Relai Arus Lebih
Relai Arus Lebih
APLIKASI
PENGAMAN UTAMA
JTM ( DISTRIBUSI )
GENERATOR ( Kapasitas kecil )
TRAFO DAYA ( Kapasitas kecil )
MOTOR MOTOR BESAR
• NON DIRECTIONAL
• DIRECTIONAL
• KONTROL TEGANGAN
• PENAHAN TEGANGAN
KARAKTERISTIK
@ ARAH
1. TIDAK BERARAH ( NON DIRECTIONAL )
2. BERARAH ( DIRECTIONAL )
@ ARUS – WAKTU
1. TANPA TUNDA ( MOMENT = INSTANT )
2. TUNDA WAKTU ( TIME DELAY )
# DEFINITE ( TERTENTU ) = INDEPENDEN
# INVERSE ( I – t BERBANDING TERBALIK )
= DEPENDEN
SI / NI = Standard / Normal Iverse
VI = Very Inverse
EI = Exteremely Inverse
LTI = Long Time Invers
KARAKTERISTIK INSTANT = MOMENT
t SET
I
ISET Moment
KARAKTERISTIK TUNDA WAKTU
TERTENTU ( DEFINITE TIME )
t SET
I SET I
KARAKTERISTIK TUNDA WAKTU
INVERSE
INVERSE
t SET
ISET I
KARAKTERISTIK KOMBINASI INSTANT
DENGAN TUNDA WAKTU TERTENTU
(DEFINITE TIME )
t SET
t SET Moment
ISET I
ISET Moment
KARAKTERISTIK KOMBINASI INSTANT
DENGAN TUNDA WAKTU INVERSE
t
t SET
t SET Moment
ISET I
ISET Moment
TIPE PLUNGER
KONTAK
PLUNGER
PEGAS
Fp 0.6
BELITAN
0.8
Fe 1.0
1.2
INTI LUAR
SETTING
Fe = GAYA ELEKTROMEKANIK Faktor Pabrik
Fp = GAYA PEGAS
Φ L U ΦL
U
2 2
KUMPARAN LAGGING
PIRINGAN
Is
KUMPARAN UTAMA
TAP SETTING
KONTAK DIAM
DENGAN MENGATUR
JARAK KONTAK
TIPE RELAI STATIK
SUPLAI DC
A CT RECTIFIER
LEVEL
R Vin DETECTOR
Vo
SETTING RELAI
VREF BANTU
CURVE
SHAPER
FILTER
CS R F
Ia F Is
MAX
I RL
Ib GATE LD T LD
& 1 2
1
Ic RECT.
Is
INSTANT RL
LD
3
LD = LEVEL DETECTOR 3
T = TIMER
R = REGULATOR
SETTING
INSTANT
IBA DOC
HS OUTPUT
STATIC OVER CURRENT RELAY RELAY
MCGG OUTPUT
DRIVER TIME / CURRENT
OUTPUT RELAY
HS TIME
0.4/0
FULLWAVE
INTERPOSSING MICRO 0.2/0
RECTIFIER
COMPUTER
CT 0.2/0
0.1/0
0.05/0
INPUT
0.05/0.025
TMS SWITH SETTING
A/D
16/0
8//0
0.2/0.1 0.4/0 0.8/0 4//0
0.2/0 0.4/0 2/0
1/0
CURRENT SETTING
HIGH SET SWITH
SETTING
IBA DOC
RELAI
OCR / GFR
A B C E
INST INST TIPE
MCGG 82
t t NAME
I > Is I > Is PLATE
IS IN IS IN RESET
xt xt KARAK
TERISTIK
I INST I INST
Is Is
IBA DOC
PRINSIP SETTING OCR
* Is = k In In = Arus Nominal
k = Faktor pabrik ( 1 s/d 2 )
