AC Paket
Tipe Floor Standing
Tipe Duct Connection
AC Paket
Tipe Floor Standing
Tipe Duct Connection
1. Pendahuluan ..............................................................................................vi
1.1 Perhatian Keselamatan........................................................................ vi
AC Paket
Tipe Floor Standing
Tipe Duct Connection
Seri FV(P)G(R), FD(R), RU(R)
— Pendingin Saja — ...................................... 1
Daftar Isi iv
Si41-901
i Daftar Isi
Si41-901
1.2 R-410A ............................................................................................. 109
2. Diagram Pengkabelan ........................................................................... 112
2.1 Unit Indoor (R-22) ............................................................................. 112
2.2 Unit Outdoor (R-22) ........................................................................... 115
2.3 Unit Indoor (R-410A) ......................................................................... 118
2.4 Unit Outdoor (R-410A)....................................................................... 121
3 Pengkabelan Lapangan ......................................................................................................... 124
3.1 R-22 ................................................................................................. 124
3.2 R-410A ............................................................................................. 130
AC Paket
Tipe Floor Standing
Tipe Duct Connection
Seri AFV(P)(R), AFD(R), RU(R)
— Pendingin Saja — .................................. 136
Daftar Isi iv
Si41-901
1.2 R-22: AFVP10-20KAY1
R-410A: AFVPR10-20NY1 ................................................................ 174
1.3 R-22: AFD05-20KAY1
R-410A: AFDR05-20NY1 .................................................................. 178
2. Unit Outdoor ........................................................................................... 186
2.1 R-22: RU05NY1S / RU06NY1S
R-410A: RUR05NY1S / RUR06NY1S................................................ 186
2.2 R-22: RU08-20NY1S
R-410A: RUR08-20NY1S.................................................................. 195
i Daftar Isi
Si41-901
2.4 Unit Outdoor (R-410A)....................................................................... 248
3 Pengkabelan Lapangan ......................................................................................................... 251
3.1 R-22 ................................................................................................. 251
3.2 R-410A ............................................................................................. 257
Daftar Isi iv
Si41-901 Pendahuluan
1. Pendahuluan
1.1 Perhatian Keselamatan
Perhatian Pastikan membaca perhatian keselamatan berikut sebelum melakukan pekerjaan
dan perbaikan.
Peringatan Item-item perhatian diklasifikasikan ke dalam “ Peringatan" dan" Perhatian".
Item "Peringatan" sangat penting karena mereka dapat menyebabkan kematian atau
cedera serius jika item tersebut tidak diikuti dengan benar. Item "Perhatian" juga dapat
menyebabkan kecelakaan serius dalam beberapa kondisi jika item tersebut tidak diikuti.
Oleh karena itu, pastikan untuk mematuhi semua item perhatian keselamatan yang
dijelaskan di bawah ini.
Tentang Piktogram
Simbol ini mengindikasikan item yang harus dilaksanakan dengan hati-hati.
Piktogram menunjukkan item yang harus diperhatikan.
Simbol ini mengindikasikan tindakan terlarang.
Item atau tindakan yang dilarang ditunjukkan dalam ilustrasi atau di dekat simbol.
Simbol ini mengindikasikan tindakan atau petunjuk yang harus dilakukan.
Petunjuk tersebut ditunjukkan dalam ilustrasi atau di dekat simbol.
Setelah pekerjaan perbaikan selesai, pastikan melakukan operasi pengujian untuk
memastikan bahwa peralatan beroperasi secara normal, dan menjelaskan kepada
pelanggan tentang perhatian pengoperasian produk.
Saat melepas pipa hisap atau pembuangan dari kompresor di bagian yang
dilas, terlebih dahulu memindahkan gas refrigeran ke tempat yang
berventilasi baik.
Jika ada gas yang tersisa di dalam kompresor, gas refrigeran atau mesin
refrigerasi akan mengeluarkan minyak saat pipa dilepas, dan dapat
menyebabkan cedera.
Jika gas refrigeran bocor selama pekerjaan perbaikan, beri ventilasi di area
tersebut. Gas refrigeran dapat menghasilkan gas beracun saat kontak
dengan nyala api.
vi
Pendahuluan Si41-901
Perhatian
Jangan memperbaiki komponen listrik dengan tangan basah.
Bekerja pada peralatan dengan tangan basah dapat menyebabkan sengatan
listrik.
vii
Si41-901 Pendahuluan
Peringatan
Pastikan menggunakan rangkaian listrik khusus untuk peralatan, dan
mengikuti standar teknis yang terkait dengan peralatan listrik tersebut,
peraturan pengkabelan internal, dan panduan petunjuk pemasangan ketika
melakukan pekerjaan listrik.
Kapasitas rangkaian listrik yang tidak memadai dan pekerjaan listrik yang
tidak tepat dapat menyebabkan sengatan listrik atau kebakaran.
Pastikan menggunakan kabel yang ditetapkan untuk pengkabelan antara unit indoor
dan outdoor. Buat sambungan dengan aman dan atur jalur kabel dengan benar
sehingga tidak ada gaya yang menarik kabel di terminal sambungan.
Sambungan yang tidak benar dapat menimbulkan panas berlebih atau kebakaran.
Ketika melakukan pengkabelan antara unit indoor dan outdoor, pastikan
penutup terminal tidak terangkat atau turun akibat kabel.
Jika penutup tidak terpasang dengan benar, bagian terminal sambungan
dapat menyebabkan sengatan listrik, menimbulkan panas berlebih atau
kebakaran.
Jangan merusak atau memodifikasi kabel listrik.
Kabel listrik yang rusak atau dimodifikasi dapat menyebabkan sengatan listrik
atau kebakaran. Menempatkan benda berat pada kabel listrik, dan memanasi
atau menarik kabel listrik dapat merusak kabel.
Jangan mencampur udara atau gas selain dari refrigeran yang ditentukan (R-
22) dalam sistem refrigeran.
Jika udara memasuki sistem refrigerasi, maka akan menimbulkan tekanan
tinggi yang berlebihan, yang menyebabkan kerusakan peralatan dan cedera.
Jika gas refrigeran bocor, pastikan menemukan titik kebocoran dan perbaiki
sebelum pengisian refrigeran. Setelah pengisian refrigeran, pastikan tidak
ada refrigeran yang bocor.
Jika titik kebocoran tidak dapat ditemukan dan pekerjaan perbaikan harus
dihentikan, pastikan untuk melakukan pump down dan menutup katup servis,
untuk mencegah gas refrigeran bocor ke dalam ruangan. Gas refrigeran
tidak berbahaya, tetapi dapat menghasilkan gas beracun saat kontak
dengan nyala api, seperti kipas dan pemanas lainnya, tungku dan kompor.
Ketika mengganti baterai koin di remote kontrol, pastikan membuang baterai
lama untuk mencegah agar anak kecil tidak menelannya.
Jika anak kecil menelan baterai koin tersebut, segera periksakan ke dokter.
Perhatian
Instalasi pemutus kebocoran diperlukan dalam beberapa kasus tergantung
pada kondisi tempat instalasi, untuk mencegah sengatan listrik.
Jangan memasang peralatan di tempat yang ada kemungkinan kebocoran
gas yang mudah terbakar.
Jika gas yang mudah terbakar bocor dan berada di sekitar unit, hal itu dapat
menyebabkan kebakaran.
Pastikan untuk memasang kemasan dan segel pada kerangka instalasi Hanya untuk unit
dengan benar. yang tak
Jika kemasan dan segel tidak terpasang dengan benar, air dapat memasuki terpisahkan
ruangan dan membasahi furnitur dan lantai.
1.1.3 Inspeksi setelah Perbaikan
Peringatan
Periksa untuk memastikan bahwa steker kabel listrik tidak kotor atau longgar,
kemudian masukkan steker ke stopkontak dengan aman.
Jika steker berdebu atau sambungannya longgar, dapat menyebabkan
sengatan listrik atau kebakaran.
Jika kabel listrik dan kawat timah memiliki goresan atau berubah bentuk,
pastikan untuk menggantinya.
Kabel dan kawat yang rusak dapat menyebabkan sengatan listrik,
menimbulkan panas berlebih atau kebakaran.
viii
Pendahuluan Si41-901
Peringatan
Jangan gunakan kabel listrik sambungan atau kabel perpanjangan, atau
berbagi stopkontak yang sama dengan peralatan listrik lainnya, karena dapat
menyebabkan sengatan listrik, menimbulkan panas berlebih atau kebakaran.
Perhatian
Periksa untuk melihat apakah komponen dan kabel telah terpasang dan
tersambung dengan benar, dan apakah sambungan di terminal telah disolder
atau dikerutkan dengan aman..
Pemasangan dan sambungan yang tidak tepat dapat menyebabkan
timbulnya panas
Jika platform atauberlebihan, kebakaran telah
rangka pemasangan atau sengatan listrik. harus diganti.
berkarat, maka
Platform atau rangka pemasangan yang berkarat dapat menyebabkan unit
jatuh, yang mengakibatkan cedera.
Periksa pembumian dan perbaiki jika peralatan tidak dibumikan dengan
benar. Pembumian yang tidak tepat dapat menyebabkan sengatan listrik.
ix
Si41-901
AC Paket
Tipe Floor Standing
Tipe Duct Connection
Seri FV(P)G(R), FD(R),
RU(R)
— Pendingin Saja —
Seri Model
Kelas 05 06 08 10 13 15 18 20
FVG 05B 06B 08B 10B — — — —
Unit
FVPG — — — 10B 13B 15B 18B 20B
Indoor
R-22 FD 05KA 06KA 08KA 10KA 13KA 15KA 18KA 20KA
Unit
RU 05N 06N 08N 10N 13N 15N 18N 20N
Outdoor
FVGR 05N 06N 08N 10N — — — —
Unit
FVPGR — — — 10N 13N 15N 18N 20N
Indoor
R-410A FDR 05N 06N 08N 10N 13N 15N 18N 20N
Unit
RUR 05N 06N 08N 10N 13N 15N 18N 20N
Outdoor
1
Si41-901
Bagian 1
Nama Model dan
Catu Daya
1. Nama Model, Catu Daya, dan Tata Nama ............................................... 3
1.1 Nama Model dan Catu Daya..................................................................3
1.2 Tata Nama ............................................................................................3
2. Tampilan Luar ............................................................................................ 4
2.1 R-22 .....................................................................................................4
2.2 R-410A .................................................................................................5
FVG R 05 B V1
Unit Outdoor
RU R 05 N Y1
2 Tampilan Luar
2.1 R-22
2.1.1 Unit Indoor
RU05NY1
RU06NY1 RU08NY1 RU10NY1
RU15NY1
RU13NY1 RU18NY1
RU20NY1
2.2 R-410A
2.2.1 Unit Indoor
RUR05NY1
RUR06NY1 RUR08NY1 RUR10NY1
RUR15NY1
RUR13NY1 RUR18NY1
RUR20NY1
Bagian 2
Fungsi
1. Fungsi....................................................................................................................7
1.1 Unit Indoor .............. .............................................................................................7
1.2 Unit Outdoor.... .....................................................................................................7
6 Fungsi
Si41-901 Fungsi
1. Fungsi
1.2 Unit Indoor
Item Fitur FVG-B FVPG-B FD-KA
FVGR-N FVPGR-N FDR-N
Kenyamanan Kecepatan kipas dapat — —
Kerja & servis diganti
Diisi awal hingga 7,5 m
Sirip PE untuk unit outdoor
Lain Tekanan statis eksternal (Diperlukan untuk (Diperlukan untuk
dapat disesuaikan — mengganti mengganti
puli) puli)
Catatan: : Fungsi ada.
— : Tidak ada fungsi
Fungsi 7
Si41-901
Bagian 3
Spesifikasi
1. Spesifikasi .................................................................................................. 9
1.1 R-22 .....................................................................................................9
1.2 R-410A ............................................................................................... 18
8 Spesifikasi
Si41-901 Spesifikasi
1. Spesifikasi
1.1 R-22
1.1.1 FVG-B
Tipe floor standing (Tipe direct air blow)
Unit Indoor FVG05BV1 FVG06BV1
Model
Unit Outdoor Y1 RU05NY1 RU06NY1
Catu daya 3 fase 50Hz 380-415V (4 kawat) 3 fase 50Hz 380-415V (4 kawat)
kW 14,7 17,6
*1. Kapasitas
Bersih Btu/h 50.000 60.000
pendinginan
*2. kcal/h 12.600 15.100
Unit indoor kW 0,5 0,5
Input daya Unit outdoor kW 5,0 5,9
Total kW 5,5 6,4
kW 15,2 18,1
*1. Kapasitas
Kotor Btu/h 51.800 61.800
pendinginan
*3. kcal/h 13.100 15.600
Unit indoor A 2,5 2,5
Arus yang mengalir
Unit outdoor A 8,2 9,6
Unit indoor FVG05BV1 FVG06BV1
Warna Putih gading Putih gading
Dimensi H×W×D mm 1.870×750×510 1.870×750×510
Tipe Cross fin coil atau Kumparan sirip silang (Fine Cross fin coil atau Kumparan sirip silang (Fine
Kumparan Baris×Tingkat×Jarak sirip louver fin and Hi-XA tube)
3×32×1,85 louver fin and Hi-XA tube)
3×32×1,85
Luas permukaan m² 0,409 0,409
Tipe Kipas siroko Kipas siroko
Penggerak Penggerak langsung 3 kecepatan Penggerak langsung 3 kecepatan
Output motor kW 0,375 0,375
Kipas
m³/min 42 42
Laju aliran udara
cfm 1.480 1.480
Tekanan statis eksternal mmH 2 O — —
Filter udara Jaring resin Jaring resin
Berat kg 90 90
Cairan mm 9,5 (Brazing/Pematrian) 9,5 (Brazing/Pematrian)
Sambung Gas mm 19,1 (Brazing/Pematrian) 19,1 (Brazing/Pematrian)
an pipa
Pembuangan mm PS 1B ulir dalam PS 1B ulir dalam
Remote control Berkabel — —
(opsi) Nirkabel — —
Unit outdoor Y1 RU05NY1 RU06NY1
Warna Putih gading Putih gading
Dimensi H×W×D mm 1.345×900×320 1.345×900×320
Tipe Cross fin coil atau Kumparan sirip silang (Fine Cross fin coil atau Kumparan sirip silang (Fine
Kumparan Baris×Tingkat×Jarak sirip louver fin and Hi-XA tube)
1×60×1,4 louver fin2×60×2,0
and Hi-XA tube)
Luas permukaan m² 1,172 1,134
Model Y1 JT170GA-Y1@K ZR72KC-TFD
Kompresor Tipe Tipe gulir tersegel kedap udara Tipe gulir tersegel kedap udara
Output motor kW 4,5 4,5
Model P47L11S×2 P47L11S×2
Tipe Baling-baling Baling-baling
Kipas Output motor W 65+90 90+90
m³/min 97 100
Laju aliran udara
cfm 3.430 3.530
Berat kg 92 105
Cairan mm 9,5 (Flare/Penyambung) 9,5 (Flare/Penyambung)
Sambung Gas mm 19,1 (Flare/Penyambung) 19,1 (Flare/Penyambung)
an pipa
Pembuangan mm 26,0 (Hole/Lubang) 26,0 (Hole/Lubang)
Pelindung panas untuk motor kipas outdoor. Saklar Pelindung panas untuk motor kipas outdoor. Saklar
tekanan tinggi. Saklar tekanan rendah. tekanan tinggi. Saklar tekanan rendah.
Perangkat pengaman Pelindung internal (kompresor, motor kipas indoor). Pelindung internal (kompresor, motor kipas indoor).
Pelindung fase terbalik. Sekering. Sekering.
Saklar panas (pipa pembuangan).
Tekanan desain Tinggi/Rendah MPa 3,0/1,6 3,0/1,6
Tahapan kapasitas % 100-0 100-0
Pengendalian refrigeran Pipa kapiler Pipa kapiler
Panjang standar m 5,0 5,0
Perpipaan Panjang maks. m 50 (Panjang setara 70m) 50 (Panjang setara 70m)
refrigeran
Selisih tinggi maks. m 30 30
Model R-22 R-22
Refrigeran
Pengisian kg 2,7 (Diisi untuk 7,5m) 3.3 (Diisi untuk 7,5m)
Oli Model Lihat pelat nama kompresor. Lihat pelat nama kompresor.
refrigeran Pengisian L 1.4 2.5
No. Gambar 4D063238E 4D063240F
Spesifikasi 9
Spesifikasi Si41-901
10 Spesifikasi
Si41-901 Spesifikasi
1.1.2 FVPG-B
Tipe floor standing (Tipe duct connection)
Unit Indoor FVPG10BY1 FVPG13BY1
Model
Unit Outdoor Y1 RU10NY1 RU13NY1
Catu daya 3 fase 50Hz 380-415V (4 kawat) 3 fase 50Hz 380-415V (4 kawat)
kW 29,3 35,2
*1. Kapasitas
Bersih Btu/h 100.000 120.000
pendinginan
*2. kcal/h 25.200 30.200
Unit indoor kW 1,0 1,6
Input daya Unit outdoor kW 10,4 13,3
Total kW 11,4 14,9
kW 30,3 36,8
*1. Kapasitas
pendinginan
Kotor Btu/h 103.400 125.600
*3. kcal/h 26.100 31.600
Unit indoor A 1,6 2,6
Arus yang mengalir
Unit outdoor A 17,6 21,7
Unit indoor FVPG10BY1 FVPG13BY1
Warna Putih gading Putih gading
Dimensi H×W×D mm 1.740×1.170×510 1.870×1.170×720
Tipe Cross fin coil atau Kumparan sirip silang (Fine Cross fin coil atau Kumparan sirip silang (Fine
Kumparan Baris×Tingkat×Jarak sirip louver fin and Hi-XA tube)
3×32×1,85 louver fin3×44×1,3
and Hi-XA tube)
Luas permukaan m² 0,707 0,94
Tipe Kipas siroko Kipas siroko
Penggerak Penggerak sabuk Penggerak sabuk
Output motor kW 1,5 2,2
Kipas
m³/min 80 120
Laju aliran udara
cfm 2.830 4.240
Tekanan statis eksternal mmH 2 O 15 15
Filter udara Jaring resin Jaring resin
Berat kg 150 180
Cairan mm 12,7 (Brazing/Pematrian) 12,7 (Brazing/Pematrian)
Sambung Gas mm 28,6 (Brazing/Pematrian) 28,6 (Brazing/Pematrian)
an pipa
Pembuangan mm PS 1B ulir dalam PS 1B ulir dalam
Remote control Berkabel – –
(opsi) Nirkabel – –
Unit outdoor Y1 RU10NY1 RU13NY1
Warna Putih gading Putih gading
Dimensi H×W×D mm 1.680×930×765 1.680×1.240×765
Tipe Cross fin coil atau Kumparan sirip silang (Fine Cross fin coil atau Kumparan sirip silang (Fine
Kumparan Baris×Tingkat×Jarak sirip louver fin and Hi-XA tube)
2×54×2,0 louver fin1×54×1,4
and Hi-XA tube)
Luas permukaan m² 2,112 2,481
Model Y1 ZR144KC-TFD ZRT162KC-TFD
Kompresor Tipe Tipe gulir tersegel kedap udara Tipe gulir tersegel kedap udara
Output motor kW 9,0 5,0+5,0
Model P68L11S P54M11S×2
Tipe Baling-baling Baling-baling
Kipas Output motor W 500 250+250
m³/min 190 210
Laju aliran udara
cfm 6.710 7.420
Berat kg 206 243
Cairan mm 12,7 (Flare/Penyambung) 12,7 (Flare/Penyambung)
Sambung Gas mm 28,6 (Brazing/Pematrian) 28,6 (Brazing/Pematrian)
an pipa
Pembuangan mm – –
Pelindung panas untuk motor kipas outdoor. Pelindung panas untuk motor kipas outdoor.
Perangkat pengaman Saklar tekanan tinggi. Saklar tekanan rendah. Saklar tekanan tinggi. Saklar tekanan rendah.
Pelindung internal (kompresor, motor kipas indoor). Pelindung internal (kompresor, motor kipas indoor).
Sekering. Sekering.
Tekanan desain Tinggi/Rendah MPa 3,0/1,6 3,0/1,6
Tahapan kapasitas % 100-0 100-50-0
Pengendalian refrigeran Pipa kapiler Pipa kapiler
Panjang standar m 5,0 5.0
Perpipaan Panjang maks. m 50 (Panjang setara 70m) 50 (Panjang setara 70m)
refrigeran
Selisih tinggi maks. m 30 30
Model R-22 R-22
Refrigeran
Pengisian kg 6.0 (Diisi untuk 7,5m) 5,0 (Diisi untuk 7.5m)
Oli Model Lihat pelat nama kompresor. Lihat pelat nama kompresor.
refrigeran Pengisian L 3,3 3,3
No. Gambar 4D063241D 3D063239F
Spesifikasi 11
Spesifikasi Si41-901
12 Spesifikasi
Si41-901 Spesifikasi
Spesifikasi 13
Spesifikasi Si41-901
1.1.3 FD-KA
Tipe duct connection high static pressure
Unit Indoor FD05KAY1 FD06KAY1
Model
Unit Outdoor Y1 RU05NY1 RU06NY1
Catu daya 3 fase 50Hz 380-415V (4 kawat) 3 fase 50Hz 380-415V (4 kawat)
kW 14,7 17,6
*1. Kapasitas
Bersih Btu/h 50.000 60.000
pendinginan
*2. kcal/h 12.600 15.100
Unit indoor kW 0,6 0,6
Input daya Unit outdoor kW 5,0 5,9
Total kW 5,6 6,5
kW 15,3 18,2
*1. Kapasitas
pendinginan
Kotor Btu/h 52.200 62.100
*3. kcal/h 13.200 15.700
Unit indoor A 1,0 1,0
Arus yang mengalir
Unit outdoor A 8,2 9,6
Unit indoor FD05KAY1 FD06KAY1
Warna Baja galvanis Baja galvanis
Dimensi H×W×D mm 450×900×850 450×1.130×850
Tipe Cross fin coil atau Kumparan sirip silang (Fine Cross fin coil atau Kumparan sirip silang (Fine
Kumparan Baris×Tingkat×Jarak sirip louver fin and Hi-XA tube)
2×24×2,0 louver fin2×24×2.0
and Hi-XA tube)
Luas permukaan m² 0,370 0,491
Tipe Kipas siroko Kipas siroko
Penggerak Penggerak sabuk Penggerak sabuk
Output motor kW 0,75 0,75
Kipas
m³/min 46 54
Laju aliran udara
cfm 1.620 1.910
Tekanan statis eksternal mmH 2 O 9 9
Filter udara – –
Berat kg 72 79
Cairan mm 9,5 (Brazing/Pematrian) 9,5 (Brazing/Pematrian)
Sambung Gas mm 19,1 (Brazing/Pematrian) 19,1 (Brazing/Pematrian)
an pipa
Pembuangan mm PS 3/4B ulir dalam PS 3/4B ulir dalam
Remote control Berkabel BRC1NU64 BRC1NU64
(opsi) Nirkabel – –
Unit outdoor Y1 RU05NY1 RU06NY1
Warna Putih gading Putih gading
Dimensi H×W×D mm 1.345×900×320 1.345×900×320
Tipe Cross fin coil atau Kumparan sirip silang (Fine Cross fin coil atau Kumparan sirip silang (Fine
Kumparan Baris×Tingkat×Jarak sirip louver fin and Hi-XA tube)
1×60×1,4 louver fin2×60×2,0
and Hi-XA tube)
Luas permukaan m² 1,172 1,134
Model Y1 JT170GA-Y1@K ZR72KC-TFD
Kompresor Tipe Tipe gulir tersegel kedap udara Tipe gulir tersegel kedap udara
Output motor kW 4,5 4,5
Model P47L11S×2 P47L11S×2
Tipe Baling-baling Baling-baling
Kipas Output motor W 65+90 90+90
m³/min 97 100
Laju aliran udara
cfm 3.430 3.530
Berat kg 92 105
Cairan mm 9,5 (Flare/Penyambung) 9,5 (Flare/Penyambung)
Sambung Gas mm 19,1 (Flare/Penyambung) 19,1 (Flare/Penyambung)
an pipa
Pembuangan mm 26,0 (Hole/Lubang) 26,0 (Hole/Lubang)
Pelindung panas untuk motor kipas outdoor. Saklar Pelindung panas untuk motor kipas outdoor. Saklar
tekanan tinggi. Saklar tekanan rendah. tekanan tinggi. Saklar tekanan rendah.
