote Controller

5.18 Kelainan Suhu Pipa Buang


Kode Kesalahan

Model RZR
yang
Berlaku

Metode Deteksi Kelainan terdeteksi dengan suhu yang terdeteksi oleh termistor pipa buang.
Kesalahan

Kondisi  Ketika suhu pipa buang naik ke tingkat tinggi yang tidak normal
Keputusan  Ketika suhu pipa buang naik mendadak
Kesalahan  Ketika suhu pipa buang tidak naik setelah operasi mulai

Dugaan  Termistor pipa buang rusak


Penyebab  Sambungan termistor pipa buang rusak
 Jumlah refrigeran tidak cukup
 Kompresor rusak
 Terputusnya termistor pipa buang
 PCB unit outdoor rusak

123 Service Diagnosis


Troubleshooting by Remote Controller SiMT281416E

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa rusa k.

Apakah suhu pipa YA


buang tinggi? Kelainan pada sistem refrigeran
(1) seperti kekurangan refrigeran,
TIDAK kompresor rusak, dll. Lakukan
pemeriksaan.

Apakah
termistor pipa buang TIDAK
dengan benar tersambung Pasang dengan benar, dan
ke PCB (A1P)? operasikan unit lagi.

YA

Apakah
termistor pipa buang TIDAK
dipasang ke pipa buang? Pasang termistor, dan operasikan
unit lagi.
YA

CHECK 1
Apakah karakteristik TIDAK
termistor pipa buang
Ganti termistor pipa buang.
normal?

YA

Ganti PCB unit outdoor (A1P).

Catatan:
1. Suhu bervariasi tergantung pada tipe model.
Model Suhu
RZR 115°C

CHECK 1 Lihat halaman 152, 153.

Service Diagnosis 124


SiMT281416E Troubleshooting by Remote Controller

5.19 Kelainan Sistem Saklar Tekanan Tinggi


Kode Kesalahan

Model RZR
yang
Berlaku

Metode Deteksi Sirkuit alat pelindung memeriksa kontinuitas dalam saklar tekanan tinggi.
Kesalahan

Kondisi Ketika tidak ada kontinuitas dalam saklar tekanan tinggi selama kompresor berhenti
Keputusan beroperasi
Kesalahan

Dugaan  Saklar tekanan tinggi tidak lengkap


Penyebab  Sambungan konektor saklar tekanan tinggi rusak
 PCB unit outdoor rusak
 Kabel lead putus

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa rusa k.

Apakah
konektor saklar pelindung
tekanan tinggi (1) dengan TIDAK
NO
benar tersambung ke PCB Sambung dengan benar.
unit outdoor?

YA

Wait for 10selama


Tunggu minutes10
after the unit
menit setelah
stops operating,
unit berhenti then checkKemudian
beroperasi. the
following.
periksa hal berikut.

Is there
Apakah ada kontinuitas TIDAK
continuity
dalam setiapinsaklar
each NO
pelindung tekanan
protection tinggi?
high pressure Ganti saklar tekanan tinggi dengan
switch? tanpa kontinuitas. Resistensi
dalam operasi normal: 10 atau
YES
YA kurang.

TIDAK
Is there
Apakah adacontinuity
kontinuitas NO
in lead
dalam wire?
kabel lead?
Ganti kabel lead.

YA

Ganti PCB unit outdoor.

Catatan:
1. Konektor
Model Konektor
RZR50~71 –
RZR100~140 X32A (A1P)

125 Service Diagnosis


Troubleshooting by Remote Controller SiMT281416E

5.20 Kelainan Sistem Termistor


Kode Kesalahan

Model RZR
yang
Berlaku

Metode Deteksi Kelainan terdeteksi dengan suhu yang terdeteksi oleh setiap termistor.
Kesalahan

Kondisi Ketika termistor terputus atau korsleting selama operasi.


Keputusan
Kesalahan

Dugaan  Termistor rusak


Penyebab  Sambungan konektor rusak
 PCB unit outdoor rusak

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa
rusak.

Periksa konektor untuk sambungan. (1)

TIDAK
Normal? Sambung dengan benar.
YA

Lepas termistor dari PCB unit


outdoor, kemudian ukur resistensi
dengan menggunakan tester.

CHECK 1 TIDAK
Ganti termistor.
Normal?

YA

Ganti PCB unit outdoor (A1P).

Catatan: 1. Konektor termistor


RZR
Kode
Termistor rusak Termistor Konektor
kesalahan
H9 Termistor udara outdoor R1T X11A
J3 Termistor pipa buang R2T X12A
J5 Termistor pipa hisap R3T X12A
J6 Termistor penukar panas R4T X12A

J7 Termistor penukar panas


menengah
R5T X12A

CHECK 1 Lihat halaman 152, 153.

Service Diagnosis 126


SiMT281416E Troubleshooting by Remote Controller

5.21 Kelainan Sensor Tekanan


Kode Kesalahan

Model RZR125 • 140LVVM(4), RZR100-140LUY1(4)


yang
Berlaku

Metode Deteksi Kesalahan terdeteksi oleh tekanan yang diukur dengan sensor tekanan (S1NPL)
Kesalahan

Kondisi Ketika tekanan yang terdeteksi adalah sebagai berikut:


Keputusan  Tekanan yang terdeteksi  -0.05Mpa terus selama 185 detik
Kesalahan  Tekanan yang terdeteksi  4.4Mpa terus selama 185 detik

Dugaan  Sensor tekanan rusak


Penyebab  PCB unit outdoor rusak
 Sambungan konektor salah

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa
rusak.

Periksa apakah konektor untuk


sensor tekanan (X17A) dengan
benar tersambung ke PCB unit
outdoor (A1P)

Apakah tersambung TIDAK


dengan benar?
Sambung dengan benar.

YA

Ukur tegangan (V) antara pin (1) dan


(3) konektor di atas CHECK 5 .

Apakah relasi antara TIDAK


tekanan dan tegangan Ganti sensor tekanan (S1NPL).
normal?

YA

Ganti PCB unit outdoor (A1P).

CHECK 5 Lihat halaman 156.

127 Service Diagnosis


Troubleshooting by Remote Controller SiMT281416E

5.22 Kelainan PCB Unit Outdoor


Kode Kesalahan

Model RZR
yang
Berlaku

Metode Deteksi  Mendeteksi kesalahan dengan nilai arus selama output bentuk gelombang sebelum
Kesalahan kompresor startup.
 Mendeteksi kesalahan dengan nilai sensor arus selama operasi disinkronkan pada
saat startup.
 Mendeteksi kesalahan menggunakan sensor tegangan lebih kapasitor seri MP-PAM.