atau 0,05 s/d 2,4 dengan
step 0.05
* Plug Setting
* Numeric
IBA DOC
# Waktu kerja (t> / to> )
Mps = 4 x Is x Is
IBA DOC
# Is instant /moment ( I>> / Io>> )
* Is instant = k In atau
k Is
In = Arus Nominal
Is = Arus setting tunda waktu
k = Faktor pabrik
* Plug setting
* Numeric
IBA DOC
@ SETTING ARUS OCR /GFR DENGAN TUNDA WAKTU
IS I N
0.1 0.05
0.1 0
0.2 0
IS ARUS SETTING 0.4 0
0.4 0
IN ARUS NOMINAL RELAI 0.4 0
FAKTOR PABRIK
0.8 0
IBA DOC
# MISAL ARUS SETTING Is = 6 A.
Is = 1.2 In
POSISI SAKLAR :
0.1 0.05
0.1 0
0.2 0 Is = ( 0.1 + 0.1 + 0.2 + 0 + 0 + 0 + 0.8 ) x 5A
0.4 0 = 1,2 x 5A
0.4 0 = 6A
0.4 0
0.8 0
IBA DOC
PEMILIHAN KARAKTERISTIK
SI VI EI LTI D2 D4 D8
0 1 0 1 0 1 0
0 0 1 1 0 0 1
0 0 0 0 1 1 1
0 1 0 1
0 1 0 1
0 1 0 1
IBA DOC
KURVA / KARAKTERISTIK
13,5
t tms
I 1
@ EXTREMELY INVERSE ( EI )
80
t 2 tms
I 1
@ LONG TIME INVERSE ( LTI )
120
t tms
I 1
IBA DOC
SETTING WAKTU
MISAL : KARAKTERISTIK EI
ARUS GANGGUAN 3 x Is ( I = 3 )
WAKTU KERJA = 1 DETIK
PEMILIHAN TMS :
I2 1 32 1
tms tk 1 0,1
80 80
IBA DOC
SETTING INSTANT
IS 6A
0 1
18 0 2
6
3 0 4
0 8
ISinst IS 0 16
0
IBA DOC
20KV
X
DATA SETTING
P1
300/5A 50 / 51 I> = 5A; Io> = 1A ; I>> = 35A
10P15 51N t>=0,5 detik ;to>=0,5 detik
30VA P2 Karakteristik tunda waktu = SI
In relai = 5A
Io>> tdk aktip
F
Ihs3f=3300A
Ihs2f=2000A
Ihs!f= 210A
MCGG 82
INDICATOR
TMS INST CURVE RESET
49 SETTING SETTING SELECTION
50 TIME DELAY
<<
21 << TRIP 13
μC INST TRIP POWER +
IA Is Vx
22
PhA SUPPLY
CIRCUIT
14
-
<<
INPUT CURRENT
CIRCUIT SETTING RL 1-1
Ph 35
Ph
33
R L1
34 PHASE FAULT
TMS INST CURVE 2
RL 1-2 29 TIME DELAYED
47 SETTING SETTING SELECTION TRIP OUTPUT
48 TIME DELAY CONTACT
<< TRIP 30
23 << OUTPUT
μC INST TRIP
IB Is
CIRCUIT RL 2-1 36
PhB Ph
24 37
PHASE FAULT
<<
INPUT CURRENT
38 INSTATANEOUS
CIRCUIT SETTING
RL 2-2 41 TRIP OUTPUT
Ph Ph RL2 CONTACT
2
42
TMS INST CURVE
45 SETTING SETTING SELECTION
RL 3-1 7
46 TIME DELAY
<< RL3 6 EARTH FAULT
TRIP
25 <<
μC INST TRIP
2 5 TIME DELAYED
IC Is RL 3-2 2 TRIP OUTPUT
PhC
26 CONTACT
<<
INPUT CURRENT 1
CIRCUIT SETTING OUTPUT
Ph Ph CIRCUIT RL 4-1
E/F 8
TMS INST CURVE 10
43 EARTH FAULT
SETTING SETTING SELECTION 9
INSTATANEOUS
44 RL4 RL 4-2 16 TRIP OUTPUT
TIME DELAY
<< 2 CONTACT
27 << TRIP
IN μC 15
INST TRIP
Is E/F
28
<<
INPUT CURRENT
CIRCUIT SETTING
E/F E/F
SAMBUNGAN ( WIRING )
OCR
PMT
OCR GFR
R
P1 S E
T
S1
CT OCR
S2
P2
3 Buah OCR
1 Buah GFR
IBA DOC
SAMBUNGAN ( WIRING )
PMT OCR
GFR
R
P1 E
T
S1