Perangkat pengaman Pelindung internal (kompresor, motor kipas Pelindung internal (kompresor, motor kipas indoor). Sekering.
indoor). Pelindung fase terbalik. Sekering.
Saklar panas (pipa pembuangan).
Tekanan desain Tinggi/Rendah MPa 3,0/1,6 3,0/1,6
Tahapan kapasitas % 100-0 100-0
Pengendalian refrigeran Pipa kapiler Pipa kapiler
Panjang standar m 5,0 5,0
Perpipaan Panjang maks. m 50 (Panjang setara 70m) 50 (Panjang setara 70m)
refrigeran
Selisih tinggi maks. m 30 30
Model R-22 R-22
Refrigeran
Pengisian kg 2,7 (Diisi untuk 7,5m) 3,3 (Diisi untuk 7,5m)
Oli Model Lihat pelat nama kompresor. Lihat pelat nama kompresor.
refrigeran Pengisian L 1,4 2,5
No. Gambar 4D063107E 4D063105H
14 Spesifikasi
Si41-901 Spesifikasi
Spesifikasi 15
Spesifikasi Si41-901
16 Spesifikasi
Si41-901 Spesifikasi
Spesifikasi 17
Spesifikasi Si41-901
1.2 R-410A
1.2.1 FVGR-N
Tipe floor standing (Tipe direct air blow)
Unit Indoor FVGR05NV1 FVGR06NV1
Model
Unit Outdoor Y1 RUR05NY1 RUR06NY1
Catu daya 3 fase 50Hz 380-415V (4 kawat) 3 fase 50Hz 380-415V (4 kawat)
kW 14,7 17,6
*1. Kapasitas
pendinginan Bersih Btu/h 50.000 60.000
*2. kcal/h 12.600 15.100
Unit indoor kW 0,5 0,5
Input daya Unit outdoor kW 5,0 5,9
Total kW 5,5 6,4
kW 15,2 18,1
*1. Kapasitas
pendinginan
Kotor Btu/h 51.800 61.800
*3. kcal/h 13.100 15.600
Unit indoor A 2,5 2,5
Arus yang mengalir
Unit outdoor A 8,2 9,6
Unit indoor FVGR05NV1 FVGR06NV1
Warna Putih gading Putih gading
Dimensi H×W×D mm 1.870×750×510 1.870×750×510
Tipe Cross fin coil atau Kumparan sirip silang (Fine Cross fin coil atau Kumparan sirip silang (Fine
Kumparan Baris×Tingkat×Jarak sirip louver fin and Hi-XA tube)
3×32×1,85 louver fin and Hi-XA tube)
3×32×1,85
Luas permukaan m² 0,409 0,409
Tipe Kipas siroko Kipas siroko
Penggerak Penggerak langsung 3 kecepatan Penggerak langsung 3 kecepatan
Output motor kW 0,245 0,245
Kipas
m³/min 42 42
Laju aliran udara
cfm 1.480 1.480
Tekanan statis eksternal mmH 2 O — —
Filter udara Jaring resin Jaring resin
Berat kg 90 90
Cairan mm 9,5 (Brazing/Pematrian) 9,5 (Brazing/Pematrian)
Sambung Gas mm 19,1 (Brazing/Pematrian) 19,1 (Brazing/Pematrian)
an pipa
Pembuangan mm PS 1B ulir dalam PS 1B ulir dalam
Remote control Berkabel — —
(opsi) Nirkabel — —
Outdoor unit Y1 RUR05NY1 RUR06NY1
Warna Putih gading Putih gading
Dimensi H×W×D mm 1.345×900×320 1.345×900×320
Tipe Cross fin coil atau Kumparan sirip silang (Fine Cross fin coil atau Kumparan sirip silang (Fine
Kumparan Baris×Tingkat×Jarak sirip louver fin and Hi-XA tube)
1×60×1,4 louver fin2×60×2,0
and Hi-XA tube)
Luas permukaan m² 1,172 1,134
Model Y1 JT170GA-P4Y1@S ZP72KCE-TFD
Kompresor Tipe Tipe gulir tersegel kedap udara Tipe gulir tersegel kedap udara
Output motor kW 4,5 4,5
Model P47L11S×2 P47L11S×2
Tipe Baling-baling Baling-baling
Kipas Output motor W 65+90 90+90
m³/min 97 100
Laju aliran udara
cfm 3.430 3.530
Berat kg 92 105
Cairan mm 9,5 (Flare/Penyambung) 9,5 (Flare/Penyambung)
Sambung Gas mm 19,1 (Flare/Penyambung) 19,1 (Flare/Penyambung)
an pipa
Pembuangan mm 26,0 (Hole/Lubang) 26,0 (Hole/Lubang)
Pelindung panas untuk motor kipas outdoor. Saklar Pelindung panas untuk motor kipas outdoor. Saklar
tekanan tinggi. Saklar tekanan rendah. tekanan tinggi. Saklar tekanan rendah.
Perangkat pengaman Pelindung internal (kompresor, motor kipas Pelindung internal (kompresor, motor kipas indoor).
indoor). Pelindung fase terbalik. Sekering. Sekering.
Saklar panas (pipa pembuangan).
Tekanan desain Tinggi/Rendah MPa 4,17/2,5 4,17/2,5
Tahapan kapasitas % 100-0 100-0
Pengendalian refrigeran Pipa kapiler Pipa kapiler
Panjang standar m 5.0 5,0
Perpipaan Panjang maks. m 50 (Panjang setara 70m) 50 (Panjang setara 70m)
refrigeran
Selisih tinggi maks. m 30 30
Model R-410A R-410A
Refrigeran
Pengisian kg 2,5 (Diisi untuk 7,5m) 3,5 (Diisi untuk 7,5m)
Oli Model Lihat pelat nama kompresor. Lihat pelat nama kompresor.
refrigeran Pengisian L 1,4 1,8
No. Gambar 4D063644B 4D063645D
18 Spesifikasi
Si41-901 Spesifikasi
Spesifikasi 19
Spesifikasi Si41-901
1.1.2 FVPGR-N
Tipe floor standing (Tipe duct connection)
Unit Indoor FVPGR10NY1 FVPGR13NY1
Model
Unit Outdoor Y1 RUR10NY1 RUR13NY1
Catu daya 3 fase 50Hz 380-415V (4 kawat) 3 fase 50Hz 380-415V (4 kawat)
kW 29,3 35,2
*1. Kapasitas
Bersih Btu/h 100.000 120.000
pendinginan
*2. kcal/h 25.200 30.200
Unit indoor kW 1,0 1,6
Input daya Unit outdoor kW 10,4 13,3
Total kW 11,4 14,9
kW 30,3 36,8
*1. Kapasitas
pendinginan
Kotor Btu/h 103.400 125.600
*3. kcal/h 26.100 31.600
Unit indoor A 1,6 2,6
Arus yang mengalir
Unit outdoor A 17,6 21,7
Unit indoor FVPGR10NY1 FVPGR13NY1
Warna Putih gading Putih gading
Dimensi H×W×D mm 1.740×1.170×510 1.870×1.170×720
Tipe Cross fin coil atau Kumparan sirip silang (Fine Cross fin coil atau Kumparan sirip silang (Fine
Kumparan Baris×Tingkat×Jarak sirip louver fin and Hi-XA tube)
3×32×1,85 louver fin3×44×1,3
and Hi-XA tube)
Luas permukaan m² 0,707 0,94
Tipe Kipas siroko Kipas siroko
Penggerak Penggerak sabuk Penggerak sabuk
Output motor kW 1,5 2,2
Kipas
m³/min 80 120
Laju aliran udara
cfm 2.830 4.240
Tekanan statis eksternal mmH 2 O 15 15
Filter udara Jaring resin Jaring resin
Berat kg 150 180
Cairan mm 12,7 (Brazing/Pematrian) 12,7 (Brazing/Pematrian)
Sambung Gas mm 28,6 (Brazing/Pematrian) 28,6 (Brazing/Pematrian)
an pipa
Pembuangan mm PS 1B ulir dalam PS 1B ulir dalam
Remote control Berkabel – –
(opsi) Nirkabel – –
Unit outdoor Y1 RUR10NY1 RUR13NY1
Warna Putih gading Putih gading
Dimensi H×W×D mm 1.680×930×765 1.680×1.240×765
Tipe Cross fin coil atau Kumparan sirip silang (Fine Cross fin coil atau Kumparan sirip silang (Fine
Kumparan Baris×Tingkat×Jarak sirip louver fin and Hi-XA tube)
2×54×2,0 louver fin1×54×1,4
and Hi-XA tube)
Luas permukaan m² 2,112 2,481
Model Y1 ZP137KCE-TFD ZPT166KCE-TFD
Kompresor Tipe Tipe gulir tersegel kedap udara Tipe gulir tersegel kedap udara
Output motor kW 9,0 5,0+5,0
Model P68L11S P54M11S×2
Tipe Baling-baling Baling-baling
Kipas Output motor W 500 250+250
m³/min 190 210
Laju aliran udara
cfm 6.710 7.420
Berat kg 206 243
Cairan mm 12,7 (Flare/Penyambung) 12,7 (Flare/Penyambung)
Sambung Gas mm 28,6 (Brazing/Pematrian) 28,6 (Brazing/Pematrian)
an pipa
Pembuangan mm – –
Pelindung panas untuk motor kipas outdoor. Saklar Pelindung panas untuk motor kipas outdoor. Saklar
Perangkat pengaman tekanan tinggi. Saklar tekanan rendah. tekanan tinggi. Saklar tekanan rendah.
Pelindung internal (kompresor, motor kipas indoor). Pelindung internal (kompresor, motor kipas indoor).
Sekering. Sekering.
Tekanan desain Tinggi/Rendah MPa 4,17/2,5 4,17/2,5
Tahapan kapasitas % 100-0 100-50-0
Pengendalian refrigeran Pipa kapiler Pipa kapiler
Panjang standar m 5,0 5,0
Perpipaan Panjang maks. m 50 (Panjang setara 70m) 50 (Panjang setara 70m)
refrigeran
Selisih tinggi maks. m 30 30
Model R-410A R-410A
Refrigeran
Pengisian kg 6,0 (Diisi untuk 7,5m) 4,5 (Diisi untuk 7,5m)
Oli Model Lihat pelat nama kompresor. Lihat pelat nama kompresor.
refrigeran Pengisian L 3,3 5,0
No. Gambar 4D063646B 3D063647C
20 Spesifikasi
Si41-901 Spesifikasi
Spesifikasi 21
Spesifikasi Si41-901
22 Spesifikasi
Si41-901 Spesifikasi
1.1.3 FDR-N
Tipe duct connection high static pressure
Unit Indoor FDR05NY1 FDR06NY1
Model
Unit Outdoor Y1 RUR05NY1 RUR06NY1
Catu daya 3 fase 50Hz 380-415V (4 kawat) 3 fase 50Hz 380-415V (4 kawat)
kW 14,7 17,6
*1. Kapasitas
Bersih Btu/h 50.000 60.000
pendinginan
*2. kcal/h 12.600 15.100
Unit indoor kW 0,6 0,6
Input daya Unit outdoor kW 5,0 5,9
Total kW 5,6 6,5
kW 15,3 18,2
*1. Kapasitas
pendinginan
Kotor Btu/h 52.200 62.100
*3. kcal/h 13.200 15.700
Unit indoor A 1,0 1,0
Arus yang mengalir
Unit outdoor A 8,2 9,6
Unit indoor FDR05NY1 FDR06NY1
Warna Baja galvanis Baja galvanis
Dimensi H×W×D mm 450×900×850 450×1.130×850
Tipe Cross fin coil atau Kumparan sirip silang (Fine Cross fin coil atau Kumparan sirip silang (Fine
Kumparan Baris×Tingkat×Jarak sirip louver fin and Hi-XA tube)
2×24×2,0 louver fin2×24×2,0
and Hi-XA tube)
Luas permukaan m² 0,370 0,491
Tipe Kipas siroko Kipas siroko
Penggerak Penggerak sabuk Penggerak sabuk
Output motor kW 0,75 0,75
Kipas
m³/min 46 54
Laju aliran udara
cfm 1.620 1.910
Tekanan statis eksternal mmH 2 O 9 9
Filter udara – –
Berat kg 72 79
Cairan mm 9,5 (Brazing/Pematrian) 9,5 (Brazing/Pematrian)
Sambung Gas mm 19,1 (Brazing/Pematrian) 19,1 (Brazing/Pematrian)
an pipa
Pembuangan mm PS 3/4B ulir dalam PS 3/4B ulir dalam
Remote control Berkabel BRC1NU64 BRC1NU64
(opsi) Nirkabel – –
Unit outdoor Y1 RUR05NY1 RUR06NY1
Warna Putih gading Putih gading
Dimensi H×W×D mm 1.345×900×320 1.345×900×320
Tipe Cross fin coil atau Kumparan sirip silang (Fine Cross fin coil atau Kumparan sirip silang (Fine
Kumparan Baris×Tingkat×Jarak sirip louver fin and Hi-XA tube)
1×60×1,4 louver fin2×60×2,0
and Hi-XA tube)
Luas permukaan m² 1,172 1,134
Model Y1 JT170G-P4Y1@S ZP72KCE-TFD
Kompresor Tipe Tipe gulir tersegel kedap udara Tipe gulir tersegel kedap udara
Output motor kW 4,5 4,5
Model P47L11S×2 P47L11S×2
Tipe Baling-baling Baling-baling
Kipas Output motor W 65+90 90+90
m³/min 97 100
Laju aliran udara
cfm 3.430 3.530
Berat kg 92 105
Cairan mm 9,5 (Flare/Penyambung) 9,5 (Flare/Penyambung)
Sambung Gas mm 19,1 (Flare/Penyambung) 19,1 (Flare/Penyambung)
an pipa
Pembuangan mm 26,0 (Hole/Lubang) 26,0 (Hole/Lubang)
Pelindung panas untuk motor kipas outdoor. Pelindung panas untuk motor kipas outdoor.
Saklar tekanan tinggi. Saklar tekanan rendah. Saklar tekanan tinggi. Saklar tekanan rendah.
Perangkat pengaman Pelindung internal (kompresor, motor kipas Pelindung internal (kompresor, motor kipas indoor).
indoor). Pelindung fase terbalik. Sekering. Sekering.
Saklar panas (pipa pembuangan).
Tekanan desain Tinggi/Rendah MPa 4,17/2,5 4,17/2,5
Tahapan kapasitas % 100-0 100-0
Pengendalian refrigeran Pipa kapiler Pipa kapiler
Panjang standar m 5,0 5,0
Perpipaan Panjang maks. m 50 (Panjang setara 70m) 50 (Panjang setara 70m)
refrigeran
Selisih tinggi maks. m 30 30
Model R-410A R-410A
Refrigeran
Pengisian kg 2,5 (Diisi untuk 7,5m) 3,5 (Diisi untuk 7,5m)
Oli Model Lihat pelat nama kompresor. Lihat pelat nama kompresor.
refrigeran Pengisian L 1,4 1,8
No. Gambar 4D063641B 4D063642D
Spesifikasi 23
Spesifikasi Si41-901
24 Spesifikasi
Si41-901 Spesifikasi
Spesifikasi 25
Spesifikasi Si41-901
26 Spesifikasi
Si41-901
Bagian 4
Remote Control
(Aksesori Pilihan)
1. Remote Control ........................................................................................................... 28
1.1 Aksesori Pilihan untuk FD-KA, FDR-N .....................................................................28
1.2 Aksesori Standar untuk FVG(R), FVPG(R)...............................................................34
1. Remote Control
1.1 Aksesori Pilihan untuk FD-KA, FDR-N
Aksesori pilihan
Model
Nama pilihan FD05KAY1 FD06KAY1 FD08KAY1 FD10KAY1 FD13KAY1 FD15KAY1 FD18KAY1 FD20KAY1
FDR05NY1 FDR06NY1 FDR08NY1 FDR10NY1 FDR13NY1 FDR15NY1 FDR18NY1 FDR20NY1
Remote control BRC1NU64
3D063005
Gbr. 1
1.1.2.1.Power (Daya)
Sistem dapat dihidupkan/dimatikan dengan menekan tombol POWER.
1.1.2.2.Skala suhu
Derajat °C atau °F dapat dipilih.
1.1.2.3.Pengaturan suhu
Pengaturan suhu dapat diatur dalam kisaran 18 – 30°C (64-86°F).
1.1.2.4.Pengaturan mode
Mode pengoperasian dapat diubah dengan menekan tombol MODE.
1.1.2.5.Pengaturan selanjutnya
Untuk mengonfirmasi pengaturan selama pemrograman, tekan tombol NEXT ini.
1.1.2.6.Lampu indikator kipas (hijau)
Lampu ini tetap menyala saat fungsi mode kipas diatur.
1.1.2.7.Lampu indikator dingin (hijau)
Lampu ini tetap menyala saat fungsi mode dingin diatur.
1.1.2.8.Lampu indikator kompresor 2 (hijau) (Tahap 2)
Lampu ini tetap menyala saat kompresor ke-2 berjalan.
1.1.2.9.Lampu indikator kompresor 1 (hijau) (Tahap 1)
Lampu ini tetap menyala saat kompresor ke-1 berjalan.
1.1.2.10. Sensor suhu
Angkur
Dinding
Loc
Pengunci
k
A
Gbr. 2. Braket pemasangan pada dinding.
Catatan: Remote control dapat dilepas menggunakan obeng datar dengan menekan pengunci dan
mendorongnya ke atas.
2. Angkat dan buka penutup, tarik ke atas untuk melepas. Lihat Gbr. 3.
untuk FD(R)05 10
UNIT INDOOR
C B A D
G Y1 Y2 O LC L N
(FAN) (COMP1) (COMP2) (LINE) (NEUTRAL)
REMOTE CONTROL BERKABEL.
Untuk FD(R)13 20
UNIT INDOOR
D B C A E
G Y1 Y2 O LC L N
(FAN)(COMP1) (COMP2) (LINE) (NEUTRAL)
REMOTE CONTROL BERKABEL.
1.1.5 Fitur
1. Power (Daya)
Sistem ini dapat dihidupkan/dimatikan dengan menekan tombol POWER.
2. Skala suhu
Derajat °C atau °F dapat dipilih.
3. Pengaturan suhu
Pengaturan suhu dapat diatur dalam kisaran 18 – 30°C (64 - 86°F).
4. Pengaturan mode
Mode pengoperasian dapat diubah dengan menekan tombol MODE.
MODE DINGIN P2 P3 P4
(TAHAP1) (TAHAP2) (PELEPAS BEBAN)
Truangan T setelan MATI MATI MATI
Tsetelan+1 Truangan Tsetelan+T HIDUP MATI HIDUP
Truangan Tsetelan+T+1 HIDUP HIDUP MATI
7. Memori permanen
Semua parameter disimpan dalam memori permanen setelah 15 detik.
8. Restart otomatis (pilihan)
Untuk Model restart otomatis (diatur dalam Program P5), selama gangguan daya, kontroler
akan secara otomatis melanjutkan operasinya.
Untuk Model restart non-otomatis, selama gangguan daya, pengguna harus menekan
tombol power untuk me-restart kontroler.
9. Watchdog
Terdapat sirkuit pengawas untuk mengawasi operasi mikroprosesor.
10.Perlindungan kelambatan kompresor
Setiap kali kompresor dimatikan, akan selalu ada kelambatan minimal 3 menit sebelum
kompresor dapat restart. Jika terjadi gangguan daya, sistem akan mengalami kelambatan
kompresor dalam kisaran 3-4 menit secara acak.
Kompresor tambahan dapat menyala setelah kompresor utama menyala sedikitnya 1
menit.
11.Pengalihan kompresor utama (pilihan)
Untuk model 2 kompresor (diatur dalam Program P4), ketika kedua kompresor mati,
kompresor tersebut akan mengalihkan tugas operasi antara utama dan pembantu pada
operasi berikutnya.
3PN10253-1A
12.Mode pemasang
Mode pemasang digunakan untuk memprogram semua parameter agar sesuai dengan
sistem yang digunakan. Ada 5 program.