Kondisi  Ketika arus terdeteksi pada saat output bentuk gelombang sebelum mengoperasikan
Keputusan kompresor
Kesalahan  Ketika sensor arus salah selama operasi disinkronkan
 Ketika tegangan lebih terjadi di MP-PAM (1)
 Jika IGBT salah
 Jika pengaturan jumper rusak

Dugaan  PCB unit outdoor rusak (A1P)


Penyebab  IPM 2 rusak
 Sensor arus rusak
 MP-PAM rusak
 IGBT (3) atau sirkuit penggerak rusak

Catatan: 1. MP: Multi Pulsa


2. IPM: IPM adalah alat semikonduktor untuk tenaga listrik yang menggabungkan
sirkuit penggerak dan fitur self-protection perangkat listrik yang mengontrol
tenaga listrik.
3. IGBT: IGBT adalah alat semikonduktor daya yang biasanya digunakan sebagai
saklar elektronik.

Service Diagnosis 128


SiMT281416E Troubleshooting by Remote Controller

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa
rusak.

Putar catu daya ke OFF sekali.

Apakah kabel lead


untuk kompresor TIDAK
tersambung ke PCB dan Sambung dengan kuat dan
kompresor dengan kuat? benar.

YA

Periksa nilai resistensi untuk


motor kipas.

Apakah nilai resistensi TIDAK


Ganti motor kipas.
motor kipas normal?

YA

Apakah sekring TIDAK


Ganti sekring.
memiliki kontinuitas?
Gunakan sekring yang
YA dispesifikasikan saja.

Daya ON lagi.

YA
Kesalahan ditampilkan lagi. Ganti PCB unit outdoor.

NOTIDAK

Tidak ada masalah dengan unit.


Faktor eksternal (suara, dll)
selain kerusakan unit mungkin
menjadi penyebabnya.

129 Service Diagnosis


Troubleshooting by Remote Controller SiMT281416E

5.23 Suhu Sirip Radiasi Meningkat


Kode Kesalahan

Model RZR100-140LVVM(4), RZR100-140LUY1(4)


yang
Berlaku

Metode Deteksi Suhu sirip terdeteksi oleh termistor sirip radiasi.


Kesalahan

Kondisi Ketika suhu sirip radiasi inverter meningkat secara tidak normal karena penyebaran
Keputusan panas rusak.
Kesalahan

Dugaan  Termistor sirip radiasi rusak


Penyebab  Suhu udara outdoor tinggi
 Bukaan hisap tersumbat
 Sirip radiasi kotor
 PCB unit outdoor rusak
 Pengaktifan saklar panas sirip
 Pendinginan sirip radiasi inverter tidak memadai
 Sambungan konektor rusak

Service Diagnosis 130


SiMT281416E Troubleshooting by Remote Controller

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa rusak.

Apakah
suhu sirip radiasi YA
tinggi? Hilangkan penyebabnya.
(1)

NO
TIDAK

Apakah
konektor termistor
sirip radiasi dengan TIDAK
benar tersambung ke Sambung dengan benar.
PCB unit outdoor?

YA

Putar catu daya ke ON,


kemudian tekan tombol periksa
pada remote control sekali.

Apakah kode
Kesalahan ditampilkan YA Lihat Diagnosis Kesalahan .
pada remote control?

NO
TIDAK

Apakah kode
kesalahan YA Ganti PCB unit outdoor.
muncul lagi ketika
unit memulai
operasi?

NO
TIDAK

Lanjutkan operasi.

Catatan: 1.Nilai deteksi suhu sirip radiasi


Model Deteksi Reset
RZR 76°C 66°C

131 Service Diagnosis


Troubleshooting by Remote Controller SiMT281416E

5.24 Kelebihan Arus Output DC (Instan)


Kode Kesalahan

Model RZR
yang
Berlaku

Metode Deteksi Kesalahan terdeteksi dengan mengubah arus yang mengalir ke transistor daya menjadi
Kesalahan tegangan dengan CT1 (sensor arus DC).

Kondisi Ketika arus berlebih terjadi pada transistor daya


Keputusan (Diaktifkan oleh kelebihan arus sesaat)
Kesalahan

Dugaan  Koil kompresor rusak (putus, isolasi buruk)


Penyebab  Kesalahan startup kompresor (kunci mekanis)
 PCB unit outdoor rusak
 Fluktuasi sesaat tegangan catu daya
 Kompresor rusak (jika bantalan tergores)
 Katup penghenti tidak dibuka

Service Diagnosis 132


SiMT281416E Troubleshooting by Remote Controller

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa
rusak.

Periksa kondisi pemasangan.

TIDAK
Apakah katup penghent terbuka?
Buka katup penghenti.

Apakah koil YA
kompresor putus Ganti kompresor.
atau isolasi rusak?

TIDAK

Putar catu daya utama ke OFF,


kemudian lepas sambungan antara
kompresor dan inverter.

CHECK 4
Pemeriksaan TIDAK
kontinuitas di transistor daya Ganti PCB unit outdoor.
(IGBT). Apakah kontinuitas RZR-LVVM(4): A1P
normal?
RZR-LUY1(4): A2P

YA

Apakah tegangan
output inverter dihasilkan
kira-kira pada peningkatan
kecepatan yang sama untuk TIDAK
setiap fasa setelah diputar ke Ganti PCB unit outdoor.
ON lagi?  Ketika mengoperasikan kompresor dengan
(1) (U-V, V-W, saluran output kompresor terputus,
W-U) kompresor berhenti karena kesalahan
setelah 5 detik. Oleh karena itu, periksa
kenaikan tegangan selama 5 detik.
YA

Periksa tegangan
Periksa catu
tegangan daya.
catu daya

Apakah terjadi penurunan


tegangan sesaat? Perbaiki catu daya.

TIDAK Pemeriksaan kompresor.


Periksa berdasarkan prosedur
diagnosis untuk suara tidak
normal, goncangan, status operasi,
dll pada kompresor.

Catatan:
1. Perkiraan nilai
Model Nilai deteksi arus lebih sesaat
RZR 32.3A
CHECK 4 Lihat halaman 155.

133 Service Diagnosis


Troubleshooting by Remote Controller SiMT281416E

5.25 Panas Elektronik (Jeda Waktu)


Kode Kesalahan

Model RZR
yang
Berlaku

Metode Deteksi Kesalahan terdeteksi dengan mengubah arus yang mengalir ke transistor daya menjadi
Kesalahan tegangan dengan CT1 (sensor arus DC).
PCB inverter mendeteksi gangguan sinyal posisi.

Kondisi Ketika kompresor kelebihan beban (kecuali saat startup) terdeteksi


Keputusan
Kesalahan

Dugaan  Kompresor kelebihan beban (selama operasi)


Penyebab  Koil kompresor putus
 Kompresor rusak (jika bantalan tergores)
 PCB unit outdoor rusak

Service Diagnosis 134


SiMT281416E Troubleshooting by Remote Controller

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa rusa k.

Apakah arus
sekunder inverter lebih tinggi YA
dari A (lihat di bawah) untuk Kompresor kelebihan beban.
setiap fasa? Perlu untuk memeriksa kompresor
dan sistem refrigeran.
NO
TIDAK

Putar catu daya utama ke OFF,


kemudian lepas sambungan
antara kompresor dan inverter.

