Anda di halaman 1dari 113

KABEL BAWAH TANAH

JENIS-JENIS KABEL
• PVC, PVC/PVC
• PVC/SWA/PVC (PVC Armoured)
• PILC (Paper Insulated Lead Covered)
• PILCDSTAS (Paper Insulated Lead Covered Double Steel Tape
and Serving)
• XLPE (Cross Link Polyethelene)
• XLPE Insulated PVC sheated
• Screen Cable
• Submerine Cable
• Oil Filled Cable
PELBAGAI JENIS KABEL
IKM KK U.G CABLE 4
KABEL
XLPE
SCREENED
AND
ARMOURED
BINAAN KABEL
• Pengalir (conductor) – Aluminium/Tembaga
• Penebat (insulator) – Kertas, PVC, XLPE
• Teras (core) – himpunan helaian
• Perisai (armour) – perlindungan mekanikal
• Salut (sheath) – kemasan luaran
• Pengisi (filler) – mengisi ruang kosong
• Screen (thin copper foil) – stress uniformity
• Pengalas (bedding) – alas antara bahagian keras dgn
bahagian lembut
• Outer sheath/Serving (PVC, jute)
KABEL
PVC/PVC
SATU TERAS
TANPA
PERISAI

IKM KK U.G CABLE 7


CONTROL
CABLE -
ARMOURED

IKM KK U.G CABLE 8


KABEL
BERISI
MINYAK
33kV

IKM KK U.G CABLE 9


KABEL
XLPE 11kV
BERPERISAI

IKM KK U.G CABLE 10


KABEL
PVC/SWA/PVC
600/1000V
ARMOURED

IKM KK U.G CABLE 11


KABEL XLPE

KABEL
PVC/SWA/PVC
IKM KK U.G CABLE 17
IKM KK U.G CABLE 18
KABEL
PVC/SWA/PVC

KABEL XLPE
KABEL
PILCDSTAS
(PAPER
CABLE)
ELECTRICAL CHARACTERISTIC

• Rintangan (ohm/km)
• Regangan (ohm/km)
• Regangan kapacitor (microfarad/km)
• Galangan (vektor sum semua diatas)
IKM KK U.G CABLE 22
IKM KK U.G CABLE 23
SUSUT VOLTAN
Susut voltan dalam milivolt bagi setiap ampiar setiap meter
(mV/A/m) boleh diperolehi dari jadual didalam buku IEE ke
16 atau dari pembuat kabel yang mana ianya bergantung kepada
bahan penebat, bilangan teras, cara pemasangan dan suhu
ambient
CHARGING CURRENT
• Kabel bawah tanah yang panjang adalah merupakan sebuah
induktor dan juga sebuah kapasitor
• Apabila bekalan AC dikenakan kepada kabel tersebut akan
terdapat charging current yang agak tinggi yang perlu diambil
kira sekiranya bekalan adalah dari generator disel atau mini
hidro, boleh menyebabkan generator berkerja pada leading
power factor
CHARGING CURRENT
Kabel 11KV Charging Current/
(mm sq.) conductor/meter at normal
voltage & frequency (mA)
16 0.48
25 0.56
35 0.62
70 0.78
120 0.90
185 1.16
BAHAN PENEBAT

• PVC
• Impregnated paper (PILC)
• Cross link polyethelene (XLPE)
• Mineral insulation oil (Oil Filled Cable)
• Mineral substance (MICC)
SUHU MAKSIMA PENEBAT
Bahan Normal (°C) Litar Pintas (°C)
XLPE 90 250
Polyethelene 75 120
Butyl rubber 80-85 230
Impreg Paper 6.6kV 80 200
Impreg Paper 15kV 75 200
Impreg Paper 22kV 70 200
Impreg Paper 33kV 65 200
Oil Filled Paper 85 150
KELEBIHAN XLPE
• Mudah dibentuk apabila panas
• Lebih ringan
• Tidak menyerap air
• Kehilangan daya dielektrik rendah
• Harganya lebih murah
• Tidak mudah bertukar bentuk oleh geseran dsb.
• Tidak mudah cair jika terkena pelarut
• Suhu operasinya tinggi
• Kekuatan fizikal dan mekanikalnya tinggi
• Sehingga 69kV
KELEMAHAN XLPE
• Bentuknya bulat, tidak sectorial, oleh itu saiz kabel menjadi lebih
besar
• Keras berbanding dengan paper dan PVC, oleh itu susah untuk
dibengkokkan
STRUKTUR PENGALIR
• Lembar – helaian paling kecil, lebih banyak lembar lebih lembutlah
sesuatu kabel itu
• Teras – himpunan beberapa bilangan lembar
• Satu teras – voltan rendah & tinggi
• Dua teras – kabel lampu jalan/kawasan
• Tiga teras – kabel voltan tinggi
• Empat teras – kabel voltan rendah
• Berbilang teras – kabel kawalan
BILANGAN LEMBAR