Program Pengaturan Catatan
C = tampilan °C (default)
P1 Tampilan °C / °F
F = tampilan °F
1, 2, 3, atau 4 °C
P2 Pengaturan daerah mati (2, 3, 4, 5, 6, 7, atau 8°F)
(1°C default)
18 – 30°C (64 - 86°F)
P3 Titik penyetelan pendinginan
(18°C default)
minimum
1C – satu kompresor dengan pelepas beban
P4 Konfigurasi (default) 2C – 2 kompresor dengan fitur
pengalihan komp utama
P5 Restart otomatis 0 – Restart non-otomatis (default)
1 – Restart otomatis
Catatan: Jika tidak ada tombol yang ditekan dalam waktu 15 detik, maka akan keluar dari mode
pemasang secara otomatis dan pengaturan baru akan disimpan dalam memori.
Jika tombol “MODE” atau “POWER” ditekan pada periode pemrograman, maka
akan keluar dari mode pemasang, tetapi pengaturan tidak akan disimpan dalam
memori.
3PN10253-1A
FAN AUTO
COOL TI MER
HEAT SLEEP
MODE TEM P 1
SWP TEM P 2
1.2.2Prosedur
Operation Procedure PENYETELAN
Operasi
Untuk pemrograman SUHU, ikuti prosedur yang
OPERASI PENDINGINAN DAN KIPAS ditunjukkan di bawah ini.
Operasikan sesuai urutan berikut. 1) PENGATURAN SUHU
Tekan tombol TEMPERATURE SETTING dan
1) PEMILIH MODE OPERASI
program suhu pengaturan.
Tekan tombol OPERATION MODE SELECTOR
beberapa kali dan pilih MODE OPERASI pilihan Setiap kali tombol ini ditekan, suhu pengaturan
Anda sebagai berikut. naik 1°C.
• OPERASI KIPAS “FAN”
Setiap kali tombol ini ditekan, suhu pengaturan
• OPERASI PENDINGINAN “COOL” turun 1°C.
2) TOMBOL ON/OFF • Pengaturan dapat diprogram untuk operasi mode
Tekan tombol ON/OFF, lampu operasi menyala dingin.
dan sistem memulai OPERASI. Dan tekan lagi • Kisaran suhu pengaturan remote control.
sistem akan berhenti. OPERASI PENDINGINAN.....TEMP..... 18 hingga
30°C
3PN10376-1B
Bagian 5
Pengkabelan dan
Perpipaan Lapangan
1. Pengkabelan dan Perpipaan Lapangan ................................................. 36
1.1 R-22: FVG05-10BV1
R-410A: FVGR05-10NV1 ....................................................................36
1.2 R-22: FVPG10-20BY1
R-410A: FVPGR10-20NY1..................................................................40
1.3 R-22: FD05-20KAY1
R-410A: FDR05-20NY1 ......................................................................44
2. Unit Outdoor ............................................................................................. 54
2.1 R-22: RU05NY1 / RU06NY1
R-410A: RUR05NY1 / RUR06NY1 ......................................................54
2.2 R-22: RU08-20NY1
R-410A: RUR08-20NY1 ......................................................................65
ALIRAN UDARA
KELUAR
KABEL PENGHUBUNG
ANTARA UNIT
OUTDOOR DAN UNIT
INDOOR
FILTER UDARA
AIR FILTER
Gbr. 8 unit : mm
3PN10373-14B
TABEL 1
MODEL A (mm)
FVG(R)05, 06 780
FVG(R)08 960
FVG(R)10 1180
UNIT INDOOR
Gbr. 9
1.1.5 Pekerjaan Perpipaan Refrigeran
Peringatan Jangan mencampur gas selain refrigeran yang ditetapkan ke dalam siklus refrigeran.
Beri ventilasi area jika ada kebocoran refrigeran selama pemasangan.
Potong ujung penyumbat sebelum memanaskan pipa untuk melepas penyumbat Gbr.10
Pipa harus dipatri ke unit indoor. Periksa ukuran pipa refrigeran dengan TABEL 2 dan
Gbr.11
Gunakan hanya pipa tembaga tanpa sambungan.
Setelah mematri pipa, gunakan isolasi untuk mengamankan pipa dalam unit
(Gbr.12). Pasang isolasi sedekat mungkin dengan badan untuk menyerap
kondensasi kebocoran.
TABEL 2 Unit: mm
Ukuran pipa refrigeran
Pipa gas(O.D.) Pipa cairan(O.D.)
FVG(R)05, 06 19,1(3/4”) × t0,8, L=10 9,5(3/8”) × t0,7, L= 7
FVG(R)08 *22,2(7/8”) × t0,8, L=10 12,7(1/2”) × t0,8, L=8
FVG(R)10 *28,6(1 1/8”) × t0,8, L=12 12,7(1/2”) × t0,8, L=8
Catatan: 1. * Tingkat temper pipa adalah tipe 1/2H (tipe bahan ditentukan dalam JIS H3300)
2. Lihat Gbr.11 dengan mengacu pada L
PANJANG PENYISIPAN L
PENYUMBAT
KE UNIT OUTDOOR
UNIT INDDOR
PEMATRIAN
POTONG SEBELUM MEMANASKAN
Gbr. 10
PENJEPIT Gbr. 11
ISOLASI
PENGURASAN PIPA CAIRAN
TUTUP LUBANG
Gbr. 12
3PN10373-14B
ISOLASI PEMASANGAN
PERANGKAP PENGURASAN
PENYUMBAT PENGURASAN
Gbr. 13
3PN10373-14B
Pemutus sirkuit
EL. BOX
1 2 3 4 5 6
Lihat detail A
1 2 3 4
KABEL KOMUNIKASI
KE UNIT OUTDOOR H05VV-U5G
DETAIL A
PIPA
PENGU
RASAN UNIT OUTDOOR
3PN10373-3B
FILTER UDA RA
unit : mm
B
BAUT
BAUT
Gbr. 16
3PN10373-3B
Catatan: 1. * Tingkat temper pipa adalah tipe 1/2H (tipe bahan ditentukan dalam JIS H3300)
2. Lihat Gbr.18 dengan mengacu pada L
PANJANG PENYISIPAN L
PENYUMBAT
KE UNIT OUTDOOR
UNIT INDDOR
POTONG SEBELUM MEMANASKAN PEMATRIAN
Gbr. 17
Gbr. 18
PENJEPIT
ISOLASI
PENGURASAN PIPA CAIRAN
UNIT INDOOR
150 mm ATA U LEBIH DI DALA M
PIPA GAS DI LUAR
TUTUP LUBANG
Gbr. 19
Peringatan Pipa pengurasan harus dipasang untuk menghindari kerusakan air yang disebabkan oleh kebocoran
dan kondensasi.
Rakit unit seperti yang ditunjukkan pada Gbr.20.
Saluran keluar pipa pengurasan dapat dipasang pada kedua sisi kiri atau kanan. Penyumbat
pengurasan dapat dilepas dan ditempatkan pada kedua sisi kiri atau kanan juga.
Sangat perlu untuk menghubungkan pipa pengurasan baik ujung atas maupun bawah (Gbr.20).
Untuk hasil terbaik, upayakan untuk membuat pipa sependek mungkin. Miringkan pipa pada sudut utk
meningkatkan aliran udara (pipa pengurasan yg disediakan dengan unit indoor adalah PT 1 ulir dalam).
Isolasi pipa pengurasan dengan aman.
Sangat perlu untuk memberi perangkap pengurasan dalam saluran keluar pengurasan untuk
mengurangi tekanan negatif yang ada dalam unit dibandingkan dengan tekanan atmosfer di luar
saat unit beroperasi.
Jaga agar pipa tetap dalam kondisi selurus mungkin untuk memudahkan pembersihan dan
mencegah akumulasi kotoran dan puing.
Setelah menutup pipa pengurasan pada sisi berlawanan dari unit, bungkus pipa pengurasan secara
menyeluruh dengan isolasi (Gbr.20).
Tuang air ke dalam panci pengurasan untuk menguji kelancaran saluran air.
INDOOR
UNIT UNIT
INDOOR
PENGURASAN
UPPER DRAIN ATAS
SAMBUNGAN-T
T-JOINT
ISOLASI PEMASANGAN
PERANGKAP PENGURASAN
DRAIN TRAP
PENYUMBAT PENGURASAN
DASAR
BASE
LOWER BAWAH
PANCI PENGURASAN DRAIN PAN
ISOLASI DENGAN AMAN
Gbr. 20
3PN10373-3B
H05VV-U4 H05VV-U5
800
800atau lebih
or more RUANG SERVIS
Pipa saluran masuk udara
Pipa saluran masuk udara
Pipa saluran Pipa saluran keluar udara
keluar udara
RUANG SERVIS
1200 atau lebih 800 atau lebih
800 atau lebih
800 atau lebih
Sediakan jarak ruang yang cukup antara unit Gbr.23 Sediakan jarak ruang yang cukup antara unit dan
dinding sekitarnya untuk mencegah terjadinya
dan dinding sekitarnya untuk mencegah kontak.
terjadinya kontak.
Permukaan plafon
Permukaan plafon
720 at au lebih
A atau lebih
60 at au lebih
Model
Tipe Tipe Filter udara kembali
(tersedia di pasaran)
FD(R)05-06 FD(R)08-10
Pelat pendukung
< FD(R)05-10 > Panci peng
A 520 570 < FD(R)13-20 > (tersedia di pasaran)
Filter udara
kembali
(tersedia di (Lihat Gbr.23 dengan
pasaran) mengacu pada “A”) 3PN10228-1A
Unit: mm
FD(R)13, FD(R)15 FD(R)18, FD(R)20
A 1710 2070
B 1620 1980
C 1402 1762
D 1770 2220
(2) Pasang baut penyangga (ukuran M10 atau W3/8 diperlukan untuk FD(R)05-10 dan baut
ukuran M12 diperlukan untuk FD(R)13-20). Gunakan baut angkur atau aksesori lain yang
tersedia di pasaran untuk memperkuat plafon agar dapat menahan berat unit.
Gbr.24 Gbr.25
F 50
Baut angkur
Pelat plafon
D
< FD(R)05-10 >
850 < FD(R)05-10 >
G E
100 or
Pelat plafon
Baut penyangga
C
D
B
A
600
850
< FD(R)13-20 >
920
3PN10228-1A
<Untuk FD(R)13-20>
1. Amankan unit dan pelat pendukung (tersedia di pasaran) di empat tempat dengan
sekrup M12.
2. Pasang pelat pendukung ke baut penyangga (lihat Gbr. 26). Dengan menggunakan ring,
amankan dan kencangkan kedua mur atas dan bawah ke baut penyangga.
3. Atur ketinggian unit sesuai yang diinginkan.
4. Pastikan bahwa unit rata atau tidak miring (lihat Gbr. 27).
Atur unit dengan menggunakan waterpas. Jika terpasang secara tidak merata, air dapat
bocor dari unit.
Saat melakukan pengaturan, uji keempat sudut unit dengan waterpas atau gunakan selang
vinil yang diisi dengan air.
5. Amankan dan kencangkan mur atas.
Kotak saklar:
1. Lepas sekrup dan braketnya.
2. Balikkan braket sehingga posisinya terbalik, kemudian pasang kembali.
1 2
Peringatan Saat memasang kotak saklar ke unit utama, pastikan menggunakan sekrup yang
disertakan (M5x8).
Gbr.26
Ring Mur Sekrup melebar (M12)
(tersedia di Mur
(tersedia di (tersedia di pasaran)
pasaran) (tersedia di pasaran)
pasaran) SALAH (x)
Ring
(tersedia di pasaran)
Braket penggantung
Pelat pendukung
Lubang panci pengurasan ekstra (tersedia di pasaran)
Kencangkan (Mur ganda) kencangkan (mur ganda)
Gbr.27
Waterpas
Waterpas
Selang vinil
Selang vinil
Peringatan Jangan mencampur gas selain refrigeran yang ditetapkan ke dalam siklus refrigeran.
Beri ventilasi area jika ada kebocoran refrigeran selama pemasangan.
Pipa harus dipatri ke unit indoor. Periksa ukuran pipa refrigeran dengan TABEL 6 dan
Gbr.29.
Gunakan hanya pipa tembaga tanpa sambungan.
TABEL 6 Unit: mm
Ukuran pipa refrigeran
Model Pipa gas (O.D.) Pipa cairan (O.D.)
FD(R)05-06 19,1 (3/4'') × t0,8, L=10 9,5 (3/8'') × t0,7, L = 7
FD(R)08 *22,2 (7/8'') × t0,8, L=10 12,7 (1/2'') × t0,8, L = 8
FD(R)10-13 *28,6 (1 1/8'') × t0,8, L=10 12,7 (1/2'') × t0,8, L = 8
FD(R)15-20 *34,9 (1 3/8'') × t0,9, L=14 15,9 (5/8'') × t0,8, L = 8
Catatan: 1. * Tingkat temper pipa adalah tipe 1/2H (tipe bahan ditentukan dalam JIS H3300)
2. Lihat Gbr.29 dengan mengacu pada L
Lepaskan kardus dan potong ujung penyumbat sebelum memanaskan pipa untuk melepas
penyumbat (lihat Gbr.28).
Setelah mematri pipa seperti yang ditunjukkan pada Gbr.29, gunakan isolasi pengepas
untuk mengamankan pipa dalam unit (lihat Gbr.30, 31-1, dan 31-2).
Pasang isolasi pengepas sedekat mungkin dengan badan untuk menyerap kondensasi
kebocoran.
Jepit isolasi pengepas dengan penjepit g yang terlampir seperti ditunjukkan pada Gbr. 30.
Bungkus sambungan isolasi pengepas dengan plester (tersedia di pasaran), pastikan
bahwa tidak ada celah antar isolasi pengepas (lihat Gbr. 31-2).
Gbr.28 Gbr.29 Gbr.30
Potong sebelum Isolasi Pengepas1
memanaskan (terlampir) Penjepit 3
kardus Waterpas Panjang penyisipan L (terlampir)
Ke unit outdoor Unit indoor
Pipa gas Isolasi Pengepas2
Penyumbat (terlampir)
Pematrian
Pipa cairan
Isolasi pipa dengan menggunakan
isolasi pengepas (tersedia di pasaran)
1 ( 2 )
Isolasi Pengepas
Tutup lubang (tersedia di
Plester
pasaran)
(tersedia di
pasaran)
3PN10228-1A
Sla nt
Bagian bawah unit
Perangkap pengurasan
Penyumbat
Isolasi pemasangan pengurasan
A
Rencana pengurasan ekstra Isolasi dengan aman
(tersedia di pasaran)
Catatan: Remote control yang tersedia di pasaran dapat digunakan jika spesifikasinya kompatibel
dengan yang ditunjukkan dalam diagram pengkabelan dan bahan teknis.
Pasang kotak saklar di lokasi yang mudah diakses (lihat Gbr.35 pada halaman 50). Jika
tidak ada tempat di dekatnya yang dapat memberikan akses mudah ke kotak saklar,
pasang ke sisi saluran masuk udara unit indoor dengan menggunakan dua lubang pada
pelat samping.
Peringatan Jangan memasang kotak saklar pada sisi saluran keluar udara dari kumparan (penukar
panas), atau di bawah pipa sekitarnya untuk menghindari kebakaran atau sengatan
listrik yang disebabkan oleh kondensasi kebocoran.
Gbr.33
Kontaktor magnetis Kontaktor magnetis
Diagram pengkabelan
Penjepit Penjepit
(tersedia di pasaran) (tersedia di pasaran)
up
Terminal Terminal
Gbr.34
3PN10228-1A
Lihat Gbr. 36
Permukaan plafon Catu daya
Kotak saklar
Unit outdoor
Remote control
Gbr.35
Terminal bumi
Penjepit
penjepit
clamp
Catu daya
Kabel bumi
Kawat timah
Kabel bumi Terminal bumi
motor kipas
Fig.36
3PN10228-1A
Peringatan Sangat perlu untuk mengonfirmasi ketegangan per satu sabuk-V kipas setelah
beroperasi selama 24~28 jam dari operasi pertama.
3PN10228-1A
3) SUARA BISING AC
Suara “SHUH” aliran berkesinambungan terdengar saat sistem dalam
COOLING OPERATION.
Ini adalah suara dari gas refrigeran yang mengalir melalui kedua unit indoor dan
outdoor.
Suara “SHUH” yang terdengar pada awal atau sesaat setelah menghentikan
operasi.
Ini adalah suara bising dari refrigeran yang disebabkan oleh penghentian aliran dan
perubahan aliran.
3PN10228-1A
2) Jika sistem tidak beroperasi dengan benar kecuali untuk kasus yang disebutkan
di atas, dan tidak terbukti adanya malafungsi yang disebutkan di atas, selidiki
sistem sesuai dengan prosedur berikut.
Jika sistem tidak beroperasi sama sekali.
· Periksa apakah terjadi kegagalan daya. Tunggu hingga daya pulih.
· Periksa apakah sekering terbakar atau pemutus telah bekerja. Ganti sekering atau setel
pemutus.
2. Unit Outdoor
2.1 R-22: RU05NY1 / RU06NY1
R-410A: RUR05NY1 / RUR06NY1
2.1.1 Tindakan Pencegahan untuk Pemasangan
Periksa kekuatan dan tingkat dasar pemasangan sehingga unit tidak akan menimbulkan
getaran atau suara bising pengoperasian setelah dipasang.
Sesuai dengan gambaran fondasi pada Gbr. 1, pasang unit secara aman dengan
baut fondasi (Siapkan empat set baut, mur, dan ring fondasi M12 masing-masing
yang tersedia di pasaran.).
Lebih baik untuk menyekrup baut fondasi hingga panjangnya 20 mm dari
permukaan fondasi.
20
Sisi pengurasan
140 620 140
117
(345-355)
Tampilan bawah
219
289
350
(Unit : mm)
47
423
Lubang pengurasa
614
n
Gbr. 1
Panjang setara adalah nilai kehilangan tekanan karena sambungan L dan perangkap di
sepanjang pipa refrigeran yang dikonversi untuk pipa dengan ukuran yang sama, kemudian
ditambahkan.
Catatan: Tetapkan batas bawah untuk panjang pipa yang diperbolehkan ke 5 m. Jika lebih pendek dari
5 m, pipa akan menjadi kelebihan beban refrigeran, yang meningkatkan kemungkinan
malafungsi yang berhubungan dengan tekanan tinggi.
1PN09662A
1PN10560B
Ke belakang
Sekrup untuk
Celah Pipa pelat depan
penghubung Ke depan Ke samping
Celah
Bingkai bawah Sekrup pelat saluran keluar
Ke bawah
pipa
* Memotong dua celah memungkinkan untuk memasang seperti yang ditunjukkan
pada gambar di atas. (Gunakan gergaji besi untuk memotong celah.)
1PN09663A
1PN10561B
Jangan biarkan zat apa pun selain refrigeran yang ditentukan seperti udara bercampur ke dalam
sirkuit pendingin. PERHATIAN
Untuk memasang pipa penghubung ke unit dalam arah ke bawah, buat lubang keluaran paksa
dengan menembus area pusat di sekitar lubang keluaran paksa dengan menggunakan bor 6 mm.
Setelah membuat lubang keluaran paksa dengan menekan, sebaiknya memberikan lapisan
perbaikan pada pinggirnya, celah, dan sekitar permukaan sisi untuk mencegah karatan.
Gbr. 2
Gbr. 6
Gbr. 5
1PN09663A
1PN10561B
Penyumbatan, dll.
Baut
Bahan isolasi
Hati-hati dengan pipa, baut,
dan sambungan panel luar.
Tampilan atas
Penyegelan
Lubang
Bagian pembuangan keluaran
paksa
Perhatian Pastikan untuk mengisolasi setiap perpipaan lapangan sampai ke sambungan pipa di
dalam unit. Pipa yang terpapar dapat menyebabkan kondensasi atau luka bakar jika
tersentuh.
1PN09663A
1PN10561B
90˚ 2˚
19,1 mm 97,2~118,8 N • m 23,3 – 23,7
A
(3/4'')
Catatan: 1. Lihat “Panduan untuk Pemasangan” untuk petunjuk tentang cara melakukan penggantian
nitrogen. (Tanyakan ke dealer Anda.)
2. Nitrogen harus ditetapkan ke 0,02 MPa (cukup sehingga dapat dirasakan di kulit) dengan
katup penurun tekanan jika mematri saat memasukkan nitrogen ke dalam pipa.
Katup penurun tekanan
Perpipaan refrigeran Katup tangan
Bagian Pemlest
yang dipatri eran
Nitrogen
Nitrogen
1PN09663A
1PN10561B
<Uji kebocoran>
Pastikan untuk menggunakan gas nitrogen.
Beri tekanan udara pipa cairan dan gas hingga 1,6 Mpa (jangan memberi tekanan udara
lebih dari 1,6 Mpa).
Jika tekanan tidak turun dalam waktu 24 jam, sistem lulus uji. Jika tekanan turun, periksa
dari mana kebocoran nitrogen tersebut, dan cegah kebocoran.
<Uji kebocoran>
Pastikan untuk menggunakan gas nitrogen.
Beri tekanan udara pipa cairan dan gas hingga 2,5 Mpa (jangan memberi tekanan udara
lebih dari 2,5 Mpa).
Jika tekanan tidak turun dalam waktu 24 jam, sistem lulus uji. Jika tekanan turun, periksa
dari mana kebocoran nitrogen tersebut, dan cegah kebocoran.
<Pengeringan vakum>
Gunakan pompa vakum yang dapat mengosongkan hingga -100,7 kPa (-755 mmHg) atau
kurang.
1. Kosongkan pipa cairan, pipa gas, dan unit indoor hingga -100,7 kPa atau kurang dengan
menggunakan pompa vakum selama lebih dari 2 jam. Setelah menghentikan pompa
vakum, konfirmasi bahwa tekanan tidak naik selama lebih dari 1 jam. Jika tekanan naik,
sistem mungkin mengandung kelembapan di dalam atau mengalami kebocoran.
2. Berikut ini harus dilakukan jika ada kemungkinan kelembapan yang tersisa di dalam pipa.
(jika pemasangan pipa refrigeran dilakukan selama musim hujan atau selama periode
waktu yang lama, atau jika air hujan dapat masuk ke dalam pipa selama pemasangan,
kelembapan mungkin tetap ada di dalam pipa.)
Setelah mengosongkan pipa cairan, pipa gas, dan unit indoor selama lebih dari 2 jam, beri
tekanan udara pipa cairan, pipa gas, dan unit indoor hingga 0,05 MPa dengan gas nitrogen
(pemecahan vakum) dan kosongkan lagi pipa cairan, pipa gas, dan unit indoor hingga -
100,7 kPa atau kurang selama lebih dari 1 jam dengan menggunakan pompa vakum
(pengeringan vakum).
