Anda di halaman 1dari 8

P&ID ODORIZER PACKAGE

Document No. PEMBANGUNAN TANGKI LPG Rev. 0


PRESSURIZED WAYAME Page
WYM-CIE-M-PID-001-A3 KAPASITAS 2X1000 MT 1 of 8

Review Summary:
1. See and revise as per comments on page 8
2. Next Submission Shall be IFA Rev.1

PEMILIK : PT. PERTAMINA (PERSERO)


KONTRAKTOR : PT. WIJAYA KARYA (PERSERO) TBK
VENDOR : PT CAKRA INNO ENGINEERING
NAMA PROYEK : PEMBANGUNAN TANGKI LPG PRESSURIZED
WAYAME KAPASITAS 2 x 1000 MT
LOKASI : AMBON, MALUKU
NO. KONTRAK : TP.01.03/U.DEP.IP.WYM/05466/V/2020
EQUIPMENT : ODORIZER INJECTION PACKAGE (D-11)

04/03
PJW, HN, PA, AW
2021

SK HN
0 01/03/21 ISSUED FOR APPROVAL BD PJW PMP
DKA
HN
C 25/08/20 RE-ISSUED FOR REVIEW SK BD PJW PMP
DKA
HN
B 29/07/20 RE-ISSUED FOR REVIEW SK BD PJW PMP
DKA
HN
A 01/07/20 ISSUED FOR REVIEW SK BD PJW PMP
DKA

PREP’D APPR’D CHK’D REV’D APPR”D


REV DATE DESCRIPTION
PT CAKRA INNO
PT WIJAYA KARYA (PERSERO) TBK
ENGINEERING
P&ID ODORIZER PACKAGE

DOCUMENT NO. Rev. 0


PEMBANGUNAN TANGKI LPG PRESSURIZED
WYM-CIE-M-PID-001-A4 WAYAME KAPASITAS 2X1000 MT Page 2 of 8

REVISION HISTORY

Amender
Date Revision Amendment
Name
01/07/20 A SK First Submission
Comment:
1. Untuk P&ID Package Vendor wajib
mengikuti legend dan symbol P&ID sesuai
standard Project (Dokumen kami
lampirkan.
2. Untuk LT-001 di SBC Tank disini fungsinya
sebagai Level indicator transmitter saja atau
juga sebagi proteksi overflow (interlock
dengan logic)? untuk proteksi overflow
harap ditambahkan gambar interlock.
3. Mohon diperjelas line yang ditunjukan pada
review no 3 ini terputus atau terkoneksi
kemana?
4. Untuk Display Discharge Pressure pompa di
HMI/Display, ditarik dari PT nomor berapa di
P&ID?
5. Ditambahkan semua keterangan untuk tiap
symbol dan legend yang ditampilkan di
P&ID, seperti ditunjukan pada review no 5.
6. Mohon ditambahkan OP Temp, Discharge
Pressure, Serta Head Pompa.
7. Ditambahkan TP Number untuk koneksi dari
package odorizer ke injection Probe
8. Gambarkan semua interlock yang ada di
system odorizer pada P&ID
9. Ditambahkan informasi destination untuk
semua output connection dari odorizer
package.
10. Untuk koneksi menuju DCS menggunakan
Modbus TCP/IP sesuai dengan klarifikasi
saat tender.
11. Tag number equipment/system diseragamkan
antara keterangan di tabel dan di gambar di
P&ID
12. Template kepala gambar menggunakan
standard project Wayame
13. Next Submission Shall be IFR Rev.B
P&ID ODORIZER PACKAGE

DOCUMENT NO. Rev. 0


PEMBANGUNAN TANGKI LPG PRESSURIZED
WYM-CIE-M-PID-001-A4 WAYAME KAPASITAS 2X1000 MT Page 3 of 8

29/07/20 B SK Second Submission


Response:
1. Noted and Incorporated
2. For indicator only HVO Controller, no
protection for overfloq or empty.
3. Noted and Incorporated
4. For discharge pressure we don’t have
pressure indicator or pressure transmitter,
since we are using back pressure
regulaotor which contanly maintain the
pressure at 200 psig.
5. Noted and Incorporated
6. Noted and Incorporated
7. Noted and Incorporated
8. All interlock system should be looked at our
wiring diagram since there’s a lot of interlock
signal, communication, and power supply.

9. Noted and Incorporated


10. For communication channel we are using
modbus protocol RS-485
11. Noted and Incorporated
12. Noted and Incorporated
13. Noted and Incorporated
Comment:
1. Add sign Mark above initial name of originator
and approval person in revision table below on
page 1 (this han been commented on last
revision review)
2. Add Tag numbr on Equipment name page 1
((this han been commented on last revision
review)
3. Change line symbol for Nv-2 Line and Gas Flow
Signal
4. Interlock is a part of P&ID and shall be drawing
in P&ID to show connection/interlock between
instrument to/from control panel. (see Attached
P&ID ODORIZER PACKAGE

DOCUMENT NO. Rev. 0


PEMBANGUNAN TANGKI LPG PRESSURIZED
WYM-CIE-M-PID-001-A4 WAYAME KAPASITAS 2X1000 MT Page 4 of 8

Project P&ID for Vendor Reference)

5. Communication Output Use MODBUS TCP/IP,


See Attachment MOM on Bildding Clarification.