CHECK 4
Pemeriksaan kontinuitas di
TIDAK
transistor daya (IGBT). Apakah Ganti PCB unit outdoor.
kontinuitas normal?
RZR-LVVM(4): A1P
RZR-LUY1(4): A2P
YA

Apakah tegangan
output inverter dihasilkan
kira-kira pada peningkatan
kecepatan yang sama untuk TIDAK
setiap fasa setelah diputar ke  Ketika mengoperasikan kompresor Ganti PCB unit outdoor.
ON lagi?
dengan saluran output kompresor RZR-LVVM(4): A1P
(1) (U-V, V-W,
terputus, kompresor berhenti
W-U)
karena kesalahan setelah 5 detik.
RZR-LUY1(4): A2P
YA Oleh karena itu, periksa kenaikan
tegangan selama 5 detik

Pemeriksaan kompresor.
Periksa berdasarkan prosedur
diagnosis untuk suara tidak
normal, goncangan, status operasi,
dll pada kompresor.

Catatan:
1. Nilai deteksi panas elektronik
Model Nilai deteksi
RZR 17A × 5 detik atau 12.1A × 260 detik

CHECK 4 Lihat halaman 155.

135 Service Diagnosis


Troubleshooting by Remote Controller SiMT281416E

5.26 Pencegahan Berhenti (Jeda Waktu)


Kode Kesalahan

Model RZR
yang
Berlaku

Metode Deteksi Kesalahan terdeteksi dari arus yang mengalir ke transistor daya menjadi tegangan
Kesalahan dengan CT1 (sensor arus DC).
PCB inverter mendeteksi gangguan sinyal posisi.

Kondisi Ketika kompresor kelebihan beban dan perubahan beban terdeteksi


Keputusan
Kesalahan

Dugaan  Katup penghenti tidak dibuka


Penyebab  Startup diferensial tekanan
 PCB unit outdoor rusak
 Kompresor rusak (terkunci)

Service Diagnosis 136


SiMT281416E Troubleshooting by Remote Controller

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa
rusak.

Periksa kondisi pemasangan.

TIDAK
Apakah katup penghenti terbuka? Buka katup penghenti.
YA

Apakah
perbedaan antara tekanan
tinggi dan rendah sebelum TIDAK
Penyamaan tekanan tidak
startup tidak lebih dari
0.2MPa? memadai.
Periksa sistem refrigeran.
YA

Putar catu daya utama ke OFF,


kemudian lepas sambungan antara
kompresor dan inverter.

CHECK 4
Pemeriksaan kontinuitas di
TIDAK
transistor daya (IGBT). Apakah Ganti PCB unit outdoor. RZR-
kontinuitas normal?
LVVM(4): A1P
RZR-LUY1(4): A2P
YA

Kompresor YA
dibumikan dan Ganti kompresor.
korsleting.

NO
TIDAK

Pemeriksaan kompresor.
Periksa berdasarkan prosedur
diagnosis untuk suara tidak
normal, goncangan, status
operasi, dll pada kompresor.

CHECK 4 Lihat halaman 155.

137 Service Diagnosis


Troubleshooting by Remote Controller SiMT281416E

5.27 Kesalahan Sistem Transmisi antara PCB Unit Outdoor


Kode Kesalahan

Model RZR
yang
Berlaku

Metode Deteksi Periksa dan pastikan apakah transmisi antara PCB unit outdoor dilakukan secara normal.
Kesalahan

Kondisi Ketika transmisi tidak dilakukan dalam jangka waktu tertentu atau lebih lama
Keputusan
Kesalahan

Dugaan  Kabel transmisi antara PCB unit outdoor salah/kontak di kabel tidak memadai
Penyebab  PCB unit outdoor rusak
 Faktor eksternal (suara, dll)
 Motor kipas unit outdoor rusak
 Kontak konektor motor kipas rusak

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa rusa k.

Apakah konektor motor TIDAK


kipas tersambung? Sambung konektor, dan putar ke
ON lagi.
YA

Lepas konektor motor kipas, dan


putar ke ON lagi.

Apakah
ditampilkan pada remote YA
control? (Apakah Ganti motor kipas.
tidak ditampilkan?) .
Transmisi inverter rusak karena
TIDAK kesalahan motor kipas

Ganti PCB unit outdoor.

Service Diagnosis 138


SiMT281416E Troubleshooting by Remote Controller

5.28 Fasa Terbuka atau Ketidakseimbangan Tegangan Catu


Daya
Kode Kesalahan

Model RZR
yang
Berlaku

Metode Deteksi Kesalahan terdeteksi dengan bentuk gelombang tegangan kapasitor sirkuit utama yang
Kesalahan dibangun di inverter.

Kondisi Ketika bentuk gelombang tegangan yang disebutkan sebelumnya sama dengan bentuk
Keputusan gelombang fasa terbuka catu daya.
Kesalahan

Dugaan  Fasa terbuka


Penyebab  Ketidakseimbangan tegangan antara fasa
 PCB unit outdoor rusak
  Kapasitor sirkuit utama rusak
  Unit daya (Putus dalam modul dioda)
  Relay magnetik rusak
  Kabel sirkuit utama salah

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa rusa k.

Periksa LED pada PCB unit TIDAK


outdoor (Ada fasa terbuka?) Faktor selain fasa terbuka

YA

Ada fasa terbuka YA


tegangan catu daya? Faktor lapangan

NO
TIDAK

Apakah ketidakseimbangan
YA
tegangan antara fasa Faktor lapangan
besar?

NO
TIDAK

Ganti PCB unit outdoor.

Catatan: Target : ±10V antara fasa, R-S, S-T, T-R

139 Service Diagnosis


Troubleshooting by Remote Controller SiMT281416E

5.29 Kelainan Termistor Sirip Radiasi


Kode Kesalahan

Model RZR100-140LVVM(4), RZR100-140LUY1(4)


yang
Berlaku

Metode Deteksi Deteksi dengan sirkuit terbuka atau korsleting pada termistor sirip radiasi selama
Kesalahan kompresor berhenti beroperasi.

Kondisi Ketika sirkuit terbuka atau korsleting pada termistor sirip radiasi terdeteksi selama
Keputusan kompresor berhenti beroperasi
Kesalahan

Dugaan  Termistor sirip radiasi rusak


Penyebab  PCB unit outdoor rusak
 Faktor eksternal (suara, dll)

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa rusa k.

Periksa LED pada PCB unit outdoor.

DoesApakah termistor fin


the radiation TIDAK
sirip radiasi salah? Selidiki faktor selain kesalahan.
thermistor error?

YA

Lepas konektor dari (1) on PCB,


kemudian periksa resistensi termistor
pada suhu normal.

CHECK 1 TIDAK
Normal? Ganti PCB unit outdoor (1).
YA

Apakah reset memungkinkan?