Jika pipa cairan, pipa gas, dan unit indoor tidak dapat dikosongkan hingga -100,7 kPa
atau kurang dalam waktu 2 jam, ulangi operasi pemecahan vakum dan pengeringan
vakum. Kemudian, konfirmasi bahwa tekanan tidak naik selama lebih dari 1 jam
setelah menghentikan pompa vakum.
1PN09663A
1PN10561B
Nitrogen
(Tertutup)
(Tertutup)
Port servis Port servis (Catatan.1)
(Sisi cairan) (Sisi gas)
Unit
indoor
Selang pengisian Pipa cairan
Pipa gas
Pengeringan vakum
Pengukur
Unit outdoor
tekanan
Katup Katup
penyumbat penyumbat
Liquid side Gas side
sisi cairan sisi gas
stop valve stop valve
(Tertutup) (Tertutup)
Port servis Port servis (Catatan.1)
(Sisi cairan) (Sisi gas)
Unit
indoor
Pompa Selang Pipa gas Pipa cairan
vakum pengisian
unit indoor
unit outdoor
Bentuk kabel dan pasang penutup dengan kuat sehingga penutup dapat disesuaikan dengan benar.
Kotak saklar
Kabel bumi
Ground
1 2 3 4 L1 L2 L3 N
Penjepit
(Aksesori)
Pelat
pemasangan
katup penyumbat
Kabel Kabel
antar catu
unit daya
<RU(R)05, 06NY1>
Perhatikan catatan yang disebutkan di bawah saat melakukan pengkabelan pada papan
terminal catu daya.
(Gunakan terminal gaya kerut bulat untuk sambungan ke papan terminal catu daya. Dalam hal
tidak dapat digunakan karena alasan yang tidak dapat dihindari, pastikan untuk mematuhi
instruksi berikut.)
Jangan menyambungkan kabel dari pengukur yang berbeda ke terminal catu daya
yang sama. (Kelonggaran pada sambungan dapat menyebabkan panas berlebih.)
Saat menyambungkan kabel dari pengukur yang sama, sambungkan sesuai dengan gambar di bawah ini.
Dalam pengkabelan, pastikan menggunakan kabel yang ditentukan, lakukan penyambungan
yang lengkap, dan atur kabel sehingga kekuatan luar tidak diberikan pada terminal.
Terminal gaya
kerut bulat
Kabel
listrik
Sambungkan Do not connect
Connect wires Jangan
Do not connect Jangan sambungkan
kabel dari wires
kabelofdari
of the same sambungkan kabel
wires of the same different
pengukur yang pengukur yang
gaugepada
to both side. dari pengukur
gauge yang
to one side. gauges.
berbeda.
sama
sama ke satu sisi.
kedua sisi.
Gunakan obeng yang benar untuk mengencangkan sekrup terminal. Obeng kecil dapat merusak kepala
sekrup dan mencegah mengencangkan yang tepat.
Mengencangkan sekrup terminal secara berlebihan dapat merusak sekrup.
Lihat bagan di bawah ini untuk torsi pengencangan untuk sekrup terminal.
Torsi pengencangan ( N • m)
M4 1,18 – 1,44
M5 2,39 – 2,91
Model Y1
L1 L2 L3 N L1 L2 L3 N
SEKERING SEKERING
SAKLAR UTAMA SAKLAR UTAMA
1 2 3 4 L1 L2 L3 N 1 2 3 4 L1 L2 L3 N
1 2 3 1 2 3 4
R R
S S
345-380V 345-380V
T1 T1
400-440V 400-440V
T2 T2
<Uji coba>
1. Pastikan katup penyumbat cairan dan gas terbuka.
<Pastikan untuk menutup penutup luar sebelum operasi, karena jika tidak melakukannya,
dapat menyebabkan sengatan listrik.>
2. Nyalakan remote control atau panel kontrol (lihat panduan pemasangan unit indoor).
3. Pastikan kompresor tidak mulai berputar dan berhenti selama uji coba dengan
mendengarkannya. Jika kompresor mulai berputar dan berhenti, segera hentikan mesin
dengan menggunakan remote control, dan periksa tingkat refrigeran, dll. Mungkin ada
semacam malafungsi.
Ada perangkat pengaman terhadap malafungsi pada kompresor.
Jika terjadi malafungsi (termasuk katup penyumbat tertutup atau tidak ada gas),
perangkat pengaman internal dapat diaktifkan karena suhu di kompresor meningkat.
Setelah ini terjadi, unit tidak akan dapat dijalankan hingga suhu pada kompresor
menurun (antara 30 menit dan 2 jam), tetapi ini tidak berarti mesin rusak. Pastikan unit
tidak dijalankan tanpa gas karena katup penyumbat tertutup atau kebocoran gas.
<Sisi gas>
Arah bukaan
<Sisi cairan>
Arah bukaan
1PN09663A
1PN10561B
20
(Lihat Gbr. 7)
1. Dalam kasus tipe RU(R)08N atau lebih, produk ini tidak dapat ditopang dengan empat sudut.
2. Ini diperlukan dalam kasus tipe RU(R)08N atau lebih.
3. Pusat produk
1 2
3 2 3
Fig. 7
(Lihat Gbr. 8)
1. Titik baut fondasi (15dia.:4 posisi)
2. Kedalaman produk
3. Lebar kaki penopang
Model A B
RU(R)08, 10N 930 792
RU(R)13, 15, 18, 20N 1240 1102
765
>66
(Unit : mm)
Gbr. 8
Perhatian Siapkan parit drainase di sekitar fondasi untuk mengalirkan air limbah dari seluruh unit. Saat
memasang unit di plafon, pastikan dasarnya tahan air dan pastikan pula memiliki kekuatan
yang cukup.
1PN09895C
1PN105464-1C
Ukuran perpipaan refrigeran dan panjang perpipaan yang diperbolehkan serta selisih
ketinggian.
Ukuran perpipaan refrigeran Panjang perpipaan yang
(Diameter luar x Ketebalan diperbolehkan (Antara unit
Outdoor unit Selisih ketinggian maks.
minimum) outdoor dan unit indoor)
(Antara unit outdoor dan
Pipa gas unit indoor)
Pipa cairan Panjang pipa Panjang
(tipe 1/2H)
(tipe O) (mm) sebenarnya setara
(mm)
Panjang setara adalah nilai hilangnya tekanan karena sambungan L dan perangkap di
sepanjang pipa refrigeran yang dikonversi untuk pipa dengan ukuran yang sama, kemudian
ditambahkan.
Catatan: Tetapkan batas bawah untuk panjang pipa yang diperbolehkan ke 5 m. Jika lebih pendek dari
5 m, pipa akan menjadi kelebihan beban refrigeran, yang meningkatkan kemungkinan
malafungsi yang berhubungan dengan tekanan tinggi.
Bagian
cekung
SAMBUNGAN BAWAH
(Lihat Gambar)
1. Pipa aksesori sisi gas (1)
2. Pipa aksesori sisi gas (2)
3. Pipa aksesori sisi gas (3)
4. Pipa aksesori sisi gas (4)
Peringatan Pastikan untuk menggunakan pipa aksesori saat menyambungkan perpipaan refrigeran.
Pastikan bahwa perpipaan lapangan tidak bersentuhan dengan pipa lainnya, panel bawah
atau depan.
Pastikan untuk melindungi perpipaan lapangan dengan isolasi, untuk mencegah
perpipaan lapangan bersentuhan dengan selubung).
1PN09895C
1PN10564-1C
Poros Penutup
Gbr. 9
Gbr. 10
1PN09896C
1PN10565-1C
Perhatian Pastikan untuk mengisolasi setiap perpipaan lapangan sampai ke sambungan pipa di
dalam unit. Pipa yang terpapar dapat menyebabkan kondensasi atau luka bakar jika
tersentuh.
1PN09896C
1PN10565-1C
Catatan: 1. Lihat “Panduan untuk Pemasangan” untuk petunjuk tentang cara melakukan penggantian nitrogen.
(Tanyakan ke dealer Anda.)
2. Nitrogen harus ditetapkan ke 0,02 MPa (cukup sehingga dapat dirasakan di kulit) dengan
katup penurun tekanan jika mematri saat memasukkan nitrogen ke dalam pipa.
Katup penurun tekanan
Perpipaan refrigeran
Bagian yang Pemlest Katup tangan
dipatri eran
Nitrogen Nitrogen
Perhatian Unit diperiksa apakah mengalami kebocoran oleh produsen. Konfirmasi apakah katup sisi cairan dan sisi
gas sudah ditutup dengan rapat sebelum uji kebocoran dan pengeringan vakum. Pastikan untuk
melakukan uji kebocoran dan pengeringan vakum dengan menggunakan port servis katup penyumbat sisi
cairan dan katup penyumbat sisi gas.
<Uji kebocoran>
Pastikan untuk menggunakan gas nitrogen.
Beri tekanan udara pipa cairan dan gas hingga 1,6 Mpa (jangan memberi tekanan udara lebih dari
1,6 Mpa).
Jika tekanan tidak turun dalam waktu 24 jam, sistem lulus uji. Jika tekanan turun, periksa dari mana
kebocoran nitrogen tersebut, dan cegah kebocoran.
<Uji kebocoran>
Pastikan untuk menggunakan gas nitrogen.
Beri tekanan udara pipa cairan dan gas hingga 2,5 Mpa (jangan memberi tekanan udara lebih dari
2,5 Mpa).
Jika tekanan tidak turun dalam waktu 24 jam, sistem lulus uji. Jika tekanan turun, periksa dari mana
kebocoran nitrogen tersebut, dan cegah kebocoran.
Port servis
Katup penyumbat
sisi cairan
Port servis
Katup penyumbat
sisi gas
1PN09896C
1PN10565-1C
<Pengeringan vakum>
Gunakan pompa vakum yang dapat mengosongkan hingga -100,7 kPa (-755 mmHg) atau
kurang.
1. Kosongkan pipa cairan, pipa gas, dan unit indoor hingga -100,7 kPa atau kurang dengan
menggunakan pompa vakum selama lebih dari 2 jam. Setelah menghentikan pompa
vakum, konfirmasi bahwa tekanan tidak naik selama lebih dari 1 jam. Jika tekanan naik,
sistem mungkin mengandung kelembapan di dalam atau mengalami kebocoran.
2. Berikut ini harus dilakukan jika ada kemungkinan kelembapan yang tersisa di dalam pipa.
(jika pemasangan perpipaan refrigeran dilakukan selama musim hujan atau selama
periode waktu yang lama, atau jika air hujan dapat masuk ke dalam pipa selama
pemasangan, kelembapan mungkin tetap ada di dalam pipa.)
Setelah mengosongkan pipa cairan, pipa gas, dan unit indoor selama lebih dari 2 jam, beri
tekanan udara pipa cairan, pipa gas, dan unit indoor hingga 0,05 MPa dengan gas nitrogen
(pemecahan vakum) dan kosongkan lagi pipa cairan, pipa gas, dan unit indoor hingga -
100,7 kPa atau kurang selama lebih dari 1 jam dengan menggunakan pompa vakum
(pengeringan vakum).
Jika pipa cairan, pipa gas, dan unit indoor tidak dapat dikosongkan hingga -100,7 kPa
atau kurang dalam waktu 2 jam, ulangi operasi pemecahan vakum dan pengeringan
vakum. Kemudian, konfirmasi bahwa tekanan tidak naik selama lebih dari 1 jam
setelah menghentikan pompa vakum.
(Note.1) For RU(R)20N, connect the charge hose to service port of gas side stop valve
either (1) or (2).
UJI KEBOCORAN PENGERINGAN VAKUM
Regulator Pengukur Pengukur
Katup Katup tekanan Katup Katup
tekanan Unit penyumba Unit Liquid side
penyumbat
penyumba penyumbat
Liquid side outdoor
outdoor stop
sisivalv e
cairan t sisi gas stop valve
sisi cairan
t sisi gas
(Tertutup) (Tertutup)
Nitrogen
(Tertutup) (Tertutup)
(Close) (Close)
Port servis Port servis Port servis Port servis
(Sisi gas)(Cat.1) (Sisi cairan) (Sisi gas)(Cat..1) (Sisi cairan)
Unit Unit
indoor
Indo Pompa Selang pengisian Pipa cairan Pipa gas
Selang pengisian Pipa cairan Pipa gas or
vakum
Isolasi Pipa
Setelah menyelesaikan uji kebocoran dan pengeringan vakum, lakukan pengisolasian
perpipaan lapangan. Pertimbangkan poin berikut:
Pastikan untuk mengisolasi pipa cairan dan pipa gas. Tidak mengisolasinya dapat
menyebabkan kebocoran air.
Pastikan isolasi yang digunakan dapat bertahan pada suhu 80°C.
Jika ada kemungkinan bahwa kondensasi pada katup penyumbat dapat menetes ke
dalam unit indoor melalui celah pada isolasi dan pipa karena unit outdoor terletak lebih
tinggi dari unit indoor, dll., cegah kebocoran air dengan menyumbat sambungan, dll.
seperti yang ditunjukkan pada gambar di bawah.
Katup Katup
penyumbat sisi penyumbat sisi
gas (1) gas (2)
Katup penyumbat
sisi cairan
Katup Penyumbatan, dll.
penyumbat Katup penyumbat
sisi gas Penyumbatan, dll. sisi cairan
Perpipaan
lapangan
Perpipaan
Isolasi lapangan
Isolasi
<RU(R)08-18N> <RU(R)20N>
1PN09896C
1PN10565-1C
Indoor
unit
Weighing Charge hose Liquid pipe Gas pipe
instrument
Setelah menyelesaikan pengisian refrigeran tambahan, buka katup penyumbat sisi cairan dan
katup penyumbat sisi gas (Dalam kasus RU(R)20N, kedua katup sisi gas (1) dan (2)).
Jika tidak memerlukan pengisian refrigeran tambahan, buka katup penyumbat sisi cairan
dan katup sisi gas setelah menyelesaikan pengeringan vakum
(Menjalankan sistem dengan posisi katup tertutup dapat merusak kompresor.)
1PN09896C
1PN10565-1C
Kabel bumi
<RU(R)08-10N>
Bumi KE UNIT INDOOR
Memasang
lengan isolasi.
Pengkabelan antara
unit outdoor dan X1M
unit indoor L1 L2 L3 N
X2M
N
L1 L2 L3
1 2 3 4 4PN10042
5 6 -4
dan kabel bumi
Sekering
Terminal bumi
Bumi Kabel bumi
KE UNIT INDOOR <RU(R)13-20N>
<PEMASANGAN KABEL>
<PENYAMBUNGAN BUMI>
Bahan
1 2 3 Ring penutup
Penjepit resin penjepit
(Lainnya) Terminal gaya kerut
Bahan Notch
penjepit
Kabel Kabel bumi
1PN09896C
1PN10565-1C
<Pengambilan kabel>
Kabel listrik dan kabel pembumian dilewatkan dari lubang kabel listrik di samping, depan
(lubang knock) atau bingkai bawah (lubang knock).
Kabel transmisi dilewatkan dari lubang kabel (lubang knock) di bagian depan unit atau
dari lubang pipa.
1PN09896C
1PN10565-1C
UNIT OUTDOOR
L1 L2 L3 N 1 2 3 4 OUTDOOR UNIT
<RU(R)08 • 10N>
I UNIT INDOOR
1 2 3
L1 L2 L3 N
UTDOOR
OUNIT UNIT
OUTDOOR
1 2 3 4
<RU(R)08 • 10N>
1 2 3 4 I UNIT INDOOR
UNIT OUTDOOR
OUTDOOR UNIT
L1 L2 L3 N 1 2 3 4 5 6
<RU(R)13 • 15 • 18 • 20N>
1 2 3 4 5 UNIT INDOOR
1PN09896C
1PN10565-1C
Item yang
Apakah kabel sesuai dengan diperiksa
diagram pengkabelan
Pastikan tidak ada pengkabelan yang terlupakan dan tidak ada fase
Kabel catu daya yang terlewatkan atau fase terbalik.
Kabel antar unit Apakah unit dibumikan dengan benar?
Apakah ada sekrup pengikatan kabel yang longgar?
Kabel bumi Apakah resistensi isolasi sedikitnya 1M?
Gunakan mega-tester 500V saat mengukur isolasi.
* Jangan gunakan mega-tester untuk sirkuit yang bukan 220-240V.
Apakah ukuran perpipaan sudah benar?
Perpipaan refrigeran Apakah bahan isolasi untuk perpipaan terpasang dengan
aman? Apakah pipa cairan dan gas diisolasi
Apakah katup penyumbat untuk sisi cairan dan sisi gas terbuka?
Refrigeran tambahan Apakah Anda menuliskan refrigeran tambahan dan panjang perpipaan
refrigeran?
1PN09896C
1PN10565-1C
Uji coba
1. Pastikan katup penyumbat cairan dan gas terbuka.
< Pastikan untuk menutup penutup luar sebelum operasi, karena jika tidak melakukannya,
dapat menyebabkan sengatan listrik.>
2. Nyalakan remote control atau panel kontrol (lihat panduan pemasangan unit indoor).
3. Pastikan kompresor tidak mulai berputar dan berhenti selama uji coba dengan
mendengarkannya. Jika kompresor mulai berputar dan berhenti, segera hentikan mesin
dengan menggunakan remote control, dan periksa tingkat refrigeran, dll. Mungkin ada
semacam malafungsi.
Ada perangkat pengaman terhadap malafungsi pada kompresor.
Jika terjadi malafungsi (termasuk katup penyumbat tertutup atau tidak ada gas),
perangkat pengaman internal dapat diaktifkan karena suhu di kompresor meningkat.
Setelah ini terjadi, unit tidak akan dapat dijalankan hingga suhu pada kompresor
menurun (antara 30 menit dan 2 jam), tetapi ini tidak berarti mesin rusak. Pastikan unit
tidak dijalankan tanpa gas karena katup penyumbat tertutup atau kebocoran gas.
<Sisi gas>
Arah bukaan
< Sisi cairan>
Arah bukaan
1PN09896C
1PN10565-1C
Bagian 6
Fungsi dan Operasi
1. Garis Besar Fungsi .................................................................................. 80
1.1 Unit Indoor ............................................................................................80
1.2 Unit Outdoor .........................................................................................81
2. Bagan Alur Operasi.................................................................................. 82
2.1 Bagan Alur Operasi (FD(R)+RU(R)-N)..................................................82
3. Bagian Fungsional Listrik ........................................................................ 84
3.1 Unit Indoor (R-22) .................................................................................84
3.2 Unit Indoor (R-410A).............................................................................85
3.3 Unit Outdoor (R-22) .............................................................................. 86
3.4 Unit Outdoor (R-410A) .......................................................................... 86
4. Detail Fungsi ............................................................................................ 87
4.1 Spesifikasi Fungsional FVG(R) • FVPG(R) Unit Indoor...........................87
Unit (Output)
(Input) dooIndoor
r unit
(Fungsi)
Tombol MODE
Seri FD(R)
(Fungsi)
(Fungsi)
Time up 60S
Apakah perangkat
pengaman dalam Unit tidak ber
operasi.
kondisi normal? TIDAK
YA
K1R relai unit outdoor ON. K3R
relai unit indoor ON. Maka, K1R
dan K2R ON.
Pertimbanga
n termostat ON Termostat OFF
Termostat ON
K1M Mgs unit outdoor ON, maka
kompresor dan kipas outdoor
beroperasi.
<Kasus 2>
Apakah perangkat
pengaman dalam Unit tidak ber
operasi.
kondisi normal? TIDAK
YA
K1R relai unit outdoor ON. K3R
relai unit indoor ON. Maka, K1R
dan K2R ON.
Pertimbangan
termostat ON Termostat OFF
Termostat ON
K1M Mgs unit outdoor ON, maka
kompresor dan kipas outdoor
beroperasi.
3.1.1 FVG05-10BV1
Item Nama Simbol M odel
FVG05BV1 FVG06BV1 FVG08BV1 FVG10BV1
Kontroler Remote control berkabel P.C.B SDR4041102
1Fase 220-240V 1Fase 220-240V
Motor M1F 1Fase 220-240V 6P 375W
Motor 4P 550W 4P 375W
kipas Kapasitor penggerak C1R 7,55F 440VAC 185F 440VA C 105F 440VA C
Ruangan R1T NTC 6,8KW@25?
Termistor
Pembekuan R2T NTC 6,8KW@25?
Lainnya Transformator Tr 230V/13V 0,4A
3.1.2 FVPG10-20BY1
Model
Item Nama Simbol
FVPG10BY1 FVPG13BY1 FVPG15BY1 FVPG18BY1 FVPG20BY1
Kontroler Remote control berkabel P.C.B SDR4041103 SDR4041104
MET-T
3Fase MET-T 3Fase 220/380V 4P TFO-K 3Fase 380/415V 4P
Motor M1F
Motor 220/380V 3HP 5HP
kipas 4P
Kelebihan beban --- 2HP
3,6A 5A 8A
Ruangan R1T NTC 6,8KW@25?
Termistor
Pembekuan R2T NTC 6,8KW@25?
Lainnya Transformator Tr 230V/13V 0,4A
3.1.3 FD05-10KAY1
Item Nama Simbol M odel
FD05KAY1 FD06KAY1 FD08KAY1 FD10KAY1
Kontroler Remote control berkabel P.C.B BRC1NU64
Motor M1F TFO 3Fase 380/415V 6P 0,75kW IK 3Fase 400V 4P 1,5kW
Motor
Nilai pengaturan relai kelebihan K1M 1,8A 3,6A
kipas
Lainnya Saklarbeban
magnetis K1M CLK-15JT40-P6C(Model baru) CLK-15JT40-P6A(Model lama)
3.1.4 FD13-20KAY1
Item Nama Simbol M odel
FD13KAY1 FD15KAY1 FD18KAY1 FD20KAY1
Kontroler Remote control berkabel P.C.B BRC1NU64
Motor M1F TFO 3Fase 380/415V 6P 2,2Kw TFO 3Fase 380/415V 4P 3,7kW
Motor
Nilai pengaturan relai kelebihan K1M 5,0A 8,0A
kipas
Lainnya Saklarbeban
magnetis K1M CLK-15JT40-P6C(Model baru) CLK-15JT40-P6A(Model lama)
3.2.1 FVGR05-10NV1
Item Nama Simbol M odel
FVGR05NV1 FVGR06NV1 FVGR08NV1 FVGR10NV1
Kontroler Remote control berkabel P.C.B SDR4041102
1Fase 220-240V 1Fase 220-240V
Motor M1F 1Fase 220-240V 6P 375W
Motor 4P 550W 4P 375W
kipas Kapasitor penggerak C1R 7,55F 440VAC 185F 440VA C 105F 440VA C
Ruangan R1T NTC 6,8KW@25?