CT OCR
S2
P2
2 Buah OCR
1 Buah GFR
IBA DOC
PENGUJIAN RELAI ARUS LEBIH
1. PENGUJIAN INDIVIDUAL
2. PENGUJIAN FUNGSI
1. CARA SETTING
2. INTERNAL DIAGRAM RELAI
3. ALAT UJI / RANGKAIAN PENGUJIAN
4. ITEM PENGUJIAN
5. PROSEDUR PENGUJIAN
6. HASIL UJI DAN KESIMPULAN
JENIS / ITEM PENGUJIN
3. KARAKTERISTIK INSTANTANEOUS
1. ARUS PICK UP [ ARUS AWAL / MULA ]
I pick up
I reset
I beban
t
t gangguan
PENGUJIAN INDIVIDUAL
RELAI ARUS LEBIH
21
TIMER 22
23 29
24 30
START STOP
25
26
R
220 Vac 27
28
13
Vdc
A
14
220 Vac
RANGKAIAN PENGUJIAN
1 2 T1 T2 P1 P2 C2 C1 C0 CT SEC VOLTMETER 220 V
A SELECTOR
V A A
OVR
75 V OCR UVR OTHER
150V 10 A UCR RELAY
300V B 5A A
B
OFF 1A
B SELECTOR MIN MAX MIN MAX TEST CONDITION
V A A 15
16
OVR
75 V OCR UVR OTHER
150V
300V B
10 A UCR RELAY MCGG 82
5A B A
OFF 1A
B SELECTOR MIN MAX MIN MAX TEST CONDITION
OCR / GFR
YANG DIUJI
HAND TERMINAL
RELAI OCR / GFR
MCGG 82
ALAT UJI
XS92a ABB +
21 13
Vx
22 14 -
23 29
24 t>
30
25 41
26 42
t >>
27 1
28 to>
2
15
to >>
16
KONTAK
OCR/GFR
DIAGRAM
KONTROL DC
(+)
RELAI
BANTU
RE 1
(-)
TRIP PMT
(+)
RE 2
RELAI ALARM
BANTU
RE 3
(-)
RANGKAIAN SIGNALISASI
(+)
KONTAK
RELAI
RESET
TEST LAMP
RELAI BANTU
RE
LAMPU
SIGNAL
P2
V SYMBOL LEGEN
20KV/V3
Q2 100V/V3 F1 Over Current & Earth Fault Relay
125VA,CL 1,0 S6 F2 Grounding Phase Detecting Relay
HL1-3 T5 x5
T F3 Auto Recloser Relay
fu1-3 5 PL1-3 Ammeter double scale 0 – 200/400/1A
0,3A P2 KV meter 20KV / 100V
F1 F2 P31-2 MWHmeter In - Out
S6 Selector Switch Volt 4 Position
X3-X4 Current Test Blick
MCGG52 MCGG22
50 / 51 50G/51G X5 Potential Test Block
50G/51G HL1-3 Neon Voltage Indicator
200 – 400/
1A,30VA,10P20
T1-3 TO METERING
x4 REMOTE
x3 MWH MWH CONTROL
T1-3
IN OUT A PANEL
200 – 400/
1A,15VA,0,5 PL1-3
F3 P3-1 P3-2
MVTR51
79
x
Q1
630A
34 35 9 8
33 10
I >>
13 14
42 41
38 36
+T
37 13
110VDC
14 -T
Io >
1 2
5 7
POWER CIRCUIT PROTECTION
6
Io >> FEEDER SCHEMATIC
15 16
9 8
10
+C
+T
LOCAL REMOTE
M 2 4 4
2
S8 1 3 1 3 38 8 34 5 8 5
CB
F1 F1 F1 F1 F2 F2
CLOSE 0 OPEN 4 4 6 36 9 35 7 9 7
S1
7/4
S3 3 S1 2 3 5
K4
15/8 7/4
1
OPEN
CLOSE
FROM RCP FROM TRIPPING
K3 PANEL BUCHOLZ ORDER
FACILITY
15/6
X 2 4 6 CIRCUIT BREAKER
YL CONTROL FEEDER
1 3 SCHEMATIC
M 5
Q1 YB KN
OPEN
N CLOSE
-T
-C
SETTING OCR
GANGGUAN FASA – FASA [ TUNDA WAKTU
k S I max
ISEI min .....[1]
kD
ISET max 0,8I HS2Φ min....[2]
ISET min ISET max ISET ISET min
ISET max ISET min ISET ISET max
k S 1,1 1,2
k D 80%
I max arus - beban - max.