IKM KK U.G CABLE 32


SHAPE OF CONDUCTOR

IKM KK U.G CABLE 33


KABEL SATU TERAS
• Digunakan untuk penyambungan antara alatubah ke Papan Suis
Utama dimana jaraknya pendek
• Juga untuk penyambungan didalam bangunan
• Pihak TNB menggunakan kabel voltan tinggi satu teras bertujuan
untuk mengurangkan saiz kabel dan mudah mengesan dan
memperbaiki kerosakan
PENGGUNAAN KABEL PVC/PVC

No KVA Jenis Kabel

1 300kVA (417A) 1 x 300mm/fasa Aluminium

2 300 - 500kVA (695A) 2 x 300mm/fasa Aluminium

3 500 - 750kVA (1043A) 2 x 500mm/fasa Aluminium

4 750 -1000kVA (1391A) 2 x 500mm/fasa Tembaga

5 1000 -1125kVA (1565A) 2 x 630mm/fasa Tembaga


PENGENALAN TERAS

• 1 – Fasa Merah
• 2 – Fasa Kuning
• 3 – Fasa Biru
• 4 – Neutral
• Atau menggunakan warna sahaja tanpa angka (kabel
PVC/SWA/PVC)
• MERAH untuk fasa HITAM untuk neutral bagi kabel dua
teras lampu kawasan
KEUPAYAAN MEMBAWA ARUS

• Bahan (Tembaga atau Aluminium)


• Luas keratan rentas
• Jenis penebat
• Bilangan teras
• Berperisai atau tidak
• Udara bebas atau dalam trunking
• Suhu ambient
• Penebat haba
VOLTAN KABEL

• 500V
• 1000V/600V
• 11,000V
• 33,000V
• 66,000V
KABEL MASUK UTAMA

• PVC/SWA/PVC (Armoured cable)


• PILC / PILCDSTAS (Paper cable)
• XLPE (Cross link polyethylene)

• MICC (Mineral Insulated Copper


Cable) – untuk fire risk area
SAIZ KABEL/ARUS
mm persegi Arus (ampere)
16 105
25 135
35 165
50 195
70 240
95 290
120 335
150 375
185 425
240 490
300 550
400 620
500 760
630 850
LALUAN KABEL

• Laluan biasa – tepi jalan, tanah lapang


• Melintasi jalanraya
• Melintasi landasan keretapi
• Melintasi parit
• Melintasi sungai
• G.I pipe dan earthenware, corrugated pipe
MENANAM KABEL
• Trench
• Pasir, batu bata, penanda kabel
• Bending radius
• Sediakan drum kabel
• Jack drum kabel
• Pasang roller supaya senang ditarik
• Stokin kabel
• Penanda kabel (cable marker)
CABLE LAID DIRECT IN GROUND
• Bottom of the trench covered with 75mm sand
• Lay cable, no overlapping, no crossing each other
• Cover on top of cable with 75mm sand
• Cable protective cover/indicator shall be clay brick/concrete
slab/PVC sheath or other approved materials, arranged lengthwise
from end to end
• For cable more than 120mm sq. use more than one row of bricks.
One row for each cable
• Provide 25mm overhang on each side of the cable
• Oranged coloured 6mm diameter multi-strand nylon rope laid along
the cable route
CABLE RUN ON WALL
• Use hot dipped galvanised sheet steel cable trays
• Cable trays shall be suspended from floor slabs by hangers or
mounted on wall by brackets at 600 mm interval
• Where cable trays pass through floors or fire resistant walls, the
surrounding hole shall be sealed to full thickness of the floor or
wall with non-hygroscopic fire-resisting materials of minimum 2
hour fire rating material
CABLE TRAY
• Hot dipped galvanised sheet finished with orange enamel colour
• Minimum thickness is 1.5mm
• Width up to 300mm
• 2.5mm thickness for greater than 300mm width
• Supported at least 25mm from the trench and 600mm interval
• Bracket shall be anti-rust treated and painted with one coat of
primer
• All joint shall be bridge with tinned copper tape not less than
25mm x 3mm
CABLE SADDLES
• Use saddle to tie cable to the trays
• Saddles for cables on cable trays shall be fixed by bolts, washers and
nuts
CABLE TRENCH
• Dalam 750mm (2.5 kaki)
• Lebar 450mm (1.5 kaki)
• Lapisan pasir 75 mm di dasar trench
• Batu bata atau penanda kabel atau plastic sheet
• Lapisan pasir diatas kabel
• Trench didalam bilik suis hendaklah diisi pasir keparas sehingga
menutup dan melepasi cable duct
IKM KK U.G CABLE 48
IKM KK U.G CABLE 49
IKM KK U.G CABLE 50
IKM KK U.G CABLE 51
IKM KK U.G CABLE 52
IKM KK U.G CABLE 53
IKM KK U.G CABLE 54
CABLE
DUCT