Termistor
Pembekuan R2T NTC 6,8KW@25?
Lainnya Transformator Tr 230V/13V 0,4A
3.2.2 FVPGR10-20NY1
Model
Item Nama Symbol
FVPGR10NY1 FVPGR13NY1 FVPGR15NY1 FVPGR18NY1 FVPGR20NY1
Kontroler Remote control berkabel P.C.B SDR4041103 SDR4041104
MET-T
3Fase MET-T 3Fase 220/380V 4P TFO-K 3Fase 380/415V 4P
Motor M1F
Motor 220/380V 3HP 5HP
kipas 4P
Kelebihan beban --- 2HP
3,6A 5A 8A
Ruangan R1T NTC 6,8KW@25?
Termistor
Pembekuan R2T NTC 6,8KW@25?
Lainnya Transformator Tr 230V/13V 0,4A
3.2.3 FDR05-10NY1
Item Nama Simbol M odel
FDR05NY1 FDR06NY1 FDR08NY1 FDR10NY1
Kontroler Remote control berkabel P.C.B BRC1NU64
Motor M1F TFO 3Fase 380/415V 6P 0,75kW IK 3Fase 400V 4P 1,5kW
Motor
Nilai pengaturan relai kelebihan K1M 1,8A 3,6A
kipas
Lainnya Saklarbeban
magnetis K1M CLK-15JT40-P6C(Model baru) CLK-15JT40-P6A(Model lama)
3.2.4 FDR13-20NY1
Item Nama Simbol M odel
FDR13NY1 FDR15NY1 FDR18NY1 FDR20NY1
Kontroler Remote control berkabel P.C.B BRC1NU64
Motor M1F TFO 3Fase 380/415V 6P 2,2kW TFO 3Fase 380/415V 4P 3,7kW
Motor
Nilai pengaturan relai kelebihan K1M 5,0A 8,0A
kipas
Lainnya Saklarbeban
magnetis K1M (
CLK-15JT40-P6C(Model (Sen
baru) CLK-15JT40-P6A(Model lama)
(Sen
in
Sore
w
Model
M odel
Item Nama Simbol
RU13NY1 RU15NY1 RU18NY1 RU20NY1
Kompresor Kompresor gulir M1C ZRT162KC-TFD ZRT216KC-TFD ZRT250KC-TFD ZRT288KC-TFD
Motor (Atas) M1F 8554MTA-A15S 8554MTA-A16S 8554NTA-A13S 220-240V 400W
Motor (Bawah) M2F 220-240V 6P 250W 220-240V 6P 300W 8554NTA-A13S 220-240V 400W
Motor
kipas Kapasitor penggerak C1R 10,05F 440VAC
Kapasitor penggerak C2R
Perlindung Saklar tekanan tinggi S1PH ACB-J311 OFF3,25MPa ON2,5MPa
an tekanan Saklar tekanan rendah S1PL LCB-JA19 OFF0,12MPa ON0,22MPa
Sekering F1U 5A 250V
K1M
Lainnya Kontaktor magnetis CLK-35J-P6 AC220-240V
K2M
Relai daya K1R LY2F AC220V (2C)
3.4 Outdoor Unit (R-410A)
3.4.1 RUR-NY1
Model
M odel
Item Nama Simbol
RUR05NY1 RUR06NY1 RUR08NY1 RUR10NY1
Kompresor Kompresor gulir M1C JT170GA-P4Y1@S ZR72KCE-TFD ZR108KCE-TFD ZR137KCE-TFD
Motor (Atas) M1F YFK-90-6 220-240V 6P 90W 8556PTA-A16S 220-240V 500W
YFK-65-6 YFK-90-6
Motor (Bawah) M2F ---
Motor 220-240V 6P 65W 220-240V 6P 90W
kipas Kapasitor penggerak C1R 6,05F 440VAC 12,05F 440VAC
Kapasitor penggerak C2R 6,05F 440VAC ---
Perlindung
Saklar tekanan tinggi S1PH PS80-03-0279 OFF3,3MPa ON2,55MPa ACB-J311 OFF3,25MPa ON2,5MPa
an tekanan LCB-JA191OFF-0,0
Saklar tekanan rendah S1PL LCB-JA19 OFF0,12MPa ON0,22MPa
3MPaON0,05MPa
Sekering F1U 5A 250V 10A 250V
Kontaktor magnetis K1M CLK-20J-P6 AC220-240V CLK-35J-P6 AC220-240V
Lainnya
Pelindung fase terbalik Q1RP RPJ-400V ---
Relai daya K1R LY2F AC220V (2C)
Model
Item Nama Simbol
RUR13NY1S RUR15NY1S RUR18NY1S RUR20NY1S
Kompresor Kompresor gulir M1C ZRT166KCE-TFD ZRT206KCE-TFD ZRT240KCE-TFD ZRT274KCE-TFD
Motor (Atas) M1F 8554MTA-A15S 8554MTA-A16S 8554NTA-A13S 220-240V 400W
Motor (Bawah) M2F 220-240V 6P 250W 220-240V 6P 300W 8554NTA-A13S 220-240V 400W
Motor
kipas Kapasitor penggerak C1R 10,05F 440VAC
Kapasitor penggerak C2R
Perlindung Saklar tekanan tinggi S1PH ACB-1UB32 OFF4,15MPa ON3,2MPa ACB-1UB69W OFF4,47MPa ON3,36MPa
an tekanan Saklar tekanan rendah S1PL LCB-JA135 OFF0,245MPa ON0.353MPa
Sekering F1U 5A 250V
Lainnya Kontaktor magnetis K1,2M CLK-35J-P6 AC220-240V
Relai daya K1R LY2F AC220V (2C)
4. Detail Fungsi
4.1. Spesifikasi Fungsional FVG(R) • FVPG(R) Unit Indoor
4.1.1 Gambar Konfigurasi Sistem
Konfigurasi sistem dasar meliputi sebagai berikut:
Motor kipas
Remote control
Termostat penukar panas
Komp. terus berjalan lebih dari 10 Kipas indoor pada kecepatan rendah, Sistem MATI
menit. dan
Perhatian Saat melakukan pemeliharaan dan catu daya harus dimatikan, pastikan untuk terlebih dahulu
MEMATIKAN saklar ON/OFF remote control.
Mematikan saklar catu daya saat saklar ON/OFF masih HIDUP sangat berbahaya karena
“fungsi reset otomatis kegagalan daya” akan menyebabkan kipas indoor langsung mulai
berputar, atau kipas unit outdoor secara otomatis mulai berputar tiga menit setelah catu daya
dihidupkan kembali.
Simbol Deskripsi
T/B Tidak berlaku
S1PL Saklar tekanan rendah
S1PH Saklar tekanan tinggi
Perangkat Q1 Saklar panas pipa pembuangan
pengaman Q1M Saklar panas motor kipas 1
Q2M Saklar panas motor kipas 2
F1C Kelebihan beban motor kipas
OL Output alarm
Tampilan 7 --- Tidak menunjukkan 7 segmen.
segmen Fr "Fr"menunjukkan 7 segmen.
Bagian 7
Pemecahan
Masalah
1. Inspeksi Pemeliharaan ............................................................................ 90
1.1 Peninjauan ............................................................................................90
2. Bagaimana Cara Menangani Permintaan Pemeliharaan ...................... 92
2.1 Bagan Alur ............................................................................................92
3. Pemecahan Masalah Menurut Kondisi Peralatan .................................. 93
3.1 Pemecahan Masalah Menurut Kondisi Peralatan ....................................93
3.2 Peralatan tidak Beroperasi .....................................................................94
3.3 Kipas Beroperasi, tetapi Kompresor tidak Beroperasi .............................96
3.4 Operasi Pendinginan Mulai, tetapi Langsung Berhenti ............................98
3.5 Setelah Peralatan Dimatikan, Tidak Bisa Langsung Dinyalakan Kembali100
3.6 Peralatan Beroperasi, tetapi tidak Memberikan Pendinginan ................. 101
3.7 Peralatan Mengeluarkan Kabut Putih ................................................... 102
3.8 Peralatan Menghasilkan Kebisingan Keras atau Getar.......................... 103
3.9 Peralatan Mengeluarkan Debu ............................................................. 104
Pemecahan Masalah 89
Inspeksi Pemeliharaan Si41-901
1. Inspeksi Pemeliharaan
1.1. Peninjauan
Pedoman Pedoman nilai operasi saat beroperasi dalam kondisi standar dengan menekan tombol uji coba
untuk Kondisi pada remote control adalah sebagaimana dijelaskan dalam tabel di bawah. RU(R)05 - 20N
Operasi digunakan sebagai contoh unit outdoor pada tabel.
Optimal
Hubungan antara Hal-hal yang terjadi yang dibandingkan dengan nilai normal dirangkum dalam tabel di
Status bawah ini. (Diukur selama 15 ~ 20 menit atau lebih setelah operasi dimulai)
Pengoperasian AC
dan Tekanan / Arus
yang Mengalir Saat pendinginan
Status AC Tekanan Tekanan Arus yang
Rendah Tinggi Mengalir
Pengotoran FiIter Udara Lebih rendah Lebih rendah Lebih rendah
Hubung Singkat Udara Saluran Lebih rendah Lebih rendah Lebih rendah
Masuk/Keluar Unit Indoor
Pengotoran Sirip Unit Outdoor Lebih tinggi Lebih tinggi Lebih tinggi
Hubung Singkat Udara Saluran Lebih tinggi Lebih tinggi Lebih tinggi
Masuk/Keluar Unit Outdoor
Udara Tercampur dalam Refrigeran Lebih tinggi Lebih tinggi Lebih tinggi
Air Tercampur dalam Refrigeran *1 Lebih rendah Lebih rendah Lebih rendah
Kotoran Tercampur dalam Refrigeran *2 Lebih rendah Lebih rendah Lebih rendah
Kekurangan Refrigeran (Gas) Lebih rendah Lebih rendah Lebih rendah
Kompresi Tidak Memuaskan *1 Lebih tinggi Lebih rendah Lebih rendah
Catatan:1. *1 Air di refrigeran membeku di dalam pipa kapiler atau katup ekspansi, dan pada
dasarnya merupakan fenomena yang sama dengan pump down.
2. *2 Kotoran di refrigeran menyumbat filter di bagian dalam perpipaan, dan pada dasarnya
merupakan fenomena yang sama dengan pump down.
90 Pemecahan Masalah
Si41-901 Inspeksi Pemeliharaan
Kurva
Kejenuhan
Refrigeran
Pemecahan Masalah 91
Bagaimana Cara Menangani Permintaan Pemeliharaan Si41-901
Berjalan
Normal
(Pemeliharaan wajib)
92 Pemecahan Masalah
Si41-901 Pemecahan Masalah Menurut Kondisi Peralatan
Pemecahan Masalah 93
Pemecahan Masalah Menurut Kondisi Peralatan Si41-901
Kemungkinan Penyebab Sekering terputus atau kontak rusak pada sirkuit operasi
Saklar operasi atau titik kontak pada remote control rusak
Saklar tekanan tinggi atau saklar tekanan rendah rusak
Saklar magnetis motor kipas rusak
Aktivasi atau kesalahan relai arus berlebih motor kipas
Termostat suhu pipa pembuangan rusak (RU(R)05NY1 saja)
Isolasi pada sistem listrik tidak memadai
Titik kontak atau saklar magnetis untuk kompresor rusak
Kompresor rusak
Perlindungan fase terbalik (RU(R)05NY1 saja)
Pemecahan Masalah
Apakah saklar
Apakah saklar daya
daya
OFF atau
OFF
atau sekering
sekering YA
sirkuit kontrol Hidupkan saklar daya atau ganti
saklar daya terputus? sekering.
terputus?
TIDAK
Apakah ada YA
pemadaman listrik? Tunggu hingga daya kembali.
TIDAK
YA
Periksa motor kipas.
TIDAK
Apakah ada
kerusakan atau Kerusakan atau aktuasi perangkat
aktuasi perangkat YA pengaman seperti:
pengaman?
• Relai arus berlebih motor kipas
indoor
TI • Saklar termostat pipa pembuangan
DA • Saklar tekanan tinggi atau
K saklar tekanan rendah
• Perlindungan fase terbalik
Apakah
isolasi pada sistem TI
listrik memadai? DA Periksa bagian isolasi atau kabel
K yang rusak.
YA
Kabel listrik atau relai, dll. Periksa kabel listrik atau relai, dll.
kemungkinan rusak.
94 Pemecahan Masalah
Si41-901 Pemecahan Masalah Menurut Kondisi Peralatan
Kemungkinan Penyebab Sekering terputus atau kontak rusak pada sirkuit operasi
Saklar operasi atau titik kontak pada remote control rusak
Saklar tekanan tinggi atau saklar tekanan rendah rusak
Saklar magnetis motor kipas rusak
Aktivasi atau kesalahan saklar panas untuk motor kipas
Termostat suhu pipa pembuangan rusak (RU(R)05NY1 saja)
Isolasi pada sistem listrik tidak memadai
Titik kontak atau saklar magnetis untuk kompresor rusak
Kompresor rusak
Perlindungan fase terbalik (RU(R)05NY1 saja)
Pemecahan Masalah
TIDAK
YA
TIDAK
Apakahcatu
Apakah catudaya
dayake
ke kumparan
kumparan relai"K1R"
"K1R" YA
relai
dari dari unit indoor
unit indoor atau Relai K1R rusak dan ganti.
atau outdoor?
outdoor?
TIDAK
Apakah ada
kerusakan atau YA
Kerusakan atau aktuasi perangkat
aktuasi perangkat
pengaman seperti:
pengaman?
• Termostat perlindungan atau relai
arus berlebih motor kipas indoor
TID
AK • Saklar termostat pipa pembuangan
• Saklar tekanan tinggi atau
saklar tekanan rendah
• Perlindungan fase terbalik
Apakah
isolasi pada sistem TI Periksa bagian isolasi
listrik memadai? atau kabel yang rusak.
YA
Kabel listrik atau relai, dll. Periksa kabel listrik atau relai, dll.
kemungkinan rusak.
Pemecahan Masalah 95
Pemecahan Masalah Menurut Kondisi Peralatan Si41-901
Pemecahan Masalah
Perhatian Pastikan untuk mematikan saklar listrik sebelum menghubungkan atau
memutuskan sambungan, atau kerusakan komponen dapat terjadi.
YA
Apakah peralatan YA
beroperasi? Normal.
TIDAK
YA
96 Pemecahan Masalah
Si41-901 Pemecahan Masalah Menurut Kondisi Peralatan
Pemecahan Masalah
Perhatian Pastikan untuk mematikan saklar listrik sebelum menghubungkan atau
memutuskan sambungan, atau kerusakan komponen dapat terjadi.
YA
Apakah peralatan YA
beroperasi? Normal.
TIDAK
YA
Pemecahan Masalah 97
Pemecahan Masalah Menurut Kondisi Peralatan Si41-901
Pemecahan Masalah
TIDAK
Apakah filter
udara atau YA
Bersihkan filter udara
penukar panas
atau penukar panas indoor.
indoor kotor?
TIDAK
Apakah penukar YA
panas kotor? Pembersihan
penukar panas.
TIDAK
Kemungkinan penyebab
sebagai berikut:
* Pengisian refrigeran berlebihan · Setelah pengeringan
* Pencampuran udara dalam vakum, isikan
sistem refrigeran refrigeran dalam
* Saklar tekanan rusak jumlah yang benar.
* Kekurangan refrigeran Periksa saklar
LPS berhenti beroperasi
tekanan tinggi.
· Perbaiki kebocoran
refrigeran.
Setelah pengeringan
vakum, isikan
refrigeran dalam
jumlah yang benar.
Periksa saklar
tekanan rendah.
98 Pemecahan Masalah
Si41-901 Pemecahan Masalah Menurut Kondisi Peralatan
Pemecahan Masalah
TIDAK
Apakah filter
udara atau YA
Bersihkan filter udara
penukar panas
atau penukar panas indoor.
indoor kotor?
TIDAK
Apakah penukar YA
panas kotor? Pembersihan
penukar panas.
TIDAK
Kemungkinan penyebab
sebagai berikut:
* Pengisian refrigeran berlebihan · Setelah pengeringan
* Pencampuran udara dalam vakum, isikan
sistem refrigeran refrigeran dalam
* Saklar tekanan rusak jumlah yang benar.
* Kekurangan refrigeran Periksa saklar
LPS berhenti beroperasi tekanan tinggi.
· Perbaiki kebocoran
refrigeran.
Setelah pengeringan
Kemungkinan penyebab
vakum, isikan
refrigeran dalam
jumlah yang benar.
Periksa saklar
tekanan rendah.
Pemecahan Masalah 99
Pemecahan Masalah Menurut Kondisi Peralatan Si41-901
Pemecahan Masalah
Perhatian Pastikan untuk mematikan saklar listrik sebelum menghubungkan atau
memutuskan sambungan, atau kerusakan komponen dapat terjadi.
Putar saklar operasi pada
posisi ON dan OFF, lalu
tunggu pada sisi ON.
Apakah ada
perbedaan
suhu antara TIDA
saluran K Pipa kapiler tersumbat.
masuk dan
saluran keluar
pipa kapiler?
YA
Kompresor Periksa kompresor.
rusak
Pemecahan Masalah
Perhatian Pastikan untuk mematikan saklar listrik sebelum menghubungkan atau
memutuskan sambungan, atau kerusakan komponen dapat terjadi.
Ukur suhu udara hisap dan
udara pembuangan.
Selisih suhu = Suhu
udara hisap – Suhu
udara pembuangan.
TIDAK
TID
Kemungkinan penyebab sebagai berikut
AK
* Pemilihan model yang tidak tepat Pemasangan unit tambahan
* Pengaruh sinar matahari langsung harus dipertimbangkan.
Apakah ada embun
beku yang timbul di Apakah arus
sekitar port saluran YA pengoperasian lebih YA
masuk penukar kecil dari tingkat
panas unit indoor yang ditentukan?
atau port saluran
keluar pipa kapiler? TIDAK
TIDAK
Kekurangan gas mungkin
menimbulkan masalah.
Pemecahan Masalah
Perhatian Pastikan untuk mematikan saklar listrik sebelum menghubungkan atau
memutuskan sambungan, atau kerusakan komponen dapat terjadi.
YA
TID
AK
TID
AK
TIDAK
Pemecahan Masalah
Apakah kebisingan
menimbulkan getaran YA Sisipkan peredam getaran ke dalam
pada bagian bagian pemasangan, atau perkuat
pemasangan unit? bagian pemasangan.
Kebisingan kecil YA
TIDAK “shoo...” yang terus- Normal. Suara tersebut adalah
menerus selama kebisingan aliran gas (refrigeran) di
Apakah TIDAK operasi pendinginan bagian dalam unit AC.
perpipaan telah TIDAK Sisipkan bahan bantalan ke
diamankan?
penopang pipa seperti pelana.
Suara "shoo ..."
[Sisi catu daya] YA muncul sesaat setelah Normal. Kebisingan adalah suara
operasi dimulai atau yang timbul pada saat aliran gas
berhenti.
YA
(refrigeran) berubah atau berhenti.
Apakah kipas YA TIDAK
bersentuhan Bongkar dan hilangkan bagian
dengan komponen yang bersentuhan.
lainnya? Suara “shoo...” muncul
selama pendinginan
TIDAK atau setelah operasi Normal. Suara pengoperasian
YA perangkat pembuangan
berhenti.
Apakah pipa
YA TIDAK
bersentuhan Perbaiki perpipaan secara manual
dengan atau pasang bobot mati pada pipa.
selubung?
TIDAK
Apakah kebisingan
suara aliran YA
berasal dari katup Normal.
penurun tekanan
atau pipa kapiler? * Pengisian refrigerant
Berlebihan
TIDAK * Udara masuk ke dalam
sistem refrigerant Setelah pengeringan vakum,
* Kebisingan aliran akibat isi dengan refrigeran dalam
kekurangan refrigeran. jumlah yang benar.
(Berbunyi shoo...)
Pemecahan Masalah
Apakah masalah
timbul pada saat
operasi dimulai lagi YA
Debu yang terkumpul di bagian
setelah perpanjangan
dalam unit indoor tertiup keluar.
masa operasi?
Diperlukan pembersihan bagian
dalam unit indoor.
TIDAK
Apakah dilengkapi YA
Debu yang terkumpul di bagian
dengan filter udara?
dalam unit indoor tertiup keluar.
Diperlukan pembersihan bagian
TIDAK dalam unit indoor.