Is reset possible? TIDAK
Ganti PCB unit outdoor (1).

YA

Reset

Catatan:
1. Konektor
Model Konektor PCB
RZR-LVVM(4) X111A A1P
RZR-LUY1(4) X111A A2P

CHECK 1 Lihat halaman 152, 153.

Service Diagnosis 140


SiMT281416E Troubleshooting by Remote Controller

5.30 Kelainan Pengaturan Kapasitas


Kode Kesalahan

Model RZR
yang
Berlaku
2
Metode Deteksi Periksa apakah nilai yang ditetapkan ditulis dalam E PROM (di pabrik) atau nilai adaptor
Kesalahan pengaturan kapasitas yang ditetapkan (untuk penggantian) sama dengan kapasitas unit
outdoor.
2
Kondisi Ketika nilai yang ditetapkan pada E PROM berbeda dari kapasitas unit outdoor atau
Keputusan adaptor pengaturan kapasitas kecuali untuk model PCB yang dipasang. (Keputusan
Kesalahan kesalahan hanya dilakukan saat catu daya diputar ke ON.)

Dugaan  Nilai E2PROM yang diatur salah


Penyebab  Adaptor pengaturan kapasitas salah
 PCB unit outdoor rusak

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa rusak.

Apakah adaptor
pengaturan kapasitas TIDAK
tersambung ke PCB Sambung adaptor untuk model
unit outdoor? (1) yang berlaku.

YA

Pastikan bahwa gabungan dari


adaptor pengaturan kapasitas yang Jika salah, perbaiki gabungan.
tersambung benar.

Catatan:
1. Adaptor pengaturan kapasitas tidak disambung di pabrik. (Kapasitas ditulis di E²PROM.) Adaptor
pengaturan kapasitas diperlukan hanya jika PCB diganti dengan PCB cadangan.

141 Service Diagnosis


Troubleshooting by Remote Controller SiMT281416E

5.31 Kekurangan Refrigeran (Kesalahan)


Kode Kesalahan

Model RZR
yang
Berlaku

Metode Deteksi (Dalam operasi normal)


Kesalahan Kekurangan refrigeran terdeteksi dengan derajat bukaan katup ekspansi elektronik dan
suhu dan tekanan yang diukur.

Kondisi (Dalam pendinginan)


Keputusan Ketika katup ekspansi elektronik terbuka sepenuhnya dan ekanan rendah di bawah 0.25
Kesalahan Mpa terus menerus selama 30 menit.

Dugaan  Katup penghenti tidak dibuka


Penyebab  Jumlah refrigeran tidak memadai
 Sistem pipa refrigeran tersumbat

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa rusa k.

TIDAK
Apakah katup penghenti terbuka? Buka katup penghenti.

YA

Apakah jumlah TIDAK


refrigeran benar? Kumpulkan refrigeran. Setelah
pengeringan vakum, isi refrigeran
YA dengan jumlah yang benar.

CHECK 7
Periksa penyumbatan pada sistem
pipa rerigeran.

Catatan:
 Alarm kekurangan refrigeran ditunjukkan tetapi operasi terus
berlanjut.

CHECK 7 Lihat halaman 158.

Service Diagnosis 142


SiMT281416E Troubleshooting by Remote Controller

5.32 Kelainan Tegangan Catu Daya


Kode Kesalahan

Model RZR
yang
Berlaku

Metode Deteksi Kesalahan terdeteksi dengan tegangan kapasitor sirkuit utama yang dibangun di inverter
Kesalahan dan tegangan catu daya.

Kondisi Ketika tegangan kapasitor sirkuit utama yang dibangun di inverter dan penurunan
Keputusan tegangan catu daya atau ketika terjadi gagal daya selama beberapa detik atau lebih.
Kesalahan  Remote control tidak menentukan kelainan.

Dugaan  Tegangan catu daya turun


Penyebab  Gagal daya sesaat
 Kabel sirkuit utama rusak
 PCB unit outdoor rusak
 Komponen sirkuit utama rusak

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa
rusak.

Periksa LED pada


PCB unit outdoor. (Apakah TIDAK
tegangan tidak memadai?)
Faktor lain

YA

Apakah tegangan catu TIDAK


daya antara (*1)?
Faktor lapangan

YA
TIDAK
Apakah kabel benar? Perbaiki kabel.
YA
Ketika kompresor hidup, ukur
tegangan antara + dan – kapasitor
elektrolit (C+, C-).

Apakah tegangan yang YA


diukur (1) atau lebih? Pantau tegangan
TIDAK (Penurunan tegangan sesaat)

Ganti PCB unit outdoor (A1P).

Catatan: 1. Nilai tegangan


Model Nilai
RZR-LVVM(4) 220 ~ 240V ± 10%
RZR-LUY1(4) 380 ~ 415V ± 10%

143 Service Diagnosis


Troubleshooting by Remote Controller SiMT281416E

5.33 Kesalahan Transmisi antara Unit Indoor dan Outdoor


Kode Kesalahan

Model RZR
yang
Berlaku

Timbulnya Kesalahan Kesalahan timbul ketika mikro-prosesor mendeteksi bahwa transmisi antara unit indoor
dan outdoor tidak normal selama waktu tertentu.
Kondisi Ketika transmisi normal tidak dilakukan selama jangka waktu tertentu atau lebih
Keputusan
Kesalahan

Dugaan  Kabel transmisi indoor-outdoor salah


Penyebab  PCB unit indoor rusak
 PCB unit outdoor rusak
 Sekring putus
 Motor kipas rusak
 Faktor eksternal (suara, dll)
 Catu daya rusak

Service Diagnosis 144


SiMT281416E Troubleshooting by Remote Controller

Pemecahan masalah
Diagnosis kabel yang salah, rusak atau putus. Jika LED pada PCB unit indoor OFF, hal ini
menunjukkan bahwa kabel transmisi antara unit indoor dan outdoor salah, rusak atau putus .

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa
rusak.

Apakah
tegangan catu daya TIDAK
antara 220 dan 240V atau Faktor lapangan
380 atau 415V?
YA

Apakah ada tipe


kabel yang salah, terminal TIDAK
longgar atau kontak rusak Pasang kabel dengan benar dan
dalam kabel transmisi antara dengan aman kencangkan
unit indoor dan outdoor?
sekrup terminal.

YA

TIDAK Apakah
aksesori opsional (1)
tersambung?
YA

Apakah
daya untuk aksesori
opsional disediakan dari
antara 1 dan 2 di blok TIDAK
terminal X1M atau X2M? Pasang kabel dengan benar.

YA

Apakah HAP pada YA


PCB unit outdoor berkedip? S
(PCB unit outdoor) B

TIDAK

Putar catu daya ke OFF dan lepas


konektor motor kipas unit outdoor.
Kemudian putar daya ke ON lagi.