25/08/20 C SK Third Submission


Responses:
1. Noted and Incorporated
2. Noted and Incorporated
3. Noted and Incorporated
4. Noted and Incorporated
5. OK, Communication output Use MODBUS
Ethernet TCP/IP, with Converter RS-485 to
Ethernet TCP/IP.

10/10/20 Comments:
1. Add Tag number on Equipment name page 1
((this han been commented on last revision
review)
2. MAWP Value in this document is not valid for
Inspection and Testing (hydrotest)
3. Set Pressure PSV Odorant Tank?

4. Delete, Not Signal to N300 Controller & DCS


5. Change Orientation TP-06 Gas LPG
Metering.
6. Set Press. (PR-002)?
7. Check MAWP with Calculation

18/11/20 0 SK Fourth Submission


1. Noted and Incorporated
2. Noted and Incorporated
3. Set Press. 10.55 kg/cm2
4. Noted and Incorporated
5. Noted and Incorporated
6. Set Press. 3.5Kg/cm3
7. Noted and Incorporated
P&ID ODORIZER PACKAGE

DOCUMENT NO. Rev. 0


PEMBANGUNAN TANGKI LPG PRESSURIZED
WYM-CIE-M-PID-001-A4 WAYAME KAPASITAS 2X1000 MT Page 5 of 8

01/03/21 0 (Replace) SK Fifth Submission (Replace)


Add Abbreviation Instrumentation Symbol Control
Panel
P&ID ODORIZER PACKAGE

DOCUMENT NO. Rev. 0


PEMBANGUNAN TANGKI LPG PRESSURIZED
WYM-CIE-M-PID-001-A4 WAYAME KAPASITAS 2X1000 MT Page 6 of 8

Table of Content

1. COVER ........................................................................................................................ 1
2. REVISION HISTORY ................................................................................................... 2
3. TABLE OF CONTENT ................................................................................................. 3
4. P&ID ODORIZER PACKAGE ...................................................................................... 4
NOTE

4 0 ISSUED FOR APPROVAL 01/03/21

3 C RE-ISSUED FOR REVIEW 25/08/20

2 B RE-ISSUED FOR REVIEW 29/07/20

1 A ISSUED FOR REVIEW 01/07/20 -

NO. REV DESCRIPTION DATE REMARKS

PROJECT :

PEMBANGUNAN TANGKI LPG PRESSURIZED


WAYAME KAPASITAS 2X1000 MT

OWNER :

PT.PERTAMINA

CONTRACTOR :

PT.WIJAYA KARYA (Persero) Tbk.

VENDOR :

CAKRA INNO PT WIKA


DRAWN CHECKED APPROVED CHECKED APPROVED
SIGNATURE

NAME ZN Bd Dd PJW/DKA PMP


TITLE DRF/ENG LED/MENG PM ENG/MENG PM
DATE 24/02/21 24/02/21 01/03/21

TITLE :

PIPING AND INSTRUMENTATION DIAGRAM


ODORIZER INJECTION PACKAGE

DRAWING NUMBER SHEET REV. SCALE

WYM-CIE-M-PID-001-A3 1 OF 2 0 NTS

A3
NOTE

4 0 ISSUED FOR APPROVAL 01/03/21

3 C RE-ISSUED FOR REVIEW 25/08/20

2 B RE-ISSUED FOR REVIEW 29/07/20

1 A ISSUED FOR REVIEW 01/07/20 -

NO. REV DESCRIPTION DATE REMARKS

PROJECT :

)ORZ5DWH6LJQDOXVH
PEMBANGUNAN TANGKI LPG PRESSURIZED
+DUGZLUH HOHWULFDOOLQH
WAYAME KAPASITAS 2X1000 MT
&KDQJHWKLVOLQHIURP
FRPPXQLFDWLRQVLJQDOOLQHWR
HOHFWULFDOOLQH  OWNER :

PT.PERTAMINA

CONTRACTOR :

PT.WIJAYA KARYA (Persero) Tbk.

VENDOR :

CAKRA INNO PT WIKA


DRAWN CHECKED APPROVED CHECKED APPROVED
SIGNATURE

NAME ZN Bd Dd PJW/DKA PMP


TITLE DRF/ENG LED/MENG PM ENG/MENG PM
DATE 24/02/21 24/02/21 01/03/21

TITLE :

PIPING AND INSTRUMENTATION DIAGRAM


ODORIZER INJECTION PACKAGE

DRAWING NUMBER SHEET REV. SCALE

WYM-CIE-M-PID-001-A3 2 OF 2 0 NTS

A3