Bagian 8
Lampiran
1. Diagram Perpipaan ................................................................................ 106
1.1 R-22 ................................................................................................. 106
1.2 R-410A ............................................................................................. 109
2. Diagram Pengkabelan ........................................................................... 112
2.1 Unit Indoor (R-22) ............................................................................. 112
2.2 Unit Outdoor (R-22) .......................................................................... 115
2.3 Unit Indoor (R-410A) ......................................................................... 118
2.4 Unit Outdoor (R-410A) ...................................................................... 121
3. Pengkabelan Lapangan ......................................................................... 124
3.1 R-22 ................................................................................................. 124
3.2 R-410A ............................................................................................. 130
Lampiran 105
Diagram Perpipaan Si41-901
1. Diagram Perpipaan
1.1 R-22
FVG05BV1 / FD05KAY1 + RU05NY1
FVG06BV1 / FD06KAY1 + RU06NY1
C : 3D062796B
C : 3D062797B
106 Lampiran
Si41-901 Diagram Perpipaan
C : 3D062798B
C : 3D062799A
Lampiran 107
Diagram Perpipaan Si41-901
C : 3D062800A
C : 3D062801A
108 Lampiran
Si41-901 Diagram Perpipaan
1.2 R-410A
FVGR05NV1 / FDR05NY1 + RUR05NY1
FVGR06NV1 / FDR06NY1 + RUR06NY1
C : 3D063700
C : 3D063701
Lampiran 109
Diagram Perpipaan Si41-901
C : 3D063702
C : 3D063703
110 Lampiran
Si41-901 Diagram Perpipaan
C : 3D063705
Lampiran 111
Diagram Pengkabelan Si41-901
2. Diagram Pengkabelan
2.1 Unit Indoor (R-22)
2.1.1 FVG-B
FVG05BV1 / FVG06BV1 / FVG08BV1
SDR3010209-1C
FVG10BV1
SDR3010211-1D
112 Lampiran
Si41-901 Diagram Pengkabelan
2.1.2 FVPG-B
FVPG10BY1
SDR3010213-1D
SDR3010206-1F
Lampiran 113
Diagram Pengkabelan Si41-901
2.1.3 FD-KA
FD05KAY1 / FD06KAY1 / FD08KAY1 / FD10KAY1
3D062244F
3D062245F
114 Lampiran
Si41-901 Diagram Pengkabelan
3D061686B
RU06NY1
3D061685B
Lampiran 115
Diagram Pengkabelan Si41-901
RU08NY1
3D062781B
RU10NY1
3D062159B
116 Lampiran
Si41-901 Diagram Pengkabelan
3D062158B
Lampiran 117
Diagram Pengkabelan Si41-901
SDR3010210-1A
FVGR10NV1
SDR3010212-1B
118 Lampiran
Si41-901 Diagram Pengkabelan
2.3.2 FVPGR-N
FVPGR10NY1
SDR3010213-1D
SDR3010206-1F
Lampiran 119
Diagram Pengkabelan Si41-901
2.3.3 FDR-N
FDR05NY1 / FDR06NY1 / FDR08NY1 / FDR10NY1
3D062244F
3D062245F
120 Lampiran
Si41-901 Diagram Pengkabelan
3D061686B
RUR06NY1
3D061685B
Lampiran 121
Diagram Pengkabelan Si41-901
RUR08NY1
3D063584A
RUR10NY1
3D062159B
122 Lampiran
Si41-901 Diagram Pengkabelan
3D062158B
Lampiran 123
Pengkabelan Lapangan Si41-901
3 Pengkabelan Lapangan
3.1 R-22
3.1.1 FVG-B
FVG05BV1 + RU05NY1
FVG06BV1 + RU06NY1
C: 4D063521C
124 Lampiran
Si41-901 Pengkabelan Lapangan
FVG08BV1 + RU08NY1
FVG10BV1 + RU10NY1
4D063506B
Lampiran 125
Pengkabelan Lapangan Si41-901
3.1.2 FVPG-B
FVPG10BY1 + RU10NY1
4D063507A
126 Lampiran
Si41-901 Pengkabelan Lapangan
FVPG13BY1 + RU13NY1
FVPG15BY1 + RU15NY1
FVPG18BY1 + RU18NY1
FVPG20BY1 + RU20NY1
4D063508B
Lampiran 127
Pengkabelan Lapangan Si41-901
3.1.3 FD-KA
FD05KAY1 + RU05NY1
FD06KAY1 + RU06NY1
FD08KAY1 + RU08NY1
FD10KAY1 + RU10NY1
4D063510B
128 Lampiran
Si41-901 Pengkabelan Lapangan
FD13KAY1 + RU13NY1
FD15KAY1 + RU15NY1
FD18KAY1 + RU18NY1
FD20KAY1 + RU20NY1
4D063511A
Lampiran 129
Pengkabelan Lapangan Si41-901
3.2 R-410A
3.2.1 FVGR-N
FVGR05NV1 + RUR05NY1
FVGR06NV1 + RUR06NY1
4D063723
130 Appendix
Si41-901 Pengkabelan Lapangan
FVGR08NV1 + RUR08NY1
FVGR10NV1 + RUR10NY1
4D063722
Lampiran 131
Pengkabelan Lapangan Si41-901
3.2.2 FVPGR-N
FVPGR10NY1 + RUR10NY1
4D063507A
132 Appendix
Si41-901 Pengkabelan Lapangan
FVPGR13NY1 + RUR13NY1
FVPGR15NY1 + RUR15NY1
FVPGR18NY1 + RUR18NY1
FVPGR20NY1 + RUR20NY1
4D063508B
Lampiran 133
Pengkabelan Lapangan Si41-901
3.2.3 FDR-N
FDR05NY1 + RUR05NY1
FDR06NY1 + RUR06NY1
FDR08NY1 + RUR08NY1
FDR10NY1 + RUR10NY1
4D063510B
134 Appendix
Si41-901 Pengkabelan Lapangan
FDR13NY1 + RUR13NY1
FDR15NY1 + RUR15NY1
FDR18NY1 + RUR18NY1
FDR20NY1 + RUR20NY1
4D063511A
Lampiran 135
Si41-901
AC Paket
Tipe Floor Standing
Tipe Duct Connection
Seri AFV(P)(R), AFD(R),
RU(R)
— Pendingin Saja —
Seri Model
Kelas 05 06 08 10 13 15 18 20
AFV 05KA 06KA 08KA 10KA — — — —
Unit
AFVP — — — 10KA 13KA 15KA 18KA 20KA
Indoor
R-22
AFD 05KA 06KA 08KA 10KA 13KA 15KA 18KA 20KA
Unit
RU 05N 06N 08N 10N 13N 15N 18N 20N
Outdoor
AFVR 05N 06N 08N 10N — — — —
Unit
AFVPR — — — 10N 13N 15N 18N 20N
Indoor
R-410A AFDR 05N 06N 08N 10N 13N 15N 18N 20N
Unit
RUR 05N 06N 08N 10N 13N 15N 18N 20N
Outdoor
136
Si41-901
Bagian 1
Nama Model dan
Catu Daya
1. Nama Model, Catu Daya, dan Tata Nama ........................................... 138
1.1 Nama Model dan Catu Daya ............................................................. 138
1.2 Tata Nama........................................................................................ 138
2. Tampilan Luar ........................................................................................ 139
2.1 R-22 ................................................................................................. 139
2.2 R-410A ............................................................................................. 140
Unit Outdoor
RU R 05 N Y1 S
Untuk Thailand
Simbol catu daya
Y1 : 3 fase 50Hz 380-415V
Mengindikasikan kategori desain utama
Indikasi kapasitas
Refrigeran
Kosong : R-22
R : R-410A
Unit outdoor
RU : Pendingin saja
2. Tampilan Luar
2.1 R-22
2.1.1 Unit Indoor
RU13NY1S RU15NY1S
RU18NY1S
RU20NY1S
2.2 R-410A
2.2.1 Unit indoor
BRC1NU64S
(untuk AFDR)
2.2.3 Unit outdoor
RUR13NY1S RUR15NY1S
RUR18NY1S
RUR20NY1S
Bagian 2
Fungsi
1. Fungsi ............................................................................................................ 142
1.1 Unit Indoor ................................................................................................... 142
1.2 Unit Outdoor ................................................................................................ 142
Fungsi 141
Fungsi Si41-901
1. Fungsi
1.1 Unit Indoor
142 Fungsi
Si41-901
Bagian 3
Spesifikasi
1. Spesifikasi .............................................................................................. 144
1.1 R-22 ................................................................................................. 144
1.2 R-410A ............................................................................................. 153
Spesifikasi 143
Spesifikasi Si41-901
1. Spesifikasi
1.1 R-22
1.1.1 AFV-KA
Tipe floor standing (Tipe direct air blow)
Unit Indoor AFV05KAV1 AFV06KAV1
Model
Unit Outdoor Y1 RU05NY1S RU06NY1S
Catu daya 3 fase 50Hz 380V (4 kawat) 3 fase 50Hz 380V (4 kawat)
kW 14,7 17,6
*1. Kapasitas
Bersih Btu/h 50.000 60.000
pendinginan
*2. kcal/h 12.600 15.100
Unit indoor kW 0,5 0,5
Input daya Unit outdoor kW 5,0 5,9
Total kW 5,5 6,4
kW 15,2 18,1
*1. Kapasitas
Kotor Btu/h 51.800 61.800
pendinginan
*3. kcal/h 13.100 15.600
Unit indoor A 2,5 2,5
Arus yang mengalir
Unit outdoor A 8,2 9,6
Unit indoor AFV05KAV1 AFV06KAV1
Warna Putih gading Putih gading
Dimensi H×W×D mm 1.870×750×510 1.870×750×510
Tipe Cross fin coil atau Kumparan sirip silang (Fine Cross fin coil atau Kumparan sirip silang (Fine
Kumparan Baris×Tingkat×Jarak sirip louver fin and Hi-XA tube)
3×32×1,85 louver fin and Hi-XA tube)
3×32×1,85
Luas permukaan m² 0,409 0,409
Tipe Kipas siroko Kipas siroko
Penggerak Penggerak langsung 3 kecepatan Penggerak langsung 3 kecepatan
Output motor kW 0,375 0,375
Kipas
m³/min 42 42
Laju aliran udara
cfm 1.480 1.480
Tekanan statis mmH 2 O – –
Filter udara eksternal Jaring resin Jaring resin
Berat kg 90 90
Cairan mm 9,5 (Brazing/Pematrian) 9,5 (Brazing/Pematrian)
Sambungan Gas mm 19,1 (Brazing/Pematrian) 19,1 (Brazing/Pematrian)
pipa
Pembuangan mm PS 1B ulir dalam PS 1B ulir dalam
Remote control Berkabel – –
(opsi) Nirkabel – –
Unit outdoor Y1 RU05NY1S RU06NY1S
Warna Putih gading Putih gading
Dimensi H×W×D mm 1.345×900×320 1.345×900×320
Tipe Cross fin coil atau Kumparan sirip silang (Fine Cross fin coil atau Kumparan sirip silang (Fine
Kumparan Baris×Tingkat×Jarak sirip louver fin and Hi-XA tube)
1×60×1,4 louver fin2×60×2,0
and Hi-XA tube)
Luas permukaan m² 1,172 1,134
Model Y1 JT170GA-Y1@K ZR72KC-TFD
Kompresor Tipe Tipe gulir tersegel kedap udara Tipe gulir tersegel kedap udara
Output motor kW 4,5 4,5
Model P47L11S×2 P47L11S×2
Tipe Baling-baling Baling-baling
Kipas Output motor W 65+90 90+90
m³/min 97 100
Laju aliran udara
cfm 3.430 3.530
Berat Kg 92 105
Cairan Mm 9,5 (Flare/Penyambung) 9,5 (Flare/Penyambung)
Sambungan Gas Mm 19,1 (Flare/Penyambung) 19,1 (Flare/Penyambung)
pipa
Pembuangan mm 26,0 (Hole/Lubang) 26,0 (Hole/Lubang)
Pelindung panas untuk motor kipas outdoor. Saklar Pelindung panas untuk motor kipas outdoor. Saklar
tekanan tinggi. Saklar tekanan rendah. tekanan tinggi. Saklar tekanan rendah.
Perangkat pengaman Pelindung internal (kompresor, motor kipas Pelindung internal (kompresor, motor kipas indoor).
indoor). Pelindung fase terbalik. Sekering. Sekering.
Saklar panas (pipa pembuangan).
Tekanan desain Tinggi/Rendah MPa 3,0/1,6 3,0/1,6
Tahapan kapasitas % 100-0 100-0
Pengendalian refrigeran Pipa kapiler Pipa kapiler
Panjang standar m 5,0 5,0
Perpipaan Panjang maks. m 50 (Panjang setara 70m) 50 (Panjang setara 70m)
refrigeran
Selisih tinggi maks. m 30 30
Model R-22 R-22
Refrigeran
Pengisian kg 2,7 (Diisi untuk 7,5m) 3,3 (Diisi untuk 7,5m)
Oli Model Lihat pelat nama kompresor. Lihat pelat nama kompresor.
refrigeran Pengisian L 1,4 2,5
No. Gambar 4D063279E 4D063280F
144 Spesifikasi
Si41-901 Spesifikasi
Spesifikasi 145
Spesifikasi Si41-901
1.1.2 AFVP-KA
Tipe floor standing (Tipe duct connection)
Unit Indoor AFVP10KAY1 AFVP13KAY1
Model
Unit Outdoor Y1 RU10NY1S RU13NY1S
Catu daya 3 fase 50Hz 380V (4 kawat) 3 fase 50Hz 380V (4 kawat)
kW 29,3 35,2
*1. Kapasitas
pendinginan
Bersih Btu/h 100.000 120.000
*2. kcal/h 25.200 30.200
Unit indoor kW 1,0 1,6
Input daya Unit outdoor kW 10,4 13,3
Total kW 11,4 14,9
kW 30,3 36,8
*1. Kapasitas
Kotor Btu/h 103.400 125.600
pendinginan
*3. kcal/h 26.100 31.600
Unit indoor A 1,6 2,6
Arus yang mengalir
Unit outdoor A 17,6 21,7
Unit indoor AFVP10KAY1 AFVP13KAY1
Warna Putih gading Putih gading
Dimensi H×W×D mm 1.740×1.170×510 1.870×1.170×720
Tipe Cross fin coil atau Kumparan sirip silang (Fine Cross fin coil atau Kumparan sirip silang (Fine
Kumparan Baris×Tingkat×Jarak sirip louver fin and Hi-XA tube)
3×32×1,85 louver fin3×44×1,3
and Hi-XA tube)
Luas permukaan m² 0,707 0,94
Tipe Kipas siroko Kipas siroko
Penggerak Penggerak sabuk Penggerak sabuk
Output motor kW 1,5 2,2
Kipas
m³/min 80 120
Laju aliran udara
cfm 2.830 4.240
Tekanan statis eksternal mmH 2 O 15 15
Filter udara Jaring resin Jaring resin
Berat kg 150 180
Cairan mm 12,7 (Brazing/Pematrian) 12,7 (Brazing/Pematrian)
Sambungan Gas mm 28,6 (Brazing/Pematrian) 28,6 (Brazing/Pematrian)
pipa
Pembuangan mm PS 1B ulir dalam PS 1B ulir dalam
Remote control Berkabel – –
(opsi) Nirkabel – –
Unit outdoor Y1 RU10NY1S RU13NY1S
Warna Putih gading Putih gading
Dimensi H×W×D mm 1.680×930×765 1.680×1.240×765
Tipe Cross fin coil atau Kumparan sirip silang (Fine Cross fin coil atau Kumparan sirip silang (Fine
Kumparan Baris×Tingkat×Jarak sirip louver fin and Hi-XA tube)
2×54×2,0 louver fin1×54×1,4
and Hi-XA tube)
Luas permukaan m² 2,112 2,481
Model Y1 ZR144KC-TFD ZRT162KC-TFD
Kompresor Tipe Tipe gulir tersegel kedap udara Tipe gulir tersegel kedap udara
Output motor kW 9,0 5,0+5,0
Model P68L11S P54M11S×2
Tipe Baling-baling Baling-baling
Kipas Output motor W 500 250+250
m³/min 190 210
Laju aliran udara
cfm 6.710 7.420
Berat kg 206 243
Cairan mm 12,7 (Flare/Penyambung) 12,7 (Flare/Penyambung)
Sambungan Gas mm 28,6 (Brazing/Pematrian) 28,6 (Brazing/Pematrian)
pipa
Pembuangan mm – –
Pelindung panas untuk motor kipas outdoor. Saklar Pelindung panas untuk motor kipas outdoor. Saklar
Perangkat pengaman tekanan tinggi. Saklar tekanan rendah. tekanan tinggi. Saklar tekanan rendah.
Pelindung internal (kompresor, motor kipas indoor). Pelindung internal (kompresor, motor kipas indoor).
Sekering. Sekering.
Tekanan desain Tinggi/Rendah MPa 3,0/1,6 3,0/1,6
Tahapan kapasitas % 100-0 100-50-0
Pengendalian refrigeran Pipa kapiler Pipa kapiler
Panjang standar m 5,0 5,0
Perpipaan Panjang maks. m 50 (Panjang setara 70m) 50 (Panjang setara 70m)
refrigeran
Selisih tinggi maks. m 30 30
Model R-22 R-22
Refrigeran
Pengisian kg 6,0 (Diisi untuk 7,5m) 5,0 (Diisi untuk 7,5m)
Oli Model Lihat pelat nama kompresor. Lihat pelat nama kompresor.
refrigeran Pengisian L 3,3 3,3
No. Gambar 4D063281D 3D063282F
146 Spesifikasi
Si41-901 Spesifikasi
Spesifikasi 147
Spesifikasi Si41-901
148 Spesifikasi
Si41-901 Spesifikasi
1.1.3 AFD-KA
Tipe duct connection high static pressure
Unit Indoor AFD05KAY1 AFD06KAY1
Model
Unit Outdoor Y1 RU05NY1S RU06NY1S
Catu daya 3 fase 50Hz 380V (4 kawat) 3 fase 50Hz 380V (4 kawat)
kW 14,7 17,6
*1. Kapasitas
Bersih Btu/h 50.000 60.000
pendinginan
*2. kcal/h 12.600 15.100
Unit indoor kW 0,6 0,6
Input daya Unit outdoor kW 5,0 5,9
Total kW 5,6 6,5
kW 15,3 18,2
*1. Kapasitas
pendinginan
Kotor Btu/h 52.200 62.100
*3. kcal/h 13.200 15.700
Unit indoor A 1,0 1,0
Arus yang mengalir
Unit outdoor A 8,2 9,6
Unit indoor AFD05KAY1 AFD06KAY1
Warna Putih gading Putih gading
Dimensi H×W×D mm 450×900×850 450×1.130×850
Tipe Cross fin coil atau Kumparan sirip silang (Fine Cross fin coil atau Kumparan sirip silang (Fine
Kumparan Baris×Tingkat×Jarak sirip louver fin and Hi-XA tube)
2×24×2,0 louver fin2×24×2,0
and Hi-XA tube)
Luas permukaan m² 0,370 0,491
Tipe Kipas siroko Kipas siroko
Penggerak Penggerak sabuk Penggerak sabuk
Output motor kW 0,75 0,75
Kipas
m³/min 46 54
Laju aliran udara
cfm 1.620 1.910
Tekanan statis eksternal mmH 2 O 9 9
Filter udara – –
Berat kg 72 79
Cairan mm 9,5 (Brazing/Pematrian) 9,5 (Brazing/Pematrian)
Sambungan Gas mm 19,1 (Brazing/Pematrian) 19,1 (Brazing/Pematrian)
pipa
Pembuangan mm PS 3/4B ulir dalam PS 3/4B ulir dalam
Remote control Berkabel BRC1NU64S BRC1NU64S
(opsi) Nirkabel – –
Unit outdoor Y1 RU05NY1S RU06NY1S
Warna Putih gading Putih gading
Dimensi H×W×D mm 1.345×900×320 1.345×900×320
Tipe Cross fin coil atau Kumparan sirip silang (Fine Cross fin coil atau Kumparan sirip silang (Fine
Kumparan Baris×Tingkat×Jarak sirip louver fin and Hi-XA tube)
1×60×1,4 louver fin2×60×2,0
and Hi-XA tube)
Luas permukaan m² 1,172 1,134
Model Y1 JT170GA-Y1@K ZR72KC-TFD
Kompresor Tipe Tipe gulir tersegel kedap udara Tipe gulir tersegel kedap udara
Output motor kW 4,5 4,5
Model P47L11S×2 P47L11S×2
Tipe Baling-baling Baling-baling
Kipas Output motor W 65+90 90+90
m³/min 97 100
Laju aliran udara
cfm 3.430 3.530
Berat kg 92 105
Cairan mm 9,5 (Flare/Penyambung) 9,5 (Flare/Penyambung)
Sambungan Gas mm 19,1 (Flare/Penyambung) 19,1 (Flare/Penyambung)
pipa
Pembuangan mm 26,0 (Hole/Lubang) 26,0 (Hole/Lubang)
Pelindung panas untuk motor kipas outdoor. Saklar Pelindung panas untuk motor kipas outdoor. Saklar
tekanan tinggi. Saklar tekanan rendah. tekanan tinggi. Saklar tekanan rendah.
Perangkat pengaman Pelindung internal (kompresor, motor kipas Pelindung internal (kompresor, motor kipas indoor).
indoor). Pelindung fase terbalik. Sekering. Sekering.
Saklar panas (pipa pembuangan).
Tekanan desain Tinggi/Rendah MPa 3,0/1,6 3,0/1,6
Tahapan kapasitas % 100-0 100-0
Pengendalian refrigeran Pipa kapiler Pipa kapiler
Panjang standar m 5,0 5,0
Perpipaan Panjang maks. m 50 (Panjang setara 70m) 50 (Panjang setara 70m)
refrigeran
Selisih tinggi maks. m 30 30
Model R-22 R-22
Refrigeran
Pengisian kg 2,7 (Diisi untuk 7,5m) 3,3 (Diisi untuk 7,5m)
Oli Model Lihat pelat nama kompresor. Lihat pelat nama kompresor.
refrigeran Pengisian L 1,4 2,5
No. Gambar 4D063278D 4D063277F
Spesifikasi 149
Spesifikasi Si41-901
150 Spesifikasi
Si41-901 Spesifikasi
Spesifikasi 151
Spesifikasi Si41-901
152 Spesifikasi
Si41-901 Spesifikasi
1.2 R-410A
1.2.1 AFVR-N
Tipe floor standing (Tipe direct air blow)
Unit Indoor AFVR05NV1 AFVR06NV1
Model
Unit Outdoor Y1 RUR05NY1S RUR06NY1S
Catu daya 3 fase 50Hz 380V (4 kawat) 3 fase 50Hz 380V (4 kawat)
kW 14,7 17,6
*1. Kapasitas
pendinginan
Bersih Btu/h 50.000 60.000
*2. kcal/h 12.600 15.100
Unit indoor kW 0,5 0,5
Input daya Unit outdoor kW 5,0 5,9
Total kW 5,5 6,4
kW 15,2 18,1
*1. Kapasitas
Kotor Btu/h 51.800 61.800
pendinginan
*3. kcal/h 13.100 15.600
Unit indoor A 2,5 2,5
Arus yang mengalir
Unit outdoor A 8,2 9,6
Unit indoor AFVR05NV1 AFVR06NV1
Warna Putih gading Putih gading
Dimensi H×W×D mm 1.870×750×510 1.870×750×510
Tipe Cross fin coil atau Kumparan sirip silang (Fine Cross fin coil atau Kumparan sirip silang (Fine
Kumparan Baris×Tingkat×Jarak sirip louver fin and Hi-XA tube)
3×32×1,85 louver fin and Hi-XA tube)
3×32×1,85
Luas permukaan m² 0,409 0,409
Tipe Kipas siroko Kipas siroko
Penggerak Penggerak langsung 3 kecepatan Penggerak langsung 3 kecepatan
Output motor kW 0,245 0,245
Kipas
m³/min 42 42
Laju aliran udara
cfm 1.480 1.480
Tekanan statis eksternal mmH 2 O – –
Filter udara Jaring resin Jaring resin
Berat kg 90 90
Cairan mm 9,5 (Brazing/Pematrian) 9,5 (Brazing/Pematrian)
Sambungan Gas mm 19,1 (Brazing/Pematrian) 19,1 (Brazing/Pematrian)
pipa
Pembuangan mm PS 1B ulir dalam PS 1B ulir dalam
Remote control Berkabel – –
(opsi) Nirkabel – –
Unit outdoor Y1 RUR05NY1S RUR06NY1S
Warna Putih gading Putih gading
Dimensi H×W×D mm 1.345×900×320 1.345×900×320
Tipe Cross fin coil atau Kumparan sirip silang (Fine Cross fin coil atau Kumparan sirip silang (Fine
Kumparan Baris×Tingkat×Jarak sirip louver fin1×60×1,4
and Hi-XSL tube) louver fin2×60×2,0
and Hi-XSL tube)
Luas permukaan m² 1,172 1,134
Model Y1 JT170G-P4Y1@S ZP72KCE-TFD
Kompresor Tipe Tipe gulir tersegel kedap udara Tipe gulir tersegel kedap udara
Output motor kW 4,5 4,5
Model P47L11S×2 P47L11S×2
Tipe Baling-baling Baling-baling
Kipas Output motor W 65+90 90+90
m³/min 97 100
Laju aliran udara
cfm 3.430 3.530
Berat kg 92 105
Cairan mm 9,5 (Flare/Penyambung) 9,5 (Flare/Penyambung)
Sambungan Gas mm 19,1 (Flare/Penyambung) 19,1 (Flare/Penyambung)
pipa
Pembuangan mm 26,0 (Hole/Lubang) 26,0 (Hole/Lubang)
Pelindung panas untuk motor kipas outdoor. Saklar Pelindung panas untuk motor kipas outdoor. Saklar
tekanan tinggi. Saklar tekanan rendah. tekanan tinggi. Saklar tekanan rendah.