IKM KK U.G CABLE 55


IKM KK U.G CABLE 56
IKM KK U.G CABLE 57
IKM KK U.G CABLE 58
REKOD KABEL

• Laluan kabel
• Penanda kabel
• Jenis kabel
• Saiz kabel
• Panjang kabel
• Tempat sambungan kabel
MENGENALPASTI KABEL

• Minimum Method
• Maximum Method
• Cable Route Tracer
• Pemakuan Kabel
JENIS-JENIS SAMBUNGAN

• Sambungan terus
• Sambungan tee
• Sambungan breecher
• Married joint
SEBAB-SEBAB SAMBUNGAN

• Satu drum tak cukup panjang


• Pecahan bekalan kepada pengguna
• Membaiki kerosakan kabel
• Pencantuman kabel kepada perkakas suis
KAEDAH SAMBUNGAN

• Berisi kompaun (bitumin, exposy resin)


• Sambungan hangat kecut
TEMPAT DILARANG SAMBUNG
• Tempat tidak rata seperti cerun bukit kecuali disokong
secukupnya
• Di selekoh yang agak tajam
• Di dalam G.I duct
• Dibawah tarmac atau kawasan permukaan konkrit
• Ditempat terdedah kepada gegaran yang akan memberi kesan
kepada penyambungan
PENYAMBUNG MEKANIKAL /
WELDING
• Penyambung mekanikal (cable link atau ferrule) biasanya
digunakan untuk kabel bervoltan 600/1000V dan sehingga
11,000V
• Welding joint pula digunakan dimana electrical dan mechanical
properties adalah sangat diperlukan berada pada tahap yang
paling baik tanpa pertambahan garispusat kabel, lazimnya untuk
transmission cable

IKM KK U.G CABLE 65


JENIS TAMATAN
• Cable gland
• Cable box
• Hangat kecut (heat shringkable)
• Tier box
• Kepala gajah/cendawan
CABLE
LUG

IKM KK U.G CABLE 67


PENAMATAN
KABEL
HANGAT
KECUT
MEMANASKAN
HEAT
SHRINGKABLE
SLEEVE
PENAMATAN
KABEL
DIDALAM
PAPAN
SUIS
KABEL
HENDAKLAH
DIIKAT
DENGAN
KUKUH
KEPADA
PAPAN SUIS
PEMBUMIAN
CABLE
SLEEVE

IKM KK U.G CABLE 74


PEMBUMIAN
LEAD
SLEEVE

IKM KK U.G CABLE 75


SAMBUNGAN
KEPADA
TALIAN
AERIAL
DAN
SAMBUNGAN
PEMBUMIAN

IKM KK U.G CABLE 76


DILINDUNGI
DENGAN
G.I PIPE

IKM KK U.G CABLE 77


IKM KK U.G CABLE 78
IKM KK U.G CABLE 79
SAMBUNGAN
KE TALIAN
KAKI LIMA

IKM KK U.G CABLE 80


PENAMATAN
KEPADA
ALATUBAH

IKM KK U.G CABLE 81


IKM KK U.G CABLE 82
KABEL
VOLTAN
RENDAH

IKM KK U.G CABLE 83


KABEL
VOLTAN
TINGGI
DAN
RENDAH

IKM KK U.G CABLE 84


TEMPAT DITAMATKAN

• Feeder pillar
• Papan suis
• Tier box
• Perkakas suis
• Punca alatubah
• Cable box
• Atas tiang talian aerial
BENDING RADIUS
• Bending radius amat penting untuk diberi penekanan yang serius
kerana jika kabel dibengkokkan dengan berlebihan ini akan
merosakan kabel, samada penebatnya rosak atau pengalir itu
sendiri yang rosak
• Jejari bengkokan bergantung diantaranya kepada saiz kabel,
bilangan dan saiz lembar, jenis kabel, berperisai atau tidak, jenis
bahan penebat, dsb.