KOORDINASI OCR
# DEFINITE TIME
I SC I SB I SA I HS
t C t B t A
Δt 0,4 0,5det
A B C
t
1,3 det
0,8 det
0,3 det
I
KOORDINASI OCR
# INVERSE TIME
A B C
TMS B TMS C
TMS A
I
SETTING ELEMEN INSTANTANEOUS
SETTING INSTANT
# INSTANTANEOUS
A B C
A B C
t tA
tB
t INST tC
t INST
t I
TMS B TMS C
TMS A
t INST t INST
I
SETTING GFR
[RELAI GANGGUAN TANAH ]
PERLU DIPERHATIKAN ;
# PADA SUTM
3VO 0,3VNom
2. RELAI GANGGUAN TANAH BERARAH
[ DIRECTONAL GFR ]
A SELECTOR
V A A
OVR
75 V OCR UVR OTHER
150V 10 A UCR RELAY
300V B 5A A
B
OFF 1A
B SELECTOR MIN MAX MIN MAX TEST CONDITION
V A A 15
16
OVR
75 V OCR UVR OTHER
150V
300V B
10 A UCR RELAY MCGG 82
5A B A
OFF 1A
B SELECTOR MIN MAX MIN MAX TEST CONDITION
OCR / GFR
YANG DIUJI
HAND TERMINAL
RELAI OCR / GFR
MCGG 82
ALAT UJI
XS92a ABB +
21 13
Vx
22 14 -
23 29
24 t>
30
25 41
26 42
t >>
27 1
28 to>
2
15
to >>
16
FR = 50 U = 57 V
DFR= 0 I =...A
DF = 0 PHI= 90
FC = SESUAI JENIS GANGGUAN
SQ = PU / DROP DU = 0
A = SQ = 2 DI = 0,01
IRA = 0 A =0 DPH=0
TO = 100 AUTO LUH = 220
TL = 100 SQ = 1F0 LUL = 0
TF = > t set A =1 LIH = 20A
IN1 = 1 LIL = 0
IN2 = 0 LPI =359
OU1= 0/1 LPO = 0
OU2= 0 UJI PU / DROP OFF
TI = 2 START + / -
TT = 0 Sambungan ke kontak dilepas
MOD= UI
MT = 1 Uji waktu kerja [ sambungan
OP = 0 ke kontak dipakai]
START +
0 2X ENTER
FC = CODE GANGGUAN
111 = R KE E
112 = S KE E
113 = T KE E
121 = GANGGUAN R S
122 = GANGGUAN ST
123 = GANGGUAN TR
L1 L2 L3 Io IRF
1
SPAJ 140 C 2
6
7
KETERANGAN GAMBAR :
Rx Tx
63 1 2 3 4 5 6 7 8 9 25 26 27 11 10 62 61 70 71 72 74 75 77 78 80 81 68 69 65 66
1A
5A
5A
1A
1A
1A
5A
5A
F
E D C B A
U2
TS1 SS1 SS2 SS3 TS2
1 1 1 1 1
SGB6 TRIP
U3
SGB7
U1/SGR3/2
U1/SGR2/8
U1/SGR3/4
U1/SGR3/1
U1/SGR2/2
U1/SGR2/4
U1/SGR2/6
U1/SGR2/1
U1/SGR3/3
U1/SGR2/7
U1/SGR3/5
U1/SGR3/6
U1/SGR2/3
U1/SGR2/5
U1/SGR3/7
U1/SGR3/8
U1/SGR1/1
U1/SGR1/3
U1/SGR1/5
U1/SGR1/7
U1/SGR1/8
U1/SGR1/2
U1/SGR1/4
U1/SGR1/6
UI
3I>
U1/SGB1 T1
T2
U1/SGB2 3I> T3
T4
U1/SGB3 Io> T5
T6
U1/SGB4 Io>> T7