IsApakah
HAPHAPblinking?
berkedip?
(Outdoor unit
(PCB unit PCB)
outdoor) YA
Ganti motor kipas unit outdoor.
NO
TIDAK

145 Service Diagnosis


Troubleshooting by Remote Controller SiMT281416E

Periksa nilai resistensi motor kipas


unit outdoor.

Apakah nilai
resistensi motor kipas TIDAK
Ganti motor kipas unit outdoor.
unit outdoor normal?

YA

Apakah sekring TIDAK


memiliki kontinuitas? Ganti sekring.

YA

CHECK 8
Periksa tegangan output kipas.

TIDAK
Apakah tegangan output Ganti PCB unit outdoor.
normal?

YA
Setelah memutar catu daya ke OFF,
dengan benar pasang konektor motor
kipas kemudian kembalikan daya.

Apakah U4" error


Does " kesalahan YA
B muncul lagi?
reoccur? Ganti PCB unit outdoor.
TIDAK
After turning OFF the power supply,
correctly insert the connector of the
fan motor and then restore the power.

Ganti PCB unit indoor.


Apakah
kesalahan atau
muncul lagi?
TIDAK Tidak ada masalah dengan unit.
Faktor eksternal (suara, dll)
selain kerusakan unit mungkin
menjadi penyebabnya.

Catatan:
1. Aksesoris opsional mengacu pada adaptor untuk kabel, auto grill dan aksesoris lainnya.

CHECK 8 Lihat halaman 159.

Service Diagnosis 146


SiMT281416E Troubleshooting by Remote Controller

5.34 Kesalahan Transmisi antara Unit Indoor dan Remote


Control
Kode Kesalahan

Model Semua model indoor


yang
Berlaku

Timbulnya Kesalahan Kesalahan timbul ketika mikro-prosesor mendeteksi bahwa transmisi antara unit indoor
dan remote control tidak normal selama waktu tertentu.
Dugaan  Remote control rusak
penyebab  PCB unit indoor rusak
 Penyebab dari luar (suara...)
 Sambungan 2 remote control utama (ketika menggunakan 2 remote control).

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa rusak.

Kontrol dengan 2 YA SS1 kedua remote YA


remote control control diatur ke Atur salah satu remote control ke
UTAMA. SUB, putar catu daya ke OFF
TIDAK TIDAK untuk sementara, kemudian
restart operasi.

Reset secara
Semua monitor normal TIDAK
NO normal ketika catu TIDAK
mikro-komputer PCB unit daya diputar ke OFF Ganti PCB unit indoor.
indoor berkedip. untuk sementara.

YA YA

Kesalahan dapat ditimbulkan oleh


suara.
Periksa daerah sekitarnya dan
restart operasi.
Menggunakan kabel
transmisi banyak-inti YA Ganti dengan kabel independen
antara unit indoor dan
remote control dua-inti.
TIDAK

Apakah TIDAK
ditampilkan terus- PCB remote control rusak atau
menerus? ganti PCB unit indoor yang rusak.
YA

Masalah dapat disebabkan oleh


faktor eksternal (suara, dll) selain
kesalahan.

147 Service Diagnosis


Troubleshooting by Remote Controller SiMT281416E

5.35 Kesalahan Transmisi antara Remote Control UTAMA


dan SUB Remote Control
Kode Kesalahan

Model Semua model indoor


yang
Berlaku

Timbulnya Kesalahan Kesalahan timbul ketika, jika mengontrol dengan 2 remote control, mikro-prosesor
mendeteksi bahwa transmisi antara unit indoor dan remote control (UTAMA dan SUB)
tidak normal selama waktu tertentu.
Dugaan  Kesalahan transmisi antara remote control UTAMA dan SUB remote control
penyebab  Sambungan antara SUB remote control
 PCB remote control rusak.

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa
rusak.

Mengontrol dengan TIDAK Saklar SS-1 TIDAK


2 remote control pada PCB remote control Putar saklar SS-1 salah satu
diputar ke UTAMA.
remote control ke UTAMA.
YA YA Putar catu daya ke OFF, dan
restart operasi.

Kedua saklar TIDAK Apakah ada


SS-1 pada remote kontinuitas dalam YA
kabel remote control?
Putar daya ke OFF sekali dan
control diputar ke SUB
restart operasi.
YA Ganti PCB remote control jika
NO
TIDAK timbul kesalahan.

Ganti kabel remote control.

Putar saklar SS-1 sala satu


remote control ke UTAMA.
Putar catu daya ke OFF, dan
restart operasi.

Service Diagnosis 148


SiMT281416E Troubleshooting by Remote Controller

5.36 Kelainan Saklar Pengaturan Lapangan


Kode Kesalahan

Model Semua model indoor


yang
Berlaku

Timbulnya Kesalahan Kesalahan timbul ketika pengaturan lapangan yang diatur untuk pair/twin/triple/double
twin salah.
Dugaan  PCB unit indoor atau outdoor rusak
penyebab  PCB catu daya rusak
 Kabel transmisi unit indoor-outdoor, indoor-indoor
 Kabel remote control rusak.

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa rusak.

Apakah remote
control tersambung ke lebih YA
dari 1 unit indoor? Sambung remote control dengan
benar.
NO
TIDAK

Apakah pengaturan TIDAK


Pair/Twin/Triple diatur Atur ke Pair dengan benar.
dengan benar?

Apakah
monitor normal mikro- TIDAK Apakah jumper indoor-indoor
komputer (HAP) semua N TIDAK
dan indoor-outdoor Sambung dengan benar.
PCB unit indoor berkedip? tersambung dengan benar?

YA YA

Apakah PCB catu TIDAK


daya tersambung Sambung dengan benar.
dengan benar?

YES

Putar daya ke OFF sekali, kemudian


restart, dan restart operasi. Apakah ada 220-240 VAC TIDAK
antara No.1 dan No.3 X2M Ganti transformator.
(Unit indoor)?

YA
Kabel salah, periksa ulang.

TIDAK Apakah jumper indoor-indoor TIDAK


Beroperasi dengan normal? dan indoor-outdoor Sambung dengan benar.
tersambung dengan benar?
YA

YA
Ganti PCB unit indoor.

Beroperasi dengan normal.

149 Service Diagnosis


Troubleshooting by Remote Controller SiMT281416E

5.37 Kesalahan Pengaturan Alamat Terpusat


Kode Kesalahan

Model Semua model unit indoor


yang
Berlaku

Metode Deteksi Mikro-komputer unit indoor mendeteksi dan menilai sinyal alamat terpusat sesuai dengan
Kesalahan transmisi antara unit indoor.

Kondisi Ketika mikro-komputer menilai bahwa sinyal alamat terpusat terduplikasi


Keputusan
Kesalahan

Dugaan  Pengaturan alamat terpusat rusak


penyebab  PCB unit indoor rusak

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa rusak.

Apakah perangkat yang


terkait dengan kontrol YA
terpusat tersambung ke Ubah pengaturan sehingga
unit indoor? alamat terpusat tidak terduplikasi.