IKM KK U.G CABLE 86


MIN. BENDING RADIUS
1 XLPE single core unarmoured 20D (overall diameter)
XLPE single core armoured 20D

2 XLPE three core unarmoured 15D


XLPE three core armoured 12D

3 PILC cable up to 2” overall 12D


diameter

4 PILC cable more than 2” overall 20D


diameter
IKM KK U.G CABLE 87
JENIS-JENIS KEROSAKAN

• Litar pintas (shunt fault)


• Litar buka (series fault)
• Rosak/Bocor ke Bumi
• Rintangan tinggi
PUNCA KEROSAKAN KABEL
• Kerosakan mekanikal (kerja pengorekan tanah)
• Kecuaian semasa merentang kabel
• Kemasukan lembapan atau air atau cecair
• Tanah runtuh atau tanah mendap
• Kegagalan di Penyambungan
• Usia kabel terlalu lama
• Perpindahan sebatian
• Di makan anai-anai
• Tegangan berlebihan
MENGESAN KEROSAKAN
• Dapatkan surat kebenaran kerja
• Asingkan bekalan, discharge, bumikan, kunci
• Gantung tanda AWAS & BAHAYA
• Analisa jenis kerosakan
• Pin–pointing kerosakan
• Buat ujian pengesahan
LANGKAH KESELAMATAN
• OFF semua bekalan dari pencawang berhampiran
• Gantung papan tanda AWAS ORANG SEDANG
BERKERJA
• Pastikan punca bekalan telah diasingkan
• Sahkan kabel telah dimatikan
• Discharge kabel
• Bumikan kabel
UJIAN-UJIAN KABEL
• Penebatan
• Tekanan – kabel voltan tinggi
• Keselanjaran
• Ujian fasa – untuk multicore cable sahaja
• Turutan fasa (phase sequence)
• Pembumian perisai
• Kelembapan (moisture content)
• Bending test
• Partial discharge – rongga halus
KABEL SEDANG DI UJI DI KILANG
SPESIFIKASI KABEL
• Jenis bahan pengalir (tembaga / Aluminium)
• Jenis penebat
• Jenis perlindungan mekanikal
• Luas keratan rentas
• Bilangan teras
• Kadaran voltan
• Kod warna
PEMAKUAN KABEL
• Untuk mengenalpasti kabel
• Menggunakan cable spike, rod bumi, tukul
• Untuk memastikan kabel yang hendak dibaiki itu telah tiada
bekalan
• Jika kabel masih mempunyai bekalan akan berlaku letupan dan
alat perlindungan (pemutus litar atau fius) akan bertindak
memutuskan bekalan
IKM KK U.G CABLE 96
PENYOKONG KABEL
• Kabel hendaklah disokong sewajarnya supaya berat kabel tidak
akan menyebabkan ianya melemahkan dan merosakan
sambungan atau tamatan kabel terutama untuk kabel yang
dipasang menegak bagi bangunan tinggi
• Hendaklah diikat supaya tidak beralih dari kedudukan asalnya
• Dilindungi dari kesan geggaran atau hentakan yang boleh
mengagalkan pada bahagian sambungan
CABLE MARKER
• Berbentuk Trapezoidal
• 100mm square bahagian atas (top face)
• 150mm square bahagian bawah (bottom face)
• 400mm tinggi
• 300mm ditanam dalam tanah
• Anak panah menunjukkan arah kabel
• Cable Joint Marker dengan binaan yang sama dengan
perkataan dan tanda
CABLE MARKER

IKM KK U.G CABLE 99


CABLE MARKER

IKM KK U.G CABLE


10
0
CABLE MARKER

IKM KK U.G CABLE


10
1
KABEL TIDAK DIGUNAKAN LAGI

IKM KK U.G CABLE


10
2
IKM KK U.G CABLE
10
3
IKM KK U.G CABLE
10
4
IKM KK U.G CABLE
10
5
CABLE END MUST BE PROTECTED
FROM INGRESS OF MOISTURE

IKM KK U.G CABLE


10
6
CABLE IN G.I
PIPE –
CROSSING THE
ROAD

IKM KK U.G CABLE


10
7
CLOSED UP

IKM KK U.G CABLE


10
8
IKM KK U.G CABLE
10
9
IKM KK U.G CABLE
11
0
IKM KK U.G CABLE
11
1
GALVANISED
IRON PIPE –
CABLE
CROSSING
DRAIN

IKM KK U.G CABLE


11
2
IKM KK U.G CABLE
11
3