T8
U1/SGB5
U1/SGB8
AC Setting U1/SGF4
Reset T9
0,1…1s
>
SGB/6
SGR3/4
SGR2/3
I >> t>> SGR2/4
1
>
SGR1/4
START 2
SS1 D
SGB2
SGF1/4 AR3
BS 1
0,1..1S
SIGNAL 1
SS2 C
SGF2/8
SGR3/5 AR2
SGR1/5 SIGNAL 2
SGR3/6 SS3 B
SGR2/5
Io > AR1
to> ko SGR2/6
>
SGR1/6
Io
SGR3/7 RESET
SGB3
SGR1/7 PROGRAM
>
SGB/7
TRIP
SGR3/8 1 TS2 A
Io >> SGR2/7
to>> 1
> SGR2/8
SGR1/8
RESET
>
TRIP
SGB4
SGB5
REMOTE SETTING
SGB6
RELAY RESET
REDUCED BLOCK DIAGRAM SPCJ 4D 29 SPTU R1
STEP
I>/In
RESET
n x 1s 0 0 0 0 t> [s]
k
I>>/In
t>> [s]
k
# kemudian tekan push botton PROGRAM kira Io>/In
to> [s]
kira 5 detik sampai display menunjuk seperti ko
gambar dibawah ini. Io>>/In
to>> [s]
ko
PROGRAM SGF
5s 0 0 0 0 SGR
TRIP
SGB
# kemudian tekan tombol push botton PROGRAM I>/In
t> [s]
kira kira 1 detik sampai display menunjuk seperti k RESET
gambar dibawah ini I>>/In STEP
t>> [s]
( lampu indikator t>, t>>, to>, to>> menyala ) k
Io>/In
to> [s]
PROGRAM ko
Io>>/In
1s 0 0 0 0 to>> [s]
ko
SGF
PROGRAM
SGR
TRIP
SGB
# kemudian tekan tombol push botton STEP/RESET
dan PROGRAM secara bersamaan ,maka lampu
indikator TRIP akan menyala dan display
I>/In
menunujuk seperti dibawah ini ( berarti oke ) t> [s]
k RESET
I>>/In STEP
RESET t>> [s]
STEP k
Io>/In
to> [s]
ko
Io>>/In
0 0 0 0 to>> [s]
ko
PROGRAM SGF
1s PROGRAM
SGR
TRIP
SGB
3. Dengan kondisi display seperti dibawah, kemudian tekan
tombol push botton RESET / STEP maka lampu indikator
IRF akan menyala .
IRF
RESET I>/In
STEP
1s 0 0 0 0 t> [s]
k RESET
I>>/In STEP
t>> [s]
k
Io>/In
to> [s]
ko
Io>>/In
to>> [s]
ko
SGF
PROGRAM
SGR
TRIP
SGB
PROGRAM SWITCH GROUP SGF, SGB, SGR
3.1. SGR1 Saklar ini digunakan untuk memilih tingkatan proteksi yang dibawa
ke output signal starting SS1 dan output signal tripping TS2 .
SGR1 ini terbagi atas :
SGR1/1 untuk signal starting tingkat I> disambung ke SS1 ( terminal relai
nomer 77 – 78 ).
SGR1/2 untuk signal tripping tingkat I> disambung ke TS2 ( terminal relai
nomer 65 – 66 ).