NO
TIDAK

Ganti PCB unit indoor.

Service Diagnosis 150


SiMT281416E Troubleshooting by Remote Controller

5.38 Kesalahan Transmisi antara Unit Indoor dan Outdoor


/Pipa dan Kabel tidak Cocok/Kekurangan Refrigeran
Kode Kesalahan

Model RZR
yang
Berlaku

Metode Deteksi Periksa transmisi antara unit indoor dan outdoor dengan mikro-komputer ketika daya
Kesalahan diputar ke ON.
Mendeteksi dengan memeriksa perbedaan suhu berikut selama operasi kompresor.
A: Perbedaan suhu terdeteksi oleh termistor penukar panas indoor (R2T) dan
termistor udara hisap indoor (R1T)
B: Perbedaan suhu penguapan (Te) terdeteksi oleh termistor penukar panas indoor
(R2T) dan sensor kompresor

Kondisi Ketika kabel transmisi antara unit indoor dan outdoor salah
Keputusan Ketika kondisi berikut terus berlanjut selama 20 menit selama operasi kompresor
Kesalahan A: R2T – R1T < 4ºC, dan
B: R2T – Te > 14ºC

Dugaan  Kabel transmisi antara unit indoor dan outdoor salah


penyebab  Kabel dan pipa tidak cocok
 Kekurangan refrigeran
 Sistem pipa refrigeran tersumbat

Pemecahan masalah

Perhatian Pastikan untuk mematikan saklar daya sebelum menyambung atau melepas konektor, atau komponen bisa
rusak.

Apakah muncul
YA
ketika daya diputar ke ON?

Fasa kabel transmisi antara unit


NO indoor dan outdoor salah.
TIDAK
Sambung dengan benar kabel
transmisi antara unit indoor dan
Apakah sambungan outdoor.
kabel transmisi dan pipa TIDAK
antara unit indoor dan Cocokkan sambungan kabel
outdoor cocok? transmisi dan pipa antara unit
indoor dan outdoor.
YA

Apakah kadar
TIDAK
refrigeran benar? isi ulang refrigeran dengan jumlah
yang benar setelah pemulihan
refrigeran dan pengeringan vakum.
YA
CHECK 7
Periksa penyumbatan pada sistem
pipa refrigeran.

CHECK 7 Lihat halaman 158.

151 Service Diagnosis


Troubleshooting by Remote Controller SiMT281416E

CHECK 1 Pemeriksaan Termistor

Termistor
Jika penyebab masalah terkait dengan termistor, maka termistor harus diperiksa sebelum mengubah
PCB.

Untuk informasi lebih lanjut tentang termistor, lihat:


 “Diagram Pengkabelan’’ pada halaman 162
 “Fungsi Termistor” pada halaman 27.

Ikhtisar Termistor
Tabel berikut berisi ikhtisar termistor:
Indoor

FHQ140-CA, Tabel (pada halaman


FCQ, FHQ-BV FAQ, FVQ FBQ Termistor berikutnya)
R1T R1T R1T Termistor udara hisap indoor 2
R2T R2T, R3T R2T Termistor penukar panas indoor 2
– – R3T Termistor udara buang indoor 3

Outdoor
RZR100-
RZR50- 140LVVM(4) Tabel (pada halaman
71LVVM(4) RZR100- Termistor
berikutnya)
140LUY1(4)
R1T R1T Termistor udara outdoor 2
R2T R2T Termistor udara buang 3
R3T R3T Termistor udara hisap 2
R4T R4T Termistor pipa pembagi penukar panas unit outdoor 2
R5T R5T Termistor penukar panas menengah 2
– R10T Termistor sirip radiasi 1

Pemeriksaan
Untuk memeriksa termistor, lakukan hal berikut:
Langkah Tindakan
1 Lepas termistor dari PCB
2 Baca suhu dan nilai resistor.
3 Periksa apakah nilai yang diukur sesuai dengan nilai dalam tabel di halaman berikutnya.

Service Diagnosis 152


SiMT281416E Troubleshooting by Remote Controller

Resistensi Termistor/ Karakteristik Suhu

Tabel 1 Tabel 2 Tabel 3


T°C k T°C k T°C k
-30 354.1 -30 361.7719 -30 3257.371
-25 259.7 -25 265.4704 -25 2429.222
-20 192.6 -20 196.9198 -20 1827.883
-15 144.2 -15 147.5687 -15 1387.099
-10 109.1 -10 111.6578 -10 1061.098
-5 83.25 -5 85.2610 -5 817.9329
0 64.10 0 65.6705 0 635.0831
5 49.70 5 50.9947 5 496.5712
10 38.85 10 39.9149 10 391.0070
15 30.61 15 31.4796 15 309.9511
20 24.29 20 25.0060 20 247.2696
25 19.41 25 20.0000 25 198.4674
30 15.61 30 16.1008 30 160.2244
35 12.64 35 13.0426 35 130.0697
40 10.30 40 10.6281 40 106.1517
45 8.439 45 8.7097 45 87.0725
50 6.954 50 7.1764 50 71.7703
55 5.761 55 5.9407 55 59.4735
60 4.797 60 4.9439 60 49.5180
65 4.014 65 4.1352 65 41.4168
70 3.375 70 3.4757 70 34.7923
75 2.851 75 2.9349 75 29.3499
80 2.418 80 2.4894 80 24.8586
85 2.060 85 2.1205 85 21.1360
90 1.762 90 1.8138 90 18.0377
95 1.513 95 1.5575 95 15.4487
100 1.304 100 1.3425 100 13.2768
105 1.128 105 1.1614 105 11.4395
110 0.9790 3SA48001 (AD87A001J) 110 9.8902
115 0.8527 115 8.5788
120 0.7450 120 7.4650
125 0.6530 125 6.5156
130 0.5741 130 5.7038
3PA61998L (AD92A057) 135 5.0073
140 4.4080
145 3.8907
150 3.4429
3SA48006 (AD87A001J)

153 Service Diagnosis


Troubleshooting by Remote Controller SiMT281416E

CHECK 2 Evaluasi Tekanan Tinggi yang tidak Normal


Tingkat tekanan tinggi yang tidak normal sebagian besar disebabkan oleh bagian kondensator. Isi
berikut disediakan oleh service engineer berdasarkan pemeriksaan lapangannya. Selanjutnya, nomor
dicantumkan dalam urutan tingkat pengaruhnya.

