Evaporator Lost
\bigtriangleup t=Selisih suhu air panas dari mesin dengan suhu air basin
\[ W= \frac{ Flowrate}{1000} \]
Blow down
\[ B= \frac{E}{(n-1)}-W \\ \\ \]
Makeup water
\[ M = E+W+B \\ \\ \]
Chemical lost
\[ Lost = W+B \\ \]
Contoh Perhitungan :
Kami menganjurkan dosis anti kerak formax 050 200ppm, anti lumut formax 051 200ppm
Diketahui : Cooling tower flowrate : 530 m^3/jam
Jawaban :
rubah menjadi per liter / hari ===> Sesuaikan dengan working hours pada contoh ini working
hours=24jam
1 m3 = 1000 liter
1 hari = 24 jam
n circle =4
= 530 m^3/jam
= 530.000x(24)
\[ E= 63.600 \\ \]
\[ W= \frac{ Flowrate}{1000} \\ \]
\[ W= \frac{ 12.720.000}{1000} \\ \]
\[ W= 12.720 \\ \]
\[ B= \frac{E}{n-1}-W \\ \\ \]
\[ B= \frac{63.600}{3} -12.720 \\ \\ \]
\[ B=21.200-12.720 \\ \\ \]
\[ B=8.480\\ \\ \]
= 12.720+8.480 liter
= 21.260 liter
= 200 ppm
= 4252 ml
Untuk dosis Anti Lumut formax 051 sama percis sepert yang diatas,akan tetapi nanti representatif akan
menilai ulang berdasarkan keadaan fisik cooling tower. Sebelum treatment sebaiknya dan harus cooling
tower telah di bersihkan total dengan cara cleaning dan flusing pipa-pipa untuk hasil yang maksimal.
Analisa kualitas air cooling tower dan laporan rutin yang dilaksanakan setiap bulan.
Pemberian pelatihan mengenai penanganan analisa air dan pendeteksian kualitas air secara garis besar.
Hitungan Representatif
Flowrate m³ /jam
530
12.720.000
12.720
8.480
21.200
4,24