SGR1/3 untuk signal atarting tingkat I>> disambung ke SS1 ( terminal
77 – 78 ).
SGR1/4 untuk signal tripping tingkat I>> disambung ke TS2 ( terminal
65 – 66 ).
SGR1/5 untuk signal starting tingkat Io> disambung ke SS1 ( terminal
77 – 78 ).
SGR1/6 untuk signal tripping tingkat Io> disambung ke TS2 ( terminal
65 – 66 ).
SGR1/7 untuk signal starting tingkat Io>> disambung ke SS1 ( terminal
77 – 78 ).
SGR 1/8 untuk signal tripping tingkat Io>> disambung ke TS2 ( terminal
65 – 66 ).
3.2. SGR2 Saklar ini dipakai untuk konfigurasi signal tripping tingkat
proteksi yang berbeda . Mempunyai dua output SS2 dan SS3
yang mana signal dapat disambung.
SGR2 ini terbagi atas :
SGR2/1 untuk signal starting tingkat I> disambung ke SS2
( terminal relai no 80 – 81 )
SGR2/2 untuk signal tripping tingkat I> disambung ke SS3
( terminal relai no 68 – 69 )
SGR2/3 untuk signal starting tingkat I>> disambung ke SS2
( idem SGR2/1 )
SGR2/4 untuk signal tripping tingkat I>> disambung ke SS3
( idem SGR 2/2 )
SGR2/5 untuk signal starting tingkat Io> disambung ke SS2
( idem SGR 2/1 )
SGR 2/6 untuk signal tripping tingkat Io> disambung ke SS3
( idem SGR 2/2 )
SGR2/7 untuk signal starting tingkat Io>>disambung ke SS2
( idem SGR 2/1 )
SGR2/8 untuk signal tripping tingkat Io>> disambung ke SS3
( idem SGR 2/2 )
3.3. SGR 3. Saklar ini dipakai untuk konfigurasi signal starting dan tripping
untuk output starting atau auxiliary tripping TS1
Catatan : Jika proteksi CBF (Circuit Breaker Failure ) dipilih
pada SGF 1/4 ,ini juga menggunakan output TS1.
SGR3 terbagi atas {
SGR3/1 untuk signal starting tingkat I> disambung ke TS1
( terminal relai nomer 74 – 75 )
SGR3/2 untuk signal starting tingkat I> disambung ke TS1
( idem SGR3/1 )
SGR3/3 untuk signal starting tingkat I>> disambung ke TS1
( idem SGR3/1 )
SGR3/4 untuk signal starting tingkat I>> disambung ke TS1
( idem SGR 3/1 )
SGR3/5 untuk signal starting tingkat Io> disambung ke TS1
( idem SGR3/1 )
SGR3/6 untuk signal starting tingkat Io> disambung ke TS1
( idem SGR3/1 )
SGR3/7 untuk signal starting tingkat Io>> disambung ke TS1
( idem SGR3/1 )
SGR3/8 untuk signal starting tingkat Io>> disambung ke TS1
( idem SGR 3/1 ).
CARA SETTING ( PEMROGRAMAN )
CARANYA :
a) Tekan push botton STEP-RESET sampai lampu Led Indikator SGF menyala
dan display menunjuk seperti dibawah ini :
RESET
STEP
nx1s 0 0 0
b) Kemudian tekan push botton PROGRAM kira kira 1 detik sehingga display
menunjuk seperti dibawah ini ;
PROGRAM
1s 1 0 0 0
c) Kemudian tekan push botton PROGRAM kira kira 5 detik sehingga
display menunjuk seperti gambar dibawah
PROGRAM
5s 1 0 0 0
SGF 1 / 1 = 0
PROGRAM
1x 1 1 0
SGF 1 / 2 = 0
PROGRAM
1s 1 2 0
f) Kemudian tekan push botton PROGRAM kira kira 1 detik,sehingga
display menunjuk seperti dibawah ini
SGF 1 / 3 = 0
PROGRAM
1s 1 3 0
STEP
RESET
1 4 0 1X 1 4 1