Dalam pendinginan

Item periksa (Kemungkinan penyebab) Penilaian


Apakah kipas unit outdoor berputar dengan normal? Pemeriksaan visual
Apakah penukar panas unit outdoor tersumbat? Pemeriksaan visual
Periksa apakah ada perbedaan suhu sebelum dan
Apakah ada penyumbatan sebelum atau setelah EV sesudah EV (kapiler).
(kapiler)? Periksa apakah unit katup utama EV beroperasi
(dengan suara, goncangan).
Periksa apakah ada perbedaan suhu sebelum dan
Apakah katup searah tersumbat? sesudah katup searah.
 Jika YA, katup searah tersumbat.
Apakah HPS normal? Periksa kontinuitas dengan menggunakan tester.
Apakah unit outdoor dipasang pada kondisi dimana Pemeriksaan visual
korsleting mudah terjadi?
Apakah panjang pipa 5 meter atau kurang? Pemeriksaan visual
Lakukan pengumpulan refrigeran dan pengeringan
Apakah udara masuk ke sistem refrigeran? vakum, kemudian tambahkan jumlah refrigeran yang
benar.
Lakukan pengumpulan refrigeran dan pengeringan
Apakah refrigeran kelebihan isi? vakum, kemudian tambahkan jumlah refrigeran yang
benar.

CHECK 3 Evaluasi Tekanan Rendah yang tidak Normal


Tingkat tekanan rendah yang tidak normal sebagian besar disebabkan oleh bagian evaporator. Isi
berikut disediakan berdasarkan pemeriksaan lapangan service engineer. Selanjutnya, nomor
dicantumkan dalam urutan tingkat pengaruhnya.

Dalam Pendinginan

Item periksa (Kemungkinan penyebab) Penilaian


Apakah kipas unit outdoor berputar dengan normal? Pemeriksaan visual
Apakah filter unit indoor tersumbat? Pemeriksaan visual
Periksa apakah ada perbedaan suhu sebelum dan
Apakah ada penyumbatan sebelum atau setelah EV sesudah EV (kapiler).
(kapiler)? Periksa apakah unit katup utama EV beroperasi
(dengan suara, goncangan).
Periksa apakah ada perbedaan suhu sebelum dan
Apakah katup searah tersumbat? sesudah katup searah.
 Jika YA, katup searah tersumbat.
Apakah unit outdoor dipasang pada kondisi dimana Pemeriksaan visual
korsleting mudah terjadi?
Lakukan pengumpulan refrigeran dan pengeringan
Apakah refrigeran kurang? vakum, kemudian tambahkan jumlah refrigeran yang
benar.

Service Diagnosis 154


SiMT281416E Troubleshooting by Remote Controller

CHECK 4 Pemeriksaan Transistor Daya


Penilaian berdasarkan pemeriksaan kontinuitas dengan menggunakan tester analog:
(1) Jangan menyentuh area pengisian (tegangan tinggi) selama 10 menit setelah memutar catu daya
ke OFF.
(2) Jika Anda harus menyentuh area tersebut, pastikan bahwa tegangan catu daya transistor daya 50
V atau kurang.
(3) Lepas konektor motor kipas unit outdoor.
Ketika kipas unit outdoor berputar melawan angin yang kuat, kondensator diisi dan sengatan listrik
bisa terjadi. Oleh karena itu, lepas konektor dari motor kipas unit outdoor setelah mengkonfirmasi
bahwa kipas unit outdoor berhenti.
(4) Sebelum mengukur kontinuitas, lepas sambungan antara kompresor dan transistor daya.
(5) Ukur kontinuitas dengan prosedur berikut.
[Penilaian] Normal jika hasil pemeriksaan kontinuitas adalah sebagai berikut.

Transistor daya (pada PCB)

C+— U Kontinuitas C- — U 
C+— V Kontinuitas  C- — V 
C+— W
Kontinuitas
C- — W 
U — C+  U — C- Kontinuitas
V — C+  V — C- Kontinuitas 
W — C+  W — C- Kontinuitas

Catatan:
 Jika ada kontinuitas, resistansi harus sama dengan setiap fasa.
 Jika tester digital digunakan untuk pengukuran kontinuitas,  dan kontinuitas dapat terbalik.

155 Service Diagnosis


Troubleshooting by Remote Controller SiMT281416E

CHECK 5 Pemeriksaan Sensor Tekanan


Ukur tegangan (DC) antara pin 1 dan 3 konektor.

PCB unit outdoor (A1P)


+5V

Konektor Merah

Red

Sensor tekanan
GND Black

Input A/D mikro- White


komputer

Ukur tegangan DC disini.

Tekanan yang Terdeteksi


PH
(kg/cm²) MPa
51.0 5.0

45.9 4.5

40.8 4.0

35.7 3.5

30.6 3.0
PH

25.5 2.5

20.4 2.0

15.3 1.5

10.2 1.0

5.1 0.5

0 0 PH = 1.38VH – 0.69
PH : Tekanan yang terdeteksi (MPa)
-5.1 -0.5 VH : Tegangan output (V)
-0.5 0 0.5 1 1.5 2 2.5 3 3.5 4
Tegangan output (VH) VDC

Grafik ini tersedia untuk sensor tekanan tinggi .

Service Diagnosis 156


SiMT281416E Troubleshooting by Remote Controller

CHECK 6 Pemeriksaan untuk Faktor Penyebab Operasi Basah

Mengacu pada Analisis Pohon Kesalahan (FTA) yang ditunjukkan berikut, identifikasi titik yang rusak.

Pemanas bak mesin rusak


Dwelling
refrigeran
Kompresor sering mulai dan berhenti

Pengisian refrigeran yang berlebihan  Lihat CHECK 9 .

Katup ekspansi Koil katup rusak


Defective valve coil  Apakah resistensi koil dan
elektronik rusak isolasi normal?
Defective
Tubuh katupvalve
rusak body
Kontrol derajat  Apakah karakteristik tegangan normal?
Sensor tekanan rendah rusak
super panas rusak  Apakah konektor tersambung dengan
Kontrol rusak Termistor pipa hisap rusak benar?
Operasi Apakah karakteristik resistensi termistor
Wetbasah
operation PCB unit outdoor rusak normal?
 Apakah nilai tekanan yang diperiksa oleh
Service Checker sesuai dengan
pengukuran sensor?

Evaporator  Apakah penukar panas tersumbat?


Dirty evaporator
kotor
Kapasitas
penguapan
menurun
Motor kipas rusak Apakah motor kipas dapat diputar
Decreased
Laju aliran dengan tangan?
Output Apakah resistensi koil motor dan
fanudara
airflow
kipas kipas isolasi normal?
PCB unit outdoor rusak
rate
menurun menurun
(termasuk pengaturan
kapasitas)

Catatan:
: Nilai referensi untuk derajat super panas yang akan digunakan dalam penilaian operasi basah
1. Derajat super panas pipa hisap: 4 ° C atau lebih 2. Derajat super panas pipa buang: 5 ° C atau
kurang
(Nilai di atas hanya digunakan untuk tujuan referensi. Meskipun dioperasikan dalam kisaran di atas,
operasi dapat normal dalam kondisi lain.)

157 Service Diagnosis


Troubleshooting by Remote Controller SiMT281416E

CHECK 7 Titik yang Tersumbat


Perbedaan suhu harus terjadi sebelum atau setelah titik tersumbat!