Perangkat pengaman Pelindung internal (kompresor, motor kipas indoor). Pelindung internal (kompresor, motor kipas indoor).
Pelindung fase terbalik. Sekering. Sekering.
Saklar panas (pipa pembuangan).
Tekanan desain Tinggi/Rendah MPa 4,17/2,5 4,17/2,5
Tahapan kapasitas % 100-0 100-0
Pengendalian refrigeran Pipa kapiler Pipa kapiler
Panjang standar m 5,0 5,0
Perpipaan Panjang maks. m 50 (Panjang setara 70m) 50 (Panjang setara 70m)
refrigeran
Selisih tinggi maks. m 30 30
Model R-410A R-410A
Refrigeran
Pengisian kg 2,5 (Diisi untuk 7,5m) 3,5 (Diisi untuk 7,5m)
Oli Model Lihat pelat nama kompresor. Lihat pelat nama kompresor.
refrigeran Pengisian L 1,4 1,8
No. Gambar 4D063715B 4D063716E
Spesifikasi 153
Spesifikasi Si41-901
154 Spesifikasi
Si41-901 Spesifikasi
1.2.2 AFVPR-N
Tipe floor standing (Tipe duct connection)
Unit Indoor AFVPR10NY1
Model
Unit Outdoor Y1 RUR10NY1S
Catu daya 3 fase 50Hz 380V (4 kawat)
kW 29,3
*1. Kapasitas
pendinginan
Bersih Btu/h 100.000
*2. kcal/h 25.200
Unit indoor kW 1,0
Input daya Unit outdoor kW 10,4
Total kW 11,4
kW 30,3
*1. Kapasitas
Kotor Btu/h 103.400
pendinginan
*3. kcal/h 26.100
Unit indoor A 1,6
Arus yang mengalir
Unit outdoor A 17,6
Unit indoor AFVPR10NY1
Warna Putih gading
Dimensi H×W×D mm 1.740×1.170×510
Tipe Cross fin coil atau Kumparan sirip silang (Fine
Kumparan Baris×Tingkat×Jarak sirip louver fin and Hi-XA tube)
3×32×1,85
Luas permukaan m² 0,707
Tipe Kipas siroko
Penggerak Penggerak sabuk
Output motor kW 1,5
Kipas
m³/min 80
Laju aliran udara
cfm 2.830
Tekanan statis mmH 2 O 15
Filter udara eksternal Jaring resin
Berat kg 150
Cairan mm 12,7 (Brazing/Pematrian)
Sambungan Gas mm 28,6 (Brazing/Pematrian)
pipa
Pembuangan mm PS 1B ulir dalam
Remote control Berkabel –
(opsi) Nirkabel –
Unit outdoor Y1 RUR10NY1S
Warna Putih gading
Dimensi H×W×D mm 1.680×930×765
Tipe Cross fin coil atau Kumparan sirip silang (Fine
Kumparan Baris×Tingkat×Jarak sirip louver fins2×54×2.0
and Hi-XSL tube)
Luas permukaan m² 2,112
Model Y1 ZP137KCE-TFD
Kompresor Tipe Tipe gulir tersegel kedap udara
Output motor kW 9,0
Model P68L11S
Tipe Baling-baling
Kipas Output motor W 500
m³/min 190
Laju aliran udara
cfm 6.710
Berat kg 206
Cairan mm 12,7 (Flare/Penyambung)
Sambungan Gas mm 28,6 (Brazing/Pematrian)
pipa
Pembuangan mm –
Pelindung panas untuk motor kipas outdoor. Saklar
Perangkat pengaman tekanan tinggi. Saklar tekanan rendah.
Pelindung internal (kompresor, motor kipas indoor).
Sekering.
Tekanan desain Tinggi/Rendah MPa 4,17/2,5
Tahapan kapasitas % 100-0
Pengendalian refrigeran Pipa kapiler
Panjang standar m 5,0
Perpipaan Panjang maks. m 50 (Panjang setara 70m)
refrigeran
Selisih tinggi maks. m 30
Model R-410A
Refrigeran
Pengisian kg 6,0 (Diisi untuk 7,5m)
Oli Model Lihat pelat nama kompresor.
refrigeran Pengisian L 3,3
No. Gambar 4D063717B
Spesifikasi 155
Spesifikasi Si41-901
156 Spesifikasi
Si41-901 Spesifikasi
Spesifikasi 157
Spesifikasi Si41-901
1.2.3 AFDR-N
Tipe duct connection high static pressure
Unit Indoor AFDR05NY1 AFDR06NY1
Model
Unit Outdoor Y1 RUR05NY1S RUR06NY1S
Catu daya 3 fase 50Hz 380V (4 kawat) 3 fase 50Hz 380V (4 kawat)
kW 14,7 17,6
*1. Kapasitas
pendinginan
Bersih Btu/h 50.000 60.000
*2. kcal/h 12.600 15.100
Unit indoor kW 0,6 0,6
Input daya Unit outdoor kW 5,0 5,9
Total kW 5,6 6,5
kW 15,3 18,2
*1. Kapasitas
Kotor Btu/h 52.200 62.100
pendinginan
*3. kcal/h 13.200 15.700
Unit indoor A 1,0 1,0
Arus yang mengalir
Unit outdoor A 8,2 9,6
Unit indoor AFDR05NY1 AFDR06NY1
Warna Putih gading Putih gading
Dimensi H×W×D mm 450×900×850 450×1.130×850
Tipe Cross fin coil atau Kumparan sirip silang (Fine Cross fin coil atau Kumparan sirip silang (Fine
Kumparan Baris×Tingkat×Jarak sirip louver fin and Hi-XA tube)
2×24×2,0 louver fin2×24×2,0
and Hi-XA tube)
Luas permukaan m² 0,370 0,491
Tipe Kipas siroko Kipas siroko
Penggerak Penggerak sabuk Penggerak sabuk
Output motor kW 0,75 0,75
Kipas
m³/min 46 54
Laju aliran udara
cfm 1.620 1.910
Tekanan statis eksternal mmH 2 O 9 9
Filter udara – –
Berat kg 72 79
Cairan mm 9,5 (Brazing/Pematrian) 9,5 (Brazing/Pematrian)
Sambungan Gas mm 19,1 (Brazing/Pematrian) 19,1 (Brazing/Pematrian)
pipa
Pembuangan mm PS 3/4B ulir dalam PS 3/4B ulir dalam
Remote control Berkabel BRC1NU64S BRC1NU64S
(opsi) Nirkabel – –
Unit outdoor Y1 RUR05NY1S RUR06NY1S
Warna Putih gading Putih gading
Dimensi H×W×D mm 1.345×900×320 1.345×900×320
Tipe Cross fin coil atau Kumparan sirip silang (Fine Cross fin coil atau Kumparan sirip silang (Fine
Kumparan Baris×Tingkat×Jarak sirip louver fin1×60×1,4
and Hi-XSL tube) louver fin2×60×2,0
and Hi-XSL tube)
Luas permukaan m² 1,172 1,134
Model Y1 JT170G-P4Y1@S ZP72KCE-TFD
Kompresor Tipe Tipe gulir tersegel kedap udara Tipe gulir tersegel kedap udara
Output motor kW 4,5 4,5
Model P47L11S×2 P47L11S×2
Tipe Baling-baling Baling-baling
Kipas Output motor W 65+90 90+90
m³/min 97 100
Laju aliran udara
cfm 3.430 3.530
Berat kg 92 105
Cairan mm 9,5 (Flare) 9,5 (Flare)
Sambungan Gas mm 19,1 (Flare) 19,1 (Flare)
pipa
Pembuangan mm 26,0 (Hole) 26,0 (Hole)
Pelindung panas untuk motor kipas outdoor. Saklar Pelindung panas untuk motor kipas outdoor. Saklar
tekanan tinggi. Saklar tekanan rendah. tekanan tinggi. Saklar tekanan rendah.
Perangkat pengaman Pelindung internal (kompresor, motor kipas Pelindung internal (kompresor, motor kipas indoor).
indoor). Pelindung fase terbalik. Sekering. Sekering.
Saklar panas (pipa pembuangan).
Tekanan desain Tinggi/Rendah MPa 4,17/2,5 4,17/2,5
Tahapan kapasitas % 100-0 100-0
Pengendalian refrigeran Pipa kapiler Pipa kapiler
Panjang standar m 5,0 5,0
Perpipaan Panjang maks. m 50 (Panjang setara 70m) 50 (Panjang setara 70m)
refrigeran
Selisih tinggi maks. m 30 30
Model R-410A R-410A
Refrigeran
Pengisian kg 2,5 (Diisi untuk 7,5m) 3,5 (Diisi untuk 7,5m)
Oli Model Lihat pelat nama kompresor. Lihat pelat nama kompresor.
refrigeran Pengisian L 1,4 1,8
No. Gambar 4D063712B 4D063713E
158 Spesifikasi
Si41-901 Spesifikasi
Spesifikasi 159
Spesifikasi Si41-901
160 Spesifikasi
Si41-901 Spesifikasi
Spesifikasi 161
Si41-901
Bagian 4
Remote Control
(Aksesori Pilihan)
1. Remote Control ...................................................................................... 163
1.1 Aksesori Pilihan untuk AFD-KA, AFDR-N ......................................... 163
1.2 Aksesori Pilihan untuk AFV(R), AFVP(R).......................................... 169
1. Remote Control
1.1 Aksesori Pilihan untuk AFD-KA, AFDR-N
Aksesori pilihan
Nama pilihan Model
AFD05KAY1 AFD06KAY1 AFD08KAY1 AFD10KAY1 AFD13KAY1 AFD15KAY1 AFD18KAY1 AFD20KAY1
AFDR05NY1 AFDR06NY1 AFDR08NY1 AFDR10NY1 AFDR13NY1 AFDR15NY1 AFDR18NY1 AFDR25NY1
Remote control BRC1NU64S
SDR4140048A
3D063005
3PN10254-2
1.1.4
3PN10253-2A
3PN10253-2A
1.1.5
3PN10253-2A
P1
P2
P3
P4
P5
3PN10253-2A
AFV05~10KAV1
AFVR05~10NV1
3PN10376-8B
Bagian 5
Pengkabelan dan
Perpipaan Lapangan
1. Pengkabelan dan Perpipaan Lapangan ............................................... 171
1.1 R-22: AFV05-10KAV1
R-410A: AFVR05-10NV1 .................................................................. 171
1.2 R-22: AFVP10-20KAY1
R-410A: AFVPR10-20NY1 ................................................................ 174
1.3 R-22: AFD05-20KAY1
R-410A: AFDR05-20NY1 .................................................................. 178
2. Unit Outdoor ........................................................................................... 186
2.1 R-22: RU05NY1S / RU06NY1S
R-410A: RUR05NY1S / RUR06NY1S................................................ 186
2.2 R-22: RU08-20NY1S
R-410A: RUR08-20NY1S.................................................................. 195
1.1.2
1.1.3
3PN10373-13B
1.1.4
1.1.5
3PN10373-13B
1.1.6
1.1.7
3PN10373-13B
3PN10376-2B
1.2.2
3PN10373-2B
1.2.3
1.2.4
3PN10373-2B
1.2.5
1.2.6
3PN10373-2B
1.2.7
3PN10373-2B
1.3.2
3PN10373-4B
1.3.3
1.3.4
3PN10373-4B
1.3.5
3PN10373-4B
1.3.6
1.3.7
3PN10373-4B
3PN10373-4B
1.3.8
1.3.9
3PN10373-4B
1.3.10
3PN10373-4B
1.3.11
3PN10373-4B
2. Unit Outdoor
2.1 R-22: RU05NY1S / RU06NY1S
R-410A: RUR05NY1S / RUR06NY1S
2.1.1
1PN09912A
2.1.2
1PN09913A
2.1.3
1PN09913A
1PN09913A
2.1.4
1PN09913A
2.1.5
1PN09913A
2.1.6
1PN09913A
1PN09913A
2.1.7
1PN09913A
2.2.2
1PN10367D
1PN10367D
2.2.3
1PN10367D
1PN10436D
1PN10436D
1PN10436D
2.2.4
1PN10436D
2.2.5
1PN10436D
2.2.6
1PN10436D
1PN10436D
2.2.7
1PN10436D
Bagian 6
Fungsi dan Operasi
1. Garis Besar Fungsi ................................................................................ 207
1.1 Unit Indoor ........................................................................................ 207
1.2 Unit Outdoor ..................................................................................... 208
2. Bagan Alur Operasi................................................................................ 209
2.1 Bagan Alur Operasi (AFD(R)+RU(R)) ................................................ 209
3. Bagian Fungsional Listrik ...................................................................... 211
3.1 Unit Indoor (R-22) ............................................................................. 211
3.2 Unit Indoor (R-410A) ......................................................................... 212
3.3 Unit Outdoor (R-22) .......................................................................... 213
3.4 Unit Outdoor (R-410A) ...................................................................... 213
4. Detail Fungsi .......................................................................................... 214
4.1 Spesifikasi Fungsional AFV(R) • AFVP(R) Unit Indoor ....................... 214
(Fungsi)
Seri AFDV(R)
(Input) (Output)
Unit indoor
(Fungsi)
(Fungsi)
Apakah perangkat
pengaman dalam Unit tidak ber
kondisi normal? TIDAK operasi.
YA
K1R relai unit outdoor ON. K3R
relai unit indoor ON. Maka, K1R
dan K2R ON.
Pertimbanga
n termostat ON Termostat OFF
Termostat ON
K1M Mgs unit outdoor ON, maka
kompresor dan kipas outdoor
beroperasi.
<Kasus 2>
Apakah perangkat
Unit tidak ber
pengaman dalam
operasi.
kondisi normal? TIDAK
YA
K1R relai unit outdoor ON. K3R
relai unit indoor ON. Maka, K1R
dan K2R ON.
Pertimbanga
n termostat ON Termostat OFF
Termostat ON
K1M Mgs unit outdoor ON, maka
kompresor dan kipas outdoor
beroperasi.
3.1.1 AFV05-10KAV1
Item Nama Simbol M odel
AFV05KAV1 AFV06KAV1 AFV08KAV1 AFV10KAV1
Kontroler Remote control berkabel P.C.B SDR4041102
1Fase 220-240V 1Fase 220-240V
Motor M1F 1Fase 220-240V 6P 375W
Motor 4P 550W 4P 375W
kipas Kapasitor penggerak C1R 7,55F 440VAC 185F 440VA C 105F 440VA C
Ruangan R1T NTC 6,8KW@25?
Termistor
Pembekuan R2T NTC 6,8KW@25?
Lainnya Transformator Tr 230V/13V 0,4A
3.1.2 AFVP10-20KAY1
Model
Item Nama Simbol
AFVP10KAV1 AFVP13KAV1 AFVP15KAV1 AFVP18KAV1 AFVP20KAV1
Kontroler Remote control berkabel P.C.B SDR4041103 SDR4041104
MET-T
3Fase MET-T 3Fase 220/380V 4P TFO-K 3Fase 380/415V 4P
Motor M1F
Motor 220/380V 3HP 5HP
kipas 4P
Kelebihan beban --- 2HP
3,6A 5A 8A
Ruangan R1T NTC 6,8KW@25?
Termistor
Pembekuan R2T NTC 6,8KW@25?
Lainnya Transformator Tr 230V/13V 0,4A
3.1.3 AFD05-10KAY1
Item Nama Simbol M odel
AFD05KAY1 AFD06KAY1 AFD08KAY1 AFD10KAY1
Kontroler Remote control berkabel P.C.B BRC1NU64
Motor M1F TFO 3Fase 380/415V 6P 0,75kW IK 3Fase 400V 4P 1,5kW
Motor
Nilai pengaturan relai kelebihan K1M 1,8A 3,6A
kipas
Lainnya Saklarbeban
magnetis K1M CLK-15JT40-P6C(Model baru) CLK-15JT40-P6A(Model lama)
3.1.4 AFD13-20KAY1
Item Nama Simbol M odel
AFD13KAY1 AFD15KAY1 AFD18KAY1 AFD20KAY1
Kontroler Remote control berkabel P.C.B BRC1NU64
Motor M1F TFO 3Fase 380/415V 6P 2,2kW TFO 3Fase 380/415V 4P 3,7kW
Motor
Nilai pengaturan relai kelebihan K1M 5,0A 8,0A
kipas
Lainnya Saklarbeban
magnetis K1M CLK-15JT40-P6C(Model baru) CLK-15JT40-P6A(Model lama)
3.2.1 AFVR05-10NV1
Item Nama Simbol M odel
AFVR05NV1 AFVR06NV1 AFVR08NV1 AFVR10NV1
Kontroler Remote control berkabel P.C.B SDR4041102
1Fase 220-240V 1Fase 220-240V
Motor M1F 1Fase 220-240V 6P 375W
Motor 4P 550W 4P 375W (521)
kipas Kapasitor penggerak C1R 7,55F 440VAC 185F 440VA C 105F 440VA C
Ruangan R1T NTC 6,8KW@25?
Termistor
Pembekuan R2T NTC 6,8KW@25?
Lainnya Transformator Tr 230V/13V 0,4A
3.2.2 AFVPR10-20NV1
Model
Item Nama Simbol
AFVPR10NV1 AFVPR13NV1 AFVPR15NV1 AFVPR18NV1 AFVPR20NV1
Kontroler Remote control berkabel P.C.B SDR4041103 SDR4041104
MET-T
3Fase MET-T 3Fase 220/380V 4P TFO-K 3Fase 380/415V 4P
Motor M1F
Motor 220/380V 3HP 5HP
kipas 4P
Kelebihan beban --- 2HP
3,6A 5A 8A
Ruangan R1T NTC 6,8KW@25?
Termistor
Pembekuan R2T NTC 6,8KW@25?
Lainnya Transformator Tr 230V/13V 0,4A
3.2.3 AFDR05-10NY1
Item Nama Simbol M odel
AFDR05NY1 AFDR06NY1 AFDR08NY1 AFDR10NY1
Kontroler Remote control berkabel P.C.B BRC1NU64
Motor M1F TFO 3Fase 380/415V 6P 0,75kW IK 3Fase 400V 4P 1,5kW
Motor
Nilai pengaturan relai kelebihan K1M 1,8A 3,6A
kipas
Lainnya Saklarbeban
magnetis K1M CLK-15JT40-P6C(Model baru) CLK-15JT40-P6A(Model lama)
3.2.4 AFDR13-20NY1
Item Nama Simbol M odel
AFDR13NY1 AFDR15NY1 AFDR18NY1 AFDR20NY1
Kontroler Remote control berkabel P.C.B BRC1NU64
Motor M1F TFO 3Fase 380/415V 6P 2,2kW TFO 3Fase 380/415V 4P 3,7kW
Motor
Nilai pengaturan relai kelebihan K1M 5,0A 8,0A
kipas
Lainnya Saklarbeban
magnetis K1M CLK-15JT40-P6C(Model baru) CLK-15JT40-P6A(Model lama)
Model
Item Nama Simbol
RUR13NY1S RUR15NY1S RUR18NY1S RUR20NY1S
Kompresor Kompresor gulir M1C ZRT166KCE-TFD ZRT206KCE-TFD ZRT240KCE-TFD ZRT274KCE-TFD
Motor (Atas) M1F 8554MTA-A15S 8554MTA-A16S 8554NTA-A13S 220-240V 400W
Motor (Bawah) M2F 220-240V 6P 250W 220-240V 6P 300W 8554NTA-A13S 220-240V 400W
Motor
kipas Kapasitor penggerak C1R 10,05F 440VAC
Kapasitor penggerak C2R
Perlindung Saklar tekanan tinggi S1PH ACB-1UB32 OFF4,15MPa ON3,2MPa ACB-1UB69W OFF4,47MPa ON3,36MPa
an tekanan Saklar tekanan rendah S1PL LCB-JA135 OFF0,245MPa ON0,353MPa
Sekering F1U 5A 250V
K1M
Lainnya Kontaktor magnetis CLK-35J-P6 AC220-240V
K2M
Relai daya K1R LY2F AC220V (2C)
4. Detail Fungsi
4.1 Spesifikasi Fungsional AFV(R) • AFVP(R) Unit Indoor
4.1.1 Gambar Konfigurasi Sistem
Konfigurasi sistem dasar terdiri dari dua setup sistem seperti di bawah ini.
Motor kipas
Remote control
Termostat penukar panas
Komp. terus berjalan lebih dari 10 Kipas indoor pada kecepatan rendah, Sistem MATI
menit. dan
Perhatian Saat melakukan pemeliharaan dan catu daya harus dimatikan, pastikan untuk terlebih dahulu
MEMATIKAN saklar ON/OFF remote control.
Mematikan saklar catu daya saat saklar ON/OFF masih HIDUP sangat berbahaya karena
“fungsi reset otomatis kegagalan daya” akan menyebabkan kipas indoor langsung mulai
berputar, atau kipas unit outdoor secara otomatis mulai berputar tiga menit setelah catu daya
dihidupkan kembali.
Simbol Deskripsi
T/B Tidak berlaku
S1PL Saklar tekanan rendah
S1PH Saklar tekanan tinggi
Perangkat Q1 Saklar panas pipa pembuangan
pengaman Q1M Saklar panas motor kipas 1
Q2M Saklar panas motor kipas 2
F1C Kelebihan beban motor kipas
OL Output alarm
Tampilan 7 --- Tidak menunjukkan 7 segmen.
segmen
Fr "Fr" menunjukkan 7 segmen.
Bagian 7
Pemecahan Masalah
1. Inspeksi Pemeliharaan .......................................................................... 217
1.1 Peninjauan ....................................................................................... 217
2. Bagaimana Cara Menangani Permintaan Pemeliharaan .................... 219
2.1 Bagan Alur........................................................................................ 219
3. Pemecahan Masalah Menurut Kondisi Peralatan ................................ 220
3.1 Pemecahan Masalah Menurut Kondisi Peralatan ............................... 220
3.2 Peralatan tidak Beroperasi ................................................................ 221
3.3 Kipas Beroperasi, tetapi Kompresor tidak Beroperasi......................... 223
3.4 Operasi Pendinginan Mulai, tetapi Langsung Berhenti ....................... 225
3.5 Setelah Peralatan Dimatikan, Tidak Bisa Langsung Dinyalakan
Kembali............................................................................................. 227
3.6 Peralatan Beroperasi, tetapi tidak Memberikan Pendinginan .............. 228
3.7 Peralatan Mengeluarkan Kabut Putih ................................................ 229
3.8 Peralatan Menghasilkan Kebisingan Keras atau Getar....................... 230
3.9 Peralatan Mengeluarkan Debu .......................................................... 231
1. Inspeksi Pemeliharaan
1.1 Peninjauan
Pedoman Pedoman nilai operasi saat beroperasi dalam kondisi standar dengan menekan tombol uji
untuk Kondisi coba pada remote control adalah sebagaimana dijelaskan dalam tabel di bawah. RU(R)05-
Operasi 20N digunakan sebagai contoh unit outdoor pada tabel.
Optimal
Hubungan antara Hal-hal yang terjadi yang dibandingkan dengan nilai normal dirangkum dalam tabel di
Status bawah ini. (Diukur selama 15 ~ 20 menit atau lebih setelah operasi dimulai)
Pengoperasian
AC dan Tekanan /
Arus yang Saat pendinginan
Mengalir
Status AC Tekanan Tekanan Arus yang
Rendah Tinggi Mengalir
Pengotoran FiIter Udara Lebih rendah Lebih rendah Lebih rendah
Hubung Singkat Udara Saluran Lebih rendah Lebih rendah Lebih rendah
Masuk/Keluar Unit Indoor
Pengotoran Sirip Unit Outdoor Lebih tinggi Lebih tinggi Lebih tinggi
Hubung Singkat Udara Saluran Lebih tinggi Lebih tinggi Lebih tinggi
Masuk/Keluar Unit Outdoor
Udara Tercampur dalam Refrigeran Lebih tinggi Lebih tinggi Lebih tinggi
Air Tercampur dalam Refrigeran 1 Lebih rendah Lebih rendah Lebih rendah
Kotoran Tercampur dalam Refrigeran 2 Lebih rendah Lebih rendah Lebih rendah
Kekurangan Refrigeran (Gas) Lebih rendah Lebih rendah Lebih rendah
Kompresi Tidak Memuaskan 1 Lebih tinggi Lebih rendah Lebih rendah
Catatan: 1. 1. Air di refrigeran membeku di dalam pipa kapiler atau katup ekspansi, dan pada
dasarnya merupakan fenomena yang sama dengan pump down.
2. 2. Kotoran di refrigeran menyumbat filter di bagian dalam perpipaan, dan
pada dasarnya merupakan fenomena yang sama dengan pump down.
Kurva
Kejenuhan
Refrigeran
Berjalan
Normal
(Pemeliharaan wajib)
Kemungkinan Penyebab Sekering terputus atau kontak rusak pada sirkuit operasi
Saklar operasi atau titik kontak pada remote control rusak
Saklar tekanan tinggi atau saklar tekanan rendah rusak
Saklar magnetis motor kipas rusak
Aktivasi atau kesalahan relai arus berlebih motor kipas
Termostat suhu pipa pembuangan rusak (RU(R)05NY1S saja)
Isolasi pada sistem listrik tidak memadai
Titik kontak atau saklar magnetis untuk kompresor rusak
Kompresor rusak
Perlindungan fase terbalik (RU(R)05NY1S saja)
Pemecahan
Masalah Perhatian Pastikan untuk mematikan saklar listrik sebelum menghubungkan atau
memutuskan sambungan, atau kerusakan komponen dapat terjadi.
Apakah
Apakah saklar daya
saklar OFF
daya
atau sekering sirkuit YA
OFF atau sekering Hidupkan saklar daya atau ganti
kontrol terputus?
sirkuit kontrol terputus? sekering.
TIDAK
Apakah
Apakah ada
ada YA
pemadaman listrik?
pemadaman listrik?
Tunggu hingga daya kembali.
TIDAK
YA
Periksa motor kipas.
TIDAK
Apakah ada
kerusakan atau YA
aktuasi perangkat Kerusakan atau aktuasi
pengaman? perangkat pengaman seperti:
· Relai arus berlebih motor kipas indoor
TIDAK
· Saklar termostat pipa pembuangan
· Saklar tekanan tinggi atau
saklar tekanan rendah
Apakah isolasi pada TID · Perlindungan fase terbalik
sistem listrik AK Periksa bagian isolasi atau kabel
memadai? yang rusak.
YA
Kabel listrik atau relai, dll.
Periksa kabel listrik atau relai, dll.
kemungkinan rusak.
Pemecahan Masalah
Apakah ada YA
pemadaman listrik? Tunggu hingga daya kembali.
TIDAK
YA
TIDAK
TIDAK
Apakah ada
kerusakan atau YA
Kerusakan atau aktuasi
aktuasi perangkat
pengaman? perangkat pengaman seperti:
· Termostat perlindungan atau relai
TID arus berlebih motor kipas indoor
AK · Saklar termostat pipa pembuangan
· Saklar tekanan tinggi atau
saklar tekanan rendah
· Perlindungan fase terbalik
Pemecahan Masalah
Perhatian Pastikan untuk mematikan saklar listrik sebelum menghubungkan atau
memutuskan sambungan, atau kerusakan komponen dapat terjadi.
YA
Apakah peralatan YA
beroperasi? Normal.
TIDAK
Pemecahan Masalah
Perhatian Pastikan untuk mematikan saklar listrik sebelum menghubungkan atau
memutuskan sambungan, atau kerusakan komponen dapat terjadi.
Buat pengaturan suhu berikut
dengan menggunakan remote
control.
Pendinginan: Pengaturan terendah
YA
Apakah peralatan YA
beroperasi? Normal.
TIDAK
YA
Pemecahan Masalah
TIDAK
Apakah filter
udara atau YA
Bersihkan filter udara
penukar panas
atau penukar panas indoor.
indoor kotor?
TIDAK
Apakah penukar
panas kotor? YA
Pembersihan
penukar panas.
TIDAK
Kemungkinan penyebab
sebagai berikut:
* Pengisian refrigeran · Setelah pengeringan
berlebihan
* Pencampuran udara vakum, isikan
dalam sistem refrigeran refrigeran dalam
* Saklar tekanan rusak jumlah yang benar.
* Kekurangan refrigeran Periksa saklar
LPS berhenti beroperasi tekanan tinggi.
· Perbaiki kebocoran
refrigeran.
Setelah pengeringan
vakum, isikan
refrigeran dalam
jumlah yang benar.
Periksa saklar
tekanan rendah.
Pemecahan Masalah
TIDAK
Apakah filter
udara atau penukar YA
panas Bersihkan filter udara atau
indoor kotor? penukar panas indoor.
TIDAK
Apakah ada
item yang YA
Hilangkan item yang
mengganggu
mengganggu.
aliran udara?
TIDAK
Apakah penukar
panas kotor? YA Cleaning of the heat
exchanger.
TIDAK
Kemungkinan penyebab
sebagai berikut:
* Pengisian refrigeran · Setelah pengeringan
berlebihan vakum, isikan
* Pencampuran udara refrigeran dalam
dalam sistem refrigeran jumlah yang benar.
* Saklar tekanan rusak Periksa saklar
* Kekurangan refrigeran tekanan tinggi.
LPS berhenti beroperasi
· Perbaiki kebocoran
refrigeran.
Setelah pengeringan
vakum, isikan
refrigeran dalam
jumlah yang benar.
Periksa saklar
tekanan rendah.
Pemecahan Masalah
Perhatian Pastikan untuk mematikan saklar listrik sebelum menghubungkan atau
memutuskan sambungan, atau kerusakan komponen dapat terjadi.
Putar saklar operasi pada
posisi ON dan OFF, lalu
tunggu pada sisi ON.
Apakah ada
perbedaan
suhu antara TIDA
saluran Pipa kapiler tersumbat.
masuk dan
saluran keluar
pipa kapiler?
YA
Kompresor Periksa kompresor.
rusak
Pemecahan Masalah
Perhatian Pastikan untuk mematikan saklar listrik sebelum menghubungkan atau
memutuskan sambungan, atau kerusakan komponen dapat terjadi.
Ukur suhu udara hisap dan
udara pembuangan.
Selisih suhu = Suhu
udara hisap – Suhu
udara pembuangan.
TIDAK
TID
Kemungkinan penyebab sebagai berikut
AK
* Pemilihan model yang tidak tepat Pemasangan unit tambahan
* Pengaruh sinar matahari langsung harus dipertimbangkan.
Apakah ada embun
beku yang timbul di Apakah arus
sekitar port saluran YA pengoperasian lebih YA
masuk penukar kecil dari tingkat
panas unit indoor yang ditentukan?
atau port saluran
keluar pipa kapiler? TIDAK
TIDAK
Kekurangan gas mungkin
menimbulkan masalah.
Setelah pengeringan vakum, isi dengan
refrigeran dalam jumlah yang benar.
Apakah laju aliran * Filter udara tersumbat
YA Periksa setiap bagian.
pembuangan unit * Penukar panas kotor
indoor turun? * Motor kipas rusak
TIDAK
Kemungkinan penyebab sebagai
berikut
Apakah tingkat tekanan
* Pengisian refrigeran berlebihan
tinggi lebih tinggi dari YA Periksa setiap bagian.
* Penukar panas kotor
tingkat normal?
* Arus pendek udara pembuangan
* Item yang mengganggu dalam aliran
udara
TID
AK * Motor kipas unit outdoor rusak
Kemungkinan penyebab sebagai berikut
* Kompresi dari kompresor tidak
memadai Periksa setiap bagian.
* Sirkulasi refrigeran tidak
memadai
* Katup ekspansi rusak
Pemecahan Masalah
Perhatian Pastikan untuk mematikan saklar listrik sebelum menghubungkan atau
memutuskan sambungan, atau kerusakan komponen dapat terjadi.
YA
TID
AK
TID
AK
Pemecahan Masalah
Apakah kebisingan
menimbulkan YA Sisipkan peredam getaran ke dalam
getaran pada bagian
bagian pemasangan, atau perkuat
pemasangan unit?
bagian pemasangan.
Kebisingan kecil
TIDAK “shoo...” yang terus- YA Normal. Suara tersebut adalah
menerus selama kebisingan aliran gas (refrigeran) di
operasi pendinginan bagian dalam unit AC.
Apakah TIDAK TIDAK
Sisipkan bahan bantalan ke
perpipaan telah diamankan?
penopang pipa seperti pelana.
YA TIDAK
Apakah pipa Perbaiki perpipaan secara manual
bersentuhan dengan atau pasang bobot mati pada pipa.
selubung?
TIDAK
Apakah kebisingan
suara aliran YA Normal.
berasal dari katup
penurun tekanan * Pengisian refrigeran
atau pipa kapiler? berlebihan
* Udara masuk ke dalam
sistem refrigeran Setelah pengeringan vakum,
* Kebisingan aliran akibat isi dengan refrigeran dalam
TIDAK kekurangan refrigeran. jumlah yang benar.
(Berbunyi shoo...)
Pemecahan Masalah
Apakah masalah
timbul pada saat
operasi dimulai lagi YA
Debu yang terkumpul di bagian
setelah perpanjangan dalam unit indoor tertiup keluar.
masa operasi?
Diperlukan pembersihan bagian
dalam unit indoor.
TIDAK
Apakah dilengkapi YA
Debu yang terkumpul di bagian
dengan filter udara?
dalam unit indoor tertiup keluar.
Diperlukan pembersihan bagian
TIDAK dalam unit indoor.
Bagian 8
Lampiran
1. Diagram Perpipaan ................................................................................ 233
1.1 R-22 ................................................................................................. 233
1.2 R-410A ............................................................................................. 236
2. Diagram Pengkabelan ........................................................................... 239
2.1 Unit Indoor (R-22) ............................................................................. 239
2.2 Unit Outdoor (R-22) .......................................................................... 242
2.3 Unit Indoor (R-410A) ......................................................................... 245
2.4 Unit Outdoor (R-410A) ...................................................................... 248
3. Pengkabelan Lapangan ......................................................................... 251
3.1 R-22 ................................................................................................. 251
3.2 R-410A ............................................................................................. 257
232 Lampiran
Si41-901 Diagram Perpipaan
1. Diagram Perpipaan
1.1 R-22
AFV05KAV1 / AFD05KAY1 + RU05NY1S
AFV06KAV1 / AFD06KAY1 + RU06NY1S
C : 3D062796B
C : 3D062797B
Lampiran 233
Diagram Perpipaan Si41-901
C : 3D062798B
C : 3D062799A
234 Lampiran
Si41-901 Diagram Perpipaan
C : 3D062800A
C : 3D062801A
Lampiran 235
Diagram Perpipaan Si41-901
1.2 R-410A
AFVR05NV1 / AFDR05NY1 + RUR05NY1S
AFVR06NV1 / AFDR06NY1 + RUR06NY1S
C : 3D063700
C : 3D063701
236 Lampiran
Si41-901 Diagram Perpipaan
C : 3D063702
C : 3D063703
Lampiran 237
Diagram Perpipaan Si41-901
C : 3D063705
238 Lampiran
Si41-901 Diagram Pengkabelan
2. Diagram Pengkabelan
2.1 Indoor Unit (R-22)
2.1.1 AFV-KA
AFV05KAV1 / AFV06KAV1 / AFV08KAV1
SDR3010209-2C
AFV10KAV1
SDR3010211-2D
Lampiran 239
Diagram Pengkabelan Si41-901
2.1.2 AFVP-KA
AFVP10KAY1
SDR3010213-2D
SDR3010206-2F
240 Lampiran
Si41-901 Diagram Pengkabelan
2.1.3 AFD-KA
AFD05KAY1 / AFD06KAY1 / AFD08KAY1 / AFD10KAY1
SDR3010207D
SDR3010208D
Lampiran 241
Diagram Pengkabelan Si41-901
3D062569B
RU06NY1S
3D062570A
242 Lampiran
Si41-901 Diagram Pengkabelan
RU08NY1S
3D062958B
RU10NY1S
3D062959A
Lampiran 243
Diagram Pengkabelan Si41-901
3D063145B
244 Lampiran
Si41-901 Diagram Pengkabelan
SDR3010210-2A
AFVR10NV1
SDR3010212-2B
Lampiran 245
Diagram Pengkabelan Si41-901
2.3.2 AFVPR-N
AFVPR10NY1
SDR3010213-2D
SDR3010206-2F
246 Lampiran
Si41-901 Diagram Pengkabelan
2.3.3 AFDR-N
AFDR05NY1 / AFDR06NY1 / AFDR08NY1 / AFDR10NY1
SDR3010207D
SDR3010208D
Lampiran 247
Diagram Pengkabelan Si41-901
3D062569B
RUR06NY1S
3D062570A
248 Lampiran
Si41-901 Diagram Pengkabelan
RUR08NY1S
3D063728A
RUR10NY1S
3D062959A
Lampiran 249
Diagram Pengkabelan Si41-901
3D063145B
250 Lampiran
Si41-901 Pengkabelan Lapangan
3. Pengkabelan Lapangan
3.1 R-22
3.1.1 AFV-KA
AFV05KAV1 + RU05NY1S
AFV06KAV1 + RU06NY1S
4D063522C
Lampiran 251
Pengkabelan Lapangan Si41-901
AFV08KAV1 + RU08NY1S
AFV10KAV1 + RU10NY1S
4D063512B
252 Lampiran
Si41-901 Pengkabelan Lapangan
3.1.2 AFVP-KA
AFVP10KAY1 + RU10NY1S
4D063513A
Lampiran 253
Pengkabelan Lapangan Si41-901
AFVP13KAY1 + RU13NY1S
AFVP15KAY1 + RU15NY1S
AFVP18KAY1 + RU18NY1S
AFVP20KAY1 + RU20NY1S
4D063514A
254 Lampiran
Si41-901 Pengkabelan Lapangan
3.1.3 AFD-KA
AFD05KAY1 + RU05NY1S
AFD06KAY1 + RU06NY1S
AFD08KAY1 + RU08NY1S
AFD10KAY1 + RU10NY1S
4D063515B
Lampiran 255
Pengkabelan Lapangan Si41-901
AFD13KAY1 + RU13NY1S
AFD15KAY1 + RU15NY1S
AFD18KAY1 + RU18NY1S
AFD20KAY1 + RU20NY1S
4D063516A
256 Lampiran
Si41-901 Pengkabelan Lapangan
3.2 R-410A
3.2.1 AFVR-N
AFVR05NV1 + RUR05NY1S
AFVR06NV1 + RUR06NY1S
4D063724
Lampiran 257
Pengkabelan Lapangan Si41-901
AFVR08NV1 + RUR08NY1S
AFVR10NV1 + RUR10NY1S
4D063729
258 Lampiran
Si41-901 Pengkabelan Lapangan
3.2.2 AFVPR-N
AFVPR10NY1 + RUR10NY1S
4D063513A
Lampiran 259
Pengkabelan Lapangan Si41-901
AFVPR13NY1 + RUR13NY1S
AFVPR15NY1 + RUR15NY1S
AFVPR18NY1 + RUR18NY1S
AFVPR20NY1 + RUR20NY1S
4D063514A
260 Lampiran
Si41-901 Pengkabelan Lapangan
3.2.3 AFDR-N
AFDR05NY1 + RUR05NY1S
AFDR06NY1 + RUR06NY1S
AFDR08NY1 + RUR08NY1S
AFDR10NY1 + RUR10NY1S
4D063515B
Lampiran 261
Pengkabelan Lapangan Si41-901
AFDR13NY1 + RUR13NY1S
AFDR15NY1 + RUR15NY1S
AFDR18NY1 + RUR18NY1S
AFDR20NY1 + RUR20NY1S
4D063516A
262 Lampiran
Peringatan Produk Daikin Industries, Ltd. diproduksi untuk diekspor ke berbagai negara di seluruh dunia. Daikin
Industries, Ltd. tidak memiliki kendali penuh atas produk yang diekspor ke dan digunakan di negara
tertentu. Oleh karena itu, sebelum membeli, konfirmasikan dengan importir, distributor dan/atau
pengecer resmi lokal Anda apakah produk ini sesuai dengan standar yang berlaku, dan cocok untuk
digunakan, di daerah tempat produk akan digunakan. Pernyataan ini tidak dimaksudkan untuk
mengecualikan, membatasi, atau memodifikasi penerapan dari setiap peraturan setempat.
Mintalah pemasang atau kontraktor yang memenuhi syarat untuk memasang produk ini. Jangan
mencoba memasang produk ini sendiri. Pemasangan yang tidak tepat dapat mengakibatkan
kebocoran air atau refrigeran, sengatan listrik, kebakaran, atau ledakan.
Hanya gunakan komponen dan aksesori yang disediakan atau ditentukan oleh Daikin.
Mintalah pemasang atau kontraktor yang memenuhi syarat untuk memasang komponen dan
aksesori. Penggunaan komponen dan aksesori yang tidak resmi atau pemasangan komponen
dan aksesori yang tidak tepat dapat mengakibatkan kebocoran air atau refrigeran, sengatan
listrik, kebakaran, atau ledakan.
Baca panduan pengguna secara saksama sebelum menggunakan produk ini. Panduan pengguna
memberikan peringatan dan petunjuk keselamatan yang penting. Pastikan mengikuti petunjuk dan
peringatan ini.
Jika Anda memiliki pertanyaan, silakan hubungi importir, distributor, dan/atau pengecer lokal Anda.
Organisasi:
DAIKI N I N D UST RIES, LT D. Organisasi:
DIVISI P R O D UKSI PE N G O N DISI U DA R A (AC) DAIKI N I N D UST RIES
(THAI LA N D) LT D. Semua fasilitas bisnis dan anak
Lingkup Pendaftaran: perusahaan Daikin Group di
PER A N CA NG A N/PE N GE MBA NG A N, D AN P RO D UK SI Lingkup Pendaftaran: Jepang disertifikasi di bawah
PER AL ATA N PE N G O N DISI, PE MA N AS, PE N DI NGI N, PERANCANGAN/PENGEMBANGAN standar internasional ISO
RE F RIGE R ASI U D A RA K O ME RSI AL, PE RA LA TA N DAN PRODUKSI AC DAN 14001 untuk pengelolaan
PE MA NA S KO ME RSIA L, PE RA LA TA N PE N GO N DISI KOMPONEN-KOMPONENNYA lingkungan.
U DA RA (A C) H U NIA N, VE N TIL ASI PE MBA R UA N PA NA S, TERMASUK KOMPRESOR YANG
JMI-0107 PER AL ATA N PE MBE RSI H U DA RA, U NIT RE F RIG E RASI JQA-1452 DIGUNAKAN UNTUK AC.
WA DA H TIPE KE LA UT A N, KO MP RES O R DA N KA T UP.
Dealer
Kantor Pusat:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Jepang
Kantor Tokyo:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Jepang
http://www.daikin.com/global_ac/
Spesifkasi, desain, dan isi lain yang ada dalam brosur ini berlaku sejak Mei 2009, namun dapat berubah tanpa pemberitahuan.
Si41-901
Dicetak di Jepang 05/2009 AK