3 3

4 5

ACC COM P

Unit Indoor Unit Outdoor

Titik pemeriksaan Faktor pemeriksaan Penyebab Perbaikan


 Debu
Sekitar  Tersumbat embun
1 mekanisme Perbedaan suhu  Diameter pipa yang efektif Ganti katup ekspansi
ekspansi berkurang karena kontaminasi elektronik.
yang menempel, dll.

Semprot dengan gas


2 Aki Pembekuan  Tersumbat embun nitrogen, kemudian ganti
refrigeran.
 Debu
 Tersumbat embun
3 Distributor Perbedaan suhu  Diameter pipa yang efektif Ganti penukar panas
berkurang karena kontaminasi atau distributor.
yang menempel, dll.

4 Pipa lapangan Perbedaan suhu  Pipa rusak Ganti pipa.

Perbedaan suhu  Katup penghenti tidak Buka katup pengheni


5 Katup penghenti
sepenuhnya terbuka. sepenuhnya.

Service Diagnosis 158


SiMT281416E Troubleshooting by Remote Controller

CHECK 8 Pulsa Kecepatan Kipas

(1) Atur operasi ke OFF dan daya ke OFF. Lepas konektor (1).
(2) Periksa bahwa tegangan antara pin 3 – 4 sekitar 15 VDC.
(3) Periksa bahwa tegangan antara pin 1 – 4 sekitar 5 VDC.
(4) Biarkan operasi OFF dan daya OFF. Sambung konektor (1).
(5) Periksa apakah 2 pulsa (0 dan 5 VDC) merupakan output 4 kali di pin 1 - 4 ketika motor kipas
diputar 1 putaran dengan tangan.

Periksa Tindakan
PCB rusak
Jika NG di langkah 2 dan 3 Ganti PCB unit outdoor.
Hall IC rusak
Jika NG di langkah 5
Ganti motor kipas unit outdoor.
Jika OK di langkah 2, 3 dan 5 Ganti PCB unit outdoor.

PCB

(1)
1 Input pulsa perintah rotasi (0 dan 5 VDC)
2 0 VDC
3 15 VDC
4
5
6
7 250~320 VDC

Catatan:
1. Konektor dan PCB unit outdoor
Model Konektor untuk motor kipas (1) PCB
RZR50-100LVVM(4) X106A A1P
RZR125, 140LVVM(4) X106A, X107A A1P
RZR100-140LUY1(4) X106A, X107A A2P

159 Service Diagnosis


Troubleshooting by Remote Controller SiMT281416E

CHECK 9 Pemeriksaan untuk Pengisian Refrigeran yang Berlebihan


Sebagai kriteria untuk menilai apakah refrigeran diisi secara berlebihan atau tidak, lihat kondisi operasi
berikut.

<Diagnosis pengisian refrigeran yang berlebihan>


Dalam Pendinginan
(1) Karena tekanan tinggi naik akibat pengisian yang berlebihan, kontrol kelebihan beban dilakukan
dan kapasitas cenderung habis.
(2) Karena beban tekanan, suhu pipa buang kompresor rendah.
Pendinginan
Karena frekuensi kompresor
Tekanan tinggi menurun, tekanan rendah
meningkat
(Termistor penukar panas
menengah)
Tekanan rendah Frekuensi kompresor menurun
(Sensor tekanan) Frekuensi maksimum karena kontrol perlindungan
tekanan tinggi
Frekuensi kompresor
Frekuensi kompresor Frekuensi minimum
meningkat untuk mejaga
tekanan rendah. Derajat bukaan katup ekspansi
elektronik menurun karena
Katup ekspansi kontrol perlindungan basah.
elektronik
Derajat bukaan minimum

Derajat super panas hisap Derajat super panas hisap sekitar 0 derajat

Derajat super panas buang

(Derajat pengisian refrigeran yang berlebihan)


Tingkat yang cukup
Kelebihan isi

Service Diagnosis 160


SiMT281416E Troubleshooting by Remote Controller

Bagian 7
Lampiran
1. Diagram Pengkabelan ........................................................................... 162
1.1 Unit Indoor........................................................................................ 162
1.2 Unit Outdoor ..................................................................................... 169

161 Appendix
1. Diagram pengkabelan
1.1 Unit Outdoor
SiMT281416E Troubleshooting by Remote Controller

163 Appendix
SiMT281416E Troubleshooting by Remote Controller

165 Appendix
SiMT281416E Troubleshooting by Remote Controller

167 Appendix
SiMT281416E Troubleshooting by Remote Controller

1.2 Unit Ourdoor

169 Appendix
SiMT281416E Troubleshooting by Remote Controller

171 Appendix
SiMT281416E Troubleshooting by Remote Controller

Riwayat Revisi
Bulan/Tahun Versi Isi yang direvisi

11 / 2014 SiMT281416E Edisi pertama

173 Appendix
Peringatan  Produk Daikin diproduksi untuk ekspor ke berbagai negara di seluruh dunia. Sebelum membeli,
silahkan konfirmasi dengan importir, distributor dan/atau retailer resmi lokal Anda apakah
produk ini sesuai dengan standar yang berlaku, dan cocok untuk digunakan, di daerah tempat
produk akan digunakan. Pernyataan ini tidak dimaksudkan untuk mengecualikan, membatasi
atau memodifikasi penerapan peraturan lokal apapun.
 Mintalah installer atau kontraktor yang berpengalaman untuk memasang produk ini. Jangan
mencoba untuk memasang produk sendiri. Pemasangan yang salah dapat mengakibatkan
kebocoran air atau refrigeran, sengatan listrik, kebakaran atau ledakan.
 Gunakan komponen dan aksesori yang disediakan atau ditentukan oleh Daikin saja. Mintalah
installer atau kontraktor yang berpengalaman untuk memasang komponen dan aksesori
tersebut. Penggunaan komponen dan aksesori yang tidak asli atau pemasangan komponen
dan aksesori yang salah bisa menyebabkan kebocoran air atau refrigeran, sengatan listrik,
kebakaran atau ledakan.
 Baca panduan pengguna dengan teliti sebelum menggunakan produk ini. Panduan pengguna
menyediakan petunjuk keselamatan dan peringatan yang penting. Pastikan untuk mengikuti
petunjuk dan peringatan.
Jika ada pertanyaan, hubungi importir, distributor dan/atau retailer lokal Anda.

Peringatan tentang korosi produk


1. AC tidak boleh dipasang di area yang menghasilkan gas korosif, seperti gas asam atau gas bersifat basa .
2. Jika unit outdoor akan dipasang dekat dengan pantai laut, kontak langsung dengan angin laut harus dihindari. Jika Anda perlu
memasang unit outdoor dekat dengan pantai laut, hubungi distributor lokal Anda.

Dealer
Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com
c All rights reserved

 Spesifikasi, desain dan konten lainnya yang muncul dalam brosur ini berlaku sejak SiMT281416E
November 2014 namun dapat berubah tanpa pemberitahuan. 11/2014 AK